Escolar Documentos
Profissional Documentos
Cultura Documentos
Thorsten Punke
Global Program Manager Building Networks
Program Manager Data Center EMEA
Introduction
With the introduction of new services and the increased number of electrically powered
devices, the topic of EMC and installation has become very important. 1 and 10 Gigabit
Ethernet have made this part of everyday practice, and it is also very significant in the
planning of IT networks.
For planners and operators the key sources of information on this are EN 50174-2 and the
global version, ISO/IEC 14763-2.
These standards ensure that installation and the environment are considered alongside the
pure performance of cable lengths. This is more important for sensitive channels such as 1
and 10 Gigabit than for others such as 100 Mbit/s.
One paper that will be especially significant in the future is ISO/IEC 29106, which defines the
MICE classes.
EMC requirements are defined for each class. E1 and E3 are typical office and industrial
environments.
Here it is important to recognize that the environment must be considered as well as the
actual IT system performance. For this reason various test series and conditions have been
defined for electrotechnology.
Radiation
Immunity
With symmetrical data cables there are two ways in which both types can be controlled:
Twisting
Shielding
The effect of both mechanisms is summarized in the coupling attenuation parameter. This
comprises the effects of twisting and shielding for STP and twisting for UTP systems.
Twisting
Shielding
STP
X
X
UTP
X
Electromagnetic
Electrostatic discharge contact
(0,667 C)
Electrostatic discharge air
(0,132 C)
Radiated RF - AM
E1
E2
E3
4 kV
4 kV
4 kV
8 kV
8 kV
8 kV
EFT/B (communication)
500 V
1000 V
2000 V
Surge voltage
(transient potential
difference)
communication and
supply conductor to
earth
Magnetic field (50/60 Hz)
500 V
1000 V
2000 V
1 Am-1
3 Am-1
30 Am-1
Under discussion
Under discussion
Under discussion
Conducted RF
These conditions simulate typical everyday EMC regarding the systems immunity to
possible causes of disturbance. MICE defines an environment, in this case an
electromagnetic environment. Each definition simulates how a typical source of disturbance
would occur in practice.
.-.-.-.-.-.Electromagnetic
Sources
Implication
Floor covering
Floor covering
Conducted RF
EFT/B (Communication)
Surge voltage (transient potential
difference)
communication and
supply conductor to earth
Magnetic field (50/60 Hz)
In practice no system works alone. In many cases the cause of problems can be deduced
from this interaction. This includes switching procedures for cables, radio, harmonic waves,
etc.
To specify the environment it is necessary to analyze and classify the existing environment.
This table will help in making a first approximate estimate.
Interference source
E classification
< 3 km
E3
3 km
E1 or E2
Fluorescent lamps
< 0.15 m
E3
0.15 m
E1 or E2
< 0.5 m
E3
0.5 m
E1 or E2
<3m
E3
3m
E1 or E2
< 0.5 m
E3
0.5 m
E1 or E2
Electrical motors
Mobile phones
The distances mentioned here are valid for all currently defined services, which are defined
in cabling standards IS 11801 edition 2.1 and EN 50173-x, as well as current services such
as 1 & 10 Gigabit Ethernet.
Important: the recently introduced cabling standards make it obligatory to consider MICE in
the planning and operating phases. A cabling system must function without any faults in the
environment for which it was specified. E1 is the least demanding class.
First the separation class is determined by the cable type. So for example for PiMF cables
this would be Class d, and for U/UTP cables class a or b. The general parameter for both
cable types is coupling attenuation. The assignment of TCL for UTP cables in the norm is
due to North American influences.
IT Cables
Separation
class
Shielded
Unshielded
Coaxial/Twin axial
Shielding attenuation at
30 MHz to 100 MHz
dB
80 dBa
70-10x lg f
85 dB
55 dB
60-10x lg f
55 dB
40 dB
50-10x lg f
40 dB
< 40 dB
50-10x lg f
< 40 dB
Cables conforming to EN 50288-4-1 (EN 50173-1:2007, Category 7) also comply with separation class d".
Cables conforming to EN 50288-2-1 (EN 50173-1:2007, Category 5) and EN 50288-5-1 (EN 50173-1:2007, Category 6)
also comply with separation class c". These cables can deliver the performance of separation class d", provided that they
keep to the applicable requirements for data link attenuation.
c
Cables conforming to EN 50288-3-1 (EN 50173-1:2007, Category 5) and EN 50288-6-1 (EN 50173-1:2007, Category 6)
also comply with separation class b". These cables can deliver the performance of separation classes c" or d", provided
that they keep to the applicable requirements for earthing symmetry attenuation.
d
Cables conforming to EN 50117-4-1 (EN 50173-1:2007, Category BCT-C), also comply with separation class d".
Separation without
electromagnetic
barriers
Minimum Gap in mm
Open
metallic
containmenta
Perforated
metallic
containment
Solid metallic
containmentd
b,c
d (S/FTP)
10 mm
8 mm
5 mm
0 mm
c (F/UTP)
50 mm
38 mm
25 mm
0 mm
b (U/UTP)
100 mm
75 mm
50 mm
0 mm
a (U/UTP)
300 mm
225 mm
150 mm
0 mm
a Screening performance (0 MHz to 100 MHz) equivalent to welded mesh steel basket of mesh size 50 mm x 100 mm
(excluding ladders). This screening performance is also achieved with steel tray (trunking without cover) of less than
1,0 mm wall thickness and more than 20 % equally distributed perforated area.
Screening performance (0 MHz to 100 MHz) equivalent to steel tray (trunking without cover) of 1,0 mm wall thickness
and no more than 20 % equally distributed perforated area. This screening performance is also achieved with screened
power cables that do not meet the performance defined in Note d.
The upper surface of installed cables shall be at least 10 mm below the top of the barrier.
Screening performance (0 MHz to 100 MHz) equivalent to a steel conduit of 1,5 mm wall thickness. Separation specified
With the help of these tables the required gaps can be calculated very effectively in practice.
At higher voltages or if there is a high number of conductors, then a correction factor can be
used. The gap should be multiplied by this factor.
Electrical circuit typea, b, c
Quantity of circuits
20 A 230 V 1-phase
1 to 3
0.2
4 to 6
0.4
7 to 9
0.6
10 to 12
0.8
13 to 15
1.0
16 to 30
31 to 45
46 to 60
61 to 75
>75
Example:
PiMF cable, 15 active current carrying conductors in the power cable (unshielded) 230V
single phase, plastic cable duct with no separation.
The cable corresponds to Class d, so together with the other conditions, this means the gap
should be 10mm.
For a high voltage unshielded cable Class b should be taken, giving a gap of 100mm. For
simple U/UTP constructions take Class a, giving a 300 mm separation distance.
These are absolute minimum limits. However practical test results show that these gaps are
insufficient. As is the case with many standards, these values should be recognized as the
lowest common denominator.
Seperation in Air
4000
3500
3000
2500
UTP Class D
UTP Class E
Limit
STP Class E
STP Class E
Limit
0
0
UTP Class E
3
6
Length cm
12
UTP Class D
25
50
Test results at Delta Labs separation distance of different cabling systems to power cables
If for example the E1 specification of 500 V was the basis, then a minimum gap of 12cm was
determined. At 1000 V this had already increased to 25cm.
The S/STP system can be installed without a gap right up to 2000 V. During the test the data
rate and signal quality were checked. In the case of U/UTP a fall below minimum values
completely broke off transmission.
In practice usual levels are up to about 2000 V. In order to cover a broad spectrum in
practice, 1000 V is a good basis.
At 1000 V the figures are:
U/UTP = 25 cm distance
S/STP = 0 cm distance
Note: Tests have been conducted while 10 Gigbait Ethernet was operating over the
the cabling channels. The single results for each systems shows where the
application stopped.
10
Summary
Based on the test series of both accredited test laboratories we recommend the following:
For U/UTP cabling a safety distance of at least 30 cm (for 230 V and approx. 15 electrical
circuits) should be maintained. Alternatively all U/UTP cables can be installed in a closed
metal duct.
For S/FTP systems the separation distance can be be 0 mm.
Both test series have shown that switching on and off can seriously disturb data traffic at 1 &
10 Gb/s through U/UTP cables. The only way is screening, which is already contained within
S/FTP cables.
11
The safety distance for U/UTP cables should be higher than those defined in EN 50174-2.
Both independent test series have clearly confirmed this.
Distances from other sources of disturbance
EN 50174-2 indicates the distances to be maintained from several other sources of
disturbance.
Source of disturbance
Fluorescent lamps
Neon lamps
Mercury vapour lamps
High-intensity discharge lamps
Arc welders
Frequency induction heating
Hospital equipment
Radio transmitter
TV transmitter
Radar
Minimum separation
mm
130a
130a
130a
130a
800a
1000a
b
b
b
b
When installing UTP systems it is obligatory to follow safety policy, otherwise interruption of
data traffic will result. In normal STP systems no interruption was found.
Note: Tests have been conducted while 10 Gigbait Ethernet was operating over the the
cabling channels. At 10 Gb/s data transfer was completely broken off within a distance of 0,5
m from U/UTP systems. Up to 3m the effct occur although when the poer cable of the lamp
was not separated. No interference was observed with any shielded systems.
12
Walkietalkies
Mobilecommunicationdevices
(mobilephone,GSMcard)
System01
System02
System03
System04
System05
8
8
8
8
9
9
9
9
9
9
At 10 Gb/s data transfer was completely broken off within a distance of 3m from U/UTP
systems. No interference was observed with any shielded systems.
13
Overview
Coupling
attenuation
MICE
Class E1
Distance
power to
data cable
Up to 25 cm
ANEXT
check
No 1
MICE
Class
E2 and E3
No 2
Mandatory
Distance from
fluorescent
tubes
Min. 3m 3
U/UTP
System
40 dB
FTP System
60 dB
S/FTP
System
80 dB
Yes
Yes
0- 1 cm
Automatic
0 mm
Yes
Yes
0 cm
Automatic
0 mm
For the planner and end user the EMC factor is a practical measure of how good or bad a
systems data transmission performance is in relation to EMV.
The various test series have shown that a high EMC factor 4 leads to operational safety and
low costs. Because simplified installation and operating costs have a significant influence on
total costs, you get considerably more for the same or less money.
A second important point is transmission quality. A good NEXT or return loss is of no benefit
if minor interference is enough to break off data transmission.
If you consider all these points then there is no sensible alternative to an STP solution.
The future formula for complete system compliance to standards is:
14
UTP
Office
Industry
Home cabnling
9/9/-
STP
9
9
9
Data center
All of the above apply to certain buildings and client groups, e.g. in a hospital or airport. In
these cases UTP cabling is not advisable, since it is impossible to assure data transmission.
In these sensitive areas even a short interruption of data traffic cannot be tolerated.
Environment
Hosptial
Airport
Hotels
Station
UTP
9
9/- 5
-
STP
9
9
9
9
Military
http://www.utp-vs-stp.com/web/Microsites/UTP-vs-STP/
15
Latin America
Europe
Asia
Pacific
Kessel-Lo, Belgium
Ph: +32-16-35-2190
Fx: +32-16-35-2188
Cergy-Pontoise, France
Ph: +33-1-3420-2122
Fx: +33-1-3420-2268
Sydney, Australia
Ph: +61-2-9554-2600
Fx: +61-2-9554-2519
16
PDF-02/10
2010 Tyco Electronics Corporation All rights reserved
AMP, AMP NETCONNECT, MPOptimate, Tyco Electronics and TE Logo are trademarks.
http://www.ampnetconnect.eu