Você está na página 1de 129

PV EL SALVADOR

Estudios Sistmicos: Cortocircuitos

Cliente:

SunPower Energy Systems Spain, S.L.


Paseo de la Castellana 86
28046 Madrid
SPAIN

DIgSILENT Ibrica S.L.


Jos Abascal, 44
E-28003 Madrid
Tel.: +34 911273723
http://www.digsilent.es
e-mail: iberica@digsilent.com

Please contact
A. Morales
Tel.: +34 911273723
e-mail: a.morales@digsilent.com

REF: REP-ELSALVADOR-SHC
Version: v001
Date:
31.01.2014
PF Build:
15.0.1

PV EL SALVADOR

Estudios Sistmicos: Cortocircuito

Contenidos
Versiones ................................................................................................................................................. 5
ndice de figuras ..................................................................................................................................... 6
ndice de tablas ...................................................................................................................................... 7
1 Alcance ................................................................................................................................................. 8
2 Descripcin del Proyecto ..................................................................................................................... 9
2.1 Descripcin de la conexin ...................................................................................................................... 9
2.2 Diagrama unilineal funcional ................................................................................................................. 11
2.3 Inversores fotovoltaicos ........................................................................................................................ 14
3 Consideraciones del Estudio .............................................................................................................. 15
3.1 Zonas de Estudio ................................................................................................................................. 15
3.2 Informacin Tcnica del SIC y Herramienta de Simulacin Utilizada .......................................................... 17
3.3 Perodo de aplicacin: Septiembre 2014 ................................................................................................. 17
3.4 Demanda en el SIC .............................................................................................................................. 17
3.5 Ampliaciones consideradas en Zona Norte .............................................................................................. 17
3.6 Escenarios de operacin ....................................................................................................................... 18
3.7 Definicin y aplicacin de fallas ............................................................................................................. 18
3.8 Modelos y Metodologa de clculo .......................................................................................................... 20
3.8.1 Modelos para las nuevas ampliaciones consideradas con fecha Septiembre 2014 .................................. 21
3.8.2 Modelo de inversor nueva planta fotovoltaica El Salvador .................................................................... 21
3.8.3 Mtodo mejorado para ajuste la corriente de cortocircuito en caso de cortocircuitos desequilibrados ...... 21
3.9 Corrientes de cortocircuito .................................................................................................................... 22
3.10 Interruptores Considerados ................................................................................................................. 22
4 Resultados.......................................................................................................................................... 25
4.1 Fallas trifsicas (3F) ............................................................................................................................. 25
4.1.1 Sin el parque fotovoltaico ................................................................................................................. 25
4.1.2 Con el parque fotovoltaico................................................................................................................ 29
4.1.3 Comparacin ................................................................................................................................... 32
4.1.4 Observaciones................................................................................................................................. 35
4.2 Fallas bifsicas (2F) .............................................................................................................................. 36
4.2.1 Sin el parque fotovoltaico ................................................................................................................. 36
4.2.2 Con el parque fotovoltaico................................................................................................................ 38

PV EL SALVADOR

Estudios Sistmicos: Cortocircuito

4.2.3 Comparacin ................................................................................................................................... 41


4.2.4 Observaciones................................................................................................................................. 44
4.3 Fallas bifsicas a tierra (2FT) ................................................................................................................. 45
4.3.1 Sin el parque fotovoltaico ................................................................................................................. 45
4.3.2 Con el parque fotovoltaico................................................................................................................ 47
4.3.3 Comparacin ................................................................................................................................... 50
4.3.4 Observaciones................................................................................................................................. 53
4.4 Fallas monofsicas a tierra (1FT) ........................................................................................................... 54
4.4.1 Sin el parque fotovoltaico ................................................................................................................. 54
4.4.2 Con el parque fotovoltaico................................................................................................................ 57
4.4.3 Comparacin ................................................................................................................................... 60
4.4.1 Observaciones................................................................................................................................. 62
5 Verificacin de la capacidad de los interruptores ............................................................................. 63
5.1 Valores Mximos Obtenidos en las Barras Consideradas ........................................................................... 63
5.1.1 Con la nueva instalacin fotovoltaica ................................................................................................. 63
5.1.2 Sin la nueva instalacin fotovoltaica .................................................................................................. 65
5.2 Resultados de la verificacin de la capacidad de ruptura de los interruptores ............................................. 67
6 Conclusiones ...................................................................................................................................... 71
ANEXO 1: Lista de generadores considerados ..................................................................................... 72
ANEXO 2: Referencias y Documentacin ............................................................................................. 80
ANEXO 3: PROCEDIMIENTO DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE
CORTOCIRCUITO PARA LA VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL
SIC, CDEC-SIC, Septiembre 2009 ....................................................................................................... 110

PV EL SALVADOR

Estudio de Cortocircuito

Versiones
Versin

Fecha

REP-ELSALVADOR-SHC V0

02/12/2013

REP-ELSALVADOR-SHC V1

31/01/2014

PV EL SALVADOR

Comentarios

Estudio de Cortocircuito

ndice de figuras
Figura 1: Placa de caractersticas del transformador de la planta fotovoltaica [ANEXO 1] ........................................... 10
Figura 2: Subestacin 110/23kV ........................................................................................................................... 11
Figura 3: Diagrama unifilar de la planta El Salvador ................................................................................................ 12
Figura 4: Zona de influencia en la red de Atacama ................................................................................................. 16

PV EL SALVADOR

Estudio de Cortocircuito

ndice de tablas
Tabla 1: Leyenda diagrama unilineal funcional ....................................................................................................... 13
Tabla 2: Datos de transformadores de inversor ...................................................................................................... 14
Tabla 3: Ampliaciones Septiembre 2014 ................................................................................................................ 17
Tabla 4: Barras en las que se aplican los cortocircuitos ........................................................................................... 18
Tabla 5: Interruptores considerados en el estudio de capacidad de ruptura .............................................................. 23
Tabla 6: Fallas trifsicas - sin la nueva instalacin .................................................................................................. 25
Tabla 7: Fallas trifsicas - con la nueva instalacin ................................................................................................. 29
Tabla 8: Fallas trifsicas - comparacin ................................................................................................................. 32
Tabla 9: Fallas bifsicas - sin la nueva instalacin ................................................................................................... 36
Tabla 10: Fallas bifsicas - con la nueva instalacin ................................................................................................ 38
Tabla 11: Fallas bifsicas - comparacin ................................................................................................................ 41
Tabla 12: Fallas bifsicas a tierra - sin la nueva instalacin...................................................................................... 45
Tabla 13: Fallas bifsicas a tierra - con la nueva instalacin .................................................................................... 47
Tabla 14: Fallas bifsicas a tierra - comparacin ..................................................................................................... 50
Tabla 15: Fallas monofsicas a tierra - sin la nueva instalacin ................................................................................ 54
Tabla 16: Fallas monofsicas a tierra con la nueva instalacin .............................................................................. 57
Tabla 17: Fallas monofsicas a tierra - comparacin ............................................................................................... 60
Tabla 18: Corrientes mximas obtenidas con la nueva instalacin fotovoltaica conectada ........................................... 63
Tabla 19: Corrientes mximas obtenidas sin la nueva instalacin fotovoltaica conectada ............................................ 65
Tabla 20: Verificacin de la capacidad de ruptura de interruptores considerando la nueva instalacin fotovoltaica ........ 68
Tabla 21: Verificacin de la capacidad de ruptura de interruptores de la nueva instalacin fotovoltaica ....................... 70
Tabla 22: Generadores considerados en el estudio de cortocircuito .......................................................................... 72

PV EL SALVADOR

Estudio de Cortocircuito

1 Alcance
El objetivo principal del presente estudio de cortocircuito es verificar la suficiente capacidad de ruptura de los
interruptores, en todas las nuevas instalaciones y en aquellas existentes en el entorno que pudiesen verse afectadas por
la conexin de la nueva instalacin fotovoltaica PV El Salvador. Los interruptores debern soportar la corriente mxima
de cortocircuito, que se establezca a travs de stos, debido a fallas en cualquiera de las instalaciones del SIC, durante
el tiempo de despeje de la falla.
El estudio incluye el clculo de varios cortocircuitos en la red elctrica Chilena, realizado con los datos de la base de
datos de DIgSILENT PowerFactory de fecha 2013.
Este estudio se ha realizado de acuerdo con el procedimiento DO "Trminos y condiciones del clculo de corrientes de
cortocircuito para la verificacin del dimensionamiento de interruptores en el SIC", publicado en el sitio Web del CDECSIC [1].

PV EL SALVADOR

Estudio de Cortocircuito

2 Descripcin del Proyecto


La planta fotovoltaica "El Salvador" se construir en las proximidades de Diego de Almagro (Chile, Tercera Regin),
promovida por Solventus, Etrion y Total. La fecha estimada de puesta en servicio de la instalacin es Septiembre de
2014.
Esta planta tendr una potencia aproximada de 70.156MWp y 68MWac.
La planta fotovoltaica estar basada en mdulos Sunpower 435, instalados en el sistema Oasis v2.0, un sistema con
seguidor a un eje. Estos mdulos se conectarn en serie para formar cadenas o strings, que posteriormente se pondrn
en paralelo en las cajas de primer nivel o Combiner Boxes; stas se conectarn a los inversores distribuidos por la
planta.
La planta contendr 45 estaciones AC o AC-stations, cada una formada por un inversor Power One ULTRA de 1,560 kVA
y un transformador de 1560kVA. El inversor recoger la potencia generada por el campo fotovoltaico (corriente
continua) y la convertir en potencia en corriente alterna. Cada inversor estar conectado a un transformador de tipo
pad-mounted que eleva la tensin a 23kV. Los transformadores se conectarn entre s mediante lneas subterrneas de
23kV y, finalmente, a celdas de media tensin ubicadas en el Edificio de la Subestacin.
Para evacuar la energa generada por la planta, se construir una subestacin, donde se elevar la tensin a 110kV; la
planta se conectar a la lnea que une las subestaciones de Diego de Almagro (Transelec) y Codelco Salvador (Codelco),
entre los postes N 81 y 82.

2.1 Descripcin de la conexin


La planta fotovoltaica El Salvador se conectar a la lnea L1, lnea de 110kV que une las subestaciones de Diego de
Almagro y Codelco Salvador y forma parte del Sistema de Transmisin Adicional propiedad de Codelco. Las
caractersticas de dicha lnea, conforme a la informacin suministrada por el cliente [ANEXO 1], son las siguientes:

Lnea: Diego de Almagro - Salvador

Tensin: 110kV

Nmero del circuito: 1

Longitud: 48.2 km

Conductor: ACSR Penguin N4 AWG

La conexin de la planta con la lnea L1 se realizar entre los postes N 81 y 82, a 20.25 y 20.49km de Diego de
Almagro, respectivamente.
Para realizar la interconexin se construir una subestacin en la planta, con un nico pao. Dicho pao contendr un
transformador con las siguientes caractersticas [10]:

Potencia nominal: 50/72MVA ONAN/ONAF

Tensin nominal: 110/23kV (OLTC lado HV 1.25%, 1;9;17) Consigna de tensin OLTC lado LV: 1 p.u.

ndice: DYn11

PV EL SALVADOR

Estudio de Cortocircuito

Tensin de cortocircuito = 12.5%

Perdidas en el cobre: 300 kW

Corriente en vaco: 0.2%

Perdidas en vaco: 50kW

Figura 1: Placa de caractersticas del transformador de la planta fotovoltaica [ANEXO 1]

PV EL SALVADOR

10

Estudio de Cortocircuito

Figura 2: Subestacin 110/23kV


La subestacin se conectar a la lnea L1 mediante una lnea de interconexin de 110 kV y 75m de longitud
aproximadamente. Las caractersticas de esta lnea son las siguientes:

Lnea: Interconexin

Tensin: 110kV

Nmero del circuito: 1

Longitud: 75 m

Conductor: AAAC DARIEN

2.2 Diagrama unilineal funcional


El diagrama unilineal de la instalacin se presenta a continuacin.

PV EL SALVADOR

11

Estudio de Cortocircuito

Figura 3: Diagrama unifilar de la planta El Salvador

PV EL SALVADOR

12

Estudio de Cortocircuito

Tabla 1: Leyenda diagrama unilineal funcional

PV EL SALVADOR

13

Estudio de Cortocircuito

2.3 Inversores fotovoltaicos


Los inversores Power-One ULTRA de 1,560 kVA de Power-One tienen las caractersticas tcnicas siguientes [5]:

Tipo: ULTRA-1400.0-TLOUTD-690

Tensin nominal: 690V

Frecuencia nominal: 50Hz

Potencia aparente nominal: 1560 kVA

Potencia activa nominal (Pn): 1560 kW

Corriente nominal: 1300 A

Contribucin a falta: 1.09 p.u.

El modelo de inversor para la plataforma DIgSILENT PowerFactory fue proporcionado por el fabricante Power-One. Este
modelo es apto para la realizacin de estudios de rgimen permanente, cortocircuito y estabilidad transitoria. Cada
inversor estar conectado a un transformador de tipo pad-mounted que eleva la tensin a 23kV. Las caractersticas de
los transformadores son [11]:

Potencia nominal 1.56 MVA

Tensin nominal 23/0.69 kV, tomas en HV 2x2.5%

ndice: DY11

Tensin de cortocircuito = 6%

Perdidas en el cobre: 12.46 kW

Corriente en vaco: 0.11%

Tabla 2: Datos de transformadores de inversor

PV EL SALVADOR

14

Estudio de Cortocircuito

3 Consideraciones del Estudio


3.1 Zonas de Estudio
La zona de inters se sita en la red de Atacama y se compone, como indicado en la figura siguiente, de las
subestaciones de:
-

Diego de Almagro 110kV

El Salvador 110kV

Potrerillos 110kV

El Salado 110kV

Y de las lneas entre estas subestaciones (Lneas: Diego de Almagro-El Salvador, Diego de Almagro-El Salado, Diego de
Almagro-Potrerillos, Diego de Almagro-Isla Manto Verde, Diego de Almagro-Isla Centenario, Diego de Almagro-Planta de
xido, El Salvador-Llanta).
La nueva planta se conectar a la lnea que une las subestaciones de Diego de Almagro (Transelec) y Codelco Salvador
(Codelco), entre los postes N 81 y 82.
Los interruptores considerados en este estudio son los interruptores de 110kV y 220kV de las subestaciones de la zona
de inters: Diego de Almagro, Potrerillos, El Salvador y el Salado.

PV EL SALVADOR

15

Estudio de Cortocircuito

Figura 4: Zona de influencia en la red de Atacama

PV EL SALVADOR

16

Estudio de Cortocircuito

3.2 Informacin Tcnica del SIC y Herramienta de Simulacin


Utilizada
Para la simulacin del sistema se utiliz la base de datos del SIC en formato DIgSILENT PowerFactory correspondiente a
los escenarios bases confeccionados por la DO del CDEC-SIC para el mes de Septiembre de 2013, agregando la planta
fotovoltaica El Salvador en proyecto y otros proyectos actualmente en curso.

3.3 Perodo de aplicacin: Septiembre 2014


El estudio considera la red en su estado de Septiembre 2014 y la planta fotovoltaica El Salvador como ampliacin del
sistema.

3.4 Demanda en el SIC


El incremento de la demanda considerada en Septiembre 2014 es:
-

Cargas industriales de la zona Atacama: + 6.2%

Cargas residenciales de la zona Atacama: + 5.9%

La demanda en la zona norte de Atacama se ha determinado como la suma de la demanda en las lneas MaitencilloCardones sin generacin local despachada al norte de S/E Maitencillo, obteniendo:
-

Demanda Alta: 341MW

Demanda Baja: 317MW

3.5 Ampliaciones consideradas en Zona Norte


Las nuevas instalaciones de generacin consideradas en Septiembre 2014 son:

Tabla 3: Ampliaciones Septiembre 2014


Proyecto Generacin

Punto de Conexin

Central Fotovoltaica Llano de

Barra seccionadora en LT 220 kV Cardones -

Llampos

Cerro Negro Norte

Proyecto Fotovoltaico San

Barra seccionadora en LT 220 kV Cardones -

Andrs

Carrera Pinto.

Proyectos Fotovoltaicos

Tap-Off en LT 220 kV Maitencillo - Cardones

Valleland I y Valleland II

c1.

Parque elico Taltal

Tap Off en LT 220 kV Diego de Almagro


Paposo

Parque Elico Pacfico y La

S/E Seccionadora circuito 1 Las Palmas Pan

Cebada (Los Cururos)

de Azcar 220 kV (a 30 km de Las Palmas)

PV EL SALVADOR

Capacidad Instalada MW

Fecha de Puesta en
Servicio

100

Febrero 2014

50

1 trimestre 2014

67

1 semestre 2014

99

Septiembre 2014

72

Marzo de 2014

17

Estudio de Cortocircuito

Proyecto Generacin

Parque Elico El Arrayn


Proyecto Solar SolaireDirect
Generation x 05

Punto de Conexin

Capacidad Instalada MW

Barra seccionadora en LT 220 kV Las Palmas


Pan de Azcar C2
S/E Los Loros

Fecha de Puesta en
Servicio

115

Marzo 2014

50

3 trimestre 2014

3.6 Escenarios de operacin


Se ha considerado la configuracin del sistema que presenta la mayor contribucin de las centrales de generacin al
cortocircuito, esto significa, tener conectadas todas las unidades de generacin, todas las lneas y transformadores en
servicio, talque se configure el mayor enmallamiento del sistema. En total se han considerado 277 generadores
sncronos. La lista de generadores sncronos se proporciona en Anexo 1.
Dos escenarios se han considerado con la misma configuracin del sistema:
-

Escenario sin la nueva instalacin fotovoltaica

Escenario con la nueva instalacin fotovoltaica

No se han empleado redes equivalentes externas para representar el sistema. Se ha empleado toda la red tal y como
suministrada por CDEC-SIC con fecha Septiembre 2013.
La resistencia de las lneas areas y cables que se ha considerado es la disponible en la base de datos de las
instalaciones del CDEC-SIC que se emplean en el clculo de flujos de potencia.

3.7 Definicin y aplicacin de fallas


Las fallas indicadas en [ANEXO 3] son:

Fallas trifsicas (3F)

Fallas bifsicas (2F)

Fallas bifsicas a tierra (2FT)

Fallas monofsicas a tierra (1FT)

Se ha realizado el estudio con estos tipos de falla en todas las barras de 110kV, 154kV y 220kV de la red de Atacama.

Tabla 4: Barras en las que se aplican los cortocircuitos

Barra
H2
H1
J1
A
J2

PV EL SALVADOR

Subestacin
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones

Tensin nominal
[kV]
110
110
220
154
220

18

Estudio de Cortocircuito

Barra
J2
H1
H2
J1
IB
HA
J
Aux. D. Almagro J
J
Reactor D. de Almagro 2
J1
J2
Reactor D. de Almagro 1
El Salvador 110 kV
Llanta 1
Potrerillos 110 kV
Llanta 2
Tap Planta de xidos 110 kV
Tap Las Luces 110 kV
H
H
J
H
J1
J2
H1
H2
Alto del Carmen 110 kV
H
Torre 2 (Los Lirios)
H
J
J
Vallenar 110 kV
J
Tap Punta Toro
Tap Castilla
H
PV EL SALVADOR

Subestacin
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E Carrera Pinto
S/E Paposo
S/E Paposo

S/E Taltal
S/E El Salado
Central San Lorenzo de Almagro
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
S/E Cerrillos
S/E Los Loros
S/E La Candelaria
S/E La Coipa
S/E Agrosuper

S/E Tierra Amarrilla

Tensin nominal
[kV]
220
110
110
220
110
110
220
220
220
220
220
220
220
110
110
110
110
110
110
110
110
220
110
220
220
110
110
110
110
110
110
220
220
110
220
110
110
110
19

Estudio de Cortocircuito

Barra
H
Tap Impulsin 110 kV
H
H
H
H
Reactor D. Almagro
J
H
H
H
H
H
Tap Ro Huasco
Tap El Edn
B1
B2
B1
B2
Paipote
Jorquera
Tap Jorquera C2
Ro Huasco 110
Caserones
Tap Jorquera C1
CNN
Travesa
T_PV_El Salvador HV
Tap PV El Salvador

Subestacin
S/E Refugio
S/E Hernn Fuentes
S/E Caldera
S/E Impulsion
S/E Los Colorados (CMP)
S/E Medellin
S/E Copiapo
S/E Magnetita
S/E Cenizas
S/E Kozan
S/E Plantas

S/E Chacayes
S/E Chacayes
S/E Chacayes(1)
S/E Chacayes(1)
S/E Paipote

Tensin nominal
[kV]
110
110
110
110
110
110
220
220
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
110
110

3.8 Modelos y Metodologa de clculo


El mtodo de clculo empleado es el mtodo de la norma IEC 60909 que supone las siguientes simplificaciones [ANEXO
3]:
a)

Durante el tiempo de duracin del cortocircuito no existe cambio en el tipo de cortocircuito, esto es, un
cortocircuito trifsico permanece trifsico y un cortocircuito monofsico permanece monofsico durante todo el
tiempo del cortocircuito.

PV EL SALVADOR

20

Estudio de Cortocircuito

b)

Durante el tiempo de duracin del cortocircuito, no existen cambios topolgicos en la red.

c)

La impedancia de los transformadores es referida a la posicin nominal del cambiador de tomas. No obstante,
el clculo de corrientes de cortocircuito debe considerar un factor de correccin que represente a la posicin
del cambiador de tomas que de origen a la menor impedancia de cortocircuito.

d)

Las magnitudes de la resistencia del arco del cortocircuito y de la impedancia de falla se consideran
despreciables.

e)

No se consideran: las capacitancias de las lneas, las admitancias shunt y las cargas estticas (no-rotatorias),
excepto las correspondientes a la red de secuencia cero del sistema.

f)

El tiempo mnimo de separacin de los contactos de un interruptor a considerar ser de 40 milisegundos. Dicho
valor, est constituido por la suma del tiempo de operacin del rele ms rpido que acta sobre el trip del
interruptor y del tiempo de inicio de la separacin de sus contactos.

3.8.1 Modelos para las nuevas ampliaciones consideradas con fecha Septiembre 2014
Se modelan las nuevas instalaciones con un modelo genrico de generador esttico sin contribucin a la corriente de
falla de acuerdo a la normativa IEC.

3.8.2 Modelo de inversor nueva planta fotovoltaica El Salvador


Para modelar los inversores y su contribucin al cortocircuito se ha tenido en cuenta la informacin del fabricante. El
fabricante estipula que cada inversor contribuye a la falta con 1.09 veces su corriente nominal en secuencia positiva,
excepto si la tensin de secuencia negativa supera un cierto nivel en cuyo caso la contribucin a la falta es nula.
La contribucin de la nueva instalacin a la corriente de cortocircuito se mira en terminales de un inversor y en
terminales del transformador HT/MT lado HT.

3.8.3 Mtodo mejorado para ajuste la corriente de cortocircuito en caso de


cortocircuitos desequilibrados
El fabricante del inversor realiza una supervisin de la tensin de secuencia negativa en terminales del inversor en el
momento en que tiene lugar un cortocircuito. Cuando la tensin de secuencia negativa supera un umbral fijado por
defecto por el fabricante, el inversor no contribuye al cortocircuito.
Para poder simular estas condiciones en cada inversor, se ha implementado un algoritmo en DPL con el proceso
siguiente:
-

Clculo de cortocircuitos monofsicos, bifsicos y bifsicos a tierra.

Supervisin de tensin de secuencia negativa, comparacin con umbral lmite


o

Si la tensin de secuencia negativa es mayor modificacin de la contribucin al cortocircuito nula en


los inversores en los que se detecta la condicin.

Si la tensin de secuencia negativa es menor modificacin de la contribucin al cortocircuito


correspondiente a 1.09pu de corriente de secuencia positiva en los inversores en los que se detecta la
condicin.

PV EL SALVADOR

21

Estudio de Cortocircuito

Repeticin del clculo de cortocircuito

Emisin de resultados finales.

3.9 Corrientes de cortocircuito


Las componentes de la corriente de cortocircuito que se debern calcular son [ANEXO 3]:
a)

Corriente de cortocircuito simtrica inicial (r.m.s)

b)

Corrientes de cortocircuito simtrica y asimtrica de interrupcin (r.m.s.), evaluada en el instante de 40


milisegundos despus de iniciada la falla

c)

Corriente de cortocircuito mxima instantnea (peak) (cierre contra cortocircuito)

d)

Corriente de cortocircuito en rgimen permanente (r.m.s).

Para el clculo de estas componentes, se han empleado los valores por defecto para las mquinas sncronas y
asncronas disponibles en la base de datos de las instalaciones del CDEC-SIC. Cabe sealar que hay una mquina
asncrona en la base de datos que representa una instalacin elica.

3.10 Interruptores Considerados


Un interruptor estar adecuadamente dimensionado si satisface las condiciones que se sealan a continuacin,
supeditado a las mayores corrientes de cortocircuito que se determinen de acuerdo con lo establecido en el Artculo 11
de [ANEXO 3]:
a)

La capacidad de ruptura simtrica nominal del interruptor, deber ser mayor que la corriente de cortocircuito
simtrica de interrupcin que se establezca a travs de ste, en el instante de 40 milisegundos despus de
iniciado el cortocircuito.

b)

La capacidad de ruptura asimtrica del interruptor, deber ser mayor que la corriente de cortocircuito de
interrupcin asimtrica que se establezca a travs de ste, en el instante de 40 milisegundos despus de
iniciado el cortocircuito.

c)

La capacidad de cierre contra cortocircuito nominal del interruptor, deber ser mayor que la corriente de
cortocircuito mxima instantnea (peak), que se establezca a travs de ste.

d)

La corriente de cortocircuito de duracin nominal del interruptor dada por el (I2t) de diseo, denominada
corriente trmica (Ith), deber ser mayor que el Ik2t correspondiente a la corriente de cortocircuito en rgimen
permanente para un perodo de operacin de la primera proteccin de respaldo. Muchos de los interruptores
de la base de datos del CDEC-SIC carecen del dato de diseo, por tanto se han comparado slo los disponibles.
Se ha empleado un tiempo para el clculo de Ith de 120ms.

Los interruptores considerados en este estudio son los interruptores de 110kV y 220kV de las subestaciones de la zona
de inters: Diego de Almagro, Potrerillos, El Salvador y el Salado.

PV EL SALVADOR

22

Estudio de Cortocircuito

Tabla 5: Interruptores considerados en el estudio de capacidad de ruptura

Interruptor (INT)

IM S/E DIEGO DE
ALMAGRO HS
IM S/E DIEGO DE
ALMAGRO HT1
IM S/E DIEGO DE
ALMAGRO J3
IM S/E DIEGO DE
ALMAGRO H5
IM S/E DIEGO DE
ALMAGRO H3
IM S/E DIEGO DE
ALMAGRO HR
IM S/E DIEGO DE
ALMAGRO J1
IM S/E DIEGO DE
ALMAGRO JT3
IM S/E DIEGO DE
ALMAGRO HT2
IM S/E DIEGO DE
ALMAGRO H1
IM S/E DIEGO DE
ALMAGRO H2
IM S/E DIEGO DE
ALMAGRO JZ1
IM S/E DIEGO DE
ALMAGRO HT3
IM S/E DIEGO DE
ALMAGRO J4

Subestacin (ST)

Barra

Elemento

S/E Diego de Almagro

HA

HA-IB

S/E Diego de Almagro

IB

S/E Diego de Almagro

S/E Diego de Almagro

HA

S/E Diego de Almagro

IB

S/E Diego de Almagro

HA

S/E Diego de Almagro

S/E Diego de Almagro

S/E Diego de Almagro

HA

HA-IB
Carrera Pinto - Diego
de Almagro 220 kV
D.Almagro-Reactor
220 kV L2

Diego de Almagro El Salvador


Diego de Almagro Llanta 110kV C1

Capacidad
Ruptura
Simtrica
[kA]

Capacidad
Ruptura
Asimtrica
[kA]

Capacidad
Cierre En
Cortocircuito
[kA]

Tipo
INT

Modelo
INT

Fabricante
INT

FA 1

MERLIN GERIN

123

2000

32

40

64

FA 1

MERLIN GERIN

123

2000

32

40

64

LTB 245E1

ABB

245

3150

40

50

100

FA 1

MERLIN GERIN

123

2000

32

40

64

FA 1

MERLIN GERIN

123

2000

32

40

64

FA 1

MERLIN GERIN

123

2000

32

40

64

MERLIN GERIN

245

3150

40

50

80

FA2
HGF114/1A

ALSTOM

245

3150

32

40

64

FA 1

MERLIN GERIN

123

2000

32

40

64

FA 1

MERLIN GERIN

123

2000

32

40

64

MERLIN GERIN

123

2000

32

40

64

ABB

245

3150

40

50

100

S/E Diego de Almagro

HA

S/E Diego de Almagro

IB

S/E Diego de Almagro

FA 1
HPL
245/31B1U
S

S/E Diego de Almagro

IB

FA 1

MERLIN GERIN

123

2000

32

40

64

S/E Diego de Almagro

J
El
Salvador
110 kV
El
Salvador
110 kV

3AQ1 EE
MAGRINI
GALILEO
OCERD 123
MAGRINI
GALILEO
OCERD 123

SIEMENS

245

3150

40

50

80

MAGRINI

110

800

14.6

S/I

S/I

MAGRINI

110

800

14.6

S/I

S/I

IM S/E EL SALVADOR
H1

01-Atacama

IM S/E EL SALVADOR
H2

01-Atacama

PV EL SALVADOR

D.Almagro-Reactor
220 kV L2
Diego de Almagro
Planta de xidos
110 kV
Diego de Almagro Llanta 110kV C2

Corriente
Nominal
[A]

Tensin
Nominal
[kV]

Diego de Almagro El Salvador

El Salvador - Llanta

23

Estudio de Cortocircuito

Interruptor (INT)

Subestacin (ST)

Barra

01-Atacama

El
Salvador
110 kV

Elemento

Tipo
INT

Modelo
INT

Fabricante
INT

Tensin
Nominal
[kV]

Corriente
Nominal
[A]

Capacidad
Ruptura
Simtrica
[kA]

Capacidad
Ruptura
Asimtrica
[kA]

Capacidad
Cierre En
Cortocircuito
[kA]

115

1200

S/I

S/I

S/I

115

800

75

S/I

S/I

110

800

14.6

S/I

S/I

115

800

75

S/I

S/I

110

800

14.6

S/I

S/I

110

800

14.6

S/I

S/I

110

800

14.6

S/I

S/I

110

800

14.6

S/I

S/I

145

3150

40

10

100

IM S/E EL SALVADOR
HT1

01-Atacama

IM S/E EL SALVADOR
H3

01-Atacama

El
Salvador
110 kV
El
Salvador
110 kV

IM S/E EL SALVADOR
HT2

01-Atacama

El
Salvador
110 kV

A-B

IM S/E POTRERILLOS
H3

01-Atacama

Potrerillos
110 kV

Potrerillos - Diego de
Almagro

IM S/E POTRERILLOS
H2

01-Atacama

Potrerillos
110 kV

Potrerillos - Diego de
Almagro

IM S/E POTRERILLOS
HT1

01-Atacama

Potrerillos
110 kV

01-Atacama

Potrerillos
110 kV

WESTINGH
OUSE
1150-GM5000
WESTINGHOUSE
ALLISCHALMERS
BZO-160115F
ALLIS- CHALMERS
MAGRINI
GALILEO
OCERD 123
MAGRINI
ALLISCHALMERS
BZO-160115F
ALLIS- CHALMERS
MAGRINI
GALILEO
OCERD 123
MAGRINI
MAGRINI
GALILEO
OCERD 123
MAGRINI
MAGRINI
GALILEO
OCERD 123
MAGRINI
MAGRINI
GALILEO
OCERD 123
MAGRINI

S/E Diego de Almagro

IB

ABBLTB145D1

S/E El Salado

3PA1FG

SIEMENS

123

3150

40

50

100

3AP1FG

SIEMENS

123

3150

50

100

8DN9
SIEMENS
3AP1 FG

SIEMENS

245

3150

40
31.5 (1
seg)

SIEMENS

110

4000

40

10

IM S/E EL SALVADOR
HT3

IM S/E POTRERILLOS
HT2
IM S/E DIEGO DE
ALMAGRO H6LNEAMV
IM S/E El Salado HT1
IM S/E DIEGO DE
ALMAGRO H9
IM S/E DIEGO DE
ALMAGRO JT6
IM S/E DIEGO DE
ALMAGRO H8

PV EL SALVADOR

S/E Diego de Almagro

HA

S/E Diego de Almagro

S/E Diego de Almagro

HA

A-B

A-B

El Salvador - Llanta

I. Manto Verde
D.Almagro - El
Salado 110 kV

Diego de Almagro Emelda 110 kV

135
40

24

Estudio de Cortocircuito

4 Resultados
Los resultados del estudio se presentan a continuacin para los cuatro tipos de faltas consideradas, con y sin considerar la nueva planta fotovoltaica. A
continuacin para cada tipo de falla se incluye una seccin donde se comparan los dos casos y observar el incremento en las corrientes de cortocircuito
respecto al caso base sin la instalacin fotovoltaica nueva.
Los resultados proporcionados en tablas son:
-

Tensin [kV]: tensin nominal de la barra.

Ikss [kA]: Corriente de cortocircuito simtrica inicial o subtransitoria en kA.

Ip [kA]: Corriente mxima en kA.

Ib [kA]: Corriente de cortocircuito simtrica de interrupcin en kA.

Ibasy [kA]: Corriente de cortocircuito asimtrica de interrupcin en kA.

Ik [kA]: Corriente de cortocircuito en rgimen permanente en kA.

Ith [kA]: Corriente de cortocircuito trmica en kA.

4.1 Fallas trifsicas (3F)


4.1.1 Sin el parque fotovoltaico
Tabla 6: Fallas trifsicas - sin la nueva instalacin

Barra
H
J1

PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda

Tensin
[kV]

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
110
7.016
17.405
6.760
7.512
7.002
7.801
220
10.863
27.297
10.565
12.148
10.752
12.212

25

Estudio de Cortocircuito

Barra
J2
H1
H2
J
J
H
H2
H1
J1
A
J2
J
H
H
B1
B2
B1
B2
H
HA
IB
J
H
H
PV EL SALVADOR

Subestacin
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Chacayes
S/E Chacayes
S/E Chacayes(1)
S/E Chacayes(1)
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes

Tensin
[kV]
220
110
110
220
220
110
110
110
220
154
220
220
110
110
110
110
110
110
110
110
110
220
110
110

Ikss [kA] Ip [kA]


Ib [kA]
10.863
27.297
10.565
5.541
12.282
5.410
5.541
12.282
5.410
5.403
13.258
5.273
10.651
26.184
10.453
1.162
2.027
1.162
4.970
12.600
4.970
4.970
12.600
4.970
8.588
20.634
8.403
0.000
0.000
0.000
8.588
20.634
8.403
4.863
11.038
4.851
2.979
0.000
0.000
0.000
0.000
3.379
7.352
7.352
5.421
3.260
2.846

6.003
0.000
0.000
0.000
0.000
7.122
18.832
18.832
13.308
6.834
5.700

2.979
0.000
0.000
0.000
0.000
3.379
7.093
7.093
5.290
3.256
2.846

Ibasy
[kA]
Ik [kA]
Ith [kA]
12.148
10.752
12.212
5.426
5.494
5.858
5.426
5.494
5.858
5.696
5.388
5.959
11.429
10.527
11.763
1.162
1.162
1.189
5.307
4.970
5.637
5.307
4.970
5.637
8.893
8.526
9.353
0.000
0.000
0.000
8.893
8.526
9.353
4.932
4.839
5.176
2.981
0.000
0.000
0.000
0.000
3.383
8.538
8.538
5.718
3.263
2.847

2.979
0.000
0.000
0.000
0.000
3.379
7.337
7.337
5.406
3.253
2.846

3.093
0.000
0.000
0.000
0.000
3.534
8.440
8.440
5.981
3.405
2.953
26

Estudio de Cortocircuito

Barra
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
PV EL SALVADOR

Subestacin
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV

Tensin
[kV]
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
2.065
3.867
2.065
2.912
5.830
2.912
6.721
15.624
6.643
2.331
5.194
2.331
2.720
4.686
2.720
1.751
3.176
1.751
2.886
5.227
2.886
10.717
26.374
10.513
7.702
19.055
7.637
7.702
19.055
7.637
10.717
26.374
10.513
8.563
20.566
8.379
3.127
6.096
3.127
4.577
11.742
4.455
4.577
11.742
4.455
2.658
5.197
2.658
1.039
2.181
1.039
0.963
1.600
0.963
3.180
6.533
3.180
4.932
12.436
4.932
4.165
7.975
4.142
4.247
9.107
4.221
4.343
9.372
4.313
1.296
2.177
1.296

Ibasy
[kA]
Ik [kA]
Ith [kA]
2.065
2.065
2.125
2.913
2.912
3.021
6.832
6.672
7.212
2.356
2.331
2.467
2.720
2.720
2.779
1.751
1.751
1.797
2.886
2.886
2.960
11.517
10.592
11.845
7.978
7.623
8.546
7.978
7.623
8.546
11.517
10.592
11.845
8.864
8.500
9.324
3.128
3.127
3.233
5.347
4.569
5.265
5.347
4.569
5.265
2.658
2.658
2.748
1.041
1.039
1.086
0.963
0.963
0.981
3.182
3.180
3.311
5.234
4.932
5.563
4.143
4.156
4.296
4.234
4.238
4.456
4.330
4.333
4.562
1.296
1.296
1.322
27

Estudio de Cortocircuito

Barra
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

PV EL SALVADOR

Subestacin
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110
110
23

Ikss [kA] Ip [kA]


Ib [kA]
1.437
2.424
1.437
2.159
4.073
2.159
3.973
7.292
3.973
2.742
4.805
2.742
0.000
0.000
0.000
5.421
13.308
5.290
5.421
13.308
5.290
1.667
2.747
1.667
5.419
13.302
5.288
3.230
7.109
3.230
2.661
6.136
2.661
4.158
8.316
4.135
3.240
7.414
3.240
3.206
6.676
3.203
5.421
13.308
5.290
3.249
3.654
0.000

7.340
6.135
0.000

3.249
3.654
0.000

Ibasy
[kA]
Ik [kA]
Ith [kA]
1.437
1.437
1.466
2.159
2.159
2.224
3.973
3.973
4.081
2.742
2.742
2.805
0.000
0.000
0.000
5.718
5.406
5.981
5.718
5.406
5.981
1.667
1.667
1.698
5.715
5.404
5.978
3.256
3.230
3.409
2.726
2.661
2.847
4.137
4.149
4.312
3.306
3.240
3.457
3.209
3.200
3.346
5.718
5.406
5.981
3.274
3.654
0.000

3.249
3.654
0.000

3.453
3.726
0.000

28

Estudio de Cortocircuito

4.1.2 Con el parque fotovoltaico


Tabla 7: Fallas trifsicas - con la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
A
J2
J
H
H
B1
B2
B1
B2
H
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Chacayes
S/E Chacayes
S/E Chacayes(1)
S/E Chacayes(1)
S/E Copiapo

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
154
220
220
110
110
110
110
110
110
110

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
7.305
18.022
7.050
7.752
6.977
8.088
10.867
27.304
10.570
12.148
10.728
12.216
10.867
27.304
10.570
12.148
10.728
12.216
5.541
12.283
5.411
5.426
5.483
5.858
5.541
12.283
5.411
5.426
5.483
5.858
5.505
13.513
5.380
5.814
5.353
6.073
10.657
26.193
10.458
11.431
10.500
11.768
1.163
2.027
1.163
1.163
1.163
1.189
4.973
12.605
4.973
5.309
4.973
5.640
4.973
12.605
4.973
5.309
4.973
5.640
8.603
20.662
8.418
8.905
8.488
9.368
0.000
0.000
0.000
0.000
0.000
0.000
8.603
20.662
8.418
8.905
8.488
9.368
4.896
11.105
4.885
4.965
4.795
5.209
2.980
0.000
0.000
0.000
0.000
3.380

6.004
0.000
0.000
0.000
0.000
7.124

2.980
0.000
0.000
0.000
0.000
3.380

2.981
0.000
0.000
0.000
0.000
3.384

2.980
0.000
0.000
0.000
0.000
3.380

3.094
0.000
0.000
0.000
0.000
3.535
29

Estudio de Cortocircuito

Barra
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
PV EL SALVADOR

Subestacin
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla

Tensin
[kV]
110
110
220
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
7.696
19.660
7.436
7.696
19.660
7.436
5.523
13.565
5.398
3.324
6.939
3.321
2.847
5.701
2.847
2.065
3.868
2.065
2.913
5.831
2.913
6.730
15.640
6.652
2.338
5.208
2.338
2.720
4.686
2.720
1.751
3.176
1.751
2.886
5.228
2.886
10.723
26.384
10.519
7.703
19.058
7.638
7.703
19.058
7.638
10.723
26.384
10.519
8.578
20.594
8.394
3.128
6.098
3.128
4.601
11.803
4.480
4.601
11.803
4.480
2.658
5.198
2.658
1.039
2.182
1.039
0.968
1.606
0.968
3.181
6.534
3.181

Ibasy
[kA]
Ik [kA]
Ith [kA]
8.881
7.337
8.806
8.881
7.337
8.806
5.838
5.371
6.096
3.328
3.169
3.470
2.848
2.847
2.953
2.065
2.065
2.125
2.914
2.913
3.022
6.841
6.640
7.220
2.364
2.338
2.475
2.720
2.720
2.779
1.751
1.751
1.797
2.886
2.886
2.961
11.519
10.565
11.850
7.979
7.604
8.547
7.979
7.604
8.547
11.519
10.565
11.850
8.876
8.463
9.338
3.129
3.128
3.234
5.375
4.527
5.293
5.375
4.527
5.293
2.659
2.658
2.749
1.041
1.039
1.086
0.968
0.968
0.986
3.183
3.181
3.312
30

Estudio de Cortocircuito

Barra
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL
PV EL SALVADOR

Subestacin
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110
110
23

Ikss [kA] Ip [kA]


Ib [kA]
4.934
12.441
4.934
4.510
8.851
4.487
4.410
9.427
4.386
4.511
9.705
4.483
1.305
2.187
1.305
1.448
2.437
1.448
2.160
4.073
2.160
3.973
7.292
3.973
2.743
4.806
2.743
4.502
8.831
4.479
5.523
13.565
5.398
5.523
13.565
5.398
1.667
2.747
1.667
5.521
13.559
5.396
3.232
7.112
3.232
2.661
6.137
2.661
4.363
8.742
4.342
3.241
7.415
3.241
3.298
6.845
3.296
5.523
13.565
5.398
3.251
3.654
10.980

7.342
6.135
25.189

3.251
3.654
10.980

Ibasy
[kA]
Ik [kA]
Ith [kA]
5.236
4.934
5.566
4.488
4.156
4.666
4.399
4.165
4.624
4.500
4.262
4.736
1.305
1.305
1.331
1.448
1.448
1.477
2.160
2.160
2.224
3.974
3.973
4.081
2.743
2.743
2.806
4.480
4.148
4.657
5.838
5.371
6.096
5.838
5.371
6.096
1.667
1.667
1.698
5.835
5.369
6.093
3.258
3.232
3.411
2.726
2.661
2.847
4.345
4.090
4.526
3.307
3.241
3.458
3.301
3.115
3.439
5.838
5.371
6.096
3.275
3.654
11.210

3.251
3.654
10.980

3.454
3.726
11.726
31

Estudio de Cortocircuito

4.1.3 Comparacin
Tabla 8: Fallas trifsicas - comparacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
A
J2
J
H
H
B1
B2
B1
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Chacayes
S/E Chacayes
S/E Chacayes(1)

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
154
220
220
110
110
110
110
110

Ikss
Ibasy
[kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
0.289
0.618
0.290
0.240
-0.025
0.288
0.004
0.007
0.004
0.000
-0.024
0.003
0.004
0.007
0.004
0.000
-0.024
0.003
0.000
0.000
0.000
0.000
-0.012
0.000
0.000
0.000
0.000
0.000
-0.012
0.000
0.102
0.255
0.107
0.119
-0.035
0.114
0.006
0.009
0.006
0.002
-0.026
0.005
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.005
0.002
0.002
0.002
0.002
0.002
0.005
0.002
0.002
0.002
0.002
0.015
0.028
0.015
0.012
-0.037
0.014
0.000
0.000
0.000
0.000
0.000
0.000
0.015
0.028
0.015
0.012
-0.037
0.014
0.032
0.067
0.034
0.034
-0.044
0.034
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
32

Estudio de Cortocircuito

Barra
B2
H
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
PV EL SALVADOR

Subestacin
S/E Chacayes(1)
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio

Tensin
[kV]
110
110
110
110
220
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110

Ikss
Ibasy
[kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.002
0.001
0.001
0.001
0.001
0.343
0.828
0.343
0.342
0.000
0.366
0.343
0.828
0.343
0.342
0.000
0.366
0.102
0.258
0.108
0.120
-0.034
0.115
0.064
0.105
0.065
0.065
-0.084
0.065
0.001
0.001
0.001
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.001
0.001
0.001
0.009
0.016
0.009
0.008
-0.032
0.009
0.007
0.015
0.007
0.007
0.007
0.008
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.001
0.001
0.001
0.006
0.009
0.006
0.002
-0.026
0.005
0.001
0.002
0.001
0.001
-0.019
0.001
0.001
0.002
0.001
0.001
-0.019
0.001
0.006
0.009
0.006
0.002
-0.026
0.005
0.015
0.028
0.015
0.012
-0.037
0.014
0.001
0.001
0.001
0.001
0.001
0.001
0.025
0.061
0.025
0.029
-0.042
0.027
0.025
0.061
0.025
0.029
-0.042
0.027
0.001
0.001
0.001
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
33

Estudio de Cortocircuito

Barra
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
PV EL SALVADOR

Subestacin
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

Tensin
[kV]
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110

Ikss
Ibasy
[kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
0.005
0.006
0.005
0.005
0.005
0.005
0.001
0.001
0.001
0.001
0.001
0.001
0.002
0.005
0.002
0.002
0.002
0.002
0.345
0.876
0.345
0.346
0.000
0.369
0.163
0.321
0.165
0.165
-0.073
0.168
0.168
0.334
0.171
0.170
-0.071
0.174
0.009
0.010
0.009
0.009
0.009
0.009
0.011
0.013
0.011
0.011
0.011
0.011
0.000
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
4.502
8.831
4.479
4.480
4.148
4.657
0.102
0.258
0.108
0.120
-0.034
0.115
0.102
0.258
0.108
0.120
-0.034
0.115
0.000
0.000
0.000
0.000
0.000
0.000
0.102
0.258
0.108
0.120
-0.034
0.115
0.002
0.003
0.002
0.002
0.002
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.206
0.426
0.208
0.208
-0.059
0.214
0.000
0.001
0.000
0.000
0.000
0.000
0.091
0.169
0.093
0.092
-0.085
0.093
0.102
0.258
0.108
0.120
-0.034
0.115
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.002
0.001
0.001
0.001
0.001
34

Estudio de Cortocircuito

Barra
Subestacin
Vallenar 110 kV
01-Atacama
TF_PV_ELSALVADOR_INTERNAL PV EL SALVADOR

Tensin
[kV]

Ikss
Ibasy
[kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
110
0.000
0.000
0.000
0.000
0.000
0.000
23
10.980
25.189
10.980
11.210
10.980
11.726

4.1.4 Observaciones
Como se puede comprobar, la nueva instalacin tiene poca contribucin a la corriente de cortocircuito y a la red, excepto en su punto de conexin.

PV EL SALVADOR

35

Estudio de Cortocircuito

4.2 Fallas bifsicas (2F)


4.2.1 Sin el parque fotovoltaico
Tabla 9: Fallas bifsicas - sin la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
J
H
H
H
HA
IB
J
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220
220
110
110
110
110
110
220

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
5.828
14.458
5.828
8.243
5.828
6.480
9.383
23.578
9.383
13.269
9.383
10.549
9.383
23.578
9.383
13.269
9.383
10.549
4.788
10.613
4.788
6.771
4.788
5.062
4.788
10.613
4.788
6.771
4.788
5.062
4.488
11.013
4.488
6.347
4.488
4.950
9.175
22.555
9.175
12.976
9.175
10.133
1.005
1.753
1.005
1.422
1.005
1.028
4.277
10.841
4.277
6.048
4.277
4.851
4.277
10.841
4.277
6.048
4.277
4.851
7.265
17.454
7.265
10.274
7.265
7.912
7.265
17.454
7.265
10.274
7.265
7.912
4.131
9.376
4.131
5.842
4.131
4.396
2.571
2.914
6.119
6.119
4.503

5.179
6.141
15.673
15.673
11.053

2.571
2.914
6.119
6.119
4.503

3.635
4.121
8.654
8.654
6.368

2.571
2.914
6.119
6.119
4.503

2.669
3.047
7.024
7.024
4.968
36

Estudio de Cortocircuito

Barra
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
PV EL SALVADOR

Subestacin
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)

Tensin
[kV]
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
2.776
5.821
2.776
2.456
4.919
2.456
1.784
3.341
1.784
2.513
5.031
2.513
5.714
13.285
5.714
2.000
4.456
2.000
2.355
4.057
2.355
1.513
2.744
1.513
2.490
4.511
2.490
9.232
22.718
9.232
6.662
16.483
6.662
6.662
16.483
6.662
9.232
22.718
9.232
7.244
17.398
7.244
2.698
5.259
2.698
3.689
9.466
3.689
3.689
9.466
3.689
2.294
4.486
2.294
0.899
1.887
0.899
0.830
1.380
0.830
2.743
5.635
2.743
4.244
10.701
4.244
3.535
6.770
3.535
3.599
7.717
3.599

Ibasy
[kA]
Ik [kA]
Ith [kA]
3.926
2.776
2.900
3.474
2.456
2.548
2.522
1.784
1.836
3.554
2.513
2.607
8.081
5.714
6.132
2.828
2.000
2.117
3.330
2.355
2.406
2.140
1.513
1.553
3.522
2.490
2.555
13.055
9.232
10.203
9.421
6.662
7.392
9.421
6.662
7.392
13.055
9.232
10.203
10.244
7.244
7.888
3.815
2.698
2.789
5.218
3.689
4.245
5.218
3.689
4.245
3.244
2.294
2.372
1.271
0.899
0.939
1.174
0.830
0.846
3.879
2.743
2.856
6.002
4.244
4.787
5.000
3.535
3.647
5.090
3.599
3.776
37

Estudio de Cortocircuito

Barra
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla

Subestacin
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV

Tensin
[kV]
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
3.678
7.937
3.678
1.116
1.875
1.116
1.237
2.087
1.237
1.865
3.518
1.865
3.439
6.311
3.439
2.371
4.155
2.371

Ibasy
[kA]
Ik [kA]
Ith [kA]
5.201
3.678
3.864
1.579
1.116
1.138
1.749
1.237
1.262
2.638
1.865
1.921
4.863
3.439
3.532
3.354
2.371
2.426

4.2.2 Con el parque fotovoltaico


Tabla 10: Fallas bifsicas - con la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
5.828
14.458
5.828
8.243
5.828
6.480
9.385
23.580
9.385
13.272
9.385
10.550
9.385
23.580
9.385
13.272
9.385
10.550
4.788
10.613
4.788
6.771
4.788
5.062
4.788
10.613
4.788
6.771
4.788
5.062
4.488
11.013
4.488
6.347
4.488
4.950
9.178
22.557
9.178
12.979
9.178
10.134
1.005
1.753
1.005
1.422
1.005
1.028
4.278
10.843
4.278
6.050
4.278
4.851
4.278
10.843
4.278
6.050
4.278
4.851
7.271
17.463
7.271
10.283
7.271
7.917
38

Estudio de Cortocircuito

Barra
J2
J
H
H
H
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
PV EL SALVADOR

Subestacin
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo

Tensin
[kV]

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
220
7.271
17.463
7.271
10.283
7.271
7.917
220
4.131
9.376
4.131
5.842
4.131
4.396
110
110
2.571
5.180
2.571
3.636
2.571
2.669
110
2.914
6.142
2.914
4.121
2.914
3.047
110
6.119
15.673
6.119
8.654
6.119
7.024
110
6.119
15.673
6.119
8.654
6.119
7.024
220
4.503
11.053
4.503
6.368
4.503
4.968
110
2.776
5.821
2.776
3.926
2.776
2.900
110
2.457
4.919
2.457
3.474
2.457
2.548
110
1.784
3.341
1.784
2.523
1.784
1.836
110
2.513
5.031
2.513
3.554
2.513
2.607
220
5.718
13.289
5.718
8.087
5.718
6.135
220
2.003
4.462
2.003
2.832
2.003
2.120
110
2.355
4.057
2.355
3.330
2.355
2.406
110
1.513
2.744
1.513
2.140
1.513
1.553
110
2.491
4.512
2.491
3.523
2.491
2.555
220
9.234
22.720
9.234
13.059
9.234
10.204
110
6.662
16.483
6.662
9.422
6.662
7.392
110
6.662
16.483
6.662
9.422
6.662
7.392
220
9.234
22.720
9.234
13.059
9.234
10.204
220
7.250
17.407
7.250
10.253
7.250
7.893
110
2.698
5.260
2.698
3.816
2.698
2.789
220
3.689
9.466
3.689
5.218
3.689
4.245
39

Estudio de Cortocircuito

Barra
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
PV EL SALVADOR

Subestacin
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

Tensin
[kV]
220
110
110
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110

Ikss [kA] Ip [kA]


Ib [kA]
3.689
9.466
3.689
2.294
4.486
2.294
0.899
1.887
0.899
0.833
1.382
0.833
2.743
5.636
2.743
4.245
10.703
4.245
3.535
6.770
3.535
3.599
7.717
3.599
3.678
7.937
3.678
1.120
1.877
1.120
1.242
2.090
1.242
1.865
3.518
1.865
3.439
6.311
3.439
2.371
4.155
2.371
3.529
6.753
3.529
4.503
11.053
4.503
4.503
11.053
4.503
1.444
2.379
1.444
4.501
11.048
4.501
2.774
6.104
2.774
2.302
5.307
2.302
3.527
7.055
3.527
2.802
6.411
2.802
2.732
5.688
2.732

Ibasy
[kA]
Ik [kA]
Ith [kA]
5.218
3.689
4.245
3.245
2.294
2.373
1.271
0.899
0.939
1.177
0.833
0.848
3.879
2.743
2.856
6.003
4.245
4.788
5.000
3.535
3.647
5.090
3.599
3.776
5.201
3.678
3.864
1.584
1.120
1.142
1.756
1.242
1.266
2.638
1.865
1.921
4.863
3.439
3.532
3.354
2.371
2.426
4.990
3.529
3.640
6.368
4.503
4.968
6.368
4.503
4.968
2.043
1.444
1.471
6.365
4.501
4.966
3.923
2.774
2.927
3.255
2.302
2.462
4.988
3.527
3.658
3.962
2.802
2.989
3.864
2.732
2.851
40

Estudio de Cortocircuito

Barra
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

Subestacin
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
220
4.503
11.053
4.503
6.368
4.503
4.968
110
110
2.803
6.331
2.803
3.964
2.803
2.979
110
3.166
5.315
3.166
4.477
3.166
3.228
23
7.791
17.602
7.791
11.018
7.791
8.280

4.2.3 Comparacin
Tabla 11: Fallas bifsicas - comparacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220

Ibasy
Ikss [kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.001
0.002
0.003
0.002
0.001
0.002
0.001
0.002
0.003
0.002
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.002
0.002
0.003
0.002
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.002
0.001
0.001
0.001
0.001
0.001
0.002
0.001
0.001
0.001
0.001
0.006
0.008
0.006
0.009
0.006
0.005
0.006
0.008
0.006
0.009
0.006
0.005
41

Estudio de Cortocircuito

Barra
J
H
H
H
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
PV EL SALVADOR

Subestacin
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo

Tensin
[kV]
220
110
110
110
110
110
220
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.004
0.005
0.004
0.003
0.005
0.003
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.002
0.002
0.001
0.001
0.001
0.001
0.001
0.001
0.002
0.002
0.002
0.006
0.008
0.006
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.000
0.000
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.005
0.004
0.003
0.004
0.003
0.003
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.001
0.001
0.001
0.000
0.001
0.001
0.000
0.003
0.002
0.001
0.009
0.006
0.005
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
42

Estudio de Cortocircuito

Barra
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
PV EL SALVADOR

Subestacin
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

Tensin
[kV]
110
110
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.001
0.002
0.000
0.000
0.000
0.001
0.002
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.004
0.002
0.004
0.005
0.003
0.005
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
3.529
6.753
3.529
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.002
0.001
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.005
0.004
0.004
0.007
0.005
0.005
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
4.990
3.529
3.640
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
43

Estudio de Cortocircuito

Barra
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

Subestacin
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
23

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.001
0.000
0.000
0.000
0.000
7.791
17.602
7.791

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.001
0.000
0.000
0.000
0.000
0.000
11.018
7.791
8.280

4.2.4 Observaciones
Como se puede comprobar, la nueva instalacin tiene poca contribucin a la corriente de cortocircuito y por tanto poco impacto en la red externa, excepto
en su punto de conexin.

PV EL SALVADOR

44

Estudio de Cortocircuito

4.3 Fallas bifsicas a tierra (2FT)


4.3.1 Sin el parque fotovoltaico
Tabla 12: Fallas bifsicas a tierra - sin la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
J
H
H
H
HA
IB
J
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220
220
110
110
110
110
110
220

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
7.837
19.441
7.837
11.083
7.837
8.713
11.939
30.002
11.939
16.393
11.939
13.423
11.939
30.002
11.939
16.393
11.939
13.423
6.518
14.448
6.518
8.417
6.518
6.890
6.518
14.448
6.518
8.417
6.518
6.890
5.593
13.724
5.593
7.794
5.593
6.169
10.869
26.719
10.869
15.371
10.869
12.003
1.098
1.914
1.098
1.420
1.098
1.122
6.156
15.606
6.156
8.378
6.156
6.982
6.156
15.606
6.156
8.378
6.156
6.982
9.119
21.910
9.119
12.397
9.119
9.932
9.119
21.910
9.119
12.397
9.119
9.932
4.396
9.977
4.396
6.217
4.396
4.678
2.861
3.296
8.741
8.741
5.633

5.765
6.946
22.389
22.389
13.828

2.861
3.296
8.741
8.741
5.633

3.920
4.584
12.300
12.300
7.841

2.861
3.296
8.741
8.741
5.633

2.970
3.446
10.035
10.035
6.215
45

Estudio de Cortocircuito

Barra
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
PV EL SALVADOR

Subestacin
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)

Tensin
[kV]
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
2.948
6.181
2.948
2.727
5.461
2.727
1.954
3.660
1.954
2.792
5.590
2.792
6.430
14.947
6.430
2.083
4.641
2.083
2.623
4.520
2.623
1.656
3.003
1.656
2.808
5.087
2.808
10.967
26.989
10.967
8.402
20.789
8.402
8.402
20.789
8.402
10.967
26.989
10.967
9.082
21.813
9.082
3.532
6.884
3.532
5.125
13.150
5.125
5.125
13.150
5.125
2.535
4.958
2.535
0.932
1.956
0.932
0.907
1.508
0.907
3.072
6.313
3.072
6.024
15.190
6.024
3.896
7.460
3.896
4.358
9.345
4.358

Ibasy
[kA]
Ik [kA]
Ith [kA]
4.061
2.948
3.080
3.729
2.727
2.829
2.601
1.954
2.011
3.816
2.792
2.897
8.961
6.430
6.899
2.926
2.083
2.205
3.234
2.623
2.680
2.176
1.656
1.699
3.971
2.808
2.881
15.510
10.967
12.121
11.497
8.402
9.323
11.497
8.402
9.323
15.510
10.967
12.121
12.349
9.082
9.889
4.995
3.532
3.651
7.105
5.125
5.897
7.105
5.125
5.897
3.434
2.535
2.622
1.309
0.932
0.974
1.163
0.907
0.924
4.238
3.072
3.199
8.235
6.024
6.795
5.333
3.896
4.019
6.163
4.358
4.573
46

Estudio de Cortocircuito

Barra
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla

Subestacin
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV

Tensin
[kV]
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
4.480
9.669
4.480
1.219
2.047
1.219
1.350
2.278
1.350
2.047
3.860
2.047
3.751
6.885
3.751
2.585
4.529
2.585

Ibasy
[kA]
Ik [kA]
Ith [kA]
6.336
4.480
4.707
1.573
1.219
1.243
1.748
1.350
1.377
2.736
2.047
2.108
4.943
3.751
3.853
3.351
2.585
2.644

4.3.2 Con el parque fotovoltaico


Tabla 13: Fallas bifsicas a tierra - con la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
7.837
19.441
7.837
11.083
7.837
8.713
11.942
30.006
11.942
16.398
11.942
13.425
11.942
30.006
11.942
16.398
11.942
13.425
6.518
14.448
6.518
8.417
6.518
6.891
6.518
14.448
6.518
8.417
6.518
6.891
5.593
13.724
5.593
7.794
5.593
6.169
10.873
26.724
10.873
15.376
10.873
12.006
1.098
1.914
1.098
1.420
1.098
1.122
6.159
15.611
6.159
8.381
6.159
6.984
6.159
15.611
6.159
8.381
6.159
6.984
9.130
21.928
9.130
12.412
9.130
9.942
47

Estudio de Cortocircuito

Barra
J2
J
H
H
H
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
PV EL SALVADOR

Subestacin
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo

Tensin
[kV]

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
220
9.130
21.928
9.130
12.412
9.130
9.942
220
4.396
9.977
4.396
6.217
4.396
4.678
110
110
2.862
5.765
2.862
3.921
2.862
2.971
110
3.296
6.947
3.296
4.585
3.296
3.447
110
8.741
22.389
8.741
12.300
8.741
10.035
110
8.741
22.389
8.741
12.300
8.741
10.035
220
5.633
13.828
5.633
7.841
5.633
6.215
110
2.948
6.181
2.948
4.061
2.948
3.080
110
2.728
5.461
2.728
3.730
2.728
2.829
110
1.954
3.660
1.954
2.601
1.954
2.011
110
2.793
5.591
2.793
3.817
2.793
2.897
220
6.435
14.955
6.435
8.969
6.435
6.904
220
2.086
4.648
2.086
2.931
2.086
2.209
110
2.623
4.520
2.623
3.234
2.623
2.680
110
1.656
3.003
1.656
2.176
1.656
1.699
110
2.809
5.087
2.809
3.972
2.809
2.881
220
10.971
26.994
10.971
15.515
10.971
12.124
110
8.403
20.790
8.403
11.498
8.403
9.324
110
8.403
20.790
8.403
11.498
8.403
9.324
220
10.971
26.994
10.971
15.515
10.971
12.124
220
9.093
21.831
9.093
12.364
9.093
9.899
110
3.532
6.885
3.532
4.996
3.532
3.652
220
5.145
13.199
5.145
7.133
5.145
5.918
48

Estudio de Cortocircuito

Barra
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
PV EL SALVADOR

Subestacin
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

Tensin
[kV]
220
110
110
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110

Ikss [kA] Ip [kA]


Ib [kA]
5.145
13.199
5.145
2.536
4.958
2.536
0.932
1.956
0.932
0.910
1.510
0.910
3.073
6.313
3.073
6.026
15.194
6.026
3.896
7.460
3.896
4.358
9.345
4.358
4.480
9.669
4.480
1.224
2.051
1.224
1.356
2.283
1.356
2.047
3.860
2.047
3.752
6.885
3.752
2.585
4.529
2.585
3.888
7.441
3.888
5.633
13.828
5.633
5.633
13.828
5.633
1.616
2.663
1.616
5.630
13.821
5.630
2.927
6.440
2.927
2.409
5.554
2.409
3.922
7.844
3.922
2.933
6.712
2.933
3.258
6.782
3.258

Ibasy
[kA]
Ik [kA]
Ith [kA]
7.133
5.145
5.918
3.435
2.536
2.622
1.309
0.932
0.974
1.167
0.910
0.927
4.239
3.073
3.200
8.238
6.026
6.797
5.333
3.896
4.019
6.163
4.358
4.573
6.336
4.480
4.707
1.580
1.224
1.248
1.756
1.356
1.383
2.736
2.047
2.108
4.943
3.752
3.853
3.352
2.585
2.645
5.321
3.888
4.011
7.841
5.633
6.215
7.841
5.633
6.215
1.988
1.616
1.646
7.837
5.630
6.212
4.083
2.927
3.088
3.406
2.409
2.577
5.546
3.922
4.067
4.149
2.933
3.130
4.607
3.258
3.399
49

Estudio de Cortocircuito

Barra
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

Subestacin
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
220
5.633
13.828
5.633
7.841
5.633
6.215
110
110
3.036
6.858
3.036
4.284
3.036
3.226
110
3.736
6.272
3.736
4.443
3.736
3.810
23
11.100
25.079
11.100
14.523
11.100
11.797

4.3.3 Comparacin
Tabla 14: Fallas bifsicas a tierra - comparacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220

Ibasy
Ikss [kA]
Ip [kA] Ib [kA] [kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.004
0.003
0.005
0.003
0.002
0.003
0.004
0.003
0.005
0.003
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.004
0.005
0.004
0.005
0.004
0.003
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.005
0.002
0.003
0.002
0.002
0.002
0.005
0.002
0.003
0.002
0.002
0.011
0.018
0.011
0.015
0.011
0.010
0.011
0.018
0.011
0.015
0.011
0.010
50

Estudio de Cortocircuito

Barra
J
H
H
H
HA
IB
J
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
PV EL SALVADOR

Subestacin
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo

Tensin
[kV]
220
110
110
110
110
110
220
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.006
0.008
0.006
0.004
0.007
0.004
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.004
0.005
0.004
0.001
0.001
0.001
0.001
0.001
0.001
0.004
0.005
0.004
0.011
0.018
0.011
0.001
0.001
0.001
0.020
0.049
0.020
0.020
0.049
0.020

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.000
0.000
0.000
0.000
0.000
0.001
0.000
0.000
0.008
0.006
0.005
0.005
0.004
0.004
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.000
0.000
0.005
0.004
0.003
0.001
0.001
0.001
0.001
0.001
0.001
0.005
0.004
0.003
0.015
0.011
0.010
0.001
0.001
0.001
0.028
0.020
0.022
0.028
0.020
0.022
51

Estudio de Cortocircuito

Barra
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
PV EL SALVADOR

Subestacin
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

Tensin
[kV]
110
110
110
110
110
110
110
110
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.003
0.001
0.001
0.001
0.002
0.005
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.005
0.004
0.005
0.006
0.005
0.006
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
3.888
7.441
3.888
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000

Ibasy
[kA]
Ik [kA] Ith [kA]
0.001
0.000
0.000
0.000
0.000
0.000
0.003
0.003
0.003
0.001
0.001
0.001
0.003
0.002
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.006
0.005
0.005
0.008
0.006
0.006
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
5.321
3.888
4.011
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
52

Estudio de Cortocircuito

Barra
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

Subestacin
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
23

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
11.100
25.079
11.100

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
14.523
11.100
11.797

4.3.4 Observaciones
Como se puede comprobar, la nueva instalacin tiene poca contribucin a la corriente de cortocircuito y por tanto poco impacto en la red externa, excepto
en su punto de conexin.

PV EL SALVADOR

53

Estudio de Cortocircuito

4.4 Fallas monofsicas a tierra (1FT)


4.4.1 Sin el parque fotovoltaico
Tabla 15: Fallas monofsicas a tierra - sin la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
J
H
H
H
HA
IB
J
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220
220
110
110
110
110
110
220

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
7.941
19.697
7.941
11.230
7.941
8.828
12.268
30.830
12.268
17.350
12.268
13.793
12.268
30.830
12.268
17.350
12.268
13.793
6.537
14.489
6.537
9.244
6.537
6.910
6.537
14.489
6.537
9.244
6.537
6.910
5.593
13.725
5.593
7.910
5.593
6.169
10.967
26.959
10.967
15.509
10.967
12.112
0.807
1.407
0.807
1.141
0.807
0.825
6.234
15.803
6.234
8.816
6.234
7.070
6.234
15.803
6.234
8.816
6.234
7.070
9.128
21.932
9.128
12.910
9.128
9.941
9.128
21.932
9.128
12.910
9.128
9.941
3.567
8.096
3.567
5.044
3.567
3.796
2.582
3.136
8.805
8.805
5.636

5.202
6.610
22.553
22.553
13.837

2.582
3.136
8.805
8.805
5.636

3.651
4.435
12.452
12.452
7.971

2.582
3.136
8.805
8.805
5.636

2.680
3.279
10.108
10.108
6.219
54

Estudio de Cortocircuito

Barra
H
H
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
PV EL SALVADOR

Subestacin
S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)

Tensin
[kV]
110
110
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
2.192
4.595
2.192
2.439
4.884
2.439
1.585
2.969
1.585
2.500
5.005
2.500
5.981
13.905
5.981
1.474
3.284
1.474
1.884
3.247
1.884
1.293
2.345
1.293
2.693
4.878
2.693
11.091
27.294
11.091
8.608
21.298
8.608
8.608
21.298
8.608
11.091
27.294
11.091
9.089
21.829
9.089
3.576
6.971
3.576
5.060
12.982
5.060
5.060
12.982
5.060
2.201
4.305
2.201
0.643
1.350
0.643
0.646
1.073
0.646
2.841
5.837
2.841
6.131
15.459
6.131
3.342
6.400
3.342
4.164
8.928
4.164

Ibasy
[kA]
Ik [kA]
Ith [kA]
3.099
2.192
2.290
3.449
2.439
2.530
2.242
1.585
1.631
3.536
2.500
2.593
8.459
5.981
6.418
2.084
1.474
1.560
2.665
1.884
1.925
1.829
1.293
1.327
3.808
2.693
2.763
15.685
11.091
12.258
12.174
8.608
9.552
12.174
8.608
9.552
15.685
11.091
12.258
12.853
9.089
9.896
5.057
3.576
3.697
7.156
5.060
5.821
7.156
5.060
5.821
3.113
2.201
2.276
0.910
0.643
0.672
0.913
0.646
0.658
4.017
2.841
2.958
8.670
6.131
6.916
4.726
3.342
3.448
5.888
4.164
4.369
55

Estudio de Cortocircuito

Barra
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla

Subestacin
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV

Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV

Paposo - Diego de Almagro 1 220kV


Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

PV EL SALVADOR

Tensin
[kV]
110
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
4.292
9.264
4.292
0.882
1.481
0.882
0.984
1.660
0.984
1.688
3.183
1.688
2.912
5.344
2.912
1.895
3.321
1.895

Ibasy
[kA]
Ik [kA]
Ith [kA]
6.070
4.292
4.510
1.247
0.882
0.899
1.392
0.984
1.004
2.387
1.688
1.738
4.118
2.912
2.991
2.680
1.895
1.939

5.636
5.636
1.189
5.634
2.216
1.684
3.610
2.096
3.051
5.636

13.837
13.837
1.958
13.830
4.878
3.883
7.220
4.796
6.353
13.837

5.636
5.636
1.189
5.634
2.216
1.684
3.610
2.096
3.051
5.636

7.971
7.971
1.681
7.968
3.134
2.381
5.105
2.964
4.315
7.971

5.636
5.636
1.189
5.634
2.216
1.684
3.610
2.096
3.051
5.636

6.219
6.219
1.211
6.216
2.339
1.801
3.744
2.236
3.184
6.219

2.684
3.162

6.062
5.308

2.684
3.162

3.795
4.471

2.684
3.162

2.852
3.224

56

Estudio de Cortocircuito

4.4.2 Con el parque fotovoltaico


Tabla 16: Fallas monofsicas a tierra con la nueva instalacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
J
H
H
H
HA
IB
J
H
H
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220
220
110
110
110
110
110
220
110
110

Ibasy
Ikss [kA] Ip [kA]
Ib [kA]
[kA]
Ik [kA]
Ith [kA]
7.941
19.697
7.941
11.230
7.941
8.828
12.270
30.830
12.270
17.353
12.270
13.793
12.270
30.830
12.270
17.353
12.270
13.793
6.537
14.489
6.537
9.244
6.537
6.911
6.537
14.489
6.537
9.244
6.537
6.911
5.593
13.725
5.593
7.910
5.593
6.169
10.969
26.959
10.969
15.512
10.969
12.112
0.807
1.407
0.807
1.141
0.807
0.825
6.235
15.805
6.235
8.818
6.235
7.071
6.235
15.805
6.235
8.818
6.235
7.071
9.134
21.937
9.134
12.918
9.134
9.946
9.134
21.937
9.134
12.918
9.134
9.946
3.573
8.104
3.573
5.053
3.573
3.801
2.582
3.136
8.805
8.805
5.636
2.201
2.439

5.202
6.610
22.553
22.553
13.837
4.595
4.884

2.582
3.136
8.805
8.805
5.636
2.201
2.439

3.652
4.435
12.452
12.452
7.971
3.113
3.450

2.582
3.136
8.805
8.805
5.636
2.201
2.439

2.681
3.280
10.108
10.108
6.219
2.298
2.530
57

Estudio de Cortocircuito

Barra
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
PV EL SALVADOR

Subestacin
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV

Tensin
[kV]
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110
110
110

Ikss [kA] Ip [kA]


Ib [kA]
1.585
2.969
1.585
2.500
5.005
2.500
5.984
13.906
5.984
1.475
3.285
1.475
1.884
3.247
1.884
1.293
2.345
1.293
2.693
4.878
2.693
11.093
27.294
11.093
8.609
21.299
8.609
8.609
21.299
8.609
11.093
27.294
11.093
9.094
21.835
9.094
3.576
6.971
3.576
5.070
13.006
5.070
5.070
13.006
5.070
2.202
4.304
2.202
0.643
1.350
0.643
0.646
1.073
0.646
2.841
5.837
2.841
6.132
15.461
6.132
3.342
6.400
3.342
4.164
8.928
4.164
4.292
9.264
4.292
0.883
1.480
0.883

Ibasy
[kA]
Ik [kA]
Ith [kA]
2.242
1.585
1.631
3.536
2.500
2.594
8.462
5.984
6.420
2.086
1.475
1.561
2.665
1.884
1.925
1.829
1.293
1.327
3.809
2.693
2.763
15.688
11.093
12.259
12.175
8.609
9.552
12.175
8.609
9.552
15.688
11.093
12.259
12.861
9.094
9.901
5.058
3.576
3.697
7.170
5.070
5.832
7.170
5.070
5.832
3.113
2.202
2.277
0.910
0.643
0.672
0.914
0.646
0.659
4.018
2.841
2.958
8.672
6.132
6.916
4.726
3.342
3.448
5.888
4.164
4.369
6.070
4.292
4.510
1.249
0.883
0.900
58

Estudio de Cortocircuito

Barra
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

PV EL SALVADOR

Subestacin
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110
110
23

Ikss [kA] Ip [kA]


Ib [kA]
0.986
1.660
0.986
1.688
3.183
1.688
2.912
5.344
2.912
1.895
3.321
1.895
3.333
6.379
3.333
5.636
13.837
5.636
5.636
13.837
5.636
1.189
1.958
1.189
5.634
13.830
5.634
2.217
4.878
2.217
1.684
3.883
1.684
3.610
7.220
3.610
2.096
4.796
2.096
3.078
6.389
3.078
5.636
13.837
5.636
2.684
3.162
11.085

6.062
5.308
25.046

2.684
3.162
11.085

Ibasy
[kA]
Ik [kA]
Ith [kA]
1.395
0.986
1.006
2.387
1.688
1.738
4.118
2.912
2.991
2.680
1.895
1.939
4.714
3.333
3.438
7.971
5.636
6.219
7.971
5.636
6.219
1.681
1.189
1.211
7.968
5.634
6.216
3.135
2.217
2.339
2.381
1.684
1.801
5.105
3.610
3.744
2.964
2.096
2.236
4.353
3.078
3.210
7.971
5.636
6.219
3.796
4.472
15.677

2.684
3.162
11.085

2.852
3.224
11.781

59

Estudio de Cortocircuito

4.4.3 Comparacin
Tabla 17: Fallas monofsicas a tierra - comparacin

Barra
H
J1
J2
H1
H2
J
J
H
H2
H1
J1
J2
J
H
H
H
HA
IB
J
H
H
PV EL SALVADOR

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco
Central Huasco
Central San Lorenzo de Almagro
S/E Agrosuper
S/E Caldera
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Carrera Pinto
S/E Cenizas
S/E Cerrillos
S/E Copiapo
S/E Diego de Almagro
S/E Diego de Almagro
S/E Diego de Almagro
S/E El Salado
S/E Hernn Fuentes

Tensin
[kV]
110
220
220
110
110
220
220
110
110
110
220
220
220
110
110
110
110
110
220
110
110

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.002
0.000
0.002
0.002
0.000
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.000
0.002
0.000
0.000
0.000
0.001
0.002
0.001
0.001
0.002
0.001
0.006
0.006
0.006
0.006
0.006
0.006
0.006
0.008
0.006
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.010
0.000
0.010
0.000
0.000
0.000

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.003
0.002
0.000
0.003
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.001
0.000
0.000
0.000
0.002
0.001
0.001
0.002
0.001
0.001
0.008
0.006
0.004
0.008
0.006
0.004
0.008
0.006
0.005
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.014
0.010
0.008
0.000
0.000
0.000
60

Estudio de Cortocircuito

Barra
H
H
J
J
H
H
H
J2
H1
H2
J1
J
Paipote
J1
J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
PV EL SALVADOR

Subestacin
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa
S/E Los Colorados (CMP)
S/E Los Loros
S/E Magnetita
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin
S/E Paipote
S/E Paposo
S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador 110kV
Diego de Almagro - Potrerillos 110(1)
Diego de Almagro - Potrerillos 110(2)
Diego de Almagro - Tal Tal 110 kV

Tensin
[kV]
110
110
220
220
110
110
110
220
110
110
220
220
110
220
220
110
110
110
110
110
110
110
110
110

Ikss [kA]
Ip [kA] Ib [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.001
0.002
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.000
0.002
0.001
0.000
0.001
0.001
0.000
0.001
0.002
0.000
0.002
0.006
0.006
0.006
0.000
0.000
0.000
0.010
0.024
0.010
0.010
0.024
0.010
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.000
0.001
0.000
0.000
0.000
0.001
0.002
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.001
-0.001
0.001

Ibasy
[kA]
Ik [kA] Ith [kA]
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.002
0.001
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.003
0.002
0.001
0.001
0.001
0.000
0.001
0.001
0.000
0.003
0.002
0.001
0.008
0.006
0.004
0.001
0.000
0.000
0.014
0.010
0.010
0.014
0.010
0.010
0.000
0.000
0.000
0.000
0.000
0.000
0.001
0.001
0.001
0.000
0.000
0.000
0.002
0.001
0.001
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.002
0.001
0.001
61

Estudio de Cortocircuito

Barra
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1
Reactor D. de Almagro 2
Alto del Carmen 110 kV
Aux. D. Almagro J
CNN
Caserones
El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNAL

Subestacin
Diego de Almagro - Tal Tal 110 kV
Hernn Fuentes - Caldera 110kV
Maitencillo - Cardones 110 kV
Maitencillo - Cardones 110 kV
PV EL SALVADOR
Paposo - Diego de Almagro 1 220kV
Paposo - Diego de Almagro 2 220kV
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
PV EL SALVADOR

Tensin
[kV]
110
110
110
110
110
220
220
110
220
220
220
110
220
110
220
110
110
110
23

Ikss [kA]
Ip [kA] Ib [kA]
0.002
-0.001
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
3.333
6.379
3.333
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.027
0.036
0.027
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
11.085
25.046
11.085

Ibasy
[kA]
Ik [kA] Ith [kA]
0.003
0.002
0.002
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
4.714
3.333
3.438
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.038
0.027
0.026
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
0.000
15.677
11.085
11.781

4.4.1 Observaciones
Como se puede comprobar, la nueva instalacin tiene poca contribucin a la corriente de cortocircuito y por tanto poco impacto en la red externa, excepto
en su punto de conexin.

PV EL SALVADOR

62

Estudio de Cortocircuito

5 Verificacin de la capacidad de los interruptores


Un interruptor estar adecuadamente dimensionado si satisface las condiciones de corriente dadas en [ANEXO 3] que ya
se han especificado anteriormente. Las mayores corrientes se determinan como el mayor valor de los cuatro
cortocircuitos calculados, tal y como especificado en el procedimiento:

Los valores mximos se incluyen en las siguientes subsecciones.

5.1 Valores Mximos Obtenidos en las Barras Consideradas


5.1.1 Con la nueva instalacin fotovoltaica
Tabla 18: Corrientes mximas obtenidas con la nueva instalacin fotovoltaica conectada
Ip [kA]

Ib [kA]

Ik [kA]

Ik2t

Ith
[kA]

Subestacin

Central Emelda

110

7.941

19.697

7.941

11.230

7.941

7.567

8.828

J1

Central Guacolda

220

12.270

30.830

12.270

17.353

12.27

18.066

13.793

J2

Central Guacolda

220

12.270

30.830

12.270

17.353

12.27

18.066

13.793

H1

Central Huasco

110

6.537

14.489

6.537

9.244

6.537

5.128

6.911

H2

110

6.537

14.489

6.537

9.244

6.537

5.128

6.911

Central Huasco
Central San Lorenzo de
Almagro

220

5.593

13.725

5.593

7.910

5.593

3.754

6.169

S/E Agrosuper

220

10.969

26.959

10.969

15.512

10.969

14.438

12.112

S/E Caldera

110

1.163

2.027

1.163

1.422

1.163

0.162

1.189

H2

S/E Cardones

110

6.235

15.805

6.235

8.818

6.235

4.665

7.071

H1

S/E Cardones

110

6.235

15.805

6.235

8.818

6.235

4.665

7.071

J1

S/E Cardones

220

9.134

21.937

9.134

12.918

9.134

10.012

9.946

S/E Cardones

154

9.134

21.937

9.134

12.918

9.134

10.012

9.946

J2

S/E Cardones

220

8.603

20.662

8.418

8.905

8.488

8.646

9.368

S/E Carrera Pinto

220

4.896

11.105

4.885

4.965

4.795

2.759

5.209

S/E Cenizas

110

2.862

5.765

2.862

3.921

2.862

0.983

2.971

S/E Cerrillos

110

3.296

6.947

3.296

4.585

3.296

1.304

3.447

B1

S/E Chacayes

110

8.805

22.553

8.805

12.452

8.805

9.303

10.108

B2

S/E Chacayes

110

8.805

22.553

8.805

12.452

8.805

9.303

10.108

B1

S/E Chacayes(1)

110

5.636

13.837

5.636

7.971

5.636

3.812

6.219

PV EL SALVADOR

Tensin [kV] Ikss [kA]

Ibasy
[kA]

Barra

63

Estudio de Cortocircuito

B2

S/E Chacayes(1)

110

2.948

6.181

2.948

4.061

2.948

1.043

3.08

S/E Copiapo

110

3.380

7.124

3.380

3.730

3.38

1.371

3.535

HA

S/E Diego de Almagro

110

7.696

19.660

7.436

8.881

7.337

6.460

8.806

IB

S/E Diego de Almagro

110

7.696

19.660

7.436

8.881

7.337

6.460

8.806

S/E Diego de Almagro

220

6.435

14.955

6.435

8.969

6.435

4.969

6.904

S/E El Salado

110

3.324

6.939

3.321

3.328

3.169

1.205

3.47

S/E Hernn Fuentes

110

2.847

5.701

2.847

3.330

2.847

0.973

2.953

S/E Impulsion

110

2.065

3.868

2.065

2.176

2.065

0.512

2.125

S/E Kozan

110

2.913

5.831

2.913

3.972

2.913

1.018

3.022

S/E La Candelaria

220

11.093

27.294

11.093

15.688

11.093

14.767

12.259

S/E La Coipa

220

8.609

21.299

8.609

12.175

8.609

8.894

9.552

S/E Los Colorados (CMP)

110

8.609

21.299

8.609

12.175

8.609

8.894

9.552

S/E Los Loros

110

11.093

27.294

11.093

15.688

11.093

14.767

12.259

S/E Magnetita

110

9.094

21.835

9.094

12.861

9.094

9.924

9.901

J2

S/E Maitencillo

220

10.723

26.384

10.519

11.519

10.565

13.394

11.85

H1

S/E Maitencillo

110

7.703

19.058

7.638

7.979

7.604

6.938

8.547

H2

S/E Maitencillo

110

7.703

19.058

7.638

7.979

7.604

6.938

8.547

J1

S/E Maitencillo

220

10.723

26.384

10.519

11.519

10.565

13.394

11.85

S/E Medellin

220

8.578

20.594

8.394

8.876

8.463

8.595

9.338

Paipote

S/E Paipote

110

3.128

6.098

3.128

3.129

3.128

1.174

3.234

J1

S/E Paposo

220

4.601

11.803

4.480

5.375

4.527

2.459

5.293

J2

S/E Paposo

220

6.132

15.461

6.132

8.672

6.132

4.512

6.916

S/E Plantas

110

3.896

7.460

3.896

5.333

3.896

1.821

4.019

S/E Refugio

110

4.358

9.345

4.358

6.163

4.358

2.279

4.573

S/E Taltal

110

4.480

9.669

4.480

6.336

4.48

2.408

4.707

S/E Tierra Amarrilla

110

3.181

6.534

3.181

3.183

3.181

1.214

3.312

Torre 2 (Los Lirios)

Cardones - Planta 110 kV


Diego de Almagro - El
Salvador 110kV
Diego de Almagro Potrerillos 110(1)
Diego de Almagro Potrerillos 110(2)
Diego de Almagro - Tal
Tal 110 kV
Diego de Almagro - Tal
Tal 110 kV
Hernn Fuentes - Caldera
110kV
Maitencillo - Cardones
110 kV
Maitencillo - Cardones
110 kV

110

4.934

12.441

4.934

5.236

4.934

2.921

5.566

110

4.510

8.851

4.487

4.488

4.156

2.073

4.666

110

4.410

9.427

4.386

4.943

4.165

2.082

4.624

110

4.511

9.705

4.483

4.500

4.262

2.180

4.736

110

3.888

7.441

3.888

5.321

3.888

1.814

4.011

110

5.636

13.837

5.636

7.971

5.636

3.812

6.219

110

5.636

13.837

5.636

7.971

5.636

3.812

6.219

110

3.973

7.292

3.973

3.974

3.973

1.894

4.081

110

5.634

13.830

5.634

7.968

5.634

3.809

6.216

PV EL SALVADOR
Paposo - Diego de
Almagro 1 220kV

110

4.502

8.831

4.479

4.480

4.148

2.065

4.657

220

5.523

13.565

5.398

5.838

5.371

3.462

6.096

Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro
Tap Castilla
T_PV_El Salvador HV
Reactor D. de Almagro 1

PV EL SALVADOR

Ip [kA]

Ib [kA]

Ik [kA]

Ik2t

Ith
[kA]

Subestacin

TapOff PV El Salvador

Tensin [kV] Ikss [kA]

Ibasy
[kA]

Barra

64

Estudio de Cortocircuito

Barra
Reactor D. de Almagro 2

Subestacin
Paposo - Diego de
Almagro 2 220kV

Alto del Carmen 110 kV

Tensin [kV] Ikss [kA]

Ip [kA]

Ibasy
[kA]

Ib [kA]

Ik [kA]

Ith
[kA]

Ik2t

220

5.523

13.565

5.398

5.838

5.371

3.462

6.096

01-Atacama

110

2.933

6.712

2.933

4.149

2.933

1.032

3.13

Aux. D. Almagro J

01-Atacama

220

5.521

13.559

5.396

5.835

5.369

3.459

6.093

CNN

01-Atacama

220

5.636

13.837

5.636

7.971

5.636

3.812

6.219

Caserones

01-Atacama

220

2.661

6.137

2.661

2.726

2.661

0.850

2.847

El Salvador 110 kV

01-Atacama

110

4.363

8.742

4.342

4.345

4.09

2.007

4.526

Jorquera

01-Atacama

220

3.736

7.415

3.736

4.477

3.736

1.675

3.81

Potrerillos 110 kV

01-Atacama

110

11.100

25.079

11.100

15.677

11.1

14.785

11.797

Reactor D. Almagro

01-Atacama

220

5.523

13.565

5.398

5.838

5.371

3.462

6.096

Ro Huasco 110

01-Atacama

110

0.000

0.000

0.000

0.000

0.000

Travesa

01-Atacama

110

3.251

7.342

3.251

3.275

3.251

1.268

3.454

Vallenar 110 kV
TF_PV_ELSALVADOR_INTERNA
L

01-Atacama

110

3.654

6.135

3.654

3.654

3.654

1.602

3.726

23

10.980

25.189

10.980

11.210

10.98

14.467

11.726

PV EL SALVADOR

5.1.2 Sin la nueva instalacin fotovoltaica


Tabla 19: Corrientes mximas obtenidas sin la nueva instalacin fotovoltaica conectada
Barra
H
J1
J2
H1
H2

Subestacin
Central Emelda
Central Guacolda
Central Guacolda
Central Huasco

Tensin [kV]
110
220
220
110
110

Central Huasco
Central San Lorenzo de
Almagro

S/E Agrosuper

220

S/E Caldera

110

H2
H1
J1
A
J2

S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones
S/E Cardones

220

110
110
220
154
220

Ikss
[kA]

Ibasy
Ip [kA] Ib [kA] [kA]

7.941 19.697

7.941

12.268 30.830 12.268


12.268 30.830 12.268
6.537 14.489
6.537 14.489
5.593 13.725

6.537
6.537
5.593

10.967 26.959 10.967


1.162

2.027

6.234 15.803
6.234 15.803
9.128 21.932
9.128 21.932
8.588 20.634

1.162
6.234
6.234
9.128
9.128
8.403

11.230

Ik [kA]
7.941

17.350 12.268
17.350 12.268
9.244
9.244
7.910

6.537
6.537
5.593

15.509 10.967
1.422
8.816
8.816
12.910
12.910
8.893

1.162
6.234
6.234
9.128
9.128
8.526

S/E Carrera Pinto

220

4.863 11.038

4.851

4.932

4.839

S/E Cenizas

110

2.861

2.861

3.920

2.861

H
B1
B2
B1

PV EL SALVADOR

S/E Cerrillos
S/E Chacayes
S/E Chacayes
S/E Chacayes(1)

110
110
110
110

3.296

5.765
6.946

8.805 22.553
8.805 22.553
5.636 13.837

3.296
8.805
8.805
5.636

4.584
12.452
12.452
7.971

3.296
8.805
8.805
5.636

Ik2t

Ith [kA]

7.567
18.060
18.060

8.828
13.793
13.793

5.128

6.910

5.128

6.910

3.754
14.433

6.169
12.112

0.162

1.189

4.664

7.070

4.664

7.070

9.998

9.941

9.998

9.941

8.723

9.353

2.810

5.176

0.982

2.970

1.304
9.303
9.303

3.446
10.108
10.108

3.812

6.219

65

Estudio de Cortocircuito

Barra
B2
H
HA

Subestacin
S/E Chacayes(1)
S/E Copiapo
S/E Diego de Almagro

Tensin [kV]
110
110
110

Ikss
[kA]
2.948
3.379

Ibasy
Ip [kA] Ib [kA] [kA]
6.181
7.122

7.352 18.832

2.948
3.379
7.093

4.061
3.729
8.538

Ik [kA]
2.948
3.379
7.337

IB

S/E Diego de Almagro

110

7.352 18.832

7.093

8.538

7.337

S/E Diego de Almagro

220

6.430 14.947

6.430

8.961

6.430

H
H
H
H
J
J

S/E El Salado
S/E Hernn Fuentes
S/E Impulsion
S/E Kozan
S/E La Candelaria
S/E La Coipa

110
110
110
110
220
220

S/E Los Colorados (CMP)

110

S/E Los Loros

110

S/E Magnetita

110

J2
H1
H2
J1
J

S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Maitencillo
S/E Medellin

220
110
110
220
220

3.260
2.846
2.065
2.912

6.834
5.700
3.867
5.830

3.256
2.846
2.065
2.912

11.091 27.294 11.091


8.608 21.298
8.608 21.298

8.608
8.608

11.091 27.294 11.091


9.089 21.829

9.089

10.717 26.374 10.513


7.702 19.055
7.702 19.055

7.637
7.637

10.717 26.374 10.513


8.563 20.566

8.379

3.263
3.330
2.176
3.971

3.253
2.846
2.065
2.912

15.685 11.091
12.174
12.174

8.608
8.608

15.685 11.091
12.853

9.089

11.517 10.592
7.978
7.978

7.623
7.623

11.517 10.592
8.864

8.500

Paipote

S/E Paipote

110

3.127

6.096

3.127

3.128

3.127

J1

S/E Paposo

220

4.577 11.742

4.455

5.347

4.569

J2
H
H
H
H
Torre 2 (Los Lirios)
TapOff PV El Salvador
Llanta 1
Llanta 2
Tap Las Luces 110 kV
Tap Planta de xidos 110 kV
Tap Impulsin 110 kV
Tap Punta Toro

S/E Paposo
S/E Plantas
S/E Refugio
S/E Taltal
S/E Tierra Amarrilla
Cardones - Planta 110 kV
Diego de Almagro - El Salvador
110kV
Diego de Almagro - Potrerillos
110(1)
Diego de Almagro - Potrerillos
110(2)
Diego de Almagro - Tal Tal 110
kV
Diego de Almagro - Tal Tal 110
kV
Hernn Fuentes - Caldera
110kV
Maitencillo - Cardones 110 kV

220
110
110
110
110

6.131 15.459
3.896
4.358
4.480
3.180

7.460
9.345
9.669
6.533

6.131
3.896
4.358
4.480
3.180

8.670
5.333
6.163
6.336
3.182

6.131
3.896
4.358
4.480
3.180

110

4.932 12.436

4.932

5.234

4.932

110

4.165

7.975

4.142

4.143

4.156

110

4.247

9.107

4.221

4.943

4.238

110

4.343

9.372

4.313

4.330

4.333

110

1.296

2.177

1.296

1.296

1.296

110

5.636 13.837

5.636

7.971

5.636

110

5.636 13.837

5.636

7.971

5.636

110

3.973

7.292

3.973

3.973

3.973

Tap Castilla

Maitencillo - Cardones 110 kV

110

5.634 13.830

5.634

7.968

5.634

T_PV_El Salvador HV

PV EL SALVADOR
Paposo - Diego de Almagro 1
220kV

110

2.926

6.439

2.926

4.081

2.926

220

5.421 13.308

5.290

5.718

5.406

Reactor D. de Almagro 1
Reactor D. de Almagro 2

PV EL SALVADOR

Paposo - Diego de Almagro 2

220

5.421 13.308

5.290

5.718

5.406

Ik2t

Ith [kA]

1.043

3.080

1.370

3.534

6.460

8.440

6.460

8.440

4.961

6.899

1.270

3.405

0.972

2.953

0.512

2.125

1.018
14.761

3.021
12.258

8.892

9.552

8.892
14.761

9.552
12.258

9.913
13.463

9.896
11.845

6.973

8.546

6.973
13.463

8.546
11.845

8.670

9.324

1.173

3.233

2.505

5.265

4.511

6.916

1.821

4.019

2.279

4.573

2.408

4.707

1.213

3.311

2.919

5.563

2.073

4.296

2.155

4.456

2.253

4.562

0.202

1.322

3.812

6.219

3.812

6.219

1.894

4.081

3.809

6.216

1.027

3.087

3.507

5.981

3.507

5.981

66

Estudio de Cortocircuito

Barra

Subestacin
220kV

Alto del Carmen 110 kV

01-Atacama

Aux. D. Almagro J

01-Atacama

Tensin [kV]

110
220

Ikss
[kA]

2.933

Ibasy
Ip [kA] Ib [kA] [kA]

6.712

5.419 13.302

2.933
5.288

4.148
5.715

Ik [kA]

2.933
5.404

CNN

01-Atacama

220

5.636 13.837

5.636

7.971

5.636

Caserones

01-Atacama

220

2.661

2.661

2.726

2.661

El Salvador 110 kV
Jorquera
Potrerillos 110 kV
Reactor D. Almagro
Ro Huasco 110
Travesa
Vallenar 110 kV

01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama
01-Atacama

TF_PV_ELSALVADOR_INTERNAL PV EL SALVADOR

110
220
110
220
110
110

4.158
3.736
3.206

6.136
8.316
7.414
6.676

5.421 13.308
0.000
3.249

0.000
7.340

4.135
3.736
3.203
5.290
0.000
3.249

4.283
4.477
3.209
5.718
0.000
3.274

4.149
3.736
3.200
5.406
0.000
3.249

110

3.654

6.135

3.654

3.654

3.654

23

0.000

0.000

0.000

0.000

0.000

Ik2t

Ith [kA]

1.032

3.130

3.504

5.978

3.812

6.219

0.850

2.847

2.066

4.312

1.675

3.809

1.229

3.346

3.507

5.981

0.000

0.000

1.267

3.453

1.602

3.726

0.000

0.000

5.2 Resultados de la verificacin de la capacidad de ruptura de los


interruptores
Se incluyen los resultados con la nueva instalacin fotovoltaica conectada.

PV EL SALVADOR

67

Estudio de Cortocircuito

Tabla 20: Verificacin de la capacidad de ruptura de interruptores considerando la nueva instalacin fotovoltaica

Interruptor

Subestacin

Barra

Elemento

IM S/E DIEGO DE ALMAGRO HS

S/E Diego de Almagro

HA

HA-IB

IM S/E DIEGO DE ALMAGRO HT1

S/E Diego de Almagro

IB

Tensin
Nominal [kV]

Corriente
Nominal [A]

Capacidad de
Ruptura
Simtrica [kA]

Capacidad de
Ruptura
Asimtrica [kA]

Capacidad de Cierre
en Cortocircuito
[kA]

Ib sym
max barra
[kA]

Ib asym
max barra
[kA]

Ip max
barra [kA]

I2t max
barra
[kA]

Resultado

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

245

3150

40

50

100

6.4

9.0

15.0

5.0

OK

IM S/E DIEGO DE ALMAGRO J3

S/E Diego de Almagro

D.Almagro-Reactor 220 kV
L2

IM S/E DIEGO DE ALMAGRO H5

S/E Diego de Almagro

HA

Diego de AlmagroPlanta
de xidos 110 kV

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

IM S/E DIEGO DE ALMAGRO H3

S/E Diego de Almagro

IB

Diego de Almagro - Llanta


110kV C2

IM S/E DIEGO DE ALMAGRO HR

S/E Diego de Almagro

HA

HA-IB

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

IM S/E DIEGO DE ALMAGRO J1

S/E Diego de Almagro

Carrera Pinto - Diego de


Almagro 220 kV

245

3150

40

50

80

6.4

9.0

15.0

5.0

OK

D.Almagro-Reactor 220 kV
L2

245

3150

32

40

64

6.4

9.0

15.0

5.0

OK

IM S/E DIEGO DE ALMAGRO JT3

S/E Diego de Almagro

IM S/E DIEGO DE ALMAGRO HT2

S/E Diego de Almagro

HA

IM S/E DIEGO DE ALMAGRO H1

S/E Diego de Almagro

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

HA

Diego de Almagro - El
Salvador

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

Diego de Almagro - Llanta


110kV C1

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

IM S/E DIEGO DE ALMAGRO H2

S/E Diego de Almagro

IB

IM S/E DIEGO DE ALMAGRO JZ1

S/E Diego de Almagro

245

3150

40

50

100

6.4

9.0

15.0

5.0

OK

IM S/E DIEGO DE ALMAGRO HT3

S/E Diego de Almagro

IB

123

2000

32

40

64

7.4

8.9

19.7

6.5

OK

IM S/E DIEGO DE ALMAGRO J4

S/E Diego de Almagro

245

3150

40

50

80

6.4

9.0

15.0

5.0

OK

IM S/E EL SALVADOR H1

01-Atacama

El Salvador 110
kV

Diego de Almagro - El
Salvador

110

800

14.6

S/I

S/I

4.3

4.3

8.7

2.0

OK

IM S/E EL SALVADOR H2

01-Atacama

El Salvador 110
kV

El Salvador - Llanta

110

800

14.6

S/I

S/I

4.3

4.3

8.7

2.0

OK

01-Atacama

El Salvador 110
kV

A-B

115

1200

S/I

S/I

4.3

4.3

8.7

2.0

OK

IM S/E EL SALVADOR HT3

PV EL SALVADOR

S/I

68

Estudio de Cortocircuito

Tensin
Nominal [kV]

Corriente
Nominal [A]

Capacidad de
Ruptura
Simtrica [kA]

Capacidad de
Ruptura
Asimtrica [kA]

Capacidad de Cierre
en Cortocircuito
[kA]

Ib sym
max barra
[kA]

Ib asym
max barra
[kA]

Ip max
barra [kA]

I2t max
barra
[kA]

Interruptor

Subestacin

Barra

Elemento

IM S/E EL SALVADOR HT1

01-Atacama

El Salvador 110
kV

A-B

115

800

75

S/I

S/I

4.3

4.3

8.7

2.0

OK

IM S/E EL SALVADOR H3

01-Atacama

El Salvador 110
kV

El Salvador - Llanta

110

800

14.6

S/I

S/I

4.3

4.3

8.7

2.0

OK

IM S/E EL SALVADOR HT2

01-Atacama

El Salvador 110
kV

A-B

115

800

75

S/I

S/I

4.3

4.3

8.7

2.0

OK

IM S/E POTRERILLOS H3

01-Atacama

Potrerillos 110
kV

Potrerillos - Diego de
Almagro

110

800

14.6

S/I

S/I

11.1

15.7

25.1

14.8

OK

IM S/E POTRERILLOS H2

01-Atacama

Potrerillos 110
kV

Potrerillos - Diego de
Almagro

110

800

14.6

S/I

S/I

11.1

15.7

25.1

14.8

OK

IM S/E POTRERILLOS HT1

01-Atacama

Potrerillos 110
kV

110

800

14.6

S/I

S/I

11.1

15.7

25.1

14.8

OK

IM S/E POTRERILLOS HT2

01-Atacama

Potrerillos 110
kV

110

800

14.6

S/I

S/I

11.1

15.7

25.1

14.8

OK

IM S/E DIEGO DE ALMAGRO H6-LNEAMV

S/E Diego de Almagro

IB

145

3150

40

10

100

7.4

8.9

19.7

6.5

OK

IM S/E El Salado HT1

S/E El Salado

123

3150

40

50

100

3.3

3.3

6.9

1.2

OK

123

3150

40

50

100

7.4

8.9

19.7

6.5

OK

245

3150

135

6.4

9.0

15.0

5.0

OK

110

4000

40

7.4

8.9

19.7

6.5

OK

IM S/E DIEGO DE ALMAGRO H9

S/E Diego de Almagro

HA

IM S/E DIEGO DE ALMAGRO JT6

S/E Diego de Almagro

IM S/E DIEGO DE ALMAGRO H8

PV EL SALVADOR

S/E Diego de Almagro

HA

I. Manto Verde

D.Almagro - El Salado 110


kV

Diego de Almagro - Emelda


110 kV

31.5 (1 seg)
40

10

Resultado

69

Estudio de Cortocircuito

Los detalles del interruptor de la nueva instalacin en el lado 110kV se dan en ANEXO 2 [12]. Los resultados de verificacin de capacidades se incluyen en la tabla siguiente.

Tabla 21: Verificacin de la capacidad de ruptura de interruptores de la nueva instalacin fotovoltaica

Interruptor

Subestacin

Barra

Elemento

Tensin Nominal
[kV]

Corriente Nominal
[A]

Capacidad de Ruptura
Simtrica [kA]

Capacidad de Ruptura
Asimtrica [kA]

Capacidad de Cierre en
Cortocircuito [kA]

Ib sym max
barra [kA]

Ib asym max
barra [kA]

Ip max barra
[kA]

I2t max
barra [kA]

Resultado

52H1

TapOff Planta PV nueva

52H1

123

630

40

65

4.5

4.5

8.8

2.1

OK

PV EL SALVADOR

70

Estudio de Cortocircuito

6 Conclusiones
El objetivo de este estudio era verificar la suficiente capacidad de ruptura de los interruptores, en todas las nuevas
instalaciones y en aquellas existentes en el entorno que pudiesen verse afectadas por la conexin de las nuevas
instalaciones. Se concluye que no se ha detectado ningn problema en los interruptores de las instalaciones cercanas a
la nueva instalacin fotovoltaica.
Con la hiptesis de que la contribucin de los inversores fotovoltaicos del parque fotovoltaico El Salvador a la corriente
de falla es de mximo 1.09 pu (excepto en caso de tensin de secuencia inversa elevada) y como indican los resultados,
la nueva instalacin no tiene un impacto significativo sobre las corrientes de cortocircuito salvo en su propio punto de
conexin.

PV EL SALVADOR

71

Estudio de Cortocircuito

ANEXO 1: Lista de generadores considerados


Tabla 22: Generadores considerados en el estudio de cortocircuito

Generadores considerados
Abanico U1
Abanico U2
Abanico U3
Abanico U4
Abanico U5
Abanico U6
Alfalfal U1
Alfalfal U2
Ancud
Antilhue U1
Antilhue U2
Antuco U1
Antuco U2
Arauco
Arauco U6
Blanco (Aconcagua U1)
Bocamina U1
Bocamina U2
CBB
Callao
Calle Calle U1-U7
Calle Calle U8
Campiche
Candelaria U1
Candelaria U2
Canutillar U1
Canutillar U2
Capullo
Cardones (ex Tierra Amarilla)
Carena
Caete
Celco
Cenizas U1
Cenizas U2
Cenizas U3

PV EL SALVADOR

72

Estudio de Cortocircuito

Generadores considerados
Chacabuquito U1
Chacabuquito U2
Chacabuquito U3
Chacabuquito U4
Chacayes U1
Chacayes U2
Chiburgo U1
Chiburgo U2
Chilo
Cholgun
Chufqun
Chuyaca U1-U4
Chuyaca U5-U6
Chuyaca U7-U8
Cipreses U1
Cipreses U2
Cipreses U3
Colbn U1
Colbn U2
Colihues U1
Colihues U2
Collipulli
Colmito
Comasa
Concn U1
Concn U2 y U3
Condensador Sincrnico Concepcin U1
Condensador Sincrnico Concepcin U2
Confluencia U1
Confluencia U2
Constitucin 2A
Constitucin 2B
Constitucin U1
Coronel
Coya
Curacautin U1-U3
Curacautin U2
Curauma U1

PV EL SALVADOR

73

Estudio de Cortocircuito

Generadores considerados
Curauma U2 y U3
Curillinque
DS1
DS2
Dega
Diego de Almagro U1
Diego de Almagro U2
EPSA U1
EPSA U2
EPSA U3
El Manzano
El Pen N1
El Pen N2
El Pen N3
El Pen N4
El Toro U1
El Toro U2
El Toro U3
El Toro U4
El Totoral U1 y U2
El Totoral U3
El Volcn
Emelda U1
Emelda U2
Energa Pacfico
Energa Verde U1
Energa Verde U2
Esperanza U1
Espinos N1
Espinos N2
Espinos N3
Espinos N4
Espinos N5
FPC
FPC U2
Florida
Guacolda U1
Guacolda U2

PV EL SALVADOR

74

Estudio de Cortocircuito

Generadores considerados
Guacolda U3
Guacolda U4
Guayacn U1-U2
Horcones
Hornitos
Huasco U1
Huasco U2
Huasco U3
Huasco U4
Huasco U5
Isla U1
Isla U2
Juncal (Aconcagua U2)
La Higuera U1
La Higuera U2
Laguna Verde TG
Laguna Verde U1
Laguna Verde U2
Laja (Energa Verde)
Laja 1A
Laja 1B
Laja 2
Laja 3
Laja 4
Las Nalcas
Las Vegas U1 y U2
Lebu
Licanten
Licn
Linares Norte
Lircay U1
Lircay U2
Loma Alta
Loma Los Colorados I (x4)
Loma Los Colorados II (x11)
Los Molles U1
Los Molles U2
Los Pinos

PV EL SALVADOR

75

Estudio de Cortocircuito

Generadores considerados
Los Quilos U1
Los Quilos U2
Los Quilos U3
Los Sauces
Los Vientos
Machicura U1
Machicura U2
Maitenes Aux. U1-U2
Maitenes U1-U2-U3
Mallarauco
Mampil U1
Mampil U2
Mariposas
Masisa
Monte Patria U1 y U2
Monte Patria U3 a U8
Nehuenco U1 TG
Nehuenco U1 TV
Nehuenco U2 TG
Nehuenco U2 TV
Nehuenco U3
Newen
Nueva Aldea U1
Nueva Aldea U2
Nueva Aldea U3
Nueva Aldea U4
Nueva Renca TG
Nueva Renca TV
Nueva Ventanas
Ojos de Agua
Olivos N1
Olivos N2
Olivos N3
Olivos N4
Orafti
Pacfico 1
Pacfico 2
Pacfico 3

PV EL SALVADOR

76

Estudio de Cortocircuito

Generadores considerados
Palmucho
Pangue U1
Pangue U2
Pehuenche U1
Pehuenche U2
Pelohun
PetroPower
Peuchen U1
Peuchen U2
Pilmaiquen U1
Pilmaiquen U2
Pilmaiquen U3
Pilmaiquen U4
Pilmaiquen U5
Placilla U1 y U2
Placilla U3
Providencia U1
Providencia U2
Pullinque U1
Pullinque U2
Pullinque U3
Punitaqui
Punta Colorada TG
Quelln II
Queltehues U1
Queltehues U2
Queltehues U3
Quilleco U1
Quilleco U2
Quintay U1 y U2
Quintay U3
Quintero TG1A
Quintero TG1B
Ralco U1
Ralco U2
Rapel U1
Rapel U2
Rapel U3

PV EL SALVADOR

77

Estudio de Cortocircuito

Generadores considerados
Rapel U4
Rapel U5
Renaico
Renca Carbon U1-U2
Rucatayo
Rucue U1
Rucue U2
Ro Huasco
San Clemente
San Francisco de Mostazal
San Gregorio
San Ignacio
San Isidro U1 TG
San Isidro U1 TV
San Isidro U2 TG
San Isidro U2 TV
San Lorenzo U1
San Lorenzo U2
Santa Fe Energa
Santa F 2
Santa F 3
Santa Lidia
Santa Marta
Santa Mara
Sauzal U1
Sauzal U2
Sauzal U3
Sauzalito
Taltal U1
Taltal U2
Teno N1
Teno N2
Teno N3
Termopacifico N1
Termopacifico N2
Termopacifico N3
Termopacifico N4
Trapen N1

PV EL SALVADOR

78

Estudio de Cortocircuito

Generadores considerados
Trapen N2
Trapen N3
Trapen N4
Trongol
Truful-Truful
Valdivia
Ventanas U1
Ventanas U2
Viales
Yungay TG U4
Yungay TV U4
Yungay U1
Yungay U2
Yungay U3

PV EL SALVADOR

79

Estudio de Cortocircuito

ANEXO 2: Referencias y Documentacin


[1] Esquema unifilar de la subestacin de la planta fotovoltaica El Salvador (preliminar)

PV EL SALVADOR

80

Estudio de Cortocircuito

[2] Eaton Pad-Mounted Transformers

PV EL SALVADOR

81

Estudio de Cortocircuito

PV EL SALVADOR

82

Estudio de Cortocircuito

PV EL SALVADOR

83

Estudio de Cortocircuito

PV EL SALVADOR

84

Estudio de Cortocircuito

PV EL SALVADOR

85

Estudio de Cortocircuito

PV EL SALVADOR

86

Estudio de Cortocircuito

PV EL SALVADOR

87

Estudio de Cortocircuito

PV EL SALVADOR

88

Estudio de Cortocircuito

PV EL SALVADOR

89

Estudio de Cortocircuito

PV EL SALVADOR

90

Estudio de Cortocircuito

PV EL SALVADOR

91

Estudio de Cortocircuito

PV EL SALVADOR

92

Estudio de Cortocircuito

PV EL SALVADOR

93

Estudio de Cortocircuito

PV EL SALVADOR

94

Estudio de Cortocircuito

[3] Power One Power derating vs ambient temperature

PV EL SALVADOR

95

Estudio de Cortocircuito

[4] Power-One ULTRA series inverter. P-Q capability @ Tamb<30C. (390kVA conversion module)

PV EL SALVADOR

96

Estudio de Cortocircuito

[5] Power-One ULTRA series inverter. ULTRA-700.0-TL-OUTD. ULTRA-1050.0-TL-OUTD. ULTRA-1400.0-TL-OUTD

PV EL SALVADOR

97

Estudio de Cortocircuito

PV EL SALVADOR

98

Estudio de Cortocircuito

PV EL SALVADOR

99

Estudio de Cortocircuito

PV EL SALVADOR

100

Estudio de Cortocircuito

[6] Cable datasheet Top Cable.

PV EL SALVADOR

101

Estudio de Cortocircuito

[7] Base de datos DIgSILENT PowerFactory del CDEC-SIC: EB Septiembre 2013

EB Septiembre 2013.pfd

PV EL SALVADOR

102

Estudio de Cortocircuito

[8] Documento CDEC-SIC describiendo los escenarios de los estudios sistmicos

PV EL SALVADOR

103

Estudio de Cortocircuito

PV EL SALVADOR

104

Estudio de Cortocircuito

[9] Diagrama unifilar de la red de Atacama (Autocad). Detalle de SET DIEGO DE ALMAGRO.

PV EL SALVADOR

105

Estudio de Cortocircuito

[10] Placa de caractersticas del transformador de subestacin.

PV EL SALVADOR

106

Estudio de Cortocircuito

[11] Datos de transformador de inversor

PV EL SALVADOR

107

Estudio de Cortocircuito

PV EL SALVADOR

108

Estudio de Cortocircuito

[12] Datos del interruptor de parque fotovoltaico

PV EL SALVADOR

109

Estudio de Cortocircuito

ANEXO 3: PROCEDIMIENTO DO: TRMINOS Y


CONDICIONES DEL CLCULO DE CORRIENTES DE
CORTOCIRCUITO PARA LA VERIFICACIN DEL
DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC,
CDEC-SIC, Septiembre 2009

PV EL SALVADOR

110

PROCEDIMIENTO DO
TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES
DE CORTOCIRCUITO PARA LA VERIFICACIN DEL
DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

CDEC-SIC

Direccin de Operacin

NDICE
TTULO I: ASPECTOS GENERALES ......................................................................................................... 3
ARTCULO 1.

OBJETIVO...................................................................................................................... 3

ARTCULO 2.

CONDICIN DE OPERACIN ANTE FALLAS ...................................................... 3

ARTCULO 3.

CONDICIN DE INTERRUPCIN ............................................................................ 3

ARTCULO 4.

CONDICIN DE CIERRE............................................................................................ 3

ARTCULO 5.

HERRAMIENTA DE CLCULO ................................................................................ 3

ARTCULO 6.

NORMAS DE REFERENCIA ....................................................................................... 4

TTULO II:

METODOLOGIA................................................................................................................ 4

ARTCULO 7.

SUPUESTOS Y SIMPLIFICACIONES ....................................................................... 4

ARTCULO 8.

CONDICIONES DE APLICACIN............................................................................. 5

ARTCULO 9.

CORRIENTE DE CORTOCIRCUITO ........................................................................ 5

ARTCULO 10.

TIPOS DE CORTOCIRCUITO .................................................................................... 6

ARTCULO 11.
PROCEDIMIENTO DE CLCULO DE LAS COMPONENTES DE
CORRIENTES DE CORTOCIRCUITO ....................................................................................................... 6
ARTCULO 12.
CONDICIONES PARA LA VERIFICACIN DE LA CAPACIDAD DE LOS
INTERRUPTORES.......................................................................................................................................... 9
ARTCULO 13.

CRITERIOS DE VERIFICACIN............................................................................... 9

ANEXO N 1:
DEFINICIONES ASOCIADAS AL CLCULO DE CORRIENTES DE
CORTOCIRCUITO (IEC 60909-0) .............................................................................................................. 11
ANEXO N 2:
IEC 60050-411).

DEFINICIONES ASOCIADAS A INTERRUPTORES (NORMAS: IEC 62271-100;


12

ANEXO N 3: COMPONENTES DE LA CORRIENTE TRANSITORIA EN UN CIRCUITO R-L .... 14


ANEXO N 4:
EXPRESIONES MATEMTICAS DE CORRIENTES DE CORTOCIRCUITOS
SIMTRICAS SEGN TIPOS DE CORTOCIRCUITOS......................................................................... 16
ANEXO N 5:

HOMOLOGACIN DE ALGUNOS TRMINOS DE NORMA IEC CON ANSI. 18

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

2/19

CDEC-SIC

Direccin de Operacin

PROCEDIMIENTO DO
TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE
CORTOCIRCUITO PARA LA VERIFICACIN DEL DIMENSIONAMIENTO DE
INTERRUPTORES DE PODER EN EL SIC
TTULO I: ASPECTOS GENERALES
Artculo 1.

Objetivo

El objetivo del presente procedimiento es definir los trminos, las normas y


consideraciones tcnicas, bajo los cuales se debe efectuar el clculo de corrientes
de cortocircuito que permitan verificar el dimensionamiento de los interruptores de
poder instalados en el Sistema Interconectado Central, en conformidad a lo
establecido en la Norma Tcnica de Seguridad y Calidad de Servicio, en adelante la
NT de SyCS.
Artculo 2.

Condicin de operacin ante fallas

Los interruptores debern soportar la corriente de cortocircuito, que se establezcan


a travs de stos, debido a fallas en cualquiera de las instalaciones del SIC,
durante el tiempo de despeje de la falla.
Artculo 3.

Condicin de interrupcin

Los interruptores, cuya apertura sea accionada por operacin de esquemas de


proteccin para el despeje de fallas en las instalaciones del SIC, debern ser
capaces de interrumpir la mxima corriente de cortocircuito, que se establezca a
travs de stos, de acuerdo con su ubicacin en la red y la localizacin de la falla.
Artculo 4.

Condicin de cierre

Los interruptores debern soportar la mxima corriente de cortocircuito de cierre


contra falla, ya sea por cierre de operacin manual o por cierre con reconexin
automtica.
Artculo 5.

Herramienta de clculo

La herramienta de simulacin que se emplee para el anlisis de cortocircuitos


deber considerar los criterios y supuestos establecidos en el presente
procedimiento y que permita el clculo de las componentes de la corriente de
cortocircuito establecidas en el Artculo 9.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

3/19

CDEC-SIC

Artculo 6.

Direccin de Operacin

Normas de referencia

Los criterios y supuestos establecidos, en el presente procedimiento tienen como


respaldo tcnico las siguientes normas y estndares:
o Norma IEC 60909-0 (2001)

: Short-Circuit current in three-phase a.c.


systems.
o Norma IEC 60050-441 (2000) : International
Electrotechnical
Vocabulary.
Chapter 441: Switchgear, controlgear and
fuses
o Norma IEC 62271-100 (2001) : High-Voltage switchgear and controlgear. Part
100: High Voltage alternating-current circuitbreakers
TTULO II: METODOLOGIA
Artculo 7.

Supuestos y Simplificaciones

El clculo de las corrientes de cortocircuito supone las siguientes simplificaciones:


a) Durante el tiempo de duracin del cortocircuito no existe cambio en el tipo de
cortocircuito, esto es, un cortocircuito trifsico permanece trifsico y un
cortocircuito monofsico permanece monofsico durante todo el tiempo del
cortocircuito.
b) Durante el tiempo de duracin del cortocircuito, no existen cambios topolgicos
en la red.
c) La impedancia de los transformadores es referida a la posicin nominal del
cambiador de tomas. No obstante, el clculo de corrientes de cortocircuito debe
considerar un factor de correccin que represente a la posicin del cambiador
de tomas que de origen a la menor impedancia de cortocircuito.
d) Las magnitudes de la resistencia del arco del cortocircuito y de la impedancia
de falla se consideran despreciables.
e) No se consideran: las capacitancias de las lneas, las admitancias shunt y las
cargas estticas (no-rotatorias), excepto las correspondientes a la red de
secuencia cero del sistema.
f) El tiempo mnimo de separacin de los contactos de un interruptor a considerar
ser de 40 milisegundos. Dicho valor, est constituido por la suma del tiempo
de operacin del rele ms rpido que acta sobre el trip del interruptor y del
tiempo de inicio de la separacin de sus contactos.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

4/19

CDEC-SIC

Artculo 8.

Direccin de Operacin

Condiciones de Aplicacin

EL clculo de las corrientes de cortocircuitos deber contemplar las siguientes


condiciones:
o Factor de tensin (C): Se deber considerar una tensin pre-falla igual a C
veces la tensin nominal, donde C es un factor de tensin que depende de la
tensin, segn lo indicado en la Tabla N 1.
Tabla N 1: Factor de tensin C. (Norma IEC 60909-0)
Tensin Nominal

Factor de tensin C

230 V 400V

Mayor que 400 V y menor o igual a 1000 V

1.05

Mayor que 1 kV

1.1

o Topologa de la red: Se deber considerar la configuracin del sistema que


presente la mayor contribucin de las centrales de generacin al cortocircuito,
esto significa, tener conectadas todas las unidades de generacin, todas las
lneas y transformadores en servicio, talque se configure el mayor
enmallamiento del sistema.
o Sistema equivalente: En caso de usar redes equivalentes externas para
representar el sistema o parte de este, se deber utilizar la mnima impedancia
de cortocircuito equivalente que corresponde a la mxima contribucin de
corriente al cortocircuito desde la red externa equivalente modelada.
o Resistencia RL: La resistencia de las lneas areas y cables deber ser
considerada para una temperatura de 20 C o en su defecto, las
correspondientes resistencias disponibles en la base de datos de las
instalaciones del CDEC-SIC que se emplean en el clculo de flujos de potencia.
Artculo 9.

Corriente de cortocircuito

Las componentes de la corriente de cortocircuito que se debern calcular son:


a) Corriente de cortocircuito simtrica inicial (r.m.s)
b) Corrientes de cortocircuito simtrica y asimtrica de interrupcin (r.m.s.),
evaluada en el instante de 40 milisegundos despus de iniciada la falla
c) Corriente de cortocircuito mxima instantnea (peak) (cierre contra
cortocircuito)
d) Corriente de cortocircuito en rgimen permanente (r.m.s).

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

5/19

CDEC-SIC

Direccin de Operacin

Para el clculo de estas componentes, se debern emplear los siguientes


parmetros de las mquinas rotatorias:
a) En las mquinas sincrnicas la reactancia subtransiente saturada o 0.8
veces el valor de la reactancia subtransiente no saturada.
b) En las mquinas asincrnicas la impedancia de rotor bloqueado.
Artculo 10.

Tipos de cortocircuito

El clculo de las componentes de la corriente de cortocircuito indicadas en el


Artculo 9, deber ser determinada en los siguientes tipos de fallas:
a)
b)
c)
d)

Cortocircuito
Cortocircuito
Cortocircuito
Cortocircuito

Artculo 11.

trifsico (3F).
bifsico aislado (2F).
bifsico a tierra (2FT).
monofsico a tierra (1FT).

Procedimiento de clculo de las componentes de corrientes de


cortocircuito

El procedimiento para determinar las componentes de corrientes de cortocircuito


definidas en el Artculo 9, contempla la aplicacin de las relaciones matemticas
indicadas en el Anexo 4:

Corriente de cortocircuito mxima (ip)


1. Calcular las corrientes de cortocircuito simtrica inicial (Ik) para los tipos
de fallas indicados en el Artculo 10, esto es, Ik3F, Ik2F, Ik1FT e Ik2FT.
2. Aplicar las siguientes expresiones:
i P 3F =

i P 2F

i P1FT

2 I k'' 3F

(
)
X
R
/

k
3
F

1
e
+

( X / R )k 2 F

= 2 I k'' 2 F 1 + e

(
)
X
/
R

''
k 1 FT

= 2 I k1FT 1 + e

i P 2 FT =

2 I k'' 2 FT

(
X
/
R
)

k
2
FT

1
e
+

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

6/19

CDEC-SIC

Direccin de Operacin

Nota: A continuacin, se indican las expresiones de clculo conservador para


estimar las corrientes de cortocircuito mximas, que consideran la aplicacin de
un factor de asimetra:

i P 3F = 2.7 I k'' 3F
i P 2 F = 2.7 I k'' 2 F
i P1FT = 2.7 I k''1FT
i P 2 FT = 2.7 I k'' 2 FT
3. Determinar la mayor corriente mxima (iP), como:

i PMayor = Max{i P 3F , i P 2 F , i P1FT , i P 2 FT }

Corriente de cortocircuito simtrica de interrupcin


1.

Calcular la corriente de cortocircuito simtrica de interrupcin (Ib) en el


instante de 40 milisegundos despus de ocurrida la falla, para los tipos de
falla indicados en el Artculo 10, esto es, Ib3F, Ib2F, Ib1FT e Ib2FT.

2.

Determinar la mayor corriente de cortocircuito simtrica de interrupcin


como:

I bMayor = Max I b 3F , I b 2 F , I b1FT , I b 2 FT

Corriente de cortocircuito asimtrica de interrupcin


(40 milisegundos despus de iniciada la falla)
1. Calcular las razones X/R de las corrientes de cortocircuito de interrupcin,
esto es, (X/R)b3F, (X/R)b2F, (X/R)b1FT y (X/R)b2FT segn las expresiones
indicadas en el Anexo 4.
2. Calcular la componente continua (idc) de las corriente cortocircuito de
interrupcin, a travs de la aplicacin de las siguientes expresiones:

idc3F = 2 I b3F

( X / R )b 3 F
e

idc 2 F = 2 I b 2 F

( X / R )b 2 F
e

idc1FT = 2 I b1FT

(
X
R )b1FT
/
e

idc 2 FT = 2 I b 2 FT

(
X
/
R )b 2 FT
e

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

7/19

CDEC-SIC

Direccin de Operacin

Nota: A continuacin, se indican las expresiones de clculo conservador para


estimar la componente continua de las corrientes de cortocircuito:

i dc 3F = I b3F
i dc 2 F = I b 2 F
i dc1FT = I b1FT
i dc 2 FT = I b 2 FT
3. Calcular la corriente de cortocircuito asimtrica de interrupcin (IbASY),
como:
2
I bAsy 3F = I b23F + i dc
3F
2
I bAsy 2 F = I b22 F + i dc
2F
2
I bAsy1FT = I b21FT + i dc
1FT
2
I bAsy 2 FT = I b22 FT + i dc
2 FT

Nota: A continuacin, se indican las expresiones de clculo conservador para


estimar las corrientes de cortocircuito asimtrica de interrupcin:

I bAsy 3F = 2 I b3F
I bAsy 2 F = 2 I b 2 F
I bAsy1FT = 2 I b1FT
I bAsy 2 FT = 2 I b 2 FT
4. Determinar la mayor corriente IbAsy, como:

I bAsyMayor = Max I bAsy 3F , I bAsy 2 F , I bAsy1FT , I bAsy 2 FT

Corriente de cortocircuito en rgimen permanente


1.- Calcular las corrientes de cortocircuitos simtricas en rgimen permanente
(Ik) para los tipos de fallas indicadas en el Artculo 10, esto es, Ik3F, Ik2F,
Ik1FT e Ik2FT.
2.- Determinar la mayor corriente de cortocircuito simtrica en rgimen
permanente como:

I kMayor = Max I k 3F , I k 2 F , I k1FT , I k 2 FT

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

8/19

CDEC-SIC

Artculo 12.

Direccin de Operacin

Condiciones para la Verificacin de la Capacidad de los


Interruptores

Un interruptor estar adecuadamente dimensionado si satisface las condiciones


que se sealan a continuacin, supeditado a las mayores corrientes de
cortocircuito que se determinen de acuerdo con lo establecido en el Artculo 11:
a) La capacidad de ruptura simtrica nominal del interruptor, deber ser mayor
que la corriente de cortocircuito simtrica de interrupcin que se establezca
a travs de ste, en el instante de 40 milisegundos despus de iniciado el
cortocircuito.
b) La capacidad de ruptura asimtrica del interruptor, deber ser mayor que la
corriente de cortocircuito de interrupcin asimtrica que se establezca a
travs de ste, en el instante de 40 milisegundos despus de iniciado el
cortocircuito.
c) La capacidad de cierre contra cortocircuito nominal del interruptor, deber
ser mayor que la corriente de cortocircuito mxima instantnea (peak), que
se establezca a travs de ste.
d) La corriente de cortocircuito de duracin nominal del interruptor dada por el
(I2t) de diseo, deber ser mayor que el Ik2t correspondiente a la corriente
de cortocircuito en rgimen permanente para un perodo de operacin de la
primera proteccin de respaldo.
Nota: Para establecer la capacidad de ruptura asimtrica de interruptores como
funcin de la capacidad de ruptura simtrica (ISC) y de su componente de corriente
continua asociada, expresada como un porcentaje (kdc) respecto del valor mximo de
la corriente de interrupcin simtrica (2ISC), se puede emplear la siguiente expresin:
I SC Asy = I SC

k
1 + 2 dc
100

(kA)

Donde ISC representa la capacidad de ruptura simtrica expresada en kA amperes


r.m.s.

Artculo 13.

Criterios de Verificacin

a) Corto Circuito en Barra:


Un interruptor estar adecuadamente dimensionado si la mayor de las
corrientes de cortocircuito, que se determinen de acuerdo con lo establecido
en el Artculo 11, en la barra o nudo donde se encuentra conectado, cumple
simultneamente con las condiciones sealadas en el Artculo 12.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

9/19

CDEC-SIC

Direccin de Operacin

En el caso que el interruptor no cumpla con esas condiciones para el


cortocircuito en barra, se debern determinar las corrientes de cortocircuito
que se establezcan a travs del interruptor en las condiciones sealadas en
el inciso b) de este Artculo.
b) Corrientes de Corto Circuito en el Interruptor:
La capacidad del interruptor deber satisfacer la mxima de las corrientes
de cortocircuito que se determinen en las distintas condiciones de aplicacin
de la falla, que se sealan en la figura (1). Es decir, se deber verificar lo
siguiente:

Max I CCLnea , (I CCBarra I CCLnea ), I CCLine Out , I CC Open End

Int
F

ICCLinea

ICCBarra
ICCBarra- ICCLinea
Int
F
ICCLineOut
Int
F
ICCOpenEnd
Int
F

Figura (1).

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

10/19

CDEC-SIC

ANEXO N 1:

Direccin de Operacin

Definiciones asociadas al clculo de corrientes de


cortocircuito (IEC 60909-0)

1. Corriente de cortocircuito simtrica: Valor r.m.s. de la componente


simtrica de corriente alterna (ca.) de una corriente de cortocircuito. La
componente continua o no peridica de la corriente, no es considerada.
2. Corriente de cortocircuito simtrica inicial: Valor r.m.s. de la componente
simtrica de ca. de una corriente de cortocircuito, aplicable en el instante de
iniciado el corto circuito, considerando que la impedancia mantiene el valor del
instante t=0.
3. Componente continua (no-peridica) de la corriente de cortocircuito
(iDC): Valor medio de la envolvente de la corriente de cortocircuito decayendo
desde un valor inicial hasta cero.
4. Corriente de cortocircuito mxima (peak): Valor instantneo mximo
posible de la corriente de cortocircuito.
5. Corriente de cortocircuito simtrica de interrupcin: Valor r.m.s. de la
componente simtrica de la corriente de cortocircuito, integrada en 1 ciclo,
para el instante de separacin de los contactos del primer polo del dispositivo
de interrupcin.
6. Tensin nominal del sistema (Vn): Tensin (lnea a lnea) de diseo del
sistema.
7. Cortocircuitos lejanos al generador: Cortocircuito durante el cual la
magnitud de la componente simtrica de corriente alterna (ca.) de la corriente
de cortocircuito permanece esencialmente constante.
8. Cortocircuitos cercanos al generador: Cortocircuito en el que al menos una
mquina sincrnica contribuye con una corriente de cortocircuito simtrica
inicial que es mayor que dos veces la corriente de nominal de la mquina, o un
cortocircuito para el cual la contribucin de los motores asincrnicos es mayor
que el 5% de la corriente de cortocircuito simtrica inicial sin los motores.
9. Reactancia subtransiente de una mquina sincrnica: Corresponde a la
reactancia que efectivamente se establece al momento del cortocircuito..

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

11/19

CDEC-SIC

Direccin de Operacin

ANEXO N 2:

Definiciones asociadas a interruptores (Normas: IEC


62271-100; IEC 60050-411).

1. Corriente de cortocircuito de interrupcin nominal(ISC): Es la corriente


de cortocircuito ms alta que el interruptor es capaz de interrumpir bajo
condiciones de uso y comportamiento establecidas en la norma IEC 62271-100.
La corriente es caracterizada por dos valores:
-

El valor r.m.s. de la componente de corriente alterna


El porcentaje de la componente de corriente continua

Si la componente de corriente continua no excede el 20%, la corriente de


interrupcin nominal, es caracterizada solo por el valor r.m.s. de la componente
de corriente alterna.
El interruptor ser capaz de interrumpir cualquier corriente de cortocircuito
hasta su corriente de cortocircuito de interrupcin nominal que contenga
cualquier componente de corriente alterna hasta su valor nominal y, asociada
con cualquier porcentaje de la componente de corriente continua hasta el valor
especificado.
El valor estndar de la componente de corriente alterna de la corriente de
cortocircuito de interrupcin nominal ser seleccionada desde la serie R10
especificada en la norma IEC 600059.
La serie R10 comprende los nmeros: 1 - 1.25 - 1.6 2 - 2.5 - 3.15 4 5 n
6.3 8 y aquellos formados por el producto entre estos nmeros por 10 .
2. Corriente de cortocircuito mxima nominal (Rated short-circuit making
current): Es la mxima corriente de cortocircuito que soporta el interruptor
durante el primer ciclo de la corriente de cortocircuito.
3. Determinacin de las componentes de corriente mxima, simtrica de
interrupcin y continua, de cortocircuito: De acuerdo a la informacin
contenida en la figura (2), se tiene:

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

12/19

CDEC-SIC

Direccin de Operacin

Corriente de cortocircuito

2.5

A'

D'

IC.A.

IMC
IDC
B

C'

X
M
B'

E'
0.00

0.01

0.02
0.03
tpo. seg

0.04

0.05

Figura (2)
Curva - trazo variable - expresin
AA y BB
BX
CC
DD
EE
IMC
ICA.
IDC.
I DC .
ON OM
100 =
100
I CA.
MN

Descripcin
Envolvente de la onda de corriente
Lnea de eje cero
Desplazamiento de la lnea de eje cero de la
componente de corriente alterna en cualquier
instante
Valor r.m.s de la componente de c.a. de la
corriente en cualquier instante, medido desde
curva CC
Instante de separacin de los contactos del
interruptor (iniciacin del arco de cortocircuito)
Corriente de cortocircuito mxima
Valor peak de la componente ca. de la corriente
en el instante definido por el trazo EE
Componente de corriente continua de la
corriente en el instante EE
Porcentaje de la componente de corriente
continua (dc)

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

13/19

CDEC-SIC

Direccin de Operacin

ANEXO N 3: Componentes de la corriente transitoria en un circuito R-L


Las siguientes ecuaciones representan las expresiones matemticas de la
corriente transitoria un circuito inductivo (R-L) alimentado con una fuente de
tensin de corriente alterna:
i (t ) =

2V
R2 + X 2

2 50

t
sen( wt ) + sen( + ) e X / R

2 50

i (t ) = 2 I RMS sen( wt ) + sen( + ) e X / R

V
I RMS =
R2 + X 2
X
con
= a tan
+ = 90
R
2 50

i (t ) = 2 I RMS sen( wt 90) + e X / R

Donde:
V
:
X
:
R
:

Tensin r.m.s. de la fuente de alimentacin, en volt.


Reactancia inductiva del circuito R-L, esto es, 250L, en ohm.
Resistencia del circuito R-L, en ohm.
Determina la magnitud de tensin cuando se cierra el circuito R-L.

Componente de corriente.
Simtrica r.m.s.

Expresin
I RMS

2 I RMS

Simtrica mxima
Continua en funcin del tiempo

Envolvente mxima en funcin del tiempo

i dc ( t ) = 2 I RMS

2 50

t
e X/R

2 50

t
iENV (t ) = 2 I RMS 1 + e X / R

2 50

2
t
1 + 2 e X / R

Asimtrica r.m.s. en funcin del tiempo

I ASY (t ) = I RMS

Peak en funcin de la razn X/R, en t=0.01s

iP = iENV (t ) t =0.01 = 2 I RMS 1 + e X / R

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

14/19

CDEC-SIC

Componente de corriente.
Peak para X/R=14.13, en t=0.01s

Asimtrica r.m.s en funcin de X/R en t=0.04s

Asimtrica RMS para X/R=14.13 en t=0.04s

Continua en funcin de X/R en t=0.04s


Continua para X/R=14.13 en t=0.04s

Direccin de Operacin

Expresin

iP = 2 I RMS 1 + e 14.13 = 2 1.8 I RMS

I ASY = I RMS

1 + 2 e X / R

I ASY = I RMS

1 + 2 e 14.13 = 1.157 I RMS

i dc ( t ) = 2 I RMS
i dc = 2 I RMS

e X /R

e 14.13

= 0.581 I RMS

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

15/19

CDEC-SIC

Direccin de Operacin

ANEXO N 4:

Expresiones
matemticas
de
corrientes
de
cortocircuitos simtricas segn tipos de cortocircuitos.

Las siguientes expresiones de tipo general se pueden emplear para calcular; la


corriente de cortocircuito simtrica inicia (Ik), la corriente de cortocircuito simtrica
de interrupcin (Ib), la corriente de cortocircuito simtrica de rgimen permanente
(Ik) y las correspondientes razones (X/R), segn los tipos de cortocircuito.
Cortocircuito Trifsico:

( X / R ) CC 3F

cVn

I CC 3F =

3 Z1

X1
R1

Cortocircuito Monofsico a tierra:


I CC 1FT =

3cV n
(Z 1 + Z 2 + Z 0 )

( X / R )CC1FT

X1 + X 2 + X 0
R1 + R 2 + R0

Cortocircuito Bifsico aislado de tierra:


I CC 2 F =

( X / R )CC 2F

cVn
(Z1 + Z 2 )

X1 + X 2
R1 + R2

Cortocircuito Bifsico a tierra:

(Z 0 a Z 2 )
I CC 2 FT _ B = cV n j
(Z1 Z 2 + Z1 Z 0 + Z 2 Z 0 )

Z0 a2 Z2
I CC 2 FT _ C = cV n j

(Z 1 Z 2 + Z 1 Z 0 + Z 2 Z 0 )

a = 0.5 + j

3
2

a 2 = 0.5 j

3
2

: operador

: operador

3 Z2
I CC 2 FT = I CC 2 FT _ B + I CC 2 FT _ C = cV n

(Z 1 Z 2 + Z 1 Z 0 + Z 2 Z 0 )
Z CC 2 FT =

Donde:
Vn
c

(Z 1 Z 2 + Z 1 Z 0 + Z 2 Z 0 )
3 Z2

( X / R) CC 2 FT =

Imag{Z CC 2 FT }
Real{Z CC 2 FT }

: Tensin nominal lnea a lnea del sistema en el punto de falla, en


kV.
: Factor de tensin.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

16/19

CDEC-SIC

Direccin de Operacin

Z1=R1+jX1 : Impedancia del circuito equivalente de Thevenin de la red de


secuencia positiva en el punto de falla, en ohm.
Z2=R2+jX2 : Impedancia del circuito equivalente de Thevenin de la red de
secuencia negativa en el punto de falla, en ohm.
Z0=R0+jX0 : Impedancia del circuito equivalente de Thevenin de la red de
secuencia cero en el punto de falla, en ohm.
ICC3F
: Corriente de cortocircuito simtrica RMS de fase, para cortocircuito
trifsico, en kA.
ICC1FT
: Corriente de cortocircuito simtrica RMS de fase, para cortocircuito
monofsico a tierra, en kA.
ICC2F
: Corriente de cortocircuito simtrica RMS de fase, para cortocircuito
bifsico aislado de tierra, en kA.
ICC2FT
: Corriente de cortocircuito simtrica RMS de fase, para cortocircuito
bifsico a tierra, en kA.
(X/R)CC3F : Razn X/R del cortocircuito trifsico.
(X/R)CC1FT : Razn X/R del cortocircuito monofsico a tierra.
(X/R)CC2F : Razn X/R del cortocircuito bifsico aislado de tierra.
(X/R)CC2FT : Razn X/R del cortocircuito bifsico a tierra.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

17/19

CDEC-SIC

ANEXO N 5:

Direccin de Operacin

Homologacin de algunos trminos de Norma IEC con


ANSI.

Definicin de conceptos relacionados con especificaciones tcnicas nominales de


interruptores de poder en alta tensin:
Id
1
2
3

Definicin en
Espaol

NORMA
IEC

Corriente nominal

Rated normal current

Capacidad de ruptura
simtrica
Capacidad de cierre
contra cortocircuito

Rated short-circuit breaking


current (ISC)
Rated short-circuit making
current (ip)
Constituida por:
Una componente de c.a. (ISC)
y una componente de
corriente continua definida
como un porcentaje kdc:
i dc
100
k dc =
2 I SC

Capacidad de ruptura
asimtrica

Corriente de
cortocircuito en
rgimen permanente

Steady-state short-circuit
current (Ik)

ANSI
Rated continuos current
Rated short-circuit current
Rated closing, latching, and
short time carrying
Valor r.m.s de la componente
total de interrupcin:
I SC ASY =

2
I SC

2
+ i dc

Steady-state short-circuit
current

Unidad
Amp.
r.m.s.
kA
r.m.s.
kA

kA
r.m.s.

kA
r.m.s.

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

18/19

CDEC-SIC

Direccin de Operacin

Conceptos segn normas empleados en el clculo de corrientes de cortocircuito:


Id

Conceptos

Tensin de pre-falla

Redes de secuencia para:

Reactancia de mquinas
sincrnicas empleadas en el
clculo de la corriente de
cortocircuito simtrica inicial (Ik)

Reactancia de mquinas
sincrnicas empleadas en el
clculo de la corriente de
cortocircuito de interrupcin
simtrica (Ib)
Impedancia de mquinas de
induccin en al clculo de
cortocircuito simtrica inicial (Ik)
Impedancia de mquinas de
induccin en el clculo de
corriente de cortocircuito de
interrupcin simtrica (Ib)

Impedancia de mquinas de
induccin en el clculo de
corriente de cortocircuito en
rgimen permanente (Ik)

Expresiones de para la razn X/R

Norma
IEC
cVn
Impedancias:
Z1,Z2,Z0
X saturada

ANSI
Vn

Reactancias: X1,X2,X0
Resistencias: R1, R2,R0
Turbo generadores: Xsaturada
Hidro con amortiguadores: Xsaturada
Hidro sin amortiguadores:
0.75Xsaturada

Xsaturada

Turbo generadores: Xsaturada


Hidro con amortiguadores: Xsaturada
Hidro sin amortiguadores:
0.75Xsaturada

Impedancia
de rotor
bloqueado

Reactancia de rotor bloqueado

Impedancia
de rotor
bloqueado

1.5 veces la reactancia de rotor


bloqueado

Impedancia
de rotor
bloqueado en
fallas
asimtricas
IEC

Las mquinas de induccin no aportan


a las corrientes de cortocircuito en
rgimen permanente.
Idem a IEC

Procedimiento DO: TRMINOS Y CONDICIONES DEL CLCULO DE CORRIENTES DE CORTOCIRCUITOS PARA


VERIFICACIN DEL DIMENSIONAMIENTO DE INTERRUPTORES EN EL SIC

19/19