Você está na página 1de 29

Transmission & Distribution

Protection & Contrle

PACIS
C264 EXPERTISE MAINTENANCE GUIDE

APPROVAL OF THE DOCUMENT


NAME

FUNCTION

S.GADAY

CHEF PROJET
C264

JM. BOISSET

PACIS PROJECT
MANAGER

DATE

VISA

EVOLUTION OF THE DOCUMENT


EDITION
Z

DATE
15/10/07

DRAFT
JM. BOISSET

DESCRIPTION OF THE EVOLUTION


Creation of the document

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 1/29

Edition: Z

Transmission & Distribution


Protection & Contrle

INTRODUCTION.........................................................................................................6

Connecting the shell.................................................................................................7

General traces...........................................................................................................8
3.1

HELP.............................................................................................................................. 8

3.2

help................................................................................................................................ 8

3.3

OdLogLevel x................................................................................................................ 8

3.4 SET_TRACES(task ID,msk,status)..............................................................................8


3.4.1 Main Task identification number...............................................................................8
3.4.2 Communication Task identification number..............................................................9
3.4.3 Traces mask............................................................................................................. 9
3.4.4 Communication traces............................................................................................10

3.5

S_DBTEST_print_bay.................................................................................................11

3.6

S_DBTEST_print_norgint_list....................................................................................11

3.7

S_DBTEST_print_computer_wiring..........................................................................12

TRACES FOR OPERATING MODE.........................................................................13


4.1

SET_DEV_MODE x......................................................................................................13

4.2

SET_MAINT................................................................................................................. 13

4.3

SET_ACTIVE................................................................................................................ 13

Traces for the drivers and the communication protocols..................................14


5.1

traces_sccx=y.............................................................................................................14

5.2

traces_apieth x............................................................................................................ 14

5.3

TunRSLines.................................................................................................................14

5.4

TunRSIed x..................................................................................................................14

5.5

S_DBTEST_print_line_info........................................................................................14

Traces for DIGITAL Inputs (DI)...............................................................................15


6.1

active_di board,input,state,valid...............................................................................15

6.2

aff_di_info board,input...............................................................................................15

6.3

aff_di_state board,input.............................................................................................15

6.4

aff_di_board_state board,type...................................................................................15

Traces for ANALOGUE Inputs (AI)........................................................................16


7.1

aff_ai_info board,input...............................................................................................16

7.2

aff_ai_data board,input..............................................................................................16

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 2/29

Edition: Z

Transmission & Distribution


Protection & Contrle

7.3

aff_ai_board_data board............................................................................................16

7.4

set_ai_data index,state,value....................................................................................16

Traces for CT/VT measurements...........................................................................17


8.1

CTVT_GET_MEAS.......................................................................................................17

8.2

aff_ctvt_config............................................................................................................17

8.3

aff_ctvt_data............................................................................................................... 17

Traces for DIGITAL OUTputs (DO).........................................................................18


9.1

aff_do_data.................................................................................................................18

9.2

get_state_do board.....................................................................................................18

9.3

active_ccu board,channel,order................................................................................18

9.4

active_dou board,channel,order................................................................................18

10

Traces for Binary Inputs (BI)...............................................................................19

10.1

aff_bi_info bi_norgint..............................................................................................19

10.2

aff_bi_grp_info bi_norgint......................................................................................19

10.3

aff_bi_state2 bi_norgint.........................................................................................19

10.4

active_bi norgint, order...........................................................................................19

10.5

get_di_norgint..........................................................................................................19

11

Traces for Controls..............................................................................................20

11.1

aff_co_info co_norgint...........................................................................................20

11.2

aff_all_co_info norgdeb, norgfin............................................................................20

11.3

aff_sp_info sp_norgint...........................................................................................20

12

Traces for counters (CT).....................................................................................21

12.1

aff_ct_data ct_norgint............................................................................................21

12.2

aff_ct_info ct_norgint.............................................................................................21

13

Traces for measurements (MV)...........................................................................22

13.1

aff_dm_info dm_norgint.........................................................................................22

13.2

aff_meas_info norgint............................................................................................22

13.3

aff_meas_data norgint...........................................................................................22

13.4

active_meas norgint,value,quality.........................................................................22

13.5

active_from_ai norgint,type,value,quality.............................................................22

13.6

active_meas_ctvt norgint,value,quality.................................................................22

13.7

active_meas_ied norgint,value,quality..................................................................22

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 3/29

Edition: Z

Transmission & Distribution


Protection & Contrle

13.8

aff_sig_info norgint................................................................................................23

13.9

aff_sig_data norgint...............................................................................................23

13.10

active_sig norgint,value,quality.............................................................................23

13.11

aff_spi_info norgint................................................................................................23

13.12

aff_spi_data norgint...............................................................................................23

13.13

active_spi norgint,value,quality.............................................................................23

14

Traces for autorecloser, switchgear and modules...........................................24

14.1

S_DBTEST_print_ar_item x...................................................................................24

14.2

S_AUTREC_get_ar_context....................................................................................24

14.3

S_AUTREC_get_ar_state........................................................................................24

14.4

S_DBTEST_print_cb_item x..................................................................................24

14.5

aff_sp_cb_info x.....................................................................................................24

14.6

aff_discsw_info........................................................................................................24

14.7

aff_module_info.......................................................................................................24

15

Traces for time synchronisation.........................................................................25

15.1

synchroInfoShow....................................................................................................25

15.2

synchroBdShow......................................................................................................25

16

Traces for alarms.................................................................................................26

16.1

aff_alarm_info x......................................................................................................26

16.2

ALARM_HELP..........................................................................................................26

16.3

read_alarm_header..................................................................................................26

16.4

read_diff_alarm_header..........................................................................................26

17

Traces for ATCC...................................................................................................27

17.1

18

ccaCatcAff

donGen,group,node,nivTens,device,transf.....................................27

Traces for Fast Automatism et Interlock...........................................................28

18.1

aff_eql_info..............................................................................................................28

18.2

aff_eql_data

19

index_eql.........................................................................................28

Traces for Redundancy.......................................................................................29

19.1

aff_red_data............................................................................................................. 29

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 4/29

Edition: Z

Transmission & Distribution


Protection & Contrle

1 INTRODUCTION
The aim of this document is to propose the basis of expertise of the C264 application, based on
the shell traces concept.

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 5/29

Edition: Z

Transmission & Distribution


Protection & Contrle

2 CONNECTING THE SHELL


To connect the shell you need :
a straight cable.
a tool like Tera-Term-Pro or HyperTerminal.
Communication parameter are :
19200 bauds
8 bits
No parity
1 stop
No control

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 6/29

Edition: Z

Transmission & Distribution


Protection & Contrle

3 GENERAL TRACES
3.1

HELP

Action : display the debug control available in the C264 application


Parameters : none

3.2

help

Action : display the debug control available in the VxWorks kernel


Parameters : none

3.3

OdLogLevel x

Action : display traces in the UCA2 / IEC61850 agency


Parameters : x = 1 : trace activated
X = 0 : trace desactivated

3.4

SET_TRACES(task ID,msk,status)

Action : activate / desctivate the traces


Parameters : task_ID
: task identification number (refer to the table below)
Msk
: traces level (refer to the table below)
Status
: 1 trace activated with the specified level
0 trace desactivated
3.4.1
N
01
02
04
06
13
18
20
21
22
24
25
28
37
46

Main Task identification number


Name
T01CTRL
T02SUPERV
T04HDLDI
T06HDLAI
T13SYNCHRO
T18COND
T20GESTTS
T21GESTCT
T22GESTTM
T24GESTTC
T25ALARM
T28ISAGRAF
T37ILOCK
T46AUTREC

Role
Control Task (used to managed the Digital Output selfcheck)
Supervision task
Handler for DI acquisition
Handler for AI acquisition
Time synchronisation task
Control management task
xPS management task
Counters management task
MV management task
xPC management task
Alarm management task
ISAGRAF management task
Interlock / PSL management task
Autorecloser management task

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 7/29

Edition: Z

Transmission & Distribution


Protection & Contrle

N
47
49
53
54
62
63

3.4.2

Name
T47RED
T49SYCHECK
T53ATC
T54HMILCD
T62TMU210
T63MICOMS1

Communication Task identification number

N
32
35
36
38
40
42
48
51
55
58
59
60
61
3.4.3

Role
Redundancy management task
Synchrocheck management task
ATCC management task
Local HMI management task
Protection function management task
MiCOM S1 for protection management task

Name
T32DNP3M
T35IECM2
T36T103M7
T38SERMAN
T40CLIMAN
T42MODBM2
T48MODBM7
T51DNP3S
T55T101S
T58T101M7
T59T104S
T60MODBS7
T61DNP3E

Role
Master DNP3 communication task
Master T101/T103 level 2 communication task
Master T103 level 7 communication task
Station Bus Server management task
Station Bus Client management task
Master Modbus level 2 communication task
Master Modbus level 7 communication task
Slave DNP3 communication task
Slave T101 communication task
Master T101 level 7 communication task
Server T104 communication task
Slave Modbus level 7 communication task
Slave DNP3 IP communication task

Traces mask

Bit
0
1
2
3
4
5
6
7

Description
Input messages
Output messages
Messages during task treatment
Level 2 traces (if exist)
Not used
Not used
Not used
Not used

Example :
SET_TRACES(20,3,1) activates display of input / output messages of the GESTTS task.

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 8/29

Edition: Z

Transmission & Distribution


Protection & Contrle

3.4.4

Communication traces

The shell function TRANS_PRINT_TRACE_LEVELS lists the different trace levels.


Trace name
TRANS_TRACE_NONE
TRANS_TRACE_ERROR
TRANS_TRACE_TRAME
TRANS_TRACE_DATA
TRANS_TRACE_CNX
TRANS_TRACE_MES_EMI
TRANS_TRACE_MES_REC
TRANS_TRACE_TRT_TS
TRANS_TRACE_TRT_TC
TRANS_TRACE_TRT_TM
TRANS_TRACE_TRT_PERT
TRANS_TRACE_TRT_TUN
TRANS_TRACE_SYNCHRO
TRANS_TRACE_TRT_EVT
TRANS_TRACE_EMI_TM
TRANS_TRACE_EMI_TS
TRANS_TRACE_INIT
TRANS_TRACE_TRT_GI
TRANS_TRACE_TRT_CT
TRANS_TRACE_PROTOCOL
TRANS_TRACE_TRT_GEN
TRANS_TRACE_TRT_FIC
TRANS_TRACE_TRT_SPI
TRANS_TRACE_TRT_SOE
TRANS_TRACE_TRT_POL
TRANS_TRACE_TRT_SP
TRANS_TRACE_TRT_SIG

Level
0x0000
0x0001
0x0002
0x0004
0x0008
0x0010
0x0020
0x0040
0x0080
0x0100
0x0200
0x0400
0x0800
0x1000
0x2000
0x4000
0x8000
0x10000
0x20000
0x40000
0x80000
0x100000
0x200000
0x400000
0x800000
0x1000000
0x2000000

Comment
No trace are allowed
Trace of error
Trace of sent / received frames
Trace of sent / received data
Trace of indication of connection / disconnection of IED
Trace of sent messages
Trace of received message
Trace of BI management
Trace of command management
Trace of measurement management
Trace of disturbance management
Trace of tunneling management
Trace of synchronisation frames sent to IED
Trace of events in modbus protocol
Trace of TM sent to Application after processing
Trace of TS sent to Application after processing
Trace of initialisation.
Trace of General Interrogation
Trace of Counter management
Trace from Triangle SCL Stack
General treatment
Trace for file upload or download
Trace for SPI management
Trace for SOE management
Trace for polling
Trace of SetPoint management
Trace of SIG (MPS) Management

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 9/29

Edition: Z

Transmission & Distribution


Protection & Contrle

The following table indicates which trace levels are implemented for which process :
Trace name
TRANS_TRACE_ERROR
TRANS_TRACE_TRAME
TRANS_TRACE_DATA
TRANS_TRACE_CNX
TRANS_TRACE_MES_EMI
TRANS_TRACE_MES_REC
TRANS_TRACE_TRT_TS
TRANS_TRACE_TRT_TC
TRANS_TRACE_TRT_TM
TRANS_TRACE_TRT_PERT
TRANS_TRACE_TRT_TUN
TRANS_TRACE_SYNCHRO
TRANS_TRACE_TRT_EVT
TRANS_TRACE_EMI_TM
TRANS_TRACE_EMI_TS
TRANS_TRACE_INIT
TRANS_TRACE_TRT_GI
TRANS_TRACE_TRT_CT
TRANS_TRACE_PROTOCOL
TRANS_TRACE_TRT_GEN
TRANS_TRACE_TRT_FIC
TRANS_TRACE_TRT_SPI
TRANS_TRACE_TRT_SOE
TRANS_TRACE_TRT_POL

IECM2
X
X
X
X

X
X

T103M7 MODBM2 MODBM7


X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

DNP3M
X
X
X
X
X

T101S
X

X
X
X

X
X
X
X
X
X

X
X
X
X
X
X
X
X

Nota : to have the complete list of task, type i on the shell

3.5

S_DBTEST_print_bay

Action : display the electrical configuration


Parameters : none

3.6

S_DBTEST_print_norgint_list

Action : display the list of configured norgint


Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 10/29

Edition: Z

Transmission & Distribution


Protection & Contrle

3.7

S_DBTEST_print_computer_wiring

Action : display the computer wiring


Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 11/29

Edition: Z

Transmission & Distribution


Protection & Contrle

4 TRACES FOR OPERATING MODE


4.1

SET_DEV_MODE x

Action : change the computer operating mode


Parameters : x=1 -> test mode
x=2 -> active mode
x=3 -> stand-by mode
x=4 -> maintenance mode

4.2

SET_MAINT

Action : change the computer mode to maintenance


Parameters : none

4.3

SET_ACTIVE

Action : change the computer mode to operational


Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 12/29

Edition: Z

Transmission & Distribution


Protection & Contrle

5 TRACES FOR THE DRIVERS AND THE COMMUNICATION


PROTOCOLS
5.1

traces_sccx=y

Action : display the input and output frames for a legacy bus
Parameters : x=[1,2,3,4] : port number defined in configuration
y=16 : trace activated
y=0 : trace desactivated

5.2

traces_apieth x

Action : display the input and output frames on TCP-IP


Parameters : x=16 : trace activated
x=0 : trace desactivated

5.3

TunRSLines

Action : display the protocol used on the configured legacy bus


Parameters : none

5.4

TunRSIed x

Action : display the information associated to the IEDs connected to the legacy bus number x
Parameters : x = legacy bus number (0 for SCC1, 1 for SCC2, )

5.5

S_DBTEST_print_line_info

Action : display the information associated to the configured legacy bus


Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 13/29

Edition: Z

Transmission & Distribution


Protection & Contrle

6 TRACES FOR DIGITAL INPUTS (DI)


6.1

active_di board,input,state,valid

Action : simulate a DI state change


Parameters : board : board number
input : channel number
state : DI state (1=SET, 0=RESET)
valid: DI quality (values to be defined)

6.2

aff_di_info board,input

Action : display configuration attributes of a DI


Parameters : board : board number
input : channel number

6.3

aff_di_state board,input

Action : display current state of a DI


Parameters : board : board number
input : channel number

6.4

aff_di_board_state board,type

Action : display current state of all board channels


Parameters : board : board number
type : board type (0=DIU, 1=CCU)

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 14/29

Edition: Z

Transmission & Distribution


Protection & Contrle

7 TRACES FOR ANALOGUE INPUTS (AI)


7.1

aff_ai_info board,input

Action : display configuration attributes of an AI


Parameters : board : board number
input : channel number

7.2

aff_ai_data board,input

Action : display current state and value of an AI


Parameters : board : board number
input : channel number

7.3

aff_ai_board_data board

Action : display current state and value of all board channels


Parameters : board : board number

7.4

set_ai_data index,state,value

Action : change the value and state of an AI


Parameters : index : AI index (input number + board number*number of inputs per board)
state : AI quality (values to be defined)
value : AI value

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 15/29

Edition: Z

Transmission & Distribution


Protection & Contrle

8 TRACES FOR CT/VT MEASUREMENTS


8.1

CTVT_GET_MEAS

Action : display value and quality of all measurements from TMU200/220 board
Parameters : none

8.2

aff_ctvt_config

Action : display configuration attributes of the TMU200/220 board


Parameters : none

8.3

aff_ctvt_data

Action : display data from TMU200/220 board associated to the synchrocheck function
Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 16/29

Edition: Z

Transmission & Distribution


Protection & Contrle

9 TRACES FOR DIGITAL OUTPUTS (DO)


9.1

aff_do_data

Action : display state of all channels of all configured DOU/CCU board


Parameters : none
(# : invalid / - : not activated / + : activated)

9.2

get_state_do board

Action : display state of all channels of a board


Parameters : board : board number
(# : invalid / - : not activated / + : activated)

9.3

active_ccu board,channel,order

Action : activate an output on a CCU board


Parameters : board : board number
channel : channel number
order : 1=activate, 0=desactivate

9.4

active_dou board,channel,order

Action : activate an output on a DOU board


Parameters : board : board number
channel : channel number
order : 1=activate, 0=desactivate

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 17/29

Edition: Z

Transmission & Distribution


Protection & Contrle

10 TRACES FOR BINARY INPUTS (BI)


10.1 aff_bi_info bi_norgint
Action : display the configuration attributes of a BI
Parameters : bi_norgint : requested BI norgint

10.2 aff_bi_grp_info bi_norgint


Action : display the list of BI associated to a group
Parameters : bi_norgint : norgint of the BI group

10.3 aff_bi_state2 bi_norgint


Action : display relation between DI and BI
Parameters : bi_norgint : requested BI norgint

10.4 active_bi norgint, order


Action : modify the state of a BI
Parameters : norgint : BI norgint
order : 1=SET, 0=RESET

10.5 get_di_norgint
Action : display relation between DI and BI
Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 18/29

Edition: Z

Transmission & Distribution


Protection & Contrle

11 TRACES FOR CONTROLS


11.1 aff_co_info co_norgint
Action : display configuration attributes of a control
Parameters : co_norgint : norgint of the requested control

11.2 aff_all_co_info norgdeb, norgfin


Action : display configuration attributes of controls between norgdeb and norgfin
Parameters : norgdeb : norgint of the first control
norgfin : norgint of the last control

11.3 aff_sp_info sp_norgint


Action : display the configuration attributes of a setpoint
Parameters : sp_norgint : norgint of the setpoint

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 19/29

Edition: Z

Transmission & Distribution


Protection & Contrle

12 TRACES FOR COUNTERS (CT)


12.1 aff_ct_data ct_norgint
Action : display the current counter value
Parameters : ct_norgint : norgint of the counter

12.2 aff_ct_info ct_norgint


Action : display the configuration attributes of a counter
Parameters : ct_norgint : norgint of the counter

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 20/29

Edition: Z

Transmission & Distribution


Protection & Contrle

13 TRACES FOR MEASUREMENTS (MV)


13.1 aff_dm_info dm_norgint
Action : display the configuration attributes of a digital measurements
Parameters : dm_norgint : norgint of the measurement

13.2 aff_meas_info norgint


Action : display the configuration attributes of an analogue measurements
Parameters : norgint : norgint of the measurement

13.3 aff_meas_data norgint


Action : display value and status of the measurement
Parameters : norgint : norgint of the measurement

13.4 active_meas norgint,value,quality


Action : change the value and status of the measurement
Parameters : norgint : norgint of the measurement
Value : measurement value
Quality : 0=valid, 1=faulty, 3=open circuit, 4=saturated

13.5 active_from_ai norgint,type,value,quality


Action : change the value and status of the measurement provided by an AIU board
Parameters : norgint : norgint of the measurement
Type : 0=measurement,1=TPI
Value : measurement value
Quality : 0=valid, 1=faulty, 2=undefined, 3=open circuit, 4=saturated, 5=unknown

13.6 active_meas_ctvt norgint,value,quality


Action : change the value and status of the measurement provided by the CT/VT board
Parameters : norgint : norgint of the measurement
Value : measurement value
Quality : 0=valid, 1=faulty, 3=saturated

13.7 active_meas_ied norgint,value,quality


Dsignation: C264 Expertise Maintenance Guide
Date: 15/10/07

Page: 21/29

Edition: Z

Transmission & Distribution


Protection & Contrle

Action : change the value and status of the measurement provided by an IED (legacy or
IEC61850)
Parameters : norgint : norgint of the measurement
Value : measurement value
Quality : 0=valid, 1=faulty, 2=unknown

13.8 aff_sig_info norgint


Action : display configuration attributes of a MPS
Parameters : norgint : norgint of the MPS

13.9 aff_sig_data norgint


Action : display status of the MPS
Parameters : norgint : norgint of the MPS

13.10 active_sig norgint,value,quality


Action : change the value and status of the TPI
Parameters : norgint : norgint of the TPI
Value : TPI value
Quality : 0=valid, 1=faulty, 2=undefined, 3=toggling, 4=unknown

13.11 aff_spi_info norgint


Action : display configuration attributes of a TPI
Parameters : norgint : norgint of the TPI

13.12 aff_spi_data norgint


Action : display value and status of the TPI
Parameters : norgint : norgint of the TPI

13.13 active_spi norgint,value,quality


Action : change the value and status of the TPI
Parameters : norgint : norgint of the TPI
Value : TPI value
Quality : 0=valid, 1=faulty, 2=undefined, 3=open circuit, 4=saturated, 5=unknown

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 22/29

Edition: Z

Transmission & Distribution


Protection & Contrle

14 TRACES FOR AUTORECLOSER, SWITCHGEAR AND MODULES


14.1 S_DBTEST_print_ar_item x
Action : display autorecloser data
Parameters : x : norgint of the autorecloser (available with S_DBTEST_print_norgint_list)

14.2 S_AUTREC_get_ar_context
Action : display all controls used by the autorecloser
Parameters : none.

14.3 S_AUTREC_get_ar_state
Action : display the current autorecloser status
Parameters : norgint of the autorecloser.

14.4 S_DBTEST_print_cb_item x
Action : display circuit breaker data
Parameters : x : norgint of the circuit breaker

14.5 aff_sp_cb_info x
Action : display configuration attributes of a circuit breaker
Parameters : x : norgint of the circuit breaker

14.6 aff_discsw_info
Action : display configuration attributes of a switch
Parameters : x : norgint of the switch

14.7 aff_module_info
Action : display configuration attributes of a module
Parameters : x : norgint of the module

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 23/29

Edition: Z

Transmission & Distribution


Protection & Contrle

15 TRACES FOR TIME SYNCHRONISATION


15.1 synchroInfoShow
Display synchronisation information

15.2 synchroBdShow
Display configuration attributes associated to the time synchronisation

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 24/29

Edition: Z

Transmission & Distribution


Protection & Contrle

16 TRACES FOR ALARMS


16.1 aff_alarm_info x
Action : display configuration attributes of an alarm
Parameters : x : norgint of the alarm.

16.2 ALARM_HELP
Action : List of shell action linked to the alarms
Parameters : none

16.3 read_alarm_header
Action : display global data of the alarm buffer
Parameters : none

16.4 read_diff_alarm_header
Action : display global data of the differed alarm buffer
Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 25/29

Edition: Z

Transmission & Distribution


Protection & Contrle

17 TRACES FOR ATCC


17.1 ccaCatcAff

donGen,group,node,nivTens,device,transf

Action : display of ATCC data


Parameters : donGen : ATCC general data
Group : data on groups managed by the ATCC
Node : data on topological node
NivTens : display of data per voltage level
device : display of data per devices
Transf : display of data per transformer

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 26/29

Edition: Z

Transmission & Distribution


Protection & Contrle

18 TRACES FOR FAST AUTOMATISM ET INTERLOCK


18.1 aff_eql_info
Action : display configuration attributes of all EQL
Parameters : none

18.2 aff_eql_data

index_eql

Action : display data status of the EQL


Parameters : index_eql : EQL number (given by aff_eql_info)

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 27/29

Edition: Z

Transmission & Distribution


Protection & Contrle

19 TRACES FOR REDUNDANCY


19.1 aff_red_data
Action : display data linked to C264 redundancy
Parameters : none

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 28/29

Edition: Z

Transmission & Distribution


Protection & Contrle

Blank Page

End of the document

Dsignation: C264 Expertise Maintenance Guide


Date: 15/10/07

Page: 29/29

Edition: Z