Escolar Documentos
Profissional Documentos
Cultura Documentos
Cert.N9105.SECP
Input voltage
Input current
3% (typ.)
0.99
Leakage current
EMI filter
Inrush current
35A (Vin=230Vac)
Output specifications
Output stability
V nom
(V)
MODEL
Vadj
I max (A)
521S D
12
15
515S D
15
12
524S D
24
528S D
28
548S D
48
Efficiency
Line regulation (15 %)
0.5%
1%
80% tip.
G en e ra l F e a tu res
Inte rnal de coupling d iod e on the o utp ut; both a node and
catho de available on o utp ut te rm ina ls.
100 % test and burn -in (repo rts available on req uest)
Tw o years w arranty
10
5%
(trimmer)
8.5
5
556S D
56
4.3
510S D
110
2.2
85% tip.
240 W
Switching frequency
70 KHz typical
Ripple (0 - 2MHz)
<= 1% of output
Spikes (2 - 20MHz)
<= 2% of output
2 sec typ.
Overvoltages
None
Signals
Power good signal. Switching floating contact (NC/NA) monitoring the output in
tolerance. Rel rating: 1A, 60Vdc
PG
Protections
Electromagnetic compatibilty
Safety
Continuously
Overvoltages
Case protection
Input to output
IP20
UL 94 V2
MTBF
Operating temperature
Input to case
Output to case
-10 to 55C ambient; derate the output power at 2.5% for C from
55 C to 70C
Flammability class
Environment
Insulation resistance
Relative humidity
up to 93% non condensing
Electric strength
Input to output
Input to case
Output to case
Storage temperature
-40 to +85 C
Ambient conditions
A 500S power supply module, when
operated at its rated power, can dissipate
upto 60W.
To prevent excessive heating of the
surrounding air, avoid to allocate it in
ambients where phenomena of still air can
arise.
SECAP S.r.l - Viale delle Scienze, 15 - 20082 Binasco (MI) -Italy - tel. 02.9055758 fax 02.90096482 e-mail:infosecap@secap.it web: http://www.secap.it
08980IS3e - 06/02
Description
1
General
For parallel operation of two or more
units use TB3-3 output in order to take
advantage of the internal decoupling
diode present in series to the output.
The use of this output gives the
possibility of:
- managing, indipendently for each unit,
the Power Good indications;
- avoiding the fault propagation from a
single unit to the system.
- obtaining a certain load sharing among
the various power supplies.
Mounting
The figure shows the suggested
mounting positions.
Connection
To have a better load sharing among the
various units it is suggested to connect
each power supply indipendently to the
load, or to the busbars, through cables of
the same type and having the same
length.
Calibration
The voltage drop of the internal diode is
not recovered by the control circuit, which
regulates the voltage on the anode of the
decoupling diode.
In order to compensate this voltage drop,
and in the meanwhile to obtain the best
load sharing, it is necessary to make a
calibration of the output voltage.
Follow this procedure.
- Operate on the single units ,
disconnected from the load, one at a
time.
- Load the unit with a current of nearly the
50% of its rating.
- Measure the voltage at its output
terminals by means of an instrument
having a precision better than the
required precision of the calibration.
- Adjust the output voltage to the desired value turning the frontal Vadj trimmer.
Use a properly insulated tool.
- Repeat this operation for each power supply, always using the same measuring
instrument and adjusting at the same voltage value.
2
3
4
5
Input
TB1-1
Line (protected by internal fuse)
TB1-2
Neutral
TB1-3
Protective earth
Vadj
Trimmer to adjust the output voltage; the voltage is increased turning it clockwise.
Terminals of the relay monitoring the output voltage state
TB2-1 is connected to TB2-3 when the output voltage is in tolerance;
TB2-1 is connected to TB2-2 when the output voltage is out of tolerance.
Terminals rating: 1A, 60V. The terminals are insulated both from ground and the output.
Power Good led
Led indicating the output voltage state; it is ON when the output voltage is in tolerance.
Outputs
TB3-1
Output voltage negative
TB3-2
Output voltage positive;the output voltage regulation is accomplished at this point
TB3-3
Decoupling diode cathode; the anode is connected to TB3-2.
Model identificating label
Terminals characteristics
TB1-1, TB1-2, TB1-3, TB3-1, TB3-2, TB3-3
rigid and stranded wire
Max 2.5 mm
AWG
28-14
V/A
400/24
Connections
Use interconnecting cables with a cross sectional area dimensioned for a suggested current density of
3A/mm.
Decoupling diode
A decoupling diode connected in series to the output is provided inside the power supply.
Both its anode (TB3-2) and its cathode (TB3-3) are available at output terminals.
The control circuit regulates the voltage on the anode, so the voltage drop of the diode (about 0.6V)
isn't recovered.
Use TB3-2 output in all the applications where a precise output voltage is requested.
Use TB3-3 output for parallel or redundant operation of two or more units, thus taking advantage of the
internal decoupling diode.
Refusal of acceptance
The rejected product must be returned to SECAP within 30 days from the date of
delivery to the purchaser or bearer.
The return procedure is the following:
1) contact by telephone our Technical Support Centre
2) follow the instructions stated in the paragraph "Instructions for packaging and
shipment to SECAP"
3) enclose the JUSTIFICATION OF THE REFUSAL OF ACCEPTANCE
4) send the product FREE OF CHARGES
TB4
SECAP S.r.l - Viale delle Scienze, 15 - 20082 Binasco (MI) - Italy - tel. 02.9055758 fax 02.90096482 e-mail:infosecap@secap.it web: http://www.secap.it
Reservations
SECAP reserves the right of:
1) returning packages not shipped FREE OF CHARGES
2) not repairing products without clear description of the problems they are affected by
3) not repairing products without the estimation of expenditure approval
4) not repairing products in case of outstandig accounts (paymrent in arreas, outstanding
debts, ....)
5) not repairing products modified without SECAP authorization
08980IS3e - 06/02