Você está na página 1de 118

800xA for Advant Master

Extended Graphic Library


System Version 5.1

Power and productivity


for a better world

TM

800xA for Advant Master


Extended Graphic Library

System Version 5.1

NOTICE
This document contains information about one or more ABB products and may include a
description of or a reference to one or more standards that may be generally relevant to
the ABB products. The presence of any such description of a standard or reference to a
standard is not a representation that all of the ABB products referenced in this document
support all of the features of the described or referenced standard. In order to determine
the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product.
ABB may have one or more patents or pending patent applications protecting the intellectual property in the ABB products described in this document.
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license. This
product meets the requirements specified in EMC Directive 2004/108/EEC and in Low
Voltage Directive 2006/95/EEC.

TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respective owners.

Copyright 2003-2010 by ABB.


All rights reserved.

Release:
Document number:

June 2010
3BSE026427-510

TABLE OF CONTENTS
About This Book
General ..............................................................................................................................9
Document Conventions ...................................................................................................10
Warning, Caution, Information, and Tip Icons................................................................10
Terminology.....................................................................................................................11
Related Documentation ...................................................................................................13

Section 1 - Extended Graphic Elements


Analog Input, AI..............................................................................................................15
Integer Bargraph01...............................................................................................15
Integer Limit01.....................................................................................................18
Integer Percent01..................................................................................................19
Analog Output, AO..........................................................................................................21
Integer Button01...................................................................................................21
Binary Object, GENBIN .................................................................................................22
3-Valve01 .............................................................................................................22
3-Valve Long LLD01 (Left-Left-Down)..............................................................25
3-Valve Long LRD01 (Left-Right-Down) ...........................................................28
Breaker01 .............................................................................................................31
Choke Valve01 .....................................................................................................34
Damper01 .............................................................................................................37
Fan01

.............................................................................................................40

Mixer01 .............................................................................................................43
Motor01 .............................................................................................................46
Pump01 .............................................................................................................49
Valve01

3BSE026427-510

.............................................................................................................52

Table of Contents

Data Base Parameters, DAT(x)........................................................................................ 55


Square01 ............................................................................................................ 55
Digital Input, DI .............................................................................................................. 56
Arrow01 ............................................................................................................ 56
Breaker01 ............................................................................................................ 58
Damper01 ............................................................................................................ 60
Diamond01........................................................................................................... 62
Earth01

............................................................................................................ 64

Fan01

............................................................................................................ 66

IndicatorText01 .................................................................................................... 68
IndicatorText02 .................................................................................................... 70
IndicatorText03 .................................................................................................... 72
Motor01

............................................................................................................ 74

Pump01

............................................................................................................ 76

Reg Loop01.......................................................................................................... 78
Valve01

............................................................................................................ 80

Digital Output, DO.......................................................................................................... 82


Diamond01........................................................................................................... 82
Reg Loop01.......................................................................................................... 84
Reg Loop02.......................................................................................................... 86
Square01 ............................................................................................................ 88
Valve01

............................................................................................................ 90

Motor Control, MOTCON .............................................................................................. 92


Fan01

............................................................................................................ 92

Pump01

............................................................................................................ 95

Process Controller, PIDCON .......................................................................................... 97


Integer Limit01 .................................................................................................... 97
User Defined Object, GENUSD...................................................................................... 99
Choke Valve01 ..................................................................................................... 99
Pump Down 2-Way ............................................................................................ 101
Pump Up 2-Way................................................................................................. 103
Valve01

.......................................................................................................... 105

3BSE026427-510

Table of Contents

Valve Integer01 ..................................................................................................107


Valve Control, VALVECON..........................................................................................110
3-Valve01 ...........................................................................................................110
Damper01 ...........................................................................................................114

3BSE026427-510

Table of Contents

3BSE026427-510

About This Book


General
This instruction describes the Extended Graphic Elements for 800xA for Advant
Master, which enables data retrieval from the Advant Controller 400 Series to
IndustrialIT 800xA Base System. 800xA for Advant Master contains built in display
elements and faceplates for the standard ABB object types below listed:

3BSE026427-510

Analog Input AI

Analog Output AO

Binary Object GENBIN

Data Base Parameters DAT(x)

Digital Input DI

Digital Output DO

Motor Control MOTCON

Process Controller PIDCON

User Defined Object GENUSD

Valve Control VALVECON

The Control Connection Aspects (CCA) for each object type. Each CCA
contains the following:

The name, data type, access rights (read/write) and subscription update
rate of each attribute.

The name of the corresponding OPC item (object of the controller).

A user interface to inspect the object type attribute information. It can also
be used to subscribe for the current value of each attribute.

Document Conventions

About This Book

The graphic elements aspects of each type (close-up where relevant and a
number of additional graphical presentations).

A faceplate aspect for each type.

The Object types also include additional aspects such as an Icon aspect, an Alarm
List aspect (for the instantiated object), and Trend aspect. This book is focused on
describing the graphic elements and faceplates.
The faceplate images in this manual are not updated to the latest versions. For
example, the pin button in a faceplate is not shown.
Graphic Displays and Object Displays in new version of Process Graphics use a
new background color compared to what was used in VBPG. 800xA for
AdvantMaster graphic elements are designed and verified to work using the
background color selected in VBPG (BackColor = &H00666633&). We thereby
recommend that this background color also is used when creating new graphic
displays with aspect category Graphic Display PG2, unless another background
color already have been verified to work properly with the graphic elements being
used. The background color can be changed by setting the BackColor property to
the GeneralBackColor logical color or by (not recommended) specifying
RGB(51,102,102). Graphic Displays being migrated to the new version of
Process Graphics will retain the background color.

Document Conventions
Microsoft Windows conventions are normally used for the standard presentation of
material when entering text, key sequences, prompts, messages, menu items, screen
elements, etc.

Warning, Caution, Information, and Tip Icons


This publication includes Warning, Caution, and Information where appropriate
to point out safety related or other important information. It also includes Tip to
point out useful hints to the reader. The corresponding symbols should be
interpreted as follows:

10

3BSE026427-510

About This Book

Terminology

Electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
Warning icon indicates the presence of a hazard which could result in personal
injury.
Caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could
result in corruption of software or damage to equipment/property.
Information icon alerts the reader to pertinent facts and conditions.

Tip icon indicates advice on, for example, how to design your project or how to
use a certain function
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
fully comply with all Warning and Caution notices.

Terminology
A complete and comprehensive list of Terms is included in the IndustrialIT
Extended Automation System 800xA, Engineering Concepts instruction
(3BDS100972*). The listing included in Engineering Concepts includes terms and
definitions as they that apply to the 800xA system where the usage is different from
commonly accepted industry standard definitions and definitions given in standard
dictionaries such as Websters Dictionary of Computer Terms.

3BSE026427-510

11

Terminology

About This Book

Term/Acronym
Graphic element

Description
A graphic aspect that has a reference to an Aspect
Objects. Normally a part of a graphic display. A graphical
object typically built up from several sub-elements and/or
primitive elements. Some graphic elements are provided
by ABB, while others may be built by the user.

Graphic element 1
Examples of
Graphic Elements
provided by ABB:

81.4 M/MIN
ValueField

0.0

Bar

100.0

Hscale

Graphic element
browser

A tool used to select object aware (graphic) elements in


Graphics Builder.

Graphic expression

Graphic expression is used to specify a data


subscription and a relationship between process data
and data to be displayed.

Graphic libraries

Libraries of primitive elements, and standard graphic


elements, for example faceplate element, object display
and graphic element.

Faceplate

Faceplates are used to monitor and control process


data. A faceplate has a configuration view where you
insert faceplate elements, buttons, status indicators and
aspect links. The faceplate can have up to three run-time
views:
reduced, normal and extended, depending on how much
information the user wants.

12

3BSE026427-510

About This Book

Related Documentation

Term/Acronym

Description

PG

New Process Graphics

VBPG

Visual Basic Process Graphics

Related Documentation
A complete list of all documents applicable to the 800xA IndustrialIT Extended
Automation System is provided in Released User Documents, 3BUA000263*. This
document lists applicable Release Notes and User Instructions. It is provided in
PDF format and is included on the Release Notes/Documentation media provided
with your system. Released User Documents are updated with each release and a
new file is provided that contains all user documents applicable for that release with
their applicable document number. Whenever a reference to a specific instruction is
made, the instruction number is included in the reference.

3BSE026427-510

13

Related Documentation

14

About This Book

3BSE026427-510

Section 1 Extended Graphic Elements


Analog Input, AI
Integer Bargraph01
Presentation:
1.
4.
5.
2.
3.

6.
7.

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Invisible

SELECTED = 0

? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged and I/O


Error

? Yellow

ERR = 1 and
BLOCKED = 1

Input blocked and I/O Error

? Red

ERR = 1

I/O Error

ERR = 0

Invisible

AI Error

3BSE026427-510

15

Analog Input, AI

16

Section 1 Extended Graphic Elements

Measured Value

VALUE

The object value

ERR = 1

Invisible - I/O Error

Red flashing

AL_UNACK = 1

Unacknowledged

Yellow

BLOCKED = 1

Input blocked

Red

DISTURB = 1

Alarm

Green

High Limit 2

HI_LIM2

Alarm High limit 2

HI_LIM2 >= RANGEMAX


or EN_H2 = 0

Invisible

Filled Yellow

VALUE>H2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H2 = 1

Unfilled Grey

High Limit 1

HI_LIM1

Warning High limit 1

HI_LIM1 >= RANGEMAX


or EN_H1 = 0

Invisible

Filled Yellow

VALUE>H1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE>H1 = 1

Unfilled Grey

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

Low Limit 1

Presentation

Analog Input, AI

Condition

Remarks

LO_LIM1

Warning Low limit 1

LO_LIM1 <= RANGEMIN


or EN_L1 = 0

Invisible

Filled Yellow

VALUE<L1 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L1 = 1

Unfilled Grey

Low Limit 2

LO_LIM2

Alarm Low limit 2

LO_LIM2 <= RANGEMIN


or EN_L2 = 0

Invisible

Filled Yellow

VALUE<L2 = 1 and
AL_BLK = 1

Logical color
blockedSymbol

Unfilled Yellow

AL_BLK = 1

Logical color
blockedSymbol

Filled Red

VALUE<L2 = 1

Unfilled Grey

Configuration:

Parameters

Affects

Options (bold is
default)

FrameStyle

Raised, Sunken and Flat

FrameWidth

3, any width

Orientation

Vertical, Horizontal

3BSE026427-510

Remarks

17

Analog Input, AI

Section 1 Extended Graphic Elements

Integer Limit01
Presentation:

1.

2.
3.

Behavior:
No

Description

Lock Frame

18

Presentation

Condition

Remarks
The object frame

Solid White

SELECTED = 1

Object selected

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

VALUE

Object value

Yellow

BLOCKED =1

Input blocked

? ? ? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged and I/O


Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

ERR = 1

I/O Error

Red

DISTURB = 1

Alarm

Green

Measured Value

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

Limit

Analog Input, AI

Presentation

Condition

Remarks

Yellow

BLOCKED =1

Input blocked

? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged and I/O


Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? Red

ERR = 1

I/O Error

H2 Red

ABOVE_HI_LIM2 = 1

Above High Limit 2

H1 Red

ABOVE_HI_LIM1 = 1

Above High Limit 1

L2 Red

BELOW_LO_LIM2 = 1

Below Low Limit 2

L1 Red

BELOW_LO_LIM1 = 1

Below Low Limit 1

Limit is Invisible

Configuration:
Parameters

Affects

Options (bold is default) Remarks

BackgroundColor

2. Measured Value & 3. Limit Black, any other color

Integer Percent01
Presentation:

1.

3BSE026427-510

2.

19

Analog Input, AI

Section 1 Extended Graphic Elements

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

Solid White

SELECTED = 1

Object select frame

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

VALUE

Object value

Yellow

BLOCKED =1

Input blocked

? ? ? Red flashing

ERR = 1 and
AL_UNACK = 1

Unacknowledged and I/O


Error

Red flashing

AL_UNACK = 1

Unacknowledged alarm

? ? ? Red

ERR = 1

I/O Error

Red

DISTURB = 1

Alarm

Green

Invisible
2

Measured Value

Configuration:

Parameters

Affects

Options (bold is
default)

BackgroundColor

2. Measured Value

Black, any other color

FrameStyle

Flat, Raised and Sunken

FrameWidth

0, any width

20

Remarks

3BSE026427-510

Section 1 Extended Graphic Elements

Analog Output, AO

Analog Output, AO
Integer Button01
Presentation:

1.

2.

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

White

SELECTED = 1

Object select frame

Invisible

SELECTED = 0

Output Value

VALUE

Object value

Red flashing

AL_UNACK = 1

Unacknowledged alarm

Yellow

OUTP_BLK = 1

Output blocked

Red

ERR = 1

Alarm

Cyan

MAN = 1

Magenta

MAN = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

BackgroundColor

2. Output Value

Black, any other color

FrameWidth

3BSE026427-510

2, any width

21

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Binary Object, GENBIN


3-Valve01
Presentation:

Down

Left

Right

1.

Up

2.
3. On-Symbol

22

3. Off-Symbol

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

2.2

2.3

Presentation

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

Mode Indication

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

3BSE026427-510

Condition

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication

23

Binary Object, GENBIN

No

Description

Symbol

3.1

Shape

Color

Section 1 Extended Graphic Elements

Presentation

Condition

Remarks
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Actuator

ActuatorIndVis = 1

Actuator Indication Visible

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

3 Symbol

Down, Up, Left, Right

ActuatorIndVis

3 Symbol

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1...4

24

No function in VBPG

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

3-Valve Long LLD01 (Left-Left-Down)


Presentation:
2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

25

Binary Object, GENBIN

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication
Shape

26

Section 1 Extended Graphic Elements

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Actuator

ActuatorIndVis = 1

Actuator Indication Visible

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ActuatorIndVis

3 Symbol

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1...4

3BSE026427-510

No function in VBPG

27

Binary Object, GENBIN

Section 1 Extended Graphic Elements

3-Valve Long LRD01 (Left-Right-Down)


Presentation:

False

2.
True

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

Presentation

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

28

Condition

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

2.2

2.3

Description

Presentation

Condition

Remarks

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

Mode Indication

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Symbol

3.1

Shape

Color

3BSE026427-510

Binary Object, GENBIN

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Actuator

ActuatorIndVis = 1

Actuator Indication Visible

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

29

Binary Object, GENBIN

No

Description

Section 1 Extended Graphic Elements

Presentation

Condition

Remarks

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ActuatorIndVis

3 Symbol

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1...4

30

No function in VBPG

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Breaker01
Presentation:

1.

Horizontal

Vertical
2.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

Presentation

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

3BSE026427-510

Condition

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

31

Binary Object, GENBIN

2.2

2.3

32

Section 1 Extended Graphic Elements

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

Mode Indication

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

Symbol

3.1

Shape

Presentation

Binary Object, GENBIN

Condition

Remarks
3D Display Object

Color

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

Dimension3D

3 Symbol

false, true

ModeIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

3BSE026427-510

No function in PG

33

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Choke Valve01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

34

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

3BSE026427-510

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Binary Object, GENBIN

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Actuator

ActuatorIndVis = 1

Actuator Indication Visible

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

35

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

VerticalPosition

3 Symbol

Left, Right

ActuatorIndVis

3 Symbol

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1...4

36

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Damper01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

37

Binary Object, GENBIN

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

38

Section 1 Extended Graphic Elements

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

3,1...4

3BSE026427-510

39

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Fan01
Presentation:

2.
1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

40

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

3BSE026427-510

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Binary Object, GENBIN

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

41

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

1 Symbol

Right, Up, Down, Left

ModeIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

42

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Mixer01
Presentation:

1.
2.
3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

43

Binary Object, GENBIN

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

44

Section 1 Extended Graphic Elements

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ModeIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

3BSE026427-510

45

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Motor01
Presentation:

2.
1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

46

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

3BSE026427-510

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Binary Object, GENBIN

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

47

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

48

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Pump01
Presentation:

2.
1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

49

Binary Object, GENBIN

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

50

Section 1 Extended Graphic Elements

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

3BSE026427-510

Section 1 Extended Graphic Elements

Binary Object, GENBIN

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

1 Symbol

Right, Up, Down, Left

ModeIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

3BSE026427-510

51

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Valve01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

52

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

2.2

Mode Indication

2.3

Presentation

Symbol

3.1

Shape

Color

3BSE026427-510

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Binary Object, GENBIN

ControlIndVis = 1
R Green

PC_ST_18 = 1

Remote Indication

L Green

PC_ST_17 = 1

Local Indication

C Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

On

Off-Symbol

PC_ST_24 = PC_ST_25

Off

Actuator

ActuatorIndVis = 1

Actuator Indication Visible

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or
AU_ST_04 = 1 or
AU_ST_05 = 1 or
AU_ST_06 = 1 or
AU_ST_07 = 1

UnAck signal error


UnAck feedback error
UnAck alarm Hi limit2
UnAck alarm HI limit1
UnAck alarm Lo limit1
UnAck alarm Lo limit2

Red

PC_ST_00 = 1 or
PC_ST_01 = 1 or
PC_ST_04 = 1 or
PC_ST_05 = 1 or
PC_ST_06 = 1 or
PC_ST_07 = 1

Signal error
Alarm feedback error
Alarm Hi limit2
Alarm HI limit1
Alarm Lo limit1
Alarm Lo limit2

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

53

Binary Object, GENBIN

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

ActuatorIndVis

3 Symbol

false, true

ModeIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1...4

54

No function in VBPG

3BSE026427-510

Section 1 Extended Graphic Elements

Data Base Parameters, DAT(x)

Data Base Parameters, DAT(x)


Square01
Presentation:

2.

1. On-Symbol

1. Off-Symbol

Behavior:
No

Description

Symbol

1.1

Shape

Presentation

Condition

Remarks
2D Display Object

On-Symbol

VALUE = 1

Data true

Off-Symbol

VALUE = 0

Data false

1.2

Color

Green

VALUE = 1

Label

Black

VALUE = 1

Grey

VALUE = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

FrameWidth

1 Symbol

2, 1..4

LabelText

2 Label

, any other character

BitNo

3BSE026427-510

0,0..31

55

Digital Input, DI

Section 1 Extended Graphic Elements

Digital Input, DI
Arrow01
Presentation:

1.

2. On-Symbol

2. On-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

56

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
2D and 3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

No

Description

Presentation

Condition

Remarks

2.2

Color

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Light Blue

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

2 Symbol

Right, Left, Up, Down

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

57

Digital Input, DI

Section 1 Extended Graphic Elements

Breaker01
Presentation:

Horizontal

1.

Vertical

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

58

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
2D and 3D Display
Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

3BSE026427-510

Section 1 Extended Graphic Elements

No

2.2

Description

Color

Digital Input, DI

Presentation

Condition

Remarks

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Dimension3D

2 Symbol

false, true

Orientation

2 Symbol

Horizontal, Vertical

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

No function in PG

59

Digital Input, DI

Section 1 Extended Graphic Elements

Damper01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

60

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

2 Symbol

Horizontal, Vertical

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

FrameWidth

2 Frame

2, (1..4)

3BSE026427-510

61

Digital Input, DI

Section 1 Extended Graphic Elements

Diamond01
Presentation:

1,

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

62

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
3D Display Object

ERROR = 1

Input error

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

No

Description

Presentation

Condition

Remarks

2.2

Color

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

FrameWidth

2 Frame

2, (1..4)

3BSE026427-510

No function in PG2

63

Digital Input, DI

Section 1 Extended Graphic Elements

Earth01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
2D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

64

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

65

Digital Input, DI

Section 1 Extended Graphic Elements

Fan01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
23D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

66

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

2 Symbol

Right, Left, Up, Down

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

67

Digital Input, DI

Section 1 Extended Graphic Elements

IndicatorText01
Presentation:

1. On-Symbol

1. Off-Symbol

Behavior:
No

Description

Symbol

1.1

Shape

68

Presentation

Condition

Remarks
2D Display Object

SELECTED = 0 and
ERROR = 1

Input error

[Q]

SELECTED = 1 and
ERROR = 1

Input error

On

SELECTED = 0 and
((VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1))

Input closed

[ On ]

SELECTED = 1 and
((VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1))

Input closed

Off

SELECTED = 0 and
((VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1))

Input open

3BSE026427-510

Section 1 Extended Graphic Elements

No

1.2

Description

Digital Input, DI

Presentation

Condition

Remarks

[ Off ]

SELECTED = 1 and
((VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1))

Input open

White

SELECTED = 1

Object selected

Flashing Red

ALARM_UNACK = 1

Alarm Unacknowledged

Yellow

UPD_BLK = 1 and
ERROR = 1

Input Blocked and


input error

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1) or
ERROR = 1

Alarm Acknowledged
or
input error

Yellow

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input open

Magenta

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input closed

Color

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DisturbanceUsed

1. Symbol

false, true

Inverted

1 Symbol

false, true

LabelOffText

1. Symbol

Off, any letter

LabelOnText

1. Symbol

On, any letter

3BSE026427-510

69

Digital Input, DI

Section 1 Extended Graphic Elements

IndicatorText02
Presentation:

1. On-Label

1. Off-Label

Behavior:
No

Description

Symbol

1.1

Label

70

Presentation

Condition

Remarks
2D Display Object

ERROR = 1

Input Error

Generator Not
Available

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input On Label visible


LabelOnText

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1and
Inverted = 1)

Input Off Label visible


LabelOffText

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

1.2

Color

Digital Input, DI

Presentation

Condition

Remarks

White

SELECTED = 1

Object Select

Flashing Red

ERROR = 1

Input Error

Flashing Red

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Black

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

1. Symbol

false, true

LabelOffText

1. Symbol

-, any letter

LabelOnText

1. Symbol

Generator Not Available,


any letter

3BSE026427-510

71

Digital Input, DI

Section 1 Extended Graphic Elements

IndicatorText03
Presentation:

1.
2. F-Symbol

2. B-Symbol

Behavior:
No

Description

Lock Frame

Symbol

2.1

Shape

2.2

72

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

(DISTURBANCE = 1 and
DisturbanceUsed = 1) or
ALARM_UNACK = 1

Alarm unacknowledged

Alarm Blocked
ALARM_BLK = 1 or
ALARM_PERIOD_BLK = 1
or REPEAT_FAIL_BLK = 1

Invisible

Else

Yellow flash

REPEAT_FAIL_BLK = 1

Red flash

ALARM_UNACK = 1

Yellow

ALARM_BLK = 1 or
Alarm Blocked
ALARM_PERIOD_BLK = 1

Red

DISTURBANCE = 1

Alarm unacknowledged

Alarm acknowledged

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DisturbanceUsed

2. Symbol

true, false

3BSE026427-510

73

Digital Input, DI

Section 1 Extended Graphic Elements

Motor01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

74

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

No

Description

Presentation

Condition

Remarks

2.2

Color

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

75

Digital Input, DI

Section 1 Extended Graphic Elements

Pump01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

76

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

2 Symbol

Right, Left, Up, Down

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

77

Digital Input, DI

Section 1 Extended Graphic Elements

Reg Loop01
Presentation:

1.

Up

Down

Left

Right

2. On-Symbol

78

2. Off-Symbol

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
2D Display Object

Color

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

2 Symbol

Up, Down, Right, Left

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

3BSE026427-510

79

Digital Input, DI

Section 1 Extended Graphic Elements

Valve01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

80

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Input closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Input open

Actuator

ActuatorIndVis = True

Actuator visible

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Input, DI

No

Description

Presentation

Condition

Remarks

2.2

Color

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Yellow

UPD_BLK = 1

Input blocked

Red

(DISTURBANCE = 1 and
DisturbanceUsed = 1 or
ERROR = 1

Alarm acknowledged
but disturbance exists
or
Input error

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

2 Symbol

Horizontal, Vertical

ActuatorIndVis

2 Symbol

false, true

DisturbanceUsed

2 Symbol

false, true

Inverted

2 Symbol

false, true

FrameWidth

1 Symbol

2, 1..4

3BSE026427-510

81

Digital Output, DO

Section 1 Extended Graphic Elements

Digital Output, DO
Diamond01
Presentation:

1.
2.

3. On-Symbol

3 Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Label
Label

Character

Color

Black

Symbol

3.1

Shape

82

Presentation

LabelText

3D Display Object
On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Pressed in
Output On

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Output Off

Cross

MAN_MODE = 0

Auto mode

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Output, DO

No

Description

Presentation

Condition

Remarks

3.2

Color

Yellow

OUTP_BLK = 1

Output blocked

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Red

ERROR = 1

Output error

Cyan

MAN_MODE = 1

Manual mode

Magenta

MAN_MODE = 0

Auto mode

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

3 Symbol

false, true

FrameWidth

3 Symbol

3, 1..4

LabelText

2 Label

, any character

3BSE026427-510

83

Digital Output, DO

Section 1 Extended Graphic Elements

Reg Loop01
Presentation:

1.

Up

Down

Left

Right

2. On-Symbol

84

2. Off-Symbol

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Output, DO

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected
2D Display Object

Color

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Output closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Output open

Yellow

OUTP_BLK = 1

Output blocked

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Red

ERROR = 1

Output error

Cyan

MAN_MODE = 1

Manual mode

Magenta

MAN_MODE = 0

Auto mode

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

2 Symbol

Up, Down, Left and Right

Inverted

2. Symbol

false, true

3BSE026427-510

85

Digital Output, DO

Section 1 Extended Graphic Elements

Reg Loop02
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

86

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected
2D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Output closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Output open

Yellow

OUTP_BLK = 1

Output blocked

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Red

ERROR = 1

Output error

Cyan

MAN_MODE = 1

Manual mode

Magenta

MAN_MODE = 0

Auto mode

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Output, DO

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

2 Symbol

false, true

FrameWidth

2. Symbol

2, 1..4

3BSE026427-510

87

Digital Output, DO

Section 1 Extended Graphic Elements

Square01
Presentation:

1.
2.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Label
Label

Character

Color

Black

Symbol

3.1

Shape

88

Presentation

LabelText

3D Display Object
On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Pressed in
Output On

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Output Off

Cross

MAN_MODE = 0

Auto mode

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Output, DO

No

Description

Presentation

Condition

Remarks

3.2

Color

Yellow

OUTP_BLK = 1

Output blocked

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Red

ERROR = 1

Output error

Cyan

MAN_MODE = 1

Manual mode

Magenta

MAN_MODE = 0

Auto mode

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Inverted

3 Symbol

false, true

FrameWidth

3 Symbol

3, 1..4

LabelText

2 Label

, any character

3BSE026427-510

89

Digital Output, DO

Section 1 Extended Graphic Elements

Valve01
Presentation:

1.

2. On-Symbol

2. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Symbol

2.1

Shape

2.2

90

Color

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected
3D Display Object

On-Symbol

(VALUE = 1 and
Inverted = 0) or
(VALUE = 0 and
Inverted = 1)

Output closed

Off-Symbol

(VALUE = 0 and
Inverted = 0) or
(VALUE = 1 and
Inverted = 1)

Output open

Actuator

ActuatorIndVis = True

Actuator visible

Yellow

OUTP_BLK = 1

Output blocked

Flashing Red

ALARM_UNACK= 1

Alarm unacknowledged

Red

ERROR = 1

Output error

Cyan

MAN_MODE = 1

Manual mode

Magenta

MAN_MODE = 0

Auto mode

3BSE026427-510

Section 1 Extended Graphic Elements

Digital Output, DO

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

2 Symbol

Horizontal, Vertical

ActuatorIndVis

2 Symbol

false, true

Inverted

2 Symbol

false, true

FrameWidth

2. Symbol

2, 1..4

3BSE026427-510

91

Motor Control, MOTCON

Section 1 Extended Graphic Elements

Motor Control, MOTCON


Fan01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

Solid White

SELECTED = 1

Selected

Solid Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

92

3BSE026427-510

Section 1 Extended Graphic Elements

No

Description

Mode

Symbol

3.1

Shape

Presentation

Motor Control, MOTCON

Condition

Remarks

ModeIndVis= True

Status Indication

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0

Indicates Auto Start


Init Not Performed

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

* Yellow

IND2_02 = 1

Test mode

ModeIndVis = False

Mode invisible
3D Display Object

On-Symbol

IND1_12 = 1 or
IND1_15 = 1

Off-Symbol

3.2

Color

3BSE026427-510

Started

IND1_12 = 0 and
IND1_15 = 0

Stopped

Grey

IMPLEMENTED = 0

Implemented

Grey

IND2_03 = 1

Out of service

Red flashing

AU_IND = 1

Alarm unacknowledged

Red

IND1_DIST = 1

Error

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

93

Motor Control, MOTCON

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

3. Symbol

Right, Up, Down and Left

ModIndVis

2. Mode

True, False

94

3BSE026427-510

Section 1 Extended Graphic Elements

Motor Control, MOTCON

Pump01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

Solid White

SELECTED = 1

Selected

Solid Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Mode

3BSE026427-510

ModeIndVis= True

Status Indication

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual mode

A Green flashing

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0 and
IND2_06 = 0 and
IND1_12 = 0

Indicates Auto Start


Init Not Performed

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto mode

* Yellow

IND2_02 = 1

Test mode

ModeIndVis = False

Mode invisible

95

Motor Control, MOTCON

No

Description

Symbol

3.1

Shape

Section 1 Extended Graphic Elements

Presentation

Condition

3D Display Object
On-Symbol

IND1_12 = 1 or
IND1_15 = 1

Off-Symbol

3.2

Color

Remarks

Started

IND1_12 = 0 and
IND1_15 = 0

Stopped

Grey

IMPLEMENTED = 0

Implemented

Grey

IND2_03 = 1

Out of service

Red flashing

AU_IND = 1

Alarm unacknowledged

Red

IND1_DIST = 1

Error

Green flashing

IND1_15 = 1

Change of Direction in
progress

Green

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

3. Symbol

Right, Up, Down and Left

ModIndVis

2. Mode

True, False

96

3BSE026427-510

Section 1 Extended Graphic Elements

Process Controller, PIDCON

Process Controller, PIDCON


Integer Limit01
Presentation:

1.

2.

3.

Behavior:
No

Description

Lock Frame

Measured Value

Default Presentation

Condition

Remarks

Solid White Line

SELECTED = 1

Object select frame

Dotted Yellow Line

ALARM_F1_BLK = 1 or
ALARM_F2_BLK

Alarm blocked by Operator

? ? ? in Flashing Red

TS_AI_ERROR = 1 and
ALARM_UNACK 1

Alarm Unacknowledged

Flashing Red

ALARM_UNACK = 1

Alarm Unacknowledged

? ? ? in Red

TS_AI_ERROR = 1

Alarm Acknowledged

Red

DIST = 1

Alarm Acknowledged

Green

3BSE026427-510

97

Process Controller, PIDCON

No

Description

Limit

Section 1 Extended Graphic Elements

Default Presentation

Condition

Remarks

H2 Red

TS_MV_ABOVE_H2 = 1

Alarm High Limit 2

H1 Red

TS_MV_ABOVE_H1 = 1

Alarm High Limit 1

L2 Red

TS_MV_BELOW_L2 = 1

Alarm Low Limit 2

L1 Red

TS_MV_BELOW_L1 = 1

Alarm Low Limit 1


Limit is invisible

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Background color

2 Measured Value & 3 Limit

Black, any color

98

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

User Defined Object, GENUSD


Choke Valve01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

99

User Defined Object, GENUSD

No

Description

2.2

Mode Indication

2.3

Symbol

3.1

Shape

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

3.2

Presentation

Section 1 Extended Graphic Elements

ControlIndVis = 1
M3 Green

PC_ST_18 = 1

Remote Indication

M2 Green

PC_ST_17 = 1

Local Indication

M1 Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

Off-Symbol

PC_ST_24 = PC_ST_25

Actuator

ActuatorIndVis = 1

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack signal error


UnAck feedback error

Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Signal error
Feedback error

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Color

Configuration:
Parameters

Affects

Options (bold is default) Remarks

VerticalPosition

3 Symbol

Left, Right

ActuatorIndVis

3 Symbol

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1..4

100

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Pump Down 2-Way


Presentation:

2.
1.

3. Forward-Symbol

3. Reverse-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

2.2

Presentation

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

Mode Indication

3BSE026427-510

Condition

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

101

User Defined Object, GENUSD

No

Description

2.3

Control Indication

Symbol

3.1

Shape

3.2

Presentation

Section 1 Extended Graphic Elements

Condition

Remarks

ControlIndVis = 1
M3 Green

PC_ST_18 = 1

Remote Indication

M2 Green

PC_ST_17 = 1

Local Indication

M1 Green

PC_ST_16 = 1

Central Indication
3D Display Object

Forward-Symbol

PC_ST_24 = 1 and
PC_ST_25 = 0

Reverse-Symbol

PC_ST_24 = 0 and
PC_ST_25 = 1

Off-Symbol

PC_ST_24 = PC_ST_25

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack signal error


UnAck Feedback error

Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Signal error
Feedback error

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Color

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

102

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Pump Up 2-Way
Presentation:
2.
1.

3. Forward-Symbol

3. Reverse-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

103

User Defined Object, GENUSD

No

Description

2.2

Mode Indication

2.3

Symbol

3.1

Shape

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

3.2

Presentation

Section 1 Extended Graphic Elements

ControlIndVis = 1
M3 Green

PC_ST_18 = 1

Remote Indication

M2 Green

PC_ST_17 = 1

Local Indication

M1 Green

PC_ST_16 = 1

Central Indication
3D Display Object

Forward-Symbol

PC_ST_24 = 1 and
PC_ST_25 = 0

Reverse-Symbol

PC_ST_24 = 0 and
PC_ST_25 = 1

Off-Symbol

PC_ST_24 = PC_ST_25

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack signal error


UnAck Feedback error

Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Signal error
Feedback error

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Color

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

104

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Valve01
Presentation:

2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

105

User Defined Object, GENUSD

No

Description

2.2

Mode Indication

2.3

Symbol

3.1

Shape

Condition

Remarks

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

3.2

Presentation

Section 1 Extended Graphic Elements

ControlIndVis = 1
M3 Green

PC_ST_18 = 1

Remote Indication

M2 Green

PC_ST_17 = 1

Local Indication

M1 Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

Off-Symbol

PC_ST_24 = PC_ST_25

Actuator

ActuatorIndVis = 1

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack signal error


UnAck feedback error

Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Signal error
Feedback error

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Color

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

ActuatorIndVis

3 Symbol

false, true

ModeIndVis

2 Flag

false, true

FrameWidth

3 Symbol

2,1..4

106

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Parameters

Affects

Options (bold is default) Remarks

ControlVis

2 Flag

false, true

Valve Integer01
Presentation:

5.

4.
1.
2.
3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Lock Frame
Color

Flags

2.1

Alarm Indication

3BSE026427-510

Presentation

Condition

Remarks
The Object frame

Solid White Line

SELECTED = 1

Object selected

Dotted Yellow Line

ALARM_BLK = 1

Alarm blocked
Status Indication

F Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1 or

Unack Alarm Indication

F Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Alarm Indication

X Yellow

PC_ST_08 = 1 or
PC_ST_09 = 1 or
PC_ST_10 = 1 or
PC_ST_11 = 1

Interlock Indication

107

User Defined Object, GENUSD

2.2

No

2.3

Mode Indication

Description

Symbol

3.1

Shape

3.2

ModeIndVis = 1
M Green

PC_ST_20 = 1

Manual Indication

A Green

PC_ST_19 = 1

Auto Indication

B Green

PC_ST_21 = 1

Blocked Indication

Presentation

Condition

Remarks

S Green

PC_ST_22 = 1

Standby Indication

Control Indication

Section 1 Extended Graphic Elements

ControlIndVis = 1
M3 Green

PC_ST_18 = 1

Remote Indication

M2 Green

PC_ST_17 = 1

Local Indication

M1 Green

PC_ST_16 = 1

Central Indication
3D Display Object

On-Symbol

PC_ST_24 <> PC_ST_25

Off-Symbol

PC_ST_24 = PC_ST_25

Label Actuator

ActuatorIndVis = 1

Flashing Red

AU_ST_00 = 1 or
AU_ST_01 = 1

Unack signal error


UnAck feedback error

Red

PC_ST_00 = 1 or
PC_ST_01 = 1

Signal error
Feedback error

Flashing Green

PC_ST_25 = 1

Green

PC_ST_25 = 0

Color

MV

4.1

Color

Measured Value
Flashing Red

AU_ST_00-07 = 1 or

Unacknowledged alarm

Red

PC_ST_00-07 = 1 or

Alarm

Green
5

Label Actuator

5.1

Color

108

Label
Flashing Red

AU_ST_00-02 = 1 or

Red

PC_ST_00-02 = 1 or

3BSE026427-510

Section 1 Extended Graphic Elements

User Defined Object, GENUSD

Green Flashing

PC_ST_25 = 1

Green

PC_ST_25 = 0

Configuration:
Parameters

Affects

Options (bold is default) Remarks

ActuatorIndVis

2 Flag

false, true

ControlIndVis

2 Flag

false, true

ModeIndVis

2 Flag

false, true

Label

5 Label Actuator

M, any character

UnitVisible

4 MV

true, false

FrameWidth

3 Symbol

2,1..4

3BSE026427-510

109

Valve Control, VALVECON

Section 1 Extended Graphic Elements

Valve Control, VALVECON


3-Valve01
Presentation:

Down

Left

Right

Up

1.

2.
3. On-Symbol

110

3. Off-Symbol

3BSE026427-510

Section 1 Extended Graphic Elements

Valve Control, VALVECON

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

Solid White

SELECTED = 1

Selected

Solid Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Flags

2.1

Mode Indication

2.2

2.3

Status Indication
ModeIndVis = 1
* Yellow

IND2_02 = 1 and
IND2_03 = 0

Test

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto Mode

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual Mode

Control Indication

PointOfControlIndVis = 0
S Green

IND2_04 = 1

Sequence control

L Green

IND2_01 = 1 and
IND2_04 = 0

Local control

C Green

IND2_01 = 0 and
IND2_04 = 0

Central control

PointOfControlIndVis = 0

Point of control is invisible

Interlock Indication

InterlockIndVis = 1 and
IND2_03
XA Yellow

3BSE026427-510

IND2_14 = 1

IA1

IND2_07 = 1

Ready to start

111

Valve Control, VALVECON

No

Description

Symbol

3.1

Shape

3.2

Section 1 Extended Graphic Elements

Presentation

Condition

Remarks

X Yellow

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11 = 1 or
(IND2_13 = 1 and
IND1_11 = 0) or
(IND2_00 = 0 and
(IND2_10 = 1 or
(IND2_12 = 1 and
IND1_11 = 0)))

IC1 or
IC2 or
IB2 or
(IB4 &
OPN = 0) or
(Blkintl = 0 &
(IB1 or
(IB3 &
OPN = 0)))
3D Display Object

On-Symbol

IND1_11 = 1

Limit position for open

Off-Symbol

IND1_11 = 0

No limit position for open

Actuator

ActuatorIndVis = 1

Actuator visible

Grey

IMPLEMENTED = 0

Grey

IND2_03 = 1

Out of service

Red Flashing

IND1_09 = 1

Unacknowledged Alarm

Red

IND1_08 = 1

Alarm or Error

Green flashing

IND1_15 = 1 and
IND1_12 = 0

Intermediate position Not


open

Green flashing

IND1_15 = 1 and
IND1_12 = 1

Intermediate position
Open

Color

Green

No intermediate position
Limit position for open

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Direction

3 Symbol

Down, Up, Right, Left

ActuatorIndVis

3 Symbol

false, true

ModeIndVis

2 Flag

true, false

112

3BSE026427-510

Section 1 Extended Graphic Elements

Valve Control, VALVECON

Parameters

Affects

Options (bold is default) Remarks

PointOfControlIndVis

2 Flag

true, false

InterlockIndVis

2 Flag

true, false

FrameWidth

3 Symbol

2,1..4

3BSE026427-510

113

Valve Control, VALVECON

Section 1 Extended Graphic Elements

Damper01
Presentation:
2.

1.

3. On-Symbol

3. Off-Symbol

Behavior:
No

Description

Presentation

Condition

Remarks

Lock Frame

Solid White

SELECTED = 1

Selected

Solid Yellow

IND2_00 = 1

Interlock override by
operator

Dotted Yellow

AL_BLK = 1

Alarm blocked by operator

Invisible

Flags

2.1

Mode Indication

2.2

114

Status Indication
ModeIndVis = 1

* Yellow

IND2_02 = 1 and
IND2_03 = 0

Test

A Green

IND2_05 = 1 and
IND2_02 = 0 and
IND2_03 = 0

Auto Mode

M Green

IND2_05 = 0 and
IND2_02 = 0 and
IND2_03 = 0

Manual Mode

Control Indication

PointOfControlIndVis = 0
S Green

IND2_04 = 1

Sequence control

L Green

IND2_01 = 1 and
IND2_04 = 0

Local control

3BSE026427-510

Section 1 Extended Graphic Elements

No

2.3

Description

Presentation

Condition

Remarks

C Green

IND2_01 = 0 and
IND2_04 = 0

Central control

PointOfControlIndVis = 0

Point of control is invisible

Interlock Indication

InterlockIndVis = 1 and
IND2_03 = 0
XA Yellow

X Yellow

Symbol

3.1

Shape

3.2

Valve Control, VALVECON

IND2_14 = 1

IA1

IND2_07 = 1

Ready to start

IND2_08 = 1 or
IND2_09 = 1 or
IND2_11 = 1 or
(IND2_13 = 1 and
IND1_11 = 0) or
(IND2_00 = 0 and
(IND2_10 = 1 or
(IND2_12 = 1 and
IND1_11 = 0)))

IC1 or
IC2 or
IB2 or
(IB4 &
OPN = 0) or
(Blkintl = 0 &
(IB1 or
(IB3 &
OPN = 0)))
3D Display Object

On-Symbol

IND1_11 = 1

Limit position for open

Off-Symbol

IND1_11 = 0

No limit position for open

Grey

IMPLEMENTED = 0

Grey

IND2_03 = 1

Out of service

Red Flashing

IND1_09 = 1

Unacknowledged Alarm

Red

IND1_08 = 1

Alarm or Error

Green flashing

IND1_15 = 1 and
IND1_12 = 0

Intermediate position Not


open

Green flashing

IND1_15 = 1 and
IND1_12 = 1

Intermediate position
Open

Color

Green

3BSE026427-510

No intermediate position
Limit position for open

115

Valve Control, VALVECON

Section 1 Extended Graphic Elements

Configuration:
Parameters

Affects

Options (bold is default) Remarks

Orientation

3 Symbol

Horizontal, Vertical

ModeIndVis

2 Flag

true, false

PointOfControlIndVis

2 Flag

true, false

InterlockIndVis

2 Flag

true, false

FrameWidth

3 Symbol

2,1..4

116

3BSE026427-510

ABB AB
Control Systems
Vsters, Sweden
Phone: +46 (0) 21 32 50 00
Fax:
+46 (0) 21 13 78 45
E-Mail: processautomation@se.abb.com
www.abb.com/controlsystems

Copyright 2003-2010 by ABB.


All Rights Reserved

ABB Inc.
Control Systems
Wickliffe, Ohio, USA
Phone: +1 440 585 8500
Fax:
+1 440 585 8756
E-Mail: industrialitsolutions@us.abb.com
www.abb.com/controlsystems

ABB Industry Pte Ltd


Control Systems
Singapore
Phone: +65 6776 5711
Fax:
+65 6778 0222
E-Mail: processautomation@sg.abb.com
www.abb.com/controlsystems

ABB Automation GmbH


Control Systems
Mannheim, Germany
Phone: +49 1805 26 67 76
Fax:
+49 1805 77 63 29
E-Mail: marketing.control-products@de.abb.com
www.abb.de/controlsystems

Power and productivity


for a better world

TM

3BSE026427-510

Contact us

Você também pode gostar