120KW GENERATOR
120 KW / 150 KVA DIESEL GENERATOR SET, FULLY PACKAGED:
JOHN DEERE Heavy duty diesel engine, 4 stroke, 1800rpm, Turbo
LEROY SOMER brushless alternator. IP23 protection, Insulation class H
MERLIN GERIN, Main line circuit breaker, wired, maximum output rated
Digital auto-start control panel. CE and UL compliant
Incorporated metallic fuel tank for day use
Auto Start control feature included for interoperation with ATS/AMF
12V charging alternator and 12V DC electric starter motor
12V charged DC starting battery with electrolyte and cables
Dry type air filter, fuel filter and oil filter elements installed
Mechanically welded chassis with vibration isolators
Each unit prototype and individually factory load bank tested
The generator accepts 100% rated load in one step as per NFPA110
and meets ISO8528-5 class G-3 for transient response
Compliant with ISO3046, ISO8528, BS4999, BS5514, BS5000PT99,
AS1359, IEC34, UTE5100, VDE0530 and ISO9001:2000
AVAILABLE ACCESSORIES AND OPTIONS:
Steel or Aluminum weather proof, sound attenuated enclosures
UL142 listed, double wall fuel tanks from 50 to 10,000 Gal
UL1008 listed, automatic transfer switches from 50 to 3000 Amp
D.O.T. compliant heavy duty road trailers from 3000 to 30000 Lbs
Automatic battery chargers, Engine preheaters, Remote annunciators
and many more
Voltage
480/277
440/254
380/220
230/115
220/127
208/120
600/347
Power ESP
kWe/kVA
117 / 146
117 / 146
117 / 146
117 / 146
117 / 146
115 / 144
117 / 146
Power PRP
kWe/kVA
106 / 133
106 / 133
106 / 133
106 / 133
106 / 133
105 / 131
106 / 133
Standby Amps
176
192
222
367
383
400
140
Dimensions - Open
Weight - Open
POWER DEFINITION
PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO
8528-1.
ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 85281. Overload is not allowed.
TERM OF USE
Standard reference conditions ESP/PRP 25 C/25 C Air Intlet Temp, 1000 m/1000 m m A.S.L. 60 % relative humidity.
dB(A)@1m
M226-DW
M226
80
80
dB(A)@7m
68.9
68.9
Dimensions - Enclosed
Leng : 3560mm [140in]
Widt : 1200mm [47in]
Heig : 2182mm [86in]
Leng : 3508mm [138in]
Widt : 1200mm [47in]
Heig : 1830mm [72in]
120KW GENERATOR
GENERAL POWER LIMITED, INC
Phone (305) 471 9566, Phone (888) POWER 58, Fax (305) 471 9568, Fax (305) 675 8033
www.dieselgeneratorsmiami.com
www.genpowerusa.com
info@genpowerusa.com
MIAMI, FLORIDA | TUSTIN, CALIFORNIA | PANAMA | FRANCE | COLOMBIA | U.K.
Weight - Enclosed
2560kg [5644lbs]
3443kg [7591lbs]
2160kg [4762lbs]
2500kg [5512lbs]
Tank
868 L
229 Gal
340 L
90 Gal
ENGINE SPECIFICATIONS
Engine model
DATA
GENERAL DATA
Cylinder arrangement
Displacement (C.I.)
Bore (mm) X Stroke (mm)
Compression ratio
Speed (RPM)
Pistons speed (m/s)
Maximum stand-by power at rated RPM (kW)
Frequency regulation (%)
BMEP (bar)
Governor type
EXHAUST SYSTEM
540
413
750
FUEL SYSTEM
9.1
8.4
6.3
4.2
29.5
21.5
1
5
0.032
20.6
OIL
THERMAL BALANCE
AIR INTAKE
COOLANT SYSTEM
EMISSIONS
110
16
68
AIR INTAKE_entree_max%
Intake air flow (L/s)
625
179
27.3
105
93
5
N/A
20
GENCOOL
82-94
Emissions PM (g/kWh)
Emission CO (g/kW.h)
Emissions HCNOx (g/kWh)
N/A
N/A
N/A
Emission HC (g/kW.h)
N/A
Phone (305) 471 9566, Phone (888) POWER 58, Fax (305) 471 9568, Fax (305) 675 8033
www.dieselgeneratorsmiami.com
www.genpowerusa.com
info@genpowerusa.com
MIAMI, FLORIDA | TUSTIN, CALIFORNIA | PANAMA | FRANCE | COLOMBIA | U.K.
ALTERNATOR SPECIFICATIONS
DATA
GENERAL DATA
OTHER
DATA
Alternator brand
Alternator
Number of phase
Power factor (Cos Phi)
Altitude (m)
Overspeed (rpm)
Number of pole
Excitation system
Insulation class / Temperature class
Regulation
Total harmonics TGH/THC
Wave form : NEMA=TIF-TGH/THC
Wave form : CEI=FHT-TGH/THC
Number of bearing
Coupling
Voltage regulation 0 to 100%
Recovery time (Delta U = 20% transitoire) (ms)
Continuous Nominal Rating 40C (kVA)
Standby Rating 27C (kVA)
Efficiencies 4/4 load (%)
Air flow (cfm)
Short circuit ratio (Kcc)
Direct axis synchro reactance unsaturated (Xd) (%)
Quadra axis synchro reactance unsaturated (Xq) (%)
Open circuit time constant (T'do) (ms)
Direct axis transient reactance saturated (X'd) (%)
Short circuit transient time constant (T'd) (ms)
Direct axis subtransient reactance saturated (X''d) (%)
Subtransient time constant (T"d) (ms)
Quadra axis subtransient reactance saturated (X"q) (%)
Zero sequence reactance unsaturated (Xo) (%)
Negative sequence reactance saturated (X2) (%)
Armature time constant (Ta) (ms)
No load excitation current (io) (ms)
Full load excitation current (ic) (A)
Full load excitation voltage (uc) (A)
Recovery time (Delta U = 20% transitoire) (ms)
Motor start (Delta U = 20% perm. or 50% trans.) (ms)
Transient dip (4/4 charge) - PF : 0,8 AR (%)
No load losses (kW)
Heat rejection (kW)
Phone (305) 471 9566, Phone (888) POWER 58, Fax (305) 471 9568, Fax (305) 675 8033
www.dieselgeneratorsmiami.com
www.genpowerusa.com
info@genpowerusa.com
MIAMI, FLORIDA | TUSTIN, CALIFORNIA | PANAMA | FRANCE | COLOMBIA | U.K.
LEROY SOMER
LSA442S7
3
0.8
<1000
2250
4
SHUNT
H/H
R230
<2
<50
<2
1
DIRECT
0.5%
500
155
170
91.8
0.44
0.33
363
218
2734
13
100
8
10
9.6
0.7
8.8
15
0.5
1.9
36
500
301
16.6
2.96
10.68
CONTROL PANELS
#STD_COFFRET
Standard
Option
NEXYS
NEXYS
Specifications : Frequency meter, Ammeter, Voltmeter
Alarms and faults : Oil pressure, water temperature, Overcrank,
Overspeed ( >60 kVA), Min/max alternator, Low fuel level,
Emergency stop
Engine parameters : Hours counter, Engine speed, Battery voltage,
Fuel level, AIr preheating
TELYS 2
TELYS
Specifications : Frequency meter, Ammeter, Voltmeter
Alarms and faults : Oil pressure, water temperature, No start-up,
Overspeed, Min/max alternator, Min/max battery voltage, Low fuel
level, Emergency stop
Engine parameters : Hours counter, Oil pressure, Water
temperature, Engine speed, Battery voltage, Fuel level,
Remote monitoring and control
#OPT1#O
PT3
Option
#OPT2
Phone (305) 471 9566, Phone (888) POWER 58, Fax (305) 471 9568, Fax (305) 675 8033
www.dieselgeneratorsmiami.com
www.genpowerusa.com
info@genpowerusa.com
MIAMI, FLORIDA | TUSTIN, CALIFORNIA | PANAMA | FRANCE | COLOMBIA | U.K.
Weather / Soundproof
Enclosure
M226
STANDARD FEATURES
They protect stationary and mobile generator against the bad weather, against the theft and enables the reduction of
the noise level.
Enclosures are of 12 gauge steel. Steel sheet are electro zinc coated before painting (inside and outside) with a
polyester powder rust inhibiting coat .
High corrosion resistance: stainless covered with zinc and made in dichromate, bolts and rivets, anodized aluminium
alloy hinges flexible seals between body sections.
Soundfoam between 20 and 50 mm (1 to 2 in) acoustical sound treatment
Lifting eye(s) on top of the enclosure fixed to the skid
Large doors allow easy access to the generator set for service and monitoring purposes
Window in securit glass mounted on enclosure door for control viewing .
A critical silencer is mounted inside the enclosure
Emergency stop button is accessible from outside enclosure.
Model
J120U
Dimensions
Weight
Tank
dB(A)@1m
Sound level
dB(A)@7m
LWA
(mm)
(kgs)
(l)
80
68.9
N/A
3508 x 1200 x
1830
2160
340
#OPT3
Phone (305) 471 9566, Phone (888) POWER 58, Fax (305) 471 9568, Fax (305) 675 8033
www.dieselgeneratorsmiami.com
www.genpowerusa.com
info@genpowerusa.com
MIAMI, FLORIDA | TUSTIN, CALIFORNIA | PANAMA | FRANCE | COLOMBIA | U.K.