Você está na página 1de 2

S/N

Alarm Name

Default
Level

Output Relay
Default

Description

S/N

Alarm Name

Modified

Default
Level

Output Relay
Default

Description

Modified

Start GEN

The generator has been started.

17

SMR Fan Fault

Major

A2

The fan of the rectifier is faulty.

SMR on boost

The system
batteries in
charge mode.

18

SMR PFC Fault

Major

A2

The Power Factor Correction (PFC)


circuit of the rectifier is faulty.

19

SMR Vin.High

Major

A2

The input voltage of the rectifier is


higher than the threshold.

20

SMR L.Vin Off

Major

A2

The input voltage of the rectifier is


lower than the threshold.

21

SMR H.T. Off

Major

A2

The temperature of the rectifier


main radiator is higher than the
threshold, and the rectifier stops
output.

22

SMR Env.H.T.Off

Major

A2

The environment temperature of the


rectifier is higher than the threshold,
and the rectifier shuts down for
protection.

23

SMR Env.H.T.

Major

A2

The environment temperature of the


rectifier is higher than the threshold,
and
the
rectifier
output
is
encountering linear load shedding.

24

SMR L.Vin

Major

A2

The input voltage of the rectifier is


lower than the threshold, and the
rectifier
output
current
is
encountering linear load shedding.

is charging the
boost (equalized)

Comm. Minor Alm

A7

A minor alarm occurs.

Comm. Major Alm

A7

A major alarm occurs.

AC Switch Off

Major

A1

The AC input switch is OFF.

AC Power Off

Major

A1

The mains supply is interrupted and


there is no standby AC input
available.

SPD-C Broken

Major

A3

The Class C Surge Protection


Device (SPD) is faulty.

SPD-D Broken

Mask

A3

The Class D SPD is faulty.

AC Volt. Low

Minor

The AC input voltage is lower than


AC.UnderVolt.

10

AC Volt. High

Minor

The AC input voltage is higher than


AC.OverVolt.

11

AC Curr. High

Minor

The AC input current is higher than


AC.OverCurr.

12

AC Failure

Mask

An AC-related alarm occurs.

13

Urgent AC Fail.

Mask

An AC-related alarm persists for a


certain time.

25

SMR Fuse Brk.

Major

A2

The output fuse of the rectifier is


blown.

14

Over Load

Mask

Over-load occurs to the system. Its


capacity needs to be expanded.

26

SMR CommFail

Major

A2

15

SMR Vout.High

Major

A2

The output voltage of the rectifier is


higher than the threshold, and the
rectifier stops output.

The communication between the


rectifier and the monitoring unit is
interrupted.

27

DC Volt. Low

Minor

A6

The DC output voltage is lower than


DC UnderVolt.

28

DC Volt. 2Low

Mask

A6

The DC output voltage is lower than


DC 2Low Volt.

16

SMR Iout.High

Major

A2

The output current of the rectifier is


higher than the threshold, and the
rectifier stops output.

S/N

Alarm Name

Default
Level

Output Relay
Default

Description

DC Volt.High

Minor

The DC output voltage is higher


than DC OverVolt.

30

DC Loop Brk.

Major

A4

The load loop is not connected.

31

Bat.1 Loop Brk

Major

A4

The battery 1 loop is open.

32

Bat.2 Loop Brk

Major

A4

The battery 2 loop is open.

33

Bat.1 Volt. Low

Major

A6

The battery 1 voltage is lower than


Bat.UnderVolt.

34

Bat.2 Volt. Low

Major

A6

The battery 2 voltage is lower than


Bat.UnderVolt.

35

Bat.1 Temp.High

Minor

The battery 1 working temperature


is higher than Bat.OverTemp.

37

Bat.2 Temp.High

LTD Alarm

Minor

Major

A5

Alarm Name

Modified

29

36

S/N

The battery 2 working temperature


is higher than Bat.OverTemp.
The environment temperature is
lower than LTBD Temp. As a result,
the batteries as well as the entire
loads are cut off.

Default
Level

Output Relay
Default

43

Bat. On Load

Minor

A4

The battery is discharging.

44

Env. Temp. Low

Minor

The environment temperature is


lower than Env.UnderTemp.

45

Env. Temp.High

Minor

The environment temperature is


higher than Env.OverTemp.

46

Env Hum. Low

Mask

The environment humidity is lower


than Env.UnderHum.

47

Env. Hum.High

Mask

The environment humidity is higher


than Env.OverHum.

48

Smoke Alarm

Major

The sensor detects the smoke.

49

Flood Alar

Major

The sensor detects the entrance of


water.

50

Door Magnet Alm

Minor

The door with the door magnet


switch is opened. Some object
intrudes.

51

E.T.Invalid

Mask

The
environment
temperature
detection fails. Check whether the
environment temperature sensor
and the cables are properly
installed.

52

E.H.Invalid

Mask

The environment humidity detection


fails.
Check
whether
the
environment humidity sensor and
the cables are properly installed.

LTD = Low Temperation Disconnect


38

LVD1 Alarm

Major

A5

The battery voltage is lower than


LVD1 Volt. As a result, the batteries
as well as the entire loads are cut
off.
LVD = Low Voltage Disconnect

39

LVD2 Alarm

Major

A5

The alarm is not applicable to the


system.

40

SPD-DC Alarm

Major

A3

The DC surge arrester is faulty.

41

DC Breaker Alm

Minor

Some breaker is faulty.

42

Bat.Test Fail

Minor

A4

The battery test is terminated


despite that its duration does not
reach Test Max.Hours.

Description

Modified

Note:
z A1 to A6 are the six output relays. For their corresponding interfaces, refer to the quick installation and
commissioning guide or product description manual of the DC power system.
z A7 is reserved for future expansion.