ED 21 - 301A

Split System Air Conditioners


SkyAir
(Pair and Twin-Triple-Double Twin)

LU Series
Cooling Only

ED21-301A

SkyAir LU Series (Pair) Cooling Only ..................................... 1


1. Model Name and Power Supply..............................................................2
1.1 Pair Series................................................................................................2

2. External Appearance...............................................................................4
2.1 External Appearance................................................................................4

3. Functions.................................................................................................5
3.1 LU Series..................................................................................................5

4. Specifications ..........................................................................................8
4.1 50Hz (General).........................................................................................8
4.2 50Hz (Complied with Australian Standard) ............................................19
4.3 60Hz .......................................................................................................21

5. Dimensions and Service Space ............................................................27


5.1
5.2
5.3
5.4

Indoor Unit..............................................................................................27
Remote Controller ..................................................................................42
Outdoor Unit ...........................................................................................45
Installation Service Space for R71~140LU.............................................49

6. Piping Diagrams....................................................................................51
6.1 Pair .........................................................................................................51

7. Wiring Diagrams....................................................................................54
7.1 Indoor Unit..............................................................................................54
7.2 Outdoor Unit ...........................................................................................67

8. Capacity Tables ....................................................................................74


8.1
8.2
8.3
8.4

50Hz (General).......................................................................................74
50Hz (Complied with Australian Standard) ............................................79
60Hz .......................................................................................................82
Capacity Correction Factor by the Length of Refrigerant Piping ............87

9. Operation Limits ....................................................................................88


9.1 Operation Limits .....................................................................................88

10.Sound Level ..........................................................................................89


10.1 Overall Sound Level ...............................................................................89
10.2 Octave Band Level .................................................................................90

11.Fan Performance ..................................................................................94


11.1 Fan Performance....................................................................................94

12.Electric Characteristics..........................................................................96
12.1 50Hz .......................................................................................................96
12.2 60Hz .......................................................................................................98

13.Option List .............................................................................................99


13.1 Indoor Unit..............................................................................................99
13.2 Outdoor Unit .........................................................................................102

14.Field Piping and Wiring .......................................................................103


14.1 Field piping ...........................................................................................103
14.2 Field Wiring ..........................................................................................105

SkyAir LU Series (Twin, Triple, Double Twin)


Cooling Only ........................................................... 107
1. Features ..............................................................................................108
1.1 What are Twin, Triple, Double Twin Systems? ....................................108

2. Model Name and Power Supply..........................................................109


Table of Contents

ED21-301A

2.1 Twin, Triple and Double Twin System..................................................109

3. External Appearance...........................................................................111
3.1 External Appearance............................................................................111

4. Specifications ......................................................................................112
4.1 50Hz .....................................................................................................112
4.2 60Hz .....................................................................................................118

5. Dimensions and Service Space ..........................................................124


5.1
5.2
5.3
5.4
5.5

Indoor Unit............................................................................................124
Remote Controller ................................................................................132
Outdoor Unit .........................................................................................134
Installation Service Space for R71~140LU...........................................137
Installation Service Space for R200 250KU .......................................139

6. Piping Diagrams..................................................................................140
6.1 Twin......................................................................................................140
6.2 Triple ....................................................................................................145
6.3 Double Twin .........................................................................................147

7. Wiring Diagrams..................................................................................148
7.1 Indoor Unit............................................................................................148
7.2 Outdoor Unit .........................................................................................150

8. Capacity Tables ..................................................................................155


8.1 50Hz .....................................................................................................155
8.2 60Hz .....................................................................................................158
8.3 Capacity Correction Factor by the Length of Refrigerant Piping ..........162

9. Operation Limits ..................................................................................163


9.1 Operation Limits ...................................................................................163

10.Sound Level ........................................................................................164


10.1 Overall Sound Level .............................................................................164
10.2 Octave Band Level ...............................................................................165

11.Electric Characteristics........................................................................167
11.1 50Hz .....................................................................................................167
11.2 60Hz .....................................................................................................168

12.Option List ...........................................................................................170


12.1 Indoor Unit............................................................................................170
12.2 Outdoor Unit .........................................................................................171

13.Field Piping and Wiring .......................................................................172


13.1 Field Piping...........................................................................................172
13.2 Field Wiring ..........................................................................................177

Detail Information of Options SkyAir LU Series ........................ 179


1. Remote Controller ...............................................................................180
1.1
1.2
1.3
1.4
1.5

Remote Controller, Timer, Adaptor List................................................180


Wired Remote Controller......................................................................180
Wireless Remote Controller .................................................................185
Various Control by Liquid Crystal Remote Controller...........................187
BRC15A61 Set Back Time Clock ....................................................191

2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C] .......................195


2.1
2.2
2.3
2.4
ii

BYC125KW1 Decoration Panel .....................................................195


KDBHJ55K160 Sealing Member of Air Discharge Outlet ................198
KDBP55H160WA Panel Spacer ......................................................200
KDDP55D160(K) Fresh Air Intake Kit..............................................202
Table of Contents

ED21-301A

2.5 KDDJ55X160 Fresh Air Intake Kit ...................................................205


2.6 KAFP556D80 160
HighEfficiency Filter (Including Filter Chamber)
KAFP557D80 160
HighEfficiency Filter (Including Filter Chamber) ............................207
2.7 KAFP552H80 160 Replacement HighEfficiency Filter
KAFP553H80 160 Replacement HighEfficiency Filter.................207
2.8 KRP1B98 Installation Box for Adaptor PCB ....................................207
2.9 KDDFP55D160 HighEfficiency Filter Chamber .............................208
2.10 KAFJ551K160
Replacement LongLife Filter for Decoration Panel ........................210
2.11 KAFP55D160, KAFJ55K160H (Replacement)
Ultra LongLife Filter (Including Filter Chamber).............................210
2.12 KKSJ55K160 Chamber Connection Kit ...........................................211
2.13 KDJ55K80 160 Branch Duct Chamber ..........................................212
2.14 Dimensions with Optional Kit................................................................217

3. Ceiling Mounted Cassette Corner Type [FH(Y)K] ...............................221


3.1
3.2
3.3
3.4
3.5
3.6

BYK45FJW1 71FJW1 Decoration Panel .......................................221


KPBJ52F56W 80W Panel Specer .................................................225
KDBJ52F56W 80W Air Discharge Blind Panel..............................229
KAFJ521F56 80 Replacement LongLife Filter.............................236
KHV7AW 9AW Discharge Grille ..................................................236
KFDJ52F56 80 Flexible Duct with Shutter.....................................237

4. Ceiling Mounted BuiltIn Type [FH(Y)B] .............................................242


4.1 BYBS45DJW1 Decoration Panel
BYBS71DJW1 Decoration Panel
BYBS125DJW1 Decoration Panel...................................................242
4.2 KTBJ25K56W 80W 160W Service Access Panel........................246
4.3 KAFJ252L56 80 160 HighEfficiency Filter
KAFJ253L56 80 160 HighEfficiency Filter .................................247
4.4 KAFJ251K56 80 160 Replacement LongLife Filter....................248
4.5 KAJ25L56D 80D 160D Filter Chamber for Bottom Suction .........248
4.6 KAJ25L56B 80B 160B Filter Chamber for Rear Suction .............249
4.7 KSA25K56 80 160 Canvas Duct.................................................252
4.8 KDG4DW 5DW 7DW 9DW
Air Discharge UnitDischarge Grille+Discharge Chamber
KDGC4D 5D 7D 9D
Air Discharge UnitDischarge Grille+Discharge Chamber ..............253
4.9 KDDV20A Branch Duct..................................................................256
4.10 KFDS151D 152D 153D 154D 155D 156D Flexible Duct
KFDS201D 202D 203D 204D 205D 206D Flexible Duct.....257
4.11 KBBJ25K56 80 160 Blind Board..................................................258
4.12 KDAJ25K56 71 140 Adaptor for Discharge .................................259
4.13 KDJ2507K56 80 160 Flange for Suction .....................................260
4.14 Optional Kit Installation Drawing ..........................................................261

5. New Ceiling Suspended Cassette Type [FUY] ...................................265


5.1
5.2
5.3
5.4
5.5
5.6
Table of Contents

KDBHJ49F80 140 Sealing Member of Air Discharge Outlet .........265


KDBTJ49F80 140 Decoration Panel for Air Discharge..................265
KDGJ49F80 140 Vertical Flap Kit..................................................265
KAFJ495F140 Replacement LongLife Filter..................................266
KHFJ49F80 140 LConnection Piping Kit .....................................266
KRP1B97 Installation Box for Adaptor PCB ....................................266
iii

ED21-301A

6. Ceiling Suspended Type [FH(Y)] ........................................................267


6.1
6.2
6.3
6.4

KAFJ501D56 80 112 160 Replacement LongLife Filter ..........267


KDU50B50 71 125VE Drain Pump Kit.........................................267
KHFJ5F50 60 80 160 LType Piping Kit ...................................268
KRP1C93 Installation Box for Adaptor PCB ....................................268

7. Floor Standing Type [FVY]..................................................................269


7.1 KAFJ95L160 Replacement LongLife Filter ....................................269
7.2 KRP4A95 Installation Box for Adaptor PCB ....................................269

8. Outdoor Unit........................................................................................270
8.1
8.2
8.3
8.4

iv

KIS95 Drain Piping Kit .....................................................................270


KKPJ5F180 Central Drain Plug .......................................................270
KRK5F80V1 140V1 160V1 YearRound Cooling Kit ..................271
KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D33,
KHR58P322H, KHRJ5F224F, KHRJ5F280F
Refrigerant Branch Piping Kit ..........................................................272

Table of Contents

ED21-301A

SkyAir LU Series
(Pair)
Cooling Only

Model Series
Class
Indoor
Unit

35

45

50

60

71

100

125

140

35K

50K

60K

71K

100K

125K

140K

35F

45F

60F

71FJ

35F

45F

60F

FHYB

71F

100F

125F

FUY

71FJ

100FJ 125FJ

35B

50B

60B

FHY

71B

100B

125B

FAY

71L

100FA

FVY

71LA

35G

50G

FHC
FHYC
FHK
FHYK
FHB

FH

Outdoor
R
Unit

50G(A) 60G(A) 71LU

100LA 125LA

100LU 125LU 140LU

Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and
choose an outdoor unit with anti-corrosion treatment.

SkyAir LU Series Cooling Only

Model Name and Power Supply

ED21-301A

1. Model Name and Power Supply


1.1

Pair Series

1.1.1

50Hz (General)
Indoor Unit

Note:

Outdoor Unit

FHC35KVE

R35GV1

FHC50KVE

R50GV1

FHC60KVE

R60GV1

FHYC71KVE

R71LUV1

Power Supply
1, 220~240V, 50Hz

FHYC100KVE

R100LUV1

FHYC71KVE

R71LUY1

FHYC100KVE

R100LUY1

FHYC125KVE

R125LUY1

FHYC140KVE

R140LUY1

FHK35FV1

R35GV1

FHK45FV1

R50GV1

FHK60FV1

R60GV1

FHYK71FJV1

R71LUV1

FHYK71FJV1

R71LUY1

3, 380~415V, 50Hz

FHB35FV1

R35GV1

1, 220~240V, 50Hz

FHB45FV1

R50GV1

FHB60FV1

R60GV1

FHYB71FV1

R71LUV1

FHYB100FV1

R100LUV1

FHYB71FV1

R71LUY1

FHYB100FV1

R100LUY1

FHYB125FV1

R125LUY1

FUY71FJV1

R71LUV1

FUY100FJV1

R100LUV1

FUY71FJV1

R71LUY1

FUY100FJV1

R100LUY1

FUY125FJV1

R125LUY1

FH35BVE

R35GV1

FH50BVE

R50GV1

FH60BVE

R60GV1

FHY71BVE

R71LUV1

FHY100BVE

R100LUV1

FHY71BVE

R71LUY1

FHY100BVE

R100LUY1

FHY125BVE

R125LUY1

FAY71LVE

R71LUV1

FAY100FAVE

R100LUV1

FAY71LVE

R71LUY1

FAY100FAVE

R100LUY1

FVY71LAVE

R71LUV1

FVY100LAVE

R100LUV1

FVY71LAVE

R71LUY1

FVY100LAVE

R100LUY1

FVY125LAVE

R125LUY1

3, 380~415V, 50Hz

1, 220~240V, 50Hz

3, 380~415V, 50Hz

1, 220~240V, 50Hz
3, 380~415V, 50Hz

1, 220~240V, 50Hz

3, 380~415V, 50Hz

1, 220~240V, 50Hz
3, 380~415V, 50Hz
1, 220~240V, 50Hz
3, 380~415V, 50Hz

1. Power Supply Intake : Outdoor Unit

SkyAir LU Series Cooling Only

ED21-301A

1.1.2

Model Name and Power Supply

50Hz (Complied with Australian Standard)


Indoor Unit

1.1.3

Outdoor Unit

FHC35KVE

R35GV1A

FHC50KVE

R50GAV1A

FHC60KVE

R60GAV1A

FH50BVE

R50GAV1A

FH60BVE

R60GAV1A

Power Supply
1, 240V, 50Hz

60Hz
Indoor Unit
FHC50KVE

Note:

Outdoor Unit
R50GVAL

FHC60KVE

R60GVAL

FHYC71KVE

R71LUVAL

Power Supply
1, 220V, 60Hz

FHYC100KVE

R100LUVAL

FHYC125KVE

R125LUTAL

3, 220V, 60Hz

FHYC125KVE

R125LUYAL

3, 380V, 60Hz

FHYC140KVE

R140LUTAL

3, 220V, 60Hz

FHYC140KVE

R140LUYAL

3, 380V, 60Hz

FH50BVE

R50GVAL

1, 220V, 60Hz

FH60BVE

R60GVAL

FHY71BVE

R71LUVAL

FHY100BVE

R100LUVAL

FHY125BVE

R125LUTAL

3, 220V, 60Hz

FHY125BVE

R125LUYAL

3, 380V, 60Hz
1, 220V, 60Hz

FAY71LVE

R71LUVAL

FAY100FAVE

R100LUVAL

FVY71LAVE

R71LUVAL

FVY100LAVE

R100LUVAL

FVY125LAVE

R125LUTAL

3, 220V, 60Hz

FVY125LAVE

R125LUYAL

3, 380V, 60Hz

1, 220V, 60Hz

1. Power Supply Intake : Outdoor Unit

SkyAir LU Series Cooling Only

External Appearance

ED21-301A

2. External Appearance
2.1

External Appearance

Indoor Unit

FH(Y)CK

FH(Y)KF(J)

FUYFJ

FH(Y)B

FAY71L

FAY100FA

FH(Y)BF

FVYLA

Remote Controller

Wired Type

Wireless Type

Outdoor Unit

R35G
R50G(A)

R60G(A)

R71LU

R100LU

R125LU

R140LU

SkyAir LU Series Cooling Only

ED21-301A

Functions

3. Functions
3.1

LU Series
Items

Improved Points and Functions

Ceiling Mounted Cassette (FH(Y)C)

Model Type

Indoor Unit

Existing

Existing

Outdoor Unit

Existing

Existing

35~60K

71~140K

Main
Improvement

Appearance Improved

Reduction of Operation Sound

For
Comfortable
Air
Conditioning

Auto Restart

Fan Operation Mode

Wired Type

Wireless Type

Auto Swing Function

Ceiling Soiling Prevention

Wired Type

Wireless Type

LCD Remote Controller (Option)

Two Select Thermo Sensor

For Easy
Construction
and
Maintenance

For Flexible
Control

Program Dry

High Fan Speed Mode

High Ceiling Application

Year Round Cooling Kit (Option)

Timer Selector

Fresh Air Intake Directly from the Unit

Drain Pump

LongLife Filter

Ultra LongLife Filter (Option)

Mold Resistant Treatment for Filter

Filter Sign

Mold Resistant Drain Pan

Emergency Operation

Self Diagnoses Function

Low Gas Pressure Detection (R)

{ (71~140)

Set Back Time Clock

Double Remote Control

Group Control by 1 Remote Controller

Control by DBACS

Remote/Centralized Control

{ : Functions exist.
: No Functions

SkyAir LU Series Cooling Only

Functions

ED21-301A

Items

Model Type

Improved Points and Functions

For Flexible
Control

35~60F

35~60F

71FJ

71~
125F

New Ceiling
Suspended
(FUY)
71~125FJ

Indoor Unit

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Auto Restart

Fan Operation Mode

LCD Remote Controller (Option)

Auto Swing Function

Ceiling Soiling Prevention

Wired Type

Wireless Type

Two Select Thermo


Sensor

For Easy
Construction
and
Maintenance

Ceiling Mounted
BuiltIn
(FH(Y)B)

Outdoor Unit
Main
Appearance Improved
Improvement
Reduction of Operation Sound
For
Comfortable
Air
Conditioning

Ceiling Mounted
Cassette Corner
(FH(Y)K)

Program Dry

High Fan Speed Mode

High Ceiling Application

Year Round Cooling Kit (Option)

Timer Selector

Fresh Air Intake Directly from the Unit

Drain Pump

LongLife Filter

Ultra LongLife Filter (Option)

Mold Resistant Treatment for Filter

Filter Sign

Mold Resistant Drain Pan

Emergency Operation

Self Diagnoses Function

Low Gas Pressure Detection (R)

{(71)

Set Back Time Clock

Double Remote Control

Group Control by 1 Remote Controller

Control by DBACS

Remote/Centralized Control

{
{(71~125)
(71~125)

{ : Functions exist.
: No Functions

SkyAir LU Series Cooling Only

ED21-301A

Functions

Items

Improved Points and Functions

Ceiling Suspended
(FH(Y))
35, 50B

Model Type

For Flexible
Control

71L,
100FA

71~125LA

Indoor Unit

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Existing

Reduction of Operation Sound

Auto Restart

Fan Operation Mode

Wired Type

Wireless Type

LCD Remote Controller


(Option)
Auto Swing Function

Ceiling Soiling Prevention

Wired Type

Wireless Type

Two Select Thermo


Sensor

For Easy
Construction
and
Maintenance

100B,
125B

Outdoor Unit
Main
Appearance Improved
Improvement
Reduction of Dimensions or Weight
For
Comfortable
Air
Conditioning

60, 71B

Wall
Floor
Mounted Standing
(FAY)
(FVY)

Program Dry

High Fan Speed Mode

High Ceiling Application

Year Round Cooling Kit (Option)

Timer Selector

Fresh Air Intake Directly from the Unit

Drain Pump Kit (Option)

LongLife Filter

Ultra LongLife Filter (Option)

Mold Resistant Treatment for Filter

Filter Sign

Mold Resistant Drain Pan

Emergency Operation

Self Diagnoses Function

Low Gas Pressure Detection (R)

{(71)

Set Back Time Clock

Double Remote Control

Group Control by 1 Remote Controller

Control by DBACS

Installation Box for Adapter PCB

{
(71 only)

Remote/Centralized Control

{
{
{
(100, 125) (71, 100) (71~125)

{ : Functions exist.
: No Functions

SkyAir LU Series Cooling Only

Specifications

ED21-301A

4. Specifications
4.1

50Hz (General)

FHC (Ceiling Mounted Cassette Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Air Filter
Weight

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FHC50KVE
FHC60KVE
R50GV1
R60GV1
5.34/5.3
6.44/6.4
18,200/18,100
22,000/21,800
4,590/4,560
5,540/5,500
FHC50KVE
FHC60KVE
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H) 14 (L) 10
(H) 15 (L) 11
(H) 19 (L) 14
24
24
24
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 4, 5)
BRC7C613W
BYC125KW1
BYC125KW1
BYC125KW1
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R35GV1
R50GV1
R60GV1
Ivory White
540750270
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2222.0
2282.0
0.372
0.372
0.465
RC46AV1TRT
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.1
1.7
2.2
PZ380
PZ380
PZ430
Propeller
27
45
53
28
27
40
37
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
1000
Capillary Tube
25
30
30
15
15
15
R22
R22
R22
1.10 (Charged for 10m)
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.50
0.85
1.20
4D006549A

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.

mm

FHC35KVE
R35GV1
3.54/3.5
12,100/11,900
3,040/3,010
FHC35KVE
230840840

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


5m
50Hz, 220240V
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHYC (Ceiling Mounted Cassette Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate 2

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

Comp.

Fan

Model
Color
Dimensions (HWD)
Air Filter
Weight

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
Coil

mm

mm
kg
V1
Y1
mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHYC71KVE
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHYC71KVE
230840840

FHYC100KVE
FHYC125KVE
FHYC140KVE
R100LUV1

R100LUY1
R125LUY1
R140LUY1
10.6/10.5/10.5
13.0/12.8/12.8
14.5/14.2/14.2
36,100/35,700/35,700
44,500/43,600/43,600
49,400/48,400/48,400
9,100/9,000/9,000
11,200/11,000/11,000
12,500/12,200/12,200
FHYC100KVE
FHYC125KVE
FHYC140KVE
288840840
288840840
288840840
Cross Fin coil (Waffle Louver Fins and HiXA Tubes)
281.5
2121.5
2121.5
2121.5
0.331
0.497
0.497
0.497
QTS45B14M
QTS45A17M
QTS45A17M
QTS45A17M
Turbo Fan
45
90
90
90
(H) 1921 (L) 1416
(H) 2831 (L) 2124
(H) 3336 (L) 2427
(H) 3538 (L) 2628
24
28
28
28
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 5, 6)
BRC7C613W
BYC125KW1
BYC125KW1
BYC125KW1
BYC125KW1
White
40950950
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
5
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
R140LUY1
Ivory
770900320
1,170900320
1,170900320
1,345900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
2602.0
0.634
0.983
0.983
1.134
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
JT170BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
4.50
P47L11S
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
65+90
4851
5962
92100
97109
72
87

71
84
98
109
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125140>. Low Pressure
Switch. Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
30
30
R22
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
4.1 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
1.6
4D039096
4D039079

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

Specifications

ED21-301A

FHK (Ceiling Mounted Cassette Corner Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Air Filter
Weight

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FHK45FV1
FHK60FV1
R50GV1
R60GV1
5.19/5.1
6.6/6.5
17,700/17,500
22,760/22,200
4,460/4,400
5,690/5,600
FHK45FV1
FHK60FV1
2151,110710
2151,310710
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2111.75
3111.75
3111.75
0.180
0.180
0.226
3D12H1AH1V1
3D12H1AJ1V1
4D12H1AG1V1
Sirocco Fan
20
25
45
(H) 12 (L) 9
(H) 12 (L) 10
(H) 17 (L) 14
30
31
33
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 4, 5)

BYK45FJW1
BYK45FJW1
BYK71FJW1
White
701,240800
701,240800
701,440800
Resin Net (with Mold Resistant)
8.5
8.5
9.5
R35GV1
R50GV1
R60GV1
Ivory White
540750270
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2222.0
2282.0
0.372
0.372
0.465
RC46AV1TRT
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.1
1.7
2.2
PZ380
PZ380
PZ430
Propeller
27
45
53
28
27
40
37
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
1000
Capillary Tube
25
30
30
15
15
15
R22
R22
R22
1.10 (Charged for 10m)
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.50
0.85
1.20
4D006259A

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.

10

mm

FHK35FV1
R35GV1
3.54/3.4
12,100/11,600
3,040/2,930
FHK35FV1
2151,110710

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


5m
50Hz, 220240V
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHYK (Ceiling Mounted Cassette Corner Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate 2

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

Comp.

Fan

Model
Color
Dimensions (HWD)
Air Filter
Weight

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
Coil

mm

mm
kg
V1
Y1
mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHYK71FJV1
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHYK71FJV1
2151,310710
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
3111.75
0.226
4D12H1AG1V1
Sirocco Fan
45
(H) 1718 (L) 1415
33
9.5 (Flare)
15.9 (Flare)
I. D25O. D32
BRC1C61 (Note. 5, 6)

BYK71FJW1
White
701,440800
Resin Net (with Mold Resistant)
9.5
R71LUV1
R71LUY1
Ivory
770900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
0.634
ZR36K3PFJ
ZR36K3TFD
Hermetically Sealed Scroll Type
2.24
P47L11S
Propeller
65
4851
72
71
9.5 (Flare)
15.9 (Flare)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan
Motor. Low Pressure Switch. Over Current Device. Motor
Protector (Compressor). Reverse Phase Protector (Y1).
Fuse.
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
30
R22
2.8 (Charged for 30m)
Refer to the name plate of compressor.
1.2
4D039104

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

11

Specifications

ED21-301A

FHB (Ceiling Mounted BuiltIn Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Weight

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FHB45FV1
FHB60FV1
R50GV1
R60GV1
5.19/5.1
6.6/6.5
17,700/17,500
22,760/22,200
4,460/4,400
5,690/5,600
FHB45FV1
FHB60FV1
300700800
3001,000800
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
3141.75
3141.75
3141.75
0.132
0.132
0.221
D18H2AH1V1
D18H2AJ1V1
2D18H2AH1V1
Sirocco Fan
65
85
110
(H) 11.5 (L) 9
(H) 14 (L) 10
(H) 17 (L) 13
Resin Net (with Mold Resistant)
30
31
41
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 4, 5)

BYBS45DJW1 (2 BYBS45DW2)
BYBS45DJW1 (2 BYBS45DW2)
BYBS71DJW1 (2 BYBS71DW2)
White
55880500
55880500
551,100500
3.5
3.5
4.5
R35GV1
R50GV1
R60GV1
Ivory White
540750270
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2222.0
2282.0
0.372
0.372
0.465
RC46AV1TRT
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.1
1.7
2.2
PZ380
PZ380
PZ430
Propeller
27
45
53
28
27
40
37
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
1000
Capillary Tube
25
30
30
15
15
15
R22
R22
R22
1.10 (Charged for 10m)
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.50
0.85
1.20
4D006258B

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.
6.

12

mm

FHB35FV1
R35GV1
3.54/3.4
12,100/11,600
3,040/2,930
FHB35FV1
300700800

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


5m
50Hz, 220240V
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B62 is also available.
Wire for remote controller : Field supplied.
2 This type can be used.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHYB (Ceiling Mounted BuiltIn Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate 2

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

Comp.

Fan

W
m/min

Wired
Wireless

Model
Color
Dimensions (HWD)
Weight

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

kg
mm
mm
mm

Outdoor Unit
Color
Dimensions
Coil

mm

mm
kg
V1
Y1
mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHYB71FV1
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHYB71FV1
3001,000800

FHYB100FV1
FHYB125FV1
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FHYB100FV1
FHYB125FV1
3001,400800
3001,400800
Cross Fin Coil
3141.75
3141.75
3141.75
0.221
0.338
0.338
2D18H2AJ1V1
3D18H2AN1V1
3D18H2AP1V1
Sirocco Fan
125
135
225
(H) 1921.5 (L) 1416.5
(H) 2729 (L) 2022
(H) 3540.5 (L) 2429.5
Resin Net (with Mold Resistant)
41
51
52
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 5, 6)

BYBS71DJW1 (3 BYBS71DW2)
BYBS125DJW1 (3 BYBS125DW2)
BYBS125DJW1 (3 BYBS125DW2)
White
551,100500
551,500500
551,500500
4.5
6.5
6.5
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039103

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.
7.

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B62 is also available.
Wire for remote controller : Field supplied.
3 This type can be used.

SkyAir LU Series Cooling Only

13

Specifications

ED21-301A

FUY (New Ceiling Suspended Cassette Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

Comp.

Fan

W
m/min

Wired
Wireless
V1
Y1

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

kg
mm
mm
mm

Outdoor Unit
Color
Dimensions
Coil

mm

mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

m
m
kg
L

FUY100FJV1
FUY125FJV1
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FUY100FJV1
FUY125FJV1
White
165895895
230895895
230895895
Cross Fin Coil (Multi Louver Fins and HiXA Tubes)
361.5
381.5
381.5
0.265
0.353
0.353
QTS48A
QTS50B15M
QTS50B15M
Turbo Fan
45
90
90
(H)19 (L)14
(H)29 (L)21
(H)32 (L)23
Resin Net (with Mold Resistant)
25
31
31
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I.D 20O.D 26
I.D 20O.D 26
I.D 20O.D 26
BRC1C61 (Note. 5, 6)
BRC7C529W
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039105

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.

14

FUY71FJV1
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FUY71FJV1

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FH (Ceiling Suspended Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Color
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FH35BVE
R35GV1
3.54/3.4
12,100/11,600
3,040/2,930
FH35BVE

FH50BVE
FH60BVE
R50GV1
R60GV1
5.19/5.1
6.6/6.5
17,700/17,500
22,760/22,200
4,460/4,400
5,690/5,600
FH50BVE
FH60BVE
White
195960680
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
2121.75
3121.75
3121.75
0.182
0.182
0.223
3D12K1AA1
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
62
(H) 13 (L) 10
(H) 13 (L) 10
(H) 16 (L) 13
Resin Net (with Mold Resistant)
23
24
26
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D20O. D26
I. D20O. D26
I. D20O. D26
BRC1C61 (Note. 4)
BRC7E66
R35GV1
R50GV1
R60GV1
Ivory White
540750270
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2222.0
2282.0
0.372
0.372
0.465
RC46AV1TRT
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.1
1.7
2.2
PZ380
PZ380
PZ430
Propeller
27
45
53
28
27
40
37
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
1000
Capillary Tube
25
30
30
15
15
15
R22
R22
R22
1.10 (Charged for 10m)
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.50
0.85
1.20
4D028432

1. 1 The above data are based on the following conditions.

(1)

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


5m
50Hz, 220240V
Outdoor : 35CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.
(2)

SkyAir LU Series Cooling Only

15

Specifications

ED21-301A

FHY (Ceiling Suspended Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

Comp.

Fan

W
m/min

Wired
Wireless
V1
Y1

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

kg
mm
mm
mm

Outdoor Unit
Color
Dimensions
Coil

mm

mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

m
m
kg
L

FHY100BVE
FHY125BVE
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FHY100BVE
FHY125BVE
White
1951,160680
1951,400680
1951,590680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.293
0.341
4D12K1AA1
3D12K2AA1
4D12K2AA1
Sirocco Fan
62
130
130
(H) 17 (L) 14
(H) 24 (L) 20
(H) 30 (L) 25
Resin Net (with Mold Resistant)
27
32
35
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D20O. D26
I. D20O. D26
I. D20O. D26
BRC1C61 (Note. 5)
BRC7E66
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039099

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.

16

FHY71BVE
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHY71BVE

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FAY (Wall Mounted Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate 2

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

Comp.

Fan

W
m/min

Wired
Wireless
V1
Y1

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

mm

kg
mm
mm
mm

Outdoor Unit
Color
Dimensions
Coil

mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

2
kg

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

FAY71LVE
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FAY71LVE

%
m
m
kg
L

FAY100FAVE
R100LUV1
R100LUY1
10.6/10.5/10.5
36,100/35,700/35,700
9,100/9,000/9,000
FAY100FAVE

White
2901,050230
3601,570200
Cross Fin Coil (Multi Louver Fins and HiXA Tubes)
2161.4
2121.4
0.289
0.332
QCL9686M
QCL1163MA+QCL1163MB
Cross Flow Fan
43
46
(H) 1919 (L) 1515
(H) 2323 (L) 1919
Resin Net (Washable)
Resin Net (with Mold Resistant)
13
26
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
I. D20O. D26
I. D13O. D18
BRC1C61 (Note. 5, 6)
BRC7E619
BRC7C611W
R71LUV1
R100LUV1
R71LUY1
R100LUY1
Ivory
770900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
0.634
0.983
ZR36K3PFJ
ZR48K3PFJ
ZR36K3TFD
ZR48K3TFD
Hermetically Sealed Scroll Type
2.24
3.00
P47L11S
P47L11S
Propeller
65
90
4851
5962
72
87
71
84
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor
Protector (Compressor). Reverse Phase Protector (Y1). Fuse.
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
4D039583
4D039106

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

17

Specifications

ED21-301A

FVY (Floor Standing Type)


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

Air Filter
Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate 2

Comp.

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm
V1
Y1

Liquid
Gas
Drain

Outdoor Unit
Color
Dimensions
Coil

mm

mm

m
V1
Y1
kW

2
kg

Liquid
Gas
Drain

W
m/min
V1
Y1
mm
mm
mm

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FVY71LAVE
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FVY71LAVE

FVY100LAVE
FVY125LAVE
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FVY100LAVE
FVY125LAVE
White
1,850600270
1,850600350
1,850600350
Cross Fin Coil
2401.75
2441.75
(3221.75)2
0.40
0.44
0.44 (0.222)
QS37A1AM
QS37A2AM
QS37A2AM
Sirroco Fan
30
60
90
(H) 1820 (L) 1416
(H) 2831 (L) 2225
(H) 3235 (L) 2528
Resin Net (with Mold Resistant)
39
46
47
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D20O. D26
I. D20O. D26
I. D20O. D26
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039102

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. 2 AFR (Air flow rafe) is shown at 220V (380V)240V (415V).
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
(3)

18

SkyAir LU Series Cooling Only

ED21-301A

4.2

Specifications

50Hz (Complied with Australian Standard)

FHC (Ceiling Mounted Cassette Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)

Indoor Unit
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Air Filter
Weight

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FHC35KVE
R35GV1A
3.43
11,700
2,950
FHC35KVE
230840840

FHC50KVE
FHC60KVE
R50GAV1A
R60GAV1A
5.3
6.4
18,100
21,800
4,560
5,500
FHC50KVE
FHC60KVE
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H) 16 (L) 12
(H) 17 (L) 13
(H) 21 (L) 16
24
24
24
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D25O. D32
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 4, 5)
BRC7C613W
BYC125KW1
BYC125KW1
BYC125KW1
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R35GV1A
R50GAV1A
R60GAV1A
Ivory White
540750270
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2222.0
2282.0
0.372
0.372
0.465
RC46AV1TRT
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.1
1.7
2.2
PZ380
PZ380
PZ430
Propeller
27
45
53
29
28
41
37
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
1000
Capillary Tube
25
30
30
15
15
15
R22
R22
R22
1.10 (Charged for 10m)
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.50
0.85
1.20
C : 4D010466A

1. 1 The above data are based on the following conditions.


Cooling
(1)
2.
3.
4.
5.

Piping Length

Hz, Volts

Conversion Formulae
Standard

Indoor : 27CDB, 19.0CWB


7.5m
50Hz, 240V
AS 1861
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

19

Specifications

ED21-301A

FH (Ceiling Suspended Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

FH50BVE
R50GAV1A
5.19/5.1/5.1
17,700/17,500/17,500
4,460/4,400/4,400
FH50BVE

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FH60BVE
R60GAV1A
6.6/6.5/6.5
22,760/22,200/22,200
5,690/5,600/5,600
FH60BVE

White
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
0.182
0.233
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
(H) 13 (L) 10
(H) 16 (L) 13
Resin Net (with Mold Resistant)
24
26
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D20O. D26
I. D20O. D26
BRC1C61 (Note. 4)
BRC7E66
R50GAV1A
R60GAV1A
Ivory White
540750270
685800300
Cross Fin Coil (HL Fins and HiXA Tubes)
2222.0
2282.0
0.372
0.465
RC70AV1TRT
NH41VMDT
Hermetically Sealed Rotary Type
1.7
2.2
PZ380
PZ430
Propeller
45
53
28
41
42
61
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
Capillary Tube
30
30
15
15
R22
R22
1.20 (Charged for 10m)
1.50 (Charged for 5m)
Refer to the name plate of compressor.
0.85
1.20
4D028448

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220V

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220V

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

: 27CDB, 19.0CWB
(3) Indoor
7.5m
50Hz, 240V
AS 1861
Outdoor : 35CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

20

SkyAir LU Series Cooling Only

ED21-301A

4.3

Specifications

60Hz

FHC (Ceiling Mounted Cassette Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Air Filter
Weight

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FHC50KVE
FHC60KVE
R50GVAL
R60GVAL
5.64/5.6
6.84/6.8
19,300/19,100
23,400/23,200
4,850/4,820
5,880/5,850
FHC50KVE
FHC60KVE
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
0.331
0.331
QTS45B14M
QTS45B14M
Turbo Fan
45
45
(H)15 (L)11
(H)19 (L)14
24
24
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D25O. D32
I. D25O. D32
BRC1C61 (Note. 4, 5)
BRC7C613W
BYC125KW1
BYC125KW1
White
40950950
40950950
Resin Net (with Mold Resistant)
5
5
R50GVAL
R60GVAL
Ivory White
540750270
685800300
Cross Fin Coil (FL Fins and HiXA Tubes)
2222.0
2282.0
0.372
0.465
RC60VHTNRT
RC75VHTR2T
Hermetically Sealed Rotary Type
1.5
1.8
PZ380
PZ430
Propeller
45
53
30
44
41
51
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
Capillary Tube
30
30
15
15
R22
R22
1.15 (Charged for 10m)
1.60 (Charged for 5m)
Refer to the name plate of compressor.
0.85
1.00
4D006550A

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


5m
60Hz, 220V
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

21

Specifications

ED21-301A

FHYC (Ceiling Mounted Cassette Type)


Model

Indoor Unit
Outdoor Unit

VAL
TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)

Indoor Unit
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)
Decoration
Panel
(Option)

Comp.

Fan

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm

Wired
Wireless

Model
Color
Dimensions (HWD)
Air Filter
Weight

Outdoor Unit

Color
Dimensions
Coil

mm

HWD
Type
RowStagesFin Pitch
Face Area
Model

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm
kg
VAL
TAL
YAL
mm

m
VAL
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

m
m
kg
L

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.
6.

22

FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE
R71LUVAL
R100LUVAL

R125LUTAL
R140LUTAL

R125LUYAL
R140LUYAL
8.3/8.1
11.6/11.4
14.5/14.3
16.1/15.8
28,200/27,800
39,700/38,900
49,600/48,800
55,000/53,900
7,100/7,000
10,000/9,800
12,500/12,300
13,800/13,500
FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE
230840840
288840840
288840840
288840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
Cross Fin Coil
281.5
2121.5
2121.5
2121.5
0.331
0.497
0.497
0.497
QTS45B14M
QTS45A17M
QTS45A17M
QTS45A17M
Turbo Fan
45
90
90
90
(H)19 (L)14
(H)28 (L)21
(H)33 (L)24
(H)35 (L)26
24
28
28
28
9 .5 (Flare)
9 .5 (Flare)
9 .5 (Flare)
9 .5 (Flare)
15.9 (Flare)
1 9.1 (Flare)
1 9.1 (Flare)
1 9.1 (Flare)
I. D 2 5O. D 32
I. D 25O. D 32
I. D 2 5O. D 32
I. D 2 5O. D 32
BRC1C61 (Note. 5, 6)
BRC7C613W
BYC125KW1
BYC125KW1
BYC125KW1
BYC125KW1
White
40950950
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
5
R71LUVAL
R100LUVAL

R125LUTAL
R140LUTAL

R125LUYAL
R140LUYAL
Ivory
770900320
1,170900320
1,170900320
1,345900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
2602.0
0.634
0.983
0.983
1.134
ZR36K3PFV
ZR47K3PFV

JT170BC
JT170BC

JT170BCYH
JT170BCYE
Hermetically Sealed Scroll Type
2.24
2.92
3.75
4.50
P47L11S
P47L11S
P47L11S2
P47L11S2
Propeller
75
100
95+75
65+90
49
59
94
97109 2
75
92
98
109
9 .5 (Flare)
9 .5 (Flare)
9 .5 (Flare)
9 .5 (Flare)
15.9 (Flare)
1 9.1 (Flare)
1 9.1 (Flare)
1 9.1 (Flare)
2 6.0 (Hole)
2 6.0 (Hole)
2 6.0 (Hole)
2 6.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125 140>. Low Pressure
Switch. Over Current Decive. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (TAL YAL). Fuse.
1000
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
30
30
R22
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
4.1 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
1.6
4D039107
4D040213

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


60Hz, 220V
7.5m
JIS B8616
Outdoor : 35CDB, 24CWB
(380V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rafe) is shown at 220V (380V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FH (Ceiling Suspended Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

FH50BVE
R50GVAL
5.3/5.25/4.5
18,240/18,000/15,400
4,560/4,500/3,900
FH50BVE

mm

kW

W
m/min
kg
mm
mm
mm
%
m
m
kg
L

FH60BVE
R60GVAL
6.6/6.5/5.6
22,760/22,200/19,100
5,690/5,600/4,800
FH60BVE

White
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
0.182
0.233
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
(H)13 (L)10
(H)16 (L)13
Resin Net (with Mold Resistant)
24
26
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
I. D20O. D26
I. D20O. D26
BRC1C61 (Note. 4)
BRC7E66
R50GVAL
R60GVAL
Ivory White
540750270
685800300
Cross Fin Coil (FL Fins and HiXA Tubes)
2222.0
2282.0
0.372
0.465
RC60VHTNRT
RC75VHTR2T
Hermetically Sealed Rotary Type
1.5
1.8
PZ380
PZ430
Propeller
45
53
30
44
41
51
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. Internal Protector of Compressor. Fuse.
1000
1000
Capillary Tube
30
30
15
15
R22
R22
1.15 (Charged for 10m)
1.60 (Charged for 5m)
Refer to the name plate of compressor.
0.85
1.00
4D028441

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

: 29CDB, 19.0CWB
(3) Indoor
7.5m
60Hz, 220V
SSA 385/386
Outdoor : 46CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

23

Specifications

ED21-301A

FHY (Ceiling Suspended Type)


Model

Indoor Unit
Outdoor Unit

VAL
TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)

Indoor Unit
Color
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

Comp.

Fan

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit

Color
Dimensions
Coil

mm

VAL
TAL
YAL
HWD
Type
RowStagesFin Pitch
Face Area
Model

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

m
VAL
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHY71BVE
R71LUVAL

8.3/8.1
28,200/27,800
7,100/7,000
FHY71BVE

FHY100BVE
FHY125BVE
R100LUVAL

R125LUTAL

R125LUYAL
11.6/11.4
14.5/14.3
39,700/38,900
49,600/48,800
10,000/9,800
12,500/12,300
FHY100BVE
FHY125BVE
White
1951,160680
1951,400680
1951,590680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.293
0.341
4D12K1AA1
3D12K2AA1
4D12K2AA1
Sirocco Fan
62
130
130
(H)17 (L)14
(H)24 (L)20
(H)30 (L)25
Resin Net (with Mold Resistant)
32
35
27
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D20O. D26
I. D20O. D26
I. D20O. D26
BRC1C61 (Note. 4)
BRC7E66
R71LUVAL
R100LUVAL

R125LUTAL

R125LUYAL
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFV
ZR47K3PFV

JT160BC

JT160BCYH
Hermetically Sealed Scroll Type
2.24
2.92
3.75
P47L11S
P47L11S
P47L11S2
Propeller
75
100
95+75
49
59
94
75
92
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (TAL YAL). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039110

1. 1 The above data are based on the following conditions.

(1)

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


60Hz, 220V
7.5m
JIS B8616
Outdoor : 35CDB, 24CWB
(380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
4. Wire for remote controller : Field supplied.
(2)

24

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FAY (Wall Mounted Type)


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)

Indoor Unit
Color
Dimensions
Coil

Fan

kW
Btu/h
kcal/h

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Air Filter
Weight
Piping
Connections

Liquid
Gas
Drain
Remote Controller
(Option)

mm

W
m/min
kg
mm
mm
mm

Wired
Wireless

Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

FAY71LVE
R71LUVAL
8.3/8.1
28,200/27,800
7,100/7,000
FAY71LVE

mm

kW

W
m/min
kg
mm
mm
mm

%
m
m
kg
L

FAY100FAVE
R100LUVAL
11.6/11.4
39,700/38,900
10,000/9,800
FAY100FAVE

White
2901,050230
3601,570200
Cross Fin Coil (Multi Louver Fins and HiXA Tubes)
2161.4
2121.4
0.289
0.332
QCL9686M
QCL1163MA+QCL1163MB
Cross Flow Fan
43
46
(H) 1919 (L) 1515
(H) 23 (L) 19
Resin Net (Washable)
Resin Net (with Mold Resistant)
13
26
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
I. D20O. D26
I. D13O. D18
BRC1C61 (Note. 4, 5)
BRC7E619
BRC7C611W
R71LUVAL
R100LUVAL
Ivory
770900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
0.634
0.983
ZR36K3PFV
ZR47K3PFV
Hermetically Sealed Scroll Type
2.24
2.92
P47L11S
P47L11S
Propeller
75
100
49
59
75
92
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. Low Pressure Switch. Over Current Device. Motor
Protector (Compressor). Fuse.
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
4D041586
4D039114

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


7.5m
60Hz, 220V
JIS B8616
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

25

Specifications

ED21-301A

FVY (Floor Standing Type)


Model

Indoor Unit
Outdoor Unit

VAL
TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)

Indoor Unit
Color
Dimensions
Coil

Fan

Air Filter
Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Comp.

Fan

Weight
Piping
Connections

W
m/min
kg
mm
mm
mm
VAL
TAL
YAL

Liquid
Gas
Drain

Outdoor Unit

Color
Dimensions
Coil

mm

HWD
Type
RowStagesFin Pitch
Face Area
Model

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

m
VAL
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FVY71LAVE
R71LUVAL

8.3/8.1
28,200/27,800
7,100/7,000
FVY71LAVE

FVY100LAVE
FVY125LAVE
R100LUVAL

R125LUTAL

R125LUYAL
11.6/11.4
14.5/14.3
39,700/38,900
49,600/48,800
10,000/9,800
12,500/12,300
FVY100LAVE
FVY125LAVE
White
1,850600270
1,850600350
1,850600350
Cross Fin Coil
2401.75
2441.75
(3221.75)2
0.40
0.44
0.44 (0.222)
QS37A1AM
QS37A2AM
QS37A2AM
Sirroco Fan
30
60
90
(H) 18 (L) 14
(H) 28 (L) 22
(H) 32 (L) 25
Resin Net (with Mold Resistant)
39
46
47
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I. D20O. D26
I. D20O. D26
I. D20O. D26
R71LUVAL
R100LUVAL

R125LUTAL

R125LUYAL
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFV
ZR47K3PFV

JT160BC

JT160BCYH
Hermetically Sealed Scroll Type
2.24
2.92
3.75
P47L11S
P47L11S
P47L11S2
Propeller
75
100
95+75
49
59
94
75
92
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (TAL YAL). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039113

1. 1 The above data are based on the following conditions.

(1)

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


60Hz, 220V
7.5m
JIS B8616
Outdoor : 35CDB, 24CWB
(380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed.
(2)

26

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

5. Dimensions and Service Space


5.1

Indoor Unit

5.1.1

FH(Y)C (Ceiling Mounted Cassette Type)

FHC35K + BYC125KW1
C
860~890 Ceiling opening

80

2 100=200

Unit (mm)

85

950

(165)

300 or less 680 Suspension position


420

Branch duct
connection

350
C

view
60

4-M4 Hole
(prepared hole)
7

80
80

40

860~890 Ceiling opening

950

780 Suspension position

10

55

55

55

840

80 2 100=200

12-M4 Hole
(prepared hole)

85

150

40
350

Branch duct
connection

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required space is
200mm or more.

1000 or more
Required space

30

260
270
315

165

95
110

295

For fresh air intake kit


connection
(direct installation type)

view

55

840

125
150
240

750

Adjustable (0~550)

200

10

240

Suspension
bolt
4-M8~M10

420

Note 3

40

230

view

160

7
A

Name
Number
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will


be a signal receiver. Refer to the drawing of wireless remote
controller in detail.

2. When installing an optional accessory, refer to the


installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.

5
6
7
8

Description
6.4 flare
12.7 flare
VP25

Remote control code and control


wiring connection

Air discharge grille

Air suction grille


Port for water supply
9 Corner decoration cover
10 Drain hose

O.D.32

C : 3D012310B

FHC50K + BYC125KW1
FHC60K + BYC125KW1
Unit (mm)

C
80

950

2 100=200 85
(165)

860~890 Ceiling opening


300 or less 680 Suspension position
420

9
10

Branch duct
connection

C view
60

4-M4 Hole
(prepared hole)
7

80

80

950

780 Suspension position


860~890 Ceiling opening

40
350

55

840

55

840
80

12-M4 Hole
(prepared hole)

260
270
315

40
350

Branch duct
connection

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.
2. When installing an optional accessory, refer to the
installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

SkyAir LU Series Cooling Only

165
1000 or more
Required space

125
150
240
240

For fresh air intake kit


connection
(direct installation type)

55

2100=200 85

95
110

295

150

750
Adjustable (0~550)

55

200

230

B view

40

10

30
Suspension
bolt
4-M8~M10

420

Note 3

160

7
A view

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required space is
200mm or more.
Name
Number
1
Liquid pipe connection
Gas
pipe
connection
2
Drain pipe connection
3
Power supply connection
4

3. In case of using wireless remote controller, this position will


be signal receiver. Refer to the drawing of wireless remote
controller in detail.

Remote control code and control


wiring connection

4. When the temperature and humidity in the ceiling exceed 30C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.

Air discharge grille


Air suction grille
Port for water supply
Corner decoration cover

7
9
10

Drain hose

Description
6.4 flare
15.9 flare
VP25

O.D.32

C : 3D012311B

27

Dimensions and Service Space

ED21-301A

FHYC71K + BYC125KW1
Unit (mm)

1000 or more

Note 3

4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or
the fresh air is inducted into the ceiling or the unit continues 24 hour operation,
an additional insulation (thickness 10mm or more of glasswool or polyethylene
form) is required.

C : 3D012312C

FHYC100K + BYC125KW1
FHYC125K + BYC125KW1
FHYC140K + BYC125KW1
Unit (mm)

950

2 100=200 85
(195)

80

860~890 Ceiling opening


300 or less 680 Suspension position

165

40
350

Branch duct
connection

C view
60

4-M4 Hole
(prepared hole)
7
5

80
80

950

780 Suspension position


860~890 Ceiling opening

10

155

420

160

7
A view

420

Note 3

260
270
315

14-M4 Hole
(prepared hole)

2 100=200 85

195

150

125
150
298
240

55

840
80

200

30
Suspension
bolt
4-M8~M10

55

40
50
155
165

55

840
295

40
350

Branch duct
connection

1000 or more
Required space

55

40

10

288

750
Adjustable (0~550)

B view

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will


be signal receiver. Refer to the drawing of wireless remote
controller in detail.

2. When installing an optional accessory, refer to the


installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30C


and RH 80% or the fresh air is inducted into the ceiling or the unit
continues 24 hour operation, an additional insulation (thickness
10mm or more of glasswool or polyethylene form) is required.

For fresh air intake kit


connection
(direct installation type)

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required is space
200mm or more.
Number
Name
1
Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection
5
6
7
8
9
10

Description
9.5 flare
19.1 flare
VP25

Remote control code and control


wiring connection

Air discharge grille


Air suction grille
Port for water supply
Corner decoration cover
Drain hose

O.D.32

C : 3D012313C

28

SkyAir LU Series Cooling Only

ED21-301A

5.1.2

Dimensions and Service Space

FH(Y)C with HighEfficiency Filter

KAFP556D80 557D80 for FH(Y)C35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
JC : 3D032975C

KAFP556D160 557D160 for FHYC100~140K

Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
J : 3D032976C

SkyAir LU Series Cooling Only

29

Dimensions and Service Space

5.1.3

ED21-301A

FH(Y)C with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FH(Y)C35~71K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)

Refrigerant
Piping

Note 4

View
Service Access Panel :
450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


Note:1.When installing this kit, Service Access Panel is necessary.
(It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

How to connect Chamber 4


Independently(Refer to Note 5,6)

Connection chamber(Left)
Connection chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

5
4
3
2
1
Number

JC : 3D032981D

KDDP55D160 for FHYC100~140K

Unit (mm)

Service Access Panel :


450450mm or more
Refer to Note 2

Refrigerant
Piping

Note 4

View

Service Access Panel :


450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is
necessary. (It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name
JC : 3D032984D

30

SkyAir LU Series Cooling Only

ED21-301A

5.1.4

Dimensions and Service Space

FH(Y)C with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

KDDP55D160K for FH(Y)C35~71K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

Service Access Panel :


450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel

T Joint
Plate Band (Accessory)

(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

JC : 3D032987D

KDDP55D160K for FHYC100~140K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

Service Access Panel :


450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel


Plate Band (Accessory)

T Joint
(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

J : 3D032990D

SkyAir LU Series Cooling Only

31

Dimensions and Service Space

5.1.5

ED21-301A

FH(Y)C with Panel Spacer

KDBP55H160WA for FH(Y)C35~71K


Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Description
JC : 3D005390E

KDBP55H160WA for FHYC100~140K


Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Description
JC : 3D005391D

32

SkyAir LU Series Cooling Only

ED21-301A

5.1.6

Dimensions and Service Space

FH(Y)K (Ceiling Mounted Cassette Corner Type)

FHK35F + BYK45FJW1
FHK45F + BYK45FJW1
Unit (mm)
Model

FHK35F

FHK45F

6.4

6.4

12.7

15.9

3D027409

FHK60F + BYK71FJW1
FHYK71FJ + BYK71FJW1
Unit (mm)
Model

FHK60F

FHYK71FJ

6.4

9.5

15.9

15.9

3D027408

SkyAir LU Series Cooling Only

33

Dimensions and Service Space

5.1.7

ED21-301A

FH(Y)B (Ceiling Mounted BuiltIn Type)

FHB35F + BYBS45DJW1
Without Canvas Duct
FHB45F + BYBS45DJW1
25

57

485

5
Model
195

67
150
200

300
245
215
150
135
10

3150=450

440
315

45

Suspension bolt

FH(Y)B35F

FH(Y)B45F

12.7

15.9

350 or more
(Required space)

50
65

The required ceiling depth varies according to


configuration of specific system

135 120

460

Unit (mm)

800
595 (Air suction panel center)

60

265=130

700

300 or more
45

Service space

12-7

46

460
Suction air intake position when
installing the duct

650

150
215
245
150
250
300

500

228

160

462 (Ceiling opening)

628

3150=450
485

4150=600

760 (Ceiling opening)

700

14-M5 Hole

800

D View

B View
160 P. C. D
125
(Knockout hole)

600
Fresh air intake Position

100

630 (Suspension position) 145

665=390

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

6-M5 Hole
(Circumference liner)

1. Liquid pipe connection 6.4Flare


2. Gas pipe connection Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

C View

750 (Suspension position)


A View

JC : DU224-247

FHB35F + BYBS45DJW1
With Canvas Duct
FHB45F + BYBS45DJW1
60
50

25

135 120

265=130

67
150
200

45

46

300 or more

FH(Y)B35F

Suction air intake position


when instaling the duct.

150
250
300

228

500

160

628
462 (Ceiling opening)

15.9

12.7
460

650

3150=450
485

4150=600
700

760 (Ceiling opening)

D View

14-M5 hole

800

B View
160 P. C. D

665=390

125
(Knockout hole)

600
Fresh air intake position

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

100

630 (Suspension position) 145

FH(Y)B45F

12-7

Service space

10

Model

150
215
245

195

440
315

The required ceiling depth varies according to


configuration of specific system

465 or more
Required
installation
space

Suspension bolt

57

Unit (mm)

800
595 (Air suction panel center)

45
115~255

300
245
215
150
135

700
485
460
3150=450
65

6-M5 hole
(Circumference liner)

7
750 (Suspension position)

View

1. Liquid pipe connection 6.4 Flare


2. Gas pipe connection
Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

View

JC : DU224-248

34

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

FHB60F + BYBS71DJW1
Without Canvas Duct
FHYB71F + BYBS71DJW1
Unit (mm)

45

(Reqjired space)

195

350 or more

FHYB71F

6.4

9.5
16-7
760

FH(Y)B60F

46

150
215
245

57

Model

135 120

150
200

300 or more
Survice space

Suction air intake position when


installing the duct
5150=750
785

View

150
250
300

160

500

462 (Ceiling opening)

950
927

228

10

5150=750
785

440
315

1
265=130

Suspension bolt

45

60
50

67

1000
760
65

300
245
215
150
135

The required ceiling depth varies according to


configuration of specific system

800
595 (Air suction panel center)

25

1060 (Ceiling opening)

6150=900

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

1000

1100
18-M5 Hole

View

160 P. C. D

1165=715

600
fresh air intake position

1. Liquid pipe connection Flare


2. Gas pipe connection 15.9 Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

100

630 (Suspension position) 145

125
(Knockout hole)

6-M5 Hole
(Circumference Liner)

View

1050 (Suspension position)

JC : DU226-256

View

FHB60F + BYBS71DJW1
With Canvas Duct
FHYB71F + BYBS71DJW1
60
50

25

Model
195

135 120

150
200

300
245
215
150
135
45
115~255

B
57

45

46

300 or more

FH(Y)B60F

FHYB71F

6.4

9.5

16-7
760

10

Service space

950

Suction air intake position


when instaling the duct.

1000
18-M5 hole

1100

B
160 P. C. D
125
(Knockout hole)

View

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

1. Liquid pipe connection


Flare
2. Gas pipe connection 15.9 Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

6-M5 hole
(Circumference liner)

SkyAir LU Series Cooling Only

View

600
Fresh air intake position

100

630 (Suspension position) 145

1165=715

View

6150=900

1060 (Ceiling opening)

5150=750
785

150
250
300

160

228

500

462 (Ceiling opening)

927

1050 (Suspension position)

150
215
245

The required ceiling depth varies according to


configuration of specific system

315
Suspension bolt

67

65

265=130

Unit (mm)

800
595 (Air suction panel center)
440

760
5150=750

465 or more
Required
installation
space

1000
785

View

JC : DU226-257

35

Dimensions and Service Space

ED21-301A

FHYB100F + BYBS125DJW1
Without Canvas Duct
FHYB125F + BYBS125DJW1
Unit (mm)

10

7150=1050
1185

45

150
215
245
7150=1050
1185

300 or more
Survice space

195

135 120

20-7
1160

(Reqjired space)

265=130

150
200

57

440
315

350 or more

Suspension bolt
4-M8~M10

45

60
50

67

1400
1160
65

300
245
215
150
135

The required ceiling depth varies according to


configuration of specific system

800
595 (Air suction panel center)

25

46

View

462 (Ceiling opening)

Suction air intake position


when instaling the duct.

150
250
300

228

160

500

1328

1460 (Ceiling opening)

9150=1350

1500

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

1400
24-M5 hole

View

160 P. C. D

1665=1040

600
Fresh air intake position

1. Liquid pipe connection 9.5 Flare


2. Gas pipe connection 19.1 Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

100

630 (Suspension position) 145

125
(Knockout hole)

6-M5 Hole
(Circumference Liner)

View

1450 (Suspension position)

View

JC : DU228-237

FHYB100F + BYBS125DJW1
With Canvas Duct
FHYB125F + BYBS125DJW1
25

20-7

195

5
135 120

150
200

300
245
215
150
135

315
Suspension bolt
4-M8~M10
67

65

The required ceiling depth varies according to


configuration of specific system

440

265=130

Unit (mm)

800
595 (Air suction panel center)

45
115~255

B
57

45

46

300 or more

1160

150
215
245

60
50

1160
7150=1050

465 or more
Required
installation
space

1400
1185

7150=1050
1185

10

Service space
Suction air intake position
when instaling the duct.

View

9150=1350
1400

1460 (Ceiling opening)

24-M5 hole

1500

B
160 P. C. D
125
(Knockout hole)

1665=1040

View

1. Liquid pipe connection 9.5 Flare


2. Gas pipe connection 19.1 Flare
3. Drain pipe connection VP25
4. Wire intake for remote control cord
5. Wire intake
6. Drain hole
VP25
7. Air filter
8. Air discharge Flange

6-M5 hole
(Circumference)

7
1450 (Suspension position)

Note;
1. Location of unit's Name Plate:Fan housing surface
inside of filter.
2. When installing an optional accessory, refer to the
Option Handbook.

600
Fresh air intake position

100

630 (Suspension position) 145

150
250
300

160

228

500

462 (Ceiling opening)

1328

View

View

JC : DU228-238

36

SkyAir LU Series Cooling Only

ED21-301A

5.1.8

Dimensions and Service Space

FUY (New Ceiling Suspended Cassette Type)

FUY71FJ
Unit (mm)

3D013860C

FUY100FJ
FUY125FJ
Unit (mm)

3D013859A

SkyAir LU Series Cooling Only

37

Dimensions and Service Space

5.1.9

ED21-301A

FH(Y) (Ceiling Suspended Type)

FH35B
FH50B
Unit (mm)

Model

FH(Y)35B FH(Y)50B

12.7

15.9

3D027536C
3D028600

FH60B
FHY71B
Unit (mm)

38

Model

FH(Y)60B

FHY71B

6.4

9.5

3D027537
3D027538D

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

FHY100B
Unit (mm)

3D027539B

FHY125B
Unit (mm)

3D027540

SkyAir LU Series Cooling Only

39

Dimensions and Service Space

ED21-301A

5.1.10 FAY (Wall Mounted Type)


FAY71L
Unit (mm)

3D038540B

FAY100FA
Unit (mm)

3D014381A

40

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

5.1.11 FVY (Floor Standing Type)

FVY71LA
Unit (mm)

3D031617

FVY100LA
FVY125LA
Unit (mm)

3D031618

SkyAir LU Series Cooling Only

41

Dimensions and Service Space

5.2

ED21-301A

Remote Controller

BRC7C613W (Wireless Type for FH(Y)CK)


Unit (mm)

3D005912B

BRC7C529W (Wireless Type for FUYFJ)


Unit (mm)

3D014035

42

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

BRC7E619 (Wireless Type for FAY71L)


Unit (mm)

FAY71

C : 3D034905

BRC7C611W (Wireless Type for FAY100FA)


Unit (mm)

3D010766A

SkyAir LU Series Cooling Only

43

Dimensions and Service Space

ED21-301A

BRC7E66 (Wireless Type for FH(Y)B)


Unit (mm)

3D028963

BRC1C61 (Wired Type)

More comfortable operation by


thermo sensor in the Remote Controller
Applicable Model
FH(Y)B
FH(Y)KF(J)
FH(Y)CK
FH(Y)BF
FUYFJ
FV(Y)LA (Available for 2 remote control use)
FAYFA/L

Unit (mm)

C : 3D028952

44

SkyAir LU Series Cooling Only

ED21-301A

5.3

Dimensions and Service Space

Outdoor Unit

R35G
Unit (mm)

3D006245E

R50G
R50GA
Unit (mm)

3D004855E

SkyAir LU Series Cooling Only

45

Dimensions and Service Space

ED21-301A

R60G
R60GA
Unit (mm)

3D004856H

R71LU
Unit (mm)

3D039213

46

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

R100LU
Unit (mm)

3D039214

R125LU
Unit (mm)

3D039215

SkyAir LU Series Cooling Only

47

Dimensions and Service Space

ED21-301A

R140LU
Unit (mm)

3D039216

48

SkyAir LU Series Cooling Only

ED21-301A

5.4

Dimensions and Service Space

Installation Service Space for R71~140LU

3D039172-1

SkyAir LU Series Cooling Only

49

Dimensions and Service Space

ED21-301A

3D039172-2

50

SkyAir LU Series Cooling Only

ED21-301A

Piping Diagrams

6. Piping Diagrams
6.1

Pair

R35G
R50G / R50GA
R60G / R60GA

6.4

(SEE NOTE)

NOTE :
1. GAS PIPE SPECIFICATION
R35
12.7 CuT
R50, R60 15.9 CuT

C : 4D028567
C : DW521-856K
C : 4D000695E

R71LU

3D039739

SkyAir LU Series Cooling Only

51

Piping Diagrams

ED21-301A

R100LU

3D039740

R125LU

3D039741

52

SkyAir LU Series Cooling Only

ED21-301A

Piping Diagrams

R140LU

3D039742

SkyAir LU Series Cooling Only

53

Wiring Diagrams

ED21-301A

7. Wiring Diagrams
7.1

Indoor Unit

FHC35KVE
FHC50KVE
FHC60KVE

3D005749A

54

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FHYC71KVE
FHYC100KVE
FHYC125KVE
FHYC140KVE

3D005668D

SkyAir LU Series Cooling Only

55

Wiring Diagrams

ED21-301A

FHK35FV1
FHK45FV1
FHK60FV1

DU423-5176B

56

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FHYK71FJV1

DU423-5174A

SkyAir LU Series Cooling Only

57

Wiring Diagrams

ED21-301A

FHB35FV1
FHB45FV1
FHB60FV1

DU423-5175B

58

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FHYB71FV1

DU423-5173B

SkyAir LU Series Cooling Only

59

Wiring Diagrams

ED21-301A

FHYB100FV1
FHYB125FV1

DU428-5353B

60

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FUY71FJV1
FUY100FJV1
FUY125FJV1

3D013404B

SkyAir LU Series Cooling Only

61

Wiring Diagrams

ED21-301A

FH35BVE
FH50BVE
FH60BVE

3D027501

62

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FHY71BVE
FHY100BVE
FHY125BVE

3D027502

SkyAir LU Series Cooling Only

63

Wiring Diagrams

ED21-301A

FAY71LVE

3D037717B

64

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FAY100FAVE

DU427-5410E

SkyAir LU Series Cooling Only

65

Wiring Diagrams

ED21-301A

FVY71LAVE
FVY100LAVE
FVY125LAVE

3D013540B

66

SkyAir LU Series Cooling Only

ED21-301A

7.2

Outdoor Unit

7.2.1

50Hz

Wiring Diagrams

R35GV1
R35GV1A

R50GV1

3D005285A

SkyAir LU Series Cooling Only

67

Wiring Diagrams

ED21-301A

R50GAV1A

3D028077

R60GV1

3D004030A

68

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

R60GAV1A

3D028078

R71LUV1
R100LUV1

3D037640C

SkyAir LU Series Cooling Only

69

Wiring Diagrams

ED21-301A

R71LUY1
R100LUY1

3D037642C

R125LUY1
R140LUY1

3D037644C

70

SkyAir LU Series Cooling Only

ED21-301A

7.2.2

Wiring Diagrams

60Hz

R50GVAL

3D005285A

R60GVAL

3D005750

SkyAir LU Series Cooling Only

71

Wiring Diagrams

ED21-301A

R71LUVAL
R100LUVAL

3D037935C

R125LUTAL
R140LUTAL

3D037936C

72

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

R125LUYAL
R140LUYAL

3D037937C

SkyAir LU Series Cooling Only

73

Capacity Tables

ED21-301A

8. Capacity Tables
8.1

50Hz (General)

FHC35KVE + R35GV1

3D006618

FHK35FV1 / FHB35FV1 / FH35BVE + R35GV1

3D006627A

74

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

FHC50KVE + R50GV1

C : 3D006616

FHK45FV1 / FHB45FV1 / FH50BVE + R50GV1

3D006621A

SkyAir LU Series Cooling Only

75

Capacity Tables

ED21-301A

FHC60KVE + R60GV1

3D006615

FHK60FV1 / FHB60FV1 / FH60BVE + R60GV1

C : 3D006625B

76

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUV1


FHYC71KVE / FHYK71FJV1 / FHYB71FV1 / FUY71FJV1 / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUY1

3D039613A

FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUV1


FHYC100KVE / FHYB100FV1 / FUY100FJV1 / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUY1

3D039626A

SkyAir LU Series Cooling Only

77

Capacity Tables

ED21-301A

FHYC125KVE / FHYB125FV1 / FUY125FJV1 / FHY125BVE / FVY125LAVE + R125LUY1

3D039635

FHYC140KVE + R140LUY1

3D039644

78

SkyAir LU Series Cooling Only

ED21-301A

8.2

Capacity Tables

50Hz (Complied with Australian Standard)

FHC35KVE + R35GV1A

C : 3D006618

220V

240V
14

16

220V : 5m
240V : 7.5m

C : 3D011149

FHC50KVE + R50GAV1A

C : 3D006616

220V

240V
15
0.18

17
0.18

220V : 5m
240V : 7.5m

C : 3D011150

SkyAir LU Series Cooling Only

79

Capacity Tables

ED21-301A

FH50BVE + R50GAV1A

C : 3D006621A

220V : 5m
240V : 7.5m

C : 3D011053A

FHC60KVE + R60GAV1A

C : 3D006615

220V

240V
19

21

220V : 5m
240V : 7.5m

C : 3D011151

80

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

FH60BVE + R60GAV1A

C : 3D006625B

220V : 5m
240V : 7.5m

C : 3D011054A

SkyAir LU Series Cooling Only

81

Capacity Tables

8.3

ED21-301A

60Hz

FHC50KVE + R50GVAL

3D006814

FH50BVE + R50GVAL

3D006619A

82

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

FHC60KVE + R60GVAL

3D006825

FH60BVE + R60GVAL

3D006620A

SkyAir LU Series Cooling Only

83

Capacity Tables

ED21-301A

FHYC71KVE / FHY71BVE / FAY71LVE / FVY71LAVE + R71LUVAL

3D039615A

FHYC100KVE / FHY100BVE / FAY100FAVE / FVY100LAVE + R100LUVAL

3D039628

84

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUTAL

3D039637

FHYC125KVE / FHY125BVE / FVY125LAVE + R125LUYAL

3D039638

SkyAir LU Series Cooling Only

85

Capacity Tables

ED21-301A

FHYC140KVE + R140LUTAL

3D039648

FHYC140KVE + R140LUYAL

3D039652

86

SkyAir LU Series Cooling Only

ED21-301A

8.4

Capacity Tables

Capacity Correction Factor by the Length of Refrigerant Piping

The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
Reference Data
1. In case of piping length 5m (35~140)

Cooling capacity correction factor

100

95
35455060
90

85

100
71
125

80
140
75

10

15
20
25
30
35
Length of refrigerant piping (Total length)

40

45

50 (m)
C : 3D006500C

2. In case of piping length 7.5m (71~140)

Cooling capacity correction factor

100

95

90

85

100
71
125

80

140

75

Note:

7.5 10

20
25
30
35
15
Length of refrigerant piping (Total length)

40

45

50 (m)

1.
line: Correction factor for cooling capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the
range of its limitation.

SkyAir LU Series Cooling Only

87

Operation Limits

ED21-301A

9. Operation Limits
9.1

Operation Limits

R35GV1 / R35GV1A
R50GAV1A
R60GV1 / R60GAV1A

R50GV1
R50GVAL
R60GVAL

4D006229C

R71LUV1 / R71LUY1 / R71LUVAL


R100LUV1 / R100LUY1 / R100LUVAL
R125LUY1 / R125LUTAL / R125LUYAL
R140LUY1 / R140LUTAL / R140LUYAL

3D039657

88

SkyAir LU Series Cooling Only

ED21-301A

Sound Level

10. Sound Level


10.1

Overall Sound Level


dB(A)
Model

50Hz

60Hz

220V

240V

Measuring Location

220V

FHC35K
FHC50K
FHC60K
FHYC71K
FHYC100K
FHYC125K
FHYC140K

33
33
35
35
39
42
44

29
29
30
30
34
36
37

35
35
37
37
41
44
46

31
31
32
32
36
38
39

33
35
35
39
42
44

29
30
30
34
36
37

FH(Y)C

FHK35F
FHK45F
FHK60F
FHYK71FJ

39
39
41
41

33
34
36
36

41
41
43
43

35
36
38
38

FH(Y)K

FHB35F
FHB45F
FHB60F
FHYB71F
FHYB100F
FHYB125F

38
39
41
41
41
44

32
34
35
35
35
38

40
41
43
43
43
46

34
36
37
37
37
40

FH(Y)B

FUY71FJ
FUY100FJ
FUY125FJ

40
43
44

35
38
39

42
45
46

37
40
41

FUY

4D013951

Microphone

FH35B
FH50B
FH60B
FHY71B
FHY100B
FHY125B

37
38
38
39
42
44

32
33
33
35
37
39

37
38
38
39
42
44

32
33
33
35
37
39

38
38
39
42
44

33
33
35
37
39

FH(Y)

FAY71L
FAY100FA

43
45

37
41

43
45

37
41

43
45

37
41

FAY

FVY71LA
FVY100LA
FVY125LA

41
46
49

35
40
43

43
48
51

37
42
45

41
46
49

35
40
43

FVY

Microphone

4D013827

4D028280A

4D038512B

Microphone
4D013840B

R35G
R50G(A)
R60G(A)
R71LU
R100LU
R125LU
R140LU

48
49
54

49
50
55

52
55

220 380V

240 415V

220V

48
49

49
50

49
51

380V

415V

220 380V

49
54

50
55

51
55

R35~60

R71~140LU

Microphone

4D039813

Note:

Operation sound is measured in an anechoic chamber.

SkyAir LU Series Cooling Only

89

Sound Level

10.2

ED21-301A

Octave Band Level

10.2.1 Indoor Unit


FHC35KVE
FHC50KVE

FHC60KVE
FHYC71KVE

FHYC100KVE

H
H

H
H

H
L
L

L
L

L
4D006201B

4D006198A

FHYC125KVE

FHYC140KVE

4D006205A

FHK35FV1

NC-60

H(240V)
NC-50

H
H(220V)

NC-40

H
NC-30

L(240V)

L
L

NC-20

L(220V)

4D013951

4D006206A

FHK45FV1

FHK60FV1
FHYK71FJV1

DU423-491

FHB35FV1

H
H

H
H

H
H

DU425-4158

FHB45FV1

DU423-490

DU426-4187

FHB60FV1
FHYB71FV1

FHYB100FV1

H
H

H
H

H
H

L
L

L
L

DU425-4157

90

DU426-4186

DU428-4205

SkyAir LU Series Cooling Only

ED21-301A

Sound Level

FHYB125FV1

FUY71FJV1

FUY100FJV1

H
H

L
L

4D013827

4D013828

DU429-4172

FUY125FJV1

FH35BVE

4D028280A

4D013829

FH60BVE

FH50BVE

FHY71BVE

4D028282

FHY125BVE

4D028355A

FAY71LVE

4D028284A

SkyAir LU Series Cooling Only

4D028281A

FHY100BVE

4D028283A

FAY100FAVE

4D038512B

4D014379

91

Sound Level

ED21-301A

FVY71LAVE

FVY100LAVE

FVY125LAVE

4D013841A

4D013840B

4D013842B

10.2.2 Outdoor Unit (50Hz)


R35GV1
R35GV1A

R50GV1
R50GAV1A

R60GV1
R60GAV1A

4D000697C

R71LUV1
R71LUY1

DW527-217F

DW525-597E

R100LUV1
R100LUY1

R125LUY1

4D039802

4D039804

4D039806

Note:

R140LUY1

220V, 380V
240V, 415V

4D039808

92

SkyAir LU Series Cooling Only

ED21-301A

Sound Level

10.2.3 Outdoor Unit (60Hz)


R50GVAL

R60GVAL

DW525-587B

R100LUVAL

DW527-237A

R125LUTAL
R125LUYAL

4D039811

SkyAir LU Series Cooling Only

R71LUVAL

4D039810

R140LUTAL
R140LUYAL

4D039812

4D039813

93

Fan Performance

ED21-301A

11. Fan Performance


11.1

Fan Performance

11.1.1 Ceiling Mounted BuiltIn Type


FHB35F

FHB45F

FHB60F

FHYB71F

94

SkyAir LU Series Cooling Only

ED21-301A

Fan Performance

FHYB100F

FHYB125F

Note:

1. The remote controller can be used to switch between high and low.
2. The air flow is set to standard before leaving the factory.
It is possible to switch between standard ESP and high ESP by remote controller.
3. The internal static pressure indicates the characteristics of the fan when a suction panel (optional
accessory) and a canvas for the suction panel (optional accessory) are incorporated into the main unit
(with a longlife filter).

SkyAir LU Series Cooling Only

95

Electric Characteristics

ED21-301A

12. Electric Characteristics


12.1

50Hz
Unit Combination
Indoor
Outdoor

Hz-Volts

50-220
50-230
50-240
50-220
50-230
R35GV1
FHK35FV1
50-240
50-220
50-230
R35GV1
FHB35FV1
50-240
50-220
50-230
R35GV1
FH35BVE
50-240
50-220
FHC50KVE R50G(A)V1(A) 50-230
50-240
50-220
50-230
FHK45FV1
R50GV1
50-240
50-220
50-230
FHB45FV1
R50GV1
50-240
50-220
50-230
FH50BVE
R50GV1
50-240
50-220
FH50BVE
R50GAV1A 50-230
50-240
50-220
FHC60KVE R60G(A)V1(A) 50-230
50-240
50-220
50-230
FHK60FV1
R60GV1
50-240
50-220
50-230
FHB60FV1
R60GV1
50-240
50-220
50-230
FH60BVE
R60GV1
50-240
50-220
FH60BVE
R60GAV1A 50-230
50-240
50-220
50-230
FHYC71KVE R71LUV1
50-240
50-220
50-230
FHY71BVE R71LUV1
50-240
50-220
50-230
FHYB71FV1 R71LUV1
50-240
50-220
50-230
FHYK71FJV1 R71LUV1
50-240
50-220
50-230
FVY71LAVE R71LUV1
50-240
50-220
50-230
R71LUV1
FAY71LVE
50-240
50-220
50-230
FUY71FJV1 R71LUV1
50-240
50-380/220
50-400/230
FHYC71KVE R71LUY1
50-415/240
50-380/220
50-400/230
FHY71BVE R71LUY1
50-415/240
50-380/220
FHYB71FV1 R71LUY1
50-400/230
50-415/240
50-380/220
FHYK71FJV1 R71LUY1
50-400/230
50-415/240
50-380/220
50-400/230
FVY71LAVE R71LUY1
50-415/240
50-380/220
50-400/230
R71LUY1
FAY71LVE
50-415/240
50-380/220
50-400/230
FUY71FJV1 R71LUY1
50-415/240

FHC35KVE

Power Supply
Voltage Range MCA TOCA MFA

R35GV1(A)

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz
456/264V
Min. 50Hz
342/198V

6.9

15

7.6

15

7.9

15

8.0

15

13.5

20

11.9

20

12.4

20

12.3

20

13.5

20

14.5

25

16.3

25

16.4

25

16.3

25

14.5

25

18.3

23.2

30

20.9

23.8

30

19.3

23.5

30

18.6

23.1

30

19.1

23.3

30

18.3

23.0

30

18.5

23.2

30

7.5

8.7

15

7.7

8.7

15

7.9

9.0

15

7.5

8.6

15

7.8

8.8

15

7.3

8.5

15

7.5

8.7

15

Comp
LRA RLA
29
30
31
29
30
31
29
30
31
29
30
31
42
44
46
42
44
46
42
44
46
42
44
46
42
44
46
55
58
60
55
58
60
55
58
60
55
58
60
55
58
60
82
78
75
82
78
75
82
78
75
82
78
75
82
78
75
82
78
75
82
78
75
40
38
37
40
38
37
40
38
37
40
38
37
40
38
37
40
38
37
40
38
37

4.6
4.7
4.7
5.3
5.5
5.6
5.3
5.5
5.6
5.3
5.5
5.6
9.2
9.7
10.1
9.0
9.1
9.1
9.0
9.1
9.1
9.0
9.1
9.1
9.2
9.7
10.1
10.6
10.5
10.3
11.9
12.0
12.1
11.9
12.0
12.1
11.9
12.0
12.1
10.6
10.5
10.3
13.7
13.1
12.6
14.2
13.6
13.0
14.2
13.5
13.0
14.0
13.4
12.9
14.2
13.6
13.0
13.8
13.2
12.6
13.8
13.2
12.7
5.0
4.8
4.6
5.2
4.9
4.7
5.1
4.9
4.7
5.1
4.8
4.7
5.2
4.9
4.7
5.0
4.8
4.6
5.0
4.8
4.6

OFM
kW
FLA

kW

IFM
FLA

0.027

0.4

0.045

0.6

0.027

0.4

0.025

0.2

0.027

0.4

0.065

0.5

0.027

0.4

0.062

0.6

0.045

0.3

0.045

0.6

0.045

0.3

0.025

0.2

0.045

0.3

0.085

0.7

0.045

0.3

0.062

0.6

0.045

0.3

0.062

0.6

0.053

0.6

0.045

0.6

0.053

0.6

0.06

0.6

0.053

0.6

0.11

0.7

0.053

0.6

0.062

0.6

0.053

0.6

0.062

0.6

0.065

0.6

0.045

0.6

0.065

0.6

0.062

0.6

0.065

0.6

0.125

0.9

0.065

0.6

0.045

0.5

0.065

0.6

0.030

0.7

0.065

0.6

0.068

0.4

0.065

0.6

0.045

0.6

0.065

0.6

0.045

0.6

0.065

0.6

0.062

0.6

0.065

0.6

0.125

0.9

0.065

0.6

0.045

0.5

0.065

0.6

0.030

0.7

0.065

0.6

0.068

0.4

0.065

0.6

0.045

0.6

C : 3D006610D
3D006301A
3D039576C

96

SkyAir LU Series Cooling Only

ED21-301A

Electric Characteristics

Unit Combination
Indoor
Outdoor
FHYC100KVE R100LUV1
FHY100BVE

R100LUV1

FHYB100FV1 R100LUV1
FVY100LAVE R100LUV1
FAY100FAVE R100LUV1
FUY100FJV1 R100LUV1
FHYC100KVE R100LUY1
FHY100BVE

R100LUY1

FHYB100FV1 R100LUY1
FVY100LAVE R100LUY1
FAY100FAVE R100LUY1
FUY100FJV1 R100LUY1
FHYC125KVE R125LUY1
FHY125BVE

R125LUY1

FHYB125FV1 R125LUY1
FVY125LAVE R125LUY1
FUY125FJV1 R125LUY1
FHYC140KVE R140LUY1

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240
50-220
50-230
50-240
50-220
50-230
50-240
50-220
50-230
50-240
50-220
50-230
50-240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240

Power Supply
Voltage Range MCA TOCA MFA
24.7

27.8

40

24.1

27.5

40

24.6

27.8

40

24.7

28.1

40

23.9

27.1

40

24.6

27.8

40

10.2

11.8

15

9.9

11.5

15

Max. 50Hz
456/264V

10.2

11.8

15

Min. 50Hz
342/198V

10.5

12.1

15

9.5

11.1

15

10.2

11.8

15

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz
456/264V
Min. 50Hz
342/198V

Max. 50Hz 456/264V


Min. 50Hz 342/198V

12.4

15.3

20

12.3

15.0

20

12.5

15.7

20

12.9

15.8

20

12.3

15.3

20

13.0

17.4

25

Comp
LRA RLA
114
109
105
114
109
105
114
109
105
114
109
105
114
109
105
114
109
105
50
48
46
50
48
46
50
48
46
50
48
46
50
48
46
50
48
46
51
53
56
51
53
56
51
53
56
51
53
56
51
53
56
67
71
74

18.3
17.5
16.7
18.1
17.3
16.6
18.2
17.4
16.7
18.1
17.3
16.6
18.2
17.4
16.7
18.2
17.4
16.6
6.7
6.4
6.1
6.7
6.3
6.1
6.7
6.4
6.1
6.7
6.3
6.1
6.7
6.4
6.1
6.7
6.3
6.1
8.0
8.0
8.1
8.1
8.1
8.2
7.6
7.7
7.8
8.0
8.0
8.1
7.9
7.9
8.0
8.2
8.2
8.5

OFM
kW
FLA

IFM
kW
FLA

0.09

0.8

0.090

1.0

0.09

0.8

0.135

0.7

0.09

0.8

0.135

1.0

0.09

0.8

0.060

1.3

0.09

0.8

0.046

0.3

0.09

0.8

0.090

1.0

0.09

0.8

0.090

1.0

0.09

0.8

0.135

0.7

0.09

0.8

0.135

1.0

0.09

0.8

0.060

1.3

0.09

0.8

0.046

0.3

0.09

0.8

0.090

1.0

0.065
+
0.085
0.065
+
0.085
0.065
+
0.085
0.065
+
0.085
0.065
+
0.085
0.065
+
0.090

0.6
+
0.7
0.6
+
0.7
0.6
+
0.7
0.6
+
0.7
0.6
+
0.7
0.6
+
0.8

0.090

1.0

0.144

0.7

0.225

1.4

0.090

1.5

0.090

1.0

0.090

1.0

3D039577A
3D039578A
3D039579A

SkyAir LU Series Cooling Only

97

Electric Characteristics

12.2

ED21-301A

60Hz
Unit Combination
Indoor
Outdoor

Hz-Volts

FHC50KVE

R50GVAL

60-220

FH50BVE

R50GVAL

60-220

FHC60KVE

R60GVAL

60-220

FH60BVE

R60GVAL

60-220

Power Supply
Voltage Range MCA TOCA MFA
Max. 60Hz 242V
Min. 60Hz 198V

Max. 60Hz 242V


Min. 60Hz 198V

Comp
LRA RLA

OFM
kW
FLA

kW

IFM
FLA

13.0

20

42

9.5

0.045

0.4

0.045

0.7

13.0

20

42

9.4

0.045

0.4

0.062

0.7

15.8

25

47

11.6

0.053

0.6

0.045

0.7

15.8

25

47

11.4

0.053

0.6

0.062

0.7

19.5

23.5

30

99

14.4

0.075

0.8

0.045

0.7

22.4

22.0

30

99

15.3

0.075

0.8

0.062

0.7

20.2

23.6

30

99

14.9

0.075

0.8

0.030

0.8

FHYC71KVE R71LUVAL

60-220

FHY71BVE

R71LUVAL

60-220

FVY71LAVE

R71LUVAL

60-220

FAY71LVE

R71LUVAL

60-220

19.5

23.2

30

99

14.6

0.075

0.8

0.068

0.4

FHYC100KVE R100LUVAL

60-220

24.8

27.9

40

143

18.3

0.1

0.9

0.090

1.0

R100LUVAL

60-220

25.5

27.9

40

143

18.9

0.1

0.9

0.135

1.0

FVY100LAVE R100LUVAL

60-220

25.3

28.3

40

143

18.4

0.1

0.9

0.060

1.4

FAY100FAVE R100LUVAL

60-220

24.2

27.3

40

143

18.3

0.1

0.9

0.046

0.4

FHYC125KVE R125LUTAL

60-220

21.6

24.3

30

137

15.1

0.090

1.0

R125LUTAL

60-220

23.2

24.4

30

137

16.3

0.130

1.1

FVY125LAVE R125LUTAL

60-220

22.9

25.0

30

137

15.6

0.090

1.7

FHYC125KVE R125LUYAL

60-380

13.3

15.3

20

66

8.5

0.090

1.0

R125LUYAL

60-380

14.3

15.4

20

66

9.2

0.130

1.1

FVY125LAVE R125LUYAL

60-380

14.4

16.0

20

66

8.8

0.090

1.7

FHYC140KVE R140LUTAL

60-220

Max. 60Hz 242V


Min. 60Hz 198V

22.5

30.7

40

146

15.8

0.090

1.0

FHYC140KVE R140LUYAL

60-380

Max. 60Hz 418V


Min. 60Hz 342V

13.6

17.7

25

75

8.7

0.090

1.0

FHY100BVE

FHY125BVE

FHY125BVE

Max. 60Hz 242V


Min. 60Hz 198V

Max. 60Hz 242V


Min. 60Hz 198V

Max. 60Hz 242V


Min. 60Hz 198V

Max. 60Hz 418V


Min. 60Hz 342V

0.075
+
0.095
0.075
+
0.095
0.075
+
0.095
0.075
+
0.095
0.075
+
0.095
0.075
+
0.095
0.075
+
0.100
0.075
+
0.100

0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9

3D006610D 3D006301A
3D039576C 3D039577A
3D039578A 3D039579A

Symbols:

Note:

98

MCA : Min. Circuit Amps


TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
FLA : Full Load Amps
IFM : Indoor Fan Motor
kW : Fan Motor Rated Output
1. RLA is based on the following conditions.
Indoor temp. 27CDB/19.0CWB
Outdoor temp. 35CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above the range listed.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 RLA + ea. FLA
MFA 2.25 RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. MFA
Instead of fuse, use circuit breaker.

SkyAir LU Series Cooling Only

ED21-301A

Option List

13. Option List


13.1

Indoor Unit

FH(Y)CK
Name of Option

Remark

Kit Name
35~71K

100~140K

Decoration Panel

BYC125KW1

Sealing Member of Air Discharge Outlet

KDBHJ55K160

Panel Spacer
Fresh Air Intake Kit 3

KDBP55H160WA
Chamber Type Without T Joint
With T Joint

KDDP55D160
KDDP55D160K

Direct Installation Type

KDDJ55X160

Chamber Connection Kit 4


HighEfficiency Filter

KKSJ55K160
(Colorimetric Method 65%)

KAFP556D80

KAFP556D160

(Colorimetric Method 90%)

KAFP557D80

KAFP557D160

Replacement HighEfficiency (Colorimetric Method 65%)


Filter
(Colorimetric Method 90%)

KAFP552H80

KAFP552H160

KAFP553H80

KAFP553H160

HighEfficiency Filter Chamber

KDDFP55D160

Replacement LongLife Filter Resin Net (Gravimetric Method 50%)

KAFJ551K160

Ultra LongLife Filter

KAFP55D160

Replacement Ultra LongLife Filter

KAFJ55K160H

Branch Duct Chamber


Remote Controller

KDJ55K80

KDJ55K160

Wired Type 2

BRC1C61 (Note. 5)

Wireless Type

BRC7C613W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan) 1

KRP1B57

Wiring Adaptor for Electrical Appendices 1

KRP4A53

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box for Adaptor PCB

KRP1B98
C : 3D006559E

FH(Y)KF(J)
Name of Option

Remark

Decoration Panel

Kit Name
3545F

60F71FJ

BYK45FJW1

BYK71FJW1

Panel Spacer

KPBJ52F56W

KPBJ52F80W

Air Discharge Blind Panel

KDBJ52F56W

KDBJ52F80W

Replacement LongLife Filter Resin Net

KAFJ521F56

KAFJ521F80

Discharge Grille

KHV7AW

KHV9AW

Flexible Duct with Shutter

KFDJ52F56

KFDJ52F80

Remote Controller

Wired Type 2

Set Back Time Clock

BRC1C61 (Note. 5)
BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan)

KRP1B51

Wiring Adaptor for Electrical Appendices

KRP4A51

Interface Adaptor for SkyAir Series

DTA102A52

Remote Sensor

KRCS011
C : DU423-9100B

Note:

1.
2.
3.
4.
5.

1 : Installation box for adaptor PCB (KRP1B98) is necessary.


2 : Wire for Remote Controller : Field Supplied.
3 : Refer to the Option Handbook for the detail.
4 : When using the filter (HighEfficiency Filter or Ultra LongLife Filter) and the Fresh Air Intake Kit together, this kit is necessary.
BRC1B61 is also available.

SkyAir LU Series Cooling Only

99

Option List

ED21-301A

FH(Y)BF
Name of Option

Remark

Decoration Panel
Service Access Panel

Kit Name
3545F

6071F

BYBS45DJW1

BYBS71DJW1

100F

BYBS125DJW1

125F

KTBJ25K56W

KTBJ25K80W

KTBJ25K160W

(Colorimetric
method 65%)

KAFJ252L56

KAFJ252L80

KAFJ252L160

(Colorimetric
method 90%)

KAFJ253L56

KAFJ253L80

KAFJ253L160

Replacement Long Resin Net


Life Filter

KAFJ251K56

KAFJ251K80

KAFJ251K160

Filter Chamber for Bottom Suction

KAJ25L56D

KAJ25L80D

KAJ25L160D

Filter Chamber for Rear Suction

KAJ25L56B

KAJ25L80B

KAJ25L160B

Canvas Duct

KSA25K56

KSA25K80

KSA25K160

HighEfficiency
Filter

Discharge Grille

(150)

KDG4DW

KDG5DW

KDG4DW

KDG5DW

(200)

KDG7DW

KDG9DW

KDG7DW

KDG9DW

Discharge Chamber

(150)

KDGC4D

KDGC5D

KDGC4D

KDGC5D

(200)

KDGC7D

KDGC9D

KDGC7D

KDGC9D

Branch Duct

200 150

Flexible Duct

(150)

(1m)KFDS151D, (2m)KFDS152D, (3m)KFDS153D,


(4m)KFDS154D, (5m)KFDS155D, (6m)KFDS156D

(200)

(1m)KFDS201D, (2m)KFDS202D, (3m)KFDS203D,


(4m)KFDS204D, (5m)KFDS205D, (6m)KFDS206D

KDDV20A

Blind Board

KBBJ25K56

KBBJ25K80

KBBJ25K160

Adaptor for Discharge

KDAJ25K56

KDAJ25K71

KDAJ25K140

Flange for Suction

KDJ2507K56

KDJ2507K80

KDJ2507K160

Remote Controller

Wired Type 2

BRC1C61 (Note. 4)

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan)

KRP1B54

Wiring Adaptor for Electrical Appendices

KRP4A51

Interface Adaptor for SkyAir Series

DTA102A52
C : DU423-999C

FUYFJ
Name of Option

Remark

Kit Name
71FJ
KDBHJ49F80

KDBHJ49F140

Decoration Panel for Air Discharge

KDBTJ49F80

KDBTJ49F140

Vertical Flap Kit

KDGJ49F80

LConnection Piping Kit


Remote Controller

KDGJ49F140
KAFJ495F140

KHFJ49F80

KHFJ49F140

Wired Type 2

BRC1C61 (Note. 5)

Wireless Type

BRC7C529W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Wiring Adaptor for Electrical Appendices 1


Interface Adaptor for SkyAir Series
Installation Box for Adaptor PCB
Remote Sensor

100

125FJ

Sealing Member of Air Discharge Outlet 3

Replacement LongLife Filter

Note:

100FJ

1.
2.
3.
4.
5.

KRP4A53
DTA102A52
KRP1B97
KRCS011

1 : Installation box for adaptor PCB (KRP1B97) is necessary.


2 : Wire for Remote Controller : Field Supplied.
3 : This option is required at time of installation for setting two-way opposing air flow.

C : 3D013861B

BRC1B62 is also available.


BRC1B61 is also available.

SkyAir LU Series Cooling Only

ED21-301A

Option List

FH(Y)B
Name of Option

Remark

Kit Name
35B

Replacement LongLife Filter


Drain Pump Kit
LType Piping Kit

For Upward
Direction

Remote Controller

Wired Type 4

50B

60B

71B

100B

125B

KAFJ501D56

KAFJ501D80

KAFJ501D112 KAFJ501D160

KDU50B50VE

KDU50B71VE

KDU50B125VE

KHFJ5F50

KHFJ5F60

KHFJ5F80

KHFJ5F160

BRC1C61

Wireless Type

BRC7E66

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring

KRP1B54

Wiring Adaptor for Electrical


Appendices 1

KRP4A52

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box Adaptor PCB

KRP1C93
C : 3D028285A

FAYL
FAYFA

Name of Option

Remark

Drain Pump Kit

Kit Name
71L

100FA

KKDU572CVE

Wired Type 4

Remote Controller

Wireless Type

BRC1C61 (Note. 5)
BRC7E619

Set Back Time Clock

BRC7C611W

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Wiring Adaptor for Electrical Appendices


Interface Adaptor for SkyAir Series
Installation Box for Adaptor PCB

KRP4A51 3

KRP4A51

DTA102A52

KRP4A93

C : 3D039142C
C : DU427-965E

FVYLA
Name of Option

Kit Name
71~125LA

Replacement LongLife Filter


Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Remote Controller for 2 Remote Control System

BRC1C61

Adaptor for Wiring 2

KRP1B57

Group Control Adaptor 2


Interface Adaptor for SkyAir Series
Installation Box for Adaptor PCB

Note:

KAFJ95L160

1.
2.
3.
4.
5.

1 : Installation box for adaptor PCB (KRP1C93) is necessary.


2 : Installation box for adaptor PCB (KRP4A95) is necessary.
3 : Installation box for adaptor PCB (KRP4A93) is necessary.
4 : Wire for Remote Controller : Field supplied.

KRP4A52
DTA102A52
KRP4A95
C : 4D013855A

BRC1B61 is also available.

SkyAir LU Series Cooling Only

101

Option List

ED21-301A

13.2

Outdoor Unit
13.2.1 R35~60G(A)
Name of Option

Kit Name
R35~60G(A)

Drain Piping Kit

KIS95
C : 3D005955A

13.2.2 R71~140LU
Name of Option

Kit Name
R71LU

Central Drain Plug


YearRound Cooling Kit

R100LU

R125LU

R140LU

KKPJ5F180
KRK5F80V1

KRK5F140V1

KRK5F160V1
3D039655

102

SkyAir LU Series Cooling Only

ED21-301A

Field Piping and Wiring

14. Field Piping and Wiring


14.1

Field piping

14.1.1 Maximum Allowable Piping Length and Level Difference


R35G

R50 60G(A)

Max. Allowable Piping Length

25 m

30 m

R71~140LU
50 m (Equivalent Length 70 m)

Max. Allowable Level Difference

15 m

15 m

30 m

14.1.2 Additional Refrigerant Charge


This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
The range where no charging is required.
(R35G 50G(A) : 10 m or less, R60G(A) : 5 m or less, R71~140LU : 30 m or less.)
Take the following steps for proper charging.
When connected to one indoor unit (pair system)

Main pipe (L1)

Indoor unit
One-way length of pipe (L):
L1

Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1~2, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
R35G, 50 60G(A)
Table 1

<Unit : g>

Additional Charging Amount

R35G 50G(A)

R60G(A)

20 g/m (Exceeding 10 m)

20 g/m (Exceeding 5 m)

R71~140LU
Table 2 (The maximum allowable pipe length is 50 meters.)
Pipe excess length over 30 meters
Cooling only type

R71~140

<Unit : kg>

10m or less

20m or less

0.25

0.50

14.1.3 Recharging Refrigerant


R71~140LU
When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the
amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is
an addition of the amount stated on the nameplate and the additional charging amount.
1PN05248B-1

SkyAir LU Series Cooling Only

103

Field Piping and Wiring

ED21-301A

14.1.4 Pumping-down Operation Method


The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.
Caution:

Never short-circuit the low-pressure switch in this operation.


Procedure
1. Start the fan operation with the remote controller.

Precautions
Confirm that stop valves both on the liquid and gas side
are open. Take care when the procedure 2 is done first
because the indoor unit fan may operate automatically.

2. Push the pumping-down button on the PC board of the Compressor and outdoor fan will start operation
outdoor unit.
automatically.
3. Continue operation for 1 min. until operation condition
stabilizes.
4. Close the stop valve on the liquid side securely.
(Refer to Fig. 1)

Insecure closing of the valve may result in burning of


the compressor.

5. When the low-pressure switch is activated, the unit


stops working. At this time, close the stop valve on the
gas side.

How to use the stop valve (Refer to Fig. 1)


Have a hex wrench ready. (4 mm and 6 mm)
1. Open the valve.
a. Place the hex wrench on the valve bar and turn counter-clockwise.
b. Stop when the valve bar no longer turns. It is now open.
2. Close the valve.
a. Place the hex wrench on the valve bar and turn clockwise.
b. Stop when the valve bar no longer turns. It is now closed.

(Gas side)
Opening direction
(Liquid side)
Opening direction

Fig. 1

Necessity of a trap
Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to
provide a trap at an appropriate place in the riser gas piping.
Trap installation spacing
Indoor unit
Oil trap
Gas piping
15m

Liquid piping

Marks. Install trap at


each difference in
height 15m.
Outdoor unit

Note:

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
Caution to be taken when brazing refrigerant piping
Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800C) which causes pin holes and results in refrigerant
leakage.
1PN05248B-2

104

SkyAir LU Series Cooling Only

ED21-301A

14.2

Field Piping and Wiring

Field Wiring

14.2.1 R71LU (V1 Y1 VAL), R100LU (V1 Y1 VAL), R125LU (Y1 TAL YAL), R140LU (Y1 TAL YAL)

C : DU423-5177C
C : 3D013853
C : 4D001694A
C : 4D006674A
C : 4D013833B

SkyAir LU Series Cooling Only

105

Field Piping and Wiring

106

ED21-301A

SkyAir LU Series Cooling Only

ED21-301A

SkyAir LU Series
(Twin, Triple, Double Twin)
Cooling Only
Model Series
Twin

Class
Indoor
Unit

35

50

60

FHYC

35K2

50K2

60K2

71K2 100K2 125K2

FHY

35B2

50B2

60B2

71B2 100B2 125B2

71LU

100LU

125LU

140LU

Outdoor
R
Unit

Indoor
Unit

50

71

50

60

FHYC

50K3

71K3

50K4

60K4

FHY

50B3

71B3

50B4

60B4

140LU

200KU

200KU

250KU

Outdoor
R
Unit

100

200KU

125

250KU

Double Twin

Triple

Class

71

Cautions 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.

2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and
choose an outdoor unit with anti-corrosion treatment.

SkyAir LU Series Cooling Only

107

Features

ED21-301A

1. Features
SkyAir Series - Twin, Triple, Double Twin Systems
(Simultaneous Operation System)

1.1

What are Twin, Triple, Double Twin Systems?


One large room can be cooled simultaneously by two, three or four indoor units according to the
environmental needs.
Space saving for outdoor units.
Possible to cool in outdoor temp. down to -15C by using optional year-round cooling kit
(KRK5F80, 140, 160V1)
The operation limit has been extended down to an outdoor temp. of -15C making it possible to operate the
unit in the cooling mode whenever you need it all year round.
Note:

Individual control (Such as room temperature) is not available.

(Ex.)Pair

(Ex.)Pair

(Ex.)Twin

(Ex.)Twin

(Ex.)Triple

(Ex.)Triple

FHYC50K

FHYC50K

FHYC50K

FHYC50K

FHYC50K

FHYC50K

Circuit
breaker
R140LU

Even Temperature Distribution


Only one Remote Controller
Only one Circuit Breaker
(S0026-1)

(S0027)

Only one circuit breaker is needed for versatile electric work.


Simple refrigerant system due to the branch piping kit specially designed for this system.

108

SkyAir LU Series Cooling Only

ED21-301A

Model Name and Power Supply

2. Model Name and Power Supply


2.1

Twin, Triple and Double Twin System

2.1.1

50Hz
Twin
Indoor Unit

Outdoor Unit

FHYC35KVE+FHYC35KVE

R71LUV1

FHY35BVE+FHY35BVE

R71LUV1

FHYC50KVE+FHYC50KVE

R100LUV1

FHY50BVE+FHY50BVE

R100LUV1

FHYC35KVE+FHYC35KVE

R71LUY1

FHY35BVE+FHY35BVE

R71LUY1

FHYC50KVE+FHYC50KVE

R100LUY1

FHY50BVE+FHY50BVE

R100LUY1

FHYC60KVE+FHYC60KVE

R125LUY1

FHY60BVE+FHY60BVE

R125LUY1

FHYC71KVE+FHYC71KVE

R140LUY1

FHY71BVE+FHY71BVE

R140LUY1

FHYC100KVE+FHYC100KVE

R200KUY1

FHY100BVE+FHY100BVE

R200KUY1

FHYC125KVE+FHYC125KVE

R250KUY1

FHY125BVE+FHY125BVE

R250KUY1

Power Supply

1, 220~240V, 50Hz

3, 380~415V, 50Hz

Triple
Indoor Unit

Outdoor Unit

Power Supply

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUY1
FHY50BVE+FHY50BVE+FHY50BVE

R140LUY1

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUY1
FHY71BVE+FHY71BVE+FHY71BVE

3, 380~415V, 50Hz

R200KUY1

Double Twin
Indoor Unit

Note:

Outdoor Unit

FHYC50KVE+FHYC50KVE+
FHYC50KVE+FHYC50KVE

R200KUY1

FHY50BVE+FHY50BVE+
FHY50BVE+FHY50BVE

R200KUY1

FHYC60KVE+FHYC60KVE+
FHYC60KVE+FHYC60KVE

R250KUY1

FHY60BVE+FHY60BVE+
FHY60BVE+FHY60BVE

R250KUY1

Power Supply

3, 380~415V, 50Hz

1. Power Supply Intake : Outdoor Unit

SkyAir LU Series Cooling Only

109

Model Name and Power Supply

2.1.2

ED21-301A

60Hz
Twin
Indoor Unit
FHYC35KVE+FHYC35KVE

Outdoor Unit

Power Supply

R71LUVAL

FHY35BVE+FHY35BVE

R71LUVAL

FHYC50KVE+FHYC50KVE

R100LUVAL

FHY50BVE+FHY50BVE

R100LUVAL

FHYC60KVE+FHYC60KVE

R125LUTAL

FHY60BVE+FHY60BVE

R125LUTAL

FHYC71KVE+FHYC71KVE

R140LUTAL

FHY71BVE+FHY71BVE

R140LUTAL

FHYC100KVE+FHYC100KVE

R200KUTAL

FHY100BVE+FHY100BVE

R200KUTAL

FHYC125KVE+FHYC125KVE

R250KUTAL

FHY125BVE+FHY125BVE

R250KUTAL

FHYC60KVE+FHYC60KVE

R125LUYAL

FHY60BVE+FHY60BVE

R125LUYAL

FHYC71KVE+FHYC71KVE

R140LUYAL

FHY71BVE+FHY71BVE

R140LUYAL

FHYC100KVE+FHYC100KVE

R200KUYAL

FHY100BVE+FHY100BVE

R200KUYAL

FHYC125KVE+FHYC125KVE

R250KUYAL

FHY125BVE+FHY125BVE

R250KUYAL

1, 220V, 60Hz

3, 220V, 60Hz

3, 380V, 60Hz

Triple
Indoor Unit

Outdoor Unit

Power Supply

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUTAL
FHY50BVE+FHY50BVE+FHY50BVE

R140LUTAL

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUTAL
FHY71BVE+FHY71BVE+FHY71BVE

3, 220V, 60Hz

R200KUTAL

FHYC50KVE+FHYC50KVE+FHYC50KVE R140LUYAL
FHY50BVE+FHY50BVE+FHY50BVE

R140LUYAL

FHYC71KVE+FHYC71KVE+FHYC71KVE R200KUYAL
FHY71BVE+FHY71BVE+FHY71BVE

3, 380V, 60Hz

R200KUYAL

Double Twin
Indoor Unit

Note:

110

Outdoor Unit

FHYC50KVE+FHYC50KVE+
FHYC50KVE+FHYC50KVE

R200KUTAL

FHY50BVE+FHY50BVE+
FHY50BVE+FHY50BVE

R200KUTAL

FHYC60KVE+FHYC60KVE+
FHYC60KVE+FHYC60KVE

R250KUTAL

FHY60BVE+FHY60BVE+
FHY60BVE+FHY60BVE

R250KUTAL

FHYC50KVE+FHYC50KVE+
FHYC50KVE+FHYC50KVE

R200KUYAL

FHY50BVE+FHY50BVE+
FHY50BVE+FHY50BVE

R200KUYAL

FHYC60KVE+FHYC60KVE+
FHYC60KVE+FHYC60KVE

R250KUYAL

FHY60BVE+FHY60BVE+
FHY60BVE+FHY60BVE

R250KUYAL

Power Supply

3, 220V, 60Hz

3, 380V, 60Hz

1. Power Supply Intake : Outdoor Unit

SkyAir LU Series Cooling Only

ED21-301A

External Appearance

3. External Appearance
3.1

External Appearance

Indoor Unit

2
FHYB
FHYCK

Remote Controller

Wired Type

Wireless Type

Outdoor Unit

R71LU

R100LU

R200KU

SkyAir LU Series Cooling Only

R125LU

R140LU

R250KU

111

Specifications

ED21-301A

4. Specifications
4.1

50Hz

FHYC (Ceiling Mounted Cassette Type) Twin


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit 3
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections
Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel
Color
(Option) 3
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit
Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin pitch
Face Area
Model

mm

W
m/min
kg
mm
mm
mm

mm
kg
V1
Y1
mm

m
V1
Y1

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate 2
kg

kW

W
m/min
V1
Y1
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

m
m
kg
L

FHYC50KVE2
FHYC60KVE2
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FHYC50KVE2
FHYC60KVE2
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H)1416 (L)1012
(H)1517 (L)1113
(H)1921 (L)1416
24
24
24
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 6, 7)
BRC7C613W
BYC125KW12
BYC125KW12
BYC125KW12
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039097

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.
7.

112

FHYC35KVE2
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHYC35KVE2
230840840

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rate) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
3 Each value for indoor unit shows the specification per one unit.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHYC (Ceiling Mounted Cassette Type) Twin


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 3
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel
Color
(Option) 3
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm

W
m/min
kg
mm
mm
mm

mm
kg

mm

kW

W
m/min
kg
mm
mm
mm

%
m
m
kg
L

FHYC71KVE2
R140LUY1
14.5/14.2/14.2
49,400/48,400/48,400
12,500/12,200/12,200
FHYC71KVE2
230840840
Cross Fin Coil
281.5
0.331
QTS45B14M

FHYC100KVE2
FHYC125KVE2
R200KUY1
R250KUY1
22.5/22.2/22.0
27.1/26.6/26.3
76,800/75,800/75,100
92,500/90,800/89,800
19,400/19,100/18,900
23,300/22,900/22,600
FHYC100KVE2
FHYC125KVE2
288840840
288840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2121.5
2121.5
0.497
0.497
QTS45A17M
QTS45A17M
Turbo Fan
45
90
90
(H)1921 (L)1415
(H)2831 (L)2124
(H)3336 (L)2427
24
28
28
6.4 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 6, 7)
BRC7C613W
BYC125KW12
BYC125KW12
BYC125KW12
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R140LUY1
R200KUY1
R250KUY1
Ivory
1,345900320
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2602.0
2402.0
2502.0
1.134
1.57
1.97
JT170BCYE
JT236DP1YE
JT335DP1YE
Hermetically Sealed Scroll Type
4.50
5.5
9.0
P47L11S2
P52H11SM
P52H11SM
Propeller
65+90
230+190
230+190
97109
150154
175179
109
178
202
9.5 (Flare)
12.7 (Flare)
15.9 (Flare)
19.1 (Flare)
25.4 (Flange)
28.6 (Flange)
26.0 (Hole)

Thermal Protector for Outdoor Fan


Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor.
Motor and Indoor Fan Motor. High
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor).
Pressure Switch. Low Pressure
Reverse Phase Protector. Fuse.
Switch. Over Current Device. Reverse
Phase Protector. Fuse.
1000
1000
1000
Electronic Expansion Valve
Capillary Tube
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
4.1 (Charged for 30m)
5.3 (Charged for 5m)
5.7 (Charged for 5m)
Refer to the name plate of compressor.
1.6
3.0
3.0
4D039098
4D029963
4D029965

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 380V

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

7.5m

JIS B8616

LU

5m

50Hz, 380V

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

(3) Indoor : 27CDB, 19.0CWB


7.5m
50Hz, 415V
AS 1861
LU, KU
Outdoor : 35CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. 2 AFR (Air flow rate) is shown at 380V415V.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUY1)
5. 3 Each value for indoor unit shows the specification per one unit.
6. BRC1B61 is also available.
7. Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

113

Specifications

ED21-301A

FHYC (Ceiling Mounted Cassette Type) Triple / Double Twin


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 3
Dimensions HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel
Color
(Option) 3
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit
Color
Dimensions HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm

W
m/min
kg
mm
mm
mm

FHYC50KVE3
R140LUY1
14.5/14.2/14.2
49,400/48,400/48,400
12,500/12,200/12,200
FHYC50KVE3
230840840
Cross Fin Coil
281.5
0.331
QTS45B14M
45
(H)1517 (L)1112
24
6.4 (Flare)
15.9 (Flare)
I.D25O.D32

BYC125KW13
mm

40950950

kg

5
R140LUY1

mm

1,345900320

2602.0
1.134
JT170BCYE

kW

4.50
P47L11S2

W
m/min
kg
mm
mm
mm

65+90
97109
109
9.5 (Flare)
19.1 (Flare)
26.0 (Hole)
Thermal Protector for
Outdoor Fan Motor and
Indoor Fan Motor. High
Pressure Switch. Low
Pressure Switch. Over
Current Device. Reverse
Phase Protector. Fuse.
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
30
R22
4.1 (Charged for 30m)

%
m
m
kg
L

1.6
4D039098

FHYC71KVE3
FHYC50KVE4
FHYC60KVE4
R200KUY1
R200KUY1
R250KUY1
22.5/22.2/22.0
22.5/22.2/22.0
27.1/26.6/26.3
76,800/75,800/75,100
76,800/75,800/75,100
92,500/90,800/89,800
19,400/19,100/18,900
19,400/19,100/18,900
23,300/22,900/22,600
FHYC71KVE3
FHYC50KVE4
FHYC60KVE4
230840840
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H)1921 (L)1415
(H)1517 (L)1112
(H)1921 (L)1416
24
24
24
9.5 (Flare)
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 6, 7)
BRC7C613W
BYC125KW13
BYC125KW14
BYC125KW14
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R200KUY1
R200KUY1
R250KUY1
Ivory
1,2201,280690
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2402.0
2402.0
2502.0
1.57
1.57
1.97
JT236DP1YE
JT236DP1YE
JT335DP1YE
Hermetically Sealed Scroll Type
5.5
5.5
9.0
P52H11SM
P52H11SM
P52H11SM
Propeller
230+190
230+190
230+190
150154
150154
175179
178
178
202
12.7 (Flare)
12.7 (Flare)
15.9 (Flare)
25.4 (Flange)
25.4 (Flange)
28.6 (Flange)

Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High
Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse Phase
Protector. Fuse.

1000

1000
Capillary Tube
50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
R22
R22
5.3 (Charged for 5m)
5.3 (Charged for 5m)
Refer to the name plate of compressor.
3.0
3.0
4D029963

1. 1 The above data are based on the following conditions.


Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 380V

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

JIS B8616

LU

5m

50Hz, 380V

50 (Equivalent Length 70m)


30
R22
5.7 (Charged for 5m)
3.0
4D029965

Conversion Formulae

Cooling

7.5m

1000

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

: 27CDB, 19.0CWB
(3) Indoor
7.5m
50Hz, 415V
AS 1861
LU, KU
Outdoor : 35CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. 2 AFR (Air flow rate) is shown at 380V415V.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUY1)
5. 3 Each value for indoor unit shows the specification per one unit.
6. BRC1B61 is also available.
7. Wire for remote controller : Field supplied.

114

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHY (Ceiling Suspended Type) Twin


Model

Indoor Unit
Outdoor Unit

V1
Y1
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit 3
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Air Filter
Weight
Piping
Liquid
Connections
Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Outdoor Unit
Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate 2
kg

mm

W
m/min
kg
mm
mm
mm

V1
Y1
mm

m
V1
Y1
kW

W
m/min
V1
Y1
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHY35BVE2
R71LUV1
R71LUY1
7.8/7.7/7.7
26,600/26,200/26,200
6,700/6,600/6,600
FHY35BVE2

FHY50BVE2
FHY60BVE2
R100LUV1

R100LUY1
R125LUY1
10.6/10.5/10.5
13.0/12.8/12.8
36,100/35,700/35,700
44,500/43,600/43,600
9,100/9,000/9,000
11,200/11,000/11,000
FHY50BVE2
FHY60BVE2
White
195960680
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
2121.75
3121.75
3121.75
0.182
0.182
0.233
3D12K1AA1
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
62
(H)13 (L)10
(H)13 (L)10
(H)16 (L)13
Resin Net (with Mold Resistant)
23
24
26
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 6)
BRC7E66
R71LUV1
R100LUV1

R71LUY1
R100LUY1
R125LUY1
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFJ
ZR48K3PFJ

ZR36K3TFD
ZR48K3TFD
JT160BCYE
Hermetically Sealed Scroll Type
2.24
3.00
3.75
P47L11S
P47L11S
P47L11S2
Propeller
65
90
65+85
4851
5962
92100
72
87

71
84
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (Y1). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039100

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 220240V
(380415V)

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

7.5m

(3)
2.
3.
4.
5.
6.

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

50Hz, 220240V JIS B8616


(380415V)

Indoor : 27CDB, 19.0CWB


50Hz, 240V
7.5m
AS 1861
Outdoor : 35CDB, 24CWB
(415V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rate) is shown at 220V (380V)240V (415V).
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
3 Each value for indoor unit shows the specification per one unit.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

115

Specifications

ED21-301A

FHY (Ceiling Suspended Type) Twin


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 3
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Air Filter
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

mm

W
m/min
kg
mm
mm
mm

mm

kW

W
m/min
kg
mm
mm
mm

%
m
m
kg
L

FHY71BVE2
R140LUY1
14.5/14.2/14.2
49,400/48,400/48,400
12,500/12,200/12,200
FHY71BVE2

FHY100BVE2
FHY125BVE2
R200KUY1
R250KUY1
22.5/22.2/22.0
27.1/26.6/26.3
76,800/75,800/75,100
92,500/90,800/89,800
19,400/19,100/18,900
23,300/22,900/22,600
FHY100BVE2
FHY125BVE2
White
1951,160680
1951,400680
1951,590680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.293
0.341
4D12K1AA1
3D12K2AA1
4D12KAA1
Sirocco Fan
62
130
130
(H)17 (L)14
(H)24 (L)20
(H)30 (L)25
Resin Net (with Mold Resistant)
27
32
35
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 6)
BRC7E66
R140LUY1
R200KUY1
R250KUY1
Ivory
1,345900320
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2602.0
2402.0
2502.0
1.134
1.57
1.97
JT170BCYE
JT236DP1YE
JT335DP1YE
Hermetically Sealed Scroll Type
4.50
5.5
9.0
P47L11S2
P52H11SM
P52H11SM
Propeller
65+90
230+190
230+190
97109
150154
175179
109
178
202
9.5 (Flare)
12.7 (Flare)
15.9 (Flare)
19.1 (Flare)
25.4 (Flange)
28.6 (Flange)
26.0 (Hole)

Thermal Protector for Outdoor Fan


Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor.
Motor and Indoor Fan Motor. High
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor).
Pressure Switch. Low Pressure
Reverse Phase Protector. Fuse.
Switch. Over Current Device. Reverse
Phase Protector. Fuse.
1000
1000
1000
Electronic Expansion Valve
Capillary Tube
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
4.1 (Charged for 30m)
5.3 (Charged for 5m)
5.7 (Charged for 5m)
Refer to the name plate of compressor.
1.6
3.0
3.0
4D039101
4D028444
4D028439

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 380V

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

7.5m

JIS B8616

LU

5m

50Hz, 380V

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

(3) Indoor : 27CDB, 19.0CWB


7.5m
50Hz, 415V
AS 1861
LU, KU
Outdoor : 35CDB, 24CWB
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. 2 AFR (Air flow rate) is shown at 380V415V.
4. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUY1)
5. 3 Each value for indoor unit shows the specification per one unit.
6. Wire for remote controller : Field supplied.

116

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHY (Ceiling Suspended Type) Triple / Double Twin


Model

Indoor Unit
Outdoor Unit
1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 3
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Air Filter
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Outdoor Unit
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Comp.
Model
Type
Motor Output
Fan
Model
Type
Motor Output
Air Flow Rate 2
Weight
Piping
Liquid
Connections Gas
Drain
Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

FHY50BVE3
R140LUY1
14.5/14.2/14.2
49,400/48,400/48,400
12,500/12,200/12,200
FHY50BVE3

mm

195960680

3121.75
0.182
3D12K1AA1

W
m/min

62
(H)13 (L)10

kg
mm
mm
mm

24
6.4 (Flare)
15.9 (Flare)
I.D20O.D26

R140LUY1
mm

1,345900320

2602.0
1.134
JT170BCYE

kW

4.50
P47L11S2

W
m/min
kg
mm
mm
mm

65+90
97109
109
9.5 (Flare)
19.1 (Flare)
26.0 (Hole)
Thermal Protector for
Outdoor Fan Motor and
Indoor Fan Motor. High
Pressure Switch. Low
Pressure Switch. Over
Current Device. Reverse
Phase Protector. Fuse.
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
30
R22
4.1 (Charged for 30m)

%
m
m
kg
L

1.6
4D039101

FHY71BVE3
R200KUY1
22.5/22.2/22.0
76,800/75,800/75,100
19,400/19,100/18,900
FHY71BVE3

FHY50BVE4
R200KUY1
22.5/22.2/22.0
76,800/75,800/75,100
19,400/19,100/18,900
FHY50BVE4

White
1951,160680
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.182
0.233
4D12K1AA1
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
62
(H)17 (L)14
(H)13 (L)10
(H)16 (L)13
Resin Net (with Mold Resistant)
27
24
26
9.5 (Flare)
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 6)
BRC7E66
R200KUY1
R200KUY1
R250KUY1
Ivory
1,2201,280690
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2402.0
2402.0
2502.0
1.57
1.57
1.97
JT236DP1YE
JT236DP1YE
JT335DP1YE
Hermetically Sealed Scroll Type
5.5
5.5
9.0
P52H11SM
P52H11SM
P52H11SM
Propeller
230+190
230+190
230+190
150154
150154
175179
178
178
202
12.7 (Flare)
12.7 (Flare)
15.9 (Flare)
25.4 (Flange)
25.4 (Flange)
28.6 (Flange)

Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High
Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse
Phase Protector. Fuse.

1000

1000
Capillary Tube
50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
R22
R22
5.3 (Charged for 5m)
5.3 (Charged for 5m)
Refer to the name plate of compressor.
3.0
3.0
4D028444

1. 1 The above data are based on the following conditions.


Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

50Hz, 380V

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

JIS B8616

LU

(3)
2.
3.
4.
5.
6.

5m

50Hz, 380V

1000
50 (Equivalent Length 70m)
30
R22
5.7 (Charged for 5m)
3.0
4D028439

Conversion Formulae

Cooling

7.5m

FHY60BVE4
R250KUY1
27.1/26.6/26.3
92,500/90,800/89,800
23,300/22,900/22,600
FHY60BVE4

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


7.5m
50Hz, 415V
AS 1861
LU, KU
Outdoor : 35CDB, 24CWB
Capacities are net, including a deduction for cooling for indoor fan motor heat.
2 AFR (Air flow rate) is shown at 380V415V.
In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUY1)
3 Each value for indoor unit shows the specification per one unit.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

117

Specifications

4.2

ED21-301A

60Hz

FHYC (Ceiling Mounted Cassette Type) Twin


Model

Indoor Unit
Outdoor Unit

VAL
TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)

Indoor Unit 2
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections
Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel (Option) Color
2
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit

Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

W
m/min
kg
mm
mm
mm

mm
kg
VAL
TAL
YAL
mm

m
VAL
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

m
m
kg
L

FHYC50KVE2
FHYC60KVE2
R100LUVAL

R125LUTAL

R125LUYAL
11.6/11.4
14.5/14.3
39,700/38,900
49,600/48,800
10,000/9,800
12,500/12,300
FHYC50KVE2
FHYC60KVE2
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H)14 (L)10
(H)15 (L)11
(H)19 (L)14
24
24
24
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 5, 6)
BRC7C613W
BYC125KW12
BYC125KW12
BYC125KW12
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R71LUVAL
R100LUVAL

R125LUTAL

R125LUYAL
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFV
ZR47K3PFV

JT160BC

JT160BCYH
Hermetically Sealed Scroll Type
2.24
2.92
3.75
P47L11S
P47L11S
P47L11S2
Propeller
75
100
95+75
49
59
94
75
92
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (TAL YAL). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039108

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.
6.

118

FHYC35KVE2
R71LUVAL

8.3/8.1
28,200/27,800
7,100/7,000
FHYC35KVE2
230840840

Cooling

Piping Length

Hz, Volts

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

Conversion Formulae
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


60Hz, 220V
7.5m
Outdoor : 35CDB, 24CWB
(380V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
2 Each value for indoor unit shows the specification per one unit.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHYC (Ceiling Mounted Cassette Type) Twin


Model

Indoor Unit
Outdoor Unit

TAL
YAL

1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 2
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel
Color
(Option) 2
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit
Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

W
m/min
kg
mm
mm
mm

mm
kg

TAL
YAL
mm

TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHYC71KVE2
R140LUTAL
R140LUYAL
16.1/15.8/
55,000/53,900/
13,800/13,500/
FHYC71KVE2
230840840
Cross Fin Coil
281.5
0.331
QTS45B14M

FHYC100KVE2
FHYC125KVE2
R200KUTAL
R250KUTAL
R200KUYAL
R250KUYAL
22.5/22.2/20.0
27.1/26.6/24.1
76,800/75,800/68,300
92,500/90,800/82,300
19,400/19,100/17,200
23,300/22,900/20,700
FHYC100KVE2
FHYC125KVE2
288840840
288840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2121.5
2121.5
0.497
0.497
QTS45A17M
QTS45A17M
Turbo Fan
45
90
90
(H)19 (L)14
(H)28 (L)21
(H)33 (L)24
24
28
28
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 5, 6)
BRC7C613W
BYC125KW12
BYC125KW12
BYC125KW12
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R140LUTAL
R200KUTAL
R250KUTAL
R140LUYAL
R200KUYAL
R250KUYAL
Ivory
1,345900320
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2602.0
2402.0
2502.0
1.134
1.57
1.97
JT170BC
JT212DP1
JT300DP1
JT170BCYH
JT212DP1YH
JT300DP1YH
Hermetically Sealed Scroll Type
4.50
5.5
7.5
P47L11S2
P52H11SM
P52H11SM
Propeller
100+75
230+190
230+190
101
160
190
109
177
200
9.5 (Flare)
12.7 (Flare)
15.9 (Flare)
19.1 (Flare)
25.4 (Flange)
28.6 (Flange)
26.0 (Hole)

Thermal Protector for Outdoor Fan


Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor.
Motor and Indoor Fan Motor. High
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor).
Pressure Switch. Low Pressure
Reverse Phase Protector. Fuse.
Switch. Over Current Device. Reverse
Phase Protector. Fuse.
1000
1000
1000
Electronic Expansion Valve
Capillary Tube
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
4.1 (Charged for 30m)
5.3 (Charged for 5m)
5.7 (Charged for 5m)
Refer to the name plate of compressor.
1.6
3.0
3.0
4D039109
4D029964
4D029966

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

60Hz, 220V
(380V)

KU

7.5m

JIS B8616

LU

(3)
2.
3.
4.
5.
6.

5m

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 29CDB, 19.0CWB


60Hz, 220V
7.5m
SSA 385/386
KU
Outdoor : 46CDB, 24CWB
(380V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUTAL YAL)
2 Each value for indoor unit shows the specification per one unit.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

119

Specifications

ED21-301A

FHYC (Ceiling Mounted Cassette Type) Triple / Double Twin


Model

Indoor Unit
Outdoor Unit

TAL
YAL

1 Cooling Capacity (1)/(2)/(3)

kW
Btu/h
kcal/h

Indoor Unit 2
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Decoration
Model
Panel
Color
(Option) 2
Dimensions (HWD)
Air Filter
Weight
Outdoor Unit
Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate
Liquid
Gas
Drain

mm

W
m/min
kg
mm
mm
mm

Note:

mm

40950950

kg

TAL
YAL

5
R140LUTAL
R140LUYAL

mm

1,345900320
2602.0
1.134
JT170BC
JT170BCYH

TAL
YAL
kW

4.50
P47L11S2

W
m/min
kg
mm
mm
mm

100+75
101
109
9.5 (Flare)
19.1 (Flare)
26.0 (Hole)
Thermal Protector for
Outdoor Fan Motor and
Indoor Fan Motor. High
Pressure Switch. Low
Pressure Switch. Over
Current Device. Reverse
Phase Protector. Fuse.
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
30
R22
4.1 (Charged for 30m)

%
m
m
kg
L

1.6
4D039109

FHYC71KVE3
FHYC50KVE4
FHYC60KVE4
R200KUTAL
R200KUTAL
R250KUTAL
R200KUYAL
R200KUYAL
R250KUYAL
22.5/22.2/22.0
22.5/22.2/22.0
27.1/26.6/24.1
76,800/75,800/68,300
76,800/75,800/68,300
92,500/90,800/82,300
19,400/19,100/17,200
19,400/19,100/17,200
23,300/22,900/20,700
FHYC71KVE3
FHYC50KVE4
FHYC60KVE4
230840840
230840840
230840840
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
281.5
281.5
281.5
0.331
0.331
0.331
QTS45B14M
QTS45B14M
QTS45B14M
Turbo Fan
45
45
45
(H)19 (L)14
(H)15 (L)11
(H)19 (L)14
24
24
24
9.5 (Flare)
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D25O.D32
I.D25O.D32
I.D25O.D32
BRC1C61 (Note. 5, 6)
BRC7C613W
BYC125KW13
BYC125KW14
BYC125KW14
White
40950950
40950950
40950950
Resin Net (with Mold Resistant)
5
5
5
R200KUTAL
R200KUTAL
R250KUTAL
R200KUYAL
R200KUYAL
R250KUYAL
Ivory
1,2201,280690
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2402.0
2402.0
2502.0
1.57
1.57
1.97
JT212DP1
JT212DP1
JT300DP1
JT212DP1YH
JT212DP1YH
JT300DP1YH
Hermetically Sealed Scroll Type
5.5
5.5
7.5
P52H11SM
P52H11SM
P52H11SM
Propeller
230+190
230+190
230+190
160
160
190
177
177
200
12.7 (Flare)
12.7 (Flare)
15.9 (Flare)
25.4 (Flange)
25.4 (Flange)
28.6 (Flange)

Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High
Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse
Phase Protector. Fuse.

1000

1000
Capillary Tube
50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
R22
R22
5.3 (Charged for 5m)
5.3 (Charged for 5m)
Refer to the name plate of compressor.
3.0
3.0
4D029964

1. 1 The above data are based on the following conditions.


Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

JIS B8616

LU

2.
3.
4.
5.
6.

5m
7.5m

60Hz, 220V
(380V)

1000
50 (Equivalent Length 70m)
30
R22
5.7 (Charged for 5m)
3.0
4D029966

Conversion Formulae

Cooling

(3)

120

45
(H)15 (L)11
24
6.4 (Flare)
15.9 (Flare)
I.D25O.D32

BYC125KW13

Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

FHYC50KVE3
R140LUTAL
R140LUYAL
16.1/15.8/
55,000/53,900/
13,800/13,500/
FHYC50KVE3
230840840
Cross Fin Coil
281.5
0.331
QTS45B14M

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 29CDB, 19.0CWB


60Hz, 220V
7.5m
SSA 385/386
KU
Outdoor : 46CDB, 24CWB
(380V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUTAL YAL)
2 Each value for indoor unit shows the specification per one unit.
BRC1B61 is also available.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHY (Ceiling Suspended Type) Twin


Model

Indoor Unit
Outdoor Unit

VAL
TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)

Indoor Unit 2
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Air Filter
Weight
Piping
Liquid
Connections
Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Outdoor Unit

Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model

Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

W
m/min
kg
mm
mm
mm

VAL
TAL
YAL
mm

m
VAL
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices
Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHY35BVE2
R71LUVAL

8.3/8.1
28,200/27,800
7,100/7,000
FHY35BVE2

FHY50BVE2
FHY60BVE2
R100LUVAL

R125LUTAL

R125LUYAL
11.6/11.4
14.5/14.3
39,700/38,900
49,600/48,800
10,000/9,800
12,500/12,300
FHY50BVE2
FHY60BVE2
White
195960680
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
2121.75
3121.75
3121.75
0.182
0.182
0.233
3D12K1AA1
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
62
(H)13 (L)10
(H)13 (L)10
(H)16 (L)13
Resin Net (with Mold Resistant)
23
24
26
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 5)
BRC7E66
R71LUVAL
R100LUVAL

R125LUTAL

R125LUYAL
Ivory
770900320
1,170900320
1,170900320
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2342.0
2522.0
2522.0
0.634
0.983
0.983
ZR36K3PFV
ZR47K3PFV

JT160BC

JT160BCYH
Hermetically Sealed Scroll Type
2.24
2.92
3.75
P47L11S
P47L11S
P47L11S2
Propeller
75
100
95+75
49
59
94
75
92
98
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
26.0 (Hole)
26.0 (Hole)
26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch <R125>. Low Pressure Switch.
Over Current Device. Motor Protector (Compressor) <R71 100>. Reverse Phase Protector (TAL YAL). Fuse.
1000
1000
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
2.8 (Charged for 30m)
3.7 (Charged for 30m)
3.7 (Charged for 30m)
Refer to the name plate of compressor.
1.2
1.2
1.5
4D039111

1. 1 The above data are based on the following conditions.

(1)
(2)
2.
3.
4.
5.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

Indoor : 27CDB, 19.0CWB


60Hz, 220V
5m
JIS B8616
Outdoor : 35CDB, 24CWB
(380V)
Capacities are net, including a deduction for cooling for indoor fan motor heat.
In case of drain piping for outdoor unit, drain piping kit (option) is needed.
2 Each value for indoor unit shows the specification per one unit.
Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

121

Specifications

ED21-301A

FHY (Ceiling Suspended Type) Twin


Model

Indoor Unit
Outdoor Unit

TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit 2
Color
Dimensions
HWD
Coil
Type
RowStagesFin Pitch
Face Area
Fan
Model
Type
Motor Output
Air Flow Rate
Air Filter
Weight
Piping
Liquid
Connections Gas
Drain
Remote Controller
Wired
(Option)
Wireless
Outdoor Unit
Color
Dimensions
Coil

Comp.

Fan

Weight
Piping
Connections

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate

mm

W
m/min
kg
mm
mm
mm

TAL
YAL
mm

m
TAL
YAL
kW

W
m/min
kg
mm
mm
mm

Liquid
Gas
Drain

Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Note:

%
m
m
kg
L

FHY71BVE2
R140LUTAL
R140LUYAL
16.1/15.8/
55,000/53,900/
13,800/13,500/
FHY71BVE2

FHY100BVE2
FHY125BVE2
R200KUTAL
R250KUTAL
R200KUYAL
R250KUYAL
22.5/22.2/20.0
27.1/26.6/24.1
76,800/75,800/68,300
92,500/90,800/82,300
19,400/19,100/17,200
23,300/22,900/20,700
FHY100BVE2
FHY125BVE2
White
1951,160680
1951,400680
1951,590680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.293
0.341
4D12K1AA1
3D12K2AA1
4D12K2AA1
Sirocco Fan
62
130
130
(H)17 (L)14
(H)24 (L)20
(H)30 (L)25
Resin Net (with Mold Resistant)
27
32
35
9.5 (Flare)
9.5 (Flare)
9.5 (Flare)
15.9 (Flare)
19.1 (Flare)
19.1 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 5)
BRC7E66
R140LUTAL
R200KUTAL
R250KUTAL
R140LUYAL
R200KUYAL
R250KUYAL
Ivory
1,345900320
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2602.0
2402.0
2502.0
1.134
1.57
1.97
JT170BC
JT212DP1
JT300DP1
JT170BCYH
JT212DP1YH
JT300DP1YH
Hermetically Sealed Scroll Type
4.50
5.5
7.5
P47L11S2
P52H11SM
P52H11SM
Propeller
100+75
230+190
230+190
101
160
190
109
177
200
9.5 (Flare)
12.7 (Flare)
15.9 (Flare)
19.1 (Flare)
25.4 (Flange)
28.6 (Flange)
26.0 (Hole)

Thermal Protector for Outdoor Fan


Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor.
Motor and Indoor Fan Motor. High
High Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor).
Pressure Switch. Low Pressure
Reverse Phase Protector. Fuse.
Switch. Over Current Device. Reverse
Phase Protector. Fuse.
1000
1000
1000
Electronic Expansion Valve
Capillary Tube
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
50 (Equivalent Length 70m)
30
30
30
R22
R22
R22
4.1 (Charged for 30m)
5.3 (Charged for 5m)
5.7 (Charged for 5m)
Refer to the name plate of compressor.
1.6
3.0
3.0
4D039112
4D028563
4D028564

1. 1 The above data are based on the following conditions.

Conversion Formulae

Cooling

Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

60Hz, 220V
(380V)

KU

7.5m

JIS B8616

LU

5m

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

60Hz, 220V
(3) Indoor : 29CDB, 19.0CWB
7.5m
SSA 385/386
KU
Outdoor : 46CDB, 24CWB
(380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUTAL YAL)
4. 2 Each value for indoor unit shows the specification per one unit.
5. Wire for remote controller : Field supplied.

122

SkyAir LU Series Cooling Only

ED21-301A

Specifications

FHY (Ceiling Suspended Type) Triple / Double Twin


Model

Indoor Unit
Outdoor Unit

TAL
YAL
kW
Btu/h
kcal/h

1 Cooling Capacity (1)/(2)/(3)

Indoor Unit
Color
Dimensions
Coil

Fan

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate

Liquid
Gas
Drain
Remote Controller
(Option)

Fan

Weight
Piping
Connections

mm

195960680

3121.75
0.182
3D12K1AA1

W
m/min

62
(H)13 (L)10

kg
mm
mm
mm

24
6.4 (Flare)
15.9 (Flare)
I.D20O.D26

TAL
YAL

R140LUTAL
R140LUYAL

mm

1,345900320

m
TAL
YAL

2602.0
1.134
JT170BC
JT170BCYH

Wired
Wireless

Outdoor Unit

Comp.

FHY71BVE3
R200KUTAL
R200KUYAL
22.5/22.2/20.0
76,800/75,800/68,300
19,400/19,100/17,200
FHY71BVE3

FHY50BVE4
R200KUTAL
R200KUYAL
22.5/22.2/20.0
76,800/75,800/68,300
19,400/19,100/17,200
FHY50BVE4

FHY60BVE4
R250KUTAL
R250KUYAL
27.1/26.6/24.1
92,500/90,800/82,300
23,300/22,900/20,700
FHY60BVE4

White

Air Filter
Weight
Piping
Connections

Color
Dimensions
Coil

FHY50BVE3
R140LUTAL
R140LUYAL
16.1/15.8/
55,000/53,900/
13,800/13,500/
FHY50BVE3

HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate
Liquid
Gas
Drain

kW

4.50
P47L11S2

W
m/min
kg
mm
mm
mm

100+75
101
109
9.5 (Flare)
19.1 (Flare)
26.0 (Hole)
Thermal Protector for
Outdoor Fan Motor and
Indoor Fan Motor. High
Pressure Switch. Low
Pressure Switch. Over
Current Device. Reverse
Phase Protector. Fuse.
1000
Electronic Expansion Valve
50 (Equivalent Length 70m)
30
R22
4.1 (Charged for 30m)

Safety Devices

Capacity Step
Refrigerant Control
Ref. Piping
Max. Length
Max. Height Difference
Refrigerant
Model
Charge (Factory Charge)
Ref. Oil
Model
Charge
Drawing No.

Nots:

%
m
m
kg
L

1.6
4D039112

1951,160680
195960680
1951,160680
Cross Fin Coil (Multi Louver Fins and Nhix Tubes)
3121.75
3121.75
3121.75
0.233
0.182
0.233
4D12K1AA1
3D12K1AA1
4D12K1AA1
Sirocco Fan
62
62
62
(H)17 (L)14
(H)13 (L)10
(H)16 (L)13
Resin Net (with Mold Resistant)
26
23
26
9.5 (Flare)
6.4 (Flare)
6.4 (Flare)
15.9 (Flare)
15.9 (Flare)
15.9 (Flare)
I.D20O.D26
I.D20O.D26
I.D20O.D26
BRC1C61 (Note. 5)
BRC7E66
R200KUTAL
R200KUTAL
R250KUTAL
R200KUYAL
R200KUYAL
R250KUYAL
Ivory
1,2201,280690
1,2201,280690
1,4401,280690
Cross Fin Coil (Waffle Louver Fins and HiXA Tubes)
2402.0
2402.0
2502.0
1.57
1.57
1.97
JT212DP1
JT212DP1
JT300DP1
JT212DP1YH
JT212DP1YH
JT300DP1YH
Hermetically Sealed Scroll Type
5.5
5.5
7.5
P52H11SM
P52H11SM
P52H11SM
Propeller
230+190
230+190
230+190
160
160
190
177
177
200
12.7 (Flare)
12.7 (Flare)
15.9 (Flare)
25.4 (Flange)
25.4 (Flange)
28.6 (Flange)

Thermal Protector for Compressor, Outdoor Fan Motor and Indoor Fan Motor. High
Pressure Switch. Low Pressure Switch. Over Current Relay (Compressor). Reverse
Phase Protector. Fuse.

1000

1000
Capillary Tube
50 (Equivalent Length 70m) 50 (Equivalent Length 70m)
30
30
R22
R22
5.3 (Charged for 5m)
5.3 (Charged for 5m)
Refer to the name plate of compressor.
3.0
3.0
4D028563

1. 1 The above data are based on the following conditions.


Piping Length

Hz, Volts

Standard

Model

(1)

Indoor : 27CDB, 19.5CWB


Outdoor : 35CDB, 24CWB

5m

60Hz, 220V
(380V)

LU, KU

(2)

Indoor : 27CDB, 19.0CWB


Outdoor : 35CDB, 24CWB

KU

JIS B8616

LU

5m

60Hz, 220V
(380V)

50 (Equivalent Length 70m)


30
R22
5.7 (Charged for 5m)
3.0
4D028564

Conversion Formulae

Cooling

7.5m

1000

kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3

: 29CDB, 19.0CWB
60Hz, 220V
(3) Indoor
7.5m
SSA 385/386
KU
Outdoor : 46CDB, 24CWB
(380V)
2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
3. In case of drain piping for outdoor unit, drain piping kit (option) is needed. (For R140LUTAL YAL)
4. 2 Each value for indoor unit shows the specification per one unit.
5. Wire for remote controller : Field supplied.

SkyAir LU Series Cooling Only

123

Dimensions and Service Space

ED21-301A

5. Dimensions and Service Space


5.1

Indoor Unit

5.1.1

FHYC (Ceiling Mounted Cassette Type)

FHYC35K + BYC125KW1
C
860~890 Ceiling opening

80

2 100=200

Unit (mm)

85

950

(165)

300 or less 680 Suspension position


420

Branch duct
connection

350
C

view
60

4-M4 Hole
(prepared hole)
7

80
80

40

860~890 Ceiling opening

950

780 Suspension position

10

55

55

55

840

80 2 100=200

12-M4 Hole
(prepared hole)

85

150

40
350

Branch duct
connection

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required space is
200mm or more.

1000 or more
Required space

30

260
270
315

165

95
110

295

For fresh air intake kit


connection
(direct installation type)

view

55

840

125
150
240

750

Adjustable (0~550)

200

10

240

Suspension
bolt
4-M8~M10

420

Note 3

40

230

view

160

7
A

Name
Number
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will


be a signal receiver. Refer to the drawing of wireless remote
controller in detail.

2. When installing an optional accessory, refer to the


installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.

5
6
7
8

Description
6.4 flare
12.7 flare
VP25

Remote control code and control


wiring connection

Air discharge grille

Air suction grille


Port for water supply
9 Corner decoration cover
10 Drain hose

O.D.32

C : 3D012310B

FHYC50K + BYC125KW1
FHYC60K + BYC125KW1
Unit (mm)

C
80

950

2 100=200 85
(165)

860~890 Ceiling opening


300 or less 680 Suspension position
420

9
10

Branch duct
connection

C view
60

4-M4 Hole
(prepared hole)
7

80

80

950

780 Suspension position


860~890 Ceiling opening

40
350

55

840

55

840
80

12-M4 Hole
(prepared hole)

260
270
315

40
350

Branch duct
connection

124

165
1000 or more
Required space

125
150
240
240

For fresh air intake kit


connection
(direct installation type)

55

2100=200 85

95
110

295

150

750
Adjustable (0~550)

55

200

230

B view

40

10

30
Suspension
bolt
4-M8~M10

420

Note 3

160

7
A view

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will


be signal receiver. Refer to the drawing of wireless remote
controller in detail.

2. When installing an optional accessory, refer to the


installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required space is
200mm or more.
Name
Number
1
Liquid pipe connection
Gas pipe connection
2
Drain pipe connection
3
Power supply connection
4
5

Remote control code and control


wiring connection

Air discharge grille


Air suction grille
Port for water supply
Corner decoration cover

7
8
9
10

Drain hose

Description
6.4 flare
15.9 flare
VP25

O.D.32

C : 3D012311B

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

FHYC71K + BYC125KW1
Unit (mm)

1000 or more

Note 3

4. When the temperature and humidity in the ceiling exceed 30C and RH 80% or
the fresh air is inducted into the ceiling or the unit continues 24 hour operation,
an additional insulation (thickness 10mm or more of glasswool or polyethylene
form) is required.

C : 3D012312C

FHYC100K + BYC125KW1
FHYC125K + BYC125KW1
Unit (mm)

950

2 100=200 85
(195)

80

860~890 Ceiling opening


300 or less 680 Suspension position

165

40
350

Branch duct
connection

C view
60

4-M4 Hole
(prepared hole)
7
5

80
80

950

780 Suspension position


860~890 Ceiling opening

10

155

420

160

7
A view

420

Note 3

260
270
315

14-M4 Hole
(prepared hole)

2 100=200 85

195

150

125
150
298
240

55

840
80

200

30
Suspension
bolt
4-M8~M10

55

40
50
155
165

55

840
295

40
350

Branch duct
connection

1000 or more
Required space

55

40

10

288

750
Adjustable (0~550)

B view

Notes:
1. Location of unit's Name Plate
For Main body : Switch Box cover inside surface of suction grille.
For decoration panel:Panel frame inside surface of suction grille.

3. In case of using wireless remote controller, this position will


be signal receiver. Refer to the drawing of wireless remote
controller in detail.

2. When installing an optional accessory, refer to the


installation drawings.
For fresh air intake kit ...... Inspection port is necessary.
For high efficiency filter unit ...... Inspection port is not necessary.

4. When the temperature and humidity in the ceiling exceed 30C


and RH 80% or the fresh air is inducted into the ceiling or the unit
continues 24 hour operation, an additional insulation (thickness
10mm or more of glasswool or polyethylene form) is required.

For fresh air intake kit


connection
(direct installation type)

1500mm or more
Required space
1500mm
or more

1500mm
or more

1500mm or more
When the discharge grill is closeout, the required is space
200mm or more.
Number
Name
1
Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection
4 Power supply connection
5
6
7
8
9
10

Description
9.5 flare
19.1 flare
VP25

Remote control code and control


wiring connection

Air discharge grille


Air suction grille
Port for water supply
Corner decoration cover
Drain hose

O.D.32

C : 3D012313C

SkyAir LU Series Cooling Only

125

Dimensions and Service Space

5.1.2

ED21-301A

FHYC with HighEfficiency Filter

KAFP556D80 557D80 for FHYC35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
JC : 3D032975C

KAFP556D160 557D160 for FHYC100~125K

Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
J : 3D032976C

126

SkyAir LU Series Cooling Only

ED21-301A

5.1.3

Dimensions and Service Space

FHYC with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FHYC35~71K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)

Refrigerant
Piping

Note 4

View
Service Access Panel :
450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


Note:1.When installing this kit, Service Access Panel is necessary.
(It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

How to connect Chamber 4


Independently(Refer to Note 5,6)

Connection chamber(Left)
Connection chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

5
4
3
2
1
Number

JC : 3D032981D

KDDP55D160 for FHYC100~125K

Unit (mm)

Service Access Panel :


450450mm or more
Refer to Note 2

Refrigerant
Piping

Note 4

View

Service Access Panel :


450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is
necessary. (It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name
JC : 3D032984D

SkyAir LU Series Cooling Only

127

Dimensions and Service Space

5.1.4

ED21-301A

FHYC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

KDDP55D160K for FHYC35~71K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

Service Access Panel :


450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel

T Joint
Plate Band (Accessory)

(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

JC : 3D032987D

KDDP55D160K for FHYC100~125K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

Service Access Panel :


450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel


Plate Band (Accessory)

T Joint
(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

J : 3D032990D

128

SkyAir LU Series Cooling Only

ED21-301A

5.1.5

Dimensions and Service Space

FHYC with Panel Spacer

KDBP55H160WA for FHYC35~71K


Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Description
JC : 3D005390E

KDBP55H160WA for FHYC100~125K


Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Description
JC : 3D005391D

SkyAir LU Series Cooling Only

129

Dimensions and Service Space

5.1.6

ED21-301A

FHY (Ceiling Suspended Type)

FHY35B
FHY50B
Unit (mm)

Model

FH(Y)35B FH(Y)50B

12.7

15.9

3D027536C
3D028600

FHY60B
FHY71B
Unit (mm)

130

Model

FH(Y)60B

FHY71B

6.4

9.5

3D027537
3D027538D

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

FHY100B
Unit (mm)

3D027539B

FHY125B
Unit (mm)

3D027540

SkyAir LU Series Cooling Only

131

Dimensions and Service Space

5.2

ED21-301A

Remote Controller

BRC7C613W (Wireless Type for FHYCK)


Unit (mm)

3D005912B

BRC7E66 (Wireless Type for FHYB)


Unit (mm)

3D028963

132

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

BRC1C61 (Wired Type)

More comfortable operation by


thermo sensor in the Remote Controller
Applicable Model
FHYCK
FHYB

Unit (mm)

C : 3D028952

SkyAir LU Series Cooling Only

133

Dimensions and Service Space

5.3

ED21-301A

Outdoor Unit

R71LU
Unit (mm)

3D039213

R100LU
Unit (mm)

3D039214

134

SkyAir LU Series Cooling Only

ED21-301A

Dimensions and Service Space

R125LU
Unit (mm)

3D039215

R140LU
Unit (mm)

3D039216

SkyAir LU Series Cooling Only

135

Dimensions and Service Space

ED21-301A

R200KU
Unit (mm)

3D029265

R250KU
Unit (mm)

3D029264

136

SkyAir LU Series Cooling Only

ED21-301A

5.4

Dimensions and Service Space

Installation Service Space for R71~140LU

3D039172-1

SkyAir LU Series Cooling Only

137

Dimensions and Service Space

ED21-301A

3D039172-2

138

SkyAir LU Series Cooling Only

ED21-301A

5.5

Dimensions and Service Space

Installation Service Space for R200 250KU

3D006578A

SkyAir LU Series Cooling Only

139

Piping Diagrams

ED21-301A

6. Piping Diagrams
6.1

Twin

3D039765

R71LU

140

SkyAir LU Series Cooling Only

ED21-301A

Piping Diagrams

3D039766

R100LU

SkyAir LU Series Cooling Only

141

Piping Diagrams

ED21-301A

3D039767

R125LU

142

SkyAir LU Series Cooling Only

ED21-301A

Piping Diagrams

3D039768

R140LU

SkyAir LU Series Cooling Only

143

Piping Diagrams

ED21-301A

3D030194

R200KU
R250KU

144

SkyAir LU Series Cooling Only

ED21-301A

6.2

Piping Diagrams

Triple

3D039769

R140LU

SkyAir LU Series Cooling Only

145

Piping Diagrams

ED21-301A

3D030195

R200KU

146

SkyAir LU Series Cooling Only

ED21-301A

6.3

Piping Diagrams

Double Twin

3D030196

R200KU
R250KU

SkyAir LU Series Cooling Only

147

Wiring Diagrams

ED21-301A

7. Wiring Diagrams
7.1

Indoor Unit

FHYC35KVE
FHYC50KVE
FHYC60KVE
FHYC71KVE
FHYC100KVE
FHYC125KVE

3D005668D

148

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

FHY35BVE
FHY50BVE
FHY60BVE
FHY71BVE
FHY100BVE
FHY125BVE

3D027502

SkyAir LU Series Cooling Only

149

Wiring Diagrams

7.2

Outdoor Unit

7.2.1

50Hz

ED21-301A

R71LUV1
R100LUV1

3D037640C

R71LUY1
R100LUY1

3D037642C

150

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

R125LUY1
R140LUY1

3D037644C

R200KUY1
R250KUY1

3D029091A

SkyAir LU Series Cooling Only

151

Wiring Diagrams

7.2.2

ED21-301A

60Hz

R71LUVAL
R100LUVAL

3D037935C

R125LUTAL
R140LUTAL

3D037936C

152

SkyAir LU Series Cooling Only

ED21-301A

Wiring Diagrams

R125LUYAL
R140LUYAL

3D037937C

R200KUTAL
R250KUTAL

3D029092

SkyAir LU Series Cooling Only

153

Wiring Diagrams

ED21-301A

R200KUYAL
R250KUYAL

3D029091A

154

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

8. Capacity Tables
8.1

50Hz

35 2 + R71LUV1
35 2 + R71LUY1

3D039614

50 2 + R100LUV1
50 2 + R100LUY1

3D039627A

SkyAir LU Series Cooling Only

155

Capacity Tables

ED21-301A

60 2 + R125LUY1

3D039636

50 3 + R140LUY1
71 2 + R140LUY1

3D039645

156

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

50 4 + R200KUY1
71 3 + R200KUY1
100 2 + R200KUY1

3D030166

60 4 + R250KUY1
125 2 + R250KUY1

3D030168

SkyAir LU Series Cooling Only

157

Capacity Tables

8.2

ED21-301A

60Hz

35 2 + R71LUVAL

3D039616

50 2 + R100LUVAL

3D039629

158

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

60 2 + R125LUTAL

3D039639

60 2 + R125LUYAL

3D039640

SkyAir LU Series Cooling Only

159

Capacity Tables

ED21-301A

50 3 + R140LUTAL
71 2 + R140LUTAL

3D039649

50 3 + R140LUYAL
71 2 + R140LUYAL

3D039653

160

SkyAir LU Series Cooling Only

ED21-301A

Capacity Tables

50 4 + R200KUTAL YAL
71 3 + R200KUTAL YAL
100 2 + R200KUTAL YAL

3D030167

60 4 + R250KUTAL YAL
125 2 + R250KUTAL YAL

3D030169

SkyAir LU Series Cooling Only

161

Capacity Tables

8.3

ED21-301A

Capacity Correction Factor by the Length of Refrigerant Piping


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
Reference Data
1. In case of piping length 5m (71~250)

Cooling capacity correction factor

100

95

90
200
100, 250
71
125

85

80
140
75

10

30
35
15
20
25
Length of refrigerant piping (Total length)

40

45

50 (m)
C : 3D006500C

2. In case of piping length 7.5m (71~140)

Cooling capacity correction factor

100

95

90

85

100
71
125

80

140

75

Note:

162

7.5 10

30
35
15
20
25
Length of refrigerant piping (Total length)

40

45

50 (m)

1.
line: Correction factor for cooling capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50 m, refer to the correction factor within the
range of its limitation.

SkyAir LU Series Cooling Only

ED21-301A

Operation Limits

9. Operation Limits
9.1

Operation Limits

R71LUV1 / R71LUY1 / R71LUVAL


R100LUV1 / R100LUY1 / R100LUVAL
R125LUY1 / R125LUTAL / R125LUYAL
R140LUY1 / R140LUTAL / R140LUYAL

3D039657

R200KUY1
R250KUY1

R200KUTAL / R200KUYAL
R250KUTAL / R200KUYAL

3D030170

SkyAir LU Series Cooling Only

163

Sound Level

ED21-301A

10. Sound Level


10.1

Overall Sound Level


dB(A)
Model

50Hz

60Hz

220V
FHYC35K
FHYC50K
FHYC60K
FHYC71K
FHYC100K
FHYC125K

240V

Measuring Location

220V

33
33
35
35
39
42

29
29
30
30
34
36

35
35
37
37
41
44

31
31
32
32
36
38

33
33
35
35
39
42

29
29
30
30
34
36

FHYC

4D013951

FHY35B
FHY50B
FHY60B
FHY71B
FHY100B
FHY125B

R71LU
R100LU
R125LU
R140LU

37
38
38
39
42
44

32
33
33
35
37
39

37
38
38
39
42
44

32
33
33
35
37
39

37
38
38
39
42
44

32
33
33
35
37
39

220 380V

240 415V

220V

48
49

49
50

49
51

380V

415V

220 380V

49
54

50
55

51
55

FHY

Microphone

4D028280A

R71~140LU

Microphone

4D039813

R200KU
R250KU

380V

415V

220 380V

60
61

61
62

60
61

R200 250KU

Microphone

4D027632

Note:

164

Operation sound is measured in an anechoic chamber.

SkyAir LU Series Cooling Only

ED21-301A

10.2

Sound Level

Octave Band Level

10.2.1 Indoor Unit


FHYC35KVE
FHYC50KVE

FHYC60KVE
FHYC71KVE

FHYC100KVE

2
H
H

H
H

H
L
L

L
L

L
4D006201B

4D006198A

FHYC125KVE

FHY35BVE

4D006205A

FHY50BVE

H
H

4D028280A

4D028281A

4D006206A

FHY60BVE

FHY71BVE

4D028282

FHY100BVE

4D028355A

4D028283A

FHY125BVE

4D028284A

Note:

SkyAir LU Series Cooling Only

220V, 380V
240V, 415V

165

Sound Level

ED21-301A

10.2.2 Outdoor Unit (50Hz)


R71LUV1
R71LUY1

R100LUV1
R100LUY1

4D039802

R140LUY1

R125LUY1

4D039804

R200KUY1

4D039806

R250KUY1

4D027634

4D027632

4D039808

10.2.3 Outdoor Unit (60Hz)


R71LUVAL

R100LUVAL

4D039810

R140LUTAL
R140LUYAL

R200KUTAL
R200KUYAL

Note:

4D039812

4D039811

4D039813

166

R125LUTAL
R125LUYAL

R250KUTAL
R250KUYAL

4D030106

4D030108

220V, 380V
240V, 415V

SkyAir LU Series Cooling Only

ED21-301A

Electric Characteristics

11. Electric Characteristics


11.1

50Hz
Unit Combination
Indoor

FHYC35KVE2 R71LUV1
FHY35BVE2

R71LUV1

FHYC35KVE2 R71LUY1
FHY35BVE2

R71LUY1

FHYC50KVE2 R100LUV1
FHY50BVE2

R100LUV1

FHYC50KVE2 R100LUY1
FHY50BVE2

R100LUY1

FHYC60KVE2 R125LUY1
FHY60BVE2

Power Supply

Outdoor

R125LUY1

Hz-Volts
50-220
50-230
50-240
50-220
50-230
50-240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-220
50-230
50-240
50-220
50-230
50-240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240

Comp

Voltage Range MCA TOCA MFA


19.6

23.8

30

19.2

23.8

30

Max. 50Hz
456/264V

8.3

9.3

15

Min. 50Hz
342/198V

8.3

9.3

15

24.9

28.0

40

24.9

28.0

40

Max. 50Hz
456/264V

10.4

12.0

15

Min. 50Hz
342/198V

10.4

12.0

15

Max. 50Hz
456/264V

12.8

15.5

20

Min. 50Hz
342/198V

12.8

15.5

20

Max. 50Hz 264V


Min. 50Hz 198V

Max. 50Hz 264V


Min. 50Hz 198V

LRA

RLA

82
78
75
82
78
75
40
38
37
40
38
37
114
109
105
114
109
105
50
48
46
50
48
46
51
53
56
51
53
56

14.2
13.6
13.0
14.2
13.6
13.0
5.2
4.9
4.7
5.2
4.9
4.7
18.3
17.5
16.7
18.3
17.5
16.7
6.7
6.4
6.1
6.7
6.4
6.1
8.1
8.1
8.2
8.1
8.1
8.2

OFM

IFM

kW

FLA

kW

FLA

0.065

0.6

0.0452 0.62

0.065

0.6

0.0622 0.62

0.065

0.6

0.0452 0.62

0.065

0.6

0.0622 0.62

0.09

0.8

0.0452 0.62

0.09

0.8

0.0622 0.62

0.09

0.8

0.0452 0.62

0.09

0.8

0.0622 0.62

0.065
+
0.085
0.065
+
0.085

0.6
+
0.7
0.6
+
0.7

0.0452 0.62
0.0622 0.62
3D039580

Unit Combination
Indoor

Outdoor

FHYC50KVE3 R140LUY1
FHYC71KVE2 R140LUY1
FHY50BVE3
FHY71BVE2

Power Supply

R140LUY1
R140LUY1

Hz-Volts
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240

Comp

Voltage Range MCA TOCA MFA

Max. 50Hz
456/264V

13.8

18.2

25

13.2

17.6

25

13.8

18.2

25

13.2

17.6

25

Min. 50Hz
342/198V

LRA

RLA

67
71
74
67
71
74
67
71
74
67
71
74

8.2
8.2
8.5
8.2
8.2
8.5
8.2
8.2
8.5
8.2
8.2
8.5

OFM
kW
0.065
+
0.090
0.065
+
0.090
0.065
+
0.090
0.065
+
0.090

FLA
0.6
+
0.8
0.6
+
0.8
0.6
+
0.8
0.6
+
0.8

IFM
kW

FLA

0.0453 0.63
0.0452 0.62
0.0623 0.63
0.0622 0.62
3D039580

Unit Combination
Indoor

FHYC100KVE2 R200KUY1
FHY100BVE2

R200KUY1

FHYC71KVE3 R200KUY1
FHY71BVE3

R200KUY1

FHYC50KVE4 R200KUY1
FHY50BVE4

R200KUY1

FHYC125KVE2 R250KUY1
FHY125BVE2

R250KUY1

FHYC60KVE4 R250KUY1
FHY60BVE4

Power Supply

Outdoor

R250KUY1

Hz-Volts
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240
50-380/220
50-400/230
50-415/240

Comp

Voltage Range MCA TOCA MFA


20.8

22.5

30

20.2

21.9

30

Max. 50Hz
456/264V

20.6

22.3

30

Min. 50Hz
342/198V

20.6

22.3

30

21.2

22.9

30

21.2

22.9

30

26.0

28.5

40

Max. 50Hz
456/264V

25.4

27.9

40

Min. 50Hz
342/198V

26.4

28.9

40

26.4

28.9

40

LRA

RLA

87
92
95
87
92
95
87
92
95
87
92
95
87
92
95
87
92
95
128
135
140
128
135
140
128
135
140
128
135
140

12.6
12.4
13.0
12.6
12.4
13.0
12.6
12.4
13.0
12.6
12.4
13.0
12.6
12.4
13.0
12.6
12.4
13.0
16.3
15.7
17.2
16.3
15.7
17.2
16.3
15.7
17.2
16.3
15.7
17.2

OFM
kW
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19

FLA
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2
1.3
+
1.2

IFM
kW

FLA

0.0902 1.02
0.1302 0.72
0.0453 0.63
0.0623 0.63
0.0454 0.64
0.0624 0.64
0.0902 1.02
0.1302 0.72
0.0454 0.64
0.0624 0.74
3D029999
3D030000

SkyAir LU Series Cooling Only

167

Electric Characteristics

11.2

ED21-301A

60Hz
Unit Combination
Indoor

Outdoor

Power Supply
Hz-Volts

Comp

Voltage Range MCA TOCA MFA

OFM

LRA

RLA

kW

FLA

IFM
kW

FLA

FHYC35KVE2 R71LUVAL

60-220

21.1

24.0

30

99

15.3

0.075

0.8

0.0452 0.62

FHY35BVE2

60-220

21.3

24.0

30

99

15.3

0.075

0.8

0.0622 0.72

25.7

28.1

40

143

18.9

0.1

0.9

0.0452 0.62

25.9

28.3

40

143

18.9

0.1

0.9

0.0622 0.72

0.075
+
0.095
0.075
+
0.095
0.075

0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9

R71LUVAL

FHYC50KVE2 R100LUVAL

60-220

FHY50BVE2

R100LUVAL

60-220

FHYC60KVE2 R125LUTAL

60-220

23.3

24.5

30

137

16.3

FHY60BVE2

R125LUTAL

60-220

23.5

24.7

30

137

16.3

FHYC60KVE2 R125LUYAL

60-380

14.4

15.5

20

66

9.2

FHY60BVE2

60-380

14.6

15.7

20

66

9.2

R125LUYAL

Max. 60Hz 242V


Min. 60Hz 198V

Max. 60Hz 418V


Min. 60Hz 342V

0.095
0.075
+

0.095

0.0452 0.62
0.0622 0.72
0.0452 0.62
0.0622 0.72
3D039581

Unit Combination
Indoor

Outdoor

Power Supply
Hz-Volts

Comp

Voltage Range MCA TOCA MFA

LRA

RLA

OFM

23.6

31.8

40

146

15.8

23.6

31.8

40

146

15.8

22.9

31.1

40

146

15.8

60-220

22.9

31.1

40

146

15.8

FHYC50KVE3 R140LUYAL

60-380

14.7

18.8

25

75

8.7

FHY50BVE3

R140LUYAL

60-380

14.7

18.8

25

75

8.7

FHYC71KVE2 R140LUYAL

60-380

14.0

18.1

25

75

8.7

FHY71BVE2

60-380

14.0

18.1

25

75

8.7

FHYC50KVE3 R140LUTAL

60-220

FHY50BVE3

R140LUTAL

60-220

FHYC71KVE2 R140LUTAL

60-220

FHY71BVE2

R140LUTAL

R140LUYAL

Max. 60Hz 242V


Min. 60Hz 198V

Max. 60Hz 418V


Min. 60Hz 342V

kW
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100
0.075
+
0.100

FLA
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9
0.8
+
0.9

IFM
kW

FLA

0.0453 0.73
0.0623 0.73
0.0452 0.72
0.0622 0.72
0.0453 0.73
0.0623 0.73
0.0452 0.72
0.0622 0.72
3D039581

168

SkyAir LU Series Cooling Only

ED21-301A

Electric Characteristics

Unit Combination
Indoor

Power Supply

Outdoor

Hz-Volts

Comp

Voltage Range MCA TOCA MFA

LRA

RLA

FHYC50KVE4 R200KUTAL

60-220

35.5

39.2

50

161

23.4

FHY50BVE4

R200KUTAL

60-220

35.5

39.2

50

161

23.4

FHYC71KVE3 R200KUTAL

60-220

Max. 60Hz 242V 34.8

38.5

50

161

23.4

Min. 60Hz 198V

R200KUTAL

60-220

34.8

38.5

50

161

23.4

FHYC100KVE2 R200KUTAL

60-220

34.7

38.4

50

161

23.4

FHY100BVE2

60-220

34.7

38.4

50

161

23.4

FHYC50KVE4 R200KUYAL

60-380/220

23.2

24.2

30

81

13.6

FHY50BVE4

60-380/220

23.2

24.2

30

81

13.6

FHYC71KVE3 R200KUYAL

60-380/220 Max. 60Hz


418/242V

22.5

23.5

30

81

13.6

FHY71BVE3

R200KUYAL

60-380/220

Min. 60Hz
342/198V

22.5

23.5

30

81

13.6

FHYC100KVE2 R200KUYAL

60-380/220

22.4

23.4

30

81

13.6

FHY100BVE2

60-380/220

22.4

23.4

30

81

13.6

FHYC60KVE4 R250KUTAL

60-220

41.1

52.2

60

225

27.9

FHY60BVE4

R250KUTAL

60-220

41.1

52.2

60

225

27.9

FHYC125KVE2 R250KUTAL

60-220

40.3

51.4

60

225

27.9

FHY125BVE2

60-220

40.5

51.6

60

225

27.9

FHYC60KVE4 R250KUYAL

60-380/220

27.8

30.2

40

107

17.3

FHY60BVE4

60-380/220 Max. 60Hz

27.8

30.2

40

107

17.3

FHY71BVE3

R200KUTAL

R200KUYAL

R200KUYAL

R250KUTAL

R250KUYAL

Max. 60Hz 242V


Min. 60Hz 198V

418/242V

FHYC125KVE2 R250KUYAL

60-380/220 Min. 60Hz

27.0

29.4

40

107

17.3

FHY125BVE2

60-380/220

27.2

29.6

40

107

17.3

R250KUYAL

342/198V

OFM
kW
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19
0.23
+
0.19

FLA
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6
1.8
+
1.6

IFM
kW

FLA

0.0454 0.74

0.0624 0.74
0.0453 0.73
0.0623 0.73
0.0902 1.02
0.1302 1.02
0.0454 0.74
0.0624 0.74
0.0453 0.73
0.0623 0.73
0.0902 1.02
0.1302 1.02
0.0454 0.74
0.0624 0.74
0.0902 1.02
0.1302 1.12
0.0454 0.74
0.0624 0.74
0.0902 1.02
0.1302 1.12
3D029999
3D030000

Symbols:

Note:

MCA : Min. Circuit Amps


TOCA : Total Over-Current Amps
MFA : Max. Fuse Amps (See note 7)
LRA : Locked Rotor Amps
RLA : Rated Load Amps
OFM : Outdoor Fan Motor
FLA : Full Load Amps
IFM : Indoor Fan Motor
kW : Fan Motor Rated Output
1. RLA is based on the following conditions.
Indoor temp. 27CDB/19.0CWB
Outdoor temp. 35CDB
2. TOCA means the total value of each OC set.
3. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above the range listed.
4. Maximum allowable voltage unbalance between phases is 2%.
5. MCA/MFA
MCA = 1.25 RLA + ea. FLA
MFA 2.25 RLA + ea. FLA
(Next lower standard fuse rating, Min. 15A)
6. Select wire size based on the larger value of MCA or TOCA.
7. MFA
Instead of fuse, use circuit breaker.

SkyAir LU Series Cooling Only

169

Option List

ED21-301A

12. Option List


12.1

Indoor Unit

FHYCK
Name of Option

Kit Name

Remark

35~71K

100~125K

Decoration Panel

BYC125KW1

Sealing Member of Air Discharge Outlet

KDBHJ55K160

Panel Spacer

KDBP55H160WA

Fresh Air Intake Kit 4

Chamber Type

Without T Joint

KDDP55D160

With T Joint

KDDP55D160K

Direct Installation Type

KDDJ55X160

Chamber Connection Kit 5


HighEfficiency Filter

KKSJ55K160
(Colorimetric Method 65%)

KAFP556D80

KAFP556D160

(Colorimetric Method 90%)

KAFP557D80

KAFP557D160

Replacement HighEfficiency (Colorimetric Method 65%)


Filter
(Colorimetric Method 90%)

KAFP552H80

KAFP552H160

KAFP553H80

KAFP553H160

HighEfficiency Filter Chamber

KDDFP55D160

Replacement LongLife Filter Resin Net (Gravimetric Method 50%)

KAFJ551K160

Ultra LongLife Filter

KAFP55D160

Replacement Ultra LongLife Filter

KAFJ55K160H

Branch Duct Chamber

KDJ55K80

Remote Controller

KDJ55K160

Wired Type 3

BRC1C61 (Note. 6)

Wireless Type

BRC7C613W

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring (Interlock for Fresh Air Intake Fan) 1

KRP1B57

Wiring Adaptor for Electrical Appendices 1

KRP4A53

Interface Adaptor for SkyAir Series

DTA102A52

Installation Box for Adaptor PCB

KRP1B98
C : 3D006559E

FHYB
Name of Option

Remark

Kit Name
35B

50B

60B

71B

100B

125B

Replacement LongLife Filter

KAFJ501D56

KAFJ501D80

KAFJ501D112 KAFJ501D160

Drain Pump Kit

KDU50B50VE

KDU50B71VE

KDU50B125VE

LType Piping Kit

For Upward Direction KHFJ5F50

Remote Controller Wired Type 3


Wireless Type

KHFJ5F60

KHFJ5F80
BRC7E66

Set Back Time Clock

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring

KRP1B54

Wiring Adaptor for Electrical Appendices 2

KRP4A52

Interface Adaptor for SkyAir Series


Installation Box for Adaptor PCB

KHFJ5F160

BRC1C61

DTA102A52
KRP1C93
C : 3D028285A

Note:

170

1.
2.
3.
4.
5.
6.

1 : Installation box for adaptor PCB (KRP1B98) is necessary.


2 : Installation box for adaptor PCB (KRP1C93) is necessary.
3 : Wire for Remote Controller : Field supplied.
4 : Refer to the Option Handbook for the detail.
5 : When using the filter (HighEfficiency Filter or Ultra LongLife Filter) and the Fresh Air Intake Kit together, this kit is necessary.
BRC1B61 is also available.

SkyAir LU Series Cooling Only

ED21-301A

12.2

Option List

Outdoor Unit

12.2.1 R71~140LU, R200 250KU


Name of Option

Remark

Kit Name
R71LU

R100LU

Central Drain Plug


Refrigerant
Branch Piping
Kit

For Twin Multi

R140LU

R200KU

KKPJ5F180
KHR58C21

For Triple
Multi

KHD58D33

KRK5F80V1

KRK5F140V1

R250KU

KHD58C21A

For Double
Twin Multi
YearRound Cooling Kit

R125LU

KRK5F160V1

KHD58C23A KHD58C24A
KHR58P322H

KHRJ5F224F

KHRJ5F280F

3D039655
4D029784A

SkyAir LU Series Cooling Only

171

Field Piping and Wiring

ED21-301A

13. Field Piping and Wiring


13.1

Field Piping

13.1.1 Maximum Allowable Piping Length and Difference


R71~140LU
Maximum Allowable Pipe Length
[Parenthesized Figure Represents
Equivalent Length]

Maximum Allowable Level Difference

50 m (70 m)
The total one-way pipe length should
be within 60 meters.

30 m
The level difference between the
indoor units should be 0.5 m.

Simultaneous operation system


Branched pipe

Main pipe
1PN05248B-1

R200 250KU

1PN04787B-1

172

SkyAir LU Series Cooling Only

ED21-301A

Field Piping and Wiring

13.1.2 Additional Refrigerant Charge & Recharging Refrigerant


R71~140LU
This unit requires additional charging of refrigerant according to the length of pipe connected at the site.
When the entire refrigerant pipe length is within 30 meters, the additional charging is not needed.
Take the following steps for proper charging.
When connected to two indoor units
(simultaneous operation system)

When connected to three indoor units


(simultaneous operation system)

Branched pipe
(L2)

Branched pipe (L2)

Branched pipe (L3)

Branched pipe (L3)


Main
pipe
(L1)

Main
pipe
(L1)

One-way length of pipe (L): L1+L2+L3

Branched
pipe (L4)

One-way length of pipe (L): L1+L2+L3+L4

1. Refrigerant charge amount


Additional charging of refrigerant
Select the amount of refrigerant which matches a length which exceeds the charge-less length, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.

FOR SIMULTANEOUS OPERATION SYSTEM


Find the entire pipe length by totaling that of each pipe in the order of the main pipe (L1), and branched
pipes (L2), (L3), (L4), calculate the excess length going over 30 meters, then select from Table 1 the
amount of refrigerant corresponding to the excess length.
The total value is tha amount required for additional charging.
The maximum allowable pipe length is 50 meters. Make the total refrigerant pipe length come within 60
meters. The maximum allowable pipe length here means the total length of the main pipe and the
branched pipe (the longer one of the two branched pipes).
Table 1 Additional charging amount

<Unit : kg>

Pipe excess length over 30 meters

10 m or less
Main pipe

Cooling only type

Liquid pipe

Branched pipe

20 m or less

9.5

0.25

0.50

9.5

0.25

0.50

6.4

0.15

0.30

2. Recharging refrigerant
When the entire refrigerant pipe length is within 30 meters, charge the refrigerant in accordance with the
amount mentioned on the nameplate, and when the pipe length exceeds 30 meters, the charging amount is
an addition of the amount stated on the nameplate and the additional charging amout.
1PN05248B-2

SkyAir LU Series Cooling Only

173

Field Piping and Wiring

ED21-301A

R200 250KU

1PN04788A-1

174

SkyAir LU Series Cooling Only

ED21-301A

Field Piping and Wiring

13.1.3 Pumping-down Operation Method


R71~140LU
The outdoor unit is equipped with a low-pressure switch to protect the compressor.
Take the following steps to perform the pumping-down operation.
Caution:

Never short-circuit the low-pressure switch in this operation.


Procedure
1. Start the fan operation with the remote controller.

Precautions
Confirm that stop valves both on the liquid and gas side
are open. Take care when the procedure 2 is done first
because the indoor unit fan may operate automatically.

2. Push the pumping-down button on the PC board of the Compressor and outdoor fan will start operation
outdoor unit.
automatically.
3. Continue operation for 1 min. until operation condition
stabilizes.
4. Close the stop valve on the liquid side securely.
(Refer to Fig. 1)

Insecure closing of the valve may result in burning of


the compressor.

5. When the low-pressure switch is activated, the unit


stops working. At this time, close the stop valve on the
gas side.

This is the end of pumping-down operation.


After pumping-down operation, the remote controller shows U4 even when ON button on the remote
controller is pressed, and it will not operate. Although the remote controller may or may not indicate U4
according to circumstances at this time, it is normal. When the remote controller indicates U4, the indoor
unit fan may operate (for about max 30 minutes). Turn off the main power supply switch and turn it on again
in need of operation.
How to use the stop valve (Refer to Fig. 1)
Have a hex wrench ready. (4 mm and 6 mm)
(Gas side)
Opening direction
1. Open the valve.
(Liquid side)
a. Place the hex wrench on the valve bar and turn counter-clockwise. Opening
direction
b. Stop when the valve bar no longer turns. It is now open.
2. Close the valve.
a. Place the hex wrench on the valve bar and turn clockwise.
b. Stop when the valve bar no longer turns. It is now closed.
Fig. 1

15m

Trap installation spacing


Necessity of a trap
Since there is fear of the oil held inside the riser
Indoor unit
piping flowing back into the compressor when
Oil trap
stopped and causing liquid compression
Gas piping
phenomenon, or cases of deterioration of oil return,
it will be necessary to provide a trap at an
Liquid piping
appropriate place in the riser gas piping.
Marks. Install trap at
each difference in
height 15m.
Outdoor unit

Note:

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
Caution to be taken when brazing refrigerant piping
Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g. BCuP -1 to 5 : between 700 and 800C) which causes pin holes and results in refrigerant
leakage.

1PN05248B-3

SkyAir LU Series Cooling Only

175

Field Piping and Wiring

ED21-301A

R200 250KU

Caution to be taken when brazing refrigerant piping


Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux. (Flux
has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is
used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g . BCuP -1 to 5 : between 700 and 800C) which causes pin holes and results in refrigerant
leakage.

1PN04788A-2
1PN04787B-2

176

SkyAir LU Series Cooling Only

ED21-301A

13.2

Field Piping and Wiring

Field Wiring

13.2.1 R71LU (V1 Y1 VAL), R100LU (V1 Y1 VAL), R125LU (Y1 TAL YAL), R140LU (Y1 TAL YAL)

C : 4D001694A
C : 4D006674A

SkyAir LU Series Cooling Only

177

Field Piping and Wiring

ED21-301A

13.2.2 R200 250KU (Y1 TAL YAL)

3D029782

178

SkyAir LU Series Cooling Only

ED21-301A

Detail Information of Options


SkyAir LU Series

Note : Refer to VRV Option Handbook (OH041) Concerning about


the manual for the following Central Control Kits.
Interface Adaptor for SkyAir Series
DTA102A52
Central Remote Controller
DCS302C61
Unified ON/OFF Controller
DCS301B61
Schedule Timer
DST301B61

SkyAir LU Series

179

Remote Controller

ED21-301A

1. Remote Controller
1.1

Remote Controller, Timer, Adaptor List


Name of Option

Model Series
FH(Y)CK

Remote
Wireless C/O BRC7C613W
Controller
H/P BRC7C612W
Wired

FH(Y)KF(J)

FH(Y)BF

FUYFJ

FH(Y)B

FAY71L

FAY100FA

FV(Y)LA

BRC7C529W

BRC7E66

BRC7E619

BRC7C611W

BRC7C528W

BRC7E63W

BRC7E618

BRC7C610W

C/O
BRC1C61

H/P
Set Back Time Clock

BRC1C61
(Available for 2
remote control use)

BRC15A61

Central Remote Controller

DCS302C61

Unified ON/OFF Controller

DCS301B61

Schedule Timer

DST301B61

intelligent Touch Controller

DCS601C51

Adaptor for Wiring

KRP1B57

KRP1B51

KRP1B54

KRP1B54

KRP1B57

Wiring Adaptor for


Electrical Appendicies

KRP4A53

KRP4A51

KRP4A51

KRP4A53

KRP4A52

KRP4A51

KRP4A51

KRP4A52

Interface Adaptor for


SkyAir Series
Installation Box for Adaptor
PCB

DTA102A52
KRP1B98

KRP1B97

KRP1C93

KRP4A93

DTA102A52

KRP4A95

Installation Box for Adaptor PCB is necessary.

1.2

Wired Remote Controller

BRC1C61

Operation Functions with HRV


BRC1C61
ON / OFF Operation with Air Conditioner
{
Independent operation in intermediate season
{
Ventilation mode change over (Auto / HRV / Normal)
{
Air flow change over (Auto / High / Low)
{
Setting of precooling / preheating

Setting of fresh-up operation

Filter sign display


{
: Initial Setting Only (Field setting by well known service person)

180

SkyAir LU Series

ED21-301A

Remote Controller

5 12

3
7

hr

6
8

hr

NOT
AVAILABLE

TEST

9
11
10
13
21

L H

14

20
TEST

16

1
2

19

15

17

18

ON/OFF BUTTON
Press the button and the system will start.
Press the button again and the system will stop.
OPERATION LAMP (RED)
The lamp lights up during operation.
DISPLAY
(UNDER CENTRALIZED
CONTROL)
When this display shows, the system is UNDER
CENTRALIZED CONTROL.
DISPLAY

(VENTILATION/AIR CLEANING)
This display shows that the total heat exchange
and the air cleaning unit are in operation
(These are optional accessories).

DISPLAY
(OPERATION MODE)
This display shows the current OPERATION
MODE. For cooling only type,
(Auto)
and (Heating) are not installed.

DISPLAY
TEST (INSPECTION/TEST
OPERATION)
When the INSPECTION/TEST OPERATION
BUTTON is pressed, the display shows the
system mode is in.
hr

DISPLAY

(PROGRAMMED TIME)

22

3PA59583-16Z-1

12

DISPLAY

(DEFROST)

NON-FUNCTIONING DISPLAY
If that particular function is not available, pressing
the button may display the words NOT
AVAILABLE for a few seconds.
When running multiple units simultaneously the
13 NOT AVAILABLE message will only be appear
if none of the indoor units is equipped with the
function. If even one unit is equipped with the
function, the display will not appear.
14
15

TIMER MODE START/STOP BUTTON


TIMER ON/OFF BUTTON

INSPECTION/TEST OPERATION BUTTON


16 This button is used only by qualified service
persons for maintenance purposes.
PROGRAMMING TIME BUTTON
17 Use this button for programming START and/or
STOP time.
TEMPERATURE SETTING BUTTON
18
Use this button for SETTING TEMPERATURE.
FILTER SIGN RESET BUTTON
19

hr

This display shows the PROGRAMMED TIME


of the system start or stop.
8

DISPLAY
(SET TEMPERATURE)
This display shows the set temperature.

DISPLAY
(FAN SPEED)
This display shows the set fan speed.

DISPLAY

FAN SPEED CONTROL BUTTON


20 Press this button to select the fan speed,
HIGH or LOW, of your choice.
OPERATION MODE SELECTOR BUTTON
21
Press this button to select OPERATION MODE.
AIR FLOW DIRECTION ADJUST BUTTON
22

(AIR FLOW FLAP)

10

NOTE

11

For the sake of explanation, all indications are shown


on the display in the above figure contrary to actual
running situations.

DISPLAY

(TIME TO CLEAN AIR FILTER)

3PA59583-16Z-2

SkyAir LU Series

181

Remote Controller

ED21-301A

Installation

182

SkyAir LU Series

ED21-301A

Remote Controller

SkyAir LU Series

183

Remote Controller

Note:

ED21-301A

1. Setting is carried out in the group mode, however, set the mode number inside the ( ) for individual
setting of the each indoor unit or confirmation after setting.
2. The SECOND CODE number is set to 01 when shipped from the factory.
However for the following cases it is set to 02.
Air flow direction range setting.
3. Do not make any settings not given in the table above.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, 88 may be displayed in the LCD in order for the remote controller
to initialize itself.
2P068938-1-3

184

SkyAir LU Series

ED21-301A

1.3

Remote Controller

Wireless Remote Controller

Names and Functions


Name of Option

Model Series
FH(Y)CK

FH(Y)KF(J)

FH(Y)BF

FUYFJ

FH(Y)B

FAY71L

FAY100FA

FV(Y)LA

BRC7C529W

BRC7E66

BRC7E619

BRC7C611W

BRC7C528W

BRC7E63W

BRC7E618

BRC7C610W

Remote
Wireless C/O BRC7C613W
Controller
H/P BRC7C612W

1-1
1
ON OFF

1-2
H

DOWN

10

ON OFF

UP

TEMP

FAN

L TIME

11

hr.

UP

hr.

FAN

DOWN

13

RESERVE CANCEL

hr.

TIMER

12

MODE

15

hr.

TEST

7
SWING

14
16

TEST
TEST

17

3PA63363-21T-1

Explanation of Receiver
FH(Y)CK

FAY71L

FAYFA

20

21

19

18

23

22

3PA63363-25Z

FUYFJ

FH(Y)B

22

19

21 20

23

18

3PA63363-21T-2

SkyAir LU Series

185

Remote Controller

ED21-301A

DISPLAY
(SIGNAL
TRANSMISSION)
1
This lights up when a signal is being
transmitted.
DISPLAY

(OPERATION MODE)

M L

(SET TEMPERATURE)

10

11

12

AIR FLOW DIRECTION ADJUST


14 BUTTON

15

16

This display shows the set temperature.


hr.
DISPLAY hr.

(PROGRAMMED TIME)

This display shows PROGRAMMED


TIME of the system start or stop.
5

DISPLAY

TIMER RESERVE/CANCEL BUTTON

2 This display shows the current OPERATION MODE. For straight cooling
type,
(Auto) and (Heating)
are not installed.
DISPLAY

13

17

18

(AIR FLOW FLAP)

DISPLAY

(FAN SPEED)
The display shows the set fan speed.
TEST
DISPLAY
(INSPECTION/ TEST OPERATION)
When the INSPECTION/TEST OPERATION BUTTON is pressed, the display
shows the system mode is in.
ON/OFF BUTTON
Press the button and the system will
start. Press the button again and the
system will stop.
FAN SPEED CONTROL BUTTON
Press this button to select the fan
speed, HIGH or LOW, of your choice.
TEMPERATURE SETTING BUTTON
Use this button for SETTING TEMPERATURE. (Operates with the front cover
of the remote controller closed.)
PROGRAMMING TIMER BUTTON
Use this button for programming
START and/or STOP time. (Operates
with the front cover of the remote controller opened.)
TIMER MODE START/STOP BUTTON

19

20

21

22

23

OPERATION MODE SELECTOR


BUTTON
Press this button to select OPERATION
MODE.
FILTER SIGN RESET BUTTON
Refer to the section of MAINTENANCE
in the operation manual attached to the
indoor unit.
INSPECTION/TEST OPERATION
BUTTON
This button is used only by qualified
service persons for maintenance
purposes.
EMERGENCY OPERATION SWITCH
This switch is readily used if the remote
controller does not work.
RECEIVER
This receives the signals from the
remote controller.
OPERATING INDICATOR LAMP
(Red)
This lamp stays lit while the air
conditioner runs. It flashes when the
unit is in trouble.
TIMER INDICATOR LAMP (Green)
This lamp stays lit while the timer is set .
AIR FILTER CLEANING TIME
INDICATOR LAMP (Red)
Lights up when it is time to clean the air
filter.
DEFROST LAMP (Orange)
Lights up when the defrosting operation has started. (For straight cooling
type this lamp does not turn on.)

3PA63363-21T-3

186

SkyAir LU Series

SkyAir LU Series

Control by Remote Controller

For the control of


plural indoor
units on a floor
at the same time

For above
control from
distant place

Operation of
other equipment
combined with
the operation of
indoor unit

Group control

Group control by
2 remote
controllers

Combining
control by
remote controller

Note 1

BRC1C61

Unit Name and


Model
Outline of System

Operates HRV in accordance with


indoor unit operation.

Operational functions
Start/Stop (ON/OFF)
Temperature setting
Timer setting (Settings in units of
1 hour up to a maximum of 72
hours)
Air flow setting
Air flow direction adjustment
(Swing flap)
Indication function
Operating display
Program dry function display
Defrost/Hot start display
Filter sign
Temperature setting display
Timer display
Air flow display
Abnormal operation display
In case of group control all the
indoor units in the system are set
to the same value and each unit is
controlled individually by its
internal thermostat. (Not by the
thermostat equipped in remote
controller)
In command by double remote
controls, the most recent one
takes priority. (Selection between
master and slave controller is
essential)
According to indoor units model,
some models cannot be set.

Function

Same as the number


of units controlled by
remote controller

2 remote controllers
control up to 16
indoor units from 2
different places
simultaneously

1 remote controller
controls up to 16
indoor units
simultaneously

2 remote controllers
control 1 indoor unit

1 remote controller
controls 1 indoor unit

Standard Number of
Units

(S1015)

Note:
1. These figures above show the system using wired remote controllers. Wireless remote controller replaced for wired remote controller can be used for same control.
2. In control by two remote controllers, one of two remote controllers must be a wired remote controller. Two wireless remote controllers must not be used.
3. Wiring from a wireless remote controller to the receiver can be lengthened to 200m in maximum.

For control from


2 places (distant
or local)

For control from


distant place

Remote
operation of
remote controller

2 remote control
Note 2

Example of
typical use

Objective / Use

1.4

Local operation
of remote
controller

Control Method

ED21-301A
Remote Controller

Various Control by Liquid Crystal Remote Controller


For more effective localized environmental control Daikin offers various control systems such as single or
double remote control or centralized control. This enables the construction of a variety of operational
control systems which can be adapted for various uses from remote control.

187

Set-back Time
Clock

Desired Weekly
Scheduled
Operation of ON/
OFF and
Temperature's
Set-back

BRC15A61

188
Set-back time clock

Set-back time clock

Remote controller

Remote controller

Be sure to provide a master


remote controller. This
scheduled operation cannot be
used in both cases at control by
two remote controllers and at
the connection of a group
remote control adapter.

Display function
Effective/ineffective control on
the program
The present time and the week
day
Daylight-saving time setting
Setting holidays in a week
Display of operation
mode(heating/cooling)
Usual setting temperature
(Cooling/Heating is linked to a
remote controller)
ON/OFF time setting for a day
Set-back time setting for a day

Control function
Effective/ineffective control on
the program
Daylight-saving time
The present time adjustment
Weekly operation time program
(two times a day in max.
frequency by a unit of 30 min.)
Weekly set-back operation time
program (two times a day in
max. frequency by a unit of 30
min.)
Program of setting temperature
for normal/set-back control
(each one kind for cooling and
heating . The operation mode
is linked to the remotecontroller).
Elimination of the time in an
operation of a day and a setback operation.

Max. 16 groups under


simultaneous control
by one set-back time
clock

One indoor unit control


by one set-back time
clock

(S1018)

Remote Controller
ED21-301A

SkyAir LU Series

Scheduled Control

SkyAir LU Series

Adaptor for
connection with
optional
controllers for
centralized
control

Schedule
timer
Central
remote
controller
Unified ON/
OFF
controller

Unified ON/OFF
controller

Central remote
controller

Schedule timer

For controlling
all indoor units
from one place

For carrying out


weekly schedule
operation by
1-minute units

Interface
adaptor for
SkyAir series
DTA102A52

DCS301B61

DCS302C61

DST301B61

DCS301B61

DCS302C61

DST301B61

Controls up to 64
groups of indoor units
with one central remote
controller.

Controls up to 16
groups of indoor units
with one unified ON/
OFF controller.

Controls up to128
groups (Max. 128
indoor units) with one
schedule timer, two
central remote
controller and eight
unified ON/OFF
controllers.

Double central control function


Function of liquid crystal remote
controller can be controlled
individually for each zone of the
indoor unit.
Individual/unified operation
Up to 8 patterns can be set for
operation controlled by
programmed time when used in
combination with schedule
timer.
Temperature setting for each
zone
Control operation for each room
during centralized control
Remote controller operation
rejected command
Sequential start function
Double central control function
Indoor unit ON/OFF control
Individual/unified operation
Remote controller operation
rejected command (Central
remote controller given priority
when used in combination with
central remote controller.)
Sequential start function

Respective functions of
schedule timer, central remote
controller and unified ON/OFF
controller are possible. (Control
mode of central remote
controller is given priority for
operation of remote controller
for indoor unit.)

Unification adaptor for


computerized control allows
you to simultaneously turn
indoor units connected to the
central remote controller on or
off or display at the central
monitor panel, etc.
Interface adaptor for SkyAir
series is for connection of
optional controllers for
centralized control.

Simultaneously
controls 128 groups
with one schedule
timer.

ON/OFF time can be set by


units of day, hour and minute;
ON/OFF pattern can be set by
time zone of twice per day in
accordance with application.

(S1016)

ED21-301A
Remote Controller

189

Central Control

For control by
operation
command from
building control
room

Wiring adaptor
for electrical
appendices

Adaptor for
wiring

When controlling
operation with
optional
accessories
added inside
indoor units, the
status is
displayed
outside.

Objective / Use

Remote Control

Wiring Modification

190

Control Method

Built into indoor


unit
KRP1B5154
57

KRP4A5152
53
Built into indoor
unit

With remote
temperature
setting

Unit Name and


Model

Group Unified Control (Controls group controlled indoor units all at once and simultaneously.)

Individual Control (Controls Indoor Units Individually.)

Outline of System

Operation display signal and


compressor operation signal are
supplied.

For group unified control, the


setting becomes the same for all
connected indoor units, and each
indoor unit is controlled
individually by built-in thermostat.

1 adaptor controls
the electric heater.

1 PC board
simultaneously
controls 16 group of
indoor units.

1 PC board controls
1 indoor unit.

Normally open or momentary


open type contactor
DC12~24V or no-voltage
Various control methods available
by mode select switch
Voltage, no-voltage selector
switch
Alarm and operation display
signal (no-voltage)
Selector switch of zone/individual
of alarm display
Remote temperature setting
(resistance input of 0~135)
Selector switch for remote
controller temperature setting
enable/inhibit

Standard Number of
Units

Function

(S1017)

Remote Controller
ED21-301A

SkyAir LU Series

ED21-301A

1.5

Remote Controller

BRC15A61 Set Back Time Clock

Specifications
Display of time

12hour degital dIsplay

Clock cycle type

Quartz clock type

Clock accuracy

Within 30 sec./month (environmental temperature from 15C to 35C)

Timer programming

Two pairs of programmed time for both system start and system off can be set in units of
30 minutes.

Power failure compensation time

Approximately 1 hour for a single occurrence of power failure (clock with No. of
programmed time)

Size

120(W) 120(H) 17(D) mm


(Width/Height/Depth)

Outline Drawings
120

MON TUE WED THU FRI SAT SUN

PROGRAM
OFF OFF OFF OFF OFF OFF OFF

SUMMER TIME

MON TUE WED THU FRI SAT SUN CLOCK

AM
PM

0 2 4 6 8 10 12 14 16 18 20 22 24

ON/OFF

SET BACK

PROGRAM

ON/OFF
SET BACK

OK

DAY OF
THE WEEK

SUMMER
TIME

DAY OFF

CLOCK

120

C 0 2 4 6 8 10 12 14 16 18 20 22 24

CLEAR

Specifications and appearance are subject to change without notice.


3PA63363-20V-1

About the remote controller which can connect set back time clock (BRC15A61)
Wired Remote Controller

Set Back Time Clock

Indoor Unit

Although Set Back Time Clock is connected with Wired Remote Controller in parallel with Series Method, it
does not applied to remote control of those other than the following.
Model

Remarks

BRC1A51
BRC1A52
BRC1A61
BRC1A62
BRC8A61
ARC11A52
ARC11A54

Only EC9721 the printed Circuit Board currently


used for these remote control. (Refer to Note 1)

BRC1B51
BRC1B52
BRC1B61
BRC1B62

Applied for all printed circuit boards.

BRC1C61
BRC1C51

Applied for all printed circuit boards.

Note 1) The check method of printed circuit boards' model No.


The rear face of the remote control after removing a back cover
Printed Circuit Board

EC9721

SkyAir LU Series

Printed circuit boards' model No. is indicated at the


lower left of the PC board which can be looked at
when the back cover of remote controller is removed.

Printed Circuit Boards' The product start of EC9721 was carried out after
Model No.
1997.

191

Remote Controller

ED21-301A

Names and Functions

Fig. 1
12

Fig. 2

15

20

17

PROGRAM

DAY OF
THE WEEK

SUMMER
TIME

DAY OFF

CLOCK

19

14
MON TUE WED THU FRI SAT SUN

PROGRAM

OFF OFF OFF OFF OFF OFF OFF

SUMMER TIME

MON TUE WED THU FRI SAT SUN CLOCK

ON/OFF

SET BACK

AM
PM

ON/OFF
SET BACK

OK

21

13

0 2 4 6 8 10 12 14 16 18 20 22 24

10
11

C
C 0 2 4 6 8 10 12 14 16 18 20 22 24

CLEAR

23

9
PROGRAM

ON/OFF
SET BACK

OK

DAY OF
THE WEEK

SUMMER
TIME

DAY OFF

CLOCK

16

22

18

CLEAR

Names and Functions of Operating Section (Fig.1,2)

ON/OFF (BYPASS) BUTTON

DISPLAY

Press this button to activate the time clock and the


programmed settings. Press this button again to
deactivate the programmed schedules.

(SET BACK TIME SCHEDULE)

11

This light turns on when the set back time clock


and the programmed schedules are activated.

DISPLAY

MON TUE WED THU FRI SAT SUN


AM
PM

CLOCK

DISPLAY (UNDER
CENTRALIZED CONTROL)

12

(PRESENT

TIME)

13

Displays the current time and day of the week.

DISPLAY

SUMMER TIME

14

This display indicates that the time clock has been


adjusted for summer time (daylight saving).

ON/OFF

16

(NORMAL SET

17
18

TEMPERATURE)

(SET BACK

19

20

(COOLING/HEATING

Displays the current operating mode. Individual set


back temperatures can be set for the cooling and
heating modes.
0 2 4 6 8 10 12 14 16 18 20 22 24

10

Press this button to adjust the present time and to


set the schedule times.

Press this button in the programming mode to


register the set schedules and current time settings
in the memory of the time clock.

DAY OF THE WEEK


Press this button to select the day of the week.

DAY OFF BUTTON


Press this button to set days off.

DISPLAY
(OPERATION TIME SCHEDULE)

21

TEMPERATURE SET BUTTONS


Press these buttons to adjust the normal set
temperature and the set back temperature.

When in the programming mode, press this button


to select either the ON/OFF or TEMPEATURE SET
BACK mode to set programmed times and
temperatures.

COOL/HEAT SELECT BUTTON

22

Indicates the time clock schedules for automatic


ON/OFF control.

Press this button to adjust the time clock for


daylight savings (if applicable in your area).

ON/OFF OR SET BACK MODE


SELECT BUTTON

This display indicates the set back temperature.

DISPLAY
MODE)

Press this button to enter and exit the programming


mode.

SUMMER TIME BUTTON

This display indicates the set temperature during


periods of normal operation.

DISPLAY SET BACK


TEMPERATURE)

Press this button to set the present time.

PROGRAM REGISTER BUTTON

(DAY OFF SETTING)

This display is indicated above the day(s) of the


week that have been programmed as day(s) off
when schedules are to be inactive.

DISPLAY

OFF

CLOCK ADJUST BUTTON

TIME ADJUST BUTTON

15

This display indicates that the time clock is in the


programming mode.

DISPLAY

Indicates that the system is under centralised


control or external control. In this case, some SET
BACK TIME CLOCK functions may not work.

PROGRAMMING BUTTON

DISPLAY PROGRAM

Indicates the schedules for temperature set back


periods.

OPERATION LIGHT (RED)

0 2 4 6 8 10 12 14 16 18 20 22 24

Press this button to select the cooling or heating


mode in order to set the normal set temperature
and the set back temperatures for each.

PROGRAM CLEAR BUTTON

23

Press this button to clear programmed times for


each day.
3PA63363-20V-2

192

SkyAir LU Series

ED21-301A

Remote Controller

Installation

Connected to a wired remote controller, this timer can set 2 sets of ON/OFF times in an increment of 30
minutes within a day. For each ON/OFF setting a temperature setting is also possible.

3P063547-1B-1

SkyAir LU Series

193

Remote Controller

ED21-301A

3P063547-1B-2

194

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2. Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]


2.1

BYC125KW1 Decoration Panel

BEFORE INSTALLATION
PRECAUTIONS
Refer also to the installation manual attached to the indoor unit.
ACCESSORIES
Installation manual.
NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL


<<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional
blocking pad kit.>>
HANDLING OF DECORATION PANELS
Never place the panel facing down nor lean it against a wall nor leave it on a projecting object.
Never touch or put pressure on the swing flap.
(The swing flap may malfunction.)
(1) Remove the suction grille from the decoration panel.
1) Push the suction grille lever inward and lift up the lever side.
(Refer to Fig. 1.)

2) Detach the suction grille from the decoration panel by lifting the
grille up approximately 45 degrees. (Refer to Fig. 2.)

45
Lever

Fig. 1
(2) Remove the service cover on the corner.
Slide the service cover outward to remove. (Refer to Fig. 3.)

Fig. 2

Fig. 3

SkyAir LU Series

195

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

INSTALLATION OF THE DECORATION PANEL TO THE


INDOOR UNIT BODY
<<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>>
(1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the
piping position of the indoor unit as shown in Fig. 4.
(2) Install the decoration panel.
1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of
the decoration panel to the hook of the indoor unit body. (2 positions)
2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.
(Be careful not to let the swing motor lead wire get caught in the sealing material.)
3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.)
4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered.
5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces
to 58 mm.
Sealing material
Indoor unit
Ceiling material
5 ~ 8 mm

Decoration panel

Air outlet

Hook

1)

Latch

2)
Piping position

2)

Swing flap motor


3)

4)

Fig. 4
PRECAUTIONS
Improper screwing of the screws may cause the troubles shown in
Fig. 5. Screw properly.

Air leak

Air leak from ceiling

Contamination

Dew formation, dew dripping


Fig. 5

196

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

If gap is still left between the ceiling and the decoration panel after screwing
the screws, readjust the indoor unit body height. (Refer to Fig. 6.)

Adjustment of the indoor unit body height from the


holes in the corner of the decoration panel is
possible if the indoor unit is kept leveled and the
drain piping, etc. is unaffected.

No gaps is allowed.

3
Fig. 6
(3) Wiring of the decoration panel (Refer to Fig. 7.)
6) Connect the connectors for swing flap motor lead wire
installed on the decoration panel.
If connectors are not connected, the malfunction
display (A7) appears on the remote controller.
Connect the connectors properly.
Make sure that the swing flap motor lead wire is
not caught between the indoor unit and the
decoration panel.

6)
Indoor
unit side

Decoration
panel side

Wiring

Fig. 7

Instruction Diagram
(It differs from the actual state.)

INSTALLATION OF SUCTION GRILLE AND SERVICE COVER


(1) Install the suction grille.
Install by reversing the procedure shown in PREPARATION OF DECORATION PANEL.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers demands.
NOTE)
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
(2) Install the service cover on the corner.
1) Attach the string of the service cover to the pin of the
decoration panel as in Fig. 8.

2) Install the service cover over the decoration panel.

Pin

Install the service cover by


sliding 4 latches to fit into the
holes on the decoration panel.

Fig. 8

SkyAir LU Series

197

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.2

ED21-301A

KDBHJ55K160 Sealing Member of Air Discharge Outlet

Caution
zRefer to the installation manual for both indoor unit and the decoration panel.
zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the
manual for the optional kit or the catalogue.
zContents of Kit
Prior to installation make sure you have the complete kit of parts.
Name

Sealing material(A)

Sealing material(B)

Sealing material(C)

Sealing material(D)

Quantity

1 piece

1 piece

1 piece

1 piece

Shape
and
marking

Name
Quantity

Insulation for top plate


1 piece

1 piece

Insulation for side plate


1 piece

2 pieces

1 piece

Moisture absorber for bell-mouth

2 pieces

1 piece

Moisture absorber for horizontal vane

5 kinds

Shape
and
marking

J : 1P012222-1B-1

198

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

Installation of the insulation

(1) Installation to the side plate


Adhere insulation for side plate

to the side of indoor unit.


140 class

71 class

Put the wire


through the slit of
the insulation.

(2) Installation to the top plate


Adhere insulation for top plate

When adhering
insulation, align its edge
with the bottom line of
casing.

When adhering
insulation, align its edge
with the bottom line of
casing.

to the top of the indoor unit.

(3) Adhere the moisture absorber for horizontal vane to the


edge of the horizontal vane of air outlet (Fig. 2).
(Choose the same color as panel.)
Horizontal vane
Moisture absorber
for horizontal vane
Fig. 2

Align it with the upper edge of horizontal vane.


Horizontal
vane
Moisture absorber
for horizontal vane

Fig. 1

(4) Adhere the moisture absorber in accordance with the


reference surface without wrinkles. (Fig. 4)
Adhere the moisture absorber in accordance with the
reference line . (Fig. 5)
Reference surface
Swing connector
Swing motor

(Fig. 3)

Sticking
reference

Adhere it from the edge of


switch box.
Switch box

Bellmouth

Sticking reference
Fig. 4

Fig. 5
JC : 1P012222-1B-2

SkyAir LU Series

199

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.3

ED21-301A

KDBP55H160WA Panel Spacer

Installation

35~71
100~140

200
258

C : 1P136564-1A-1

200

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

1P136564-1A-2

SkyAir LU Series

201

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.4

ED21-301A

KDDP55D160(K) Fresh Air Intake Kit

Installation

SkyAir

FH(Y)C35~140K

71

290

C : 3K011144-1-1

202

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

C : 3K011144-1-2

SkyAir LU Series

203

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

204

ED21-301A

SkyAir LU Series

ED21-301A

2.5

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KDDJ55X160 Fresh Air Intake Kit

The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be
changeable by installing the duct fan.

Dimension

3
J : D3K2175

Installation

2P066796-1B-1

SkyAir LU Series

205

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

2P066796-1B-2

206

SkyAir LU Series

ED21-301A

2.6

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KAFP556D80 160 HighEfficiency Filter (Including Filter Chamber)


KAFP557D80 160 HighEfficiency Filter (Including Filter Chamber)
Combination table

2.7

HighEfficiency Filter (Set)

Replacement HighEfficiency Filter

KAFP556D80
KAFP557D80

KAFP552H80
KAFP553H80

KAFP556D160
KAFP557D160

KAFP552H160
KAFP553H160

HighEfficiency Filter Chamber


KDDFP55D160

KAFP552H80 160 Replacement HighEfficiency Filter


KAFP553H80 160 Replacement HighEfficiency Filter
Specifications
Replacement HighEfficiency Filter

KAFP552H80

KAFP552H160

HighEfficiency Filter Chamber

KAFP553H80

KAFP553H160

KDDFP55D160

Collecting Efficiency (%)

65% (NBS Colorimetric method)

Initial Pressure Loss (Pa)

90% (NBS Colorimetric method)

34 or less

Final Pressure Loss (Pa)

98 or less

Filter

Nonwoven Fabric of Synthetic Fiber Nonwoven Fabric of Synthetic Fiber

Life (h)

2,500 h (Dust Concentration 0.15 mg / m3) 1,800 h (Dust Concentration 0.15 mg / m3)

Models to be Applied

35~71K Model

100~140K Model

35~71K Model

100~140K Model

Precaution at use
1. The highefficiency filter, and the other filter can not be installed together.
2. The unit should be operated with 4-way discharge when the highefficiency filter is installed.
It can not be applied to the high ceiling room.
3. Field setting by remote controller is necessary when the highefficiency filter is installed.
Dimension

540-20

10

10

AA

560

560

AIR
FLOW

Model

AA

KAFP552H80, 553H80

25

KAFP552H160, 553H160

45
J : D3K04256

2.8

KRP1B98 Installation Box for Adaptor PCB


Model No.
Item
Applicable Model

Dimension

Adaptor for Wiring

KRP1B98
FH(Y)C35~140K
KRP1B57
KRP4A53

D3K2169

SkyAir LU Series

207

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.9

ED21-301A

KDDFP55D160 HighEfficiency Filter Chamber

Installation

208

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

SkyAir LU Series

209

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.10

ED21-301A

KAFJ551K160 Replacement LongLife Filter for Decoration Panel

Specifications
Collecting Efficiency (%)

65 (Gravity Method)

Initial Pressure Loss (Pa)

8 or less

Final Pressure Loss (Pa)

49 or less

Filter

MildewProof Resin Net

Number of Sheets Included

1
2,500 h (Dust Concentration 0.15 mg / m3)

Life (h)
Models to Be Applied

35~140K Model
J : D3K2170C

2.11

KAFP55D160, KAFJ55K160H (Replacement) Ultra LongLife Filter


(Including Filter Chamber)

Specifications
Ultra LongLife Filter

KAFP55D160

Replacement Ultra LongLife Filter


HighEfficiency Filter Chamber
Collecting Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Filter
Life (h)
Models to Be Applied

Precaution at use
1. The Ultra longlife filter, and other filter can not be installed
together.
KDDFP55D160
2.
Field
setting by remote controller is necessary when the Ultra
50 (Gravity Method)
long
life filter is installed.
8 or less
Refer to the installation manual of Ultra longlife filter for
49 or less
setting.
MildewProof Resin Net
3. Filter cleaning period can not be displayed on the monitor when
5,000 h
the Ultra longlife filter is installed.
(Dust Concentration 0.3 mg / m3)
Refer to the left table and clean (with water) the filter
35~140K Model
periodically.
KAFJ55K160H

J : D3K2174A

Installation Iocation Filter Cleaning Period

210

Dirty Area

Every 5,000 hrs

Not Dirty Area

Every 10,000 hrs

SkyAir LU Series

ED21-301A

2.12

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

KKSJ55K160 Chamber Connection Kit


Dimension

J : D3K2186

Installation

3P089651-1A

SkyAir LU Series

211

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.13

ED21-301A

KDJ55K80 160 Branch Duct Chamber

Installation

212

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

SkyAir LU Series

213

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

2.13.1 Fan Performance and Discharge Pattern in case of using Branch Duct
Single Branch 3 Way Discharge

Sealing

Branch

Sealing

Branch

Sealing
Branch

T R

Sealing

Branch
(V0690)

35~71
Single branch ( )
50/60Hz Common use

55
50

External static pressure (Pa)

55
50

71

45

50

50

50

40

35

35

35

35

30

30

30

25

25

25

20

20

20

15

15

15

10

10

10

0
1

60
50

35

35

71

45

60

40

Single branch ( )
50/60Hz Common use

55

71

45

60

40

Single branch ( or )
50/60Hz Common use

0
0

Air volume (m3/min)

Air volume (m3/min)

Air volume (m3/min)

100~140
Single branch sealing (
50/60Hz Common use

130
120

or

Single branch sealing (


50/60Hz Common use

130
120

140

110

125

125

110

125

100

100

100

100

100

External static pressure (Pa)

140

90

90

90

80

80

80

70

70

70

60

60

60

50

50

50

40

40

40

20

20

20

20

20

20

10

10

10

0
0

Air volume (m3/min)

214

Single branch sealing (


50/60Hz Common use

130

9 10

140

0
0

Air volume (m3/min)

9 10

9 10

Air volume (m3/min)

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

Single Branch 2 Way Discharge

R
Q

Sealing

Sealing

T R

R
Branch
Q or T

Sealing

Branch

S or T

Sealing Sealing

Sealing

Branch

R or T

(V0693)

35~71

90

Single branch - 2 way discharge (


50/60Hz Common use

sealing)
90

Single branch - 2 way discharge (


50/60Hz Common use

71

80

71

80

60

60

50

50

70

35

External static pressure (Pa)

External static pressure (Pa)

70

sealing)

60
50
40
30
20
10

35

60
50
40
30
20
10

0
0

Air volume (m3/min)

Air volume (m3/min)

100~140

160

Single branch - 2 way discharge


(100~140. 50Hz)

160

150

150

140

140
Sealing

120

Sealing

110
Sealing

100
90
80
70
60
50
40

120

Sealing

110
Sealing

100
90
80
70
60
50
40

30

30

20

20

10

10

Sealing

130

External static pressure (Pa)

External static pressure (Pa)

130

0
0

8
3

9 10 11 12

Air volume (m /min)

SkyAir LU Series

Single branch - 2 way discharge


(100~140. 60Hz)

9 10 11 12

Air volume (m3/min)

215

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

2 Branches 2 Way Discharge

Sealing Sealing

Branch

Sealing

Sealing

Branch Sealing

Sealing

Branch
(V0696)

35~71

90

2 Branch - 2 way discharge (


50/60Hz Common use

90

71
60

80
70

External static pressure (Pa)

sealing) 2 Branch - 2 way discharge (


50/60Hz Common use

sealing) 2 Branch - 2 way discharge (


50/60Hz Common use

71

71

60

80

50

50

35

35

70

50

60

50

50

50

40

40

40

30

30

30

20

20

20

10

10

10
0

0
1

35

70

60

60

80

60

sealing)

Air volume (m3/min)

Air volume (m3/min)

Air volume (m3/min)

100~140

150

2 Branch - 2 way discharge


(100~140. 50Hz)

150

External static pressure (Pa)

140

140

130

Branch

130

Branch

120

Branch

120

Branch

110

Branch

110

Branch

100

100

90

90

80

80

70

70

60

60

50

50

40

40

30
20

Operation limit
less than 12m3/min

10

30
20

Operation limit
less than 12m3/min

10

0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Air volume (m3/min)

216

2 Branch - 2 way discharge


(100~140. 50Hz)

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Air volume (m3/min)

SkyAir LU Series

ED21-301A

2.14

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

Dimensions with Optional Kit

2.14.1 KDBP55H160WA Panel Spacer


KDBP55H160WA for FH(Y)C35~71K

Unit (mm)

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

Description
JC : 3D005390E

KDBP55H160WA for FHYC100~140K

Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit

3
Panel spacer
2
Decoration panel
1
Indoor unit
Number
Name

Thickness
of panel spacer

Dimension between
the bottom surface
of box and
the surface of ceiling

View

Description
JC : 3D005391D

SkyAir LU Series

217

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

2.14.2 KDDP55D160 Fresh Air Intake Kit (Without T Joint, Duct Fan)
KDDP55D160 for FH(Y)C35~71K
Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)

Refrigerant
Piping

Note 4

View
Service Access Panel :
450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


Note:1.When installing this kit, Service Access Panel is necessary.
(It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

How to connect Chamber 4


Independently(Refer to Note 5,6)

Connection chamber(Left)
Connection chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

5
4
3
2
1
Number

JC : 3D032981D

KDDP55D160 for FHYC100~140K

Unit (mm)

Service Access Panel :


450450mm or more
Refer to Note 2

Refrigerant
Piping

Note 4

View

Service Access Panel :


450450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5,6)
Note:1.When installing this kit, Service Access Panel is
necessary. (It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.
6.When installing the wireless infrared reciever to the unit,
air inlet must be on the right side as shown.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name
JC : 3D032984D

218

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

2.14.3 KDDP55D160K Fresh Air Intake Kit (With T Joint, Without Duct Fan)
KDDP55D160K for FH(Y)C35~71K
Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

3
Service Access Panel :
450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel

T Joint
Plate Band (Accessory)

(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

JC : 3D032987D

KDDP55D160K for FHYC100~140K


Service Access Panel :
450450mm or more
Refer to Note 2

Unit (mm)
Flexible Duct
(Accessory)

Service Access Panel :


450450mm or more
Refer to Note 2

Suction Duct (K-KFD9A)


Optional (Accessory)

Installation Service Access Panel


Plate Band (Accessory)

T Joint
(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.)
2.Either one of inspection hatch must be installed.
3.Field construction.
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the
obstacles, one side intake is acceptable.

5
4
3
2
1
Number

Connecting chamber(Left)
Connecting chamber(Right)
Suction chamber
Decoration panel
Indoor unit
Description
Name

J : 3D032990D

SkyAir LU Series

219

Ceiling Mounted Cassette Type (Multi Flow) [FH(Y)C]

ED21-301A

2.14.4 KAFP HighEfficiency Filter


KAFP556D80 557D80 for FH(Y)C35~71K

Unit (mm)

290

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
JC : 3D032975C

KAFP556D160 557D160 for FHYC100~140K

Unit (mm)

Note:When other optional kit is installed, refer to the installation


drawing of its optional kit.

6
5
4
3
2
1
Number

Drain pipe connection


Gas pipe connection
Liquid pipe connection
High efficiency filter
Decoration panel
Indoor unit
Description
Name
J : 3D032976C

220

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3. Ceiling Mounted Cassette Corner Type [FH(Y)K]


3.1

BYK45FJW1 71FJW1 Decoration Panel

BEFORE INSTALLATION
PRECAUTIONS
Refer also to the installation manual attached to the indoor unit.
ACCESSORIES
The box contains this manual and the parts listed below.
Item

Description

Quantity
BYK45FJ
BYK71FJ

Decoration panel

Panel fixing
screw

Washer

M5 35

1 set

1 set

5 pcs.

5 pcs.

5 pcs.

5 pcs.

NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL


Handle the decoration panel with care.
Never lean the panel against a wall, etc. nor leave it on a projecting object. (For prevention of dents and damages to the
panel surface)
Never grab the discharge grille during the installation work. (For prevention of damage to the discharge grille)
(1) Remove the suction grille from the decoration panel. (See figure below.)
1) Slide the suction grille lever and lift it up to one side.

SkyAir LU Series

221

Ceiling Mounted Cassette Corner Type [FH(Y)K]

ED21-301A

2) Unhook the suction grille off from the decoration panel.

(2) Remove the air filter.


Pull up the air filter knob to remove the air filter.

INSTALLATION OF THE DECORATION PANEL TO THE


INDOOR UNIT BODY
<<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>>
1. Installing the panel
(1) Install the decoration panel to the indoor unit body temporarily.

Portions to hook the panel's


temporary installation hooks

Portion at which
the panel is fixed.
(5 locations)

222

Temporary installation hooks

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

(2) Tighten the panel fixing screws temporarily.


1) Open the air outlet decorative covers.

Air outlet decorative covers

2) Put the panel fixing screws (5 pcs.) through the washers and tighten the screws temporarily.
3) Move the panel as indicated by the arrow in the above figure for adjustment so as to make no gap between the panel and
the ceiling.
2. Wiring between the indoor unit and the panel
With the decoration panel temporarily installed to the indoor unit, wire between the indoor unit and the decoration panel.
(See figure below.)
(1) Connect the connectors for swing motor and the limit switch on the decoration panel to those on the indoor unit body respectively.
(2) Check that the connectors are of the same color.
Panel side

Indoor unit side

(Motor power cable)


Color of connector: red

Note:
No connection of connectors or connection of connectors of different
colors causes the unit to stop operating with the Operation lamp on
the remote control blinking and the trouble code display "A7" on the
remote controller.

Panel side

Indoor unit side

(Limit switch)
Color of connector: black

SkyAir LU Series

223

Ceiling Mounted Cassette Corner Type [FH(Y)K]

ED21-301A

3. Fixing the decoration panel


(1) In order to prevent air leakage, a sealing material is provided at the spot where the indoor unit body is joined with the decoration
panel. Fix the decoration panel in the following method. (Shoulder bolts are used as the fixing screws. Tighten the bolts until their
shoulders.)
Indoor unit body
Indoor unit

Sealing material
Standard tightening length: 20 mm
Shoulder bolts are used to
protect the indoor unit. The
bolts can be tightened to the
allowance of up to 15 mm.

Decoration panel

Decoration panel body

(2) When tightening the bolts, be sure to make no gap between the panel and the ceiling and set the panel in parallel to the ceiling
and the ceiling joint.

Improper installation of the panel to the cassette body causes air leakage.

Note:
In case there remains a gap between the panel and the ceiling when
the fixing bolts have been tightened fully to their shoulders, adjust the
height of the indoor unit.

Make no gap here.

Note:
The decoration panel can be adjusted back and forth to 10 mm, respectively.

(3) Finally, make sure that the decoration panel is securely fixed to the indoor unit.
Improper installation (tightening) causes the troubles as shown below; be sure to double-check the completion of the
installation work.

No gap

Air leakage

Air leakage from the ceiling


Dust deposit
Dew buildup and dew dripping

INSTALLATION OF SUCTION GRILLE AND AIR FILTER


For their installation, take the reverse steps mentioned in "PREPARATION OF DECORATION PANEL".

224

SkyAir LU Series

ED21-301A

3.2

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KPBJ52F56W 80W Panel Specer

SkyAir LU Series

225

Ceiling Mounted Cassette Corner Type [FH(Y)K]

226

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

227

Ceiling Mounted Cassette Corner Type [FH(Y)K]

228

ED21-301A

SkyAir LU Series

ED21-301A

3.3

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KDBJ52F56W 80W Air Discharge Blind Panel

This optional kit is to blind the bottom discharge outlet, when the unit is used
with front air discharge.

Dimension

3
AA

119

14

AB
40

J : D3K1162A

Installation

SkyAir LU Series

229

Ceiling Mounted Cassette Corner Type [FH(Y)K]

230

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

231

Ceiling Mounted Cassette Corner Type [FH(Y)K]

232

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

233

Ceiling Mounted Cassette Corner Type [FH(Y)K]

234

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

235

Ceiling Mounted Cassette Corner Type [FH(Y)K]

3.4

ED21-301A

KAFJ521F56 80 Replacement LongLife Filter


Washable
Model
Items
Average Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Life (h)
Materials
Number Required Per Model
Weight (kg)

KAFJ521F56

KAFJ521F80

45 (Gravity Method)
10 or less
49
2,500 hours (Dust Particle Concentration at 0.15 mg/m3)
MildewProof Resin Net
Two pieces
0.4
0.6

Dimension

Model

KAFJ521F56

403

KAFJ521F80

503
C : D3K1145A

3.5

KHV7AW 9AW Discharge Grille


This optional kit is used when the unit is installed with front air discharge. The direction of air can be
adjusted flexibly.
This discharge grille should be installed with the following flexible duct.
Specifications
Model
Items
Air Flow Rate (m/min)
Type

KHV7AW

KHV9AW

9~13

12~19

HV type (Horizontal blade and vertical blade movable)

External Color

White

Materials

White

Steel plate (A cryptomeria only at the tip of the outlet


+ nylon flocking)

Structural Parts

Discharge grille, Screws, Blade control tool

Applicable Flexible Duct

KFDJ52F56

KFDJ52F80

Applicable Models

35 45F(J)

60 71F(J)

Dimension
AE

AD
(Ceiling opening)
AA
AB
AC

Pressure Loss

Pressure Loss Curve

91

100
(Ceiling opening)

69
83
123

55.5
8

m/s : Discharge Velocity

Air Flow Rate

4-610 Oblong hole

Model

AA

AB

AC

AD

AE

KHV7AW

523

483

466

500

488

KHV9AW

723

683

666

700

688
JC : D3K1972C

236

SkyAir LU Series

ED21-301A

3.6

Ceiling Mounted Cassette Corner Type [FH(Y)K]

KFDJ52F56 80 Flexible Duct with Shutter


Dimension

60

Only for KFDJ52F80

From indoor unit

F-7 Hole
Position of indoor unit to be set

340
(Ajustable range 290~340)

20

100

Flexible duct

Shutter

4-M5 Prepared hole


Position of discharge
grille to be set
69
98
(Internal dimension of duct)
130

To discharge outlet

B (Internal dimension of duct)


A
C
Model
A
B
D
E
KFDJ52F56 530 498 466 520
260
KFDJ52F80 730 698 666 720 2230=460

F
4
6
J : D3K2711

Installation

SkyAir LU Series

237

Ceiling Mounted Cassette Corner Type [FH(Y)K]

238

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

239

Ceiling Mounted Cassette Corner Type [FH(Y)K]

240

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted Cassette Corner Type [FH(Y)K]

SkyAir LU Series

241

Ceiling Mounted BuiltIn Type [FH(Y)B]

ED21-301A

4. Ceiling Mounted BuiltIn Type [FH(Y)B]


4.1

242

BYBS45DJW1 Decoration Panel


BYBS71DJW1 Decoration Panel
BYBS125DJW1 Decoration Panel

SkyAir LU Series

ED21-301A

Ceiling Mounted BuiltIn Type [FH(Y)B]

SkyAir LU Series

243

Ceiling Mounted BuiltIn Type [FH(Y)B]

244

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted BuiltIn Type [FH(Y)B]

SkyAir LU Series

245

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.2

246

ED21-301A

KTBJ25K56W 80W 160W Service Access Panel

SkyAir LU Series

ED21-301A

4.3

Ceiling Mounted BuiltIn Type [FH(Y)B]

KAFJ252L56 80 160 HighEfficiency Filter


KAFJ253L56 80 160 HighEfficiency Filter

Specifications
Model
Item

KAFJ252L56

Average Efficiency (%)

KAFJ252L80

KAFJ252L160

65 (Colorimetric Method)

Initial Pressure Loss (Pa)

14 or less

22 or less

KAFJ253L160

24 or less

34 or less

98 or less

Filter
Applicable Model

KAFJ253L80

90 (Colorimetric Method)

Final Pressure Loss (Pa)


Life (h)

KAFJ253L56

FlameResistant Type (with MildewProof)


2,500 (Dust Concentration at 0.15 mg/m3)
35 45F

60 71F

100 125F

1,800 (Dust Concentration at 0.15 mg/m3)


35 45F

60 71F

100 125F
J : D3K1408A
J : D3K1407A

Installation

Characteristics of Filter

SkyAir LU Series

247

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.4

ED21-301A

KAFJ251K56 80 160 Replacement LongLife Filter

Specifications
Model
Item
Dimensions (mm)
(HWD)
Average Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Filter Materials
Number of Filters
Life (h)
Applicable Model

Characteristics of Filter
KAFJ251K56

KAFJ251K80

KAFJ251K160

20506377
20701377
20451377
20656377
50% (Gravity Method)
10 or less
49
Mold Prevention Resin Net
1
2 (each one)
2 (each one)
2,500 (at Dust Particle Concentration of 0.15 mg/m3)
For indoor unit 35 45F For indoor unit 60 71F For indoor unit 100 125F
20656377

JC : D3K1147A
JC : D3K1148A

4.5

KAJ25L56D 80D 160D Filter Chamber for Bottom Suction

Applicable Model
Model

Dimension
Applicable
Model

JC : D3K1420A

Installation

3P009925-1

248

SkyAir LU Series

ED21-301A

4.6

Ceiling Mounted BuiltIn Type [FH(Y)B]

KAJ25L56B 80B 160B Filter Chamber for Rear Suction

Contents of kit
Name
Filter Chamber for Rear Suction
Blind Board
Screws
For Blind Board
(M512)
For Filter Chamber
Washer for Suspension Bracket
Suspension Bracket
Screws for Suspension Bracket (M612)
Filter Guide
Screws for Filter Guide (M512)
Applicable Model

Quantity
KAJ25L56B
1
1
4
11
4
2
2

35 45F

KAJ25L80B
1
1
6
13
4
2
2
1
2
60 71F

KAJ25L160B
1
1
6
15
4
2
2
1
2
100 125F

Preparation before installation

SkyAir LU Series

249

Ceiling Mounted BuiltIn Type [FH(Y)B]

250

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted BuiltIn Type [FH(Y)B]

SkyAir LU Series

251

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.7

ED21-301A

KSA25K56 80 160 Canvas Duct

Installation

252

SkyAir LU Series

ED21-301A

4.8

Ceiling Mounted BuiltIn Type [FH(Y)B]

KDG4DW 5DW 7DW 9DW Air Discharge UnitDischarge Grille+Discharge Chamber


KDGC4D 5D 7D 9D Air Discharge UnitDischarge Grille+Discharge Chamber

SkyAir LU Series

253

Ceiling Mounted BuiltIn Type [FH(Y)B]

254

ED21-301A

SkyAir LU Series

ED21-301A

Ceiling Mounted BuiltIn Type [FH(Y)B]

SkyAir LU Series

255

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.9

ED21-301A

KDDV20A Branch Duct

Specification

Dimension
Model

Item
Inlet Duct Size
Outlet Duct Size
Outside Insulation
Inside Insulation

Polyurethane Foam
Foam Polysthyrene

62

250

31
0
48

Pressure loss of Branch Duct


16

62

360

10

198

12

15 Hole
(Suspension bolt hole)

65

(M10 or W3/8)

4
62

Pressure Loss (Pa)

14

4
1

2
10

20

30

40

Air Volume (m3/min)


J : D3K1966C

256

SkyAir LU Series

ED21-301A

4.10

Ceiling Mounted BuiltIn Type [FH(Y)B]

KFDS151D 152D 153D 154D 155D 156D Flexible Duct


KFDS201D 202D 203D 204D 205D 206D Flexible Duct
Specification
Model KFDS151D(1m) KFDS152D(2m) KFDS201D(1m) KFDS202D(2m)
KFDS153D(3m) KFDS154D(4m) KFDS203D(3m) KFDS204D(4m)

Item
KFDS155D(5m) KFDS156D(6m) KFDS205D(5m) KFDS206D(6m)
Maximam Outer Dimension
Fitting Port Size
(Inner Dimension)
(Inner Dimension)
Operating Temperature Range
10~+75C
Applicable Model
35~125F
Structure

J : D3K04304

Pressure loss of Flexible Duct


Air

ty
oci
Vel c.)
/ se
(m
t
Duc eter
Diam m)
(m

m H20/100m

SkyAir LU Series

257

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.11

ED21-301A

KBBJ25K56 80 160 Blind Board

Installation

3P011904-1

258

SkyAir LU Series

ED21-301A

4.12

Ceiling Mounted BuiltIn Type [FH(Y)B]

KDAJ25K56 71 140 Adaptor for Discharge

SkyAir LU Series

259

Ceiling Mounted BuiltIn Type [FH(Y)B]

4.13

260

ED21-301A

KDJ2507K56 80 160 Flange for Suction

SkyAir LU Series

ED21-301A

4.14

Ceiling Mounted BuiltIn Type [FH(Y)B]

Optional Kit Installation Drawing

Discharge Chamber+Discharge Grille <150>


Discharge Chamber KDGC4D
100

Unit (mm)

3Suspension Bolt Hole


(M10 or W3/8)

Damper

255

285
(Ceiling Opening)

35~40

225

110

148

148

50

160
(Ceiling Opening)

209

72

4M5

J : D3K03300B

Discharge Grille KDG4DW


Unit (mm)

152

209

72

(Fixing Screw)

(Fixing Screw)

40

259

160
(Ceiling Opening)

285
(Ceiling Opening)
315

Pressure Loss Curve


m/s : Discharge Velocity

4M5 Screw

Pressure Loss [ Pa ]

190

10

3.6m/s

3.1m/s

5
2.2m/s
1.8m/s

Air Flow Rate [m3/min]


J : D3K03306A

SkyAir LU Series

261

Ceiling Mounted BuiltIn Type [FH(Y)B]

ED21-301A

Discharge Chamber KDGC5D


160

Unit (mm)

3Suspension Bolt Hole


(M10 or W3/8)

Damper
50

35~40

225

110

148

148

340

370
(Ceiling Opening)

160
(Ceiling Opening)

294

72

4M5

J : D3K03301B

Discharge Grille KDG5DW


152

294

72

(Fixing Screw)

(Fixing Screw)

Unit (mm)

40

344

160
(Ceiling Opening)

370
(Ceiling Opening)
400

Pressure Loss Curve


m/s : Discharge Velocity

10

4M5 Screw

Pressure Loss [ Pa ]

190

4.0m/s

5
2.6m/s

Air Flow Rate [m3/min]


J : D3K03307A

262

SkyAir LU Series

ED21-301A

Ceiling Mounted BuiltIn Type [FH(Y)B]

Discharge Chamber KDGC7D

Discharge Grille KDG7DW

SkyAir LU Series

263

Ceiling Mounted BuiltIn Type [FH(Y)B]

ED21-301A

Discharge Chamber KDGC9D


Unit (mm)
400

3Suspension Bolt Hole


(M10 or W3/8)

Damper
50

35~40

290

135

148

198

610

640
(Ceiling Opening)

160
(Ceiling Opening)

564

72

4M5

J : D3K03303C

Discharge Grille KDG9DW


Unit (mm)

152

614

72
(Fixing Screw)

40

564
(Fixing Screw)

640
(Ceiling Opening)

160
(Ceiling Opening)

670

Pressure Loss Curve


m/s : Discharge Velocity

4M5 Screw

Pressure Loss [ Pa ]

190

10

3.6m/s

2.9m/s

9 10 11 12

Air Flow Rate [m3/min]

J : D3K03309B

264

SkyAir LU Series

ED21-301A

New Ceiling Suspended Cassette Type [FUY]

5. New Ceiling Suspended Cassette Type [FUY]


5.1

KDBHJ49F80 140 Sealing Member of Air Discharge Outlet


Model
KDBHJ49F80
KDBHJ49F140

Dimension

Material
Galvanized Steel Plate
(with Flocking)

3
Model
KDBHJ49F80
KDBHJ49F140
J : D3K2096A

5.2

KDBTJ49F80 140 Decoration Panel for Air Discharge


Model
KDBTJ49F80
KDBTJ49F140

Dimension

Material
Galvanized Steel Plate
(with Flocking)

Model
KDBTJ49F80
KDBTJ49F140
J : D3K2099B

5.3

KDGJ49F80 140 Vertical Flap Kit

Dimension

Model
KDGJ49F80
KDGJ49F140

SkyAir LU Series

Packing Quantity

D3K2097A

D3K2098A

4(each 22)

265

New Ceiling Suspended Cassette Type [FUY]

5.4

ED21-301A

KAFJ495F140 Replacement LongLife Filter

Dimension

Model
Item
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)
Average Efficiency (%)
Life (h)

KAFJ495F140
7 or less
49 or less
50 (Gravity Method)
2,500
(Dust Particle Concentration at 0.15mg/m3)

Filter Pass Air Flow Rate


Materials
Number Required Per Model
Weight (kg)

18.5m /min
Mildew Proof Resin Net
1
0.4

J : D3K2101B

5.5

KHFJ49F80 140 LConnection Piping Kit


Model
KHFJ49F80
KHFJ49F140

Dimension

Liquid Side

Gas Side

J : D3K2103
J : D3K2104

5.6

KRP1B97 Installation Box for Adaptor PCB

Dimension

Model No.
Item
Adaptor for Wiring

KRP1B97
KRP4A53

J : D3K2091A

266

SkyAir LU Series

ED21-301A

Ceiling Suspended Type [FH(Y)]

6. Ceiling Suspended Type [FH(Y)]


6.1

KAFJ501D56 80 112 160 Replacement LongLife Filter

Specifications
Model
Item
Effective Life, Average Efficiency

KAFJ501D56

KAFJ501D80

KAFJ501D112

KAFJ501D160

2,500 hours (at Dust Particle Concentration of 0.15 mg/m ), 45% (by Weight Method)

Initial Pressure Loss (Pa)

10 or less

Final Pressure Loss (Pa)

59 or less

Filter Materials

Mold Prevention Resin Net

Mold Prevention Resin Net

Nos. Required

2 pieces

3 pieces

Applicable Model

35 50B

60 71B

100B

125B
J : D3K3074

6.2

KDU50B50 71 125VE Drain Pump Kit

Specifications
Model
Item

KDU50B50VE

Drainup Lift (mm)


Power Supply

KDU50B125VE

600
VP20 (Ex. dia. 26, Int. dia. 20)

Drain Con, Diameter


Pump

KDU50B71VE

Single Phase 220240V/220V 50/60Hz (from Indoor Unit PC Board)

Power Consumption (W)

Applicable Model

13.5/12 (50/60Hz)
35 50B

60 71B

100 125B

Precaution at use
1. Dont turn off the power within 5 minutes after cooling operation stops.
2. The liquid crystal display blinks to inform us that safety device actuated.
3. When cooling operations season is over, extract drain water.
Installation guide of the drain pump kit

Confirmation of Drainage

SkyAir LU Series

267

Ceiling Suspended Type [FH(Y)]

ED21-301A

Electrical Wiring

6.3

KHFJ5F50 60 80 160 LType Piping Kit


Application purpose
This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling
space. This L shape kit is an optional accessory which has been developed for improving the work of the
processing on site.
Model
Item
Applicable Model

KHFJ5F50

KHFJ5F60

KHFJ5F80

KHFJ5F160

35B

50 60B

71B

100 125B

KHFJ5F50~160

6.4

Installation

KRP1C93 Installation Box for Adaptor PCB

KRP1C93

Model No.
Item
Applicable Model
Adaptor for Wiring
Fixing Place
Dimensions
(mm)

268

W
H
D

KRP1C93
FH(Y)35~125B
KRP1B54
KRP4A52
In the Unit
109
124
38

SkyAir LU Series

ED21-301A

Floor Standing Type [FVY]

7. Floor Standing Type [FVY]


7.1

KAFJ95L160 Replacement LongLife Filter


Model
Item
Applied Model
Average Efficiency (%)
Initial Pressure Loss (Pa)
Final Pressure Loss (Pa)

Dimension

Life (h)
Materials
Number Required Per Model
Weight (kg)

KAFJ95L160
FVY71~125LA
60 (Gravity Method)
8 or less
49 or less
2,500
(Dust Concentration 0.15 mg/m3)
Mildew Proot Resin Net
1
0.4
J : D3K2438

7.2

KRP4A95 Installation Box for Adaptor PCB

KRP4A95

Model No.
Item
Applicable Model
Adaptor for Wiring
Fixing Place
Dimensions
(mm)

SkyAir LU Series

W
H
D

KRP4A95
FVY71~125LA
KRP4A52
KRP1B57
In the Unit
180
117
64

269

Outdoor Unit

ED21-301A

8. Outdoor Unit
8.1

KIS95 Drain Piping Kit


Use this plug to connect a drain hose to an outdoor unit.
Outlook
KIS95

Drain hose connection dia 16ID.


Note:

8.2

270

KIS95
Drain piping
(With Y joint)
plug (3 pcs.)

1. This is the joint for attaching a vinyl hose (field supplied).


This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose.
2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is
necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed
on the wall.
3. The position of holes are unfit to connect with outdoor units in some models.
In this case, use it without Y joint.

KKPJ5F180 Central Drain Plug

SkyAir LU Series

ED21-301A

8.3

Outdoor Unit

KRK5F80V1 140V1 160V1 YearRound Cooling Kit

R71LUV1, R71LUY1, R71LUVAL


R100LUV1, R100LUY1, R100LUVAL, R125LUY1, R125LUTAL, R125LUYAL
R140LUY1, R140LUYAL, R140LUTAL

C : 3PA60339B

SkyAir LU Series

271

Outdoor Unit

8.4

ED21-301A

KHR58C21, KHD58C21A, KHD58C23A, KHD58C24A, KHD58D33,


KHR58P322H, KHRJ5F224F, KHRJ5F280F Refrigerant Branch Piping Kit
<Caution>
This is the branch kit for refrigerant piping to connect indoor and outdoor units of TWIN/TRIPLE/ DOUBLE
Twin simultaneous ON/OFF system.

How to use
1. Uses as branch joints of refrigerant piping.
Note) It is necessary because it is not attached to the air conditioner.
2. Pipes of the joint parts are widened.
Enables easy connection and Brazing.
3. Insulation materials are equipped as standard.

Type
Model

Item

Reducer

Type
Model

Triple Multi
KHD58D33

R(Y)71LU

R(Y)100~140LU

R(Y)200KU

R(Y)250KU

R(Y)140LU

2
1

Double Twin Multi

Triple Multi
KHR58P322H
R(Y)200KU

KHRJ5F224F
R(Y)200KU

KHRJ5F280F
R(Y)250KU

Branch Pipe

Reducer

(2 sets)

(2 sets)

Branch Pipe

(2 sets)

Reducer

Liquid Side Joint

Applicable Model

Gas Side Joint

KHD58C24A

Branch Pipe

Item

272

Twin Multi
KHD58C21A
KHD58C23A

Branch Pipe

Reducer

Gas Side Joint

Liquid Side Joint

Applicable Model

KHR58C21

(2 sets)

SkyAir LU Series

ED21-301A

Outdoor Unit

Dimension
Twin/Double Twin Multi

Triple Multi

3
Model
KHR58P322H

(Horizontal)

Caution at use
1. This kit must be so installed that piping after the branch (between the kit and the indoor units) can be laid horizontally.
(Tolerance : 20)
If not possible, install the pipe as shown below.
Pipe after branching
Horizontal connection

Horizontal connection

Horizontal connection

Pipe after branching


Horizontal connection

Horizontal connection

Pipe after branching


Horizontal connection

Horizontal connection

Do not incline the pipe more than 20. Otherwise, uniform refrigerant distribution may not be available.
Inclination 20 or less

Branch
portion

Inclination 20 or less

Inclination 20 or less

Branch
portion

Branch
portion

Horizontal line

2. In case of connecting main pipe (between this kit and the outdoor unit) to this kit, do not bend
the main pipe near the connection.
If not possible, keep the length of straight portion more than 10 times of connection piping
diameter as shown on the right.
If the required length is not ensured, uniform refrigerant distribution may not be available.
(Same as the header shape pipe)
Straight portion
= (D10) or more

Main pipe

3. When connecting branch pipe with the different size indoor/outdoor pipe, use the attached
reducer to joint them as shown below. (Same as the header shape pipe)
(Ex. 1) Gas outlet of KHR58P328H
In case of piping connection
diameter (one side) 19.1

(Ex. 2) Liquid outlet of KHR58P322H


In case of piping connection
diameter 6.4
Pipe cutter

ion

Field piping
Reducer
(Accessories)
Branch pipe

ct
nne
Co rt
po

A portion

Field piping
Be sure to cut the center of
connection port with pipe
cutter.

Branch pipe
Cut the A portion as shown in
the above figure, to connect field piping.
J : 3PA38910-1G-1

SkyAir LU Series

273

Outdoor Unit

4. Insulate both the liquid side and the gas side piping completely. Use the attached
insulation for the branch piping.
Wrap the vinyl tape around the insulation joint without leaving any clearance.
5. Pipng length bewteen this kit and each indoor unit must be the same.
(Max. length differential : 10m or less)
Also, this piping length must be as short as possible. (Max. length differential : 20m or
less)
6. For the Maximum refrigerant piping length and level difference, refer to the label on the
indoor and the outdoor units and the Engineering Data Book.
7. Vertical piping is only allowed on the main piping (between the outdoor unit and this kit).
8. Refer to the Installation manuals (Refrigerant chapter) attached to the indoor and the
outdoor unit.

ED21-301A

Insulation
(Field supply)

Insulation
(Accessories)

Tape
(Field supply)

Insulation
(Field supply)

J : 3PA38910-1G-2

274

SkyAir LU Series

The air conditioners manufactured


by Daikin Industries have received
ISO 9001 certification for quality
assurance.
Certificate Number. JMI-0107
JQA-0495
JQA-1452

All Daikin Industries locations and


subsidiaries in Japan have
received environmental
management system standard
ISO 14001 certification.
Daikin Industries, Ltd.
Domestic Group
Certificate Number. EC99J2044

About ISO 14001


ISO 14001 is the standard defined by the International
Organization for Standardization (ISO) relating to
environmental management systems. Our group has
been acknowledged by an internationally accredited
compliance organisation as having an appropriate
programme of environmental protection procedures
and activities to meet the requirements of ISO 14001.

Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan

http://www.daikin.com/global/
c All rights reserved

The specifications, designs, and information in this brochure are subject to change without notice.

This book is made of recycled paper.

ED 21-301A
Printed in Japan 02/2005 FS