Escolar Documentos
Profissional Documentos
Cultura Documentos
19/05/2014
REF: RFE-SPCI-001
I-FOR INFORMATION
Approval not required
A-APPROVED
R-REJECTED
JSA
IMPORTANT NOTE: documentation approval does not relieve the manufacturer of its
responsibility for the adequancy and suitability of the information, equipments and/or
materials included in it for the function that is intended
ESPECIFICACIONES
TECNICAS DE
SISTEMA DE AGUA
CONTRA INCENDIOS
Comentario 01)
En esencia, el presente documento es una coleccin de catlogos de algunos de los
componentes aportados, asociados a la caseta de bombas (plano RFE-1-SGA-MDM-FSS-003)
Incorprese un apartado introductorio que ordene y de sentido a la coleccin de catlogos
aportados:
a) Un ndice de tems cubiertos por la especificacin, indicando codificacin KKS y plano
P&ID aplicable. Idealmente, el ndice debera cubrir todos los tems del plano RFE-1-SGA-MDMFSS-003.
b) En cada catlogo debe identificarse el n de plano e tem aplicable. P.ej: La
electrobomba hace referencia al tem 2 del plano RFE-1-SGA-MDM-FSS-003.
c) Muchos de los catlogos hacen referencia a gamas comerciales, lo que es equvoco. Debe
resaltarse el modelo exacto que est siendo suministrado.
d) Se echan en falta algunos componentes bsicos, como:
- Bomba Jockey
- Vlvulas de seguridad
PUMP
1
4 X 3 ME
85 1/32
15
18 1/4
18 1/2
10
12
G
11
7 3/8
8 1/8
15/16
3/4
8 - 3/4
7 1/2
7 1/2
4 - 3/4
28
88
ECR
BY
MAR. 6, 2013
33818
DATE
MC
5X4M
85 1/32
15
18 1/4
18 1/2
11
12 3/8
12
4 1/2
4 1/2
15/16
15/16
10
8 - 7/8
8 1/2
8 - 3/4
7 1/2
28
88
85 1/32
15
18 1/4
18 3/4
12
12
12 1/4
6 1/2
6 1/2
1 1/8
1 3/8
11
8 - 7/8
9 1/2
11
8 - 7/8
8 1/2
28
88
8 X 6 MABS
92 11/16 17 5/8
23 3/8
23 1/2
14
15 1/2 14 1/2
10 1/2
1 1/8
13 1/2
11 1/4
8 - 7/8
9 1/2
30
94
8 X 6 MI/YS
89 5/32
16 3/4 20 5/8
20 7/8
12
16 3/8 13 1/2
7 3/4
10
1 1/8
13 1/2
8 - 7/8 11 3/4
8 - 7/8 11 3/4
11
8 - 7/8
9 1/2
29
91
MASTER-DMC
12
55
56 1/4
8 X 6 MJ/YR
85 1/32
18 3/4
12
5 5/8
6 5/8
1 1/8
13 1/2
8 - 7/8 11 3/4
11
8 - 7/8
9 1/2
28
88
METRON-FD4
HUBBELL-LX-3000
11
36 1/2
58
TORNATECH-GPD
36
15
18 1/4
13
11
10 X 8 M
101 9/32
22
27 1/2
23 1/2
18
16
9 3/16
11 3/4
1 3/16
1 1/8
10
16
12 - 1
14 1/4
13 3/4
8 - 7/8
11 3/4
34
106
103 9/32
22 7/8
28 5/8
26 3/4
18
24
19
12
12
1 5/8
12
20 1/2
12 - 1
17
15
8 - 7/8
11 3/4
34
106
101 9/32
22
27 1/2
25
17
22
18
12 1/4
13 1/4
1 1/4
1 3/16
12
19
12 - 1
17
10
16
12 - 1
14 1/4
34
106
12 X 10 MAA
19 1/4
UNIT
JOB
PUMP
5
U
REV
6 X 5 MAA
3 12 X 8 MAA
ZONE
CAPACITY
ENGINE
JU6H
BB
48
54
PACKAGE
MOUNTED
CONTROLLER
(OPTIONAL)
FT. HD.
VOLTS
H.P.
AA
12
FIRETROL-FTA 1100
G.P.M. @
R.P.M.
CONTROLLER
CONTROLLER
DATE
CERTIFIED BY:
4 15/16
EXHAUST
"T"
(TURBOCHARGED)
MODELS
JU6H-UF30,-UF32,-UF34
JU6H-UF50,-UF52,-UF54
JU6H-UF58,-UFD0,-UFD2
JU6H-UFG8,-UFM0,-UFM2
JU6H-UFM8, -UFABL8
JU6H-UFABL0,-UFABL2
SHOWN
9 7/16
A
B
51 5/16
"TRWA"
7 (TURBOCHARGED w/
RAW WATER
AFTERCOOLING) MODELS
JU6H-UFAAQ8, -UFAARG
JU6H-UFAAPG, -UFAAS0
JU6H-UF60,-UF62,-UF68
JU6H-UFAB76, -UF84
IN PHANTOM
RAW WATER
OUTLET 1-1/4"NPTF
PLAN VIEW
28 31/32
3/8
AA
EXHAUST
RAW WATER
OUTLET
9
45 13/32
F
FUEL
PUMP CL
BB
10
10
23 29/32
14 9/32
M
11
11
5 13/32
13 1/2
15 1/2
D
12
13
125#
(N) SUCTION
(O) O.D. FLANGE
(P) HOLES
(Q) D.B.C.
125#
(R) DISCHARGE
(S) O.D. FLANGE
(T) HOLES
(U) D.B.C.
PUMP C
L
13
15
13
15
COUPLING
GUARD
3 1/2
14
1 1/2
TYP.
3
TYP.
15
A
12
PUMP C
L
V
W
1 1/2
GROUT MIN.
18
13
5
TYP.
30
36
DRIP RIM BASE (OPTIONAL)
C
REV.
DWG. NO.
4
13
13
30
2X 3/4 NPT
DRAINS
ITEM
2
F
OUTLINE DIMENSIONS
FOR
VARIOUS PUMPS
W/ CLARKE JU6H ENGINES
14
C02-98264 7
DRAWN
DATE
MATT C.
SCALE
5/4/2005
APPRVD.
NONE
V
15
A.P.
W
FTA550E
Jockey Pump Controllers
Specifications
Event Recording
Memory - The controller shall record all operational
and alarm events to system memory. All events shall be
time and date stamped and include an index number.
The system memory shall have the capability of storing
3000 events and allow the user access to the event log
via the user interface. The user shall have the ability to
scroll through the stored messages in groups of 1 or 10.
Serial Communications
The controller shall feature a RS485 serial communications port for use with 2 or 4 wire Modbus communications.
Solid State Pressure Transducer
The controller shall be supplied with a stainless steel
solid state pressure transducer with a range of 0-300 psi
(0-20.7 bar) 1 psi. The solid state pressure transducer
shall be used for both display of the system pressure and
control of the jockey pump controller. Systems using analog pressure devices or mercury switches for operational
control will not be accepted.
The START and STOP PRESSURE shall be adjustable
through the user interface. The pressure transducer shall
be mounted inside the controller to prevent accidental
damage. The pressure transducer shall be directly pipe
mounted to a bulkhead pipe coupling without any other
supporting members. Field connections shall be made
externally at the controller coupling to prevent distortion
of the pressure switch element and mechanism.
Seismic Certification
The controller shall be certified to meet or exceed the
requirements of the 2006 International Building Code
and the 2010 California Building Code with Importance
Factor 1.5 and Sds equal to 1.88 or less. Qualifications
SP550E-01
EmersonNetworkPower.com
Racks & Integrated Cabinets
AC Power
Embedded Computing
Outside Plant
Connectivity
Embedded Power
Services
DC Power
Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2012 Emerson Electric Co.
'iretrol Brand Products Cary
North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
DISPONIBLE
Network Power
pintado
- Nema Tipo 4X (IEC IP56), acero inoxidable #316, sin
acabado fino**
- Nema Tipo 4X (IEC IP56), acero inoxidable #316, calibre
12 con soldadura de costura, pulido y cepilldo
- Nema Tipo 4X (IEC IP56), acero inoxidable #316,
pintado
- Nema Tipo 12 (IEC IP52), acero pintado
**Sin acabado fino: Sin pintar, pulir o cepillar
Los tipos de gabinetes NEMA mencionados,
igualan o superan las exigencias de los tipos IEC
citados entre parntesis().
Caractersticas
El controlador Firetrol Mark II supervisa, muestra
y registra informacin del sistema de la bomba contra
incendios. Este sistema es estndar en todos los controladores Firetrol de servicio no limitado, para bombas
contra incendio elctricas (600 VAC max.). Un controlador y Puerto USB maestro, tambin es incluido como
estndar.
Aprobaciones
Los controles Firetrol para bombas contra incendios, son listados por Laboratorios UL (Underwriters
Laboratories), de acuerdo a UL218, Standard for Fire
Pump Controllers, CSA, Standard for Industrial Control
Equipment (cUL) y tambin son aprobados por Factory
Mutual. Estos son construidos para cumplir o exceder los
requerimientos de las autoridades de aprobacin listadas
anteriormente, as como NEMA y las ltimas ediciones
de NFPA 20, Standard for the Installation of Stationary
Pumps for Fire Protection y NFPA 70, National Electrical
Code.
Gabinetes
Los gabinetes estndar son NEMA Tipo 2 (IEC
IP11), a prueba de goteo, para instalaciones en reas
protegidas de la luz directa del sol, con temperatura
ambiente por encima de 41 F (5 C). Los siguientes
tipos de gabinetes son opcionales:
- Nema Tipo 3R (IEC IP14), acero pintado
- Nema Tipo 4 (IEC IP56), acero pintado
- Nema Tipo 4X (IEC IP56), acero inoxidable #304, sin
acabado fino**
- Nema Tipo 4X (IEC IP56), acero inoxidable #304,
Operacin
En el corazn del Mark II, hay un CPU especialmente
diseado, conformado por un procesador Intel, un reloj
de tiempo real con batera de respaldo y una sistema
de memoria con un total de 256K.
El controlador y Puerto maestro USB incluido en el
MarkII, permite la actualizacin del software, simplemente colocando una memoria USB(Memoria flash)
con el software actualizado, lo cual implica que no se
requiere de un computador porttil o aparatos externos
para realizar esta actualizacin.
Medicin
El controlador provee medicin de Amperios y Voltios,
usando la tecnologa de RMS real. La pantalla de
dos lneas permite la visualizacin del voltaje y el
amperaje en las tres fases simultneamente.
La presin es mostrada en psi o bars, con incrementos de 1 psi 0.1bars. El controlador es suministrado
como estndar para 0-300 psi (0-20.7 bars) y opcionalmente, 0-600 psi (0-41.4 bars).
Reservorio bajo
Arranque local activado
Arranque remoto activado
Arranque de emergencia
Reinicializacin del sistema
Datos Histricos
El controlador supervisa y registra los datos histricos en la memoria, en un rea separada de donde se
guardan estas alarmas/eventos. Esta informacin puede
ser vista en la pantalla y/o guardada en la memoria USB
Los siguientes datos histricos son incluidos:
Tiempo total de funcionamiento del motor
Total de arranques
Ultimo tiempo de funcionamiento del motor
Tiempo total con voltaje aplicado
Ultima corriente de arranque
Total de llamadas de arranque
Fecha y hora del ltimo arranque
Max/min corrientes de funcionamiento
Corriente de disparo
Fecha y hora del ltimo disparo por rotor bloqueado
Fecha y hora de la ltima inversin de fases
Fecha y hora de la ltima falla de fase
Max/min voltajes
Max/min frecuencias
Max/min presiones
Registro de la presin
La presin del sistema puede ser registrada en tres
formas:
Presin diferencial programada por el usuario - El
usuario selecciona un diferencial de presin, entre 5
y 50 psi (.3 - 3.4 bars); cada vez que la presin del
sistema excede este diferencial, sta es grabada.
Horaria - La presin es grabada cada hora.
Si el motor esta funcionando, la presin del sistema
es grabada automticamente cada 15 segundos.
Comunicacin Serial
El Mark II esta equipado con un Puerto de comunicacin
RS485. Opcionalmente, este puerto puede ser usado con
Modbus RTU con 2 o 4 cables, o con Modbus/TCP Ethernet LAN (Usando un modulo 5150). Comercialmente
existe una variedad de convertidores para conectarse
con otros protocolos de comunicacin.
Clasificacin de Servicio de Entrada
Los controladores son suministrados como estndar
con un terminal de conexin a tierra y con la conexin y
espaciado requeridos para ser usado como un equipo
con servicio de entrada, listado por UL.
65 kA
150 kA
200 kA
3250 HP
3250 HP
300 HP
3250 HP
3250 HP
300 HP
450-500 HP 3400 HP
450-500 HP 3400 HP
450-500 HP 3400 HP
450-500 HP 3400 HP
3500 HP
600 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3400 HP
3300 HP
3300 HP
450-700 HP
100 kA
65 kA
100 kA
150 kA
200 kA
300 HP
300 HP
450-500 HP
450-500 HP
450-500 HP
450-500 HP
600 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3500 HP
3500 HP
3500 HP
600-700 HP
200V, 60hz
208V, 60hz
220V, 50hz
220-240V, 60hz
380V, 50hz
380V, 60hz
415V, 50hz
415V, 60hz
440-480V, 60hz
550-600V, 60hz
700 HP
65 kA
100 kA
150 kA
200 kA
300 HP
300 HP
450-500 HP
450-500 HP
450-500 HP
450-500 HP
600 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3250 HP
3250 HP
3250 HP
3250 HP
3400 HP
3400 HP
3400 HP
3400 HP
3500 HP
3600 HP
3600 HP
3600 HP
100 kA
150 kA
200 kA
3200 HP
3200 HP
3200 HP
3200 HP
3300 HP
3300 HP
3300 HP
3300 HP
3450 HP
3200 HP
3200 HP
3200 HP
3200 HP
3300 HP
3300 HP
3300 HP
3300 HP
3450 HP
3200 HP
3200 HP
3200 HP
3200 HP
3300 HP
3300 HP
3300 HP
3300 HP
3450 HP
3400 HP
3300 HP
3300 HP
450-500 HP
65 kA
Conexiones de Campo
Dentro del controlador, convenientemente localizados, se encuentran los terminales que proporcionan
contactos de salida para: Bomba funcionando, inversin
de fases y falla de fase. Tambin se proveen terminales
de conexiones de campo para: Panel de alarmas remotas, pulsador de arranque remoto, vlvula de diluvio e
interlock remoto. Un diagrama de conexiones de campo,
es adherido permanentemente en la parte interna de la
puerta.
Un manual de instrucciones y operaciones, es incluido con cada controlador.
4
Paneles de Alarmas
Dentro del controlador se suministran terminales para
la conexin de campo de paneles de alarma FTA200-A
o FTA200-B, o para paneles de parada FTA200-D o
FTA200-E.
El controlador tambin puede ser suministrado
con un panel de alarma interno (built-in), instalado en
fbrica, FTA200-C.
Este panel de alarma, dar una seal audible si el
voltaje de control falla o si la bomba est funcionando,
as como tambin incorpora una seal luminosa para
monitorear el voltaje supervisor. Este sistema no afecta
las seales remotas de alarma un sistema de alarmas
remotas, completamente separado, puede seguir siendo
usado.
Tipos de Controladores
Mtodo
Arranque
Tensin Plena
Dev. Partido
Estrella-Trin.
Resistencia
Primaria
Autotransformador
Estado Slido
% Corriente de
Arranque a
Torque
Plena Carga Arranque
600%
390%
200%
300%
100%
42%
33%
25%
150%
252%*
384%
240%
25%
42%*
64%
15%
Mtodo
parada
Instantneo
Instantneo
Instantneo
Instantneo
Instantneo
Suave
Si no hay causas de arranque adicionales, el arrancador suave permitir que el motor contine la rampa de
desaceleracin, hasta que se detenga completamente.
Opciones y Modificaciones
Refirase a la hoja de descripcin del producto, para
ver la lista completa de opciones y modificaciones.
6
Interruptores de Transferencia
Informacin General
Los interruptores de transferencia Firetrol, estn
disponibles, completamente ensamblados con los
controladores de bombas contra incendios Firetrol. Los
interruptores de transferencia son fabricados en dos
versiones:
FTA900: Construccin
El controlador de la bomba elctrica contra incendios
y el interruptor de transferencia estn ensamblados en
gabinetes diferentes, pero conectados entre s. Todo el
cableado entre los dos gabinetes es realizado por Firetrol.
El gabinete que contiene el interruptor de transferencia, tiene una manija instalada externamente, para
la operacin del interruptor de aislamiento de la fuente
de emergencia. La manija de operacin tiene un enclavamiento mecnico para evitar que la puerta pueda ser
abierta cuando el interruptor de aislamiento se encuentra
en la posicin ON.
La pantalla/interfaz del MarkII, tiene incluidos LEDs
para: TRANSFER SWITCH NORMAL (Interruptor de
transferencia en Normal), TRANSFER SWITCH EMERGENCY (Interruptor de transferencia en Emergencia) y
EMERGENCY ISOLATING SWITCH OFF (Interruptor de
aislamiento de la fuente de emergencia abierto). Instalados en el gabinete, se encuentran los selectores para
transferencia (Automtica-Prueba) y para retransferencia (Retardada-Inmediata), as como tambin la alarma
audible.
Mdulo de Control
El mdulo de control incluye las siguientes funciones:
Deteccin precisa, tipo diferencial, del voltaje en
todas las fases de la fuente normal.
Voltaje de Pick-up Ajustable a 90% o 95% del
voltaje nominal. Ajustado en fbrica a 90%.
Voltaje de Drop-out Ajustable de 70% a 90% del
voltaje nominal. Ajustado en fbrica a 85%.
Deteccin precisa del voltaje de la fuente de emergencia.
Voltaje de Pick-up Ajustado en fbrica a 90% del
voltaje nominal.
Voltaje de Drop-out Ajustado en fbrica a 75% del
voltaje nominal.
Sensado preciso de la frecuencia, de la fuente de
emergencia.
Frecuencia de Pick-up Ajustado en fbrica a 95%
de la frecuencia nominal.
Frecuencia de Drop-out Ajustado en fbrica a 85%
de la frecuencia nominal.
Tiempo para neutralizar las seales de transferencia
y de arranque del generador en caso de una falla
temporal de la fuente normal.
Retardo: Ajustable a 1 o 3 segundos. Ajustado en
fbrica a 1 segundo.
La retransferencia de la fuente de emergencia a la
normal es retardada automticamente, a menos que
la fuente de emergencia falle.
7
Interruptores de Transferencia
Informacin General
Dentro del gabinete del interruptor de transferencia,
se encuentran el interruptor de aislamiento de la fuente
de emergencia, los rels de control, el mdulo de estado
slido para control y temporizacin, y el interruptor de
transferencia.
El interruptor de transferencia es elctricamente
operado y mecnicamente mantenido. Una palanca es
provista para transferir manualmente el interruptor en
caso de una emergencia o para probar la operacin del
interruptor de transferencia.
Contactos auxiliares adicionales NO y NC, que indican la posicin del interruptor de transferencia y del
interruptor de aislamiento de la fuente de emergencia,
son cableados a terminales para uso del cliente.
sta es movida a la posicin OFF, primero abre el interruptor de corriente y luego el interruptor de aislamiento. El
interruptor de corriente siempre abre y cierra la corriente
de carga.
FTA950 Capacidad de Corriente de Cortocircuito
La capacidad de corriente de cortocircuito, para el
lado de la fuente normal y para el lado de la fuente de
emergencia, del interruptor de transferencia, ser la
misma que la del controlador de la bomba de incendio
que esta ensamblado con el interruptor de transferencia.
Opciones y Modificaciones
Refirase a la hoja de descripcin del producto, para ver
la lista completa de opciones y modificaciones.
Otros Productos y Servicios de Firetrol
Contacte a la fbrica para mayor informacin acerca
de:
Controladores de bombas Jockey
Paneles de alarmas remotas de la bomba contra
incendios
Controladores de bombas contra incendios de alto
voltaje 100-4000 HP (74-2984 kW), 7200 Volts
Mximo
Controladores de bombas contra incendios tipo Diesel
Asistencia de ingeniera para aplicaciones especiales
de control de bombas contra incendios, incluyendo
sistemas de zona alta/zona baja y controladores para
reas clasificadas
Control de sistemas de motores simples, dobles o
triples
Sistemas de control de frecuencia variable
Control de motores para sistemas de recoleccin y
sistemas de aguas residuales
Sistemas basados en PLC y computadoras
ASCO 2008
Mark II
Electric Fire Pump Controllers
and
Limited Service Controllers
NS1000-40 (02-20-08)
Network Power
Table of Contents
SECTION ONE
Introduction ........................................................................................................................................................1
Mounting Legs ...................................................................................................................................................1
Mounting Controller ...........................................................................................................................................1
Wall Mount ............................................................................................................................................1-2
Floor/Base Plate Mount ...........................................................................................................................2
Making Electrical Connections ..........................................................................................................................2
General Pre-Start Up Operation ........................................................................................................................2
General Start Up Operation ...............................................................................................................................3
Voltage Check..........................................................................................................................................3
Phase Rotation ........................................................................................................................................3
Motor Rotation ......................................................................................................................................3-5
Initial Start Up Operation ...................................................................................................................................5
Abbreviated Starting Sequence ......................................................................................................................5-6
Additional Information for FTA1900 Controllers..............................................................................................6-7
SECTION TWO
Mark II Setup Notes ...........................................................................................................................................8
Mark II Menu Structure - Overview ..................................................................................................................9
Detailed Instructions
Meter Function....................................................................................................................................10
Event Log ...........................................................................................................................................10
Data Log .............................................................................................................................................10
Pressure Settings
Stop Pressure ........................................................................................................................10
Start Pressure........................................................................................................................10
Manual Stop Only .................................................................................................................. 11
Timers
On Delay Time ....................................................................................................................... 11
Minimum Run Time................................................................................................................ 11
Off Delay Time ....................................................................................................................... 11
Weekly Test Time................................................................................................................... 11
Alarm Limits
Reverse Phases ....................................................................................................................12
Clock Set ............................................................................................................................................12
Daylight Savings Time ...........................................................................................................12
System Setup
Flash Drive Autosave.............................................................................................................12
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENERGIZED! DEATH,
PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE MAY RESULT FROM CONTACT WITH ENERGIZED
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING, AND ALWAYS FOLLOW
GENERALLY ACCEPTED SAFETY PROCEDURES. LIMITED SERVICE CONTROLLER ON-OFF SWITCH MUST
BE IN THE EXTREME OFF POSITION TO OPEN THE ENCLOSURE DOOR. FIRETROL, INC. CANNOT BE LIABLE
FOR ANY MISAPPLICATION OR INCORRECT INSTALLATION OF ITS PRODUCTS.
INTRODUCTION
Firetrol combined automatic and manual fire pump controllers are intended for starting electric motor driven fire
pumps. This manual covers the following controllers:
FTA750 - Limited Service Controllers (Full Voltage Starting)
FTA1000 - Full Voltage Starting
FTA1250 - Part Winding Reduced Current
Starting (Closed Circuit Transition)
FTA1300 - Wye-Delta Reduced Voltage
Starting (Open Circuit Transition)
FTA1350 - Wye-Delta Reduced Voltage
Starting (Closed Circuit Transition)
FTA1500 - Primary Resistance Reduced Voltage
Starting (Closed Circuit Transition)
FTA1800 - Autotransformer Reduced Voltage
Starting (Closed Circuit Transition)
FTA1900 - Solid State Reduced Voltage Starting
Firetrol fire pump controllers are listed, approved or certified by the following approving authorities: Underwriters
Laboratories, Inc., Underwriters Laboratories of Canada, Canadian Standards Association, New York Board of Standards
and Appeals and Factory Mutual. They are built to meet or exceed the requirements of the approving authorities listed
above as well as NEMA and the latest editions of NFPA 20 and NFPA 70.
These instructions are intended to assist in the understanding of the installation and operation of these controllers.
Read the instructions thoroughly prior to connecting the controller. If there are any unanswered questions, please contact
the local Firetrol representative or factory service department.
MOUNTING LEGS
PROCEDURE1. If legs were supplied, unpack the legs and mounting hardware.
2. Inspect legs for damage.
3. Securely lift controller or lay it on its back being careful not to damage painted surface.
4. Attach each leg to the bottom of the enclosure using the three nuts, bolts, and washers provided for each leg.
Tighten bolts securely.
5. After legs are securely attached, stand the controller up on its legs for floor mounting. Each leg has three holes
on the bottom for anchoring to the floor or base plate.
CAUTION: The controller is not free standing! The controller must be secured to the floor or wall before opening door
or operating.
MOUNTING CONTROLLER
NOTEConsult the appropriate job plans to determine the controller mounting location. Tools and materials (all mounting) required:
1. Assortment of common hand tools of the type used to service electromechanical equipment.
2. Drill for drilling wall/floor anchor holes.
3. Hand level.
4. Tape measure.
5. Four anchors with bolts and washers, per enclosure - if wall mount.
6. Six anchors, bolts and washers, per enclosure - if floor/base plate mount.
WALL MOUNT
NOTERefer to the appropriate dimension drawing for the controller included in the instruction manual for necessary
mounting dimensions.
The controller is wall mounted by using two lower mounting brackets and four (4) wall anchors, two anchors for
the top ears and two anchors for the lower brackets. The lower brackets should be mounted in line with the mounting
ears.
1. Using either the dimension print or by measuring the distance between the centers of the two mounting ears,
transcribe this dimension on the wall.
NOTEThe bottom edge of the enclosure should be a minimum of 12 inches (305 mm) from the floor in case flooding
of the pump room occurs.
2. Drill and put two anchors into the wall for the lower mounting brackets.
3.
4.
5.
6.
Install the lower mounting brackets securely using two bolts and washers in these anchors.
Mark on the wall the location of the holes for the upper mounting ears.
Drill and put two anchors into the wall for the upper mounts.
Lift the controller onto the lower mounting brackets and align the holes in the upper mounting ears with the upper
anchors.
7. Install bolts and washers in the upper anchors.
8. Tighten the upper mounting bolts.
9. Check to be sure the enclosure door opens freely and that the enclosure is level.
10. Use the nuts, bolts and washers provided for mounting legs to seal the six holes in the bottom of the enclosure.
FLOOR/BASE PLATE MOUNT
NOTEConsult the appropriate job plans to determine the controller mounting location. Refer to the controller dimension print for necessary mounting dimensions.
The controller is floor/base plate mounted by using the three pre-drilled holes in each leg. The holes are dimensionally on the same line for ease of mounting.
1. Using either the dimension print or by measuring the distance between the center lines of the holes on one leg,
transcribe these dimensions onto floor/base plate.
2. Drill three holes in the floor/base plate for anchoring the leg.
3. Mark the location of the holes for the opposite leg and drill three more holes.
4. Secure the controller to the floor/base plate with bolts and washers and tighten.
5. Check to be sure the enclosure door opens freely and that the enclosure is level.
MAKING ELECTRICAL CONNECTIONS
Important Precautions
Prior to making any field connections:
1. Verity that the following information is compatible with other related equipment on the project:
Firetrol catalog number
Motor horsepower, voltage, phase and frequency
System pressure
2. The project electrical contractor must supply all necessary wiring for field connections in accordance with the National
Electrical Code, local electrical code and any other authority having jurisdiction.
3. Open the door of the enclosure and inspect the internal components and wiring for any signs of frayed or loose
wires or other visible damage.
4. Refer to the appropriate field connection drawing in the manual for all wiring information.
Procedure
All field connections, remote alarm functions and AC wiring are brought into the enclosure through the top, bottom, or
side conduit entrances as indicated on the dimension drawing. Refer to the National Electrical Code, the local electrical
code or any other authority having jurisdiction for proper conduit entrance location.
1. Use a hole punch, not a torch nor a drill, and punch a hole in the enclosure for the size conduit being used.
2. Install necessary conduit.
3. Pull all wires necessary for field connections, remote alarm functions, AC power and all other optional features.
Allow enough excess wire inside the enclosure to make up connections to the appropriate line, load and control
terminal block points. Be sure to consult the appropriate field connection diagram included with the manual. For
proper wire sizing, refer to the National Electrical Code, NFPA 70.
4. Make all field connections to the remote alarm functions and any other optional features. Do not connect AC
power.
5. Verify AC line voltage, phase and frequency with the controller data plate on the enclosure door prior to connecting
AC power.
6. Connect the AC power.
7. Check to see that all connections are both correctly wired (in accordance with the field connection diagram) and
tight
8. Close the enclosure door.
GENERAL PRE-START UP OPERATION
1. Controllers are shipped with the EMERGENCY RUN handle in the latched position. Be-fore placing the controller
in service, turn the EMERGENCY RUN handle and release to unlatch.
2. Check the controller for bolts, nuts and electrical connections which may have loosened during shipment.
3. If a remote start push-button is used, connect the wires to terminals 6 and 7.
4. If a deluge valve is used, remove the jumper from terminals 1 and 8. Connect wires from the normally closed contact
on the deluge valve to terminals 1 and 8.
5. If a FTA200 remote alarm panel is used, connect like numbered terminals in the remote alarm panel to terminals 17,
18, 19 and 20 in the fire pump controller. Terminals H and N must be connected if a FTA200 alarm panel is used.
6. If a FTA200 remote alarm panel is used, connect a reliable, separate, supervisory 120 volt power supply to
terminals L1 and L2 in the alarm panel.
At this time, it is necessary to prepare the controller for normal operation. See
section 2 for setup instructions for the Mark II. After the Mark II has been configured, return to this section.
Phase Rotation
The Mark II is designed to indicate phase loss and/or phase reversal. Separate LEDs indicate POWER ON and
PHASE REVERSAL. If external alarms are wired, these failures will also be indicated at the remote alarm location. The
Mark II is factory programmed for the standard ABC phase relationship. If voltage is available on all three phases and
the PHASE REVERSAL LED comes on, see Section 2 - Alarm Limits-Reverse Phases.
Note: FTA1900 ONLY - Both the Mark II and the Solid State Soft Starter are phase rotation sensitive. The above method
of clearing a phase reversal will not work on a FTA1900 controller. If a phase reversal is being shown on the Mark II
and the Solid State Soft Starter, two of the cables at the LINE side of the circuit breaker must be reversed.
1. Open the isolating switch/circuit by moving the operating handle to the OFF position.
2. Disconnect power on the line side of the isolating switch/circuit breaker. Reverse any two of the incoming
power lines. Reconnect power to the incoming feed.
3. Close the enclosure door and while holding the STOP push-button depressed, close the isolating switch/circuit
breaker.
4. Verify that the POWER AVAILABLE LED is illuminated and the PHASE REVERSAL LED is extinguished.
5. Open the isolating switch/circuit breaker and release the STOP push-button.
MOTOR ROTATION
Confirm direction of motor rotation as follows:
FTA750, 1000, 1500, 1800 CONTROLLERS
1. Close enclosure door.
2. Momentarily close the isolating switch/circuit breaker handle, i.e. move up to the ON posi-tion and then back to
OFF.
3. The pump motor should rotate immediately if system pressure is low. If system pressure is not low, press the manual
START push-button and immediately press the manual STOP push-button.
4. Observe direction of motor rotation.
5. If rotation is incorrect, confirm that the isolating switch/circuit breaker is in the OFF position, open enclosure door
and reverse any two of the motor leads (T1, T2, T3) on the load side of contactor 1M. For example, T1 and T2, T1
and T3 or T2 and T3.
6. Retest for proper rotation following steps 1 through 4.
FTA1250 CONTROLLERS
1. Close enclosure door.
2. Momentarily close the isolating switch/circuit breaker handle, i.e. move up to the ON posi-tion and then back to
OFF.
3. The pump motor should rotate immediately if system pressure is low. If system pressure is not low, press the manual
START push-button and immediately press the manual STOP push-button.
4. Observe direction of motor rotation.
5. If rotation is incorrect, confirm that the isolating switch/circuit breaker is in the OFF position, open enclosure door
and reverse any two of the corresponding motor leads (T1, T2, T3, T7, T8, T9) on the load side of both contactors
1M and 2M. For example reverse T1 and T2 on contactor 1M and T7 and T8 on contactor 2M; or T1 and T3 on
contactor 1M and T7 and T9 on contactor 2M; or T2 and T3 on contactor 1M and T8 and T9 on contactor 2M.
6. Retest for proper rotation following steps 1 through 4.
FTA1300, 1350 CONTROLLERS
1. Close enclosure door.
2. Momentarily close the isolating switch/circuit breaker handle, i.e. move up to the ON posi-tion and then back to
OFF.
3. The pump motor should rotate immediately if system pressure is low. If system pressure is not low, press the manual
START push-button and immediately press the manual STOP push-button.
4. Observe direction of motor rotation.
5. If rotation is incorrect, confirm that the isolating switch/circuit breaker is in the OFF position, open enclosure door
and reverse any two of the corresponding motor leads (T1, T2, T3, T6/T12, T4/T10, T5/T11) on the load side of both
contactors 1M and 2M. For example, reverse T1 and T2 on contactor 1M and T6/T12 and T4/T10 on contactor 2M;
or T1 and T3 on contactor 1M and T6/T12 and T5/T11 on contactor 2M; or T2 and T3 on contactor 1M and T4/T10
and T5/T11 on contactor 2M.
6. Retest for proper rotation following steps 1 through 4.
FTA1900 Controllers
1. Close enclosure door.
2. Momentarily close the isolating switch/circuit breaker handle, i.e. move up to the ON position and then back to
OFF.
3. The pump motor should rotate immediately if system pressure is low. If system pressure is not low, press the manual
START push-button and immediately press the manual STOP push-button.
4. Observe direction of motor rotation.
5. If rotation is incorrect, confirm that the isolating switch/circuit breaker is in the OFF position, open enclosure door
and reverse any two of the motor leads (T1, T2, T3) on the load side of contactor 1M. For example, T1 and T2, T1
and T3 or T2 and T3.
6. Retest for proper rotation following steps 1 through 4
FTA900, 975 POWER TRANSFER SWITCH
1. Confirm motor rotation from the normal power source for the controller as outlined above.
2. Open both the controller isolating disconnect switch/circuit breaker and the transfer switch isolating disconnect
switch by moving the operating handles to the OFF position.
3. Refer to the Automatic Transfer Switch Operators Manual. Manually transfer the switch to the emergency power
source.
4. Start the generator set at the generator control panel.
5. With the generator running at stable voltage and frequency momentarily close the power transfer switch isolating
disconnect switch. The pump motor should rotate immediately because system pressure is low. If system pressure
is not low, press the manual START push-button and immediately press the manual STOP push-button.
6. Observe motor rotation. Confirm that the isolating switch is in the OFF position. Shut down generator set.
7. If rotation is incorrect, reverse any two of the line leads at the power transfer switch isolating disconnect switch (L1,
L2, L3). For example, L1 and L2, or L2 and L3, or L1 and L3.
8. Retest for proper rotation following steps 1 through 6.
FTA950, 976 POWER TRANSFER SWITCH
1. Confirm motor rotation from the normal power source for the controller as outlined above.
2. Open both the controller and transfer switch isolating disconnect/circuit breakers by mov-ing the operating handles
to the OFF position.
3. Refer to the Automatic Transfer Switch Operators Manual. Manually transfer the switch to the emergency power
source.
4. Momentarily close the power transfer switch isolating disconnect switch/circuit breaker. The pump motor should
rotate immediately if system pressure is low. If system pressure is not low, press the manual START push-button
and immediately press the manual STOP push-button.
5. Observe motor rotation.
6. If rotation is incorrect, confirm that the isolating disconnect switch/circuit breakers are in the OFF position. Request
the utility company to disconnect the second utility incoming power at the source, then reverse any two of the line
leads at the power transfer switch isolating disconnect switch (L1, L2, L3). For example, L1 and L2, L1 and L3, or
L2 and L3.
7. Retest for proper rotation following steps 1 through 5 above.
INITIAL START-UP OPERATION
1. Place circuit breaker in ON position. The pump may start immediately if system pressure is low. The PUMP RUNNING and LOW PRESSURE LEDs will be lit.
2. If the Mark II is configured for automatic shutdown (MANUAL STOP disabled), the pump motor will continue to run
for the period of time set in the MIN RUN (or OFF DELAY) screen and then stop automatically, providing the STOP
pressure setting has been reached. Both the system pressure and MIN RUN (or OFF DELAY) time remaining will
be shown on the display. Depressing the STOP push-button during the running period will stop the motor as long
as the button is held in. However, the motor will restart when the button is released if system pressure is below the
stop setting.
3. If the controller is configured for manual shutdown (MANUAL STOP enabled), the pump will continue to run until
the STOP push-button is depressed.
4. To stop the motor otherwise, press and hold the STOP push-button and place the CIRCUIT BREAKER DISCONNECTING MEANS handle in the OFF position.
FOR MANUAL START
1. Follow the initial start-up instructions. The isolating switch/circuit breaker should be closed, the POWER AVAILABLE
LED should be illuminated and system pressure normal, i.e. higher than the programmed START PRESSURE setting.
2. Press the START push-button. The pump motor should start and continue to run. It will not stop automatically. The
running period timer and pressure switch have no control over this manual operation.
3. To stop, press the STOP push-button.
4. Starting from a remote START push-button (if used) functions in the same way as the local START push-button.
5. If the pump motor restarts, system pressure is below the START PRESSURE setting.
FOR EMERGENCY RUN START
1. Follow the initial start-up instructions. The isolating switch/circuit breaker should be closed, the green POWER
AVAILABLE LED should be illuminated and pressure normal.
2. Push and lock the EMERGENCY RUN handle. The motor will start and continue to run until both of the following
conditions have been satisfied:
a. The EMERGENCY RUN handle has been turned to un-lock position and released.
b. The STOP push-button is pushed.
3. To stop the motor with the handle locked in the run position, place the circuit breaker handle in the OFF position,
then turn the EMERGENCY RUN handle and release.
4. Return the circuit breaker operator to the ON position.
5. If the pump restarts, system pressure is below the START PRESSURE setting.
ABBREVIATED STARTING SEQUENCE
FTA750, FTA1000 FULL VOLTAGE CONTROLLER
1. Follow all of the initial start-up instructions.
2. The motor will start and run at full line voltage.
FTA1250 PART WINDING CONTROLLERS
1. Follow all of the initial start-up instructions.
2. MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary. (See section
2, Mark II Programming for details).
CAUTION: DO NOT EXCEED FOUR (4) SECONDS MAXIMUM OR MOTOR MANUFACTURERS LIMITS.
3. Contactor 1M connects 1/2 of motor windings during starting cycle. The motor may not reach full speed until the
MOTOR ACCELERATION timer has timed out and both contac-tors 1M and 2M are energized.
FTA1300-1350 WYE-DELTA CONTROLLERS 1
1. Follow all of the initial start-up instructions.
2. MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary. (See section
2, Mark II Programming for details).
CAUTION: DO NOT EXCEED THIS TIMER SETTING WITHOUT CONSULTING YOUR FIRETROL REPRESENTATIVE.
3. a. FTA1300 - Contactors 1M and 1S connect the motor in the WYE configuration. The motor may not reach full
speed until the MOTOR ACCELERATION timer has timed out, deenergizing 1S and energizing 2M, connecting
the motor in the DELTA configuration.
b. FTA1350 - Contactors 1M and 1S connect the motor in the WYE configuration. The motor may not reach full
speed until the MOTOR ACCELERATION timer has timed out, energizing 2S and connecting the resistor bank,
then energizing 2M and connecting the motor in the DELTA configuration. 2S contacts deenergize contactor 1S.
CAUTION: A minimum run timer setting of less than 3 minutes can cause overheating of the resistors in FTA1350 and
FTA1500 controllers. The resultant overheating may damage the controller.
FTA1500 PRIMARY RESISTANCE CONTROLLERS 1
1. Follow all of the initial start-up instructions.
2. MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary. (See section
2, Mark II Programming for details).
CAUTION: DO NOT EXCEED FOUR (4) SECONDS MAXIMUM.
3. Contactor 1S connects the motor in series with the resistor bank. The motor may not reach full speed until the MOTOR ACCELERATION timer has timed out and contactor 1M is energized.
FTA1800 AUTOTRANSFORMER CONTROLLERS
1. Follow all of the initial start-up instructions.
2. MOTOR ACCELERATION timer is factory set for 2 seconds and may be field adjusted if necessary. (See section
2, Mark II Programming for details).
CAUTION: DO NOT EXCEED THIS TIMER SETTING WITHOUT CONSULTING YOUR FIRETROL REPRESENTATIVE.
3. Contactor 1S and 2S close and connect the motor to the factory set 65% tap on the autotransformer during the
starting cycle. The motor may not reach full speed until the MOTOR ACCELERATION timer has timed out, deenergizing contactor 1S and energizing contactor 1M, connecting the motor to full line voltage.
FTA1900 SOLID STATE STARTING CONTROLLERS
1. Follow the initial start-up instructions.
2. Motor will start at reduced voltage on soft start contactor 1MS.
3. When soft start contactor 1MS reaches full voltage, contactor 1M closes, bypassing 1MS.
1 CAUTION: Acceptance testing of each controller shall be for a minimum of six (6) automatic and six (6) manual
starts at a minimum run time of five (5) minutes per NFPA 20 to insure resistor cooling between starts. Motor
manufacturers data must be consulted for maximum number of starts per hour and other starting conditions.
ADDITIONAL FTA1900 INSTRUCTIONS
SOFT START OPERATION
The solid state soft starter is designed to start a standard NEMA B motor at reduced voltage. The device features
a pause/sincerity test sequence to minimize hydraulic disturbances in the piping system during a soft stop. This allows
an orderly restart should there be a call-to-run during the sincerity test period.
The device is factory calibrated and should not require extensive field adjustment.
Printed circuit board mounted LEDs provide the following indication when on:
Phase Correct
+15 VDC Available
Gating SCRs
Starter On
Full Voltage
Three DIP switches provide for control of acceleration ramp time, acceleration level (jump to full voltage at pre-set
point during ramp up), deceleration ramp time, deceleration level (jump from full voltage to a pre-set lower level during
ramp down), pause test duration and pause test level.
The DIP switches are set as follows:
ACCELERATION
SW1-1 and SW1-2 set the time from reception of a run command until full voltage output of the starter. This is accomplished by setting the rate of the output voltage ramp which has a range from 0 Volts to 100% line voltage.
SW1-1 OFF; SW1-2 OFF
Accel time = 2.5 Seconds
SW1-1 ON; SW1-2 OFF Accel time = 3.5 Seconds
*SW1-1 OFF; SW1-2 ON Accel time = 5.0 Seconds
SECTION 2
Mark II Set Up
Set Up Notes:
These instructions often refer to pressing the right arrow key; earlier versions of the Mark II interface panel
had an ACK key instead. Pressing the ACK key will have the same results as the
key when following
these instructions.
User Passwords:
Adjusting the settings of the Mark II can severely effect the operation of the fire pump controller. Any adjustments
should be done by qualified personnel. This manual will refer to an operator level password and an supervisor
level password. The operator level password allows changes that might normally be made by maintenance
personnel. The supervisor password allows changes that may more seriously affect the operation of the fire
pump controller. A supervisor level password might be required by well-trained maintenance personnel, pump
distributors or manufacturers representatives.
The operator level password is shown below. This password is also on a label affixed to the back of the Mark
II on the inside of the controller door. Although this password may be changed, it is not recommended. Cost to
the owner may be incurred if the factory password is changed, then forgotten.
When prompted for the Operator Level password enter the following key sequence:
METER-MENU-METER-MENU-PRINT-ENTER
The Supervisor Level password will be supplied as necessary or will already be known by the person performing the changes to the controller.
Interlock Jumper
NOTICE: The controller is shipped with an interlock jumper in place to prevent motor
starting during the setup procedure. The Mark II display will have the INTERLOCK ON
LED turned on and the ALARM LED will blink. This will not interfere with the setup
procedure. This interlock jumper must be removed for the controller to operate automatically. Remove the jumper wire connected between field terminals #1 and #10
when setup is complete.
MENU
EVENT
LOG
MENU
3000 EVENTS
ALARM
LIMITS
UNDER VOLTAGE
OVER VOLTAGE
VOLTAGE IMBALANCE
FREQUENCY
MOTOR OVERLOAD
REVERSE PHASES
CLOCK
SET
SET DATE/TIME
DAYLIGHT SAVINGS TIME
DIAGNOSTICS
SOFTWARE VERSION
LAMP TEST
120VAC INPUTS 1-16
120VAC INPUTS 17-24
120VAC OUTPUTS
KEYPAD TEST
SERIAL LOOPBACK TEST
FLASH MEMORY TEST
USB LOOPBACK TEST
USB DRIVE TEST
-DETAILSEE FIGURE F
PAGE 20
-DETAILSEE FIGURE B
PAGE 16
MENU
HOME
DATA
LOG
-DETAILSEE FIGURE C
PAGE 17
CALLS/STARTS
TOTAL MOTOR RUN TIME
LAST MOTOR RUN TIME
LAST MOTOR START
MAXIMUM RUN CURRENTS
LAST PHASE FAILURE
LAST PHASE REVERSAL
LAST LOCKED ROTOR TRIP
LAST LOCKED ROTOR TRIP CURRENTS
MINIMUM VOLTAGES
MAXIMUM VOLTAGES
TOTAL UNIT RUN TIME
MIN/MAX FREQUENCY
MIN/MAX PRESSURE
MENU
-DETAILSEE FIGURE G
PAGE 21
MENU
-DETAILSEE FIGURE H
PAGE 22
MENU
PRESSURE
SETTINGS
-DETAILSEE FIGURE D
PAGE 18
MENU
-DETAILSEE FIGURE E
PAGE 19
TIMERS
STOP PRESSURE
START PRESSURE
PRESSURE EVENT RECORDING
MANUAL STOP ONLY
PRESSURE UNITS
LOW SUCTION/LEVEL
ZERO CALIBRATION
SPAN CALIBRATION
MENU
-DETAILSEE FIGURE I
PAGE 23
ON-DELAY
MINIMUM RUN
OFF DELAY
ACCELERATION/BYPASS
WEEKLY TEST
SYSTEM
SETUP
MODEL CONFIGURATION
OPTION CONFIGURATION
SYSTEM LANGUAGE
SYSTEM VOLTAGE
SYSTEM FREQUENCY
MOTOR FLA
CT RATIO
SERIAL NUMBER
FLASH DRIVE AUTOSAVE
SINGLE PHASE
CLEAR EVENT LOG
CLEAR DATA LOG
CHANGE PASSWORDS
NOTE:
THE MENU STRUCTURE SHOWN HERE AND THE
CORRESPONDING DETAIL FIGURE DRAWINGS ARE SUPPLIED
AS A VISUAL REFERENCE ONLY. FOR DETAILED
PROGRAMMING INSTRUCTIONS PLEASE REFER TO THE
PROGRAMMING SECTION OF THIS MANUAL.
THIS MANUAL COVERS MANY MODELS OF CONTROLLERS,
THEREFORE SOME MENU ITEMS SHOWN MAY NOT BE
AVAILBLE FOR ALL CONTROLLER TYPES.
14 9
METER
The controller provides simultaneous 3 phase metering in True RMS. When the METER button is pushed, the display
will show existing volts and amps for all three phases. Use the key to scroll to the next set of values, which is the
current frequency (hertz) and the phase rotation. Pressing the key again will display the Minimum MTR (motor) Start
Volts for each phase. The values shown are for the last start or current start if motor is running. Pressing the key
again will display the Maximum MTR (motor) Start Amps for each phase. The values shown are for the last start or current start if motor is running. You may use the key to scroll back through the various values. Press HOME to return
to the main screen.
EVENT LOG
The controller keeps an internal log of all events. This memory log stores the last 3000 events in chronological order.
To view the event log, press MENU. The display will show Event Log. Press ENTER. The most recent event will be
shown with a time/date stamp. To view the previous event, press the key. The and keys can be used to scroll
forward and backward through the events. To search more rapidly through the events, such as looking for a specific
date, press the ENTER key while viewing any event. The event will appear on the top line of the display. The event
number and search multiplier {X1, X10, X100} will appear on the bottom line of the display. To change the search multiplier, press the key. The search multiplier determines how many events are skipped when the and keys are used.
Press ENTER to return to the event screen with time/date stamp or you can scroll through the events from the current
screen. Press HOME to return to the main screen when finished viewing events.
DATA LOG
The controller keeps an internal log of historical data. This log consists of the following data:
No. of calls to start / No. of actual starts
Total Motor Run Time (Hrs:Min:Sec)
Last Motor Run Time (Min:Sec)
Last Motor Start (Time and Date)
Maximum Run Currents (3 Phase - Amps)
Last Phase Failure (Time and Date)
Last Phase Reversal (Time and Date)
Last LR (Locked Rotor) Trip (Time and Date)
Last LR (Locked Rotor) Trip Currents (3 Phase - Amps)
Minimum Voltages (3 Phase)
Maximum Voltages (3 Phase)
Total Unit Run Time (Power On Time - Hrs:Min)
Min/Max Frequency (Hertz)
Min/Max Pressure
To view the data log, press MENU until Data Log appears on the screen. Use the and keys to scroll through the
data log information. Press HOME to return to the main screen when finished viewing the data log.
10
11
CLOCK SET
Press MENU button until Clock Set appears on the display. Press the ENTER key to change the settings. Enter
the operator password. The time and date will appear with a flashing cursor over the hour (hour is in 24 hour format).
Use the and keys to set the current hour. Use the key to move the cursor to the minute setting. Use the
and
keys to set the current minute. Use the key to move the cursor to the month setting. Use the and keys to set
the current month. Use the key to move the cursor to the date setting. Use the and keys to set the current date.
Use the key to move the cursor to the year setting. Use the and keys to set the current year. When settings are
satisfactory, press ENTER to return to the main screen.
12
Product Description
Full Voltage Starting Electric
Fire Pump Controllers
FTA1000
Breaker mechanism
POWER ON LED
PUMP RUN LED
PHASE FAILURE LED
PHASE REVERSAL LED
LOW PRESSURE LED
DELUGE OPEN LED
INTERLOCK ON LED
TRANSFER SWITCH NORMAL LED (If unit
ordered with Automatic Power Transfer Switch)
TRANSFER SWITCH EMERGENCY LED (If unit
ordered with Automatic Power Transfer Switch)
EMERGENCY ISOLATING SWITCH OFF LED
(If unit ordered with Automatic Power Transfer
Switch)
Minimum Run Timer / Off Delay Timer
Daylight Savings Time Option
Weekly Test Timer
Elapsed Time Meter
Digital Pressure Display
USB Host Controller and Port
Solid State Pressure Transducer
Data Log
Event Log (3000 Events)
True RMS Metering with simultaneous 3 phase
display of amps and volts
Disk Error message
Disk Near Full message
Pressure Error message
Motor Over 320% message
Local Start message
Remote Start message
Emergency Start message
Fail To Start message
Undervoltage message
Overvoltage message
High Speed Open Serial Communications Port
NEMA Type 2 enclosure
Suitable for use as Service Equipment
-AZ
SPECIAL ENCLOSURES
-T
NEMA Type 3R (IEC IP14), Painted Steel
-E
NEMA Type 4 (IEC IP56), Painted Steel
-F
NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Unfinished**
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Painted Finish
-FD
NEMA Type 4X (IEC IP56), #316 Stainless Steel,
Unfinished**
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel
Painted Finish
-G
NEMA Type 12 (IEC IP52), Painted Steel
** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N
Intermediate withstand rating
150,000 Amps RMS Sym.
-P
High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be
available for all horsepowers and voltages. Consult factory for
availability.
ANTI-CONDENSATION SPACE HEATERS
-H
120 Volt Space Heater
-J
120 Volt Space Heater With Thermostat
-K
120 Volt Space Heater With Humidistat
-L
240 Volt Space Heater
-M
240 Volt Space Heater With Thermostat
-N
240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B
0-600 psi (0-42.25 bar) Pressure Transducer for
Fresh Water Service
-C
0-300 psi (0-21.1 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
-D
0-600 psi (0-42.25 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
AUTOMATIC POWER TRANSFER SWITCHES
FTA900 - generator set emergency supply
FTA950 - second utility emergency supply
(Refer to publication SD900-20)
FTA901 - bypass isolation switch for generator set emergency
supply
FTA951 - bypass isolation switch for second utility emergency
supply
(Refer to publication SD901-20)
ALARMS
-AC
Extra contacts (normally open & normally closed) for
remote indication, pump operating
-AF
Audible and Visible low pump room temperature alarm
-AG
Built-in reservoir low alarm
-AH
Audible low suction pressure alarm
-AM
Contacts for remote indication, pump fail to start
-AV
Contacts for remote indication, low pump room
temperature
-AW
Contacts for remote indication, reservoir low
-AY
Contacts for remote indication, low suction pressure
ASCO 2006
FTA10001900
Modifications
See Back
Start/Stop Options
A - Automatic start with timed permissive stop
after minimum run time and manual start
with manual stop, field convertible to automatic start and manual start with manual
stop only
B - Automatic start and manual start with
manual stop
C - Manual start and stop
Horsepower Rating
03 - 3 HP
05 - 5 HP
07 - 7 1/2 HP
10 - 10 HP
15 - 15 HP
20 - 20 HP
25 - 25 HP
30 - 30 HP
40 - 40 HP
50 - 50 HP
60 - 60 HP
75 - 75 HP
100 - 100 HP
125 - 125 HP
150 - 150 HP
200 - 200 HP
250 - 250 HP
300 - 300 HP
350 - 350 HP
400 - 400 HP
450 - 450 HP
500 - 500 HP
600 - 600 HP
700 - 700 HP
-BW
SPECIAL ENCLOSURES
-T
NEMA Type 3R (IEC IP14), Painted Steel
-E
NEMA Type 4 (IEC IP56), Painted Steel
-F
NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Unfinished**
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Painted Finish
-FD
NEMA Type 4X (IEC IP56), #316 Stainless Steel,
Unfinished**
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel
Painted Finish
-G
NEMA Type 12 (IEC IP52), Painted Steel
** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N
Intermediate withstand rating
150,000 Amps RMS Sym.
-P
High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be
available for all horsepowers and voltages. Consult factory for
availability.
ANTI-CONDENSATION SPACE HEATERS
-H
120 Volt Space Heater
-J
120 Volt Space Heater With Thermostat
-K
120 Volt Space Heater With Humidistat
-L
240 Volt Space Heater
-M
240 Volt Space Heater With Thermostat
-N
240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B
0-600 psi (0-42.25 bar) Pressure Transducer for
Fresh Water Service
-C
0-300 psi (0-21.1 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
-D
0-600 psi (0-42.25 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
AUTOMATIC POWER TRANSFER SWITCHES
FTA900 - generator set emergency supply
FTA950 - second utility emergency supply
(Refer to publication SD900-20)
FTA901 - bypass isolation switch for generator set emergency
supply
FTA951 - bypass isolation switch for second utility emergency
supply
(Refer to publication SD901-20)
ALARMS
-AC
Extra contacts (normally open & normally closed) for
remote indication, pump operating
-AF
Audible and Visible low pump room temperature alarm
-AG
Built-in reservoir low alarm
-AH
Audible low suction pressure alarm
-AM
Contacts for remote indication, pump fail to start
-AV
Contacts for remote indication, low pump room
temperature
-AW
Contacts for remote indication, reservoir low
-AY
Contacts for remote indication, low suction pressure
-AZ
Low pump room temperature switch, mounted and
wired
ASCO 2006
Specifications
Electric Fire Pump Controllers
FTA1000
-1900
Data Logging
The digital display shall monitor the system and
log the following data:
Motor Calls/Starts
Elapsed Motor Run Time
Last Trip Currents
Elapsed Power On Time
Last Breaker Trip
Maximum Run Currents
Minimum Voltages Minimum Run Currents
Maximum Voltages Last Motor Run Time
Last Phase Failure Last Start Currents
Last Phase Reversal Min/Max Frequency
Min/Max Pressure
Operation
A digitally set On Delay (Sequential Start) timer
shall be provided as standard. Upon a call to start, the
user interface shall display a message indicating the
remaining time value of the On Delay timer.
The controller shall be field programmable for
manual stop automatic stop. If set for automatic stopping, the controller shall allow the user to select either
a Minimum Run Timer or an Off Delay Timer. Both
timers shall be programmable through the user interface.
Event Recording
Memory - The controller shall record all operational
and alarm events to system memory. All events shall
be time and date stamped and include an index number. The system memory shall have the capability of
storing 3000 events and allow the user access to the
event log via the user interface. The user shall have
the ability to scroll through the stored messages in
groups of 1, 10, or 100.
USB Host Controller - The controller shall have a
built-in USB Host Controller. A USB port capable of
accepting a USB Flash Memory Disk (aka: flash drive,
thumb drive, memory stick, etc..) shall be provided.
The controller shall save all operational and alarm events
to the flash memory on a daily basis. Each saved
event shall be time and date stamped. The total amount
of historical data saved shall solely depend on the size
of the flash disk utilized. The controller shall have the
capability to save settings and values to the flash disk
via the user interface.
Serial Communications - The controller shall feature a RS485 serial communications port for use with
2 or 4 wire Modbus RTU communications.
Solid State Pressure Transducer
The controller shall be supplied with a solid state
pressure transducer with a range of 0-300 psi (0-20.7
bar) 1 psi. The solid state pressure switch shall be
used for both display of the system pressure and control of the fire pump controller. Systems using analog
pressure devices or mercury switches for operational
control will not be accepted.
XXXGJSFUSPMDPN4BMFT0GGJDF$BSZ
/$64"
SP1000-20 (05-03-07)
$6&2
Sequence of Operation
Full Voltage Fire Pump Controllers
Introduction
The following information is in reference to Wiring
Schematic, Publication WS1000-50.
Note: Firetrol schematics are drawn showing the
equipment in a de-energized state.
Energizing The Controller
1. Close the isolating switch/circuit breaker by moving
the handle to the ON position.
Note: The unmarked, red, Interlock jumper wire, located
between terminals #1 & #10 on the Relay PC board,
(TB1), will prevent the MarkII unit from starting the electric
motor automatically. This jumper wire should only be
removed after the pressure settings have been input,
and the system pressurized at, or above the Stop set
point.
2. The factory programmed MarkII unit will begin
initialization. Upon completion, the display will confirm
system pressure, the time, date, and Interlock ON,
which is an alarm condition and will cause the yellow
alarm LED to flash. Any other existing alarm conditions
(low system pressure, phase reversal, phase failure,
deluge open), will also be sequentially and continuously
displayed at this time, until each is rectified.
3. With the interlock jumper wire still in place, the
electric motor can only be started by depressing the
START push-button, located on the flange of the controller
enclosure, or by engaging the Emergency Run
Mechanism. After all alarm conditions have been
rectified, and the system pressurized at or above the
Stop pressure setting, then the interlock jumper may
be removed for the controllers automatic operation
(standby). With the interlock jumper removed, a drop
in system pressure to the MarkIIs set Start point, will
start the electric motor.
4. The deluge valve contacts are only operational if the
factory jumper has been removed and a normally closed
deluge valve contact has been placed between terminals
1 and 8 of the Relay PC board, (TB1). The Remote Start
is only operational if a normally open, momentarily closed
contact is wired to terminals 6 and 7 of the Relay PC
board, (TB1). If engaged, the Emergency Run
Mechanism will cause the pump motor to run as
described in the Emergency Starting and Stopping
section.
Automatic Start and Stop
1). The controllers pressure transducer initiates the
automatic start circuits for the pump motor. When
pressure falls at, or below the MarkII Start setting, relay
FTA1000
XXXGJSFUSPMDPN4BMFT0GGJDF$BSZ
/$64"
SQ1000-20 (04-12-07)
$6&2
FTA1300
Wye-Delta, Open Transition Starting
Electric Fire Pump Controllers
Product Description
DescriptionFiretrol FTA1300 Wye-Delta, Open Transition Starting Fire Pump Controllers are used with deltawound squirrel cage motors. FTA1300 controllers are
of the open circuit transition type in which the motor
circuit is opened during the transition from start to run.
The controller monitors, displays and records fire pump
system information.
Actuating the controller by the pressure switch, START
pushbutton or deluge valve contact closes the start
contactor connecting the motor to the line in the wye
connection. The motor will draw approximately 33% of
its normal inrush current and develop approximately
33% of its normal starting torque. After a time delay, the
motor is automatically reconnected in delta, applying
full voltage to the motor windings. These controllers are
recommended especially for use with generator sets.
Approvals Firetrol fire pump controllers are listed by
Underwriters Laboratories, Inc., in accordance with
UL218, Standard for Fire Pump Controllers, CSA, Standard
for Industrial Control Equipment, and approved by Factory
Mutual. They are built to meet or exceed the requirements of the approving authorities as well as NEMA and
the latest editions of NFPA 20, Installation of Centrifugal
Fire Pumps, and NFPA 70, National Electrical Code.
Standard FeaturesThe following are included as standard with each controller:
Voltage surge protector
Main Disconnect Switch sized for connected motor
horsepower and voltage
Fire pump Circuit Breaker
Single handle Isolating Disconnect Switch/Circuit
Breaker mechanism
Motor contactor
Emergency Manual Run Mechanism to mechanically
close motor contactor contacts in an emergency condition
Built-in Start and Stop push-buttons to bypass automatic start circuits
Minimum Run Timer / Off Delay Timer
SPECIAL ENCLOSURES
-T
NEMA Type 3R (IEC IP14), Painted Steel
-E
NEMA Type 4 (IEC IP56), Painted Steel
-F
NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Unfinished**
-FXP
NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Painted Finish
-FD
NEMA Type 4X (IEC IP56), #316 Stainless Steel,
Unfinished**
-FDB
NEMA Type 4X (IEC IP56), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP
NEMA Type 4X (IEC IP56), #316 Stainless Steel
Painted Finish
-G
NEMA Type 12 (IEC IP52), Painted Steel
** Unfinished (Not painted, polished or brushed).
CIRCUIT BREAKER OPTION
-N
Intermediate withstand rating
150,000 Amps RMS Sym.
-P
High withstand rating
200,000 Amps RMS Sym
Note: Intermediate and High withstand ratings may not be
available for all horsepowers and voltages. Consult factory for availability.
ANTI-CONDENSATION SPACE HEATERS
-H
120 Volt Space Heater
-J
120 Volt Space Heater With Thermostat
-K
120 Volt Space Heater With Humidistat
-L
240 Volt Space Heater
-M
240 Volt Space Heater With Thermostat
-N
240 Volt Space Heater With Humidistat
PRESSURE TRANSDUCERS
-B
0-600 psi (0-42.25 bar) Pressure Transducer for
Fresh Water Service
-C
0-300 psi (0-21.1 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
-D
0-600 psi (0-42.25 bar) Pressure Transducer for Sea
Water, Foam or Copper Corrosive Service
COMBINED AUTOMATIC POWER TRANSFER SWITCHES
FTA950 - Generator/Utility emergency source
FTA951 - Bypass Isolation for Generator/Utility emergency source
ALARMS
-AC
Extra contacts (normally open & normally closed) for
remote indication, pump operating
-AF
Audible and Visible low pump room temperature alarm
-AG
Built-in reservoir low alarm
-AH
Audible low suction pressure alarm
-AM
Contacts for remote indication, pump fail to start
-AV
Contacts for remote indication, low pump room
temperature
-AW
Contacts for remote indication, reservoir low
-AY
Contacts for remote indication, low suction pressure
-AZ
Low pump room temperature switch, mounted and wired
-BW
Extra contacts for remote indication,
phase failure/phase reversal
-BY
Contacts for remote indication, pump overload
-COM Low suction pressure alarm, (Includes selectable
-CTS
-EG
-EH
-EJ
-EK
-KH
-JR
-JT
-P
-PB
-PE
-PT
MISCELLANEOUS
-ED
Load shed circuits
-EL
Series pumping, high zone controller
-EM
Series pumping, mid zone controller(s)
-EN
Series pumping, low zone controller
-FZX
400 VAC Operation (Controller labeled for operation at
380-400 VAC - Use with voltage code FZ)
-PY
Motor space heater output contacts
-S
Tropicalization
-SEI
Seismic Certification (in accordance with IBC)
-ZPA
Customized, annual service display message
(when factory programmed or programmed by
Firetrol representative during start-up)
-ZPN 5150 Ethernet Connectivity Module (Allows users
to monitor limited controller status via a single
computer or over a computer network)
-ZPM Serial Modbus RTU Communications Protocol
(Allows users to monitor all aspects of the
controller status via a RS485 communications
network (system integration required). (Includes
RS485 to twisted pair breakout module, optical
isolation module (4000 ft. range), DC power
supply and customer connection terminal blocks).
Export packaging (Wooden crating to conform
to IPPC Standards)
FTA1000 - 1930
PD1300-50 (A)
EmersonNetworkPower.com
Racks & Integrated Cabinets
AC Power
Embedded Computing
Outside Plant
Connectivity
Embedded Power
Services
DC Power
Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2010 Emerson Electric Co.
'iretrol Brand Products Cary
North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA1100-J
DIESEL ENGINE FIRE PUMP
CONTROLLERS
STANDARD SUBMITTAL PACKAGE
SBP1100J
FTA1100
Diesel Engine Fire Pump Controllers
Product Description
FTA1100
Diesel Engine Fire Pump Controllers
Specifications
Data Logging
The digital display shall monitor the system and log the
following data:
Motor Calls/Starts
Pump Total Run Time
Last Pump Run time
Controller Power On Time
Last Pump Start
Minimum System Pressure
Maximum System Pressure
Last High Temp.
Last Low Oil Pressure
Last Engine Overspeed
Last Low Fuel Level
Last Charger Fail
Last Battery Trouble
Last Overspeed
Battery #1 Volts (Min., Now, Max.)
Battery #2 Volts (Min., Now, Max.)
Battery #1 Amps (Min., Now, Max.)
Battery #2 Amps (Min., Now, Max.)
Event Recording
Memory - The controller shall record all operational and alarm
events to system memory. All events shall be time and date
stamped and include an index number. The system memory
shall have the capability of storing 3000 events and allow the
user access to the event log via the user interface. The user
shall have the ability to scroll through the stored messages in
groups of 1, 10.
USB Host Controller
The controller shall have a built-in USB Host Controller. A
USB port capable of accepting a USB Flash Memory Disk shall
be provided. The controller shall save all operational and alarm
events to the flash memory on a daily basis. Each saved event
shall be time and date stamped. The total amount of historical data saved shall solely depend on the size of the flash disk
utilized. The controller shall have the capability to save settings
and values to the flash disk on demand via the user interface.
Seismic Certification
The controller shall be certified to meet or exceed the
requirements of the 2006 International Building Code and
the 2007 California Building Code for Importance Factor 1.5
Electrical Equipment for Sds equal to 1.88 or less severe seismic
regions. Qualifications shall be based upon successful tri-axial
shake-table testing in accordance with ICC-ES AC-156. Certification without testing shall be unacceptable. Controller shall
be clearly labeled as rated for installation in seismic areas and a
Certificate of Conformance as well as a Center of Gravity drawing
shall be provided with the controller.
Battery Chargers
The controller shall include two fully automatic, 200 amp
hour, 4 step battery chargers. The chargers shall feature a
qualification stage, in which the batteries are examined by the
charger to insure that they are not defective and are capable of
accepting a charge. The battery charger shall feature:
Selectable AC Power Voltage
Selectable Battery Voltage
Selectable Battery Type
Charge Cycle Reset Push-button
The controller shall be a Firetrol brand.
SP1100-50
EmersonNetworkPower.com
Racks & Integrated Cabinets
AC Power
Embedded Computing
Outside Plant
Connectivity
Embedded Power
Services
DC Power
Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. 2010 Emerson Electric Co.
'iretrol Brand Products Cary
North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
A B
E F GH I
C D
TO PAGE 2
WIRING SCHEMATIC
229677
FTA1100-J
WS1100-20
TEF 11-04-02
229677
FROM PAGE 1
A B
E FGHI
C D
WIRING SCHEMATIC
229677
FTA1100-J
WS1100-20
TEF 11-04-02
229677
V
ZONE
NOTES:
BY
4
101.6
O1 / 25.4 HOLE
WITH LEGS
2
2) PITCH TANK TOWARD DRAIN 1/4"/ 6.3mm PER FOOT
3) ADJUST FOUNDATION TO MAINTAIN CL FUEL INLET WITH
10' MIN.
254
C
L ENGINE FUEL PUMP
4) DRAWING IN CONFORMANCE WITH NFPA PAMPHLET
O 1/2
12.0
10 11 13 18
1 5/8
40.0
2
3
76.2
1 1/2
38.1
2 3/4
70.0
9
ENGINE
A) DEUTZ
B) CLARKE
C) CUMMINS
D) CATERPILLAR
RETURN
1/2" / 12.7
1/2" / 12.7
1/2" / 12.7
1/2" / 12.7
DELIVERY
1/2" / 12.7
1/2" / 12.7
1/2" / 12.7
1/2" / 12.7
1 1/2
38.1
5
127.0
12
DETAIL "A"
SCALE: 1:2
5
FUEL RETURN
TOP OF
TANK
10 14
10
20 19
X
DATE
WITHOUT LEGS
W
ECR
REV
72" MAX.
1828.8
FUEL SUPPLY
DETAIL "B"
SCALE: NONE
21
12
6
ALL PRIMARY DIMENSIONS ARE INCHES.
ALL SECONDARY DIMENSIONS ARE METRIC.
6
153.2
6
152.4
6
152.4
6
152.4
6
152.4
12
304.8
22
4
1
2
6
152.4
8
SEE DETAIL "B"
22
21
20
PIPE COUPLING
19
18
CHECK VALVE
17
LOCK-OPEN VALVE
16
LONG NIPPLE
9
1/4
O 27
692.2
61
1547.8
16 17
11
12
15
3
77.0
15
14
13
12
11
10
35 3/8
898.9
15
EARTHING LUG
24 3/4
628.2
11
24 1/4
616.0
-NOT PROVIDED
12 1/2
318.5
-NOT PROVIDED
14 1/4
362.7
25
634.8
19 1/4
489.7
52
1320.8
13
(OPTIONAL)
14
REV.
DWG. NO.
DESCRIPTION
9 5/8
244.9
12
ITEM QTY.
10
3
77.4
13
14
SUMP AREA 5%
OF TOTAL VOLUME
10
D02-114277
DRAWN
DATE
mcaudell
SCALE
NONE
AP
15
6X6
8X8
C
D
14
AUG. 7, 2009
DATE
BY
150#
DWG. NO.
U
L
REV.
MC
15
X
3
10
11
W/ 300# FLANGES
MODEL: 2050B-4KG-1
12
13
NONE
14
APPRVD.
AP
15
mcaudell
SCALE
DATE
1
DRAWN
C02-99668
300#
27956
13
ECR
12
REV
DISCHARGE
PRESSURE
GAUGE
7000
3100
ZONE
FM
11
4000
1800
10
1800
800
73460039
300 / 150
PILOT CONTROL
PIPING
FLANGES
1000
MAXIMUM SURGE
FLOW RATE GPM (WATER)
PILOT
460
MAXIMUM CONTINUOUS
FLOW RATE GPM (WATER)
23
584.2
500 LBS
227 KGS
16 5/16 13 1/4
414.2 336.5
8 1/2
216
73460044
PART No.
73460041
QTY.
285 LBS
130 KGS
WEIGHT CHECK
LBS / KGS
BOX
70 LBS
32 KGS
73460043
14 1/8
358.7
141 LBS
64 KGS
6 3/8
162
7 7/8 15 3/4
13
5 5/16
200
134.8 330.2
400
6 1/2 14 5/16 10 1/2
19
165.1
363.4 266.7 482.6
4X4
12 1/2
317.5
4 3/8
111.1
3X3
A
B
VALVE SIZE
(INCHES)
ITEM