Você está na página 1de 308

VRV

Product catalogue 2016


for professionals

Full
L

IBR AR
OF BIM
Y
OBJEC
TS
FOR

Minimum running costs, maximum flexibility.


Fast installation, top reliability, perfect comfort.

VRV

Why choose Daikin


Our promise is to ensure that your customers can depend on Daikin for the
ultimate in comfort, so that they are free to focus on their own working and
home lives.
We promise to dedicate ourselves to technological excellence, a design focus
and the highest quality standards so that your customers can trust and rely on
the comfort we deliver.
Our promise to the planet is absolute. Our products are at the forefront
of low energy consumption and we continuously innovate to reduce the
environmental impact of HVACR solutions further.
We lead where others follow. We will continue our global leadership in HVACR
solutions as our specialist expertise in all market sectors combined with 90
years experience enable us to deliver added value in long-lasting relationships
based on trust, respect and credibility.

Table of contents
VRV, the solution for the
commercial sector

VRV IV standard & technologies

16

Benefits

24

NE W
S-serie
s
i-serie
s

Outdoor units

34

Wide
range st
on
the
marke
t

Indoor units

122

Hot water

208

Biddle Air Curtains

218

NE W
contro
possib l
il
for AH ity
U

Ventilation and Air Handling

224

NEW
DCC60
1A51

Control Systems

258

Options and Accessories

282

Tools and platforms

298

NE W
busine
portalss

ARGUE CARDS

VRV IV sets the standard


again

8 reasons why VRV


is unique in the market
1

High energy efficiency


Variable Refrigerant Temperature leading to the highest seasonal efficiency
Customize your VRV for best seasonal efficiency & comfort
Up to 28% higher seasonal efficiency (ESEER)
First weather dependent VRV
No more cold draught by supply of high outblow temperatures
Round flow cassette with auto cleaning panel
Absolute credibility of data with Eurovent certification of air-cooled outdoor units
The best partner for your green project
A team of APs across Europe who are there to help you
Gain points in several BREEAM categories
Experience with many green and sustainable projects across Europe

Best comfort
Variable Refrigerant Temperature preventing cold draughts
True continuous heating, during defrost
15 class units for small, well insulated rooms (cassette, wall, concealed ceiling models)
Low sound indoor and outdoor units
Presence and floor sensors direct the air flow away from persons, while ensuring
an even temperature distribution

Top reliability
True technical cooling
Gas-cooled PCB
Most extensive testing before new units leave the factory
Widest support network and after sales service
All spare parts available in Europe
Preventive maintenance via i-Net

presence sensor

floor sensor

VRV Intro

Market leading controls


Intelligent Touch manager, cost-effective mini BMS integrating all Daikin
products
Easy integrating in third party BMS via BACnet, LonWorks, Modbus, KNX
Dedicated control solutions for applications such as technical cooling, shops,
hotels, ...
Daikin Cloud Service offers services such as online control, energy monitoring,
comparison of multiple sites

Stylish design products


Fully flat cassette, fully integrated in the ceiling
Daikin Emura, unique iconic design
Daikin Emura

Unique installation benefits


Automatic refrigerant charge and refrigerant containment check
4-way blow ceiling suspended cassette (FXUQ)
Plug & play Daikin air handling unit
Total solution incl. low and high temperature hydro box, Biddle air curtains, etc.
VRV configurator software for the fastest commissioning, configuration and
customisation
Outdoor unit display for quick on-site settings
Free combination of oudoor units to meet installation space or efficiency
requirements

FXUQ

7-segment display

Inventor and market leader of VRV


systems since 1982
Over 90 years of expertise in heat pumps
Designed for and produced in Europe

Unique outdoor unit range


covering all applications
and climate conditions
in design

Heat pump
Heat recovery
Replacement
Water cooled

The VRV air conditioning system is the worlds first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trademark of Dakin Industries Ltd, which is derived from the technology we call variable refrigerant volume. BREEAM is a registered trademark of BRE
(the Building Research Establishment Ltd. Community Trade Mark E5778551). The BREEAM marks, logos and symbols are the Copyright of BRE and are reproduced by
permission

In the spotlight
BIM: Building Information Modelling
What is BIM?
BIM is an intelligent model-based process that
provides insight to help you plan, design, construct
and manage buildings and infrastructure

Daikin and BIM putting


you ahead of competition
Daikin is among the first to supply a full library of
BIM objects for its VRV products.
Installers get an edge over competition where
customers demand for BIM to be used
Consultants have direct access to the base data

through the objects, to design the system

and see how our solutions can fit your project
Customers have easy access to latest relevant

information needed to maintain and manage the
installation.

Collaboration
and clash control
BIM uses a 3D model to provide the right information, to the right people, at the right time. This
process improves efficiency throughout the design
and building phases and increases savings by
discovering clashes during the design phase, rather
than later on during the building phase.

Download the Daikin BIM objects here:


http://bimobject.com/en/
product/?freetext=daikin

Green building solutions


Todays challenges
From 2015 onwards the majority of new building
projects in Europe are expected to be green
93% percent of developers & investors consider

green certification important

Visit the minisite


http://www.daikineurope.com/
minisite/sustainability/index.jsp

Daikin: the best partner


for your green project
We have a team of BREEAM accredited
professionals (AP's) at your service that support
you and your customer throughout the project
Daikin offers solutions that maximise your

BREEAM and LEED scores with heat recovery,

Variable Refrigerant Temperature and i-Net.
Daikin has successfully participated in many

green and sustainable projects across Europe

Expertise

ECPEN15-216A.indd 5

Case: Velocity, UK
Energy performace certificate B
VRV heat recovery ensures an energy cost

of 9 euro/m3 compared to a typical cost of

29 euro/m3

/m
energy cost

vs 29/m for
a CIBSE
typical office

BREEAM is a registered trademark of BRE (the Building Research Establishment Ltd. Community Trade Mark E5778551).

14/04/15 17:30

VRV Intro

Innovative outdoor units


i
VRV IV heat pumps for indoor installation

More details
on page 76

You can install highly efficient, reliable Daikin air conditioning systems in
the most demanding locations while remaining invisible from street level.

Invisible
Only the grilles are visible
Seamless integration into surrounding
architecture
Low operation sound

Intelligent
Patented V-shape heat exchanger for the most
compact unit ever
Connectable to all VRV indoor units
Total solution when combined with ventilation

units, Biddle air curtains and controls

Intuitive
Total flexibility as the outdoor unit is split

up in parts
Easy and quick to transport and install
Easy servicability, all components can be easily
reached

uniqu
e
paten
ted
conce
pt

Split outdoor unit system:


1 heat exchanger unit installed in false ceiling
2 compressor unit installed in kitchen

Compact VRV IV heat pumps


for residential and light commercial applications

More details
on page 58

They may be discreet, but Daikin VRV IV S-series


units stand out when it comes to benefits they
deliver. They provide the perfect indoor climate,
while remaining totally discreet from the outside.

Wide range of features


A total air conditioning solution integrating
air handling units and/or air curtains
Complete reliability thanks to refrigerant-cooled

PCB (not available on RXYSQ4,5,6,8TY1)
Suitable for bigger projects of up to 150 to
200m2
Light weight unit (down to 88kg) is easy to

install, transport and handle
A perfect match for any application thanks

to the wide range of small-footprint units
Operation range up to 52C in cooling

Widest range of front blow units in the market

823mm

1615mm

10/12 HP

8 HP

4/5/6 HP

Mo
co m p s t
a
on the c t unit
m
823m arket
m hig
& 88k h
g

4/5 HP

Units designed for your interior


More details
on page 130

Round flow cassette


360 air discharge for optimum
efficiency and comfort

Intelligent sensors increase


comfort and efficiency

presence sensor

Auto cleaning filter:


Increases efficiency with 50% and
makes maintenance easier since
the unit does not need to be
opened for filter cleaning
Dust can be removed easily
with a vacuum cleaner
without opening the unit

Flexible installation
with individual flap control

AUTO CLEANING FILTER

Fully flat cassette


Unique design in the market that integrates fully flat into the ceiling
Advanced technology and top efficiency combined

Unique design

floor sensor

Most
quiet
unit in
th
marke e
t
(25dBA

More details
on page 136

Designed by a European design office to fully meet


the European taste.
Fully flat into the ceiling, leaving only 8mm.
Fully integrated in the one ceiling tile, enabling
lights, speakers and sprinklers to be installed in
adjoining ceiling tiles.
Decoration panel available in 2 colours
(white and white-silver).

Intelligent sensors and flap control on round flow and fully flat cassette
Top efficiency

Top comfort

When the room is empty, the intelligent sensor


option can adjust the set temperature or switch off
the unit saving up to 27% energy.

Intelligent sensors direct


the air flow away from
persons detected in the
room
Individual flap control: easily control one or more
flaps via the wired remote controller (BRC1E52)
when rearranging the room.

Replacement VRV increases your profit


Less installation time compared to a full replacement allows you to tackle

more projects making it more profitable


Lower installation cost improves your competitive edge
Replace non-Daikin systems
Automatic charging and pipe cleaning ensures a quality replacement

VRV Intro

The quick & quality way to upgrade


R-22 and R-407C systems

More details
on page 100

Compare installation steps


Conventional solution

VRV-Q

1
2
3
4
5
6
7

1 Recover refrigerant
2 Remove units

Recover refrigerant
Remove units
Remove refrigerant pipes
Install new piping and wiring
Install new units
Leak test
Vacuum drying

8 Refrigerant charging
9 Collect contamination
10 Test operation

Re-use existing piping


and wiring
3 Install new units
4 Leak test
5 Vacuum drying
6 Automatic refrigerant
charging, cleaning and testing

Up to 45% shorter
installation time

These benefits will convince your customer


No interruption of daily business

Drastically improve your efficiency,


comfort and reliability

The Daikin
low-cost upgrade solution

Replace indoor units and BS boxes

Contact your local dealer to check


compatibility in case you need to keep
the indoor units.

Replace outdoor units


R-22 (RSXY-KA7)

R-407C (RSXYP-L7)

Comparison of 10HP systems:


Cooling mode
Heating mode

Including an air handling unit


has never been easier

R-410A (RXYQQ-T)

Up to 48%
less consumption

More details
on page 224

In situations where Daikin Heat Reclaim Ventilation units cannot satisfy the ventilation requirement, Daikin air handling units
represent the ideal solution, offering large fresh air volumes and high ESPs enabling the use of extensive ductwork runs.

The Daikin pre-configured,


plug and play solution
Our unique plug and play solutions offer you the
flexibility of an air handling unit with the ease of
selection and installation of a standard ventilation
unit
Plug&play
No configuration needed, select it like any other

ventilation device
No additional work at installer side to design the
total system

VRV IV or ERQ
condensing unit

Factory fitted and welded


fresh air package

Electronic expansion
valve

Control box

(EKEXV)

(EKEQ)

Which VRV
system offers me the best solution?
Heat recovery or heat pump?
VRV Heat recovery

Addit
io
credit nal
s
BREEA for
certifi M
cate
North

Extracted heat delivers


free hot water and heating

Cooling

+
Hot water

Heating

Simultaneous heating AND cooling from one


system
"Free" heating and hot water production by
transferring heat from areas requiring cooling
Maximum individual comfort in all areas
Technical cooling down to -20C
Components:

Outdoor unit

Indoor unit

3-pipe
refrigerant
piping

VRV Heat pump


For either heating OR cooling operation from one
system
Components:

Outdoor unit

10

Indoor unit

2-pipe
refrigerant
piping

Single and multi


BS boxes:
allows the individual
switching of indoor
units between heating
and cooling

South

VRV Intro

Air cooled or water cooled?


Air Cooled
Fast and easy to install; no need for additional
components
Low maintenance costs
Operation range from - 25C~52C
Can be installed both outdoors and indoors
Up to 54HP capacity for one system
Components:

Outdoor unit

Indoor unit

Refrigerant piping

Water Cooled
Suitable for high rise and large buildings because of
the nearly unlimited possibilities of water piping
Not affected by outdoor temperature/climate
conditions
Reduce CO2 emmisions thanks to the use of
geothermal energy as a renewable energy source
Allows heat recovery in the entire building thanks
to the storage of energy in the water circuit
Lower refrigerant levels thanks to the limited
distance between outdoor and indoor units

Addit
io
credit nal
s
BREEA for
certifi M
cate

Components:

Outdoor unit

Indoor unit

Refrigerant piping

(Geothermal)
water loop

Geothermal application

11

Which applications?

Heating
Cooling

Refrigeration

Hot water

Infrastructure
cooling

Underfloor heating
Air curtains

Ventilation

Typically, many buildings today rely on several


separate systems for heating, cooling, air curtain
heating and hot water. As a result energy
is wasted. To provide a much more efficient
alternative, VRV technology has been developed
into a total solution managing up to 70% of
a buildings energy consumption giving large
potential to cost saving.
Heating and cooling for year round comfort
Hot water for efficient production of hot water
Underfloor heating /cooling

for efficient space heating/cooling

Controls

Ventilation for high quality environments


Air curtains for optimum air separation
Controls for maximum operating efficiency
Cooling for server rooms, telecom shelters, ... via

VRV heat recovery or Sky Air units


Refrigeration via our VRV based refrigeration

units

Combine up to 70% of your buildings energy consumption


Average office energy consumption

Average hotel energy consumption

Refrigeration 3%

Lighting

Ventilation 4%
Integrate
third party
equipment

Space cooling 15%

Kitchen
Office
Other

70%

Hot water 9%

Other

Space heating 25%

Office
equipment

48%

Hot water 17%

Lighting
Space cooling 9%
Space heating 31%

12

Ventilation 5%

Integrate
third party
equipment

VRV Intro

One system,
multiple applications for hotels, offices,
retail, home
Heating and cooling

Intelligent control systems


22

Combine VRV indoor units with other stylish indoor


units in one system
New round flow cassette sets the standard for
efficiency and comfort
Extensive range of models and capacities for
optimal selection

Mini BMS which connects Daikin and third-party


equipment
Integrate intelligent control solutions with energy
management tools to reduce running costs

Low-temperature hydrobox

Biddle air curtain

Highly e fficient space heating through:


- Underfloor heating
- Low temperature radiators
- AHU water heat exchangers
Hot water from 25C to 45C
Cold water from +5C to +20C

Payback time less than 1.5 years compared to


electrical air curtain
A highly efficient solution for doorway climate
separation

High temperature hydrobox*

Ventilation

*only for connection to VRV heat recovery

Efficient hot water production for:


- Showers
- Sinks
- Tapwater for cleaning
Hot water from 25C to 80C

Widest range in DX ventilation from small heat


recovery ventilation to large scale air handling units
Provides a fresh, healthy and comfortable
environment
13

VRV
for offices and banks

VRV
for hotels

Efficiency in the workplace

Hospitality with economy

Efficient building and facilities management are key


to minimising operational costs

A hotels reputation depends on how welcome


and comfortable guests feel during their stay. Yet
at the same time, hotel owners must maintain
complete control of their operating costs and energy
consumption.

Our solutions for offices:


Significantly reduced costs for hot water and
heating by re-using heat recovered from areas
requiring cooling
Unique cassette integrating fully flat into
architectural ceilings
Intelligent sensors
- maximise efficiency by raising the indoor set point
or switching off the unit if there is nobody in the
room
- maximise comfort by directing the air flow away
from people to avoid cold draughts
A complete Daikin mini Building Energy
Management System (BEMS), with the Intelligent
Touch Manager
Plug & play connection to air handling units for a
healthier office atmosphere
Hot water production for sanitary use (e.g. kitchens)
and space heating (e.g. underfloor loops)
Truly reliable technical cooling down to -20C,
including duty/standby function

Check on
www.youtube.com/
DaikinEurope
14

Our solutions for hotels:


Low cost heating and hot water by recovering heat
from areas requiring cooling
The perfect personal environment for guests by
simultaneously heating spaces while cooling others
Flexible installation: the outdoor unit can be
installed outdoors to maximise hospitality space or
indoors to minimise external space or noise in city
centres
Concealed ceiling units developed for small, wellinsulated rooms such as hotel bedrooms, offering
very low sound levels ensuring a good night's rest
Smart energy management via Intelligent Touch
Manager puts the hotel owner in full control of
energy costs
Intelligent and user-friendly hotel room controllers
change the set point automatically when a guest
leaves the room or opens the window
Easy integration in hotel booking software
Hot water production for bathrooms, underfloor
heating and radiators up to 80C

Check on
www.youtube.com/
DaikinEurope

Hotel

Bank / Retail

VRV Intro

VRV
for retail

VRV
for residential use

Reducing retail costs

There is no place like home

Want to know more


about our commercial
solutions?

Commercial solutions
for small to large applications

365-days climate comfort for every business

Retailers are under pressure to reduce both store


development costs and running costs. That is why
affordable, energy-efficient solutions are vital for
minimising lifetime costs, while ensuring compliance
with the latest regulations.
Our retail solutions:

Compact inverter heat pump technology


Flexible installation: the outdoor unit can be

installed outdoors to maximise commercial space


or indoors to minimise external space or noise in
city centres
Unique round flow cassettes with autocleaning
panel saving up to 50% of energy use compared to
standard cassette units
Easy to use remote control with lock-key function
to avoid improper use
Individual control of each indoor unit or shop zone
Savings on runningcost via pre/post trade modes,
limiting energy use by lights, air conditioning, ...
The most efficient open-door solution with Biddle
air curtains

A cost effective, low energy consumption heat pump


system for home owners, offering maximum comfort
Our residential solutions:
Lower CO2 emissions compared to traditional
heating systems
Compact outdoor unit design with a low sound
level
Whisper-quiet indoor units down to 19dBA
Daikin Emura, iconic design wall mounted unit
Unique Nexura floor standing unit offering the feel
of a radiator with the efficiency of a heat pump
Units to be concealed in the wall or ceiling to make
them completely unnoticed
User-friendly, intuitive touch control, controlling
your entire shop including lights, sensors, ...
Manage and control multiple shops from a central
location via the Daikin Cloud Service
Up to 9 indoor units that can be connected to one
outdoor unit

Check on
www.youtube.com/
DaikinEurope

Residential

15

VRV IV standard &


technologies
Our new VRV IV systems set pioneering
standards in all-round climate comfort
performance. Total design simplicity, offering
rapid installation, full flexibility as well as
absolute efficiency and comfort. Find out
about all these revolutionary changes at
www.daikineurope.com/vrviv

16

VRV IV
Standard & Technologies

VRV IV =
3 revolutionary standards
Variable Refrigerant Temperature
Continuous comfort during defrost
VRV configurator

+ unique VRV IV core technologies


> Newly developed inverter compressor
> Refrigerant-cooled PCB
> 4-side heat exchanger
> Predictive control
> Outer rotor DC fan motor

17

Unique variable refrigerant

temperature

UNIQUE

Capacity & Load


in cooling mode

Cooling requirement

System
capacity

Design point

Refrigerant temperature

building

Variable Te

Efficiency with Variable


Refrigerant Temperature

Efficiency up

20

25

30

Calculate the benefit of variable


refrigerant temperature for your
project in our seasonal solutions
calculator:
http://extranet.daikineurope.com/en/software/
downloads/solutions-seasonal-simulator/default.jsp

Success story
Real test: up to 46% less energy consumed
A field trial was carried out in a shop of a fashion chain in
Germany and showed that the innovative Daikin VRV IV
delivers dramatically better energy efficiency compared
with previous models.
The trial results showed that the new VRV IV system
consumed up to 60% less energy than the VRV III system,
particularly during cooling. Overall energy savings during
heating averaged 20%.
18

Adjust capacity by
Te control to meet
the load (avoid over
capacity and ON/OFF
operation)

Fixed Te

Seasonal efficiency

the cooling need of the

temperature can be
the higher the efficiency

UNIQUE

Daikin VRV IV
Variable Refrigerant Temperature control for energy
saving in partial load condition.
The capacity is controlled by the inverter compressor
and variation of the evaporating (Te) and condensing
(Tc) temperature of the refrigerant in order to
achieve the highest seasonal efficiency.
Evaporating temperature can vary between 3 and 16
which is the widest on the market.

the higher the refrigerant

VRF standard
Capacity is controlled only with the variation of the
inverter compressor

The lower the capacity need,

How does it work?

temperature,

Seasonal efficiency increased by 28%


The first weather accommodating control on
the market
Customer comfort is assured thanks to higher
outblow temperatures (preventing cold
draughts)

The higher the refrigerant

Thanks to its revolutionary variable refrigerant


temperature technology (VRT), VRV IV continuously
adjusts both the inverter compressor speed and the
refrigerant temperature in cooling AND heating,
providing the necessary capacity to meet the
building load with the highest efficiency at all times!

The colder it gets the lower

The biggest leap since the


inverter compressor

How effective is the VRV IV heat pump


technology?
The trial demonstrated that by using air, an
infinitely renewable and free energy source,
the VRV IV system provides a complete and
environmentally sustainable solution for
heating, cooling and ventilation in commercial
applications. The trial also showed that only by
monitoring climate control systems carefully
and intelligently businesses can identify and
control energy waste. This is a service which
Daikin also offers.

35

Outdoor temperature

VRV IV
Standard & Technologies

Check on

8 Different modes to
maximise efficiency
and comfort

https://www.youtube.com/
DaikinEurope

For maximum energy efficiency and customer


satisfaction, the outdoor unit needs to adapt
the evaporating/condensing temperature at the
optimum point for the application.

How to set the different


modes?
Set up the main operation mode
of the system

Define how the system reacts


to changing loads

Step 1

Step 2

Automatic*

Evaporating AND condensing temperature automatically


selected according to ambient temperature
Quick reaction speed

Powerful

6
pa

te nt s

Where a quick increase of load is expected such as conference rooms.


Quick reaction speed to changing load has priority, with temporarily colder
outblow as a result.

Top efficiency

The perfect balance:


Achieves top efficiency throughout the year,
reacts quickly on the hottest days

High sensible
Target Te can be selected between 7Cto 11C

Quick reaction speed

Top efficiency

Year round top efficiency

Basic

Quick

Same as above but slower response than the powerful mode.

Mild *

This mode would be suitable for most office applications


and it is the factory set mode.
The perfect balance: Slower reaction speed with top efficiency

Powerful

Quick

Same as above but slower response.

Mild

The air off temperature remains fairly constant.


Suitable for low ceiling rooms.

Eco

Coil temperature would not change due to fluctuating load.


Suitable for computer rooms. Suitable for low ceiling rooms.

No submodes

Current VRF standard

Gives customer choice for fixing coil temperature which avoids cold draughts.
A quick reaction speed to changing load has priority, with temporarily colder
outblow as a result.

This is how most other VRF systems work and can be used for all general type of
applications. Suitable for computer rooms.
Suitable for low ceiling rooms.

* Factory setting

VRV III 20HP (2 modules)

VRV IV 18HP (1 module)

March 2012 - February 2013

March 2013 - February 2014

Avg (kWh/Month)

2.797

1.502

Total (KWh)

33.562

18.023

Total ()

6.041

3.244

9,9

5,3

Period

Yearly (operation
cost/m (/m)

46% savings = 2.797

Measured data
Fashion store Unterhaching (Germany)
Floor space: 607m
Energy cost: 0,18 /kWh
System taken into account for consumption:
- VRV IV heat pump with continuous heating
- Round flow cassettes (without auto cleaning panel)
- VAM for ventilation (2x VAM2000)
- Biddle Air curtain.

19

Real continuous
heating
during defrost mode
VRV IV continues to provide heating even when
in defrost mode, providing an answer to any
perceived disadvantages of specifying a heat
pump as a monovalent heating system.

Check on
https://www.youtube.com/
DaikinEurope

Continuous indoor comfort ensured by the heat


accumulating element and alternate defrost
An innovative alternative to traditional heating
systems

Heat pumps are known for their high energy


efficiency in heating, but frost is accumulated on
their heat exchanger during heating operation and
this must be melted periodically using a defrost
function that reverses the refrigeration cycle. This
causes a temporary temperature drop and reduced
comfort levels inside the building.
Defrosting can take over 10 minutes (depending on
the size of the system) and occurs mostly between
-7 and +7C when humidity levels in the air are high,
Humidity freezes on the coil, resulting firstly in poor
performance and eventually low comfort levels.
The VRV IV has changed the heating paradigm by
providing heat even during defrost operation thus
diminishing the temperature drop indoors and
providing comfort at all times.

Room temperature

VRV IV

VRF benchmark

Time

How does it work?


UNIQUE

Heat accumulating element

Alternate defrost

For the VRV IV heat pump single unit systems a


unique heat-accumulating element is used. This
element, based upon phase change material,
provides the energy to defrost the outdoor unit.

On all our multi unit systems only 1 outdoor


coil is defrosted at a time, ensuring continuous
comfort during the whole process.

The outdoor unit coil is


defrosted
Kan niet aders dan met
gradient, want vloeistof
warmt op en koelt af...

with the energy stored


in the heat accumulating
element

while indoors
a comfortable temperature

the outdoor unit coil is defrosted

is maintained.

one at the time


so indoors a comfortable temperature is maintained

Available on:

Available on:

Heat pump

Heat pump

Heat recovery

even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat
Replacement VRV

RYYQ8-20T

RYYQ16-54T

REYQ10-54T

RXYQQ16-42T

RXYQ16-54T
Water cooled VRV has no defrost cycles

20

RQCEQ280-848P

VRV IV
Standard & Technologies

VRV Configurator
Check on

Software for simplified commissioning,


configuration and customisation
Graphical interface
Manage systems over multiple sites in exactly
the same way
Retrieve initial settings

https://www.youtube.com/
DaikinEurope

Configurator software for simplified


commissioning
The VRV configurator is an advanced software
solution that allows for easy system configuration
and commissioning:
less time is required on the roof configuring the
outdoor unit
multiple systems at different sites can be managed
in exactly the same way, thus offering simplified
commissioning for key accounts
initial settings on the outdoor unit can be easily
retrieved.

Simplified
commissioning

Retrieve initial system


settings
User friendly interface instead of
push buttons

7-segment display
for quick and accurate error diagnosis
Outdoor unit display for quick on-site settings and
easy read out of errors together with the indication of
service parameters for checking basic functions.
easy-to-read error report
clear menu indicating quick and easy on-site
settings
indication of basic service parameters to quickly
check basic functions: high pressure, low
pressure, frequency and operation time history of
compressors, temperature of discharge/suction
pipe.
No need to unmount the big front panel of the unit
thanks to the service access

3 digit 7-segment display

Available on:
Heat recovery

Heat pump

Replacement VRV

REYQ-T

RYYQ-T

RXYQQ-T

RXYQ-T(9)
RXYSCQ-TV1 (only configurator, no 7 segment display)
RXYSQ-TV1/TY1 (only configurator, no 7 segment display)
SB.RKXYQ-T (only configurator, no 7 segment display)

21

Unique VRV IV
core technologies
Newly developed
37
compressor
patents
High efficiency 6-pole motor

Full inverter

50% stronger magnetic field and higher rotation

Enabling variable refrigerant temperature and low

efficiency

start-up currents
Stepless capacity control

Thixocasting process

Reluctance brushless DC motor

Compression volume is increased by 50% thanks

to a new high-durability material cast in a semimolten state

increased efficiency compared to AC motors

by simultaneously using normal and reluctance


torque
Powerful neodymium magnets efficiently
generate high torque
High-pressure oil reduces thrust losses

Refrigerant-cooled PCB
Reliable cooling because it is not influenced by

ambient air temperature


Smaller switchbox for smoother air flow

through the heat exchanger increasing


heat exchange efficiency with 5%

UNIQUE

patents

4-sided, 3-row heat


exchanger
Heat exchange surface up to 50% larger
(up to 235m2), leading to 30% more

efficiency

22

10

patents

Target

Predictive Control
Function (PCF)

General VRF:
Double time against VRV IV

Reaching targets faster


Reaching targets without overshooting, so there is
no waste, resulting in improved efficiency
The large number of Daikin systems already in
operation and which are monitored by our i-Net
software put us in the unique position of being
able to analyse this data and develop the predictive
control function.

2t

(VRV IV)

(general VRF)

VRV IV with PCF


General VRF with PI control
Target capacity/refrigerant temperature

VRV IV: PCF


Compressor works with predictive data for the control

result: quick convergence to the target temperature


and reduction of waste operation of the compressor

Half time
against
general
VRF

General VRF: Pi control


Compressor works with feedback only for the control

result: waste operation and longer time before reaching


target set point

DC fan motor
UNIQUE
Outer rotor DC motor for higher efficiency

Conventional motor with inner rotor

Daikin outer rotor

Larger rotor diameter results in greater force

for the same magnetic field, leading to better


efficiency
Better control, resulting in more fan steps to
match the actual capacity

Sine wave DC inverter

Optimizing the sine wave curve results in smoother


motor rotation and improved motor efficiency.
Rotor

DC fan motor

Stator

Stator

Rotor

The use of a DC fan motor offers substantial


improvements in operating efficiency compared to
conventional AC motors, especially during low speed
rotation.

E-Pass heat exchanger


Optimising the heat exchangers path layout prevents
heat being transferred from the overheated gas
section to the sub-cooled liquid section which is a
more efficient way to use the heat exchanger.

I-demand function

Standard heat exchanger

e-Pass heat exchanger

In 85C

In 85C
43C

55C
27C

55C

27C

60C

50C

55C

Out 45C

Out 45C

Power consumption
Predefined limit

Limit maximum power consumption.


The newly introduced current sensor minimizes
the difference between the actual power
consumption and the predefined power
consumption.

Time

23

VRV IV
Standard & Technologies

UNIQUE

The VRV benefits


See how you can benefit from Daikin's highly
flexible and efficiency product range

24

Benefits

VRV
Latest technology, highest efficiency
VRV, a total commercial solution
Drastically reducing your running costs
26
Top reliability
Up to 6 times greater resistance against corrosion

Comfort guaranteed at all times

28

Maximum flexibility

30

Fast installation and commissioning


Easy servicing

32

25

Drastically reducing running costs


Top reliability
Up to 6 times greater resistance
against corrosion

ON

ON

Precise zone control


VRV systems have low running costs because it
permits each zone to be controlled individually. That
is, only those rooms that require air conditioning will
be heated or cooled, while the system can be shut
down completely in rooms where no air conditioning
is required.

OFF

Anti Corrosion Treatment

ON
OFF

An anti-corrosion heat exchanger cutaway view


Hydrophilic film

Special anti corrosion treatment of the heat exchanger


provides 5 to 6 times greater resistance against acid
rain and salt corrosion.
The provision of rust proof steel sheet on the
underside of the unit gives additional protection.

Performed tests:
VDA Wechseltest
Contents of 1 cycle (7 days):
24 hours salt spray test SS DIN 50021
96 hours humidity cycle test KFW

DIN 50017
48 hours room temperature & room humidity

Aluminium

Heat exchanger

Corrosion-resistant
Acrylic resin

Degree
of corrosion
8
7
6
5
4
3
2
1
0
1 2 3 4 5

Cycle

testing period: 5 cycles

Bare aluminium
DAIKIN P.E.

Degree of

Kesternich test (SO2)


contents of 1 cycle (48 hours)

according to DIN50018 (0.21)


testing period : 40 cycles

corrosion
10
9
8
7
6
5
4
3
2
1
0


1 2 3 4 5 6 10 20 30 40 50 60 70

Cycle

26

Benefits

Technical benefits VRV

Kan niet aders dan met


gradient, want vloeistof
warmt op en koelt af...

All inverter compressors


All inverter control compressors allow to control the
refrigerant volume almost stepless. In this way the
capacity perfectly matches the different loads in every
room avoiding unnecessary energy use.

ALL

Additionally all inverter compressors also allow


precise refrigerant temperature control, automatically
adapting your VRV to your building and climate
requirements, reducing running costs with 28%.
Even more, having no ON/OFF compressors, means
total absence of high starting currents, which are being
more and more limited by the grid operators and power
suppliers.

Duty Cycling extends


operation life
The cyclical start-up sequence of multiple outdoor
units systems equalises compressor duty and extends
operating life.

Sequential Start
Up to 3 outdoor units can be connected to 1 power
supply and can be turned on sequentially. This allows
the number of breakers and their capacities to remain
small and simplifies wiring (for models of 10HP or less).

Only one power supply

1 v/d 2 kiezen

Top quality
Only brazed connections

Flare or flange

All flange and flare connections inside the unit


have been replaced by brazing connections to
ensure improved refrigerant containment. Also the
connection of the outdoor in the main pipe is brazed.
Brazing

27

Comfort guaranteed at all times

Smart Control brings


comfort
Stable room temperature
Suction air temp.

An electronic expansion valve, using PID


(Proportional Integral Derivative) control,
continuously adjusts the refrigerant volume in
respond to load variations of the indoor units.
The VRV system thus maintains comfortable room
temperatures at a virtually constant level, without the
temperature variations typical of conventional ON/
OFF control systems.

Cooling

Stable room temperature

Time
VRV SERIES (DAIKIN indoor unit (PID controlled))

Note: The graph shows the data, measured in a test room assuming
actual heating load. The thermostat can control stable room

ON/OFF controlled indoor unit (2.5HP)

temperature at 0.5C from set point.

No more cold draught


Automatic or manual adjustment of refrigerant
temperature leads to higher outblow temperatures
which avoid the cold draught coming from the
indoor unit.

16

Constant and high

Available on all VRV IV units

air discharge temperature


Room temperature

Continuous heating
During defrost
Indoor comfort not effected via the unique heat
accumulating element or alternate defrost
The best alternative to traditional heating systems

VRV IV
VRF benchmark

Available on REYQ-T, RYYQ-T, RXYQ-T(9)


and RXYQQ-T

Time

Back-up function
In the event of a compressor malfunction another
compressor or outdoor unit will take over in order
to maintain 8 hour interim capacity, allowing time
for maintenance or repair while comfort remains
guaranteed.
Single outdoor unit
with multiple compressors

28

Multi outdoor unit system

Low indoor unit


operation sound level
Daikin indoor units have very low sound operation
levels, down to 19dB(A), making them ideal for
sound sensitive areas as hotel bedrooms, etc

Benefits

Technical benefits VRV

db(A)

Perceived loudness

Treshold of hearing

Sound
-

20

Extremely soft

Rustling leaves

40

Very soft

Quiet room

60

Moderately loud

Normal conversation

80

Very loud

City traffic noise

100

Extremely loud

Symphonic orchestra

120

Threshold of feeling

Jet taking off

Daikin indoor units:


FXZQ-A

emura

19dB(A)

25.5dB(A)

Connectable to all VRV heat pumps

Connectable to VRV IV, VRV IV S-series


and VRV IV W-series*
* VRV IV W-series on special order. Consult your
local sales representative for more information

Night quiet mode


For areas where there are stringent limitations to
sound levels, the outdoor unit sound level can be
automatically reduced to meet the requirement.

Peak in the outdoor


temperature
100%
8 hrs

10 hrs

50%

Capacity* %
Load %
Operation Sound dBA

Night mode

Step 1

To manually set set the time for low noise


operation you can use the external control
adaptor DTA104A61/62/53.

Step 2

Night mode STARTS

Night mode ENDS

Example for VRV IV heat pump, factory setting.

<

00000

29

Maximum flexibility
Wide operation range
Air cooled

Water cooled

The VRV system can be installed practically anywhere.


VRV air cooled outdoor units can cool between
-20C BD and +52C DB outdoor ambient and can be
used as monovalent heating system between -25C
WB and +15.5C WB.

Standard water cooled outdoor units operation


between 10C & 45C for both heating and cooling.
In geothermal mode, the operation range is
extended to -10C* during heating and 6C during
cooling. These units are not influenced by external
conditions and function well in extreme climates.

-10C

-20C DB

52C DB

-25C WB

15.5C WB

45C

Heating mode water temperature


6C

* Ethylene glycol should be added to the water when the water inlet

45C

Cooling mode water temperature

temperature is below 5C
Cooling mode

Heating mode

With the technical cooling function, the operation range in cooling


of the heat recovery system is extended from -5C to -20C1, making
it perfect for integrating server rooms.

even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat

Contact your local dealer for more information and restrictions


VRV-W

90m piping
length after first
branch

VRV-W

30m Level difference


between indoor units

The long piping lengths, high level differences and


small refrigerant piping allows for a design with little
limitations and leaving maximum space for lettable
space.

VRV-W

40m (90m1) Level difference


between indoor and outdoor units

Flexible piping design

165m Actual piping length

even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat

Indoor installation
Unlimited water piping length

VRV IV example
Air cooled
Total piping length

Water cooled

1000m

300m

165m (190m)

120m (140m)

Longest length after first branch

90m1

40m (90m1)

Level difference between indoor and outdoor units

90m

50m (40m)

Level difference between indoor units

30m

15m

Longest length actual (Equivalent)


1 Contact your local dealer or consult technical literature for more information and restrictions
2 In case outdoor unit is located below indoor units

Phased installation
Installation of the VRV system can be implemented
floor by floor, so that sections of the building can
be put into use very quickly, or enabling the air
conditioning system to be commissioned and
operated in stages, rather than on final completion of
the project.

30

Under construction

VRV system

Installation
floor by floor

Technical benefits VRV

Indoor installation
Water cooled

Air cooled

Seamless integration in the surrounding


architecture as you cannot see the unit
Highly suited for sound sensitive areas as there is
no external operation sound
Superior efficiency, even in the most extreme
outside conditions, especially in geothermal
operation

ESP up to

78.4 Pa

VRV IV i-series heat pump for indoor installation


The ultimate and unique solution from Daikin is
to use the VRV IV i-series. This unit is optimised for
indoor installation and is the most flexible solution,
without the need for a large technical room to put
the outdoor unit and it is complete invisible!

Benefits

Standard outdoor unit installed indoors


The VRV optimised fan blade shape increases output
and reduces pressure loss. Together with the high ESP
setting (up to 78.4 Pa), it makes VRV outdoor units
ideal for indoor installation using ducts.

More details on page 76

Multiple tenants,
one outdoor unit
The multi tenant function ensures that the entire VRV
system does not shut down when the main power
supply of an indoor is switched off.
This means that the indoor units main power supply
can be turned off when a part of the building is
closed or is being serviced without affecting the rest
of the building.

operation
in holiday

in service
operation

2 solutions according to the needs:


Service setting, without additional hardware: for
service execution within 24 hours
PCB option: when tenants leave for a longer period
(holiday) and the main power supply is shut down

multi tenant

No structural
reinforcement necessary
Thanks to the vibration-free and sufficient light
construction of the outdoor units, floors do not need
to be reinforced, reducing the overall cost of the
building when compared to a chiller.

max. 398kg for a 20HP unit

31

1 v/d 2 kiezen

Fast installation and commissioning


Easy servicing
Automatic charging & testing
Efficient use of time
1

Calculate extra

Connect first bottle

Check on regular

Stop manually

refrigerant volume

on VRV & start

times weight scale

the VRV filling procedure

filling process

to check weight of

& close valves

Manual

foto in 4crkeltje zou ik


behouden

refrigerant

Automatic

Push button
on the PCB

Connect bottle

Filling procedure

to VRV & active automatic

stops automatically:

charging function

close valves

R410-A

After charging pushing the test operation button initiates a check

If the temperature drops below 20C* manual charging is necessary.

on the wiring, shut off valves, sensors and refrigerant volume.

* 10C for heat pump for cold regions


even checken in de
infographics
ik denk RQCEQ-P3
naam
op gasfleson
eventueel
* Available
REYQ-T, RYYQ-T, RXYQ-T(9), RTSYQ-PA,
RQYQ-P,map:
RXYQQ-T,
dat er een tekening van
vervangen door echt logo
een VRV bestaat

Did you know


Optimal charge = optimal efficiency
Planned installation
64 m refrigerant piping

10% undercharged

calculation:
2.2 kg extra refrigerant required

0.5 kg

up to 25% capacity loss

Real installation
76 m refrigerant piping

2.7 kg extra refrigerant


required in reality

33% more energy use

Compliance to
F-gas regulation

When activating the refrigerant containment check, the unit switches into cooling
mode and duplicates certain reference conditions based on memory data.
The result indicates whether or not refrigerant leakage has occurred.

Remote refrigerant containment check

The refrigerant volume of the complete system is calculated for the following data:

Perform the refrigerant containment check remotely


via intelligent Touch Manager.

Outdoor temperature
Reference system temperatures
Reference pressure temperatures
Refrigerant density
Types and number of indoor units

Remotely set the time and start the refrigerant containment

Connect to customer site via internet or 3G increasing customer

check when it is most convenient for you.

satisfaction as there is no disruption to the air conditioning


during business hours.

Available on RYYQ-T, RXYQ-T(9), REYQ-T, RTSYQ-PA


Next to remote checking, the function can also be activated on-site via a push button on the PCB.

32

Check the report once the check has been done.

warmt op en koelt af... warmt op en koelt af...

Technical benefits VRV

VRV configurator software


even checken in de
even checken in de
infographics map: ik denk
infographics map: ik denk
dat er een tekening van dat er een tekening van
een VRV bestaat
een VRV bestaat

For simplified commissioning, configuration and


customisation

Available on REYQ-T, RYYQ-T, RXYQ-T(9),


RXYSCQ-TV1, RXYSQ-TV1/TY1, SB.RKXYQ-T
and RXYQQ-T

3 digit 7-segment display

push buttons
Benefits

1 v/d 2 kiezen

User friendly interface instead of

1 v/d 2 kiezen

Compact design
The compact design of the outdoor units is sufficient
to allow them to be taken up to the top of a
building in a commercial elevator, overcoming site
transportation problem, particularly when outdoor
units need to be installed on each floor.
foto in crkeltje zou ik
behouden

foto in crkeltje zou ik


behouden

Push button
on the PCB

Daikin unified REFNET


piping
R410-A

Push button
on the PCB

R410-A

The unified Daikin REFNET piping system is designed


even checken in de
even checken in de
infographics map: ik denk
naaminstallation.
op gasfles eventueel
infographics map: ik denk
for simple
naam op gasfles eventueel
dat er een tekening van dat er een tekening van
vervangen door echt logo
vervangen door echt logo
een VRV bestaat
een VRV bestaat
Compared to regular T-joints, where refrigerant
distribution is far from optimal, the Daikin REFNET
joints have specifically been designed to optimise
refrigerant flow.

REFNET joint

T-joint

REFNET joint

REFNET
header

Daikin Europe N.V. advises only to use Daikin REFNET piping system.

Easy wiring Super Wiring System


Simplified wiring
Shared use of wiring between indoor units, outdoor
units and centralised remote control
Easy retrofit of centralised remote control
Impossible to make incorrect connections thanks to
non polarity wiring
Sheated wire can be used
Unique total wiring length up to 2,000 m

Cross wiring check


The cross wiring check function warns operatives of
connection errors in inter unit wiring and piping.

Auto Address Setting Function


Allows wiring between indoor and outdoor units, as
well as group control wiring of multiple indoor units,
to be performed without the bothersome task of
manually setting each address.
* auto adress setting fuction is not available for centralized operation

33

VRV Outdoor Systems


For every application a solution

34

Overview of

Widest
range of
BS boxes

Unique
continuous
heating

Widest
range

VRVIV
VRVIV
VRVIV
heat
heat pump VRV IV
Heat
pump with without
S-series
recovery continuous continuous (compact)
heating
heating

Unique
product

VRV IV
i-series

VRV III-C

VRV
Classic

Replacement
VRVIV
heat pump

Replacement
VRV III
Heat
recovery

Water
cooled
VRVIV

REYQ-T

RYYQ-T

RXYQ-T(9)

RXYSCQ-TV1
RXYSQ-TV1
RXYSQ-TY1

SB.RKXYQ-T

RTSYQ-PA

RXYCQ-A

RQYQ-P
RXYQQ-T

RQCEQ-P

RWETQ-T8

Page

40

50

50

58

76

88

94

99

99

110

Variable Refrigerant Temperature

Continuous heating
(alternate defrost)

Continuous heating
(heat accumulating element)

VRV configurator
7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode
Low noise function
Connectable to stylish indoor units
(Daikin Emura, Nexura)

Connectable to LT hydrobox for hot water

Connectable to HT hydrobox for hot water


Full inverter compressors
Gas cooled PCB
4 side heat exchanger
Reluctance brushless DC compressor
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function /
power limitation

(1)

not available on
RXYSQ4,5,6,8TY1

Outdoor Unit Product Range

functions

(1)

(1) special order unit. Contact your local sales representative

35

Outdoor units

Products overview
VRV IV heat recovery

Air cooled - heat recovery

Model

Product name
Best efficiency & comfort solution
Fully integrated solution with heat recovery for maximum efficiency
Covers all thermal needs of a building via a single point of contact: accurate
temperature control, ventilation, hot water, air handling units and Biddle air
curtains
Free heating and hot water through heat recovery
The perfect personal comfort for guests/tenants via simultaneous cooling and
heating
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature and continuous heating
Allows technical cooling
Widest range of BS boxes on the market

PG

8 10 12 13 14 16 18 20 22 24 26 28

REYQ-T

VRV IV heat pump


without continuous
heating

VRV IV heat pump


with continuous
heating

Daikins optimum solution with top comfort

VRVIV-S
series
Compact

NEW
VRVIV-S
series

Air cooled - heat pump

NEW

RXYQ-T(9)

temperature control, ventilation, air handling units and Biddle air curtains
Either connect VRV of stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as Variable Refrigerant
temperature


RXYSCQ-TV1

temperature control, ventilation, air handling units and Biddle air curtains
Either connect VRV of stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as Variable Refrigerant
temperature

58

Compact

Space saving solution without compromising on efficiency

Space saving trunk design for flexible installation


Covers all thermal needs of a building via a single point of contact: accurate

RXYSQ-TV1/
TY1

TV1
65

TY1

The invisible VRV

Unique VRV heat pump for indoor installation


Total flexibility for any shop location and building type as the outdoor unit is
invisible and split up in 2 parts

Incorporates VRV IV standards & technologies such as Variable Refrigerant

SB.RKXYQ-T*

82

temperature
Covers all thermal needs of a building via a single point of contact: accurate
temperature control, ventilation and Biddle air curtains

Where heating is priority without compromising on efficiency

VRV Classic
heat recovery

Suitable for single source heating


Extended operation range down to -25C in heating
Stable heating capacity and high efficiencies at low ambient temperatures

For standard cooling & heating requirements


Connectable to VRV indoor units, controls and ventilation
Cost-effective and fast replacement through re-use of exisiting piping
Drastically improve your comfort, efficiency and reliability
No interuption of daily business while replacing your system
Replace Daikin and other manufacturers systems safely
Cost-effective and fast replacement through re-use of exisiting piping
Drastically improve your comfort, efficiency and reliability
No interuption of daily business while replacing your system
Replace Daikin and other manufacturers systems safely
Incorporates VRV IV standards & technologies such as

Classic VRV configuration

Quick & quality replacement for R-22 and R-407C systems

RTSYQ-PA

RXYCQ-A

RQCEQ-P*

88

94

99

Quick & quality replacement for R-22 and R-407C systems

RXYQQ-T*

* Not Eurovent certified

103

RWEYQ-T8*

110

Single unit
Multi combination

special order unit

Ideal for high rise buildings, using water as heat source


emissions thanks to the use of geothermal energy as a renewable
2
energy source
No need for an external heating or cooling source when used in geothermal
mode
Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units
and Biddle air curtains
Compact & lightweight design can be stacked for maximum space saving
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature
Variable Water Flow control option increases flexibility and control

Water cooled VRV IV

50

The most compact VRV

Compact and lightweight single fan design saves space and is easy to install
Covers all thermal needs of a building via a single point of contact: accurate

heat pump

VRV III heat


pump, optimised
for heating

Daikins solution for comfort & low energy consumption

2nd half 2016

Replacement

Reduced CO
Water cooled

50

Variable Refrigerant temperature

36

VRV IVheat
pump for
indoor installation

NEW

RYYQ-T

Covers all thermal needs of a building via a single point of contact:

accurate temperature control, ventilation, hot water, air handling units


and Biddle air curtains
Connectable to stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature

44

Continuous heating during defrost


Covers all thermal needs of a building via a single point of contact:

accurate temperature control, ventilation, hot water, air handling units and
Biddle air curtains
Connectable to stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature and continuous heating

Air curtains CYV-DK-

HRV units VAM-, VKM-

AHU connection
EKEXV- + EKEQMCBA
AHU connection
EKEXV- + EKEQFCBA

HT Hydrobox HXHD-A

LT Hydrobox HXY-A

VRV IV Heat Recovery REYQ-T

O O

with only VRV indoor units

with LT/HT Hydroboxes

HRV units VAM-, VKM-

AHU connection EKEXV + EKEQMCBA

Biddle air curtain CYV-DK-

VRV IV Heat Pump RYYQ-T / RXYQ-T(9)

--Standard total system connection ratio limit: 50 ~ 130%

with only VRV indoor units

--200% total system connection ratio possible under special


circumstances

with residential indoor units

with LT Hydroboxes

HRV units VAM-, VKM-

AHU connection EKEXV + EKEQMCBA

Biddle air curtain CYV-DK-

VRV IV-S RXYSQ-/RXYSCQ-

O O O

with VRV indoor units only

--Standard total system connection ratio limit: 50 ~ 130%

--Max 32 indoor units, even on 16HP and larger systems


--Total system connection ratio up to 200% possible

--Dedicated systems (with only ventilation units) not allowed


a mix with standard VRV indoor units is allways neccessary

--Only single-module systems (RYYQ 8~20 T / RXYQ 8~20 T)


--Max 32 indoor units, even on 16HP, 18HP and 20HP systems

--Max 32 indoor units, even on 16HP and larger systems


--Contact Daikin in case of multi-module systems (>20HP)

AHU connection EKEXV + EKEQFCBA

--Standard total system connection ratio limit: 50 ~ 130%

with residential indoor units only

Remarks

-- With residential indoor: connection ratio limit: 80 ~ 130%

VRV IV i series SB.RKXYQ-T

O O O O

--Standard total system connection


ratio limit: 50 ~ 130%

VRV III Cold Region RTSYQ-PA

O O O O

--Standard total system connection


ratio limit: 50 ~ 130%

VRV Classic RXYCQ-A

O O O O O O

--Standard total system connection ratio limit: 50 ~ 120%


--In case of using at least one FXFQ20~25 indoor units on 8HP or
10HP models, the maximum connection ratio is 100%.

VRV III-Q Replacement H/R


RQCEQ-P

O O O O O O

--Standard total system connection


ratio limit: 50 ~ 130%

VRV IV-Q Replacement H/P


RXYQQ-T

O O O O

--Standard total system connection


ratio limit: 50 ~ 130%

VRV IV-W Water-cooled VRV


RWEYQ-T8

--Standard total system connection


ratio limit: 50 ~ 130%

with VRV indoor units

special order unit

with split indoor units

with HT hydrobox

--special order unit, contact your local sales representative

--special order unit, contact your local sales representative

... connection of indoor unit possible, but not neccessarily simultaneously with other allowed indoor units
... connection of indoor unit possible even simultaneously with other checked units in the same row
O ... connection of indoor not possible on this outdoor unit system

37

Outdoor Unit Product Range

VRV indoor units

Capacity (HP)
30 32 34 36 38 40 42 44 46 48 50 52 54 Description / Combination

Residential indoor units

Outdoor units

VRV Outdoor

EIFFAGE ENERGIE ET EIFFAGE ENERGIE THERMIE


OFFICE BUILDING
VRV IV HEAT PUMP WITH CONTINUOUS HEATING

PARK PHI
BREEAM EXCELLENT OFFICE BUILDING
WATERCOOLED VRV

VRV IV i-SERIES VRV IV HEAT PUMP


FOR INDOOR INSTALLATION

38

VRV Outdoor

Outdoor Unit Product Range

HOTEL LE PIGONNET, 8 REPLACEMENT VRV

VRV IV S-SERIES

CINEMEERSE, CINEMA, 12 OUTDOOR UNITS WITH AHU

39

VRV IV heat recovery


Best efficiency and comfort solution
Efficie

22

Air curtain

system

Biddle Air curtain for VRV (CYV)


Indoor units
VRV type indoor units
Hot water
Low temperature hydrobox
High temperature hydrobox

Control systems

Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit

Widest range of BS boxes for the fastest installation

7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode
Low noise function

VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort

Continuous heating
The new standard in heating comfort

VRV configurator
Software for simplified commissioning,
configuration and customisation
40

Connectable to LT hydrobox for hot water


Connectable to HT hydrobox for hot water
Full inverter compressors
Gas cooled PCB
4 side heat exchanger
Reluctance brushless DC compressor
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function

3-pipte

North

Cooling

Extracted heat delivers


free hot water and heating

Hot water

Outdoor Unit Product Range

+
South

Heating

Free heat and hot water


production
Until now, most commercial buildings have relied
on separate systems for cooling, heating, hot
water and so on, which results in a lot of wasted
energy.
An integrated heat recovery system reuses heat
from offices, server rooms, to warm other areas or
create hot water.

Maximum comfort
A VRV heat-recovery system allows simultaneous
cooling and heating.
For hotel owners, this means a perfect
environment for guests as they can freely
choose between cooling or heating.
For offices, it means a perfect working indoor
climate for both north and south-facing offices.

Cooling load

Improved efficiency

Improved mix
mode control

In heat-recovery operation the VRV IV is up to 15%


more efficient compared to VRV III. In single mode
operation, the seasonal efficiency of the system
can be even as much as 28% higher - thanks to
the variable refrigerant temperature technology compared to a conventional VRF system.

Ambient
temperature

Heating load

Optimised Partition
of Heat Exchanger for
highest seasonal efficiency
in heat recovery mode

30%

70%
During heating, the bottom of the heat exchanger stays hot,

Vertically divided heat exchanger with an


optimized ratio for mix mode operation.
This improves heat recovery efficiency by
reducing radiation losses.

which minimises frost accumulation and defrost periods.

Wide heating
operation range

-15

-10

-5

-20

-15

-10

-5

-20CWB

15
15
15.5CWB

Heating

-25

VRV IV heat recovery has a standard operation range


down to -20CWB in heating.
It can also provide cooling down to -20CDB for
technical server rooms (field setting).

-20

-20

-15

-10

-25CDB -20CDB

-25

-20

-5

43 45

-5CDB

-15

-10

Technical Cooling

-5

43CDB

43 45
Cooling

41

Advantages
of 3-pipe technology
More free heat
Daikin 3-pipe technology needs less energy to
recover heat, meaning significantly higher efficiency
during heat recovery mode. Our system can recover
heat at a low condensing temperature because it has
dedicated gas, liquid and discharge pipes.

5
moreto 15%
efficie
in hea
nt
t reco
ver

Pressure

comp
a

red to

Condensing 55 C

Condensing 45 C

In a 2-pipe system, gas and liquid travel as a mixture


so the condensing temperature needs to be higher
in order to separate the mixed gas and liquid
refrigerant. The higher condensing temperature
means more energy is used to recover heat resulting
in lower efficiency.

Lower pressure drop


means more efficiency

system

y mod
e
2-pipe

Power input Daikin


Power input 2-pipe system
Enthalpy

Up
more to 5%
co
capac oling
ity
av

Pressure

Smooth refrigerant flow in 3-pipe system thanks to

3-pipe VRV H/R

2 smaller gas pipes results in higher energy


efficiency
Disturbed refrigerant flow in large gas pipe on
2-pipe system results in bigger pressure drop

2-pipe system

ailable
a
piping t longer
length
comp
s
ared t
o 2-pip
e
system

Pipe length

Save on refrigerant
Smaller diameter pipes and 3-pipe system results

Total piping length


Longest length actual (Equivalent)

1000m
165m (190m)

Longest length after first branch

90m1

Level difference between indoor and outdoor units

90m1

Level difference between indoor units

30m

Outdoor unit in highest position. Consult your local sales


representative for restrictions on piping lengths

42

90m maximum

Flexible piping design

30m Level difference between indoor units

Combine outdoor units flexibly to reduce your carbon


footprint, optimise your system for continuous heating,
and achieve the highest efficiency.

165m Actual piping length

Freely combine outdoor


units

90m1 Level difference between indoor


and outdoor units

in up to 36% less refrigerant charge compared


to 2-pipe systems, saving on refrigerant cost and
reducing environmental impact

Fully redesigned

BS boxes
Maximum design flexibility
and installation speed
Quickly and flexibly design your system with a
Outdoor Unit Product Range

unique range of single and multi BS boxes.


A wide variety of compact and lightweight multi

BS boxes greatly reduces installation time.


Free combination of single and multi BS boxes

Single port
Unique to the market
Compact and light to install
No drain piping needed
Ideal for remote rooms
Technical cooling function
Connect up to 250 class unit (28 kW)
Allows multi-tenant applications

BS1Q 10, 16, 25 A

Multi port: 4 6 8 10 12 16
Up to 55% smaller and 41% lighter than

previous range
Faster installation thanks to a reduced number
of brazing points and wiring
All indoor units connectable to one BS box
Fewer inspection ports needed
Up to 16 kW capacity available per port
Connect up to 250 class unit (28kW) by
combining 2 ports
No limit on unused ports, permitting
phased installation
Allows multi-tenant applications

BS 4 Q14 A

BS 6, 8 Q14 A

BS 10, 12 Q14 A

BS 16 Q14 A

Faster installation thanks to open connection


No need to cut the pipe before brazing for

indoor units smaller or equal to 5.6 kW (50 class)

Cut and braze the pipe for indoor

units bigger or equal to 7.1 kW (63 class)

Maximum comfort at
all times
With the VRV BS box, any indoor unit not being used
to switch between heating and cooling maintains
the constant desired temperature. This is because
our heat recovery system does not need to equalise
pressure over the entire system after a change-over.

Off

BS box

43

REYQ-T
Up to 30m indoor unit
height difference

VRV IV heat recovery


Best efficiency & comfort solution
Fully integrated solution with heat recovery for maximum
efficiency with COPs of up to 8 !
Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, hot water, air handling
units and Biddle air curtains
Free heating and hot water production provided by transferring
heat from areas requiring cooling to areas requiring heating or hot
water
The perfect personal comfort for guests/tenants via simultaneous
cooling and heating
Continuous heating during defrost

Outdoor system
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

GWP
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

8T
8
22.4 (1) / 22.4 (2)
22.4 (3) / 22.40 (4)
25.0 (3)
5.31 (1) / 4.56 (2)
4.75 (3) / 4.47 (4)
5.51 (3)
4.22 (1) / 4.92 (2)
7.41
6.25
kW 4.72 (3) / 5.01 (4)
kW
4.54 (3)
100
200
260

mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
mm
m
Hz/V
A
REYQ

Outdoor unit module 1


Outdoor unit module 2
Nom.
Nom.
Max.
Cooling
Heating

* Check engineering data for restrictions

HP
kW
kW
kW
kW
kW
kW
kW

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
Continuous heating

44

Actual

REYQ
HP
kW
kW
kW
kW
kW
kW
kW

kW
kW

Actual

mm
mm
mm
m
A

210
162
78

Incorporates VRV IV standards & technologies: Variable Refrigerant


Temperature, continuous heating, VRV configurator, 7 segment
display and full inverter compressors, 4-side heat exchanger,
refrigerant cooled PCB, new DC fan motor
Free combination of outdoor units to meet installation space or
efficiency requirements
Possibility to extend the operation range in cooling down to -20C
for technical cooling operation such as server rooms
Contains all standard VRV features

10T
10
28.0 (1) / 28.0 (2)
28.0 (3) / 28.00 (4)
31.5 (3)
7.15 (1) / 6.19 (2)
6.29 (3) / 5.47 (4)
7.38 (3)
3.92 (1) / 4.52 (2)
7.37
5.78
4.45 (3) / 5.12 (4)
4.27 (3)

12T
14T
12
14
33.5 (1) / 33.5 (2) 40.0 (1) / 40.0 (2)
33.5 (3) / 33.5 (4) 40.0 (3) / 40.00 (4)
37.5 (3)
45.0 (3)
9.23 (1) / 8.31 (2) 10.7 (1) / 9.61 (2)
8.05 (3) / 6.83 (4) 9.60 (3) / 9.37 (4)
9.43 (3)
11.3 (3)
3.63 (1) / 4.03 (2) 3.74 (1) / 4.16 (2)
6.84
7.05
5.36
5.45
4.16 (3) / 4.90 (4) 4.17 (3) / 4.27 (4)
3.98 (3)
64 (5)
150
175
300
350
390
455

125
250
325
1,685x930x765
218
175
79
58

304
223

185
81
61

16T
16
45.0 (1) / 45.0 (2)
45.0 (3) / 45.00 (4)
50.0 (3)
12.8 (1) / 11.9 (2)
11.2 (3) / 9.88 (4)
12.9 (3)
3.52 (1) / 3.79 (2)
6.63
5.14
4.02 (3) / 4.56 (4)
3.88 (3)

18T
18
50.4 (1)
50.4 (3)
56.5 (3)
15.2
12.3 (3)
14.3
3.32
6.26
4.84
4.10 (3)
3.95

200
225
400
450
520
585
1,685x1,240x765
305
260
251
86
64
65

20T
20
56.0 (1)
56.0 (3)
63.0 (3)
18.6
14.9 (3)
17.5
3.01
5.68
4.39
3.76 (3)
3.60
250
500
650
337
261
88
66

-5.0~43.0
-20~15.5 (6)
R-410A
9.7
20.2

9.8
20.5

9.9
20.7

11.8
24.6
2,087.5
12.7

9.52
19.1
15.9

22.2
19.1

20

125
250
325
9.52
22.2

1,000
3N~/50/380-415
32

25

10T
13T
16T
REMQ5T
REMQ5T
REYQ8T
10
13
16
28.0
36.4
44.8
28.0
36.4
44.8
32.0
41.0
50.0
6.34
8.48
10.62
5.42
7.46
9.50
6.50
8.76
11.02
4.42
4.29
4.22
7.77
7.54
7.41
6.55
6.36
6.25
5.17
4.88
4.72
4.92
4.68
4.54
162.5
325.0
422.5

18T
REYQ8T
REYQ10T
18
50.4
50.4
56.5
12.46
11.04
12.89
4.04
7.38
5.98
4.57
4.38

200
400
520

225
450
585

12.7
28.6
19.1

22.2
500
40

15.9
28.6
22.2

20T

28.6

40

50

22T
24T
26T
28T
30T
32T
REYQ10T REYQ8T
REYQ12T
REYQ16T
REYQ12T
REYQ16T REYQ14T REYQ16T REYQ18T REYQ16T
20
22
24
26
28
30
32
55.9
61.5
67.4
73.5
78.5
83.9
90.0
55.9
61.5
67.4
73.5
78.5
83.9
90.0
62.5
69.0
75.0
82.5
87.5
94.0
100.0
14.54
16.38
18.11
19.93
22.03
24.43
25.6
12.80
14.34
15.95
17.65
19.25
20.35
22.4
14.94
16.81
18.41
20.73
22.33
23.73
25.8
3.84
3.75
3.72
3.69
3.56
3.43
3.52
7.06
7.07
6.87
6.95
6.72
6.48
6.63
5.68
5.54
5.46
5.41
5.23
5.03
5.14
4.37
4.29
4.23
4.16
4.08
4.12
4.02
4.18
4.10
4.07
3.98
3.92
3.96
3.88
64 (5)
250
275
300
325
350
375
400
500
550
600
650
700
750
800
650
715
780
845
910
975
1,040
15.9
19.1
34.9
28.6
1,000
50
63
80
v

Cooling

Extracted heat delivers


free hot water and heating

Hot water

Outdoor Unit Product Range

+
Heating

REYQ-T

Liquid pipe
Gas pipe
Discharge gas pipe
F1, F2 communication
Hot water

VRV indoor units


45C - 75C
Daikin
solar panel

Domestic hot water

25C - 75C
BS-Box

Air handling unit

Domestic hot
water tank
45C - 75C

BS-Box

Low temp. radiator

Heating only
hydrobox for VRV

VRV heat recovery


(REYQ8-54T)

Under floor heating


25C - 35C

Outdoor system
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

REYQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
Continuous heating
Outdoor unit module
Dimensions
Unit
Weight
Unit
Fan
Air flow rate
Sound power level
Cooling
Sound pressure level
Cooling
Operation range
Cooling
Heating
Refrigerant
Type
Charge

Power supply
Current - 50Hz

HP
kW
kW
kW
kW
kW
kW
kW

kW
kW

425
850
1,105

Actual

GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

mm
mm
mm
m
A

450
900
1,170

38T
40T
42T
REYQ8T
REYQ10T
REYQ12T
REYQ18T
38
40
42
106.3
111.9
118.0
106.3
111.9
118.0
119.0
125.5
131.5
29.74
31.58
32.75
25.10
26.64
28.69
29.24
31.11
33.18
3.57
3.54
3.60
6.66
6.68
6.79
5.25
5.20
5.28
4.24
4.20
4.11
4.07
4.03
3.96
475
950
1,235

500
1,000
1,300

525
1,050
1,365

34.9
28.6
80

44T
46T
REYQ12T REYQ14T
REYQ16T
REYQ16T
44
46
123.5
130.0
123.5
130.0
137.5
145.0
34.83
36.3
30.45
32.00
35.23
37.1
3.55
3.58
6.68
6.75
5.20
5.23
4.06
3.90
3.91
64 (5)
550
575
1,100
1,150
1,430
1,495
19.1
41.3
34.9
1,000

100

48T

50T
REYQ16T

48
135.0
135.0
150.0
38.4
33.6
38.7
3.52
6.63
5.14
4.02
3.88

50
140.4
140.4
156.5
40.8
34.7
40.1
3.44
6.49
5.03
4.05
3.90

600
1,200
1,560

625
1,250
1,625

52T

54T
REYQ18T
REYQ18T
REYQ18T
52
54
145.8
151.2
145.8
151.2
163.0
169.5
43.2
45.6
35.8
36.9
41.5
42.9
3.38
3.32
6.37
6.26
4.93
4.84
4.07
4.10
3.93
3.95
650
1,300
1,690

675
1,350
1,755

125
v

Height/Width/Depth
Cooling
Nom.
Nom.
Min.~Max.
Min.~Max.

34T
36T
REYQ16T
REYQ18T REYQ20T
34
36
95.4
101.0
95.4
101.0
106.5
113.0
28.0
31.4
23.5
26.1
27.2
30.4
3.41
3.22
6.43
6.06
4.97
4.70
4.06
3.87
3.92
3.72

Nom.

REMQ
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
Hz/V
A

5T
1,685/930/765
210
162
77
56
-5.0~43.0
-20~15.5
R-410A
9.7
20.2
2,087.5
3N~/50/380-415
20

(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (2) Nominal cooling capacities are based on: indoor
temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (3) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (4) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level
difference: 0m. Data for high efficiency series, Eurovent certified (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
(6) Technical cooling setting, refer to the installation manual for more information | Contains fluorinated greenhouse gases

45

106
Detail
B

107

112

353
134

4-15x22.5mmOblong hole
Foundation bolt hole

Detail B

4-15x22.5mmOblong hole
Foundation bolt hole

125

112

10

10

4-15x22.5mmOblong hole
Foundation bolt hole

125

View C

View C

11

1685

Detail A

729

70

11

66

160

353
134

70

100 AC

Detail
A
AC

View C

107

106

10

70

66

160

729

Detail B
729

AA
100

AA

AB

106

AC

Detail A

339

66

Pitch of foundation bolt holes

339

hole
Foundation bolt hole

160

3
AB

Pitch 4-15x22.5mm
of foundation bolt holes
Oblong
766

100

112

Detail B

AA

AC

339

REMQ5T / REYQ8-12T
3

REMQ5T
Detail A
REYQ8-12T

Pitch of foundation bolt holes


766

125

Pitch of foundation bolt holes

66

106

Pitch of foundation bolt holes

technical
drawings
2
1

AB

REMQ5T
100Detailed
REYQ8-12T
160

353
134

107

AA

Pitch of foundation bolt holes


766

112

339
AB

729

Pitch of foundation bol

REYQ8-12T

11
9

1685

122
179

131

259

97

137

930

DETAIL B

Model
AC
AA
AB
RYYQ8T, RXYQ8T, RXYQQ8T
248
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T 195
RYMQ8T 5
248
208 Model
240
REMQ5T, RYMQ10-12T, REYQ8-12T
RXYQ8T,
240
195RYYQ8T,
208

107

DETAIL A

272

RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T

328

107

131

97

765

76

373

1. Detail A and detail B indicate the dimensions after fixing the attached piping.
B
DETAIL
A
272
2.DETAIL
Knockout
hole.
Items 4 - 10:

137

Model
AA
RYYQ8T, RXYQ8T, RXYQQ8T
248
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T 195
RYMQ8T
248
REMQ5T, RYMQ10-12T, REYQ8-12T
195

515

122

373

259

259

179

Notes

76

328

76

276

3. Gas pipe
connection
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T
: 19.1 brazing
76
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
REMQ5T, REYQ8-12T
:
25.4 brazing connection
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 28.6 brazing connection
765
Notes
76
Liquid pipe

131

515

1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.

276

Notes

272

515

765

DETAIL A

122

DETAIL B

107

276

97

137

179

76

76

131

2591685

179

276

515

122

11

1685

930

328
3. Gas pipe
Inside of the switch box (M8)
11 Grounding terminal
5
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T 373: 19.1
97 brazing
107 connection
10 Pipe routing hole (bottom)
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
DETAIL
B
272 connection
REMQ5T, REYQ8-12T
: DETAIL A 25.4930
brazing
9 Pipe routing hole (front)
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 28.6 brazing connection
65
8 Power cord routing hole (bottom)
328
Notes RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
Liquid pipe
7 Power cord routing hole (front)
11 Grounding terminal
27
Equalising pipe
REMQ5T, REYQ8-12T
:
25.4 brazing connection
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
373
10 Pipe routing hole (bottom)
DetailRYYQ12T,
A and detail
B indicate
theRXYQQ12T
dimensions
after
fixing
the
attached piping.
6
1.
65
Power
cord
routing
hole
(front)
RYMQ12T,
RXYQ12T,
:

28.6
brazing
connection
RYMQ8-10T :
19.1 brazing connection
9.5 brazing connection
Q8-10T, REMQ5T, REYQ8-12T
2. ItemsLiquid
Knockout hole.
4 - 10:
9 Pipe routing hole (front)
80
Power cord routing hole (front)
pipe
Inside of the switch box (M8)
11 Grounding5terminal
RYMQ12T :
930
:
22.2 brazing connection
8 Power cord routing hole (bottom)
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
10 Pipe routing
(bottom)
65
4 holePower
cord routing hole (side)
3. Gas pipe
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 12.7 brazing connection
REYQ14-20T
9.5 brazing connection
High pressure/low
pressure gasQ8-10T,
pipe REMQ5T, REYQ8-12T
9 Pipe routing hole (front)
7 Power cord routing hole (front)
RYYQ8T,
RYMQ8T, RXYQ8T, RXYQQ8T
: 19.1 brazing connection
See
note
3.
Equalising
pipe
Equalising
pipe
connection
port
:
1 connection
2 : 22.2
RXYQ12T,
19.1 brazing
REMQ5T, REYQ8-12T : RYYQ10T,
65
3 routing hole (bottom)
8 Power
brazing
connection
RYYQ12T,
RYMQ12T,RXYQ10T,
RXYQQ12T
: 12.7
brazing
connection
RYMQ10T,
RXYQQ10T
6 Power cord routing hole (front)
Pitch of foundation
boltcord
holes
High pressure/low pressure gas pipe
19.1 brazing connection
RYMQ8-10T :
7 Power cord routing hole (front)
27
Equalising
pipe
REMQ5T,
REYQ8-12T
:
25.4 brazing connection
1076
5 Power cord routing hole (front)
RYMQ12T :
See note 3.
2
Gashole
pipe
connection port

22.2
brazing
connection
6
65
Power
cord
routing
(front)
RYMQ8-10T
:
19.1
brazingbrazing
connection
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T
: 28.6
connection
4 Power cord routing hole (side)
REYQ14-20T
80
5
Power
cord
routing
hole
(front)
Liquid
pipe
connection
port
High
pressure/low
pressure
gas
pipe
1
See note 3.
RYMQ12T :
22.2 brazing connection
Liquid pipe
Inside of the switch box (M8) Equalising pipe connection port
11 Grounding terminal 65
1
4 Power cord routing
(side)
2
3
19.1 brazing connection
name
REMQ5T, REYQ8-12T :
Remark
No. Parthole
High pressure/low pressure gas pipe
3
Pitch of foundation bolt holes
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
High pressure/low pressure gas pipe
See note 3.
10 Pipe routing hole (bottom)
Equalising pipe connection port
19.1
brazing
connection
REMQ5T, REYQ8-12T :
3

9.5
brazing
connection
393
1076
Q8-10T, REMQ5T, REYQ8-12T
High pressure/low pressure gas pipe
9 Pipe routing hole (front)
2 Gas pipe connection port
:
See note 3.
2 Gas pipe connection port
65
8 Power cord routing hole (bottom)
1 Liquid pipe connection port
134
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 12.7 brazing connection
1 Liquid pipe connection port
See note 3.
3
No. Part name
7 Power cord routing holeRemark
27
(front)
No. Part name
Equalising pipe
8
125
6 Power cord routing hole (front)
65
393
19.1 brazing connection
RYMQ8-10T :
80
5 Power cord routing hole (front)
RYMQ12T :
22.2 brazing connection
134
65
4 Power cord routing hole (side)
High pressure/low pressure gas pipe
REYQ14-20T
See note 3.
Equalising pipe connection port
8
REMQ5T, REYQ8-12T :
125
1
2 19.1 brazing connection
3

76

detail B indicate the dimensions after fixing the attached piping.


1. Detail A and
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T,
RXYQ
137
2. Items 4 - 10:
Knockout
hole.
9.5
brazing
connection
Q8-10T, REMQ5T, REYQ8-12T
3. Gas pipe
:
765 connection
RYYQ8T,
RYMQ8T,
: 19.1 brazing
brazing connection
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T RXYQ8T,
: 12.7RXYQQ8T

Detail B

Detail A
100

4-15x22.5mm - Oblong hole


Foundation bolt hole

71

High pressure/low pressure gas pipe

134

Detail B

Detail A

Remark

10

70

393

10

View C

125

View C

10

11

AA

See note 3.

107

112

Liquid pipe connection port


Part name

See note 3.

70

Gas pipe connection port

106

160

107

112

729

2D079532B

107

AB

AA

Pitch of foundation bolt holes

729

4-15x22.5mm - Oblong hole


Foundation bolt hole

2D0

70

106
Detail
B

Detail A

160

729

71

Pitch of foundation bolt holes

AA

192

310

106

2
1
No.

112

192

160

100

Pitch of foundation bolt holes


1076

71

100

192

AB

310

AB

REYQ14-20T

Pitch of foundation bolt holes

310

4-15x22.5mm - Oblong hole


Foundation bolt hole

View C

11

1685

11

1685

4
1685

515

122

Notes

Notes

76

76

76

RYMQ18-20T

46

High pressure/low pressure gas pipe


:
REYQ14-20T

High pressure/low pressure gas pipe


REYQ14-20T

131

259
122

Model
RYMQ14-16T, RXYQQ14-16T, REY
RYMQ18-20T, RXYQQ18-20T

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20

179

179

122

Liquid pipe Equalising pipe


brazing
connection
RYYQ14-16T,
RYMQ14-16T,
RXYQQ14-16T,
REYQ14-20T : :12.7

22.2
brazing
connection
RYMQ14-16T
:RXYQQ18-20T
15.9
brazing
connection
RYYQ18-20T,RXYQ14-16T,
RYMQ18-20T, RXYQ18-20T,
RYMQ18-20T
:
28.6
brazing connection
connection
RYYQ18-20T,
RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T
: 15.9 brazing
: :

131131

259

276

276

Liquid pipe
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T : 12.7 brazing connection

Equalising pipe

97

22.2 brazing connection

22.2 brazing connection


22.2 brazing connection
28.6 brazing connection

28.6
brazing
connection
22.2 brazing
connection
22.2 brazing connection

DETAIL A

DETAIL A

AA
AB
Model
RYMQ18-20T, RXYQQ18-20T
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T 240
205
RYMQ18-20T, RXYQQ18-20T
240
210

107
272

DETAIL A

328

97

76

28.6 brazing connection


RYYQ14-20T,
RXYQ14-20T,
RXYQQ14-20T
ARYMQ14-20T,
and detail
B indicate
theafter
dimensions
afterattached
fixing the piping.
attached: piping.
1. Detail
B indicate
the dimensions
fixing the
1. Detail A and detail
Items 4 - 10:
2. Items 4 - 10:
Liquid2.pipe
Knockout hole.Knockout hole.
3. Gas pipeRYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T : 12.7 brazing connection
3. Gas pipe RYYQ14-16T,

25.4 brazing connection


REYQ14-20T
:
25.4 brazing connection
REYQ14-20T
:
28.6
brazing
connection
RYYQ14-20T,
RYMQ14-20T,
RXYQ14-20T,
RXYQQ14-20T
: :
15.9
brazing
connection
RYYQ18-20T,
RYMQ18-20T,
RXYQ18-20T,
RXYQQ18-20T
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
: 28.6 brazing connection

High pressure/low
pressure gas pipe
RYMQ14-16T

259

DETAIL B

fixing the attached piping.


1. Detail A and detail B indicate the dimensions after137
137
DETAILDETAIL
B
2. Items 4 - 10:
Knockout hole.
B
765
765
3. Gas pipe
25.4 brazing connection
REYQ14-20T
:
Notes

REYQ14-20T
Equalising pipe
RYMQ18-20T
RYMQ14-16T

179

276

515
137
765

515

76

76

97

107

107

272

373

5
1240

272

328
328
373
373

C C
1240 1240

11
10
9
8
7
6
5
4
3

11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
Grounding terminal
7
Pipe routing hole (bottom) Power cord routing hole (front)
11 Grounding terminal
Pipe routing hole (front)6 Power cord routing hole (front)
10 Pipe routing
hole (bottom)
5(bottom)
Power cord routing hole (front)
Power cord routing hole
Pipe routing
hole (front)
9
4(front)
Power cord routing hole (side)
Power cord routing hole
8 routing
Power
cord
routing hole
(bottom)
Power cord
hole
(front)
Equalising
pipe
connection port
3
7routing
Power cord
hole
(front)
Power
cord
routing
hole (front)
High
pressure/low
pressure gas pipe
Power cord
hole (side)
6 routing
Power
cordGas
routing
(front) port
pipehole
connection
2
Equalising pipe connection port
5 Power 1
cordLiquid
routing
hole
(front)
pipe connection port
High pressure/low pressure gas pipe
4 PowerNo.
cordPart
routing
hole (side)
name

2 Gas pipe connection port


Equalising pipe connection port
1 Liquid pipe3connection port
No. Part name High pressure/low pressure gas pipe

2 Gas pipe connection port


1 Liquid pipe connection port
No. Part name

Inside of the switch box (M8)

Inside of the switch box (M8)

65
27
65
80
65
See note 3.
See note 3.
See note 3.

65
27

Inside of the
switch box (M8)
65

65
27
65
80
65

80
65

See note 3.
See note 3.
See note 3.

Remark
See note 3.

Remark

See note 3.

2D079533B

See note 3.
Remark

<Front>
200 or more

<Front>

400 or more
200 or more

400 or more

500 or more

100 or more

50 or more

50 or more 50 or more

100 or more

<Front>
500 or more

50 or
more

<Unit: mm>

Detailed technical drawings

REYQ-T
For centralized group layout

<Pattern1>

<Pattern1>

<Pattern1>

<Suction side>

For installation in rows

<Front>

REYQ-T

For single unit installation


300 or more

300 or more

<Front>

300 or more

300 or more

REYQ-T
For single unit installation

For installation in rows 10 or more

<Pattern1>

<Pattern1>

300 or more

300 or more

<Front>
500 or more

20 or more
<Front>group
20 or more
For
centralized
layout10 or more

10 or more
10 or more

NOTES
<Pattern2>

100 or more

500 or more

10 or more

<Front>

<Pattern2>

100
300orormore
more

10 or more

<Front>300 or20more
or more

20 or more

600 or more

<Pattern1>

10 or more 10 or more

10 or more

<Front>
500 or more

300 or more

20 or more

10 or more

<Front>

10 or more

20 or more

500 or more

900 or more

10 or more

500
or more
10 or more

20 or more
10 or more
500 or more
500 or more
1. Heights of walls in case of Patterns 1 and 2:
10 or more
20 or more
10 or more
<Front>
Front: 1500mm
<Pattern2>
Suction side: 500mm
50 or
or more
<Front> 20 or100
50 or more
50 or more 10 or100
50 or10more
<Front>
<Front>
moreor more 10 or
10 or more
20 or more
or more
<Front> 20 or more
10 or more
<Front>
<Front>
more
10 or more 10 or more
20 or
more unrestricted
more 10 or more
more
10 or more
20 or more
Side:
500Height
or more
500 or more
10 or more
500 or more
500 or more
500 or more
500 or more
100
100
600 or more
900 or more <Front>
Installation space as shown on this drawing is based on the cooling operation
or more at 35 degrees outdoor air temperature.
or more
<Pattern3>
<Pattern3>
When the design outdoor
air temperature exceedsWall
35 degrees
or the load exceeds maximum ability because of much generation load of heat in all outdoor units, take the suction side space
height unrestricted
50 or more
50 or
<Front>
<Front>
50 or
100 or more
100 or more
50 or more
more broadly than the space as shown in this drawing.
<Pattern2>
50 or more
<Pattern2>
500 or more
more
50 or
500 or more
more
Wall height
100 or more
300 above
or more wall
300 or
moreh1/2 should be added to the front and
600 or more
300 orsuction
more side service space respectively as shown in the figure on the right.
2. If the
heights are exceeded then
h2/2
and
100 or more
100 or more
more
<Front>
unrestricted 10 or more
10 or more
20 or more
100
10 or more
20 or morealways500bearing
10 or more
3. When installing the units most appropriate
shown above in order to obtainorthe
in mind
the need to leave
more best fit in the space available
500pattern
or more should be selected from those
or
more
10 or more
20 or more
10 or more
<Front>
enough space for a person to pass between units and wall and for the air50toor more
circulate<Front>
freely. (If more
50 or to
morebe installed than are catered for in the above patterns your layout should take
100 or moreunits are
<Front>
<Front>
400 or more
400 or more
100 or more
50 or
50 or more 50 or more
500 or more
50 or more
<Front>
100 or more
account
of the possibility of short
circuits.)
<Pattern2>
200 or more
200 or more
more
500 or more
4. The units
50 or to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
100 or more
100should
or morebe installed
<Front>
50 or more
50 or more 50 or more
<Front>
more
<Unit:
mm>
500 or more
500 or more

Wall height
unrestricted

50 or more

300 or more
<Front>

300 or more

Wall height unrestricted

<Front>
200 or more

400 or more
200 or more

<Front>

400 or more

<Suction side>

<Pattern3>

100
or more

50 or more

<Front>

100
or more

<Front>

500 or more

100 or more

50 or
more

50 or
more

<Front>

500 or more

100 or more

50 or more

50 or more

100 or more

100
or more

<Front>

500 or more

100 or more

50 or more

50 or more

100 or more

50 or more 50 or more

100 or more

500 or more

600 or more

50 or
more

<Front>

50 or
more

500 or more

<Unit: mm>

<Suction side>

<Front>

NOTES

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor units, take the suction side space
more broadly than the space as shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service space respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

NOTES

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation load of heat in all outdoor units, take the suction side space
more broadly than the space as shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service space respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D079542

3D079542

3D079542

47

Outdoor Unit Product Range

<Pattern3>

BS1Q-A

Individual branch selector for


VRV IV heat recovery
Unique range of single and multi BS boxes for flexible and fast
design
Compact & light to install
Ideal for remote rooms as no drain piping is needed
Allows integration of server rooms into the heat recovery solution
thanks to technical cooling function
Connect up to 250 class unit (28kW)
Faster installation thanks to open connection
Allows multi tenant applications
Connectable to REYQ-T, RQCEQ-P3 and RWEYQ-T8 VRV IV heat
recovery units

Indoor unit
Power input

Cooling
Nom.
Heating
Nom.
Maximum number of connectable indoor units
Maximum capacity index of connectable indoor units
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Piping connections
Outdoor unit
Liquid
OD
Gas
OD
Discharge gas OD
Indoor unit
Liquid
OD
Gas
OD
Sound absorbing thermal insulation
Power supply
Phase
Frequency
Voltage
Total circuit
Maximum fuse amps (MFA)

48

BS
kW
kW

mm
kg
mm
mm
mm
mm
mm

Hz
V
A

BS1Q-A

1Q10A

1Q16A
0.005
0.005

6
15 < x 100

1Q25A

8
100<x160
207x388x326
12

160<x250
15

Galvanised steel plate


9.5
15.9
12.7
9.5
15.9
Foamed polyurethane Flame-resistant needle felt
1~
50
220-240
15

22.2
19.1
22.2

BS-Q14AV1

Unique range of single and multi BS boxes for flexible and fast
design
Major reduction in installation time thanks to wide range,
compact size and light weight multi BS boxes
Up to 70% smaller and 66% lighter than previous series
Faster installation thanks to a reduced number of brazing points
and wiring
All indoor units connectable to one BS box
Less inspection ports needed compared to installing single BS
boxes
Up to 16kW capacity available per port
Connect up to 250 class unit (28kW) by combining 2 ports
No limit on unused ports allowing phased installation
Faster installation thanks to open port connection
Allows multi-tenant applications
Connectable to REYQ-T, RQCEQ-P3 and RWEYQ-T8 VRV IV heat
recovery units

Indoor unit
Power input

Cooling
Nom.
Heating
Nom.
Maximum number of connectable indoor units
Maximum number of connectable indoor units per branch
Number of branches
Maximum capacity index of connectable indoor units
Maximum capacity index of connectable indoor units per branch
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Piping connections
Outdoor unit
Liquid
OD
Gas
OD
Discharge gas OD
Indoor unit
Liquid
OD
Gas
OD
Drain
Sound absorbing thermal insulation
Power supply
Phase
Frequency
Voltage
Total circuit
Maximum fuse amps (MFA)

BS
kW
kW

Outdoor Unit Product Range

Multi branch selector for VRV IV


heat recovery

BS6,8Q14AV1

4Q14AV1
0.043
0.043
20

6Q14AV1
0.064
0.064
30

8Q14AV1
0.086
0.086
40

4
400

6
600

10Q14AV1
0.107
0.107
50

12Q14AV1
0.129
0.129
60

16Q14AV1
0.172
0.172
64

12

16

5
750
140

mm
kg

298x370x430
17

24

mm
mm
mm
mm
mm

9.5
22.2 / 19.1
19.1 / 15.9

12.7
28.6 / 22.2
19.1 / 22.2

Hz
V
A

10

298x580x430

298x820x430
26
35
38
Galvanised steel plate
12.7 / 15.9
15.9
15.9 / 19.1
28.6
28.6 / 34.9
19.1 / 22.2 / 28.6
28.6
9.5 / 6.4
15.9 / 12.7
VP20 (I.D. 20/O.D. 26)
Urethane foam, polyethylene foam
1~
50
220-440
15

298x1,060x430
50
19.1
34.9

49
49

VRV IV heat pump


Daikins optimum solution
with top comfort
Air curtain
Biddle Air curtain for VRV (CYV)
22

Indoor units
VRV type indoor units
Residential type indoor units
(such as Daikin Emura)

Hot water
Low temperature hydrobox

Control systems

Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit

7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode

VRV IV standards:

Low noise function

Variable refrigerant
temperature

Connectable to LT hydrobox

Customize your VRV for best seasonal


efficiency & comfort

Gas cooled PCB

Connectable to stylish indoor units

Full inverter compressors

4 side heat exchanger

Continuous heating

Reluctance brushless DC compressor

The new standard in heating comfort

Sine wave DC inverter

VRV configurator

DC fan motor

Software for simplified commissioning,


configuration and customisation

E-pass heat exchanger


I demand function
Manual demand function

50

For detailed explanation of these functions


refer to vrv iv technologies tab

Freely combine VRV indoor units with


stylish indoor units (Daikin Emura, Nexura,
)

M ix o

Outdoor Unit Product Range

Wide range of indoor units

R A un
its
& VR
V unit
s

FXSQ-A
VRV indoor unit

FXFQ-A
VRV indoor unit

FVXG-K
Nexura
BPMKS967A2

FTXG-LW
Daikin Emura

Connectable indoor units


15 CLASS

20 CLASS

25 CLASS

35 CLASS

FTXG20LW
FTXG20LS

FTXG25LW
FTXG25LS

FTXG35LW
FTXG35LS

FTXS20K

FTXS25K

FTXS35K
CTXS35K

Nexura Floor standing unit

FVXG25K

FVXG35K

FVXG50K

Floor standing unit

FVXS25F

FVXS35F

FVXS50F

Flexi type unit

FLXS25B

FLXS35B9

FLXS50B

Daikin Emura Wall mounted unit


Wall mounted unit

CTXS15K

42 CLASS

50 CLASS

60 CLASS

71 CLASS

FTXS60G

FTXS71G

FTXG50LW
FTXG50LS
FTXS42K

FTXS50K

FLXS60B

BPMKS box needed to connect RA indoors to VRV IV (RYYQ-T and RXYQ-T(9))

51

VRV IV

proven in practice:
40% more efficient
A field trial at a German fashion chain store
demonstrated how the innovative features
of VRV IV have improved energy efficiency
dramatically over previous models.

Results: up to 60% less


energy consumed
The results of the trial showed that the new VRV IV
system consumed much less energy, particularly when
cooling, compared with the VRV III system in some
cases up to 60% less. When heating, savings were an
average of 20%.

The Unterhaching trial demonstrates how VRV IV heat


pump technology uses a renewable energy source
air - to provide a complete and environmentally
sustainable solution for heating, cooling, and
ventilation in commercial environments. The trial also
shows that businesses can only identify and control
energy wastage through careful and intelligent
monitoring of climate control systems, a service which
Daikin can offer.

Average daily
consumption
during working
hours in kWh
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70

Energy use VRV III in 2012 in kWh

Energy use VRV IV in 2013 in kWh

60
50
40
30

Trendline energy use VRV III

20
10
0
-2

-1

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

Trendline energy use VRV IV

Difference between average daily room temperature and outdoor temperature during opening hours

VRV III 20HP (2 modules)

VRV IV 18HP (1 module)

March 2012 - February 2013

March 2013 - February 2014

Avg (kWh/Month)

2.797

1.502

Total (KWh)

33.562

18.023

Total ()

6.041

3.244

9,9

5,3

Period

Yearly (operation
cost/m (/m)

46% savings = 2.797


52

Measured data
Fashion store Unterhaching (Germany)
Floor space: 607m
Energy cost: 0,18 /kWh
System taken into account for consumption:
- VRV IV heat pump with continuous heating
- Round flow cassettes (without auto cleaning panel)
- VAM for ventilation (2x VAM2000)
- Biddle Air curtain.

Outdoor Unit Product Range

Free combination of
outdoor units
Freely combine outdoor units to optimise for
small footprint, continuous heating, highest
efficiency or any other combination

Flexible piping design


Total piping length

1000m

Longest length actual (Equivalent)

165m (190m)

Longest length after first branch

90m1

Level difference between indoor and outdoor units

90m1

Level difference between indoor units

30m

90m maximum

30m Level difference between indoor units

40m (90m1) Level difference between indoor


and outdoor units

165m Actual piping length

1 Contact your local dealer for more information and restrictions


2 in case outdoor unit is located below indoor units

53

RYYQ-T/RXYQ-T(9)

VRV IV heat pump


Daikins optimum solution with top comfort
Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, hot water, air handling
units and Biddle air curtains
Wide range of indoor units: possibility to combine VRV with stylish
indoor units (Daikin Emura, Nexura, ...)
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature, continuous heating, VRV configurator, 7 segment
display and full inverter compressors, 4-side heat exchanger,
refrigerant cooled PCB, new DC fan motor
Free combination of outdoor units to meet installation space or
efficiency requirements
Available as heating only by irreversible field setting
Contains all standard VRV features

Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
RYYQ/RXYQ
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz
Outdoor system
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

8T/8T9
8
22.4 (1) / 22.4 (2)
22.4 (3) / 22.40 (4)
25.0 (3)
5.21 (1) / 4.47 (2)
4.75 (3) / 4.47 (4)
5.51 (3)
4.30 (1) / 5.01 (2)
7.53
6.37
kW 4.72 (3) / 5.01 (4)
kW
4.54 (3)
100
200
260

mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A
RYYQ/RXYQ

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Max.
Cooling
Heating

10T
10
28.0 (1) / 28.0 (2)
28.0 (3) / 28.00 (4)
31.5 (3)
7.29 (1) / 6.32 (2)
6.29 (3) / 5.47 (4)
7.38 (3)
3.84 (1) / 4.43 (2)
7.20
5.67
4.45 (3) / 5.12 (4)
4.27 (3)

12T
12
33.5 (1) / 33.5 (2)
33.5 (3) / 33.50 (4)
37.5 (3)
8.98 (1) / 8.09 (2)
7.77 (3) / 6.59 (4)
9.10 (3)
3.73 (1) / 4.14 (2)
6.96
5.50
4.31 (3) / 5.08 (4)
4.12 (3)

125
250
325
1,685x930x765
252/194
175
79
58

243/187
162
78

5.9
12.3

6
12.5

150
300
390

14T
14
40.0 (1) / 40.0 (2)
40.0 (3) / 40.0 (4)
45.0 (3)
11.0 (1) / 9.88 (2)
9.52 (3) / 9.30 (4)
11.2 (3)
3.64 (1) / 4.05 (2)
6.83
5.31
4.20 (3) / 4.30 (4)
4.02 (3)
64 (5)
175
350
455

185

223

22T
10T
12T

251

64

65

261
88
66

10.4
21.7

11.7
24.4

11.8
24.6

86
-5~43
-20~15.5
R-410A
10.3
21.5
2,087.5
12.7

15.9
28.6

1,000
3N~/50/380-415
32

25
24T/24T9
8T
16T

HP
kW
kW
kW
kW
kW
kW
kW

kW
kW

22
61.5
61.5
69.0
16.27
14.06
16.48
3.77
7.07
5.58
4.37
4.19

24
67.4
67.4
75.0
18.2
15.85
18.31
3.70
6.81
5.42

26T
14T
26
73.5
73.5
82.5
20.0
17.29
20.30
3.68
6.89
5.39

4.25
4.10

250
500
650
391/314

260

81
61

6.3
13.2

20T
20
56.0 (1)
56.0 (3)
63.0 (3)
18.5 (1)
14.5 (3)
17.0 (3)
3.03 (1)
5.67
4.42
3.86
3.71

200
225
400
450
520
585
1,685x1,240x765

22.2

20

18T
18
50.4 (1)
50.4 (3)
56.5 (3)
15.0 (1)
12.6 (3)
14.6 (3)
3.36 (1)
6.38
4.97
4.00
3.87

356/305

9.52
19.1

16T
16
45.0 (1) / 45.0 (2)
45.0 (3) / 45.0 (4)
50.0 (3)
13.0 (1) / 12.10 (2)
11.1 (3) / 9.8 (4)
12.8 (3)
3.46 (1) / 3.73 (2)
6.50
5.05
4.05 (3) / 4.59 (4)
3.91 (3)

28T
12T
16T

30T

32T

18T
30
83.9
83.9
94.0
24.0
20.4
23.7
3.5
6.60
5.17
4.1

40

50
36T

16T

34T
16T
18T

32
90.0
90.0
100.0
26.0
22.2
25.6
3.46
6.50
5.05
4.05
3.91

34
95.4
95.4
106.5
28.0
23.7
27.4
3.4
6.44
5.01
4.0
3.9

36
101.0
101.0
113.0
31.5
25.6
29.8
3.21
6.02
4.68
3.95
3.79

400
800
1,040

425
850
1,105

450
900
1,170

20T

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)

54

Actual

RYYQ/RXYQ
HP
kW
kW
kW
kW
kW
kW
kW

Up to 30m indoor unit


height difference

28
78.5
78.5
87.5
22.0
18.87
21.90
3.57
6.69
5.23
4.16

4.06

4.00

38T/38T9
8T
10T
20T
38
106.3
106.3
119.0
29.2
25.1
29.2
3.6
6.36
5.03
4.2
4.1

40T
10T
12T
18T
40
111.9
111.9
125.5
31.3
26.7
31.1
6.74
5.29
4.0

64
275
550
715

Actual

mm
mm
m
A

300
600
780

325
650
845

350
700
910

375
750
975

15.9

475
950
1,235

500
1,000
1,300

19.1

28.6

34.9

41.3
1,000

63

80

100

FXSQ-A
VRV indoor unit

FXFQ-A
VRV indoor unit

FVXG-K
Nexura

Outdoor Unit Product Range

BPMKS967A2

FTXG-LW
Daikin Emura

RYYQ-T/RXYQ-T(9)

Connectable indoor units


15 CLASS

20 CLASS

25 CLASS

35 CLASS

FTXG20LW
FTXG20LS

FTXG25LW
FTXG25LS

FTXG35LW
FTXG35LS

FTXS20K

FTXS25K

FTXS35K
CTXS35K

Nexura Floor standing unit

FVXG25K

FVXG35K

FVXG50K

Floor standing unit

FVXS25F

FVXS35F

FVXS50F

Flexi type unit

FLXS25B

FLXS35B9

FLXS50B

Daikin Emura Wall mounted unit


Wall mounted unit

CTXS15K

42 CLASS

50 CLASS

60 CLASS

71 CLASS

FTXS60G

FTXS71G

FTXG50LW
FTXG50LS
FTXS42K

FTXS50K

FLXS60B

BPMKS box needed to connect RA indoors to VRV IV (RYYQ-T and RXYQ-T(9))

Outdoor system
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

RYYQ/RXYQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Max.
Cooling
Heating

HP
kW
kW
kW
kW
kW
kW
kW

kW
kW

Actual

Outdoor unit module for RYYQ combinations


Dimensions
Unit
Height/Width/Depth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Power supply
Current - 50Hz

GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

44T
12T

46T
14T
16T

48T

50T
16T

52T

42
118.0
118.0
131.5
33.3
28.49
32.98

44
123.5
123.5
137.5
35.0
29.97
34.70

6.65
5.19
4.14
3.99

6.62
5.17
4.12
3.96

46
130.0
130.0
145.0
37.0
31.72
36.8
3.51
6.60
5.13
4.10
3.94

525
1,050
1,365

550
1,100
1,430

575
1,150
1,495

3.54

mm
mm
m
A
RYMQ
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
Hz/V
A

48
135.0
135.0
150.0
39.0
33.3
38.4
3.46
6.50
5.05

10T
1,685/930/765
195
175
79

188
162
78

4.05
3.91
64
600
1,200
1,560
19.1
41.3
1,000

6
12.5

20

25

54
151.2
151.2
169.5
45.0
37.8
43.8
3.40
6.38
4.97
4.0

3.90
625
1,250
1,625

650
1,300
1,690

675
1,350
1,755

16T
18T
1,685/1,240/765

20T

125
12T

14T

185

223

309
81
61

58

5.9
12.3

18T
52
145.8
145.8
163.0
43.0
36.3
42.0
3.4
6.42
4.99

50
140.0
140.0
156.0
40.7
34.6
40.0
3.44
6.46
5.02

100
8T

54T
18T
18T

16T

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)

42T
10T

6.3
13.2

-5~43
-20~15.5
R-410A
10.3
21.5
2,087.5
3N~/50/380-415
32

319
260

251

64

65

261
88
66

10.4
21.7

11.7
24.4

11.8
24.6

86

40

50

(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (2) Nominal cooling capacities are based on: indoor
temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (3) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (4) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m,
level difference: 0m. Data for high efficiency series, Eurovent certified (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <=
130%) | The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into
account advanced energy saving operation functionality ( variable refrigerant temperature control operation) | Contains fluorinated greenhouse gases

55

Pitch of foundation bolt holes


766

Detail A

4-15x22.5mmOblong hole
Foundation bolt hole

Detail B

100
160

107

353
134

106

AC

Detail A

107

10

4-15x22.5mmOblong hole
Foundation bolt hole

66

125

125

View C

10

View C

70

AA

AB

339

AC

70

106

353
134

112

66

Detail B

160

112

100

125

70

Pitch of foundation bolt holes


766

106

729

AC

Detail A

66

Pitch of foundation bolt holes

AA

AB

339

RYYQ8-12T
RYMQ8-12T
100
RXYQ8-12T
RXYQQ8-12T
160

353
134

112

729

AA

339
AB

RYYQ8-12T / RYMQ8-12T / RXYQ8-12T(9)

729

Detailed technical drawings

Pitch of foundation bolt holes

107

3 1

Pitch of foundation bolt holes

RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T

Detail B

11

10

4-15x22.5mmOblong hole
Foundation bolt hole

View C

1685

11

11
1685

1685

122

122

122

131
A

930272

11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
930
8 Power cord routing hole (bottom)
Inside of the switch box (M8)
Grounding terminal
93011
(front)
10 Pipe routing7holePower
(bottom)cord routing hole11
Grounding terminal
(front) cord routing hole (front)
9 Pipe routing6holePower
10 Pipe routing hole (bottom)
65
hole (bottom)
8 Power cord5routing
Power
cord routing hole (front)
(front)
9 Pipe routing hole
7 Power cord routing
27
hole (front)
cord routing hole (side)
4 Power
Pitch of foundation bolt holes 6 Power cord routing hole (front)
8 Power cord routing
65 hole (bottom)
Equalising
pipe connection port
80 hole (front)
5 Power cord3routing
hole (front)
1076
7 Power cord routing
High
pressure gas pipe
holepressure/low
(side)
65
4 Power cord routing
6 Power cord routing hole (front)
See note 3.
Equalising pipe
2 connection
Gas pipeport
connection port
3
5 Power cord routing hole (front)
High pressure/low pressure gas pipe
1 Liquid pipe connection port Power cord routing hole (side)
4
See note 3.
2 Gas pipe connection port
No. Part name
1 Liquid pipe connection port
note 3.
Equalising pipeSee
connection
port
3
Remark
No. Part name
High pressure/low
pressure gas134
pipe
2 Gas pipe connection port
1 Liquid pipe connection port
Pitch of foundation bolt holes
No. Part name

19.1 brazing connection

71

RYYQ14-20T / RYMQ14-20T / RXYQ14-20T

71

100

106

AB

192

729

160

310

729

4-15x22.5mm - Oblong hole


Foundation bolt hole

AA

Detail B

Detail A

4-15x22.5mm - Oblong hole


Foundation bolt hole

11

71

100

106

160

Pitch of foundation bolt holes

192

Pitch of foundation bolt holes


1076

Detail B

240

Inside of the switch box (M8)

65
27
65
80
65

Inside of the switch box (M8)

65
27
65
80
65

See note 3.
See note 3.
See note 3.
Remark
393

See note 3.
See note 3.

125

See note 3.

2D079532B

Remark

2D079532B

393
134

10

393
134
125

125

View C
8

10

View C

70

Detail A

AB

310

106

RYYQ8T, RXYQ8T, RXYQQ8


AC
RYYQ10-12T,
RXYQ10-12T, R
RYMQ8T
REMQ5T,
RYMQ10-12T, REY
240

70

1076

3
100
RYYQ14-20T
RYMQ14-20T
160
RXYQ14-20T
RXYQQ14-20T
AA

AB
208
208

107

373

112

AB

High pressure/low pressure gas pipe


REMQ5T, REYQ8-12T :

328

70

373

107

328

112

179

276

259

131

DETAIL
272

RXYQQ14-20T
192

310

97
5

107373

97

DETAIL B DETAIL A

DETAIL B

112

137

137

765 765
3. Gas pipe
Notes
Notes
RYYQ8T, RYMQ8T,
RXYQ8T, RXYQQ8T
:
19.1 brazing connection
Detail A andRXYQQ10T
detail B indicate: the dimensions after
fixing
thebrazing
attached piping.
RYYQ10T, RYMQ10T, 1.RXYQ10T,
22.2
A and
detail B indicateKnockout
the dimensions
after
fixing the connection
attached piping.
1. Detail
2. Items
hole.
4 - 10:
REMQ5T, REYQ8-12T
:
2. Items
Knockout hole. 25.4 brazing connection
4 -pipe
10:
Gas
RYYQ12T, RYMQ12T,3.RXYQ12T,
RXYQQ12T :

28.6
brazing
connection
RYMQ8T, RXYQ8T, RXYQQ8T
:
19.1 brazing connection
pipe
3. Gas RYYQ8T,
RYYQ14-20T
Liquid pipe
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T :
22.2 brazing connection
RYYQ8T,
RYMQ8T,
RXYQ8T, RXYQQ8T
:
19.1 brazing connection
RYMQ14-20T
REMQ5T,
REYQ8-12T
:
25.4 brazing connection
RYYQ8-10T, RYMQ8-10T,
RXYQ8-10T,
RXYQ
RYYQ10T,
RYMQ10T,
RXYQ10T,
RXYQQ10T
: brazing connection
RYYQ12T,
RYMQ12T, RXYQ12T,
RXYQQ12T
: 9.5
22.2
brazing connection
RXYQ14-20T
28.6 brazing
connection
Q8-10T, REMQ5T, REYQ8-12T
1
REMQ5T,
REYQ8-12T2
:
25.4 brazing connection
Liquid pipe
:
RXYQQ14-20T
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T
: brazing connection
RYYQ12T, RYMQ12T,
RXYQ12T,
RXYQQ12T
:
RYYQ8-10T,
RYMQ8-10T,
RXYQ8-10T,
RXYQ 12.7
28.6 brazing connection
9.5 brazing connection
Q8-10T, REMQ5T, REYQ8-12T
Equalising pipe
Liquid
: pipe
12.7 brazing connection
RYYQ12T, RYMQ8-10T,
RYMQ12T, RXYQ12T,
RXYQQ12T
: 19.1 brazing
RYYQ8-10T,
RXYQ8-10T,
RXYQ
RYMQ8-10T :
connection
3
9.5 brazing connection
Equalising
pipe
Q8-10T,
REMQ5T,
REYQ8-12T
RYMQ12T :
22.2 brazing connection
RYMQ8-10T :
19.1 brazing connection
:
High pressure/low pressure
gas pipe
12.7
brazing connection
RYMQ12T
:
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T :
22.2 brazing
connection
19.1 brazing connection
REMQ5T, REYQ8-12T
: High pressure/low pressure gas pipe
RYYQ14-20T
Equalising pipe
19.1 brazing connection
REMQ5T, REYQ8-12T :
RYMQ14-20T
RYMQ8-10T :
19.1 brazing connection
RXYQ14-20T
RYMQ12T :
1
2
22.2 brazing connection

AA
248
195
248
195

AA
248
195
248
195

107

1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.

C
107

328

76

76

107

272

Model
RYYQ8T, RXYQ8T, RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T

729

76

Pitch of foundation bolt holes

76

Model
RYYQ8T, RXYQ8T, RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T
Model

Pitch of foundation bolt holes

Notes

97

DETAIL A
179

DETAIL B

765

259

276

515

137

9
131

259

179

515

276

515
76

76

10

AA

Detail B

Detail A

4-15x22.5mm - Oblong hole


Foundation bolt hole

View C

1685

11

11

1685
1685

515

122

after fixing the attached piping. 76


1. Detail A and detail B indicate the dimensions
76
2. Items 4 - 10:
Knockout hole.
76
76
137
3. Gas pipe
137
REYQ14-20T
:
765
765
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
:

28.6 brazing connection

Notes Notes

Liquid pipe
Detail1.ADetail
and detail
B indicate
the
dimensions
fixing
theattached
attached
piping.
1. RYMQ14-16T,
A and
detail
B indicate
the
dimensionsafter
after
fixing the
RYYQ14-16T,
RXYQ14-16T,
RXYQQ14-16T,
REYQ14-20T
: piping.
12.7 brazing connection
Knockout
hole.
2. Items2.4 Items
Knockout
hole.
- 10: 4 - 10:

RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T

RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T

High pressure/low pressure gas pipe


REYQ14-20T

RYMQ18-20T

High pressure/low pressure gas pipe


REYQ14-20T

56

179

131
107

272
328
373

97

AA RXYQQ18-20T
AB
Model
RYMQ18-20T,
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
240
205
RYMQ18-20T, RXYQQ18-20T
240
210

C
107
272

1240
5

328

373
1240

1240

15.9 brazing connection


25.4 brazing connection
25.4 brazing connection

28.6 brazing connection

:
28.6 brazing connection
Equalising pipeRYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
Liquid pipe
: 22.2
brazing
connection
RYMQ14-16T Liquid pipe
RYYQ14-16T, RYMQ14-16T,: RXYQ14-16T, RXYQQ14-16T, REYQ14-20T
12.7 brazing
connection
RXYQQ14-16T, REYQ14-20T
: brazing
12.7
brazing connection
RYMQ18-20T RYYQ14-16T, RYMQ14-16T, RXYQ14-16T,
:
28.6
connection
RYYQ18-20T,
RYMQ18-20T,
RXYQ18-20T, RXYQQ18-20T
High pressure/low
pressure gas
pipe
Equalising pipe
REYQ14-20T
:
RYMQ14-16T
:
Equalising pipe
RYMQ18-20T
:
RYMQ14-16T
:

328
373

DETAIL A

DETAIL A

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T

272

97

DETAIL B
25.4
brazing
DETAIL
B connection

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T

107

131

276

259

Notes

179

276

765

259 122

515

DETAIL B

97

DETAIL A

515

137

131

259

179

276

76

3. Gas pipe RXYQ18-20T, RXYQQ18-20T


Gas pipe
RYYQ18-20T,
3. RYMQ18-20T,
REYQ14-20T
REYQ14-20T
::

122

76

15.9 brazing connection

15.9 brazing connection

22.2 brazing connection

22.2 brazing connection


28.6 brazing connection

22.2 brazing connection


28.6 brazing connection

22.2 brazing connection

22.2 brazing connection

11
10
9
8
7
6
5
4
3

11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
7 Power cord routing hole (front)
Grounding terminal
6 Power cord routing hole (front)
Pipe routing hole (bottom)
11 Grounding
terminal
5 Power
cord routing hole (front)
Pipe routing hole (front) 10 Pipe routing hole (bottom)
4 Power cord routing hole (side)
Power cord routing hole (bottom)
routing hole (front)
9 Pipe pipe
Equalising
connection port
Power cord routing hole (front)
3
8 pressure/low
Power cord routing hole (bottom)
High
pressure gas pipe
Power cord routing hole
(front)
7 Power cord routing hole (front)
Power cord routing
(front)
Gas
pipe connection port
2 hole
6 Power cord routing hole (front)
Power cord routing hole (side)
Liquid
pipe connection port
1
Equalising pipe connection
5 port
Power cord routing hole (front)
Part name
No.
High pressure/low
pressure
pipe cord routing hole (side)
4 gas
Power

Inside of the switch box (M8)

Inside of the switch box (M8)

65
27
65
80
65
See note 3.

See note 3.
2 Gas pipe connection port
Equalising pipe connection port
3
1 Liquid pipe connection port
High pressure/low pressure gas pipeSee note 3.
Remark
No. Part name

2 Gas pipe connection port


1 Liquid pipe connection port
No. Part name

65
27
65
Inside of the switch box (M8)
80
65
See note 3.

65
27
65
80
Remark
65

See note 3.

2D079533B

See note 3.

See note 3.

2D079533B

See note 3.
See note 3.
Remark

2D079533B

RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T

Detailed technical drawings

RYYQ-T / RXYQ-T(9)
For single unit installation
(Pattern 1)

For installation in rows


(Pattern 1)

300 or more

(Pattern 1)
300 or more

10 or
more

(FRONT)
500 or more

(Pattern 2)

10 or
more

20 or more

(FRONT)
500 or more

20 or more

10 or more 10 or more

300 or more

(FRONT)
600 or more

20 or more

(FRONT)
500 or more

20 or more

10 or more
10 or more

(FRONT)
500 or more

10 or more
10 or more

300 or more

(FRONT)

20 or more

10 or more 10 or more

500 or more

10 or more

20 or more
900 or more

(Pattern 2)
100 or more

50 or more

300 or more

(FRONT)
500 or more

100 or more

50 or
more 50 or more

(Pattern 3)
300 or more

(FRONT)
200 or more

10 or more

20 or more

10 or more

10 or more

20 or more
(FRONT)

500 or more

10 or more

(Pattern 2)
100 or more

(Pattern 3)
Wall height
unrestricted

(FRONT)
500 or more

100 or more

Wall height unrestricted

50 or more
100 or
more
50 or more

300 or more

400 or more
200 or more

(FRONT)

400 or more

50 or more

(FRONT)
500 or more

(FRONT)
500 or more

100 or more

100 or more

100 or
more
50 or
more 50 or more
100 or
more
50 or more
50 or more

(FRONT)
(FRONT)
500 or more

100 or more

50 or more
50 or more

100 or more

500 or more

600 or more

50 or more

Outdoor Unit Product Range

10 or more

For centralized group layout

300 or more
100 or more

50 or more 50 or more

100 or more

(FRONT)
500 or more

50 or more

<Suction side>

<Front>

<Unit = mm>

NOTES

1. Heights of walls in case of patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more
broadly than the space as shown on this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the
space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits).
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D079542

57

VRV IV S-series heat pump


The most compact VRV
M
co m p o s t
on the ac t unit
823m market
mh
& 88k igh
g

22

Control systems

Indoor units
VRV type indoor units
Residential type indoor units
(such as Daikin Emura)

RXYSCQ4, 5TV1

Air curtain
Biddle Air curtain for VRV (CYV)

RXYSQ4, 5, 6TV1/TY1

Ventilation
Heat Reclaim ventilation
(VAM/VKM) AHU
connection kit

RXYSQ8, 10, 12TY1

Refrigerant containment check


Night quiet mode

VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort

VRV configurator
Software for simplified commissioning,
configuration and customisation

Low noise function


Connectable to stylish indoor units (Daikin Emura, Nexura)
Full inverter compressors
Gas cooled PCB (not available on RXYSQ4,5,6,8TY1)
Reluctance brushless DC compressor
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function

For detailed explanation of these functions refer to vrv iv technologies tab

58

823mm

1615mm

Widest range of front blow units on the market

8 HP

4/5/6 HP

4/5 HP
Outdoor Unit Product Range

10/12 HP

Compact:
Easy for a two person crew
to move and install.

Lowest height on the market


Ideal for roof installations

Ideal to install below a window on a Balcony

The low height mini VRV can be hidden in many

Daikin VRV IV S-series compact can be installed

Unnoticeable for parapet installation

Space saving design

discretely on a balcony thanks to its compact


dimensions, offering you air conditioning while
being almost unnoticeable.

Low height make the unit invisible from inside and unnoticeable from the outside

1,685mm

places where a twin fan unit cannot due to its low


height.

823mm

The VRV S-series is slimmer and more compact,


resulting in significant savings in installation space.

765mm

320mm

460mm
900mm

940mm

930mm

59

Wide range of indoor units


Connect VRV units
FXFQ-A

FXZQ-A

FXSQ-A
FXAQ-P

or stylish indoor units


(RA and Sky Air)

FCQG-F

BPMKS967A2

FTXG-LS - Daikin Emura


FBQ-D

BPMKS967A2

FVXG-K - Nexura

Connectable stylish indoor units


15 CLASS
Round flow cassette
Fully flat cassette
Small concealed ceiling unit
Slim concealed ceiling unit
Concealed ceiling unit with inverter driven fan
Daikin Emura Wall mounted unit
Wall mounted unit

CTXS-K

Ceiling suspended unit


Nexura Floor standing unit
Floor standing unit
Flexi type unit

20 CLASS

25 CLASS

FTXG-L

FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L

FTXS-K

FTXS-K
FVXG-K
FVXS-F
FLXS-B(9)

35 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L
CTXS-K
FTXS-K
FHQ-C
FVXG-K
FVXS-F
FLXS-B(9)

For more info about Daikins stylish indoor units, please check our indoor unit-portfolio
* VRV indoor units and stylish indoor units cannot be combined.
* To connect stylish indoor units a BPMKS unit is needed

60

42 CLASS

50 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L

60 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D

71 CLASS

FTXS-K

FTXS-K

FTXS-G

FTXS-G

FHQ-C
FVXG-K
FVXS-F
FLXS-B(9)

FHQ-C

FLXS-B(9)

Outdoor Unit Product Range

High COP values


A major feature of VRV IV S-series is its exceptional
energy efficiency. The system achieves high COPs
during both cooling and heating operation by the
use of refined components and functions.

Cooling

4.001

Nominal cooling capacities are based on: indoor


temperature: 27CDB, 19CWB, outdoor temperature: 35C,
equivalent refrigerant piping: 5m, level difference: 0m.

Heating

Nominal heating capacities are based on: indoor

4.522

temperature: 20CDB, outdoor temperature: 7CDB, 6CWB,


equivalent refrigerant piping: 5m, level difference: 0m


0 1 2 3 4 5

Minimum piping length between BP and indoor unit

2m

Maximum piping length between BP and indoor unit

15m

40m

40m

Level difference between indoor and outdoor units


Level difference between indoor units

5m

50m (40m1)

30m

15m

15m

40m maximum

250m

Minimum length between outdoor unit and first branch

Longest length after first branch

300m
150m (175m)

15m Level difference between indoor units

Longest length actual (Equivalent)

Stylish indoors
connected

50m Level difference between indoor


and outdoor units

Total piping length

VRV indoors
connected

150m Actual piping length

Flexible piping design

Outdoor unit in lowest position

61

VRV IV S-series
technologies

Refrigerantcooled PCB

Super aero grille


The spiral shaped ribs are
aligned with the direction of
discharge flow in order to
minimise turbulence and
reduce noise.

Reliable cooling because it is

not influenced by ambient air


temperature
Smaller switchbox for
smoother air flow through the
heat exchanger increasing heat
exchange efficiency with 5%

Vane fixed to rotor


Rotor

Improved fan blades


Old

New

Air streams
collide and
generate loss

Compressor

Separate
Collision

Swing type > no oil separator


Vane & rotor are unified resulting in:
Reduced noise level
Longer compressor life
Higher efficiency thanks to the
absence of internal refrigerant
leakage between high and low
pressure side

Air streams
are smoothed around V-cut
and reduces air flow loss

E-Pass heat exchanger


Optimising the heat exchangers path layout prevents
heat being transferred from the overheated gas
section to the sub-cooled liquid section which is a
more efficient way to use the heat exchanger.

Standard heat exchanger

e-Pass heat exchanger

In 85C

In 85C

43C

55C
27C

I-demand function

55C

27C

60C

50C

55C

Out 45C

Out 45C

Power consumption

Limit maximum power consumption.


The newly introduced current sensor minimizes
the difference between the actual power
consumption and the predefined power
consumption.

Predefined limit

Time

62

Mini VRV

Outdoor Unit Product Range

PIPE RUN OF 70M ALLOWS


INSTALLATION AWAY FROM THE HOUSE

LARGE VILLA APPLICATION

PARAPET INSTALLATION

OFFICE ROOFTOP INSTALLATION

63

RXYSCQ-TV1

VRV IV S-series compact


heat pump
The most compact VRV
Compact & lightweight single fan design makes the unit almost
unnoticeable
Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units and
Biddle air curtains
Wide range of indoor units: either connect VRV or stylish indoor
units such as Daikin Emura, Nexura ...
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors
3 steps in night quiet mode
Possibility to limit peak power consumption between 30 and 80%,
for example during periods with high power demand
Contains all standard VRV features

Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz

GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

Actual

RXYSCQ
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW

RXYSCQ-TV1

4TV1
4
12.1
12.1
14.2
3.43
3.18
4.14
3.53
3.81
3.43

5TV1
5
14.0
14.0
16.0
4.26
3.91
5.00
3.29
3.58
3.20
64 (1)

50

62.5
-

130
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A

162.5
823x940x460
94
91

68
51

69
52
-5~46
-20~15.5
R-410A
3.7
7.7
2,087.5
9.52
15.9
1~/50/220-240
32

(1) Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
(2) Contains fluorinated greenhouse gases

64

RXYSQ-TV1/RXYSQ-TY1

VRV IV S-series heat pump


Space saving solution without compromising
on efficiency

Outdoor Unit Product Range

Space saving trunk design for flexible installation


Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units and
Biddle air curtains
Wide range of indoor units: either connect VRV or stylish indoor
units such as Daikin Emura, Nexura ...
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors
3 steps in night quiet mode
Possibility to limit peak power consumption between 30 and 80%,
for example during periods with high power demand
Contains all standard VRV features
RXYSQ4-6TV1 / RXYSQ4-6TY1

Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

RXYSQ-TV1/RXYSQ-TY1
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW

EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz

GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

mm
kg
m/min
dBA
dBA
CDB
CWB

4TV1
4
12.1
12.1
14.2
3.03
2.68
3.43
4.00
4.52
4.14

5TV1
5
14.0
14.0
16.0
3.73
3.27
4.09
3.75
4.28
3.91

6TV1
6
15.5
15.5
18.0
4.56
3.97
5.25
3.40
3.90
3.43

4TY1
4
12.1
12.1
14.2
3.03
2.68
3.43
4.00
4.52
4.14

50

62.5

70

50

130

162.5

68
50

69

182
130
1,345x900x320
104
106
70
68
50
-5~46

51

5TY1
5
14.0
14.0
16.0
3.73
3.27
4.09
3.75
4.28
3.91
64 (1)
62.5
162.5

69

6TY1
6
15.5
15.5
18.0
4.56
3.97
5.25
3.40
3.90
3.43

8TY1
8
22.4
22.4
25.0
6.12
5.20
6.22
3.66
4.31
4.02

10TY1
10
28.0
28.0
31.5
8.24
6.60
8.33
3.40
4.24
3.78

12TY1
12
33.5
33.5
37.5
10.15
8.19
10.25
3.30
4.09
3.66

70

100

125

150

182

260
1,430x940x320
144
140
73

70
51

55

325
390
1,615x940x460
175
180
182
74
76
57
-5~52

-20~15.5
R-410A

kg
TCOeq

3.6
7.5

4.5
9.4

7
14.6

8
16.7

22.2

12.7
25.4

2,087.5

Actual

mm
mm
m
Hz/V
A

15.9

19.1

9.52
15.9

19.1
-

1N~/50/220-240
32

(1) Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
(2) Contains fluorinated greenhouse gases

3N~/50/380-415
16

25

32

65

Detailed technical drawings


RXYCSQ-TV1
RXYCSQ-TV1

4 holes for anchor bolts

Gas pipe connection 15.9 flare

Liquid pipe connection 9.5 flare

Service port (in the unit)

Grounding terminal
Inside of the switch box (M5)

Refrigerant piping intake (knockout hole)

Power supply wiring intake (knockout hole 53)

Control wiring intake (knockout hole 27)

Drain pipe connection (outside diameter 26)

30

37

52

485

460

30

M12

60
101
170

620

40

150

940

2
1

823

3
5

88

19

19

100
151

53 95

60

53 95
289
313

17

62 59 118 102

104

17

52

69

80

20
216

130
21

32
98

89

3D098107

RXYSQ4-6TV1
RXYSQ-TV1
RXYSQ4-6TY1
1

4 holes for anchor bolts

140

M12

620

140

Liquid pipe connection 9.5 flare

(2X) Service port (in the unit)

Electronic connection and grounding terminal M5 (in the switch box)

320

30

350
(345~355)

Gas pipe connection A

Refrigerant piping intake

Power supply wiring intake (knockout hole 34)

Control wiring intake (knockout hole 27)

Drain outlet

Model

59

43

30

40
94

900

30

19.1 brazed connection

RMXS140E8V1B

19.1 brazed connection

RMXS160E8V1B

19.1 brazed connection

RXYSQ4PA7V1B

4
3

15.9 flared connection

RXYSQ6PA7V1B

19.1 brazed connection


15.9 flared connection

ERX140A9V1B

19.1 brazed connection

GCA100BD4

1345

15.9 flared connection

GCA125BD4

15.9 flared connection

GCA140BD4

19.1 brazed connection

RXYSQ4PA7Y1B

15.9 flared connection

ERX125A9V1B

15.9 flared connection

RXYSQ5PA7V1B
ERX100A9V1B

RMXS112E8V1B

15.9 flared connection

RXYSQ5PA7Y1B

15.9 flared connection

RXYSQ6PA7Y1B

19.1 brazed connection

5
52
55

223

148

55
95
80

84

13

19

54

19
89
142
71

54

67

145

70

58

102

117

16

16

89

24

95

60

423
430

45

5
376

191

Model

A
RA indoor unit

VRV indoor unit

RXYSQ4(P8/T7)V1B

19.1 brazed connection

15.9 flared connection

RXYSQ5(P8/T7)V1B

19.1 brazed connection

15.9 flared connection

RXYSQ6(P8/T7)V1B

19.1 brazed connection

RXYSQ4(P8/T7)Y1B

19.1 brazed connection

15.9 flared connection

RXYSQ5(P8/T7)Y1B

19.1 brazed connection

15.9 flared connection

RXYSQ6(P8/T7)Y1B

19.1 brazed connection

3TW30374-1D

66

Detailed technical drawings


RXYSQ-TY1
RXYSQ8TY1

30

61

48

320

M12

350
(345-355)

30

4 holes for anchor bolts

44
96
160

620

30

160

940

1430

8
7
8

54 95

52
80

19

13

145

142
9
16

16

68 67

151

68

90

19

54

89

84 55

95

60

55

223

53 95

89

Outdoor Unit Product Range

67

Gas pipe connection 19.1 brazing

Liquid pipe connection 9.52 brazing

Service port (in the unit)


High pressure

Service port (in the unit)


Additional refrigerant charge

Grounding terminal

Refrigerant piping intake (knockout hole)

Power supply wiring intake (knockout hole 34)

Control wiring intake (knockout hole 27)

Drain pipe connection (outside diameter 26)

Inside of the switch box (M5)

47

395

191

3D098108

RXYSQ10-12TY1

52

30

460

490
(485-495)
64
49

30

RXYSQ10-12TY1

97
620

170

150

940

40

5
4
3
2

633
95
53

100 22

95
6

53

88

28

60

626

1615

19

80

154

62

59 118 102

52

216

20

130
21 89

98
32

RXYSQ10TMY1B: Gas pipe connection 22.2 brazing


RXYSQ12TMY1B: Gas pipe connection 25.4 brazing

RXYSQ10TMY1B: Liquid pipe connection 9.52 brazing


RXYSQ12TMY1B: Liquid pipe connection 12.7 brazing

Service port (in the unit)


Additional refrigerant charge

Service port (in the unit)


High pressure

Grounding terminal
Inside of the switch box (M8)

Refrigerant piping intake (knockout hole)

Control wiring intake (knockout hole 27)

Power supply wiring intake (knockout hole 53)

Drain pipe connection (outside diameter 26)

3D098109

67

Detailed technical drawings


RXYSCQ-TV1

68

Detailed technical drawings

Outdoor Unit Product Range

RXYSCQ-TV1

69

Detailed technical drawings


RXYSQ-TV1 / / RXYSQ4-6TY1

70

Detailed technical drawings

Outdoor Unit Product Range

RXYSQ-TV1 / / RXYSQ4-6TY1

71

Detailed technical drawings


RXYSQ-8TY1

72

Detailed technical drawings

Outdoor Unit Product Range

RXYSQ-8TY1

73

Detailed technical drawings


RXYSQ10-12TY1

74

Detailed technical drawings

Outdoor Unit Product Range

RXYSQ10-12TY1

75

VRV IV i-series heat pump


for indoor installation

uniqu
e
paten
ted
conce
pt
Air curtain
Biddle Air curtain for VRV (CYV)
22

Indoor units
VRV type indoor units

Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
Control systems

Night quiet mode

VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort

VRV configurator

Full inverter compressors


Low noise function
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function

Software for simplified commissioning,


configuration and customisation

For detailed explanation of these functions refer to vrv iv technologies tab

76

Invisible
Consider a wider range of properties because

Seamless integration into the surroundings as only

outdoor installation is not a factor


Open for business sooner because getting
building permits is simplified

No need for a roof installation or back alley

the grille is visible

Outdoor Unit Product Range

installation

Quiet
Highly suited to densely populated areas such as

city centres thanks to their low operating sound

Lightweight parts
can be installed
by two people

<
Dedicated modes reduce sound further to comply

with inner-city noise regulations

Heat exchanger sound not louder


than a normal conversation

Compressor sound not louder


than a refrigerator

77

Unique split outdoor unit for indoor installation


Compact and easy to hide, the compressor can
be installed at floor level, in a back office, storage
room, technical area or in a kitchen, while the

heat exchanger can be installed in a false ceiling


space. This means that the air conditioning system
is completely invisible and does not take up
expensive commercial floor space.

Unrivalled flexibility thanks to the fact that


the outdoor unit is split into two parts

1. The heat exchanger


can be installed in a
false ceiling space.

2. The compressor is
compact and easy to
hide, this element can
be installed at floor
level, in a back office,
storage room, technical
area or in a kitchen.

This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space.

VRV Indoor units

Heat exchanger unit

Max. 70 m

Max. 30 m

Compressor unit

78

Outdoor Unit Product Range

Invisible air suction and air discharge

79

The problem solver


for many installation issues
Example 1

High flexibilty
The other way around: install the modules
where if fits your customer, not where it is
the best fit for the outdoor unit
If there is no flat roof or backgarden available for
installation of the outdoor unit, VRV IV i-series offers
the solution.
The suction and exhaust can be installed at the
faade or at the rear of the building as the inverter
fans allows ESP to be adjusted to the length of the
ductwork.
The compressor module can be installed up to 30 m
from the heat exchanger unit in a storage room, ....

80

Flexible installation thanks to inverter fans

Example 2

Back alley or rooftop needs very long


piping lengths
Long installation time
Additional cost
Capacity loss

Outdoor Unit Product Range

Shorter pipe runs to the indoor units reduces


installation costs compared to rooftop
or back alley installation
VRV IV i-series can be installed close to the
indoor units
Quicker installation
Lower cost
No capacity loss

short distance

Example 3

No need for bulky and expensive sound


countermeasures
To comply with city regulation countermeasures
are needed for standard units
Expensive sound cages might be needed to
reduce sound (standard outdoor unit sound =
50~60 dBA)
Inside installation using expensive floor space
Reduced floor space

Other VRF
technical
aera
stock
kitchen

More floor space

VRV IV i-series

With VRV IV i-series you easily comply with city


regulation without additional measures
Operation sound 47 dBA (flexible to install in
corridor, shop area, ) or lower with attenuator
No floor space is used as units can be installed in
false ceiling, against the wall,

sound
cage

Expensive counter measures

Other VRF

No additional measures needed

VRV IV i-series
=

stock
kitchen
SHOP

SHOP

81

Patented V-shape
heat exchanger
for best surface to volume ratio
Optimised air flow and
temperature distribution
Best performance for defrost (tested in high humidity
down to -20C).

patents

Patented
perforated
and insulated
partition plate
Reduces conductivity and
prevents cold bridges

Only
400mm
high
Fits easily in
any false ceiling

Super efficient
centrifugal fans
Standard delivered filter
with the unit to prevent dirt from entering the
heat exchanger

82

Over 50% efficiency increase compared


to sirocco fan
Patented backward- curved blade
technology
More pressure increase

Compressor unit with


rotating switchbox
Flexibility by back and top
refrigerant connection possibility

Rotating switchbox
For easy access to all compressor parts

Only

77 kg
Tube-in-tube
subcool heat
exchanger
This patented heat
exchanger increases the
capacity of the system by
ensuring optimal state
of refrigerant in the heat
exchanger module. This
in turn increases overall
efficiency.

No drain connection
needed
Thanks to natural evaporation
Minimized cold surface to reduce

dew formation
Fast and easy installation

Non welded
bottom casing
Avoids any corrosion risk

Small footprint
Maximizes useable floor space (600 x 550 mm)
Can easily be mounted in a storage room, back office,

83

Outdoor Unit Product Range

Flexible and easy to install

SB.RKXYQ-T

VRV IV heat pump for indoor


installation
The invisible VRV
Unique VRV heat pump for indoor installation

Unrivalled flexibility because the unit is split up into two elements:


the heat exchanger and the compressor
Heat exchanger
unit

SB.RKXYQ5T

Max. 70 m
Max. 30 m

VRV Indoor
units

Compressor unit

Highly suited to densely populated areas thanks to the low


operation sound and seamless integration into surrounding
architecture as only the grille is visible
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

SB.RKXYQ
Compressor unit
Heat exchanger unit
Nom.
Nom.
Max.
Cooling
Heating

35CDB
6CWB
6CWB
Nom.
Nom.
Max.

EER
COP

at nom. capacity
at nom. capacity
at max. capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Fan
External static
Max.
Nom.
pressure
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Temperature
Min.
Max.
around casing
Piping connections
Between Compressor
Liquid
module (CM) and heat
Gas
exchanger module (HM)

35CDB
6CWB
6CWB
35CDB
6CWB
6CWB

HP
kW
kW
kW
kW
kW
kW
kW/kW
kW/kW
kW/kW

OD
OD

Pa
Pa
CDB
CWB
CDB
CDB
mm
mm

Between Compressor Liquid


module (CM) and indoor
Gas
units (IU)

OD

mm

OD

mm

Total piping length

Actual

System

Incorporates VRV IV standards & technologies: Variable Refrigerant


Temperature, VRV configurator and full inverter compressors
Lightweight units (max. 97kg) can be installed by two people
Unique V-shape heat exchanger results in compact dimensions
(h/e unit only 400mm high) allowing false ceiling installation,
while ensuring top efficiency
Super efficient centrifugal fans (over 50% efficiency increase
compared to sirocco fan)
Small footprint compressor unit (600 x 550 mm)
8HP
launch
maximizing useable floor space
2nd ha
Contains all standard VRV features

2016

5T
RKXYQ5T
RDXYQ5T
5
14.0
14.0
16.0
4.38
3.68
4.71
3.20
3.80
3.40
10 (1)
62.5
162.5
150
60
-5~46
-20~15.5
5
35
12.7
19.1

22.2

9.5

9.52

15.9

19.1

140

300

compressor module
RKXYQ5T
RKXYQ8T
701/600/554
701/760/554
77
100
47
56
R-410A
R-410A
2
4
4.2
8.4
2,087.5
2,087.5
3N~/50/380-415
3N~/50/380-415
16
-

heat exchanger module


RDXYQ5T
RDXYQ8T
397/1,456/1,044
397/1,456/1,044
97
107
Centrifugal
Centrifugal
55
Discharge duct
Discharge duct
47
R-410A
R-410A
1N~/50/220-240
1N~/50/220-240
10
-

(1) Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).

Outdoor unit module


Dimensions
Weight
Fan

Sound power level


Sound pressure level
Refrigerant

Power supply
Current - 50Hz

Unit
Unit
Type
Air flow rate
Discharge direction
Cooling
Cooling
Type
Charge

Height/Width/Depth

Cooling
Nom.
Nom.

GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

*Note: blue cells contain preliminary data

84

Nom.

mm
kg
m/min
dBA
dBA
kg
TCOeq
Hz/V
A

8T
RKXYQ8T
RDXYQ8T
8
22.4
22.4
(1)
100
260
150
-5~46
-20~15.5
5
35
12.7

lf

Detailed technical drawings


RDXYQ-T
RDXYQ5T7V1B
63

239

62

255

149

45

View A
5

239

705

1044

Suspension position

9 (4x)

4
149

1456
1498

Suspension position

45

View A

9 (4x)

1196

99

Outdoor Unit Product Range

1456
1498

Suspension position

8
1196

117

2
25

102

27

25

117

298

397

99

26

67

27

659
102

716

659
716

9 Hook

9 Hook

8 Service door

8 Service door

7 Air discharge side


6 Air suction side

7 Air discharge side


6 Air suction side
5 Wiring intake (low voltage wiring)
4 Wiring intake (high voltage wiring)

wiring)
5 Wiring intake (low voltage
Drain outlet
3

wiring)
4 Wiring intake (high voltage
connection port
2 Gas pipe
3 Drain outlet

1 Liquid pipe connection port


No. Part name

2 Gas pipe connection port

1 Liquid pipe connection port


No. Part name

Transmission wiring connection


Power supply connection

Transmission wiring connection


VP25
Power supply
connection
19.1 brazing
connection
VP25 12.7 brazing connection
Remark
19.1 brazing connection
12.7 brazing connection
Remark

2D098826

2D098826

RKXYQ-T

RKXYQ5T7Y1B
600

4x O17
554

Foundation bolt hole

118

View A

57

101

8
57

Indoor unit

701

54
6

337

365

4
Heat exchanger unit

426
Pitch of foundation bolt holes

88

120

55

516

59

Pitch of foundation bolt holes

85

8 Handle
7 Pipe routing hole
6 Wiring intake (low voltage wiring)
5 Wiring intake (high voltage wiring)

15

4 Gas pipe connection port


3 Liquid pipe connection port
2 Gas pipe connection port
1 Liquid pipe connection port
No. Part name

Knockout hole.
Transmission wiring connection
Power supply connection
15.9 brazing connection
9.5 brazing connection
19.1 brazing connection
12.7 brazing connection
Remark

3D098827

85

Detailed technical drawings


RDXYQ-T
RDXYQ5T7V1B

100 or more

Air discharge side

Air suction side


50 or more

100 or more

10 or more

500 or more

3D098834

RKXYQ-T

10 or more

10 or more

500 or more

10 or more

10 or more

RKXYQ5T7Y1B

Front view
Top view

3D098835

86

Outdoor Unit Product Range

Keep looking
youll never find me

The city secret


Unseen in the best places
Our VRV IV i-series offers you a truly unique solution for installations where
you need a totally invisible system. It is compact and easy to hide indoors,
with only the grilles being visible outside. Split into two lightweight
components, the compressor can be installed at floor level in a storage room
or technical area, and the heat exchanger unit, which is only 400 mm high,
can be installed in a standard false ceiling. The VRV IV i-series has a patented
V-shaped heat exchanger which boosts efficiency. So your customer can
now enjoy all the power of a fully invisible VRV system.

i
Find out more at www.daikineurope.com/citysecret
87

VRVIII-C
VRV heat pump

where heating is priority


without compromising on efficiency
Air curtain
Biddle Air curtain for VRV (CYV)
22

Indoor units
VRV type indoor units

Control systems

Automatic refrigerant charge


Refrigerant containment check
Night quiet mode
Low noise function
Reluctance brushless DC compressor
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function
88

Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit

COP for a 10HP unit


4.00
3.00
COP

The use of two stage compression technology


results in improved energy saving performance at
low ambients, with a COP of more than 3.0 at -10C
outdoor ambient for the entire range.

Outdoor Unit Product Range

High COP at low ambients

ump

at p

he
dard

2.00

Stan

1.00
0.00
-25

-20

-15

-10
-5
Outdoor temp. (WB)

10

Wide heating operation


range
VRVIII-C has a standard operation range down to
-25CWB outdoor ambient in heating and can also
provide cooling down to - 5CDB outdoor ambient.

Heating mode

Cooling mode

VRVIII-C

Standard VRV

-25CWB

-20CWB

15.5C

43CDB

-5C

Outdoor Temp.

Outdoor Temp.

(kW) 35

VRVIII-C has a stable heating capacity, even in


low ambients, making it suitable for single source
heating. The heating capacity is 130% in comparison
with the standard VRV heating capacity under similar
conditions.

30
heating capacity

Stable heating capacity

25
20

standard heat pump

15
10
5
0

-25

-20

-15

-10
-5
0
Outdoor temp. (CWB)
Heating capacity 10HP outdoor unit

10

89

High heat up speed


Heat up time is dramatically reduced, particularly
under low ambient conditions. The required time
for the indoor unit heat exchanger discharge
temperature to reach 40C has been reduced by 50%.

Start heating operation

60
50

30

30

25

20
10

20

Indoor temperature C

Discharge temperature (C)

40

Indoor heat exchanger temperature VRVIII-C

Standard heat pump

Indoor heat exchanger temperature standard heat pump

50% reduction

-10
-20
-5

5 6
10
Elapsed time (min.)

Indoorpositie
temperatureblauwe
VRVIII-C
lijnen:

15

14 15

20

X +10

Indoor temperature standard heat pump


* Field test data in Japan with 14 HP unit (Akita City Jan 2006)

Short defrost time


The time required for defrost is reduced to 4 minutes
less than half that of the standard VRVIII system (10
minutes), leading to a more stable interior indoor
temperature and considerably improved comfort
levels.
* Field test data in Japan with 10 HP unit (Akita City Jan 2006)

10m

Longest length after first branch

40m (90m1)

Level difference between


indoor and outdoor units

50m (40m)

Level difference between indoor units


1 Contact your local dealer for more information and restrictions
2 In case outdoor unit is located below indoor units

90

15m

90m maximum

Longest length between


outdoor unit and function unit

500m
165m (190m)

15m Level difference between


indoor units

Longest length actual (Equivalent)

50m Level difference between indoor


and outdoor units

Total piping length

165m Actual piping length

Flexible piping design

RTSYQ-PA

VRVIII heat pump,


optimised for heating
Where heating is priority without compromising
on efficiency

Outdoor Unit Product Range

First system in the industry developed for heating operation


in low ambient conditions, making it suitable for single source
heating
Extended operation range down to -25C in heating
Stable heating capacity and high COP values at low ambients
thanks to the two stage compression technology (COP values of
3.0 and more at -10C)
Improved comfort thanks to shorter defrost time
Shorter heat up time compared to standard VRVIII heat pump
Contains all standard VRV features
RTSYQ14-16PA

Heating
capacity

Two stage compression

High

Liquid injection

Two stage compression technology enables the system to create


higher pressures resulting in a higher heating capacity under low
ambient conditions. The second inverter compressor (located in the
function unit) is specially designed to provide higher pressures.
After heat is exchanged in the indoor unit, gas and liquid are
separated at the gas-liquid separator. This enables the refrigerant in
gas condition to be recovered and transmitted direct to the high
pressure compressor.

Gas-liquid
separator
Middle

Pressure

Gas injection

Low

Input power

Evaporator capacity

Enthalpy

Outdoor system
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

RTSYQ
Outdoor unit module 1
Outdoor unit module 2
Function unit
Nom.
Nom.
Cooling
Heating

10PA
RTSQ10PAY1

14PA
RTSQ14PAY1
-

10
28.0
31.5 (1) / 28.0 (2)
7.90
7.78 (1) / 8.18 (2)
3.54
4.05 (1) / 3.42 (2)
21
125
250
325
60/62
9.52
22.2

14
40.0
45.0 (1) / 40.0 (2)
12.6
11.4 (1) / 12.8 (2)
3.17
3.95 (1) / 3.13 (2)
30
175
350
455
61/63

16PA
RTSQ16PAY1

20PA
RTSQ8PAY1
RTSQ12PAY1

16
45.0
50.0 (1) / 45.0 (2)
14.9
13.0 (1) / 15.0 (2)
3.02
3.85 (1) / 3.00 (2)
34
200
400
520

20
56.0
63.0 (1) / 55.9 (2)
15.4
15.4 (1) / 18.7 (2)
3.64
4.09 (1) / 2.99 (2)
43
250
500
650

BTSQ20PY1

Nom.
Nom.

EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Sound pressure level
Cooling
Nom./Max.
Piping connections
Liquid
OD
Gas
OD
Oil equalizing
OD
Total piping length
System
Actual
Current - 50Hz
Maximum fuse amps (MFA)

HP
kW
kW
kW
kW
kW
kW

dBA
mm
mm
mm
m
A

63/65
12.7

15.9
28.6

19.1
500

25

35

40

50

(1) Heating: Indoor temp. 20CDB; outdoor temp. 7CDB,6CWB (2) Heating: Indoor temp. 20CDB; outdoor temp. -10CWB

Outdoor unit module


Dimensions
Unit
Weight
Unit
Fan
Air flow rate
Sound power level
Cooling
Operation range
Cooling
Heating
Refrigerant
Type
Charge

Power supply
Current - 50Hz

Height/Width/Depth
Cooling
Nom.
Min.~Max.
Min.~Max.

GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

Nom.

RTSQ
mm
kg
m/min
dBA
CDB
CWB

BTSQ20P
1,570/460/765
110
-

kg
TCOeq

Hz/V
A

8PA

10PA
1,680/930/765

205

12PA

200

14PA
16PA
1,680/1,240/765
338
344
233
239

10.9
22.8

11.7
24.4

257
185
-5~43
-25~15.5
R-410A

9.4
19.6

10.5
21.9
2,087.5
3~/50/380-415

20

25

35

40

91

Detailed technical drawings


RTSYQ10PA
RTSYQ10PA
(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

Outdoor unit

NOTES

300 or more

(Pitch of foundation
bolt holes)

(Pitch of foundation bolt holes)

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)

10 or more

10 or more

(Front)
500 or more

Function unit

500mm

<Suction side>

<Front>

1500mm

50~100mm

System

Outdoor unit

DWG. No.

Function unit

DWG. No.

RTSYQ10PA

RTSQ10PA

3D076289

BTSQ20P

3D060838

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space to be shown in this drawing is based
on the cooling operation at 35 degrees outdoor air
temperature. When the design outdoor air temperature
exceeds 35 degrees or the load exceeds maximum ability
because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the
space to be shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and
h1/2 should be added to the front and suction side service
spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should
be selected from those shown above in order to obtain
the best fit in the space available always bearing in mind
the need to leave enough space for a person to pass
between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in
the above patterns your layout should take account of the
possibility of short circuits.)
4. The units should be installed to leave sufficient space
at the front for the on site refrigerant piping work to be
carried out comfortably.
5. In case there expected heavy snow, prepare some
countermeasures recommended as follows:
1) Outdoor and Function unit must be installed on a
foundation (field supply) in order to secure a distance
of 200-300mm or more between the bottom frame and
the snow-laid ground surface.
2) Install a snowbreak hood (option) and remove its back
side air inlet grill.
6. Air outlet of snowbreak hood must face at right angle or
lower level than the winter wind, in case a snowbreak
hood is installed at the air outlet of the unit.
7. In case there expected to freeze of exhausted water from
de-frost operation due to the cold outdoor temperature in
winter time, secure a sufficient space between the bottom
frame and the foundation. (500-1000mm is suggested as
an appropreate distance.)

3D076286

RTSYQ14,16PA
RTSYQ14,16PA

500mm

<Suction side>

<Front>

300 or more
(Pitch of foundation bolt holes)

Outdoor unit

1500mm

NOTES

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)

10 or more

(Front)
500 or more

Function unit

System

Outdoor unit

DWG. No.

Function unit

DWG. No.

RTSYQ14PA

RTSQ14PA

3D076291

BTSQ20P

3D060838

RTSYQ16PA

RTSQ16PA

3D076291

BTSQ20P

3D060838

10 or more

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space to be shown in this drawing is based
on the cooling operation at 35 degrees outdoor air
temperature. When the design outdoor air temperature
exceeds 35 degrees or the load exceeds maximum ability
because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the
space to be shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and
h1/2 should be added to the front and suction side service
spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should
be selected from those shown above in order to obtain
the best fit in the space available always bearing in mind
the need to leave enough space for a person to pass
between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in
the above patterns your layout should take account of the
possibility of short circuits.)
4. The units should be installed to leave sufficient space
at the front for the on site refrigerant piping work to be
carried out comfortably.
5. In case there expected heavy snow, prepare some
countermeasures recommended as follows:
1) Outdoor and Function unit must be installed on a
foundation (field supply) in order to secure a distance of
200-300mm or more between the bottom frame and the
snow-laid ground surface.
2) Install a snowbreak hood (option) and remove its back
side air inlet grill.
6. Air outlet of snowbreak hood must face at right angle or
lower level than the winter wind, in case a snowbreak
hood is installed at the air outlet of the unit.
7. In case there expected to freeze of exhausted water from
de-frost operation due to the cold outdoor temperature in
winter time, secure a sufficient space between the bottom
frame and the foundation. (500-1000mm is suggested as
an appropreate distance.)

3D076287

92

Detailed technical drawings


RTSYQ20PA
4-15 x 22.5 - mm - Oblong holes
(Foundation bolt hole)
(Pitch of foundation
bolt holes)

(Pitch of foundation bolt holes)

Outdoor unit 2

20mm
For installation in rows
< Pattern 1 >

For single unit installation


300 or more

500 or more

<Front>

<Front>

10 or more

50 or more

300 or more
500 or more

< Pattern 2 >

<Front>
20 or more
10 or more

50 or more10 or more

500 or more

500 or more
<Front>

100 or more

< Pattern 2 >

<Suction side>

<Front>

<Front>

500
100orormore
more

< Pattern 3 >

50 or more

Wall height unrestricted

10
or more
System

Outdoor unit 1

< Pattern 2 >

RTSYQ20PA

50 or more
50 or more

500 or more
<Front>

400 or more

100 or more
RTSQ12PA
10 or more

50 or more

10 or more

300 or more

10 or
more

or more
10 or10
more

20 or more

Outdoor unit 2
10 or more

3D076290
<Front>
20 or moreRTSQ8PA

DWG. No.

Function unit

100 or more
3D076290
50 or more

<Front>

<Front>

50 or more

< Pattern 2 >

50 or more
10 or more

100 or more

500 or more

50 or more

10 or more

<Front>
100 or more
300 or more
500 or more

10 or more
50 or more

<Front>
20 or more
<Front>
100 or more
or more
500 600
or more

100 or more

100 or more
100 or more

10 or more

10 or more

50 or more

<Front>

10 or more

50 or more
10 or more

50 or more

50 or more
< Unit: mm >

50 or more 100 or more


more
5010orormore

20 or more

100 or more

500 or more

< Pattern 3 >

10 or more

<Front>
300 or more
100 or more
500 or more
<Front>

50 or more

10 or more

10 or more

<Front>

50 or more

50 or more

20 or more
100 or more

50 or more

50 or more
< Unit: mm >
300 or
more

50 or more

500 or more
<Front>

3D076288
10 or more

50 or more

100 or more
<Front>

10 or more

100 or more
For installation in rows

<Front>
100 or more
500 or more < Pattern 1 >

<Front>

50 or more

10 or more

100 or more

300 or
more
20 or more

200 or more
20 or more

No.

3D060838

20 or more
<Front>

200 or more

500 or more

50 or
more

10 DWG.
or more

BTSQ20P
10 or more

< Pattern 2 >

Wall height unrestricted


300 or more

400 or more

300 or
more

50 or more

50 or
or more
20
more

DWG. No.

500 or more

200 or more

200 or more

< Pattern 3 >


For single unit installation
< Pattern 1 >

<Front>

500 or more

<Front>

100 or more

20 or more

< Front >

50 or
more

<Front>

10 or more

10 or more

600 or more

300 or more

RTSYQ-PA
RTSYQ-PA

300 or more50 or more

1500mm

1500mm

50 or
more

20 or more

10 or more

100 or more

20 or more

300 or more

10 or more

600 or more

500mm

10 or
more

10 or more

< Pattern 1 >

10 or more
10 or more

(Front)

20 or more

For installation in rows


300 or more

20 or more

10 or more

10 or more

20 or more

50 or more
< Pattern 2 >

Wall height unrestricted

10 or more

100 or more

100 or more

10 or more

< Suction side >

10 or more

300 or more
50 or more
400 or more

<Front>

<Front>

100 or more

500 or more

200 or more

50 or more
10 or more

50 or more

<Front>
500 or more

500mm

300 or more
< Pattern 1 >

20 or more

50~100mm

< Front >

RTSYQ-PA
For single unit installation

Function unit

1500mm

RTSYQ-PA

10 or
more

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
Installation space to be shown in this drawing is based
on the cooling operation at 35 degrees outdoor air
temperature. When the design outdoor air temperature
exceeds 35 degrees or the load exceeds maximum ability
because of much generation load of heat in all outdoor
unit, take the suction side space more broadly than the
space to be shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and
h1/2 should be added to the front and suction side service
spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should
be selected from those shown above in order to obtain
the best fit in the space available always bearing in mind
the need to leave enough space for a person to pass
between units and wall and for the air to circulate freely.
(If more units are to be installed than are catered for in
the above patterns your layout should take account of the
possibility of short circuits.)
4. The units should be installed to leave sufficient space
at the front for the on site refrigerant piping work to be
carried out comfortably.
5. In case there expected heavy snow, prepare some
countermeasures recommended as follows:
1) Outdoor and Function unit must be installed on a
foundation (field supply) in order to secure a distance of
200-300mm or more between the bottom frame and the
10 or more
snow-laid ground surface.
2) Install a snowbreak hood (option) and remove its back
side air inlet grill.
10 or more
6. Air outlet of snowbreak hood must face at right angle or
lower
level
than
the
winter
wind,
in case a snowbreak
50 or more
300 orismore
hood
installed at the air outlet of the unit.
7. In case there expected to freeze of exhausted water from
de-frost operation due to the cold outdoor temperature in
winter time, secure a sufficient space between the bottom
<Front>and20the
frame
foundation. (500-1000mm
50 or more is suggested as
or more
10 or more
20 or more
10 or an
more appropreate distance.)

< Suction side >

Outdoor unit 1

10 or more
< Pattern 1 >

NOTES

(Pitch of foundation bolt holes)


(Pitch of foundation bolt holes)

(Pitch of foundation
bolt holes)

500mm

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)

50 or more

100 or more
<Front>

200 or more
100 or more
10 or more

3D059348C

1.

Heights of walls in case of Patterns 1 and 2:


< Unit: mm >
Front: 1500 mm
Suction side : 500 mm
Side: Height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When the design outdoor air temperature exceeds 35 degrees or the
load exceeds maximum ability because of much generation load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing.

2.

If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.

3.

When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)

4.

The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

5.

Installation of snowbreak hood (field supply; ask you dealer for details) is recommended in case there expected an effect from snow and space between outdoor unit and function unit is more
than 100 mm.

NOTES

1.

Heights of walls in case of Patterns 1 and 2:


Front: 1500 mm

100 or more

50 or more

50 or more

500mm

50 or more

< Suction side >

100 or more

< Front >

<Front>
500 or more

1500mm

50 or more

NOTES

3D059348C

93

Outdoor Unit Product Range

RTSYQ20PA

VRV Classic heat pump


RXYCQ-A
For standard cooling & heating requirements
22

Indoor units
VRV type indoor units

Ventilation
Heat Reclaim ventilation (VAM/VKM)

Control systems

Low noise function


Reluctance brushless DC compressor
Sine wave DC inverter
DC fan motor
E-pass heat exchanger
Manual demand function
94

Outdoor Unit Product Range

Benefits
For projects with standard cooling & heating

requirements
Fits any building as also indoor installation is
possible as a result of high external static pressure
of up to 78.4 Pa. Indoor installation leads to less
piping length, lower installation costs, increased
efficiency and better visual aesthetics
The ability to control each conditioned zone

individually keeps VRV system running costs to an


absolute minimum
Spread your installation cost by phased installation
Connectable to all standard VRV indoor units,
controls and ventilation

Flexible piping design


Total piping length
Longest length actual (Equivalent)
Longest length after first branch

300m
135m (155m)
40m (90m1)

Level difference between indoor and outdoor units

30m

Level difference between indoor units

15m

1 Contact your local dealer for more information and restrictions

95

RXYCQ-A

VRV Classic
Classic VRV configuration
For standard cooling & heating requirements
Connectable to all standard VRV indoor units, controls and
ventilation
Contains all standard VRV features

RXYCQ14-20A

Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Nom.
Nom.
Cooling
Heating

Nom.
Nom.

EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz

GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

Contains fluorinated greenhouse gases

96

Actual

RXYCQ
HP
kW
kW
kW
kW
kW
kW

mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A

8A
8
20.0
22.4
6.60
5.80
3.03
3.86

10A
10
25.0
28.0
6.74
7.00
3.71
4.00

100
200
200
1,680x635x765
159
95
78
58

125
250
250
187
171
59

12A
12
30.0
33.6
8.77
8.62
3.42
3.90
150
300
360
1,680x930x765
240
185
81
61

6.2
12.9

7.7
16.1

8.4
17.5

15.9

9.52
19.1

22.2

14A
14
35.0
31.5
11.4
8.18
3.07
3.85
64
175
350
420

16A
16
40.0
44.8
12.9
11.8
3.10
3.80
200
400
480

196
64
-5~43
-20~15.5
R-410A
8.6
18
2,087.5

18A
18
45.0
50.4
15.0
13.8
3.00
3.65
225
450
540
1,680x1,240x765
316
233
86
65

11.3
23.6

11.5
24

12.7

25

250
500
600
324
239
88
66

11.7
24.4
15.9

28.6
300
3N~/50/380-415

16

20A
20
50.4
56.5
17.9
16.1
2.81
3.50

40

Detailed technical drawings


RXYCQ8A
RXYCQ8A

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)
(Pitch of foundation
bolt holes)

(Pitch of foundation bolt holes)

Detail for front side

Detail for bottom side


(knock-out hole)

Outdoor Unit Product Range

(knock-out hole)

(knock-out hole)

(knock-out hole)

No.
1
2
3
4
5
6
7
8
9
10

(knock-out hole)

Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)

NOTES

Remarks
9.5 Brazing connection
15.9 Brazing connection
Inside of switch box (M8)
62
45
27
50
27

1. Detail for front side and detail for bottom side indicate the dimensions
after fixing the attached piping.

3D080764

RXYCQ10-14A
RXYCQ10-14A

(Pitch of foundation
bolt holes)

(Pitch of foundation bolt holes)

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)

(for 10HP)

Detail for front side

(knock-out hole)

Detail for bottom side

(knock-out hole)

(knock-out hole)

(knock-out hole)

No.
1
2
3
4
5
6
7
8
9
10

Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)

(knock-out hole)

Remarks
See note 2
See note 2
Inside of switch box (M8)
62
45
27
65.5
27

NOTES

1. Detail for front side and detail for bottom side indicate the dimensions after fixing the
attached piping.
2. Gas pipe:
19.1 Brazing connection: RXYCQ10
22.2 Brazing connection: RXYCQ12
28.6 Brazing connection: RXYCQ14
Liquid pipe:
9.5 Brazing connection: RXYCQ10, RXYCQ12
28.6 Brazing connection: RXYCQ14
3D080763

97

Detailed technical drawings


RXYCQ16-20A
RXYCQ16-20A

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)
(Pitch of foundation
bolt holes)

(Pitch of foundation bolt holes)

Detail for front side

Detail for bottom side


(knock-out hole)
(knock-out hole)

(knock-out hole)

Model.
RXYCQ16
RXYCQ18
RXYCQ20

(knock-out hole)

No.
1
2
3
4
5
6
7
8
9
10

AA
83
83
63

AB
179
179
160

(knock-out hole)

Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)

Remarks
See note 2
See note 2
Inside of switch box (M8)
62
45
27
65.5
27

NOTES

1. Detail for front side and detail for bottom side indicate the dimensions after fixing the
attached piping.
2. Gas pipe:
28.6 Brazing connection: RXYCQ16,18,20
Liquid pipe:
12.7 Brazing connection: RXYCQ20
9.5 Brazing connection: RXYCQ16,18

3D080767

RXYCQ-A
RXYCQ-A
For single unit installation
< Pattern 1 >

For installation in rows


< Pattern 1 >

300 or more

10 or more
< Pattern 2 >

50 or more

300 or more

10 or more 10 or more

< Front >


500 or more
100 or more

< Front >


500 or more

20 or more

< Pattern 2 >

50 or more 50 or more

300 or more

< Front >


200 or more

300 or more

20 or more

< Front >


500 or more

10 or more

300 or more

10 or more

< Front >


600 or more

20 or more

10 or more
10 or more

10 or more

< Front >


500 or more

20 or more

10 or more

< Front >


500 or more

20 or more
< Front >

10 or more

100 or more

100 or more

< Pattern 3 >

< Pattern 3 >

For centralized group layout


< Pattern 1 >

Wall height unrestriced

< Front >


500 or more

100 or more

Wall height unrestriced

300 or more

10 or more

20 or more

10 or more

50 or more
< Pattern 2 >
100 or more

100 or more

300 or more

400 or more
200 or more

< Front >

400 or more

50 or more

< Front >


500 or more

100 or more

50 or more
50 or more

50 or more

< Front >


500 or more

100 or more

50 or more
50 or more

< Front >


500 or more

100 or more

100 or more
< Front >

50 or more

100 or more

50 or more

98

h1

< Suction side >

500 mm

< Front >

1. Heights of walls in case of Patterns 1 and 2:


Front: 1500mm
Suction side: 500mm
Side: height unrestricted.
Installation space to be shown in this drawing is based on the cooling operation at 35 degrees outdoor air temperature. When
the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability because of much generation
load of heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces
respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best
fit in the space available always bearing in mind the need to leave enough space for a person to pass between units and
wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout
should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

1500 mm

NOTES

h2

< Unit: mm >

3D051451W

Replacement VRV
Quick & quality replacement for R-22
and R-407C systems
Air curtain
Biddle Air curtain for VRV (CYV)

Indoor units
VRV type indoor units

Outdoor Unit Product Range

22

Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit

Control systems

VRV III
VRV IV

Heat pump

Heat pump & Heat recovery

Variable refrigerant temperature

Automatic refrigerant charge

Customize your VRV for best seasonal efficiency & comfort

Night quiet mode


Low noise function

VRV configurator

Full inverter compressors

Software for simplified commissioning, configuration and customisation


7 segment indicator

4 side heat exchanger

Automatic refrigerant charge

Reluctance brushless DC compressor

Night quiet mode

Sine wave DC inverter

Low noise function

DC fan motor

Full inverter compressors

E-pass heat exchanger

Gas cooled PCB

I demand function

Reluctance brushless DC compressor


Sine wave DC inverter
DC fan motor
E-pass heat exchanger
I demand function
Manual demand function

Manual demand function


For more information on these features refer to the VRV IV technologies tab

99

Replacement
technology
The quick and quality way of
upgrading R-22 and R-407C systems
These benefits will convince your customer
Drastically improve your efficiency, comfort and reliability
Avoid loss of business

Lower long-term costs

Replacing now prevents unplanned, lengthy downtime


of air conditioning systems. It also avoids loss of business for shops,
complaints from guests in hotels, lower working efficiency and loss
of tenants in offices.

EU Directives prohibit system repairs with R-22 after January 1, 2015.


Delaying the required R-22 replacement until an unplanned system
breakdown is a losing game. Replacement day will come. Installing
a technically advanced system lowers energy consumption and
maintenance costs from day one.

Quick and easy installation

Up to 48%
less consumption

No interruption of daily business while replacing the system


thanks to phased-in, fast installation.

Smaller footprint, more performance


Thanks to a smaller footprint, Daikin outdoor units save space.
Also, more indoor units can be connected to
the new outdoor unit compared to the old system,
allowing to increase capacity.

Keep your refrigerant piping


The Daikin
low-cost upgrade solution

Replace indoor units


and BS boxes
Contact your local dealer to
check compatibility in case you
need to keep
the indoor units.

!
100

Replace outdoor units

Comparison of 10HP systems:


Cooling mode
Heating mode
R-22 (RSXY-KA7)

R-407C (RSXYP-L7)

R-410A (RXYQQ-T)

Your copper pipes will last for multiple generations


- copper pipes used in air conditioning systems tested by Daikin
will last over 60 years after installation.
- Japan/China have replaced with VRV
Q-series already 10 years ago!
Umeda Center Building, Japan
- original A/C system: 20 years in use
- replacement with VRV Q-series:
2006 - 2009
2013
- capacity up from 1620HP to
(1st)
2322HP
- SHASE renewal award:

! Planning your replacement in future?


Monitor your system now!

Outdoor Unit Product Range

Your building use might have changed


over the years. Monitoring and Daikin
expert advice prepare you for an optimum
replacement to maximize efficiency and
comfort, while minizing the investment cost
of your new system.

VRV-Q benefits to increase your profit


Optimise your business

Compare installation steps

Less installation time

Conventional solution

VRV-Q

1
2
3
4
5
6
7

1 Recover refrigerant
2 Remove units

Tackle more projects in less time thanks to faster installation.


It is more profitable than replacing the full system with new
piping.

Lower installation costs

Reducing installation costs enables you to offer customers


the most cost-effective solution and improve your
competitive edge.

Replace non-Daikin systems

It is a trouble-free replacement solution for Daikin systems


and for systems made by other manufacturers.

Recover refrigerant
Remove units
Remove refrigerant pipes
Install new piping and wiring
Install new units
Leak test
Vacuum drying

8 Refrigerant charging
9 Test operation

Easy as one-two-three

Re-use existing piping


and wiring
3 Install new units
4 Leak test
5 Vacuum drying
6 Auromatic refrigerant
charging, cleaning and
testing

A simple solution for replacement technology enables you


to handle more projects for more customers in less time and
offer them the best price! Everybody gains.

Up to 45% shorter
installation time

Automatic refrigerant charge


The unique automatic refrigerant charge eliminates the need
to calculate refrigerant volume and ensures that the system
will operate perfectly. Not knowing the exact piping lengths
because of changes or mistakes in case you didnt do the
original installation or replacing a competitor installation no
longer poses a problem.

Automatic pipe cleaning


There is no need to clean inside piping as this is handled
automatically by the VRV-Q unit. Finally the test operation is
performed automatically to save time.

One touch
convenience:
Measure and charge

refrigerant
Automatic pipe

cleaning
Test operation
101

RQCEQ-P3 (heat recovery)

Replacement VRV
Cost effective and fast replacement as only the outdoor and
indoor unit needs to be replaced, meaning almost no work has to
be carried out inside the building
Efficiency gains of more than 70% can be realized, by virtue of
technological developments in heat pump technology and the
more efficient R-410A refrigerant
Less intrusive and time consuming installation compared
to installing a new system, as the refrigerant piping can be
maintained
Unique automatic refrigerant charge eliminates the need to
calculate refrigerant volume and allows safe replacement of
competitor replacement
Automatic cleaning of refrigerant piping ensures a clean piping
network, even when a compressor breakdown has occurred
Accurate temperature control, fresh air provision, air handling
units and Biddle air curtains all integrated in a single system
requiring only one single point of contact
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors (for RXYQQ-T units)
Possibility to add indoor units and increase capacity without
changing the refrigerant piping
Possibility to spread the various stages of replacement thanks to
the modular design of the VRV system
Free combination of outdoor units to meet installation space or
efficiency requirements (for RXYQQ-T units)
Contains all standard VRV features

Outdoor system
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

RQCEQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Nom.
Nom.
Cooling
Heating

HP
kW
kW
kW
kW
kW
kW

Nom.
Nom.

EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Sound pressure level
Cooling
Nom.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)

Actual

dBA
mm
mm
mm
m
A

RQCEQ712-848P

280P3
360P3
460P3
500P3
540P3
636P3
712P3
744P3
816P3
848P3
RQEQ140P3 RQEQ180P3
RQEQ140P3
RQEQ180P3 RQEQ212P3
RQEQ140P3
RQEQ180P3 RQEQ212P3
RQEQ140P3 RQEQ180P3 RQEQ140P3
RQEQ180P3
RQEQ212P3
RQEQ180P3
RQEQ212P3
RQEQ180P3
RQEQ212P3 RQEQ180P3
RQEQ212P3
RQEQ212P3
10
13
16
18
20
22
24
26
28
30
28.0
36.0
45.0
50.0
54.0
63.6
71.2
74.4
81.6
84.8
32.0
40.0
52.0
56.0
60.0
67.2
78.4
80.8
87.2
89.6
7.04
10.3
12.2
13.9
15.5
21.9
21.2
23.3
27.1
29.2
8.00
10.7
13.4
14.7
16.1
17.7
20.7
21.2
23.1
23.6
3.98
3.48
3.77
3.61
3.48
2.90
3.36
3.19
3.01
2.90
4.00
3.72
3.89
3.80
3.72
3.79
3.80
3.81
3.77
3.79
21
28
34
39
43
47
52
56
60
64
140
180
230
250
270
318
356
372
408
424
280
360
500
540
636
712
744
816
848
364
468
598
650
702
827
926
967.0
1,061
1,102
57
61
62
63
64
63
64
65
66
9.52
12.7
15.9
19.1
22.2
25.4
28.6
34.9
19.1
22.2
25.4
28.6
300
30
40
50
60
70
80
90

Contains fluorinated greenhouse gases

Outdoor unit module


Dimensions
Unit
Weight
Unit
Fan
Air flow rate
Sound power level
Cooling
Sound pressure level
Cooling
Operation range
Cooling
Heating
Refrigerant
Type
Charge

Power supply
Current - 50Hz

102

Height/Width/Depth
Cooling
Nom.
Nom.
Nom.
Min.~Max.
Min.~Max.

GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

RQEQ
mm
kg
m/min
dBA
dBA
CDB
CWB

140P3

kg
TCOeq

10.3
21.5

Hz/V
A

180P3
1,680/635/765

212P3

175

179

95
54

15

110
58
-5~43
-20~15.5
R-410A
10.6
22.1
2,087.5
3~/50/380-415
20

60

11.2
23.4

22.5

RQYQ-P/RXYQQ-T (heat pump)

Outdoor Unit Product Range

Replacement VRV

RXYQQ8-12T

Outdoor unit
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

RXYQQ-T
Outdoor unit module 1
Nom.
Nom.
Max.
Cooling
Heating

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge

Piping connections

Power supply
Current - 50Hz
Outdoor unit
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

HP
kW
kW
kW
kW
kW
kW
kW

kW
kW

mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq

Actual

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3
HP
kW
kW
kW
kW
kW
kW
kW

Nom.
Nom.
Max.

EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)

8T

10T

12T

8
22.4
22.4
25.00
5.21
4.75
5.5
4.30
7.53
6.37
4.72
4.54

10
28.0
28.0
31.50
7.29
6.29
7.38
3.84
7.20
5.67
4.45
4.27

12
33.5
33.5
37.50
8.98
7.77
9.1
3.73
6.96
5.50
4.31
4.12

100
200
260

125
250
325
1,685x930x765
194
175
79
58

150
300
390

14T
14
40.0
40.00
45.00
11.0
9.52
11.2
3.64
6.83
5.31
4.20
4.02
64
175
350
455

185

223

6
12.5

6.3
13.2

187
162
78

11.1
23.2

5.9
12.3

15.9

9.52
19.1

16T

18T

20T

16
45.0
45.0
50.00
13.0
11.1
12.8
3.46
6.50
5.05
4.05
3.91

18
50.4
50.4
56.50
15.0
12.6
14.6
3.36
6.38
4.97
4.00
3.87

20
56.0
56.0
63.00
18.5
14.50
17.0
3.03
5.67
4.42
3.86
3.71

200
225
400
450
520
585
1,685x1,240x765
305

81
61
-5~43
-20~15.5
R-410A

250
500
650
314

260

251

64

65

261
88
66

10.4
21.7

11.7
24.4

11.8
24.6

86

10.3
21.5
2,087.5

mm
mm
m
Hz/V
A
RXYQQ-T

Nom.
Nom.
Max.
Cooling
Heating

RQYQ140P
RQYQ140P
5
14.0
16.0
3.36
3.91
4.17
4.09
10
62.5
125
162.5
1,680x635x765
175
95
54.0

kW
kW

Actual

mm
mm
m
A

3~/50/380-415
15

20

12.7
22.2

25

15.9
28.6

300
3N~/50/380-415
32

40

50

22T
24T
26T
28T
30T
32T
34T
36T
38T
40T
42T
RXYQQ10T RXYQQ8T
RXYQQ12T
RXYQQ16T
RXYQQ8T
RXYQQ10T
RXYQQ12T RXYQQ16T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ16T RXYQQ18T RXYQQ20T RXYQQ10T RXYQQ12T RXYQQ16T
RXYQQ20T RXYQQ18T RXYQQ16T
22
24
26
28
30
32
34
36
38
40
42
61.5
67.4
73.5
78.5
83.9
90.0
95.4
101.0
106.3
111.9
118.0
69.0
75.0
82.5
87.5
83.9
100.0
95.4
113.0
106.3
111.9
131.5
94.0
106.5
119.0
125.5
16.27
18.21
19.98
21.98
24.0
26.0
28.0
31.5
29.2
31.3
33.29
16.48
18.31
20.30
21.90
20.4
25.6
23.7
29.8
25.1
26.7
32.98
23.7
27.4
29.2
31.1
3.78
3.70
3.68
3.57
3.5
3.4
3.2
3.6
3.54
7.07
6.81
6.89
6.69
6.60
6.50
6.44
6.02
6.36
6.74
6.65
5.58
5.42
5.39
5.23
5.17
5.05
5.01
4.68
5.03
5.29
5.19
4.37
4.25
4.16
4.10
4.05
4.00
3.95
4.2
4.14
4.19
4.10
4.06
4.00
3.91
3.90
3.79
4.1
4.0
3.99
64
275
300
325
350
375
400
425
450
475
500
525
550
600
650
700
750
800
850
900
950
1,000
1,050
715
780
845
910
975
1,040
1,105
1,170
1,235
1,300
1,365
15.9
19.1
28.6
34.9
41.3
300
63
80
100

Contains fluorinated greenhouse gases | The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | The AUTOMATIC ESEER value corresponds with normal VRV4
Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation) | Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor,
etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)

103

Detailed technical drawings


RQCEQ280-360P
RQCEQ280-360P3
Oblong holes

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

Oblong holes

(Foundation bolt holes)

(Pitch of foundation bolt holes)

(Foundation bolt holes)

Outdoor unit 1

Outdoor unit 2

or more

SPACE EXAMPLE FOR INSTALLATION

(Front)
or more

Unit:mm

Model name
RQCEQ280P3
RQCEQ360P3

or more

< Suction side >

or more

< Front >

or more

or more

Outdoor unit 1
RQEQ140P3
RQEQ180P3

Drawing N.
3D066441A
3D066441A

Outdoor Unit 2
RQEQ140P3
RQEQ180P3

Drawing N.
3D066441A
3D066441A

NOTES

1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D066856A

104

Detailed technical drawings


RQCEQ460-636P
RQCEQ460-636P3
Oblong holes
(Foundation bolt hole)

Oblong holes

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

Oblong holes
(Foundation bolt hole)

(Pitch of foundation bolt holes)

(Foundation bolt hole)

Outdoor Unit 2

Outdoor Unit 3

Outdoor Unit Product Range

Outdoor Unit 1

or more

or more

SPACE EXAMPLE FOR INSTALLATION

< Front >

or more

or more

or more
or more

< Suction side >

or more

or more

Unit:mm

Model name
RQCEQ460P3
RQCEQ500P3
RQCEQ540P3
RQCEQ636P3

Outdoor unit 1
RQEQ180P 3
RQEQ180P3
RQEQ180P3
RQEQ212P 3

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

Outdoor Unit 2
RQEQ140P3
RQEQ180P3
RQEQ180P3
RQEQ212P3

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

Outdoor unit 1
RQEQ140P3
RQEQ140P3
RQEQ180P3
RQEQ212P3

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

NOTES

1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D066860A

105

Detailed technical drawings


RQCEQ721-848P
RQCEQ712-848P3

Oblong holes
(Foundation bolt hole)
Oblong holes
(Foundation bolt hole)

Oblong holes

Oblong holes

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

(Pitch of foundation bolt holes)

(Foundation bolt hole)

(Pitch of foundation bolt holes)

(Foundation bolt hole)

(Foundation bolt hole)

Outdoor Unit 1

Outdoor Unit 2

Outdoor Unit 3

Outdoor Unit 4

or more

or more

or more

SPACE EXAMPLE FOR INSTALLATION

or more

< Front >

or more

or more

or more
or more

or more

< Suction side >

or more

Unit: mm
Model name
RQCEQ712P3
RQCEQ744P3
RQCEQ816P3
RQCEQ848P3

Outdoor unit 1
RQEQ212P3
RQEQ212P3
RQEQ212P3
RQEQ212P3

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

Outdoor Unit 2
RQEQ180P3
RQEQ212P3
RQEQ212P3
RQEQ212P3

Drawing N.
3D0664413
3D0664413
3D0664413
3D0664413

Outdoor unit 3
RQEQ180PA
RQEQ180PA
RQEQ212PA
RQEQ212PA

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

Outdoor unit 4
RQEQ140P3
RQEQ140P3
RQEQ180P3
RQEQ212P3

Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A

NOTES

1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

3D066865A

106

Detailed technical drawings


RQYQ140P
(Pitch of foundation bolt holes)

4-15 x 22.5 - mm - Oblong holes


(Foundation bolt hole)
(Pitch of foundation bolt holes)

RQYQ140P

BACK SIDE UP PART

DETAIL FOR FRONT SIDE

(knock-out hole)

DETAIL FOR BOTTOM SIDE

Outdoor Unit Product Range

(knock-out hole)

(knock-out hole)

(knock-out hole)

(knock-out hole)

No.
1
2
3
4
5
6
7
8
9
10

Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)

Remarks
9.5 Brazing connection
See note 3.
Inside of switch box (M8)
62
45
27
50
27
See note 2.
See note 2.

3D066442
NOTES

shows the dimensions after xing the accessory pipes.

For piping connection method (front and bottom sides) see the installation manual.

Gas pipe
15.9 Brazing connection: RQYQ140P

107

RXYQ8-12T
RXYQQ8-12T

Detailed technical
drawings
2

Detail A

729

Detail B

Detail A

Pitch of foundation bolt holes

Foundation bolt hole

4-15x22.5mmOblong hole
Foundation bolt hole

Detail B

107

107

112

112

134

353

134
125

125
4-15x22.5mmOblong hole
Foundation bolt hole

70

125

10

View C

10

View C

10

10

4-15x22.5mmOblong hole
Foundation bolt hole

11

107
70

112

729

4-15x22.5mmOblong hole
Foundation bolt hole
4-15x22.5mmOblong hole

353

134

70

66

729

729

Detail B

106

AC

353
125

70

Detail B

Detail A

160

66
106
106

107

AC

100
Detail A
AC

66

106

160

160

112

100

353
134

View C

11

View C

11
11

1685

AB

AA

AC

Detail B
729

339

66

100

66
106

Pitch of foundation bolt holes

AA

Detail A

Pitch of foundation bolt holes

339

AC

AA

AB

AA
339

AB

160

160

Pitch of foundation bolt holes


766

100

Pitch of foundation bolt holes

339
AB

AA

RYYQ8-12T
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T

AB

RXYQQ8-12T3

Pitch of foundation bolt holes


766
Pitch
of foundation
bolt holes
Pitch
of foundation
bolt holes
766 766

339

1 2

Pitch of foundation bolt holes

RYYQ8-12T
RYMQ8-12T
RYYQ8-12T
RYYQ8-12T
RXYQ8-12T
RYMQ8-12T
RYMQ8-12T
1
RXYQQ8-12T
RXYQ8-12T
RXYQ8-12T
RXYQQ8-12T
RXYQQ8-12T

100

Pitch of foundation bolt holes


766

11

1685

122
131

179

Model
RYYQ8T, RXYQ8T, RXYQQ8T
Model

76

76

5
97

272 107
97

179

259

276

131

179

259

276

122
179 131

DETAIL A
DETAIL B

Notes

107

259

76
DETAIL B
137

76

9
6

122

122
137

97

276

76

131

259
276

515

76

259 179

276

515

515

515
76

6
7

1075

97

137
765

515

76

1685

122

1685

1685

DETAIL B

DETAIL A

AA
248

AB
-

AC
-

RYYQ10-12T, RXYQ10-12T,
RXYQQ10-12T
195
RYYQ8T,
RXYQ8T,
RXYQQ8T
Model
AC
AA
AB
248
208
240
RXYQ10-12T,
RYYQ8T,RYMQ8T
RXYQ8T, RXYQQ8T RYYQ10-12T,248
- RXYQQ10-12T
195
208
240
REMQ5T,
RYMQ10-12T,
REYQ8-12T
RYYQ10-12T,
RXYQ10-12T,
RXYQQ10-12T
195
RYMQ8T
RYMQ8T
248
208 REYQ8-12T
240
REMQ5T, RYMQ10-12T,
5 REYQ8-12T
107REMQ5T, RYMQ10-12T,
240
195
208 Model

RYYQ8T, RXYQ8T, RXYQQ8T


RYYQ10-12T, RXYQ10-12T, RXYQ
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-1

272

328

AA
248
195
248
195

131

765
137
DETAIL B
A
272
DETAILBAindicateDETAIL
272
373
328
the
dimensions after fixing the attached piping.
1. Detail A and detail
Notes
765
765
2. Items 4 - 10:
Knockout
hole.
328
328
373
NotesBNotes
930
indicate the dimensions after fixing the attached piping.
1. Detail A and detail
11 Grounding terminal
3. Gas pipe
2. RYYQ14-20T
Knockout hole.
Items 4 - 10:
373
373
76
A and detail
indicate
the dimensions
after fixingafter
the attached
piping.
76 the dimensions
1. Detail
A andBdetail
B indicate
fixing the
attached piping.
1. Detail
930
RYMQ14-20T
5 11 connection
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T 97
:
10 Pipe routing hole (bottom)
19.1 brazing
107
Inside of the switch box (M8)
2. Items
KnockoutKnockout
hole.
4 - 10: 4 - 10:
Grounding terminal
3. Gas pipe
2. Items
hole.
930
RXYQ14-20T
RYYQ10T,
RYMQ10T,
RXYQ10T,
RXYQQ10T
:
930
22.2 brazing
connection
9 Pipe routing hole (front)
137
1 : 2
RYYQ8T, RYMQ8T,
RXYQ8T,
Pipe routing
hole (bottom) Grounding terminal
pipe
Inside of the switch box (M8)
19.1 brazing connection
terminal
1110Grounding
3. Gas
Gas pipe RXYQQ8T
Inside of the switch box (M8)
DETAIL
B
11
3.
Pitch of foundation
bolt holes
RXYQQ14-20T
DETAIL: A
272
REMQ5T, REYQ8-12T
RYYQ10T, RYMQ10T,
RXYQ10T,
RXYQQ10T
:
25.4
brazing
connection
8 Power cord routing hole (bo
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
:
109 Pipe
routing
holehole
(bottom)
Pipe
routing
(front)
19.1
brazing
connection
: 22.2 brazing
connection
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
10
Pipe
routing
hole
(bottom)

19.1
brazing
connection
1076
765brazing
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :
RYYQ10T, RYMQ10T,
RXYQQ10T :
REMQ5T, REYQ8-12T
: RXYQ10T,
routing
hole
(front) hole (bottom)
22.2connection
brazing connection
9 8 Pipe
28.6 brazing
connection
25.4
65
7 Power cord routing hole (fro
Power
cord
routing
RYYQ10T, RYMQ10T,
RXYQ10T, RXYQQ10T
:
22.2 brazing connection
9 Pipe routing hole (front)
328
REMQ5T,
REYQ8-12T
Notes
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T ::

25.4
brazing
connection
65
Power
cord
routing
hole
(bottom)
8

28.6
brazing
connection
Liquid pipe
7 Power cord routing hole
27
REMQ5T,
REYQ8-12T
: :
6 Power cord routing hole (fro
25.4 brazing connection
65
Power cord routing hole (bottom)
8 (front)
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T

28.6
brazing
connection
7
27
cord routing hole (front)
Liquid pipe
RYYQ12T,
RXYQQ12T
3 fixing: the attached piping.
6 Power
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
65
373
Power
cord routing hole
(front)
5 Power cord routing hole (fro
28.6 brazing connection
A and
detail B RYMQ12T,
indicate theRXYQ12T,
dimensions
after
1. DetailLiquid
7
27
Power
cord
routing
hole
(front)
pipe
6 connection
65 80
cord routing hole (front)
9.5 brazing
RYYQ8-10T,
RYMQ8-10T,
RXYQ
Q8-10T, REMQ5T,
REYQ8-12T
5 Power
Power cord routing hole
RYYQ14-20T
2. Items
Knockout hole.
4 - 10:
LiquidRXYQ8-10T,
pipe
4 Power cord routing hole (sid
6 (front)
Power cord routing hole (front)
RYYQ8-10T,
RYMQ8-10T, RXYQ8-10T,
RXYQ
393 65
9.5 brazing connection
80
5 Power cord routing hole (front)
Q8-10T, REMQ5T,
REYQ8-12T
930
:
9.5 brazing connection
65
4 Power cord routing hole5 (side)
RYYQ8-10T,
RYMQ8-10T,
RXYQ8-10T,
RXYQ
Q8-10T,
REMQ5T,
REYQ8-12T
RYMQ14-20T
80
routing hole
(front)
12.7 brazing
connection
Inside of the switch box (M8)
Grounding
terminal
cord routing hole (side) Power
65
4 Power
11cord
:
3. Gas pipe
Equalising pipe connection
9.5 brazing connectionRYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :
:
Q8-10T,
REMQ5T,
REYQ8-12T
3

12.7
brazing
connection
See
note
3.
134
Equalising pipe connection Power
port cord routing hole (side)
RYYQ12T, RYMQ12T,
RXYQ12T,
RXYQQ12T
:
65
RXYQ14-20T
12.7 brazing
See note 3.
High pressure/low pressure
Equalising pipe connection 4
port
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T ::
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
10
Pipe routing hole (bottom)
19.1connection
brazing connection Equalising pipe
3
1
2
:
3
High pressure/low pressurepipe
gas pipe
1 RYYQ12T,
2
High pressure/low pressure gas Equalising
Pitch of8foundation bolt holes
Equalising RYYQ10T,
pipe Equalising
12.7 brazing connection
See note 3.
pipe routing
connection
port
RYMQ12T,
RXYQ12T,
RXYQQ12T
:
RYMQ10T,
RXYQ10T,
RXYQQ10T
:
pipe
hole
(front)
Pitch of foundation bolt holes
22.2
brazing connection RYMQ8-10T RXYQQ14-20T
9 Pipe
2 Gas pipe connection port
125
3
19.1 brazing
connection
:
2 Gas
Gas
pipe
connection
port
See note See
3. note 3.
2
High
pressure/low
pressure
gas
pipe
pipe
connection
port
1076
RYMQ8-10T
:

19.1
brazing
connection

19.1
brazing
connection
RYMQ8-10T
:
REMQ5T,Equalising
REYQ8-12T
:
pipe
1076
25.4 brazing connection RYMQ12T :
65
8 Power cord routing hole (bottom)
1 Liquid pipe connection port
Liquid
pipe
connection
1
See
note
3.
Liquid
pipe
connection
port2port

22.2
brazing
connection
1
See
note
3.
RYMQ12TRYYQ12T,
:
RYMQ12T
:
See note 3.
Gas pipe connection port
connection
RYMQ12T,: RXYQ12T, RXYQQ12T : 22.2 brazing
22.2
brazing
connection
RYMQ8-10T
19.1
brazing
connection
28.6
brazing
connection
No. Part name
7 Power cord routing holeRemark
27
(front) Remark
name
Part
name
No.
No.Part
High pressure/low pressure gas pipe
High
pressure/low
pressure gas pipe
1 Liquid pipe connection port
High pressure/low
pressure
gas pipe
See note 3.
22.2 brazing connection
Liquid pipeRYMQ12T : 3
6
65
19.13brazing connection
19.1
brazing connection
REMQ5T,: REYQ8-12T :
REMQ5T, REYQ8-12T :
19.1 brazing
connection
Remark
No. Part namePower cord routing hole (front)
REMQ5T,
REYQ8-12T
RYYQ14-20T
High pressure/low pressure gas pipe

71

160
100

106

70

106

160
AA
AA

Detail B

View C

134

125

393
134

107

125

View C

4-15x22.5mm - Oblong hole


Foundation bolt hole

10

4-15x22.5mm - Oblong hole


4-15x22.5mm - Oblong hole Foundation bolt hole

11

View C

View C

11

Foundation bolt hole

1685

Detail A

Remark

10

Detail B

Detail A

107

112

107

70

729

Detail B

2D079532B

See note 3.

70

71

100

10

2D079532B
2D079532B

See note 3.

393

112

Detail A

10

Part name

107

AA
4-15x22.5mm - Oblong hole
Foundation bolt hole

Liquid pipe connection port

106

112

11

729

310

Detail B

192

AB

192
AB

AA

Detail A

160

See note 3.

125

Gas pipe connection port

71

100

106

160

393

Power cord routing hole (side)

70

71

80
65

Power cord routing hole (front)

134connection port
Equalising pipe
High pressure/low pressure gas pipe

2
1
No.

112

4-15x22.5mm
- Oblong hole
Pitch of foundation
bolt holes
1076 Foundation bolt hole

Pitch of foundation bolt holes

729

AB

Detail B

19.1 brazing connection

100

310

22.2 brazing connection

Detail A

310

19.1 brazing connection

192

AB

192

310

RXYQQ14-20T

Equalising pipe
160
RYYQ14-20T
RYMQ8-10T :
RYMQ14-20T
AA
RYMQ12T :
RXYQ14-20T
1
High
pressure/low
pressure
gas pipe 2
RXYQQ14-20T
REMQ5T, REYQ8-12T :

5
4

Pitch of foundation bolt holes


1076

Pitch of foundation bolt holes

729

9.5
connection
brazing
19.1 brazing
connection
71
12.7 brazing connection
106

Pitch of foundation bolt holes

192

AB

310

RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ

REMQ5T, REYQ8-12T
REYQ8-12T :
RYMQ14-20T
Q8-10T, REMQ5T,
:
RXYQ14-20T
1 RXYQQ12T
2
RYYQ12T, RYMQ12T,
:
100 RXYQ12T,
RXYQQ14-20T

Pitch of foundation bolt holes

YYQ14-20T
YMQ14-20T
XYQ14-20T
XYQQ14-20T

4
11

11

122

1685

1685

RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :

RYMQ18-20T

3. Gas pipe
Equalising pipe :
REYQ14-20T
RYMQ14-16T

28.6 brazing connection


25.4connection
brazing connection
22.2 brazing
::
High pressure/low pressure gas pipe
RYMQ18-20T
:
RYYQ14-20T,
RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
:
28.6connection
brazing connection
28.6 brazing
REYQ14-20T
:
22.2 brazing connection
High
pressure/low
pressure
gas
pipe
Liquid pipe
REYQ14-20T
:
RYYQ14-16T,
RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T,
REYQ14-20T : 22.2 brazing
12.7connection
brazing connection

Equalising pipe

RYMQ14-16T
108
RYMQ18-20T

High pressure/low pressure gas pipe

15.9 brazing connection

122
97

C5

22.2 brazing connection


28.6 brazing connection

DETAIL B

179

11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
7 Power cord routing hole (front)
2. Items 4 - 10:
hole. 5
1240
97 107 Knockout
6 Power cord routing hole (front)
3. Gas pipe
5 Power cord routing hole (front)
272
DETAIL A
25.4 brazing connection
REYQ14-20T
:
4

Notes

272

328

373

1240

765

Power cord routing hole (side)

107

Inside of the switch box (M8)

328

65
27
65
80
65

High pressure/low pressure gas pipe

High pressure/low pressure gas pipe


REYQ14-20T

Equalising pipe connection port

8
7
6
5
4

Remark

Power cord routing hole (bottom)


Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (side)

AB
205
210

AB
205
210

373
1240

11

Grou

2D079533B
10

See note 3.

3 connection port
See note 3.
2 Gas pipe
High pressure/low pressure gas pipe
11 Grounding terminal
portport
Seenote
note
1 Liquid2 pipe
Gasconnection
pipe connection
10
3. 3.
Pipe routing
holeconnection
(bottom) See
22.2
brazing
Remark
No. Part name
note 3.
1 Liquid pipe connection port
9 Pipe routing hole (front) See

AA
240
240

Model
RYMQ14-16T, RXYQQ14-16T,
RYMQ18-20T, RXYQQ18-20T

272

DETAIL A

AA
240
240

328 RXYQ14-20T, RXYQQ14-20T


RYYQ14-20T, RYMQ14-20T,
28.6
brazing
11 Grounding terminal :
Inside of the switch box (M8)See note 3.
Equalising
pipe
connection
portconnection
10 Pipe routing hole (bottom)3 High pressure/low pressure gas pipe
Liquid pipe
373
9 Pipe routing hole (front) 2 Gas pipe connection port
See note 3.
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T,
REYQ14-20T
:
12.7 brazing connection
11 Grounding
Inside of the switch box (M8)
terminal
65
81240
Power
cord
routing
hole
(bottom)
See note 3.
10 Pipe routing hole (bottom)
1 Liquid pipe connection port
7 Power
27
hole
(front)
RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T
: (front)
Pipe routing
routing hole
9 cord
Remark
Part name 15.9 brazing connection
No.
65
6 Power
65
8 cord
routing
hole (front)
Power
cord routing
hole (bottom)
80
7 cord
27
5 Power
Power
cord routing
hole (front)
routing
hole (front)
Equalising pipe
65
6 cord
Power
cord routing
hole (front)
65
4 Power
routing
hole (side)
RYMQ14-16T
:
22.2 brazing connection
80
5 Power
routing hole
(front)
Equalising
pipecord
connection
port
See note 3.
65
3
4 Power cord routing hole (side)
RYMQ18-20T
:
28.6 brazing connection

No. Part name

97

137

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T

76

76

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T

122

1240

107

131

179

12.7 brazing connection

1. Detail A and detail B indicate the dimensions after fixing the attached piping.
15.9 brazing connection
RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T
:
2. Items 4 - 10:
Knockout hole.
22.2 brazing connection
:

RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T

373

DETAIL A

Notes

Equalising pipe
25.4 brazing connection
:
indicate the dimensions
piping.
1. Detail A and detail B 76
22.2 brazing connection
RYMQ14-16T
: after fixing the attached 76
Items 4 - 10: RXYQQ14-20T
Knockout hole.
RYYQ14-20T, RYMQ14-20T,2.RXYQ14-20T,
:
28.6 brazing connection
RYMQ18-20T
:
28.6 brazing connection
Gas pipe
3.
137
Liquid pipe
DETAIL
25.4
brazing B
connection
REYQ14-20T
:
High pressure/low
pressure gas pipe
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :
12.7 brazing connection
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T,
RXYQQ14-20T
:
28.6
brazing
connection
REYQ14-20T
: 765
22.2
brazing
connection
15.9 brazing connection
RYYQ18-20T, RYMQ18-20T, RXYQ18-20T,
RXYQQ18-20T
:
Notes Liquid pipe
Equalising pipe
RYMQ14-16T

131

259

276

515

328

12.7 brazing connection


DETAIL
B brazing connection
15.9

272

276

137

107

259

the dimensions
after fixing
the attached
piping.
1. Detail A and detail B indicate
RYYQ18-20T,
RYMQ18-20T,
RXYQ18-20T,
RXYQQ18-20T
765
2. Items 4 - 10:
Knockout hole.

3. Gas pipe
REYQ14-20T

97

131

515

Notes

25.4 brazing connection


DETAIL A
28.6 brazing connection

179

328

276

272
7
373

122

131

107

259

DETAIL A
259

276

Notes

131

259

97

DETAIL B

1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.
76
76 pipe
3. Gas
REYQ14-20T
:
137
DETAIL B :
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
765
Liquid pipe
76
76
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :

515

137

765

1685

122

4
179

515

76

179

1685

276

515

4
76

Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T

Inside of the switch box (M8)

65
27
65
80
65

2D079533B

2D079533B

9
8
7
6
5
4
3

Pipe

Pipe

Powe

Pow

Pow

Powe

Pow

Equa

High

2 Gas
1 Liqui
No. Part

For single unit installation

For installation in rows

(Pattern 1)

(Pattern 1)

(Pattern 1)

300 or more

300 or more

RQYQ140P

10 or
more

10 or
more

(FRONT)
500 or more

50 or
more 50 or more

(FRONT)
500 or more

(Pattern103)
or more
500
or more
300 or more

10 or more

20 or more
(FRONT)
500 or more(PATTERN 1)

(Pattern 2)

300 or more

100 or more

(Pattern 3)

Wall height
unrestricted

100 or more

(FRONT)
500 or more

10 or more
10 or more

(FRONT)
500 or more

10 or more
10 or more

300 or more

20 or more

10 or more 10 or more

100 or
more

900 or more

50 or more

(Front)

500
or more

50 or more

100 or
more
50 or
more 50 or more

100 or more

500
or more

100 or more

10 or more

50 or more

400 or more

(FRONT)

10 or more

20 or more
500 or more
(FRONT)(PATTERN 1)

600100
or more
or more

100 or more

(FRONT)
500 or more

20 or more
100 or more
500 or more

500
or more

(FRONT)
500 or more

100 or
more
10 or more
50 or more
50 or more

20 or more

10 or more

10 or more

50(Front)
or more
50 or more

100 or more

10 or more

or more
100 or20 more

(PATTERN 3)

100 or more

50 or more

(Front)
500 or more

100 or more

50 or more

50 or more

500 or more

500 or more

RYYQ-T
RYMQ-T (Front)
RXYQ-T 200 or more
RXYQQ-T
(Unit : mm)

100 or more

50 or more

(Front)

400 or more

50 or more

400 or more

100 or more

50 or more

100 or more

100 or more

50 or more

500 or more

(Front)

50 or more

For installation in rows

(Front)

100 or more

50 or more

(Unit : mm)

For single unit installation

500
or more

<Front>

400 or more

50 or more

600 or more

(Front)

200 or more

500 or more

<Unit = mm>

(Front)

50 or more

Wall height
unrestricted

300 or more

(Front)
10 or more
500
or (FRONT)
more
50 or more

(PATTERN 2)

100 or more

(Front)

50 or more

600 or more

100 or more

(PATTERN 2)

100 or more

Wall height unrestricted

900
or more

20 or more

10 or
or more
50
more 50 or more

(Front)

(PATTERN 3)

10 or more

20 or more

100 or more

300

300 or moreor more


10 or more

(PATTERN 2)

50 or more

500 or more

(FRONT)

10 or more

10 or more

500
or more

(Front)

(Front)

10 or more

(Front)
100 or more

50 or more

(FRONT)
500 or more

300 or more

400 or more
200 or more

10 or more

300 or more

20 or more

10 or more

(PATTERN 2)

(FRONT)
200 or more

(PATTERN
1)
20 or more

300 or more

(Front)

(Front)

100 or more

10 or more

20 or more

50 or more

10 or more
Wall
height unrestricted
20
or more

20 or more
500 or more

20 or more

(PATTERN 2)

50 or more

For centralized group layout

10 or more

(PATTERN 1)

(Front)

10 or more

20 or more

(FRONT)
600 or more

Outdoor Unit Product Range

100 or more

For installation in rows

(PATTERN 1)

50 or more

10 or more 10 or more

500 or more

(FRONT)

(Pattern 2)

100 or more
For single unit installation

300
or more

20 or more

(FRONT)
500 or more

300 or more

<Suction side>

(Pattern 2)

20 or more

Detailed technical drawings

300 or more

For centralized group layout

50 or more
(Unit : mm)

3D066327

NOTES
(Pattern 1)
(Pattern 1)
(Pattern 1)
Heights of walls in case of patterns 1 and 2: Front: 1500mm. Suction side: 500 mm. Side: Height unrestricted. Installation space to be shown in this drawing
300
or
more
300 or outdoor
more
300 or more
is based on the cooling operation at 35 degrees
air temperature. When the design outdoor
air temperatur exceeds 35 degrees300oror the
more load exceeds
NOTES
maximum ability because of much generation load heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing.

500 or more

(FRONT)

of walls
in case
of patterns
1then
andh2/2
2: and h1/2 should be added to the front and suction side service spaces respectively as shown in the gure on
10 or
10 orare
2 1. 10Heights
Ifor more
the above
wall heights
exceeded
more
more
(FRONT)
20 or more
20 or more
10 or more 10 or more
20 or more
(FRONT)
10 or more
(FRONT)
20 or more
10 or more 10 or more
(FRONT)
Front:
1500mm
the right.
500 or more
500 or more
10 or more
500 or more

(Front)

20 or more

600 or more

10 or more

(Suction side)

10 or more

RQYQ140P

For centralized group layout

Suction
side: 500mm
900 or more
When installing
the units the most appropriate pattern should be selected from those shown above in order to obtain the best t in the space available always
Side:
Height
unrestricted
(Pattern
(Pattern
2) room for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed
bearing
in2)mind
the need to leave
enough
RYYQ-T
100 orfor
more
Installation
space
asin shown
on patterns
this drawing
is 100
based
on the
at 35 degrees
outdoor
air temperature.
or more
than are catered
the above
your layouts
should
takecooling
accountoperation
of the possibility
of
short circuits.)
300 or more
or more
20 or more
10 or more
(FRONT)
RYMQ-Tthe design outdoor air temperature exceeds 35 degrees or the load 10exceeds
10 or take
more the
20 suction
or more
500 orspace
more 10more
or more
of much
all outdoor
unit,
side
500 or more
10 or more load of heat
20 orinmore
10 or more
4 When
The units should be installed to leave sufcient space at the front for the on site refrigerant maximum
piping
workability
to be carried
outgeneration
comfortably.
(FRONT)
RXYQ-T
broadly than the space as shown on this drawing.
(Pattern 2)
50 or
RXYQQ-T
2. 50Iforthe
wall heights
and h1/2 should
to the front and suction side service spaces respectively as shown in the figure on the right.
more above(FRONT)
50 or exceeded
more
more are
100 orthen
more h2/2 (FRONT)
100 or morebe added
50 or more
500 or more
or more be selected from those shown above in order to obtain the best fit in the
3. When installing
the units most appropriate pattern500should
100 or
500 or more
(FRONT)
100 or
more and also for the air to circulate freely.
space (Pattern
available.
Always keep in(Pattern
mind 3)the need to leave enough space for amore
person to pass between units and wall
RXYQQ-T
3)
height
unrestricted
(If more units are to be installed than are catered for inWallthe
above
patterns50your
should take
account50
ofor the possibility
of short 100
circuits).
or morelayout(FRONT)
more 50 or more
50 or more
100 or more
or more
(FRONT)
Wall height
50 or more
500 or more
4. The
should
beunrestricted
installed to leave sufficient
spaceinatrows
the front for the on site For
refrigerant
piping
worklayout
to be carried out comfortably.
500 or more
50 or more
Forunits
single
For installation
centralized
group
100 or more
300 unit
or more installation
3

300 or more

10 or
more

10 or
more

(FRONT)
500 or more

20 or more

(FRONT)
500 or more

For single
(Patternunit
2) installation

(Pattern 2)
100 or more

50 or more

(FRONT)
500 or more

50 or
more 50 or more
10 or more

(Pattern 3)
300 or more

(FRONT)
200 or more

NOTES

10 or more 10 or more

Wall height
unrestricted

300 or more

(FRONT)

500 or3)
more
(Pattern

50 or more

100 or more

(FRONT)
50010orormore
more

20 or more

300 or more

400 or more50 or
(FRONT)
(FRONT)
200 or more more 50 or more
500 or more
(Pattern 3)
300 or more

(FRONT)
500 or more

20 or more

100
20 orormore
(FRONT)
500 or more more
50 or more

100 or more

400 or more

100 or more

(Pattern 3)
Wall height
unrestricted

20 or more

10 or more
10 or more

(Pattern 1)

(Pattern 2)

(Pattern 2)

100 or more

50 or more 50 or more

(FRONT)
500 or more

20 or more

50 or more

(FRONT)
500 or
or more
more
500

100 or more
(FRONT)

10 or more 10 or more

10 or more
10 or more

300 or more
20 or more

300 or more

10 or more 10 or more

(FRONT)
500 or more

10 or more

10 or more

50 or more

(FRONT)
500 or more

100 or more

Wall height unrestricted


300 or more

100 or
20more
or more
50 or
more 50 or more

(FRONT)
500 or more

100
or more2)
(Pattern

50 or more

20 or more

100 or
more
50 or more
50 or more

10 or more
10 or more

(FRONT)
500 or more

100 or more

(FRONT)
500 or more
10 or more
10 or more

300 or more

20 or more

50 or more
50 or more
20 or more

300 or more

100 or more

50 or more 50 or more

(FRONT)
500 or more

100 or more

50 or
more 50 or more

10 or more

(FRONT)

500 or more

900 or more

10 or more

600 or more

20 or more
(FRONT)

100 or more

50 or more

500 or more

(FRONT)
500 or more

100 or more

(FRONT)
(FRONT)
500 or more

10 or more

20 or more

100 or more

10 or more

500 or more

500 or more

(FRONT)

10 or more 10 or more

100 or
more

100 or
more
50 or more

20 or more
(FRONT)

300 or more

(FRONT)
600 or more

100 or more

10 or more

(FRONT)
500 or more

10 or more

20 or more
900 or more

50 or more

Wall height unrestricted

(Pattern 2)

100 or more

For centralized group layout

10 or more

300 or more
10 or
more

(FRONT)
600 or more

For installation in rows


(Pattern 1)

100 or more

300 or more

<Unit = mm>
20 or more

100 or more
(Pattern 1)

600 or more

300 or more

<Suction side>

10 or more

400 or more

100 or
more
50 or more
50 or more

(Pattern(FRONT)
1)
50 or more
100 or more
500 or more
300 or more

<Front>

(Pattern 1)
(FRONT)
200300
or or
more
more

RYYQ-T
(Pattern 1)
RYMQ-T
400 or more
(FRONT)
200 or more
RXYQ-T
300 or more
RXYQQ-T

50 or more
500 or more

<Unit = mm>

50 or more
50 or more

100 or more

3D07954250 or more

<Suction side>

<Front>

<Front>

1. Heights of walls in case of patterns 1 and 2:


Front: 1500mm
Suction side: 500mm

50 or more

<Suction side>

600 or more
1. Heights of walls in case of patterns 1 and 2:
100 or
more
Front: 1500mm
300 or more
50 or more
(FRONT)
50 or more
100 or more
400 or more
400 or more
(FRONT)
(FRONT)
500 or more
100 or more
50 or more
50 or more 50 or more
Suction side: 500mm
(FRONT)
100 or more
200 or more
200 or more
500 or more
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
<Unit = mm>
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more
broadly than the space as shown on this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the
space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits).
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.

NOTES

10 or more

109

Water cooled
VRV IV W-series
Ideal for high rise buildings,
using water as heat source

Unified
r
for hea ange
t pump
& heat
rec
and sta overy
n
& geoth dard
ermal
series

22

Air curtain
Biddle Air curtain for VRV (CYV)

Indoor units
VRV type indoor units OR
Residential type indoor units*
(such as Daikin Emura, ...)

Hot water
High temperature hydrobox*

Control systems
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit

Widest range of BS boxes for the fastest installation

VRV IV standards:
Variable refrigerant temperature
Customize your VRV for best seasonal efficiency & comfort
Full inverter compressors
Reluctance brushless DC compressor
Sine wave DC inverter
Manual demand function

For more information on these features refer to the VRV IV technologies tab
* on request. Contact your local sales representative for more information

110

Outdoor Unit Product Range

Geothermal operation
and advantages
Geothermal operation uses the more stable
temperature of the ground around the building,
eliminating the need for another heat source. It
reduces CO2 emissions and is an infinitely renewable
energy source.

Indoor installation makes


unit invisible from the
outside
Seamless integration in the surrounding architecture
as you cannot see the unit
Highly suited for sound sensitive areas as there is
no external operation sound
Superior efficiency, even in the most extreme
outside conditions, especially in geothermal
operation

Wide operation range


Standard water cooled outdoor units have a wide
operation range between 10C & 45C inlet water
temperature, both in heating and cooling. In
geothermal mode the operation range is extended
even more, down to -10C* in heating and 6C in
cooling mode.

-10C

45C

Heating
6C

45C

* Ethylene glycol should be added to the water when the water inlet
temperature is below 5C

Cooling

111

High energy efficiencies


results from 2-stage heat
recovery
Stage 1: Heat recovery between indoor
units in the same refrigerant circuit
Heat exhausted from indoor units in cooling mode
is transferred to units in areas requiring heating,
maximising energy efficiency and reducing electricity
costs.

Stage 2: Heat recovery between the outdoor


units via the water loop - also available on
heat pump units!
Second stage heat recovery is achieved within the
water loop between the water cooled outdoor units.

stage 2

stage 1

Heat recovery between indoor units

Heat recovery between outdoor units


(Heat recovery and heat pump)
Cooling tower (Closed type), boiler

All indoor units in


cooling mode

Heat rejected to loop

VRV-W

Indoor units mainly

Heat rejected to loop

cooling, partly heating

VRV-W

Full Heat Recovery

VRV-W

Indoor units
Heat absorbed from loop

mainly heating,
partly cooling

VRV-W

All indoor units


in heating mode

Heat absorbed from loop


* Above system configurations
are for illustration purposes only.
VRV-W

112

Ceiling height

Space saving - Stacked


configuration
The adoption of a new water heat exchanger
and optimization of the refrigerant control circuit
has resulted in the industrys most compact and
lightweight design. The unit weight of 149kg* and
height of 1,000mm makes installation easy. Stacked
configuration is also possible, contributing further to
space savings.

3,200mm
or higher

Floor level
* for 8HP unit
100-300mm

Outdoor Unit Product Range

Stacked configuration is possible.

Variable water flow control


The variable water flow control option reduces
energy use by the circulation pump by reducing
the water flow when possible and not using a fixed
water flow all the time.

Cooling tower (Closed type), boiler


Flow Valve
Input Signal
Variable water
Flow Control Valve

Inverter Pump

Standard water strainer


A standard water strainer reduces installation time.
The new filter also has less pressure drop at higher
water flows.

Connections
PHE connections
Mesh size
Design Pressure
Design Temp.
Glycol resistance
Pressure drop

Specifications
G1
G1
Max. particle diam. 0,5mm
2.0MPa
Max. 80oC
Up to 40% ethylene glycol
See below graph

Lower refrigerant levels


Water-cooled VRV systems typically have less
refrigerant per system making it ideal to comply
with the EN378 legislation limiting the amount of
refrigerant in hospitals and hotels.
The refrigerant levels remain limited
thanks to:
limited distance between outdoor and indoor unit
modularity: enabling small systems per floor instead
of one big system. Thanks to the water circuit heat
recovery is still possible in the entire building

113

Fully redesigned BS boxes


Maximum design flexibility
and installation speed
Quickly and flexibly design your system with a

unique range of single and multi BS boxes.


A wide variety of compact and lightweight multi

BS boxes greatly reduces installation time.


Free combination of single and multi BS boxes

Single port
Unique to the market
Compact and light to install
No drain piping needed
Ideal for remote rooms
Technical cooling function
Connect up to 250 class unit (28 kW)
Allows multi-tenant applications

BS1Q 10, 16, 25 A

Multi port: 4 6 8 10 12 16
Up to 55% smaller and 41% lighter than

previous range

BS 4 Q14 A

BS 6, 8 Q14 A

BS 10, 12 Q14 A

BS 16 Q14 A

Faster installation thanks to a reduced number

of brazing points and wiring


All indoor units connectable to one BS box
Fewer inspection ports needed
Up to 16 kW capacity available per port
Connect up to 250 class unit (28kW) by

combining 2 ports
No limit on unused ports, permitting

phased installation
Allows multi-tenant applications

Flexible piping design

Actual piping length between the VRV-W


and indoor units: 120m (Equivalent piping length: 140m)

Flexible water piping


Water cooled VRV uses water as its heat source, so
it is optimal for large buildings, including tall, multistorey buildings, because the system can tolerate
water pressure of up to 1.96 MPa.
Furthermore, if the currently installed heat sources
water temperature is between 10C and 45C, it may
be possible to use the existing water pipe work and
heat source. This alone makes it an ideal system
solution for building refubishment projects.

VRV-W

Level difference between indoor units: 15m


VRV-W

Level difference
between the VRV-W

Total piping length


Longest length actual (Equivalent)

50m if the VRV-W is above


40m if the VRV-W is below

120m (140m)

Longest length after first branch

40m (90m1)

Level difference between


indoor and outdoor units

50m (40m)

Level difference between indoor units

and indoor units:

300m

VRV-W

15m
Indoor installation

1 Contact your local dealer for more information and restrictions


2 In case outdoor unit is located below indoor units

Unlimited water piping length


Water piping
Refrigerant piping

114

Park Phi, Enschede - The Netherlands


BREEAM excellent office building

VRV-WIII geothermal system, Daikin Altherma HT, Sky Air, aircooled chiller with heat recovery, iManager,
iTouch Manager, i-Net

BREEAM EXCELLENT OFFICE


BUILDING - WATERCOOLED VRV
115

Outdoor Unit Product Range

For Gerard Schrder the choice for this system


was an easy one: As far as Im concerned, with the
VRV Heat Recovery system, Daikin has the Rolls
Royce in heat pump technology. If you want to
build a sustainable office building, there really is
no other alternative.

Application
examples
Dry cooler used for cooling, Chiller used for heating

Dry Cooler

Chiller

Expansion tank

Circulator Pump

Flow valve
or flow control valve

Stop valve

Strainer

Heat exchanger

Flow switch

Three way valve

Cooling mode
Heating mode
Refrigerant flow

116

Outdoor Unit Product Range

Dry cooler used for cooling, boiler used for heating

Dry Cooler

Boiler

Expansion tank

Circulator Pump

Flow valve
or flow control valve

Stop valve

Strainer

Heat exchanger

Flow switch

Three way valve

Cooling mode
Heating mode
Refrigerant flow

117

Geothermal operation

Hot water tank

Ground loop

Expansion tank

Circulator Pump

Heat exchanger

Buffer tank

Flow valve
or flow control valve

Liquid heater
Strainer

Cooling mode
Heating mode
Refrigerant flow

118

Flow switch
Stop valve
Three way valve

Ground loop
Examples
Open system

Conditions:
At 20 m depth water has a constant temperature

of 10C through the year


Surface water cools down to 5C during winter

Outdoor Unit Product Range

Uses water from a well or surface water (river, lake). The water is
pumped back to a second well or surface water

Can be the most economical type of


geothermal system

Constant ground water temperature has


positive impact on heat pump efficiency

O Risk to damage system components because


of water quality a secondary loop might be
required to protect the heat exchanger

O
Water should be tested for acidity, mineral
content, organic content and corosiveness:

O
In many areas open systems are prohibited
due to environmental concerns

Closed system
Uses water pipes that are buried in the ground and exchange
heat with the ground
Vertical system conditions
Typical depth: 30-140 m. Below 15 m, the
temperature of the ground is constant around
10C

Less surface space required


Very constant ground temperature
O Expensive due to drilling cost

For smaller applications also horizontal loops can be used


Horizontal loop system
Typical trench depth: 1 2 m. The ground

temperature varies, but always above 5C


(Exception: in cold areas)
Slinky loop: the plastic geothermal loop pipe
is coiled in overlapped circles and flattened
(Installed where there is not enough space for
closed horizontal)

Installation is easier and less expensive than


vertical closed loops.

O Mainly for small applications as the property


land should be large enough

O You cannot plant trees or build constructions


over the land containing the loop.

O Glycol is needed to prevent freezing of the water.

119

RWEYQ-T8

VRV IV water cooled series

Launc
12HP u h of
n
exten it and
t
the ra ion of
nge u
p to
36HP
2nd ha
lf 2016

Ideal for high rise buildings, using water as heat source


Unified range for standard and geothermal series simplifies stock.
Geothermal series reduce CO2 emmisions thanks to the use of
geothermal energy as a renewable energy source
No need for an external heating or cooling source when used in
geothermal mode
Covers all thermal needs of a building via a single point of contact:
accurate temperature control, ventilation, air handling units and
Biddle air cutains
Compact & lightweight design can be stacked for maximum space
saving
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors
2-stage heat recovery: first stage between indoor units, second
stage between outdoor units thanks to the storage of energy in
the water circuit
Available in heat pump and heat recovery version
Variable Water Flow control option increases flexibility and control
Contains all standard VRV features

RWEYQ8-10T8

VRV-W

Level difference between the VRV-W and indoor units:


50m if the VRV-W is above
40m if the VRV-W is below
Level difference between indoor units: 15m

VRV-W

Indoor installation
Unlimited water piping length
Outdoor unit
System

Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz

Power supply
Current - 50Hz

Water piping
Refrigerant piping

Standard operation
RWEYQ

Outdoor unit module 1


Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Cooling
Heating

Nom.
Nom.

EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
Nom.
connection
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Inlet water
Cooling
Min.~Max.
Heating
Min.~Max.
temperature
Refrigerant
Type
Charge

Piping connections

Geothermal operation

GWP
Liquid
Gas
Discharge gas
Water

OD
OD
OD
Inlet/Outlet

Total piping length


System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)

Actual

HP
kW
kW
kW
kW
kW
kW

mm
kg
dBA
dBA
CDB
CWB
kg
TCOeq

8T8
RWEYQ8T
8
22.4 (1) / 22.4 (2)
25.0 (3) / 25.0 (4)
4.42 (1) / 4.45 (2)
4.21 (3) / 4.30 (4)
5.07 (1) / 5.03 (2)
5.94 (3) / 5.81 (4)

10T8
RWEYQ10T
10
28.0 (1) / 27.5 (2)
31.5 (3) / 31.5 (4)
6.14 (1) / 6.35 (2)
6.00 (3) / 6.20 (4)
4.56 (1) / 4.33 (2)
5.25 (3) / 5.08 (4)

100
125
200
250
260
325
1,000x780x550
137

16T8
18T8
20T8
RWEYQ8T
RWEYQ10T
RWEYQ8T
RWEYQ10T
16
18
20
44.8 (1) / 44.8 (2) 50.4 (1) / 49.9 (2) 56.0 (1) / 55.0 (2)
50.0 (3) / 50.0 (4) 56.5 (3) / 56.5 (4) 63.0 (3)/ 63.0 (4)
8.8 (1) / 8.9 (2) 10.6 (1) / 10.8 (2) 12.3 (1) / 12.7 (2)
8.4 (3) / 8.6 (4) 10.2 (3) / 10.5 (4) 12.0 (3) / 12.4 (4)
5.07 (1) / 5.03 (2) 4.77 (1) / 4.62 (2) 4.56 (1) / 4.33 (2)
5.94 (3) / 5.81 (4) 5.53 (3) / 5.38 (4) 5.25 (3) / 5.08 (4)
36 (5)
200
225
250
400
450
500
520
585
650

24T8

26T8
RWEYQ8T
RWEYQ8T
RWEYQ8T
24
26
67.2 (1) / 67.2 (2) 72.8 (1) / 72.3 (2)
75.0 (3) / 75.0 (4) 81.5 (3) / 81.5 (4)
13.3 (1) / 13.4 (2) 15.0 (1) / 15.3 (2)
12.6 (3) / 12.9 (4) 14.4 (3) / 14.8 (4)
5.07 (1) / 5.03 (2) 4.86 (1) / 4.74 (2)
5.94 (3) / 5.81 (4) 5.65 (3) / 5.51 (4)
300
600
780
-

30T8
RWEYQ10T
RWEYQ10T
RWEYQ10T
28
30
78.4 (1) / 77.4 (2) 84.0 (1) / 82.5 (2)
88.0 (3) / 88.0 (4) 94.5 (3) / 94.5 (4)
16.7 (1) / 17.2 (2) 18.4 (1) / 19.1 (2)
16.2 (3) / 16.7 (4) 18.0 (3) / 18.6 (4)
4.69 (1) / 4.51 (2) 4.56 (1) / 4.33 (2)
5.43 (3) / 5.27 (4) 5.25 (3) / 5.08 (4)

325
650
845

28T8

350
700
910

375
750
975

50

51

53

54

55

10~45
-10 / 10.0~45

56

R-410A

3.5
7.3

4.2
8.8

mm
9.52
mm 19.10 (6)
22.2 (6)
mm 15.9 (7) / 19.10 (8) 19.1 (7) / 22.10 (8)
ISO 228 - G1 1/4 B External
Thread/ISO 228 - G1 1/4 B
External Thread
m
Hz/V
3N~/50/380-415
A
20

2,087.5
15.9

12.7

19.1
34.9 (6)
28.6 (7) / 34.90 (8)

28.6 (6)
22.2 (7) / 28.60 (8)
300
32

50

(1) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol) (2) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol. (3) Heating: Indoor temp. 20CDB; inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol). (4) Heating: Indoor temp. 20CDB;
inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol. (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio
restriction for the system (50% <= CR <= 130%) (6) In case of heat pump system, gas pipe is not used (7) In case of heat recovery system (8) In case of heat pump system | Contains fluorinated greenhouse gases

120

Detailed technical drawings


RWEYQ-T
Top view

Bottom view

Foundation bolt hole


8x 17

Item

After attaching accessoires pipe


Front view

Right side view

Rear view

Part name

Remark

Liquid pipe

See table 1

Suction pipe

See table 1

Gas pipe

See table 1

Water in connection

External pipe thread ISO 228 - G1 1/4 B

Water out connection

External pipe thread ISO 228 - G1 1/4 B

Drain outlet

External pipe thread ISO 228 - G1/2 B

Grounding terminal

M5

Power supply wiring intake

29

Cable inlet

29

Outdoor Unit Product Range

RWEYQ-T8

NOTES

1. The grounding terminal is located in the switch box.

Manufacturer label
Table 1
Model
Operation system
Liquid pipe
Suction pipe
Gas pipe (high/low pressure)
Connection method
Liquid pipe
Suction pipe
Gas pipe (high/low pressure)
In case of a heat pump, the suction pipe is not used.

RWEYQ8

Heat pump
9.5

Heat recovery
9.5
19.1
15.9

19.1
Flare connection

Heat pump
9.5

RWEYQ10

22.2

Heat recovery
9.5
22.2
19.1

Brazed connetion

3D085178B

RWEYQ-T

Service space
(rear)

For installation
in a row
Secure 300mm or more of service space
even not using for rear side take-out

Service space
(rear)

Service space
(rear)

Outside unit

Outside unit

500 or more

For single unit


installation

500 or more

RWEYQ-T8

390 or more

Outside unit
Water piping
installation space
Secure enough
space for removing
front plate

350 or less
20 or more
Space for
installation in
a row

Front view

20 or more
Space for
installation in
a row
350 or more

20 or more
Space for
installation in
a row

Service space
(front)

300 or more

Service space
(front)

900 or more

H: free
W: 179 mm

250 or less

Service space
(front)

20 or more
Space for
installation in
a row

900 or more

Secure 300mm or more of ventilation space


above the marked part of outside unit

20 or more
Space for
installation in
a row

: Required service space


: Ventilation space

100 or more
Water piping installation space

Right side view

3D048341F

121

VRV Indoor units


One of the widest ranges on the market,
it currently compromises no less than
26 different stylish and elegant models in 116
different variants. All designed to maximise
comfort, minimise operating noise and
simplify installation and servicing.

122

UNIQUE
UNIQUE

VRV indoor units

Stylish indoor units

Ceiling mounted cassette units


FXFQ-A130
FXZQ-A136
FXCQ-A139
FXKQ-MA142

BPMKS
Accessory to connect stylish indoor units
191

Concealed ceiling units


FXDQ-M9144
FXDQ-A146
FXSQ-A 152
FXMQ-P7 / FXMQ-MB
162
FXTQ-A 170

SLIMMEST
IN CLASS

UNIQUE
DESIGN UNIT

UNIQUE
RADIATING PANEL

Wall mounted
FTXG-LS/LW192
CTXS-K / FTXS-K
196
Floor standing
FVXG-K200
FVXS-F203
Flexi type unit
FLXS-B(9) 205

Wall mounted unit


FXAQ-P175

UNIQUE

SLIMMEST
IN CLASS

Ceiling suspended units


FXHQ-A178
FXUQ-A181
Floor standing units
FXNQ-A183
FXLQ-P188

123

Indoor Units

VRV Indoor units

Indoor units

Products overview
Type Model

Ceiling mounted cassette


Concealed ceiling
Wall mounted
Ceiling suspended

Capacity class (kW)


Product name

PG 15 20 25 32 40 50 63 71 80 100 125 140 200 250

360 air discharge for optimum efficiency and comfort


Auto cleaning function ensures high efficiency
Intelligent sensors save energy and maximize comfort
Flexibility to suit every room layout
Lowest installation height in the market!

FXFQ-A

133

Unique design that integrates fully flat into the ceiling


Perfect integration in standard architectural ceiling tiles
Blend of iconic design and engineering excellence
Intelligent sensors save energy and maximize comfort
Small capacity unit developed for small or well-insulated rooms
Flexibility to suit every room layout

FXZQ-A

136

2-way blow
ceiling
mounted
cassette

Thin, lightweight design installs easily in narrow ceiling spaces


Depth of all units is 620mm, ideal for narrow ceiling spaces
Flexibility to suit every room layout
Reduced energy consumption thanks to DC fan motor
The flaps close entirely when the unit is not operating
Optimum comfort with automatic air flow adjustment to the required load

FXCQ-A

139

Ceiling
mounted
corner
cassette

1-way blow unit for corner installation


Compact dimensions enable installation in narrow ceiling voids
Flexible installation thanks to different air discharge options

FXKQ-MA

142

Small
concealed
ceiling unit

Designed for hotel rooms


Compact dimensions enable installation in narrow ceiling voids
Discretely concealed in the ceiling: only the grilles are visible
Flexible installation as the air suction direction can be altered from rear to
bottom suction

FXDQ-M9

144

Slim
concealed
ceiling
unit

Slim design for flexible installation


Compact dimensions enable installation in narrow ceiling voids
Medium external static pressure up to 44Pa
Only grilles are visible
Small capacity unit developted for small of well-insulated rooms
Reduced energy consumption thanks to DC fan motor

FXDQ-A

146

Concealed Slimmest yet most powerfull medium static pressure unit on the market!
ceiling
Slimmest unit in class, only 245mm
Low operating sound level
unit
Medium external static pressure up to 150Pa facilitates using flexible ducts of
with
varying lengths
medium
Automatic air flow adjustment function measures the air volume and static
ESP
pressure and adjusts it towards the nominal air flow, guaranteeing comfort

FXSQ-A

152

FXMQ-P7

162

FXMQ-MB

162

FXTQ-A

170

For rooms with no false ceilings nor free floor space


Flat, stylish front panel is more easy to clean
Small capacity unit developted for small of well-insulated rooms
Reduced energy consumption thanks to DC fan motor
The air is comfortably spread up- and downwards thanks to 5 different
discharge angles

FXAQ-P

175

For wide rooms with no false ceilings nor free floor space
Ideal for comfortable air flow in wide rooms thanks to Coanda effect
Rooms with ceilings up to 3.8m can be heated or cooled very easily!
Can easily be installed in both new and refurbishment projects
Can even be mounted in corners or narrow spaces without any problem
Reduced energy consumption thanks to DC fan motor

FXHQ-A

178

FXUQ-A

181

For perimeter zone air conditioning


Can be installed in front of glass walls or free standing as both the front and
the back are finished
Ideal for installation beneath a window
Requires very little installation space
Wall mounted installation facilitates cleaning beneath the unit

FXLQ-P

183

Ideal for installation in offices, hotels and residential applications


Discretely concealed in the wall, leaving only the suction and discharge grilles
visible
Can even be installed underneath a window
Requires very little installation space as the depth is only 200mm
High ESP allows flexible installation

FXNQ-A

188

UNIQUE

Round flow
cassette

Floor standing

UNIQUE

Fully flat
cassette

Concealed ESP up to 200, ideal for large sized spaces


Optimum comfort guaranteed no matter the length of ductwork or type of
ceiling
grilles, thanks to automatic air flow adjustment
unit
Reduced energy consumption thanks to DC fan motor
with high
Flexible installation as the air suction direction can be altered from rear to
ESP
bottom suction
Concealed
ceiling
ESP up to 270, ideal for extra large sized spaces
unit
Only grilles are visible
with high Large capacity unit: up to 31.5 kW heating capacity
ESP
For the highest energy efficiency
Concealed Automatic air flow adjustment function guarantees comfort
ceiling unit Easy installation in narrow ceilings (245mm height)
with high High external static pressure up to 270Pa facilitates using flexible ducts of
varying lengths
efficiency
Only the suction and discharge grilles are visible
Wall
mounted
unit

Ceiling
suspended
unit

Unique Daikin unit for high rooms with no false ceilings nor free floor space
Rooms with ceilings up to 3.5m can be heated up or cooled down very easily!
4-way blow Can easily be installed in both new and refurbishment projects
Can be partly recessed in the ceiling if a small ceiling void is available (88mm)
ceiling
suspended Flexibility to suit every room layout
Reduced energy consumption thanks to DC fan motor
unit

Concealed
floor
standing
unit

UNIQUE

Floor
standing
unit

Cooling capacity (kW)1

1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0

Heating capacity (kW)2

1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5

124

(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m
(2) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m

Stylish indoor units

overview
Depending on the application, Split and Sky Air
indoor units can be connected to our VRV IV
and VRV IV S-series outdoor units. Refer to the
outdoor unit portfolio for combination restrictions.

Fully flat
cassette

FFQ-C

Small concealed ceiling unit

FDBQ-B

Slim concealed ceiling unit

FDXS-F(9)

Concealed ceiling unit


with inverter-driven fan

FBQ-D

Daikin Emura
Wall mounted unit

FTXG-LW/LS

192

Wall mounted unit

CTXS-K
FTXS-K

196

Wall mounted unit

FTXS-G

196

Ceiling suspended unit

FHQ-C

Nexura floor standing unit

FVXG-K

200

Floor standing unit

FVXS-F

203

Flexi type unit

FLXS-B(9)

205

Model

Product name

PG

15

20

25

Round flow cassette


(incl. auto-cleaning
function1)

Ceiling
mounted
cassette

Concealed
ceiling

Wall
mounted

Ceiling
suspended

Floor
standing

42

50

60

71

Decoration panel BYCQ140DG or BYCQ140DGF + BRC1E52A/B needed

To connect stylish indoor units a BPMKS unit is needed

2
3

35

For RXYS(C)Q units a mix of RA indoor units and VRV indoor units is not allowed

VRV IV W-series on special order. Consult your local sales representative for more information

125

Indoor Units

RWEYQ-T84

Type

RXYQ-T(9)

FCQG-F

Capacity class (kW)

RYYQ-T

RXYSCQ-TV1 /
RXYSQ-TV1 /
RXYSQ-TY13

Connectable outdoor unit

VRV Indoor

CONCEALED CEILING UNIT WITH HIGH ESP

ROUND FLOW CASSETTE

SMALL CONCEALED CEILING UNIT

126

Indoor Units

VRV Indoor

FULLY FLAT CASSETTE

HOT WATER PRODUCTION

STYLISH INDOOR UNITS

127

Indoor units

We care

Benefits overview

Inverter technology

In combination with inverter controlled outdoor units

Home leave operation

During absence, indoor comfort levels can be maintained

Fan only

The air conditioner can be used as fan, blowing air without cooling or heating

Auto cleaning filter


Floor and presence sensor

Auto cooling-heating changeover

Automatically selects cooling or heating mode to achieve the set temperature

Air treatment

Whisper quiet

When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and the fan to
low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired
Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the
neightbourhood

Air filter

Removes airborne dust particles to ensure a steady supply of clean air

Humidity
control

Comfort

Draught prevention

The filter automatically cleans itself once a day. Simplicity of upkeep means optimum energy efficiency and maximum
comfort without the need for expensive or time-consuming maintenance
The presence sensor directs the air away from any person detected in the room. The floor sensor detects the average
floor temperature and ensures an even temperature distribution between ceiling and floor

Dry programme

Allows humidity levels to be reduced without variations in room temperature

Other funtcions

Remote control & timer

Air flow

Ceiling soiling prevention

128

Vertical auto swing

The air discharge of the indoor unit is specially designed to prevent air being blown against the ceiling to prevent
ceiling stains
Possibility to select automatic vertical moving of the air discharge louvre, for uniform air flow and temperature
distribution

Fan speed steps

Multiple fan speeds to select,to optimize comfort levels

Individual flap control

Individual flap control via the wired remote controller makes it simple to fix the position of each flap individually,
to suit any new room configuration. Optional closure kits are available as well

Weekly timer

Timer can be set to start and stop operation anytime on a daily or weekly basis

Infrared remote control

Infrared remote control with LCD to remotely control your indoor unit

Wired remote control

Wired remote control to remotely control your indoor unit

Centralised control

Centralised control to to control several indoor units from one single point

Auto-restart

The unit restarts automatically at the original settings after power failure

Self-diagnosis

Simplifies maintenance by indicating system faults or operating anomalies

Drain pump kit

Facilitates condensation draining from the indoor unit

Multi tenant

The indoor units main power supply can be turned off when leaving the building or for servicing purposes

Ceiling mounted cassette units

FXFQ-A

FXZQ-A

FXCQ-A

G1
F8
(optional)

G1

Wall
mounted
unit

Concealed ceiling units

FXKQ-MA FXDQ-M9

Ceiling suspended
units

Floor standing units

FXDQ-A

FXSQ-A

FXMQ-P7

FXMQ-MB

FXTQ-A

FXAQ-P

FXHQ-A

FXUQ-A

FXNQ-A

FXLQ-P

Indoor Units

G1

G1
F8
(optional)

G1
F8
(optional)

G1

G1

G1

G1

3 (50~63)
2 (80~100)

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Optional

Optional

Standard

( )

( )

( )

( )

Standard (50~63)
Optional
Optional (80~100)

( )

129

ARGUE CARDS

FCQG-F/FCQHG-F/FXFQ-A

Round flow cassette


Why choose a round flow cassette?
360 air discharge for optimum efficiency and comfort in shops, offices and restaurants.
Unique auto-cleaning panel.
Unique functions which help save costs
Daikin was the first company to launch a cassette
using the round flow principle with sensors* and
a unique auto-cleaning panel*.

... More energy efficient than any other


The auto-cleaning panel* means:
Running costs are reduced
by 50% compared with standard solutions thanks
to automatic daily filter cleaning.
Less time is required to maintain the filter:
dust can be removed easily with a vacuum cleaner without opening the unit.
For fine dust applications (i.e. clothing shops)
a finer mesh filter (BYCQ140DGF) ensures consistent, optimum performance.
Round flow cassette - overview decoration panels
BYCQ140DG

BYCQ140DW

BYCQ140D

Auto-cleaning auto-cleaning
panel
panel with
fine mesh
filter

BYCQ140DGF

White panel

Standard
panel

White with
grey louvers

Full white

White with
grey louvers

White with
grey louvers

Thanks to presence and floor sensors*, the unit


changes its setpoint or switches off compleately,
if there are no people in the room,
resulting in energy savings of up to 27%.

AUTO CLEANING FILTER

Dust can be removed easily


with a vacuum cleaner
without opening the unit.

References
Wolverhampton, UK
Running costs were reduced
by up to 50% compared
with standard solutions
thanks to daily filter cleaning.

Energy consumption
(kWh)
9000
8000
7000
6000

Standard round
flow cassette

Up to 50% savings
thanks to
auto-cleaning panel

5000

Auto cleaning cassette

4000
3000
2000
1000
0

July
Aug.
Sept.
Oct.
Nov.
Cumulative energy comparison over 12 months

130

Dec.

Jan.

Feb.

March

April

May

June

July

And improved comfort

Benefits for the installer

360 air flow discharge pattern.


The presence sensor* directs
the air away from anyone
it detects in the room.
The floor sensor*
detects the average floor
temperature and ensures an even
temperature distribution between
the ceiling and the floor.
presence
sensor

Indoor Units

Product with unique functions in this market.


Less time needed for onsite maintenance.
Use the controller to individually open or close any
of the four flaps to easily adapt to a changing room
layout.
Easy set-up of the sensor option to improve comfort
and save energy.

Benefits for the consultant

floor sensor

* available as an option

Flexible installation
Flaps can be individually controlled or closed
using the wired remote control, to suit room
configuration.
Optional closure kits are also available.

Product with unique functions in this market.


Designed for use in all types and sizes of commercial
offices and retail environments.
Ideal product for improving BREEAM score/EPBD in
combination with Sky Air Seasonal Smart or VRV IV
heat pump units.

Benefits for the end user

Designed for use in all types and sizes of commercial


offices and retail environments.
Perfect environment conditions: no more draughts
or cold feet.
Save up to 50% on running costs with the autocleaning panel, which also facilitates maintenance.
Your customers can save up to 27% on their energy
bills thanks to the sensor option.
Flexible use of space thanks to individual flap
control.

Marketing tools
Visit the website: www.daikineurope.com/minisite/
round-flow-cassette/

www.youtube.com/DaikinEurope

131

AUTO CLEANING PANEL WITH FINE


MESH FILTER, IDEAL FOR CLOTHING
SHOPS

132

FXFQ-A

Round flow cassette


360 air discharge for optimum efficiency and comfort
360 air discharge ensures uniform air flow and temperature
distribution
Daily automatic filter cleaning results in higher efficiency &
comfort and lower maintenance costs. Dust can easily be removed
with a vacuum cleaner without opening the unit
Two optional intelligent sensors improve energy efficiency and comfort.
Individual flap control: flexibility to suit every room layout without
changing the location of the unit.
Modern style decoration panel is available in 3 dierent variations:
white (RAL9010) with grey louvers, full white (RAL9010) or auto
cleaning panel
Reduced energy consumption thanks to specially developed small
tube heat exchanger, DC fan motor and drain pump
Optional fresh air intake
Fresh air intake opening in casing

FXFQ20-63A

BRC1E52A/B

BRC7FA532F

Optional fresh air intake kit

* Brings in up to 7% of fresh air into the room

* Allows larger quantities of fresh air to be


brought in up to 10%
* Distributes fresh air so it is most effectively
pre-cooled / pre-heated

Indoor Units

Lowest installation height in the market: 214mm for class 20-63


Standard drain pump with 675mm lift increases flexibility and
installation speed

675mm

Branch duct discharge allows to optimize air distribution in

irregular shaped rooms or to supply air to small adjacent rooms

/////////////////////////

///////////////////
Main unit

Branch discharge

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Decoration panel

Main discharge

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 2
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 3
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 4
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

FXFQ
kW
kW
kW
kW
mm
mm
mm
kg

20A
2.2
2.5

25A
2.8
3.2

32A
3.6
4.0
0.038
0.038

19

mm
kg

mm
mm
Hz/V
A

63A
7.1
8.0
0.061
0.061

80A
9.0
10.0
0.092
0.092

100A
11.2
12.5
0.115
0.115
246

125A
14.0
16.0
0.186
0.186
288

840
840

mm
kg

dBA
dBA
dBA

50A
5.6
6.3
0.053
0.053

204

mm
kg

mm
kg
m/min
m/min

40A
4.5
5.0

12.5/10.6/8.8
12.5/10.6/8.8
49/31/29/28
31/29/28

20

21
24
26
Galvanised steel plate
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter
Pure White (RAL 9010)
130x950x950
10.3
BYCQ140D7GW1 - auto cleaning panel
Pure White (RAL 9010)
130x950x950
10.3
BYCQ140D7W1W - full white
Pure White (RAL 9010)
50x950x950
5.4
BYCQ140D7W1 - white with grey louvers
Pure white (RAL 9010)
50x950x950
5.4
13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9
13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9
Resin net with mold resistance
51/53/55/60/61/33/31/29
35/33/30
38/34/30
43/37/30
45/41/36
33/31/29
35/33/30
38/34/30
43/37/30
45/41/36
R-410A
2,087.5
6.35
9.52
12.7
15.9
VP25 (O.D. 32 / I.D. 25)
1~/50/60/220-240/220
16
BRC7FA532F
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt. |
BYCQ140D7W1: pure white standard panel with grey louvers; BYCQ140D7W1W: pure white standard panel with white louvers; BYCQ140D7GFW1: pure white auto cleaning panel.

133

Detailed technical drawings


FXFQ20-63A WITH AUTO-CLEANING PANEL

FXFQ80-125A WITH AUTO-CLEANING PANEL

134

Detailed technical drawings

Indoor Units

FXFQ20-63A WITH STANDARD PANEL

FXFQ80-125A WITH STANDARD PANEL

135

ARGUE CARDS

FFQ-C /FXZQ-A

Fully Flat Cassette


Design & Genius in one
Why choose fully flat cassette
Unique design in the market that integrates fully flat into the ceiling
Advanced technology and top efficiency combined
Most quiet cassette available on the market

Marketing tools
Visit the website: www.daikineurope.com/fullyflat

Unique design

Benefits for the installer


Unique product in the market!
Most quiet unit (25dBA)
The user-friendly remote control, available
in several languages, enables the easy set-up
of sensor option and control of the individual
flap position
Meeting European design taste.

Benefits for the consultant


Unique product in the market!
Blends seamlessly in any modern office
interior design
Ideal product to improve BREEAM score/EPBD
in combination with Sky Air Seasonal Smart
(FFQ-C) or VRV IV heat pump units (FXZQ-A).

Benefits for the end user


Engineering excellence and unique design
in one
Most quiet unit (25dBA)
Perfect working conditions:
no more cold draughts
Save up to 27% on your energy bill
thanks to the optional sensors
Flexible usage of space and suits any room
configuration thanks to individual
flap control
User-friendly remote control, available
in several languages.

Designed by a European design office to fully meet


the European taste.
Fully flat into the ceiling, leaving only 8mm.
Fully integrated in the one ceiling tile, enabling
lights, speakers and sprinklers to be installed in
adjoining ceiling tiles.
Decoration panel available in 2 colours
(white and white-silver).

Differentiating in technology
Optional presence sensor
When the room is empty, it can adjust the set
temperature or switch off the unit saving energy.
When people are detected, the direction of
the airflow is adapted to avoid cold draughts being
directed towards occupants.
Optional floor sensor
Detects the temperature difference and
re-directs the airflow to ensure even
temperature distribution.

Top efficiency
When the room is empty, the sensor option can
adjust the set temperature or switch off the unit
saving up to 27% energy.
Individual flap control: easily control one or more
flaps via the wired remote controller (BRC1E52)
when rearranging the room. When fully closing or
blocking the flaps, the option Sealing member of
air discharge outlet is needed.
* for FFQ25,35C in combination with RXS25,35L3

Most quiet unit in the market


Most silent cassette in the market (25dBA),
important for office applications.

136

www.youtube.com/
DaikinEurope

FXZQ-A

Fully flat cassette


Unique design in the market that integrates fully flat into
the ceiling
Fully flat integration in standard architectural ceiling tiles, leaving
only 8mm
Remarkable blend of iconic design and engineering excellence
with an elegant finish in white or a combination of silver and
white
Two optional intelligent sensors improve energy efficiency and
comfort.
15 class unit especially developed for small or well-insulated
rooms, such as hotel bedrooms, small offices, etc.
Individual flap control: flexibility to suit every room layout without
changing the location of the unit!

FXZQ-A

BRC1E52A/B

BRC7F530W/S

Branch duct discharge allows to optimize air distribution in


irregular shaped rooms or to supply air to small adjacent rooms

/////////////////////////

Indoor Units

Reduced energy consumption thanks to specially developed small


tube heat exchanger, DC fan motor and drain pump
///////////////////
Main unit
Branch discharge

Main discharge

Standard drain pump with 630mm lift increases flexibility and


installation speed
500 mm

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

Weight
Casing
Decoration panel

Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 2
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 3
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Dimensions do not include control box (2) Contains fluorinated greenhouse gases

FXZQ
kW
kW
kW
kW
mm
mm
mm
kg

mm
kg

mm
kg

mm
kg
m/min
m/min
dBA
dBA
dBA

mm
mm
Hz/V
A

15A
1.7
1.9

20A
2.2
2.5
0.043
0.036

25A
2.8
3.2

32A
3.6
4.0
0.045
0.038

40A
4.5
5.0
0.059
0.053

50A
5.6
6.3
0.092
0.086

260
575
575
15.5

16.5
Galvanised steel plate
BYFQ60CW
White (N9.5)
46x620x620
2.8
BYFQ60CS
White (N9.5) + Silver
46x620x620
2.8
BYFQ60B3W1
White (RAL9010)
55x700x700
2.7
8.5/7/6.5
8.7/7.5/6.5
9/8/6.5
10/8.5/7
11.5/9.5/8
8.5/7/6.5
8.7/7.5/6.5
9/8/6.5
10/8.5/7
11.5/9.5/8
Resin net with mold resistance
49/50/51/54/31.5/28/25.5
32/29.5/25.5
33/30/25.5
33.5/30/26
37/32/28
31.5/28/25.5
32/29.5/25.5
33/30/25.5
33.5/30/26
37/32/28
R-410A
2,087.5
6.35
12.7
VP20 (I.D. 20/O.D. 26)
1~/50/220-240
16
BRC7F530W (white panel) / BRC7F530S (grey panel) / BRC7EB530 (standard panel)
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

18.5

14.5/12.5/10
14.5/12.5/10
60/43/40/33
43/40/33

137

Detailed technical drawings


FXZQ-A NEW PANEL

FXZQ-A OLD PANEL

138

FXCQ-A

2-way blow ceiling mounted


cassette
Thin, lightweight design installs easily in narrow corridors
Depth of all units is 620mm, ideal for narrow spaces
Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
Reduced energy consumption thanks to specially developed small
tube heat exchanger, DC fan motor and drain pump
Stylish unit blends easily with any interior. The flaps close entirely
when the unit is not operating and there are no air intake grilles
visible
Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation device is required

FXCQ20-40A

Fresh air intake opening in casing

BRC1E52A/B

BRC7C52

* Brings in up to 10% of fresh air into the room

/////////////////////////

Indoor Units

Optimum comfort guaranteed with automatic air flow adjustment


to the required load
Maintenance operations can be performed by removing the front
panel
Branch duct discharge allows to optimize air distribution in
irregular shaped rooms or to supply air to small adjacent rooms

///////////////////
Main unit

Branch discharge

Main discharge

Standard drain pump with 580mm lift increases flexibility and


installation speed
500 mm

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Decoration panel

Fan-Air flow rate - 50Hz

Nom.
Nom.
Cooling
Heating
Unit

Unit
Material
Model
Colour
Dimensions
Weight
Cooling

Nom.
Nom.
Height
Width
Depth

HeightxWidthxDepth
High/Nom./Low

Air filter
Type
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Contains fluorinated greenhouse gases

FXCQ
kW
kW
kW
kW
mm
mm
mm
kg

20A
2.2
2.5
0.031
0.028

0.039
0.035

40A
4.5
5.0
0.041
0.037

50A
5.6
6.3
0.059
0.056

63A
7.1
8.0
0.063
0.060

80A
9.0
10.0
0.090
0.086

125A
14.0
16.0
0.149
0.146

305
990

1,445

620
19

10.5/9/7.5

dBA
dBA

32.0/30.0/28.0
32.0/30.0/28.0

Hz/V
A

32A
3.6
4.0

775

mm
kg
m/min

mm
mm

25A
2.8
3.2

22
25
33
38
Galvanised steel plate
BYBCQ40HW1
BYBCQ63HW1
BYBCQ125HW1
Fresh white (6.5Y 9.5/0.5)
55x1,070x700
55x1,285x700
55x1,740x700
10
11
13
11.5/9.5/8
12/10.5/8.5
15/13/10.5
16/14/11.5 26/22.5/18.5 32/27.5/22.5
Resin net with mold resistance
34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0
34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0
R-410A
2,087.5
6.35
9.52
12.7
15.9
VP25 (O.D. 32 / I.D. 25)
1~/50/220-240
16
BRC7C52
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

139

Detailed technical drawings


FXCQ20-40A

FXCQ50A

140

Detailed technical drawings

Indoor Units

FXCQ63A

FXCQ80-125A

141

FXKQ-MA

Ceiling mounted corner


cassette
1-way blow unit for corner installation
Compact dimensions, can easily be mounted in a narrow ceiling
void (only 220mm ceiling space required, 195 with panel spacer,
available as accessory)
Optimum air flow conditions are created by either downward
air discharge or frontal air discharge (via optional grille) or a
combination of both

FXKQ-MA

Downward discharge

Frontal discharge

BRC1E52A/B

BRC4C61

Closed decoration panel


Combination

Maintenance operations can be performed by removing the front


panel
Standard drain pump with 330mm lift increases flexibility and
installation speed
500 mm

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Decoration panel

Fan-Air flow rate - 50Hz


Air filter
Sound pressure level
Refrigerant
Piping connections

Power supply
Current - 50Hz
Control systems

Nom.
Nom.
Cooling
Heating
Unit

Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Cooling
High/Low
Type
Cooling
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Contains fluorinated greenhouse gases

142

Nom.
Nom.
Height
Width
Depth

FXKQ
kW
kW
kW
kW
mm
mm
mm
kg

mm
kg
m/min
dBA

mm
mm
Hz/V
A

25MA
2.8
3.2

32MA
3.6
4.0

40MA
4.5
5.0
0.076
0.056

0.066
0.046

63MA
7.10
8.00
0.105
0.085

215
1,110

1,310
710

31
Galvanised steel plate
BYK45FJW1
White
70x1,240x800
8.5
11/9

13/10
Resin net with mold resistance
38.0/33.0
40.0/34.0
R-410A
2,087.5
6.35
12.7
VP25 (O.D. 32 / I.D. 25)
1~/50/60/220-240/220
15
BRC4C61
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

34
BYK71FJW1
70x1,440x800
9.5
18/15
42.0/37.0

9.52
15.9

Detailed technical drawings


FXKQ25, 32, 40MA
FXKQ25,32,40MA

Required installation space


1,500 mm or
more

200 mm or more
200 mm or more

760 (Ceiling opening)


350 (Suspension position)

20 mm or more

Nr.
1
2
3
4

1,150 (Suspension position)


1,200 (Ceiling opening)

5
6
7

Front discharge duct position

Suspension bolt

9
1,000 or more
Required installation space

10

Description

6.4 Flare connection


12.7 Flare connection
VP25 (O.D. 32)
Inside switch box (M4)

NOTES

Location of units name plate:


For main body: Bottom part of fan housing inside of air suction grille.
For decoration panel: Service lid face inside of air suction grille.

When installing an optional accessory, refer to the installation drawings.

Indoor Units

4-M4 hole

Name

Liquid pipe connection


Gas pipe connection
Drain pipe connection
Wire intake
Interunit wiring connection
Grounding terminal
Discharge
Air suction grille
Long life filter
Suspension bolt

3D038840

FXKQ63MA
FXKQ63MA

Required installation space


200 mm or more

760 (Ceiling opening)


350 (Suspension position)

1,500 mm or
more
20 mm or more

Nr.
1
2
3
4
5
1,350 (Suspension position)
1,400 (Ceiling opening)

6
7
8

Front discharge duct position

Suspension bolt

1,000 or more
(Required
installation space)

6-M4 hole

10

200 mm or more

Name

Liquid pipe connection


Gas pipe connection
Drain pipe connection
Wire intake
Interunit wiring connection
Grounding terminal
Discharge
Air suction grille
Long life filter
Suspension bolt

Description

9.5 Flare connection


15.9 Flare connection
VP25 (O.D. 32)
Inside switch box (M4)

NOTES

Location of units name plate:


For main body: Bottom part of fan housing inside of air suction grille.
For decoration panel: Service lid face inside of air suction grille.

When installing an optional accessory, refer to the installation drawings.


3D038841

143

FXDQ-M9

Small concealed ceiling unit


Designed for hotel applications
Compact unit (230mm high & 502mm deep), can easily be
mounted in narrow ceiling voids
Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
Flexible installation, as the air suction direction can be altered
from rear to bottom suction

For easy mounting, the drain pan can be located to the left or
right of the unit

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

Required ceiling void >


Weight
Unit
Casing
Colour
Material
Fan-Air flow rate Cooling
High/Low
50Hz
Heating
High/Low
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level Cooling
High/Low
Heating
High/Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Contains fluorinated greenhouse gases

144

FXDQ-M9

BRC1E52A/B

FXDQ
kW
kW
kW
kW
mm
mm
mm
mm
kg

20M9
2.2
2.5

m/min
m/min

6.7/5.2
6.7/5.2

dBA
dBA
dBA

mm
mm
Hz/V
A

BRC4C62

25M9
2.8
3.2
0.050
0.050
230
652
502
250
17
Unpainted
Galvanised steel
7.4/5.8
7.4/5.8

Resin net with mold resistance


50
37/32
37/32
R-410A
2,087.5
6.35
12.7
I.D. 21.6, O.D. 27.2
1~/50/230
16
BRC4C62
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

Detailed technical drawings


FXDQ-M9
FXDQ-M9
(Suspension position)

Part name
Liquid pipe connection ( 6.35)
Gas pipe connection ( 12.7)
Drain hole (o.d. 27.2 - i.d. 21.6)
Transmission wiring port
Power supply wiring port
Service space
Switch box
Nameplate

250 or more

(Suspension position)

Nr
1
2
3
4
5
6
7
8

Indoor Units

300 or more

3TW25774-1

145

FXDQ-A

Slim concealed ceiling unit


Slim design for flexible installation
Compact dimensions, can easily be mounted in a ceiling void of
only 240mm

FXDQ15-32A

Medium external static pressure up to 44Pa facilitates unit use


with flexible ducts of varying lengths
Discretely concealed in the ceiling: only the suction and discharge
grilles are visible
15 class unit especially developed for small or well-insulated
rooms, such as hotel bedrooms, small offices, etc.
Reduced energy consumption thanks to specially developed DC
fan motor
Flexible installation, as the air suction direction can be altered
from rear to bottom suction

BRC1E52A/B BRC4C65

Standard drain pump with 750mm lift increases flexibility and


installation speed

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

Required ceiling void >


Weight
Unit
Casing
Colour
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Fan-External static
High/Nom.
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Contains fluorinated greenhouse gases

146

FXDQ
kW
kW
kW
kW
mm
mm
mm
mm
kg

15A
1.7
1.9

20A
2.2
2.5

25A
2.8
3.2

32A
3.6
4.0

0.071
0.068

40A
4.5
5.0
0.078
0.075

50A
5.6
6.3
0.099
0.096

63A
7.1
8.0
0.110
0.107

200
750

950

1,150

26

29

620
240
22
Galvanised steel / Non painted

m/min

7.5/7.0/6.4

Pa

dBA
dBA

mm
mm
Hz/V
A

8.0/7.2/6.4
30/10

50
32/31/27

10.5/9.5/8.5

12.5/11.0/10.0

16.5/14.5/13.0

44/15

Removable / washable / mildew proof


51
52
53
33/31/27
34/32/28
35/33/29
R-410A
2,087.5
9.52
12.7
VP20 (I.D. 20/O.D. 26)
1~/50/60/220-240/220
16
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

54
36/34/30

15.9

Detailed technical drawings

Indoor Units

FXDQ15-32A

FXDQ40-50A

147

Detailed technical drawings


FXDQ63A

FXDQ15A

3D081424A

148

Detailed technical drawings

Indoor Units

FXDQ20-25A

FXQQ32A

149

Detailed technical drawings


FXDQ40A

FXDQ50A

150

Detailed technical drawings

Indoor Units

FXDQ60A

151

FXSQ-A

Concealed ceiling unit


with medium ESP
Slimmest yet most powerful medium static pressure unit
on the market
Slimmest unit in class, only 245mm (300mm built-in height) and
therefore narrow ceiling voids are no longer a challenge
FXSQ-A

Whisper quiet operation: down to 25dBA sound pressure level


Medium external static pressure up to 150Pa facilitates using
flexible ducts of varying lengths
Possibility to change ESP via wired remote control allows
optimisation of the supply air volume
Discretely concealed in the wall: only the suction and discharge
grilles are visible
15 class unit especially developed for small or well-insulated
rooms, such as hotel bedrooms, small offices, etc.
Reduced energy consumption thanks to specially developed DC
fan motor and drain pump
Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation is required
Fresh air intake opening in casing

Optional fresh air intake kit

* Brings in up to 10% of fresh air into the room

* Allows larger quantities of fresh air to be bought in

Flexible installation: air suction direction can be altered from rear


to bottom suction and choice between free use or connection to
optional suction grilles
//////////////////////////////////////////

For free use into a false


ceiling

//////////////////////////////////////////

For connecting onto a


suction canvas
(not supplied by Daikin)

//////////////////////////////////////////

For direct connection


to Daikin panel (via
EKBYBSD kit)

Standard built-in drain pump with 625mm lift increases flexibility


and installation speed

152

BRC1E52A/B BRC4C65

FXSQ-A

Automatic Airflow
Adjustment function

External static pr essure (Pa)

Automatically selects the most appropriate fan curve to achieve the


units nominal air flow within 10%

Fan characteristic
curves

Why?
After installation the real ducting will frequently differ from the
initially calculated air flow resistance the real air flow may be
much lower or higher than nominal , leading to a lack of capacity or
uncomfortable air temperature
Duct resistance
curves

Automatic Airflow Adjustment function will adapt the units fan


speed to any ducting automatically(10 or more fan curves are
available on every model), making installation much faster

matic adjustment )

/min)
Indoor Units

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Fan-Air flow rate 50Hz

Nom.
Nom.
Cooling
Heating
Unit

Unit
Colour
Material
Cooling
Heating
High/Nom.

Nom.
Nom.
Height
Width
Depth

High/Nom./Low
High/Nom./Low

Fan-External static
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

FXSQ
kW
kW
kW
kW
mm
mm
mm
kg

15A
1.7
1.9

m/min 8.7/7.5/6.5
m/min 8.7/7.5/6.5
Pa

dBA
dBA 29.5/28/25
dBA 31.5/29/26

mm
mm
Hz/V
A

20A
2.2
2.5
0.041
0.038

25A
2.8
3.2

32A
3.6
4.0
0.045
0.042

40A
4.5
5.0
0.092
0.089

50A
5.6
6.3

63A
7.1
8.0
0.095
0.092

80A
9.0
10.0
0.121
0.118

100A
11.2
12.5
0.157
0.154

125A
14.0
16.0
0.214
0.211

140A
16.0
18.0
0.243
0.240

245
550
23.5

9/7.5/6.5
9/7.5/6.5

700

1,000
1,400
1,550
800
24
28.5
29
35.5
36.5
46
47
51
Not painted (galvanised)
Galvanised steel plate
9.5/8/7.0 15/12.5/11 15.2/12.5/11 21.0/18/15 23/19.5/16 32/27/23 36/31.5/26 39/34/28
9.5/8/7 15/12.5/11 15.2/12.5/11 21/18/15 23/19.5/16.0 32/27/23 36/31.5/26 39/34/28
150/30

54
30/28/25
32/29/26

150/40

150/50

Resin net with mold resistance


55
60
59
61
64
31/29/26
35/32/29
33/30/27 35/32/29 36/34/31 39/36/33 41.5/38/34
33/30/27
37/34/29
35/32/28 37/34/30 37/34/31 40/37/33 42/38.5/34
R-410A
2,087.5
6.35
9.52
12.7
15.9
VP20 (I.D. 20/O.D. 26)
1~/50/60/220-240/220
16
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

153

FXSQ15-32A
Detailed technical drawings

FXSQ15-32A
69
KJ

800
301

KC

KH

KE

110

245
178

38

100
65

50

140

25

40

300 or more
Service space

550
342

210

Suspension bolt

2x65= 130

( Knockout hole.

Fresh air intake position

109

O100

170

ARROW VIEW A

365

32

KF

179.2

50

500 or more
Service space

KD
504

145

150

145

95

588 Suspension position


4x65= 260

KA

210

2x140= 280

126 P.C.D.
4-M4 (CLASS 2)

50

KK

Suspension position

KB
ARROW VIEW A

630

KG

Item

Name

Description

KA

Liquid pipe connection port

6.35 flared connection

KB

Gas pipe connection port

12.70 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

/
/
VP20 (OD 26, ID 20)

/
/
/
/

Notes

1. When installing optional accessories, refer to their respective documentation.


2.The ceiling depth varies according to the documentation of the specific system.

3D094888A

FXSQ40-50A

69
25

40

492

38

KJ

800
301

KC

KE

KH

110

178

245

140

100
65

50

210

700

Suspension bolt

Fresh air intake position

2x65= 130

(Knockout hole.

109

O100

170

300 or more
Service space

FXSQ40-50A

ARROW VIEW A

3x140= 420

126 P.C.D.

515

4-M4 (CLASS 2)

32

KF

500 or more
Service space

179

50

50

KK
KD

654
4x145= 590

95

KA

210

738 Suspension position


6x65= 390

630 Suspension position

KB

ARROW VIEW A

42
Item

Name

Description

KA

Liquid pipe connection port

6.35 flared connection

KB

Gas pipe connection port

12.70 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

155

130

130 120

KG

5-O4.7 HOLE

/
/
VP20 (OD 26, ID 20)

/
/
/
/

Notes

1. When installing optional accessories, refer to their respective documentation.


2.The ceiling depth varies according to the documentation of the specific system.

3D094919A

154

FXSQ63-80A

Detailed technical drawings


FXSQ63-80A
25

69
40

301

38

65

KE

KH

110

245

KC

KJ

178

100

50

140

800
300 or more
Service space

1000
792

210

Suspension bolt

2x65= 130

(Knockout hole.

Fresh air intake position

109

O100

170

ARROW VIEW A

32

5x146= 730

126 P.C.D.

KF

500 or more
Service space

815

4 x M4 (CLASS 2)

179

50

50

KK
KD

954

1038 Suspension position

6x145= 890

95

KA

210

11x65= 715

630 Suspension position

KB

42
Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.90 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

135

125 98 117 135

125

100

KG

8-O4.7 HOLE

/
/

Indoor Units

Item

ARROW VIEW A

KG

VP20 (OD 26, ID 20)

/
/
/
/

Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.

3D094916A

FXSQ100-125A

FXSQ100-125A

65

100

KJ

800
301

KC

KE

KH

110

178

245

140

25

69
40

50

300 or more
Service space

1400
1192

210

Suspension bolt

Fresh air intake position

2x65= 130

( Knockout hole.

109

O100

38

170

ARROW VIEW A

KK
32

7x156= 1092

KF

179

50
KD

500 or more
Service space

1215

50

126 P.C.D.
4 x M4 (CLASS 2)

1354
8X150= 1200

1438 Suspension position

95

KA

630 Suspension position

KB

42
Item

150

Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.90 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

147.5 147.5 115 115

150

147.5 147.5 115

KG

ARROW VIEW A

226

16x65= 1040

KG

10xO4.7 HOLE

/
/
VP20 (OD 26, ID 20)

/
/
/
/

Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.

3D094917A

155

Detailed technical drawings


FXSQ140A

1550

Suspension bolt

69

1342

40

25
KJ

800
301

KC

KE

KH

110

245
178

140

100
65

50

210

Fresh air intake position

2x65= 130

(Knockout hole.

38
62
109

O100
170

300 or more
Service space

FXSQ140A

ARROW VIEW A

126 P.C.D.

32

179

1504
9x150= 1350

60
95
210

18x65= 1170

KD

50

Suspension position

1588
60

KF

500 or more
Service space

4 x M4 (CLASS 2)

50

KK
8x156= 1248
1365

KA
630 Suspension position

KB

42

Item

151

123 122 123 116 115

Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.90 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

151

KG

KG

ARROW VIEW A

10xO4.7 HOLE

123 122 123 116

/
/
VP20 (OD 26, ID 20)

/
/
/
/

Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.

3D094928A
FXSQ15A

FXSQ15A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

*1

MTap*1

UpperlimitofESP

HTap*2

LTap*1

L T (*1)
L T*2 (*1)
UpperlimitofESP

MTap*2

LTap*2

50

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

100

*3

*2

LowerlimitofESP

HTap*3

UpperlimitofESP

MTap*3

LTap*3

*3

LowerlimitofESP

0
5,5

Mark
*1
*2
*3

6,5

MAX

STD

ESP[Pa]
150
100
50

7,5

Airflowrate[m/min]

8,5

100

HTap
MTap
LTap

50

2.
LowerlimitofESP

0
5,5

9,5

6,5

7,5

Airflowrate[m/min]

8,5

9,5

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
7,5

Airflowrate[m/min] 8,5

9,5

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

156

1.

*1

LowerlimitofESP

Externalstaticpressure[Pa]

UpperlimitofESP

150

150

3D096999

Detailed technical drawings


FXSQ2025A

FXSQ20-25A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

150

150

UpperlimitofESP

1.

*1
MTap*1

UpperlimitofESP

100

HTap*2
LTap*1
*2

MTap*2

UpperlimitofESP

*2

LowerlimitofESP

LTap*2

50
HTap*3

*3

UpperlimitofESP

MTap*3

LTap*3

100

5,5

MTap

*3

6,5
Mark
*1
*2
*3

ESP[Pa]
150
100
30

MAX

STD

7,5

8,5

HTap

50

LTap

LowerlimitofESP

5,5

9,5

6,5

7,5

8,5

9,5

Airflowrate[m/min]

Airflowrate[m/min]

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

2.

LowerlimitofESP

Airflowraterange(H)

Indoor Units

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

*1

LowerlimitofESP

10

Airflowrate[m/min]

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095680A

FXSQ32A

FXSQ32A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

150

150

*2

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

*1

LowerlimitofESP

HTap*2

LTap*1

UpperlimitofESP

MTap*2

LTap*2

*2

LowerlimitofESP

50
*3

HTap*3

UpperlimitofESP

LTap*3

MTap*3

6,5

Externalstaticpressure[Pa]

Mark
*1
*2
*3

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

MAX

STD

ESP[Pa]
150
100
30

7,5

100
HTap
MTap
LTap

50

2.

*3

LowerlimitofESP

LowerlimitofESP

0
5,5

1.

*1

MTap*1

UpperlimitofESP

100

UpperlimitofESP

8,5

9,5

10,5

5,5

Airflowrate[m/min]

6,5

7,5

8,5

9,5

10,5

Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)

10

11

Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095681A

157

Detailed technical drawings


FXSQ40A

FXSQ40A
200

200

Fancharacteristics (3)
Airflowautoadjustment

Fancharacteristics (1)
HTap*1

150

150

UpperlimitofESP

*1

1.

*1

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

LowerlimitofESP

MTap*1

UpperlimitofESP

100

HTap*2
LTap*1
*2

MTap*2

*2

UpperlimitofESP

LowerlimitofESP

LTap*2

50

HTap*3

*3

UpperlimitofESP

MTap*3

LTap*3

HTap
MTap
LTap

50

2.

*3
LowerlimitofESP

LowerlimitofESP

0
9

10
Mark
*1
*2
*3

Externalstaticpressure[Pa]

100

11

13

14

15

16

17

10

Airflowrate[m/min]

ESP[Pa]
150
100
30

MAX

STD

12

12

13

14

15

16

17

Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

11

Airflowraterange(H)

13

14

15

16

17

Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095682A

FXSQ50A

FXSQ50A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

150

150

UpperlimitofESP

1.

*1

*1

LowerlimitofESP

MTap*1

HTap*2
LTap*1
MTap*2

*2

UpperlimitofESP

*2

LowerlimitofESP

LTap*2

50

*3

UpperlimitofESP

HTap*3
MTap*3

LTap*3

*3

LowerlimitofESP

0
9

Mark
*1
*2
*3

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

UpperlimitofESP

100

10

MAX

STD

11

12

13

Airflowrate[m/min]

ESP[Pa]
150
100
30

14

15

100
HTap
MTap

LTap

50

2.
LowerlimitofESP

16

17

10

11

12

13

Airflowrate[m/min]

14

15

16

17

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

Airflowraterange(H)

13

14

15

16

17

Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

158

3D095688A

Detailed technical drawings


FXSQ63A

FXSQ63A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

UpperlimitofESP

150

150

1.

*1

LowerlimitofESP

*1

Externalstaticpressure[Pa]

HTap*2
LTap*1

L T

(*1)

*2

*2

MTap*2

UpperlimitofESP

50

LowerlimitofESP

LTap*2

*3

UpperlimitofESP

HTap*3
MTap*3

LTap*3

*3

LowerlimitofESP

0
12

Mark
*1
*2
*3

13

14

15

ESP[Pa]
150
100
30

MAX

STD

16

17

Airflowrate[m/min]

18

19

20

21

22

23

100
HTap
MTap
LTap

50

2.
LowerlimitofESP

0
24

12

13

14

15

16

17

18

Airflowrate[m/min]

19

20

21

22

23

24

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

Airflowraterange(H)

Indoor Units

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

MTap*1

UpperlimitofESP

100

18

19

20

Airflowrate[m/min]

21

22

23

24

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095690A

FXSQ80A

FXSQ80A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

150

150
MTap*1

Externalstaticpressure[Pa]

UpperlimitofESP

100

HTap*2
LTap*1
*2

*2

LowerlimitofESP

LTap*2

*3

UpperlimitofESP

HTap*3
MTap*3

LTap*3

LowerlimitofESP

0
13,5

Mark
*1
*2
*3

Externalstaticpressure[Pa]

MTap*2

UpperlimitofESP

50

14,5

MAX

STD

15,5

16,5

ESP[Pa]
150
100
40

17,5

18,5

1.

LowerlimitofESP

Externalstaticpressure[Pa]

*1

UpperlimitofESP

*1

19,5

Airflowrate[m/min]

20,5

21,5

22,5

23,5

24,5

*3

100

HTap
MTap
LTap

50

2.

LowerlimitofESP

0
25,5

13,5

26,5

14,5

15,5

16,5

17,5

18,5

19,5

20,5

Airflowrate[m/min]

21,5

22,5

23,5

24,5

25,5

26,5

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
19,5

20,5

21,5

22,5

Airflowrate[m/min]

23,5

24,5

25,5

26,5

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095692A

159

Detailed technical drawings


FXSQ100A

FXSQ100A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

*1

LowerlimitofESP

MTap*1

100

HTap*2

LTap*1
*2

MTap*2

UpperlimitofESP

*2

LowerlimitofESP

LTap*2

*3

50

UpperlimitofESP

HTap*3
MTap*3

LTap*3

*3

LowerlimitofESP

100

HTap
MTap
LTap

50

2.
LowerlimitofESP

19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5

19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5

Airflowrate[m/min]

Airflowrate[m/min]

Externalstaticpressure[Pa]

Mark
*1
*2
*3

MAX

STD

ESP[Pa]
150
100
40

1.

*1

Externalstaticpressure[Pa]

UpperlimitofESP

Externalstaticpressure[Pa]

UpperlimitofESP

150

150

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0

Airflowraterange(H)

27

28

29

30

31

32

33

34

35

36

37

Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D095696A

FXSQ125A

FXSQ125A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

UpperlimitofESP

150

150
*1

MTap*1

UpperlimitofESP

1.

*1

LTap*1

HTap*2
*2

MTap*2

UpperlimitofESP

*2

LTap*2

50

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

LowerlimitofESP

100

LowerlimitofESP

*3

UpperlimitofESP

HTap*3

MTap*3
LTap*3

*3

LowerlimitofESP

0
22

23

Mark
*1
*2
*3

24

MAX

STD

25

26

ESP[Pa]
150
100
50

27

28

29

30

31

Airflowrate[m/min]

32

33

34

35

36

37

38

39

40

100

HTap
MTap
LTap

50

2.

LowerlimitofESP

41

22

23

24

25

26

27

28

29

30

31

32

Airflowrate[m/min]

33

34

35

36

37

38

39

40

41

1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

Externalstaticpressure[Pa]

Airflowraterange(H)

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
30,5

31,5

32,5

33,5

34,5

35,5

Airflowrate[m/min]

36,5

37,5

38,5

39,5

40,5

41,5

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

160

3D095697A

Detailed technical drawings


FXSQ140A

FXSQ140A
200

200

Fancharacteristics (1)

Fancharacteristics (3)
Airflowautoadjustment

HTap*1

150

150
MTap*1

*1

*1

LowerlimitofESP

Externalstaticpressure[Pa]

Externalstaticpressure[Pa]

UpperlimitofESP

100

HTap*2
LTap*1

MTap*2

*2

*2

LowerlimitofESP

UpperlimitofESP

50

LTap*2

*3

HTap*3
MTap*3

UpperlimitofESP

1.

UpperlimitofESP

*3

LTap*3

LowerlimitofESP

100

HTap
MTap

50

LTap

2.
LowerlimitofESP

0
25

Mark
*1
*2
*3

26

27

MAX

STD

28

ESP[Pa]
150
100
50

29

30

31

32

33

Airflowrate[m/min]

34

35

36

37

38

39

40

41

42

23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45

Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment

Fancharacteristics (2)
Fieldsettingwithremotecontrol

Indoor Units

Externalstaticpressure[Pa]

Airflowraterange(H)

200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
35

36

37

38

Airflowrate[m/min]

39

40

41

42

Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure

3D096688A

161

FXMQ-P7/FXMQ-MB

Concealed ceiling unit


with high ESP
Ideal for large sized spaces
FXMQ-P7: ESP up to 200 Pa
Possibility to change ESP via wired remote control allows
optimisation of the supply air volume
High external static pressure up to 200Pa facilitates extensive duct
and grille network
Discretely concealed in the wall: only the suction and discharge
grilles are visible
Reduced energy consumption thanks to specially developed DC
fan motor
Fresh air intake integrated in the same system thus reducing
installation cost as no additional ventilation device is required

FXMQ40P7

BRC1E52A/B BRC4C65

Fresh air intake opening in casing


Fresh air intake position

FXMQ-MB: ESP up to 270


High external static pressure up to 270Pa facilitates extensive duct
and grille network
Discretely concealed in the wall: only the suction and discharge
grilles are visible
Large capacity unit: up to 31.5 kW heating capacity
Reduced energy consumption thanks to specially developed DC
fan motor

* Brings in up to 10% of fresh air into the room

Flexible installation, as the air suction direction can be altered


from rear to bottom suction

Standard built-in drain pump with 625mm lift increases increases


flexibility and installation speed

///////////////////////////////////////////////////////////////////////////////////////

162

FXMQ-P7/FXMQ-MB

Automatic Airflow
Adjustment function

External static pressure (Pa)

Automatically selects the most appropriate fan curve to achieve the


units nominal air flow within 10%

Fan characteristic
curves

Air flow (rated)

Why?

Air flow (actual)

After installation the real ducting will frequently differ from the
initially calculated air flow resistance the real air flow may be
much lower or higher than nominal , leading to a lack of capacity or
uncomfortable air temperature

Air flow (with


automatic
adjustment)

Duct resistance
curves

Automatic Airflow Adjustment function will adapt the units fan


speed to any ducting automatically(10 or more fan curves are
available on every model), making installation much faster

Indoor Units

Air flow (m3/min)

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

FXMQ-P7/FXMQ-MB
kW
kW
kW
kW
mm
mm
mm
mm
kg

Required ceiling void >


Weight
Unit
Casing
Colour
Material
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Fan-External static
High/Nom.
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

50P7
5.6
6.3
0.110
0.098

63P7
7.1
8.0
0.120
0.108

80P7
9.0
10.0
0.171
0.159
300

100P7
11.2
12.5
0.176
0.164

1,000

125P7
14.0
16.0
0.241
0.229

200MB
22.4
25.0
0.895
0.895

250MB
28.0
31.5
1.185
1.185
470
1,380
1,100
132
-

1,400
700
350

35

46
Unpainted

m/min
m/min
Pa

18/16.5/15
18/16.5/15

25/22.5/20
25/22.5/20

Galvanised steel plate


32/27.5/23
39/33.5/28
32/27.5/23
39/33.5/28

200/100

dBA
dBA
dBA

61/41/39/37
41/39/37

mm
mm

6.35
12.7

Hz/V
A

19.5/17.8/16
19.5/17.8/16

58/54.0/50

72/67.0/62
-/-/-

270/160

Resin net with mold resistance


64/67/65/42/40/38
43/41/39
42/40/38
43/41/39
R-410A
2,087.5

270/170
-/48/-/45
-/-/-

70/44/42/40
44/42/40

9.52
15.9
VP25 (I.D. 25/O.D. 32)
1~/50/60/220-240/220

19.1

22.2
PS1B
1~/50/220-240

16
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

163

Detailed technical drawings


FXMQ50P7
FXMQ50P7

DETAIL B

VIEW A-A

125 (Knock out hole)


fresh air intake position

350 or more
(Service space)

Suspension bolt

500 or more

6 x M5 (On circumference)

DETAIL B

(Service space)

Item
1
2
3
4
5
6
7
8
9
10

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Remote control wiring connection
Power supply connection
Drain hole
Air filter
Air suction side
Air discharge side
Nameplate

Description
6.35 Flare connection
12.70 Flare connection
VP25 (0D 32, ID 25)
VP20 (0D 32, ID 25)
-

631 (Suspension position)

1038 (Suspension position)

3TW32694-1
NOTES

Refer to outlook drawing for installing optional accessories when installing optional accessories.

The required ceiling depth varies according to the configuration of the specific system.

For maintenance of the air filter, it is necessary to provide a service access panel.
Refer to the filter installation method drawing.

FXMQ63-80P7
FXMQ63-80P7
(Knock out hole)
Fresh air intake position

350 or more
(Service space)

Suspension bolt

Detail B

500 or more
(Service space)

(On circumference)

Item Name
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Remote control wiring connection
5
Power supply connection
6
Drain hole
7
Air filter
8
Air suction side
9
Air discharge side
10 Nameplate

631 (Suspension position)

390 or more
(Service space)

1038 (Suspension position)

(Ceiling opening)

Description
9.52 Flare connection
15.90 Flare connection
VP25 (OD 32, ID 25)
VP25 (OD 32, ID 25)
-

Detail B

(Ceiling opening)

NOTES

View A-A

1. Refer to the outlook drawing of optional accessories when installing them.


2. The required ceiling depth varies according to the configuration of the specific
system.
3. For maintenance of the air filter, it is necessary to provide a service access
panel.
4. Optional decoration panel: BYBS71DJW1 (light ivory white 10Y9/0.5)

With decoration panel

3TW31234-1B

164

Detailed technical drawings


FXMQ100-125P7
FXMQ100-125P7
(Knock out hole)
Fresh air intake position

350 or more
(Service space)

Suspension bolt

Detail B

500 or more
(Service space)

(On circumference)

Item Name
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Remote control wiring connection
5
Power supply connection
6
Drain hole
7
Air filter
8
Air suction side
9
Air discharge side
10 Nameplate

Detail B

Description
9.52 Flare connection
15.90 Flare connection
VP25 (OD 32, ID 25)
VP25 (OD 32, ID 25)
-

Indoor Units

View A-A

(Ceiling opening)

(Ceiling opening)

631 (Suspension position)

390 or more
(Service space)

1438 (Suspension position)

NOTES

1.
2.
3.
4.
With decoration panel

Refer to the outlook drawing of optional accessories when installing them.


The required ceiling depth varies according to the configuration of the specific system.
For maintenance of the air filter, it is necessary to provide a service access panel.
Optional decoration panel: BYBs125DJW1 (light ivory white 10Y9/0.5)

3TW31254-1B

FXMQ-MB

165

Detailed technical drawings


FXMQ50P7
Fan characteristics (1)

Upper limit of ESP


(max ESP)

Fan characteristics (3)


(airflow auto adjustment)

H (max ESP)
Lower limit of ESP
(max ESP)

M (max ESP)
L (max ESP)

Upper limit of ESP


(std ESP)

M (std ESP)
H (std ESP)
L (std ESP)

Lower limit of ESP


(std ESP)

External static pressure [Pa]

External static pressure [Pa]

FXMQ50P7

Upper limit of ESP

Upper limit of ESP by


airflow auto adjustment
H
Lower limit of ESP by
airflow auto adjustment

M
L

Lower limit of ESP

Airflow [m3/min]

Airflow [m3/min]

Fan characteristics (2)

(Field setting with remote control)

External static pressure [Pa]

Range of available air flow rate (H)

Airflow [m3/min]

3TW32698-1

NOTES

1.
2.

Fan characteristics as shown are in fan only mode.


ESP: External static pressure

FXMQ63P7
Fan characteristics (1)

Fan characteristics (3)


(airflow auto adjustment)

H (max ESP)
Upper limit of ESP
(max ESP)

M (max ESP)
Lower limit of ESP
(max ESP)

L (max ESP)

H (std ESP)

Upper limit of ESP


(std ESP)

M (std ESP)
Lower limit of ESP
(std ESP)

L (std ESP)

Airflow [m3/min]

External static pressure [Pa]

External static pressure [Pa]

FXMQ63P7

Upper limit of ESP by


airflow auto adjustment

Upper limit of ESP

H
M

Lower limit of ESP by


airflow auto adjustment

L
Lower limit of ESP

Airflow [m3/min]

Fan characteristics (2)

(Field setting with remote control)

External static pressure [Pa]

Range of available air flow rate (H)

Airflow [m3/min]

1.
2.

166

NOTES

Fan characteristics as shown are in fan only mode.


ESP: External static pressure

3TW32708-1

Detailed technical drawings


FXMQ80P7
Fan characteristics (1)

Fan characteristics (3)


(airflow auto adjustment)

H (max ESP)
Upper limit of ESP
(max ESP)

M (max ESP)
Lower limit of ESP
(max ESP)

L (max ESP)

H (std ESP)

Upper limit of ESP


(std ESP)

M (std ESP)
Lower limit of ESP
(std ESP)

L (std ESP)

External static pressure [Pa]

External static pressure [Pa]

FXMQ80P7

Upper limit of ESP by


airflow auto adjustment

Upper limit of ESP

H
M

Lower limit of ESP by


airflow auto adjustment

L
Lower limit of ESP

Airflow [m3/min]

Airflow [m3/min]

Fan characteristics (2)

(Field setting with remote control)

Indoor Units

External static pressure [Pa]

Range of available air flow rate (H)

Airflow [m3/min]

1.
2.

3TW32718-1

NOTES

Fan characteristics as shown are in fan only mode.


ESP: External static pressure

FXMQ100P7
Fan characteristics (1)

Fan characteristics (3)


(airflow auto adjustment)

H (max ESP)
Upper limit of ESP
(max ESP)
M (max ESP)

Lower limit of ESP


(max ESP)

L (max ESP)
Upper limit of ESP
(std ESP)

H (std ESP)
M (std ESP)
Lower limit of ESP
(std ESP)

L (std ESP)

Airflow [m3/min]

External static pressure [Pa]

External static pressure [Pa]

FXMQ100P7

Upper limit of ESP by


airflow auto adjustment
H

Upper limit of ESP


M

Lower limit of ESP by


airflow auto adjustment

L
Lower limit of ESP

Airflow [m3/min]

Fan characteristics (2)

(Field setting with remote control)

External static pressure [Pa]

Range of available air flow rate (H)

Airflow [m3/min]

1.
2.

3TW32728-1

NOTES

Fan characteristics as shown are in fan only mode.


ESP: External static pressure.

167

Detailed technical drawings


FXMQ125P7
Fan characteristics (1)

Fan characteristics (3)


(airflow auto adjustment)

H (max ESP)
Upper limit of ESP
(max ESP)

M (max ESP)

L (max ESP)

H (std ESP)

Lower limit of ESP


(max ESP)

Upper limit of ESP


(std ESP)
L (std ESP)

M (std ESP)

Airflow [m3/min]

Lower limit of ESP


(std ESP)

External static pressure [Pa]

External static pressure [Pa]

FXMQ125P7

Upper limit of ESP

Upper limit of ESP by


airflow auto adjustment
H
M

Lower limit of ESP by


airflow auto adjustment

L
Lower limit of ESP

Airflow [m3/min]

Fan characteristics (2)

(Field setting with remote control)

External static pressure [Pa]

Range of available air flow rate (H)

Airflow [m3/min]

1.
2.

NOTES

Fan characteristics as shown are in fan only mode.


ESP: External static pressure

FXMQ200MB

168

3TW32738-1

Detailed technical drawings

Indoor Units

FXMQ250MB

169

FXTQ-A

Concealed ceiling unit


For the highest energy efficiency
Automatic air flow adjustment function measures the air volume
and static pressure and adjusts it towards the nominal air flow,
whatever the length of duct, making installation easier and
guaranteeing comfort. Moreover, the ESP can be changed via the
wired remote control to optimize the supply air volume (for 50
and 63 class)
Narrow ceilings voids are no longer a challenge, 50 & 60 class units
can swiftly be integrated as they only are 245mm in height.
High external static pressure up to 270Pa facilitates using flexible
ducts of varying lengths
Discretely concealed in the ceiling: only the suction and discharge
grilles are visible

FXTQ50A

BRC1E51A/B BRC4C65

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Fan-Air flow rate - 50Hz
Fan-External static pressure - 50Hz
Sound power level
Sound pressure level
Refrigerant
Piping connections

Power supply
Current - 50Hz
Control systems

Nom.
Nom.
Cooling
Heating
Unit

Nom.
Nom.
Height
Width
Depth

Unit
Material
Cooling
High/Low
High/Nom.
Cooling
Nom.
Cooling
High/Low
Type
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Simplified wired remote control for hotel applications
Wired remote control

Only connectable to REYQ8-16T, RYYQ8-16T, RXYQ8-16T(9)

170

FXTQ
kW
kW
kW
kW
mm
mm
mm
kg

50A
5.6
6.3
0.214
0.211

63A
7.1
8.0
0.243
0.240

80A
8.7
10.0
1.294
1.294

245
1,400

100A
11.2
12.5
1.465
1.465
470
1,380
1,100
137

1,550
800

47

51

36/26
150/50

39/28
140/50

39/33

42/34

Galvanised steel plate


m/min
Pa
dBA
dBA
mm
mm
Hz/V
A

58/50
221/132

72/62
270/191

48/45
R-410A
9.52
15.9
VP20

19.1

22.2
PS1B

1~/50/60/220-240/220
16

15
BRC4C65
BRC2E52C (heat recovery) / BRC3E52C (heat pump)
BRC1D52 / BRC1E52A/B

Detailed technical drawings

FXTQ50A

FXTQ50A

Fresh air intake position

65

KC

KE

KH

110

245

800
301

KJ

178

100

50

140

25

69
40

300 or more
Service space

1400
1192

210

Suspension bolt

2x65= 130

( Knockout hole.

38

O100

109

170

ARROW VIEW A

KK
32

7x156= 1092

KF

179

50

50

126 P.C.D.

KD

500 or more
Service space

1215

4 x M4 (CLASS 2)

1354
8X150= 1200

1438 Suspension position

95

KA
KB
630 Suspension position

KG

42
Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.90 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

147.5 147.5 115 115

150

147.5 147.5 115

KG

ARROW VIEW A

10xO4.7 HOLE

/
/

Indoor Units

Item

150

226

16x65= 1040

VP20 (OD 26, ID 20)

/
/
/
/

Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3. Editable data for this drawing are available in the GDE (E-BOM) system.

3D098385

FXTQ63A

1550

Suspension bolt

40
50

25
KJ

800
301

KC

KE

KH

110

245
178

140

69

1342

210

100
65

Fresh air intake position

2x65= 130

(Knockout hole.

38
62
109

O100
170

300 or more
Service space

FXTQ63A

ARROW VIEW A

8x156= 1248
1365

126 P.C.D.

32
500 or more
Service space

4 x M4 (CLASS 2)
1588

179

50

1504
9x150= 1350

Suspension position

18x65= 1170

KD

60
95
210

60

KF

50

KK

KA
630 Suspension position

KB

42

Item

151

123 122 123 116 115

Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.90 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Wiring connection

KE

Power supply connection

KF

Drain outlet

KG

Air filter

KH

Air suction side

KJ

Air discharge side

KK

Nameplate

151

123 122 123 116

KG

ARROW VIEW A

KG

10xO4.7 HOLE

/
/
VP20 (OD 26, ID 20)

/
/
/
/

Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3. Editable data for this drawing are available in the GDE (E-BOM) system.

3D098386

171

Detailed technical drawings


FXTQ80-100A
FXTQ80-100A
Field piping
Indoor unit

Gas side

Liquid side

FXTQ80A7VEB

19.1 Accessory pipe

9.5

FXTQ100A7VEB

22.2 Accessory pipe

9.5

1148

9
32 - O4.7

1380

1296

11 x 100 = 1100

11 x 100 = 1100

Name

Description

Liquid pipe connection port

Flare connection

Gas pipe connection port

Brazed connection

Grounding terminal

Inside of the switch box (M5)

Control box

5
6

Power supply connection

Hook

Air discharge side

Transmission wiring connection


M10

Air suction side

10

Accessory pipe

11

Nameplate

12

Drain pipe connection

Brazed connection
Internal pipe thread PS1B
Largest diameter 33, 349
Smallest diameter 30, 391

13
32 - O4.7

Water inlet

245

1100 Minimum

Service space

250

3 x 100 = 300

11 x 100 = 1100
1200
1230

13

11

30
6

VIEW A

32 - O7

Air suction side

30

1100
12

200
250

50

613
760

3 x 100 = 300

3 x 100 = 300

470

330

30

360

Air discharge side

296

25

330

360

u 150

650 Minimum
Service space

Inspection hole
q600 Minimum

390

10

60

5 x 200 1000
1200

1230

16 - O8

3D098090

FXTQ50A
Applicable models
FXTQ50A
FXTQ50A2VEB

200

200

Fan characteristics (3)

Fan characteristics (1)

Air flow auto adjustment


H-Tap *1
150

*1
Upper limit of ESP

M-Tap *1

*1
Lower limit of ESP

100

L-Tap *1

H-Tap *2

*2
Upper limit of ESP

M-Tap *2
*2
Lower limit of ESP

L-Tap *2

External static pressure [Pa]

External static pressure [Pa]

150

Upper limit of ESP

1.

H-Tap

100

M-Tap

2.

L-Tap
50

50

H-Tap *3

*3
Upper limit of ESP

M-Tap *3
L-Tap *3

*3
Lower limit of ESP

Lower limit of ESP


0

0
22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

22

41

23

24

25

MAX
STD

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

Air flow rate [m/min]

Air flow rate [m/min]


Mark
*1
*2
*3

26

1. Upper limit of ESP by air flow auto adjustment

ESP [Pa]
150
100
50

2.

Fan characteristics (2)


Field setting with remote control

Lower limit of ESP by air flow auto adjustment

Air flow rate range (H)


200
190
180
170

External static pressure [Pa]

160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
30.5

31.5

32.5

33.5

34.5

35.5

36.5

37.5

38.5

39.5

40.5

41.5

Air flow rate [m/min]

Notes:
1. Fan characteristics as shown are in "fan only" mode.
2. ESP: External static pressure.
3. Editable data for this dwg. are available in GDE (e-bom) system.

172

3D098396

Detailed technical drawings

FXTQ63A
Applicable models
FXTQ63A
FXTQ63A2VEB

200

200

Fan characteristics (3)

Fan characteristics (1)

Air flow auto adjustment


H-Tap *1
150

150

External static pressure [Pa]

External static pressure [Pa]

1.
M-Tap *1

*1
Lower limit of ESP

*1
Upper limit of ESP

H-Tap *2

100

L-Tap *1

M-Tap *2
*2
Lower limit of ESP

*2
Upper limit of ESP
L-Tap *2
*3
Upper limit of ESP

50

Upper limit of ESP

H-Tap

100

M-Tap
L-Tap

H-Tap *3

2.

50

M-Tap *3
*3
Lower limit of ESP

L-Tap *3

Lower limit of ESP

0
25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

23

24

25

26

27

28

29

30

31

Mark
*1
*2
*3

MAX
STD

ESP [Pa]
150
100
50

32

33

34

35

36

37

38

39

40

41

42

43

44

45

Air flow rate [m/min]

Air flow rate [m/min]

Fan characteristics (2)


Field setting with remote control

1.

Upper limit of ESP by air flow auto adjustment

2.

Lower limit of ESP by air flow auto adjustment

Air flow rate range (H)


200
190
180
170

150
140
130
120
110
100
90
80
70
60

Indoor Units

External static pressure [Pa]

160

50
40

FXTQ80A

30
20
10
0
35

36

37

38

39

40

41

42

Air flow rate [m/min]

Notes:
1. Fan characteristics as shown are in "fan only" mode.
2. ESP: External static pressure.
3. Editable data for this dwg. are available in GDE (e-bom) system.

3D098397

FXTQ80A
FXTQ80A

300

High
High ESP

FXTQ80A
P
ES
of
it
im
rl P
pe ES
p
Low
h
U ig
H
High ESP

300

P
ES
of
it
il m
P
r
pe ES
Low
Up igh
H
High
SPESP

of

P
ES

300

High
High ESP

w E
Lo i g h
H

to
mi
r li SP
e
w E
Lo i g h
H

High
Standard ESP
fE
to P
i
m
r li d ES
e
p
r
Up nda
High
Sta
SP
Standard ESP
f E Low
it o
lim ESP
r
Standard
ESP
e rd
p
p

200

U nda
Sta

100

Low
Standard ESP

S
of E
mit
er li EPSP
LowndarfdES
Setralimit oSP

100

P
ES
of
it
lim P
r
pe ES
Low
Up igh
H
High ESP

SP
fE

to
mi
r li P
we ES
Lo i g h
H

SP
fE

200

External static pressure [Pa]

External static pressure [Pa]

External static pressure [Pa]

200

t
High
mi
r li SP
High eESP

High
Standard ESP

SP
fE
it o
lim ESP
r
pe rd
Up nda
Sta
Low
Standard ESP
100

SP
of E
mit SP
er li
Lowndard E
Sta

Lowndard E
Sta

0
48

50

55

58

60

65

Air flow rate [m/min]


Notes

1.The remote controller can be used to switch between 'high' and 'low'.

48
48

5050

55

55 58

6058

60

Air flow rate [m/min]

Air flow rate [m/min]

65

is factory-set to 'standard'. It is possible to switch between 'standard ESP'


2.The air flow65
and 'high ESP' by remote controller setting.

Notes

Notes
1.The remote controller can be used to switch between 'high' and 'low'.
remote
can
be used Ittois switch
'high' and
'low'.ESP'
1.The
air flowcontroller
is factory-set
to 'standard'.
possiblebetween
to switch between
'standard
2.The
and 'high ESP' by remote controller setting.

2.The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP'

and 'high ESP' by remote controller setting.

4D098100

173

FXTQ100A

Detailed technical drawings


300

FXTQ100A

FXTQ100A

High
High ESP
SP
fE
it o
im
rl P
pe S
Up igh E
H
Low
SP
f E High ESP

it o
im
rl P
pe E S
p
U igh
P
H f ES
Low
it o
lim SP High ESP

External static pressure [Pa]

External static pressure [Pa]

200

200

E
per
Up ndard
Sta

SP
fE
it o
r lim ESP
e
p
Up ndard
Sta

Low
Standard ESP

300

High
High ESP

to
mi
r li
we ESP
o
L gh
Hi
200
SP High
fE
o
it
Standard ESP
im

rl
we SP
L o gh E
Hi
High
Standard ESP

Low
Standard ESP

100

High
High ESP

SP
fE

External static pressure [Pa]

300

SP
fE
it o
lim
r
we SP
L o gh E
Hi
High
Standard ESP

SP
fE
it o
lim SP
E
per
Up ndard
Sta

Low
Standard ESP

100

P
of ES
r limit
Lowe ard ESP
d
Stan

P
of ES
r limit
Lowe ard ESSPP
d
Stanlimit of E

100

SP
fE
it o
lim
r
P
pe S
Up igh E
H
Low
High ESP

r
Lowe ard ESP
d
Stan

0
60

62

65

70

72

75

80

Air flow rate [m/min]


Notes

00
60
60

1.The remote controller can be used to switch between 'high' and 'low'.

62
62

65 65

70

72
70

7275

75

Air flow rate [m/min]

Air flow rate [m/min]

The air flow is factory-set


to 'standard'. It is possible to switch between 'standard ESP'
2.80
80
and 'high ESP' by remote controller setting.

Notes

Notes
1.The remote controller can be used to switch between 'high' and 'low'.
remote
can
be used Ittois switch
'high' and
'low'.ESP'
1.The
air flowcontroller
is factory-set
to 'standard'.
possiblebetween
to switch between
'standard
2.The
and 'high ESP' by remote controller setting.

2.The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP'

and 'high ESP' by remote controller setting.

4D098101

4D098101

4D098101

174

FXAQ-P

Wall mounted unit


For rooms with no false ceilings nor free floor space
Flat, stylish front panel blends easily within any interior dcor and
is easier to clean
Can easily be installed in both new and refurbishment projects
15 class unit especially developed for small or well-insulated
rooms, such as hotel bedrooms, small offices, etc.
Reduced energy consumption thanks to specially developed DC
fan motor
The air is comfortably spread up- and downwards thanks to
5 different discharge angles that can be programmed via the
remote control
Maintenance operations can be performed easily from the front of
the unit

FXAQ20-32P

BRC7EB518

Indoor Units

BRC1E52A/B

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Fan-Air flow rate 50Hz
Air filter
Sound power level
Sound pressure level
Refrigerant
Piping connections

Power supply
Current - 50Hz
Control systems

Nom.
Nom.
Cooling
Heating
Unit

Unit
Colour
Cooling

Nom.
Nom.
Height
Width
Depth

FXAQ
kW
kW
kW
kW
mm
mm
mm
kg

15P
1.7
1.9
0.017
0.025

20P
2.2
2.5
0.019
0.029

25P
2.8
3.2
0.028
0.034

32P
3.6
4.0
0.030
0.035
290

40P
4.5
5.0
0.020
0.020

795

50P
5.6
6.3
0.033
0.039

63P
7.1
8.0
0.050
0.060

1,050
238

11

14
White (3.0Y8.5/0.5)

High/Low

Type
Cooling
High/Nom.
Cooling
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

m/min

dBA
dBA

mm
mm
Hz/V
A

7.0/4.5
52.0/34.0/29.0

7.5/4.5

8/5

8.5/5.5

12/9

15/12

Washable resin net


53.0/54.0/55.5/57.0/60.0/35.0/29.0
36.0/29.0
37.5/29.0
39.0/34.0
42.0/36.0
R-410A
2,087.5
6.35
12.7
VP13 (I.D. 13/O.D. 18)
1~/50/220-240
16
BRC7EB518
BRC1E52A/B / BRC1D52
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

19/14
65.0/47.0/39.0

9.52
15.9

175

Detailed technical drawings


FXAQ15-32P
FXAQ15-32P

30 or more
(Required space)

Approx 400

Dimensions for
full open front panel

50 or more

(Required space)

90 or more

Piping direction

Name plate Note 2

Piping direction

Piping direction

(Required space)

50 or more
(Required space)

Outside line

120 or less

2500 or more
For installation
in high spaces

Approx 475
Approx 460
(Filter part)

Approx 290
(Flexible tube part)

Filter part

80 hole

Approx 415
Mounting location

Nr
1
2
3
4
5
6
7
8
9

Name

Description

Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole

12.7mm Flare connection


6.4mm Flare connection
VP13 (External dia. 18)
M4

80 hole
Piping and
Wiring intake

3D065064A

NOTES

Location of units of Name Plate: Right side surface of casing.

In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.

FXAQ40-50P
FXAQ40-50P

30 or more
(Required space)

Approx 400

(Required space)

90 or more

Piping direction

Dimensions for
full open front panel

Name plate Note 2


50 or more

Piping direction

Piping direction

(Required space)

Outside line

2500 or more
50 or more
For installation
(Required space) in high spaces

120 or less

Approx 475
Approx 460
(Filter part)

Filter part

80 hole

Approx 290
(Flexible tube part)
Approx 415

80 hole
Piping and
Wiring intake

Mounting location

Nr
1
2
3
4
5
6
7
8
9

176

Name
Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole

Description

12.7mm Flare connection


6.4mm Flare connection
VP13 (External dia. 18)
M4

3D065065A

NOTES

Location of units of Name Plate: Right side surface of casing.

In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.

Detailed technical drawings


FXAQ63P
FXAQ63P

90 or more
(Required space)

Piping direction

30 or more
(Required space)

Approx 400

Dimensions for
full open
front panel

Piping direction

Name plate Note 2

Piping direction

50 or more

50 or more

(Required space)

(Required space)

Outside line

2500 or more
For installation
in high spaces

120 or less

Approx 475
Approx 460
Filter part

Filter part

80 hole

Approx 415

Mounting location

Name
Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole

Description

15.9mm Flare connection


9.5mm Flare connection
VP13 (External dia. 18)
M4

3D065066A

NOTES

Location of units of Name Plate: Right side surface of casing.

In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.

Indoor Units

Nr
1
2
3
4
5
6
7
8
9

80 hole
Piping and
Wiring intake

177

FXHQ-A

Ceiling suspended unit


For wide rooms with no false ceilings nor free floor space
Ideal for comfortable air flow in wide rooms thanks to Coanda
effect: up to 100 discharge angle

FXHQ63A

Even rooms with ceilings up to 3.8m can be heated up or cooled


down very easily without capacity loss
Can easily be installed in both new and refurbishment projects
Can easily be mounted in corners and narrow spaces, as it only
needs 30mm lateral service space

Air inlet
30 or more
(Service space)

////////////////////////////

Obstruction

////////////////////////////////////

Air outlet

BRC7G53

Reduced energy consumption thanks to specially developed DC


fan motor and drain pump
Stylish unit blends easily with any interior. The flaps close entirely
when the unit is not operating and there are no air intake grilles
visible

////////////////////////////////////////////

//////////////////////

//////////////////////

30 or more
(Service
space)

BRC1E52A/B

300

Fresh air intake integrated in the same system thus reducing


installation cost as no additional ventilation device is required
Fresh air intake opening in casing

* Brings in up to 10% of fresh air into the room

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Weight
Casing

Nom.
Nom.
Height
Width
Depth

Unit
Colour
Material
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
(1) Contains fluorinated greenhouse gases

178

FXHQ
kW
kW
kW
kW
mm
mm
mm
kg

32A
3.6
4.0
0.107
0.107

m/min
m/min

14.0/12.0/10.0
14.0/12.0/10.0

dBA
dBA
dBA

36.0/34.0/31.0
36.0/34.0/31.0

mm
mm

6.35
12.7

Hz/V
A

960
24

63A
7.1
8.0
0.111
0.111
235
1,270
690
33
Fresh White
Resin
20.0/17.0/14.0
20.0/17.0/14.0
Resin net with mold resistance
37.0/35.0/34.0
37.0/35.0/34.0
R-410A
2,087.5

100A
11.2
12.5
0.237
0.237
1,590
39

29.5/24.0/19.0
29.5/24.0/19.0

44.0/37.0/34.0
44.0/37.0/34.0

9.52
15.9
VP20 (I.D. 20/O.D. 26)
1~/50/220-240
16
BRC7G53
BRC1E52A/B / BRC1D52
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

Detailed technical drawings

Indoor Units

FXHQ32A

FXHQ63A

179

Detailed technical drawings


FXHQ100A

3D069633D

180

FXUQ-A

4-way blow
ceiling suspended unit
Unique Daikin unit for high rooms with
no false ceilings nor free floor space
Even rooms with ceilings up to 3.5m can be heated up or cooled
down very easily without capacity loss
Can easily be installed in both new and refurbishment projects
Recessed installation possible in small ceiling voids (88 mm)
Individual flap control: flexibility to suit every room layout without
changing the location of the unit!

FXUQ-A

BRC1E52A/B

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Nom.
Nom.
Cooling
Heating
Unit

Weight
Casing

Nom.
Nom.
Height
Width
Depth

Unit
Colour
Material
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Contains fluorinated greenhouse gases

FXUQ
kW
kW
kW
kW
mm
mm
mm
kg

Standard drain pump with 500mm lift increases flexibility and


installation speed
Indoor Units

Reduced energy consumption thanks to specially developed small


tube heat exchanger, DC fan motor and drain pump
Stylish unit blends easily with any interior. The flaps close entirely
when the unit is not operating and there are no air intake grilles
visible
Optimum comfort guaranteed with automatic air flow adjustment
to the required load
5 different discharge angles between 0 and 60can be
programmed via the remote control

BRC7C58

VP20
500

//////////////////////////////////////////////

71A
8.0
9.0
0.090
0.073

100A
11.2
12.5
0.200
0.179
198
950
950

26

27
Fresh White
Resin

m/min
m/min

22.5/19.5/16.0
22.5/19.5/16.0

dBA
dBA

40.0/38.0/36.0
40.0/38.0/36.0

31.0/26.0/21.0
31.0/26.0/21.0
Resin net with mold resistance

mm
mm
Hz/V
A

47.0/44.0/40.0
47.0/44.0/40.0

R-410A
2,087.5
9.52
15.9
I.D. 20/O.D. 26
1~/50/60/220-240/220-230
16
BRC7C58
BRC1E52A/B / BRC1D52
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

181

Detailed technical drawings


FXUQ-A

182

FXLQ-P

Floor standing unit


For perimeter zone air conditioning
Unit can be installed as free standing model by use of optional
back plate
Its low height enables the unit to fit perfectly beneath a window
Stylish modern casing finished in pure white (RAL9010) and iron
grey (RAL7011) blends easily with any interior
Requires very little installation space

>20mm

1750mm

100mm

////////////////////////////////

Floor standing

///////////////////////////////////////////////////////////

///////////////////////////////////////////////////////////

>20mm

//////////////////

FXLQ20,25P

BRC1E52A/B BRC4C65

////////////////////////////////

Wall mounted

Indoor Units

Wall mounted installation facilitates cleaning beneath the unit


where dust tends to accumulate

Wired remote control can easily be integrated in the unit

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Fan-Air flow rate 50Hz
Air filter
Sound power level
Sound pressure level
Refrigerant
Piping connections

Power supply
Current - 50Hz
Control systems

Nom.
Nom.
Cooling
Heating
Unit

Unit
Colour
Cooling

Nom.
Nom.
Height
Width
Depth

High/Low

Type
Cooling
Nom.
Cooling
High/Low
Heating
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

FXLQ
kW
kW
kW
kW
mm
mm
mm
kg
m/min

dBA
dBA
dBA

20P
2.2
2.5

25P
2.8
3.2
0.049
0.049

32P
3.6
4.0

40P
4.5
5.0

50P
5.6
6.3

0.090
0.090
600
1,140
232
32
Fresh white (RAL9010) / Dark grey (RAL7011)

1,000
27
7/6

8/6

63P
7.1
8.000
0.110
0.110
1,420
38

11/8.5

14/11

16/12

38/33
38/33

39/34
39/34

40/35
40/35

Resin net
35/32
35/32
R-410A
2,087.5

mm
mm
Hz/V
A

6.35
12.7
O.D. 21 (Vinyl chloride)
1~/50/60/220-240/220
15
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

9.52
15.9

183

Detailed technical drawings


FXLQ20-25P
FXLQ20-25P

20 or more
100 or more

1750 or more

100 or more
Discharge

Suction

Front of face
1000 or more

Base

Required installation space

Piping hole (rear)

4-12x30 Oblong hole


Hole for fear mounting
Level adjusting screw in standard accessory
4xM6
2-12x18 Oblong hole
Hole for f xing to the f oor

Wiring hole (bottom)

Item
1
2
3
4
5

Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Switch box
Air f lter

Description
6.4 Flare connection
12.7 Flare connection
O.D.21

Piping hole (bottom)

3TW32294-1

FXLQ32-40P
);/43

RUPRUH
RUPRUH

RUPRUH

RUPRUH
'LVFKDUJH

6XFWLRQ

)URQWRIIDFH
RUPRUH

%DVH

5HTXLUHGLQVWDOODWLRQVSDFH

3LSLQJKROH UHDU

[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ
/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\
[0
[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU

:LULQJKROH ERWWRP

3LSLQJKROH ERWWRP

,WHP






1DPH
/LTXLGSLSHFRQQHFWLRQ
*DVSLSHFRQQHFWLRQ
'UDLQSLSHFRQQHFWLRQ
6ZLWFKER[
$LUIOWHU

'HVFULSWLRQ
)ODUHFRQQHFWLRQ
)ODUHFRQQHFWLRQ
2'

7:

184

Detailed technical drawings


FXLQ50-63P
);/43
RUPRUH
RUPRUH

RUPRUH

RUPRUH
'LVFKDUJH

6XFWLRQ

)URQWRIIDFH
RUPRUH

%DVH

5HTXLUHGLQVWDOODWLRQVSDFH

3LSLQJKROH UHDU

0RGHO
);/
);/

/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\
[0

$



%


Indoor Units

[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ

[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU

:LULQJKROH ERWWRP

3LSLQJKROH ERWWRP

,WHP






1DPH
/LTXLGSLSHFRQQHFWLRQ
*DVSLSHFRQQHFWLRQ
'UDLQSLSHFRQQHFWLRQ
6ZLWFKER[
$LUIOWHU

'HVFULSWLRQ
$)ODUHFRQQHFWLRQ
%)ODUHFRQQHFWLRQ
2'

7:

185

FXNQ-A

Concealed floor standing unit


Designed to be concealed in walls
Discretely concealed in the wall: only the suction and discharge
grilles are visible
Requires very little installation space as the depth is only 200mm

FXNQ-A

BRC1E52A/B

BRC4C65

Its low height (620 mm) enables the unit to fit perfectly beneath a
window
High ESP allows flexible installation

Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions

Weight
Casing
Fan-Air flow rate 50Hz

Nom.
Nom.
Cooling
Heating
Unit

Unit
Colour
Material
Cooling
Heating
High/Nom.

Nom.
Nom.
Height
Width
Depth

High/Nom./Low
High/Nom./Low

Fan-External static
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications

(1) Including installation legs (2) Contains fluorinated greenhouse gases

186

FXNQ
kW
kW
kW
kW
mm
mm
mm
kg

m/min
m/min
Pa

dBA
dBA
dBA

mm
mm
Hz/V
A

20A
2.2
2.5

25A
2.8
3.2
0.071
0.068

32A
3.6
4.0

40A
4.5
5.0
0.078
0.075

50A
5.6
6.3
0.099
0.096

63A
7.1
8.00
0.110
0.107

620 / 720 (1)


750

950

1,150

27.5

32

200
23.5

8.0/7.2/6.4
8.0/7.2/6.4
41/10

Unpainted
Galvanised steel plate
10.5/9.5/8.5
10.5/9.5/8.5
42/10

52/15

12.5/11/10.0
12.5/11/10.0

16.5/14.5/13.0
16.5/14.5/13.0

59/15

55/15

Resin net with mold resistance


51/52/53/30/28.5/27
32/30/28
33/31/29
30/28.5/27
32/30/28
33/31/29
R-410A
2,087.5
6.35
12.7
VP20 (I.D. 20/O.D. 26)
1~/50/60/220-240/220
16
BRC4C65
BRC1D52 / BRC1D61 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)

54/35/33/32
35/33/32

9.52
15.9

Detailed technical drawings


FXNQ20-32A
FXNQ20-32A
790

300
ARROW VIEW B

170
156

80

4x150=600

ARROW VIEW A

200

620

680
662

14-M4
740

20 or more

Suspension position

100

16-O4.7 HOLE

5x100= 500

130
63

330
179.4

100

KD
KF

48

KK
300 or more
Service space

KJ
5x100= 500

790
50
10
42
50

240 or more

90

KH

8.4

ARROW VIEW
A

620

100 or more

500

KC

723

KA

Suspension position

KH

310

4-M8~M10

48

24

60

Suspension bolt

KB

57.5

20 or more

12.5
19.5

Inspection door

KJ

KE
46

16-O4.3 HOLE

601

171

ARROW VIEW B

Front suction

KG

180
116
100

4-O5 HOLE
5x100= 500
601

16-O4.3 HOLE

810
830
Item

Bottom suction

Description

Liquid pipe connection port

6.40 flared connection

KB

Gas pipe connection port

12.7 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Drain hose

ID 25

KE

Control box

KF

Transmission line

KG

Power supply connection

KH

Suspension bracket

KJ

Air filter

KK

Mounting foot

Indoor Units

Name

KA

Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.

3D096749A

FXNQ40-50A
FXNQ40-50A
990

300

ARROW VIEW B

880
620

862
4x150= 600

90

156

200

170
18-M4

12.5

20 or more

57.5

ARROW VIEW A

Inspection door

19.5

80

90

940

Suspension position

20 or more

8x100= 800

KD

63
310

723

KF
KJ

48
8.4

KK
300 or more
Service space

42
50

KJ

KE

7x100= 700
50

990
10

240 or more

90
130

KH
330

KH

100
179.4

100 or more

500

KC

620

KA

48

24

Suspension position

4-M8~M10

ARROW VIEW
A

100

22-O4.7 HOLE

60

Suspension bolt

KB

801

46

20-O4.3 HOLE

ARROW VIEW B

171

Front suction
7x100= 700

116
100

4-O5 HOLE

180

KG

801
1010

20-O4.3 HOLE

1030

Bottom suction
Item

Name

Description

KA

Liquid pipe connection port

6.4 flared connection

KB

Gas pipe connection port

12.70 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Drain hose

ID 25

KE

Control box

KF

Transmission line

KG

Power supply connection

KH

Suspension bracket

KJ

Air filter

KK

Mounting foot

Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.

3D096747

187

Detailed technical drawings


FXNQ63A
FXNQ63A
ARROW VIEW B

300

200

80

156
170

57.5

19.5
12.5

1080
1060
6x150= 900

620

1190

ARROW VIEW A

Inspection door

18-M4

20 or more

1140
Suspension position

20 or more

10x100= 1000

130
63

330
100
179.4

620

KF

KK
300 or more
Service space

1190

50

KJ

9x100= 900
1001

KE
46

24-O4.3 HOLE

171

10
42
50

240 or more

KH

KD

48
8.4

ARROW VIEW
A

723

100 or more

500

KC

Suspension position

KH
KA

48
90

310

4-M8~M10

100
24

26-O4.7 HOLE

60

Suspension bolt

KB

KJ

ARROW VIEW B

Front suction

KG
180
116
100

4-O5 HOLE
9x100= 900
1001

24-O4.3 HOLE

75

1210
1230
Item

Bottom suction

Name

Description

KA

Liquid pipe connection port

9.52 flared connection

KB

Gas pipe connection port

15.9 flared connection

KC

Drain pipe connection

VP20 (OD 26, ID 20)

KD

Drain hose

ID 25

KE

Control box

KF

Transmission line

KG

Power supply connection

KH

Suspension bracket

KJ

Air filter

KK

Mounting foot

Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.

3D096740A

FXNQ20-25A

188

Detailed technical drawings

Indoor Units

FXNQ32A

FXNQ40A

189

Detailed technical drawings


FXNQ50A

FXNQ63A

190

VRV heatpump combined with

stylish indoor units


Combine VRV indoor units
with stylish indoor units
on a VRV IV heat pump

FXSQ-A
VRV indoor unit

FXFQ-A

FVXG-K
Nexura

VRV IV heat pump

BPMKS967A2

FTXG-LW

Indoor Units

VRV indoor unit

RYYQ-T
RXYQ-T(9)

Daikin Emura

Connect only stylish indoor units


to VRV IV S-series or VRV IV W-series outdoor units
FCQG-F

on a VRV III-S heat pump

BPMKS967A2

FTXG-LS - Daikin Emura


FBQ-D
RXYSCQ-TV1

BPMKS967A2

FVXG-K - Nexura

RXYSQ-TV1
RXYSQ-TY1
* Special order unit, contact your local sales representative for more information

RWEYQ-T8*

BPMKS967A

Branch provider
To connect Split and Sky Air indoor units
to VRV outdoor units
Branch provider

BPMKS967B2

Connectable indoor units


Max. indoor unit connectable capacity
Max. connectable combination
Dimensions
Height x Width x Depth
Weight

BPMKS967B2

mm
kg

BPMKS967B3

1~2

1~3

14.2
71+71

20.8
60+71+71
180x294x350

191

ARGUE CARDS

emura

Daikin Emura
Form. Function. Redesigned

Why choose Daikin Emura?


Unique design. Designed in Europe for Europe.
High seasonal efficiency, further improved
by energy saving techniques like weekly timer
and intelligent eye.
Optimal comfort thanks to advanced
technologies e.g. 2-area intelligent eye,
whisper quiet operation and online controller.

192

Benefits

A remarkable blend between iconic design and


engineering excellence
Stylish design in matt crystal white and silver
Whisper quiet with sound levels down to 19 dBA
Horizontal and vertical autoswing
2-area intelligent eye saves energy by reducing
the set point if nobody is present and directs
airflow away from people, thus avoiding cold
draught
Weekly timer
Online controller:
Always in control no matter where you are

FTXG-LW/S

Wall mounted unit


Design at its best, delivering
superior efficiency and comfort
Seasonal efficiency values up to A+++
Remarkable blend of iconic design and engineering excellence
with an elegant finish in silver and anthracite or in matt crystal
white
Daikin Emura has been awarded with Reddot design award 2014
by an international jury, thanks to its excellent design
Designed to perfectly balance technological leadership and the
beauty of aerodynamics
Online controller (optional): control your indoor from any location
with an app, via your local network or internet
Whisper quiet in operation: the operating of the unit can hardly
be heard. The sound pressure level goes down to 19dBA!

FTXG-LW

FTXG-LS

Indoor Units

ARC466A1

Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate

Unit
Unit
Type
Cooling
Heating

Cooling
Heating
Sound pressure level Cooling

HeightxWidthxDepth

High/Nom./Low/Silent
operation

m/min

High/Nom./Low/Silent
operation

m/min

Sound power level

Heating
Control systems
Power supply

FTXG
mm
kg

High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation

Infrared remote control


Phase / Frequency / Voltage

20LW

20LS

Hz / V

25LS
35LW
35LS
303x998x212
12
Removable / washable / mildew proof

8.9/6.6/4.4/2.6

40/34/28/19

50LW

50LS

10.9/7.8/4.8/2.9

10.9/8.9/6.8/3.6

12.4/9.6/6.9/4.1

12.6/10.5/8.1/5.0

54
56

59
59

60
60

38/32/25/19

45/34/26/20

46/40/35/25

45/37/29/20

47/41/35/25

10.2/8.4/6.3/3.8

dBA
dBA
dBA
dBA

25LW

11.0/8.6/6.3/3.8

41/34/28/19
ARC466A1
1~ / 50 / 220-240

(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.

193

Detailed technical drawings


FTXG20-35LW/S

FTXG50LW/S

194

195
Indoor Units

C/FTXS-K

Wall mounted unit


Discreet, modern design for optimal efficiency and
comfort thanks to 2 area intelligent eye
Discreet, modern design. Its smooth curve blends beautifully

with the wall resulting in an unobtrusive presence that matches


all interior dcors.
High quality matt crystal white finish
Whisper quiet in operation: the operating of the unit can hardly
be heard. The sound pressure level goes down to 19dBA!
Ideal for installation in bedrooms (20,25 class) and larger or
irregular shaped living areas (35,42,50 class)
2 area intelligent eye: air flow is sent to a zone other than where
the person is located at that moment; if no people are detected,
the unit will automatically switch over to the energy-efficient
setting (FTXS35,42,50K)
Online controller (optional): control your indoor from any
location with an app, via your local network or internet

Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate

Unit
Unit
Type
Cooling
Heating

Cooling
Heating
Sound pressure level Cooling

HeightxWidthxDepth

Control systems
Power supply

CTXS15K

ARC466A6

CTXS35K
20K
289x780x215
8

High/Nom./Low/Silent
operation

m/min

7.9/6.3/
4.7/3.9

9.2/7.2/
5.2/3.9

8.8/6.7/
4.7/3.9

High/Nom./Low/Silent
operation

m/min

9.0/7.5/
6.0/4.3
55

10.1/8.1/
6.3/4.3
59

9.5/7.8/
6.0/4.3

Sound power level

Heating

FTXS
mm
kg

C/FTXS-K

High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation

Infrared remote control


Phase / Frequency / Voltage

dBA
dBA
dBA
dBA

42K
50K
298x900x215
11
Removable / washable / mildew proof
9.1/7.0/
11.2/8.5/
11.2/9.1/
11.9/9.6/
5.0/3.9
5.8/4.1
7.0/4.1
7.4/4.5
10.0/8.0/
6.0/4.3
58

58

35K

12.1/9.3/
6.5/4.2

12.4/10.0/
7.8/5.2
59
59

37/31/25/21 42/35/28/21 40/32/24/19 41/33/25/19 45/37/29/19 45/39/33/21

60G
71G
290x1,050x250
12

13.3/10.8/
8.4/5.5

16.0/16.0/
11.3/10.1

17.2/17.2/
11.5/10.5

17.2/14.9/
12.6/11.3

19.5/16.7/
14.2/12.6
63
62

60
60
46/40/34/23

59

45/41/36/33 46/42/37/34

38/33/28/21 41/36/30/21 40/34/27/19 41/34/27/19 45/39/29/19 45/39/33/22 47/40/34/24 44/40/35/32 46/42/37/34


-

Hz / V

25K

ARC466A6

ARC466A9
1~ / 50 / 220-240

ARC452A3

(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.

196

Detailed technical drawings


CTXS15-35K/FTXS20-25K

CTXS15K / FTXS20-25K
Indoor air flow

Minimum space for air passage

30MIN

The ( ) mark shows the piping direction.

Rear side

780

Left side

Right side

50MIN

50MIN

Service space

Required space for service and ventilation

Including mounting plate


Front grille fixing screws
Located inside of the unit

217
215
Signal receiver
Operation lamp

Service space

Nameplate
Liquid pipe 6.4 CuT
The length of the pipe outside the unit is 400mm.

289

Timer lamp
Intelligent Eye lamp

Gas pipe 9.5 CuT


The length of the pipe outside the unit is 350mm.

Indoor unit On/OFF switch


Bottom side

Room temperature sensor


Located inside of the unit

Flap

Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.

Terminal block with earth terminal


Located inside of the unit
Intelligent Eye sensor
Nameplate

780
16

Up/down (automatic)

6
172
47.3

15v

21.5
45v

59.5

Left/right (manual)

59
65 Hole

Hole for embedded piping


65 Hole

5v

v
45

45v

Indoor Units

45v

Fan

47.3

45v

189

106

5v

5v

Signal transmitter

58.5

549

Dry

Heating

289

Cooling

Standard location of holes in the wall

45v

Blade angle

Infrared remote controller


(ARC466A6)

3D092255

FTXS35-42K
FTXS35-42K
/ CTXS35K

Indoor air flow

Minimum space for air passage

30 MIN.

The ( ) mark shows the piping direction.

Rear side

900
Left side

Right side

50 MIN.

50 MIN.

Service space

Service space

Required space for service and ventilation

Including mounting plate

217
215

Front grille fixing screws


Located inside of the unit

Nameplate

Signal receiver
Operation lamp

Liquid pipe 6.4 CuT


The length of the pipe outside the unit is 400mm.

298

Timer lamp
Intelligent Eye lamp

Gas pipe 9.5 CuT


The length of the pipe outside the unit is 350mm.

Indoor unit On/OFF switch


Bottom side

Room temperature sensor


Located inside of the unit

Flap
Auxiliary flap
Located inside of the unit

Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.

Terminal block with earth terminal


Located inside of the unit
Intelligent Eye sensor
Up/down (automatic)

58.5

60v

10v
30v

60v

189

60v

60v

10v

21.5

10v

Fan

60v

65v

Left/right (automatic)

10v
45v

Infrared remote controller


(ARC466A9)

60v

191.5

10v

10v

48

Signal transmitter

900
633

298

10v

Dry

Heating

v
45

66
Hole for embedded piping
65 Hole

106

48

Cooling

14.5

Nameplate

65 Hole

Standard location of holes in the wall

Blade angle

3D092256

197

Detailed technical drawings


FTXS50K

FTXS50K
Indoor air flow

Minimum space for air passage

30 MIN.

The ( ) mark shows the piping direction.

Rear side

900
Left side

Right side

50 MIN.

50 MIN.

Service space

Service space

Required space for service and ventilation

Including mounting plate

217
215

Front grille fixing screws


Located inside of the unit

Nameplate

Signal receiver
Operation lamp

Liquid pipe 6.4 CuT


The length of the pipe outside the unit is 400mm.

298

Timer lamp
Intelligent Eye lamp

Gas pipe 12.7 CuT


The length of the pipe outside the unit is 350mm.

Indoor unit On/OFF switch


Bottom side

Room temperature sensor


Located inside of the unit

Flap
Auxiliary flap
Located inside of the unit

Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.

Terminal block with earth terminal


Located inside of the unit
Intelligent Eye sensor
Up/down (automatic)

58.5

10v
30v

60v

189

60v

60v

10v

21.5

10v

Fan

60v

65v

Left/right (automatic)

10v
45v

Infrared remote controller


(ARC466A9)

60v

191.5

298

60v

900
633

10v

48

Signal transmitter

Dry

Heating
10v

v
45

66
Hole for embedded piping
65 Hole

106

48

Cooling
10v

14.5

Nameplate

65 Hole

Standard location of holes in the wall

Blade angle

3D092257

FTXS60G

198

Detailed technical drawings

Indoor Units

FTXS71G

199

Logo grijs

ARGUE CARDS

The best of two worlds united

Pure comfort
and design

radiant
heat

Why choose Nexura?


Unique radiant heat panel that heats up just like a traditional radiator
Whisper quiet operation down to 19 dBA
Unobtrusive yet stylish design
Reduced air flow, creating an even distribution of air through the room

Comfort is key
Nexura makes your world a comfortable one.
The coolness of a summer breeze or the cosiness of
an extra heat source brings a feeling of well-being
to your living space all year round. Its unobtrusive
yet stylish design with a front panel that radiates
additional heat, its low noise level and reduced air
flow turn your room into a haven.

Benefits

Vertical autoswing
Weekly timer
Guaranteed operation down to -25C (with
RXLG-M)

Radiant heat panel

Online controller

To add even more comfort on cold days,


the aluminium front panel of the Nexura unit has
the capability of warming up, just like a traditional
radiator. The result? A comfortable feeling of warm
air that envelopes you. And all you have to do to
activate this unique feature is push the radiant
button on your remote control.

Always in control, no matter where you are.


Control your indoor from any location
with an app, via your local network or internet.

200

FVXG-K + RXG-L

Floor standing unit with radiant


heat panel
Stylish floor standing unit with radiant heat panel for
comfortable heat and very low noise
The aluminium part of the front panel of the Nexura indoor unit
has the capability of warming up, just like a traditional radiator, to
add even more comfort on cold days
Quiet and discrete, Nexura offers you the best in heating and
cooling, in comfort and design
The indoor unit distributes air at the sound of a whisper. The noise
produced amounts to barely 22dB(A) in cooling and 19dB(A) in
radiant heat mode. In comparison, the ambient sound in a quiet
room amounts to 40dB(A) on average.
Comfortable vertical auto swing ensures draughtfree operation
and prevents ceiling soiling
Online controller (optional): control your indoor from any location
with an app, via your local network or internet
Can be installed against a wall or recessed
Its low height enables the unit to fit perfectly beneath a window

FVXG-K

Indoor Units

ARC466A2

Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate

Unit
Unit
Type
Cooling
Heating

Cooling
Heating
Sound pressure level Cooling

HeightxWidthxDepth

High/Nom./Low/Silent
operation

m/min

High/Nom./Low/Silent
operation

m/min

Sound power level

Heating
Control systems
Power supply

FVXG
mm
kg

High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation/Radiant heat

Infrared remote control


Phase / Frequency / Voltage

dBA
dBA
dBA
dBA

Hz / V

25K

35K
600x950x215
22
Removable / washable / mildew proof

50K

8.9/8.9/5.3/4.5

9.1/9.1/5.3/4.5

10.6/10.3/7.3/6.0

10.2/8.0/5.8/5.0

12.2/10.0/7.8/6.8

9.9/7.8/5.7/4.7
52
53

58
60

38/32/26/23

39/33/27/24

44/40/36/32

39/32/26/22/19

40/33/27/23/19

46/40/34/30/26

ARC466A2
1~ / 50 / 220-240

(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.

201

Detailed technical drawings


FVXG25-35K

FVXG50K

202

FVXS-F + RXS-L(3)

Floor standing unit


Floor standing unit for optimal heating comfort thanks to
dual airflow
Its low height enables the unit to fit perfectly beneath a window
Can be installed against a wall or recessed
Vertical auto swing moves the discharge flaps up and down for
efficient air and temperature distribution throughout the room
Online controller (optional): control your indoor from any location
with an app, via your local network or internet

FVXS-F

Indoor Units

ARC452A1

Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate

Unit
Unit
Type
Cooling
Heating

Cooling
Heating
Sound pressure level Cooling

HeightxWidthxDepth

High/Nom./Low/Silent
operation

m/min

High/Nom./Low/Silent
operation

m/min

Sound power level

Heating
Control systems
Power supply

FVXS
mm
kg

High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation

Infrared remote control


Phase / Frequency / Voltage

dBA
dBA
dBA
dBA

Hz / V

25F

35F
600x700x210
14
Removable / washable / mildew proof

50F

8.2/8.2/4.8/4.1

8.5/8.5/4.9/4.5

10.7/10.7/7.8/6.6

8.8/6.9/5.0/4.4

9.4/7.3/5.2/4.7

11.8/10.1/8.5/7.1

52
52

60
60

38/32/26/23

39/33/27/24

44/40/36/32

38/32/26/23

39/33/27/24

45/40/36/32

ARC452A1
1~ / 50 / 220-240

(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.

203

Detailed technical drawings


FVXS25-35F
FVXS25-35F

unit (mm)

666 (half concealed)


Operation lamp

Note) 1. The mark (Y) shows piping direction


Front panel fixed screws
(inside)

Timer lamp

Room temp. thermistor

Signal receiver

Terminal block with earth


terminal

Indoor unit ON/OFF switch

Model name label

Main unit fixing screw

Air outlet
selection
switch
(Inside)

95 (Half concealed)

Signal transmitter

Gas pipe (J9.5 CuT)

584 (half concealed)

Name plate

Liquid pipe (J6.4 CuT)

Drain
socket

Front panel fixed screws


Drain hose

Hole for splint


Hole for piping

Hole for piping

Infrared remote control

85

Air flow

Adjusting the air flow direction

Required space

Hole for piping

For performance
50 MIN

(for
maintenance)

(for
performance)

Up/down (automatic)
Cool, dry
Cooling
/ dry
Heat
(Heat pump model)

Right/left (manual)
Upper air outlet

(Wall hole)

(Wall hole)

50 MIN

Hole for splint

VP20
I.D. J20
O.D. J26
L 220

Main unit fixed screws

Upward air flow


limit (OFF)

Lower air outlet


Upward air flow
limit (ON)

Wall hole for half concealed

3D056135A

FVXS50F
FVXS50F

unit (mm)

666 (half concealed)


Operation lamp

Note) 1. The mark (Y) shows piping direction

Timer lamp

Room temp. thermistor

Signal receiver

Terminal block with earth


terminal

Indoor unit ON/OFF switch

Front panel fixed screws


(inside)

Model name label

Main unit fixing screw

Air outlet
selection
switch
(Inside)

95 (Half concealed)

Signal transmitter

Gas pipe (J12.7 CuT)

584 (half concealed)

Name plate

Liquid pipe (J6.4 CuT)

Drain
socket

Front panel fixed screws


Drain hose

Hole for splint


Hole for piping

Hole for piping

For performance
50 MIN
(for
performance)

Right/left (manual)
Upper air outlet

(Wall hole)

(Wall hole)

50 MIN
(for
maintenance)

Hole for splint


Hole for piping

Infrared remote control


Adjusting the air flow direction

Required space

Up/down (automatic)
Cooling / dry Cool, dry
Heat
(Heat pump model)
Upward air flow
limit (OFF)

Lower air outlet


Upward air flow
limit (ON)

Wall hole for half concealed

204

VP20
I.D. J20
O.D. J26
L 220

85

Air flow

Main unit fixed screws

3D056136A

FLXS-B(9) + RXS-L(3)

Flexi type unit


Flexible unit, ideal for rooms without false ceiling, can fit
on either ceiling or wall
Can fit on either ceiling or lower wall; its low height enables the
unit to fit beneath a window
Vertical auto swing moves the discharge flaps up and down for
efficient air and temperature distribution throughout the room
Home leave operation maintains the indoor temperature at your
specified comfort level during absence, thus saving energy
Online controller (optional): control your indoor from any location
with an app, via your local network or internet

FLXS-B(9)

Indoor Units

ARC433B67

Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate

HeightxWidthxDepth

High/Nom./Low/Silent
operation

m/min

Heating

High/Nom./Low/Silent
operation

m/min

Cooling
Heating
Sound pressure level Cooling
Heating

25B

35B9

50B

60B

490x1,050x200
16

17
Removable / washable / mildew proof

Sound power level

Control systems
Power supply

FLXS
mm
kg

Unit
Unit
Type
Cooling

High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation

Infrared remote control


Phase / Frequency / Voltage

dBA
dBA
dBA
dBA

7.6/7.6/6.0/5.2

8.6/7.6/6.6/5.6

11.4/11.4/8.5/7.5

12.0/10.7/9.3/8.3

9.2/8.3/7.4/6.6

12.8/10.4/8.0/7.2

12.1/9.8/7.5/6.8

12.8/10.6/8.4/7.5

51
51

53
59

59

37/34/31/28

38/35/32/29

47/43/39/36

48/45/41/39

37/34/31/29

46/36/33/30

46/41/35/33

47/42/37/34

1~ / 50/60 / 220-240/220-230

1~ / 50 / 220-240

60

ARC433B67
Hz / V

1~ / 50/60 / 220-240/220-230

(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.

205

Detailed technical drawings


FLXS25-35B(9)

FLXS50-60B

206

Detailed technical drawings

Indoor Units

FLXS25-35B(9)

FLXS50-60B

207

Hot water
Efficient hot water production for underfloor
heating, radiators and air handling units, or
for producing hot water for sinks, baths and
showers. Integrating heat recovery into the
VRV system means that the production of hot
water is virtually free.

208

Hot water
Low temperature hydrobox
HXY-A8210


High temperature hydrobox
HXHD-A8212
215

Hot Water

Accessories for hot water

Hydrobox range
Capacity class (kW)
Type

Product name

Model

HXY-A8

Ideal for hot or cold water in underfloor loops, air handling units, low temperature
radiators
Hot/cold water from 5 to 45C
Large operation range (down to -20C and up to 43C)
Fully integrated water-side components save time on system design
Space saving contemporary wall hung design

HXHD-A8

Ideal for sanitary hot water (e.g. bathrooms, sinks) and space heating (e.g. underfloor
heating, radiators, air handling units)
Hot water from 25 to 80C
"Free" heating and hot water through heat recovery
Uses heat pump technology to produce hot water efficiently, providing up to 17%
savings compared to a gas boiler
Possibility to connect thermal solar collectors

80

125

Leaving water
temperature range

5 C - 45 C

25 C - 80 C

For high efficiency space heating and cooling

Low
temperature
hydrobox

For efficient hot water production and space heating

High
temperature
hydrobox

209

HXY-A8

Low temperature hydrobox


for VRV
For high efficiency space heating and cooling
Air to water connection to VRV for applications such as underfloor,
air handling units, low temperature radiators,
Leaving water temperature range from 5C to 45C without
electric heater
Super wide operating range for hot/cold water production from
-20 to +43C ambient outdoor temperature
Saves time on system design as all water-side components are
fully integrated with direct control over leaving water temperature
Space saving contemporary wall hung design
No gas connection or oil tank needed
Connectable to VRV IV heat pump and heat recovery
HXY-A8

Liquid pipe
Gas pipe
F1, F2 communication
Hot/cold water

VRV indoor units

Air handling unit

Low temp. radiator

VRV IV heat pump


VRV IV heat recovery

Under floor heating

Indoor unit
Cooling capacity
Heating capacity
Dimensions
Weight
Casing
Operation range

Nom.
Nom.
Unit
Unit
Colour
Material
Heating
Domestic hot
water

Refrigerant
Refrigerant circuit
Water circuit
Power supply
Current

Ambient
Water side
Ambient
Water side

Type / GWP
Gas side diameter
Liquid side diameter
Piping connections diameter
Phase/Frequency/Voltage
Recommended fuses

Contains fluorinated greenhouse gases

210

HeightxWidthxDepth

Min.~Max.
Min.~Max.
Min.~Max.
Min.~Max.

HXY
kW
kW
mm
kg

C
C
CDB
C
mm
mm
inch
Hz/V
A

080A8
8.0
9.00

125A8
12.5
14.00
890x480x344
44
White
Precoated sheet metal
-20~24
25~45
N/A
N/A
R-410A / 2.087,5
15.9
9.5
G 11/4 (female)
1~/50/220-240
6~16

Detailed technical drawings


HXY-A8
HXY-A8

Required space for service and ventilation

Holes (12) for fixation to the wall


Water out connection (1-1/4 F BSP)
Water in connection (1-1/4 F BSP)
Refrigerant liquid connection 9.52 (flare)
Refrigerant suction connection 15.9 (flare)
Pump
User interface
Safety valve (pressure)
Air purge
Expansion vessel
Pressure gauge
Heat exchanger (refrigerant / water)
Shut off valve with drain / fill valve (1-1/4 F BSP) (included accessory)
Water filter
Power supply / Communication wire entrance

HXY-A8

Service door

3D079938

90
85
80

HXY-A8 75
70

ESP (kPa)

HXY-A8

65
95
60
90
55
85
50
80
45
75
40

ESP (kPa)

70
35
65
30
60
25
55

15

17.5

20

22.5

25

27.5

30

32.5

35

37.5

40

30

32.5

35

37.5

40

Flow (l/min)

50
45
40

35
30
25
15

17.5

20

22.5

25

27.5

Flow (l/min)

3D097625

211

Hot Water

Switchbox terminals

95

HXHD-A8

High temperature hydrobox


for VRV
For efficient hot water production and space heating
Air to water connection to VRV for applications such as bathrooms,
sinks, underfloor heating, radiators and air handling units
Leaving water temperature range from 25 to 80C without electric heater
Free heating and hot water production provided by transferring heat
from areas requiring cooling to areas requiring heating or hot water
Uses heat pump technology to produce hot water efficiently,
providing up to 17% savings compared to a gas boiler
Possibility to connect thermal solar collectors to the domestic hot
water tank
Super wide operating range for hot water production from -20 to
+43C ambient outdoor temperature
Saves time on system design as all water-side components are
fully integrated with direct control over leaving water temperature
Various control possibilities with weather dependant set point or
thermostat control
The indoor unit and domestic hot water tank can be stacked to
save space, or installed next to each other, if only limited height is
available

HXHD-A8

EKHWP-B

EKHWP-B

No gas connection or oil tank needed


Connectable to VRV IV heat recovery

45C - 75C
Daikin
solar panel

Domestic hot water

25C - 75C
VRV indoor units

BS-Box

Air handling unit

Domestic hot
water tank
45C - 75C

BS-Box

Low temp. radiator

Heating only
hydrobox for VRV

VRV heat recovery


(REYQ8-54T)

Under floor heating


25C - 35C

45C - 75C
Daikin
solar panel

Domestic hot water

25C - 75C
Air handling unit

Domestic hot
water tank
45C - 75C

Water Cooled VRV IV


RWEYQ-T8
(special order unit)
Heating only
hydrobox for VRV

Liquid pipe
Gas pipe
Discharge gas pipe
F1, F2 communication
Hot water
Indoor unit
Heating capacity
Dimensions
Weight
Casing

Nom.
Unit
Unit
Colour
Material
Sound pressure level Nom.
Night quiet mode
Operation range
Heating
Domestic hot
water
Refrigerant
Refrigerant circuit
Water circuit
Power supply
Current

Under floor heating


25C - 35C

HeightxWidthxDepth

Level 1
Ambient
Water side
Ambient
Water side

Type / GWP
Gas side diameter
Liquid side diameter
Piping connections diameter
Heating water system
Water volume
Phase/Frequency/Voltage
Recommended fuses

Min.~Max.
Min.~Max.
Min.~Max.
Min.~Max.

Max.~Min.

HXHD
kW
mm
kg

dBA
dBA
C
C
CDB
C
mm
mm
inch
l
Hz/V
A

(1) Sound levels are measured at: EW 55C; LW 65C (2) Sound levels are measured at: EW 70C; LW 80C (3) Field setting (4) Contains fluorinated greenhouse gases

212

Low temp. radiator

125A8
14.0
705x600x695
92
Metallic grey
Precoated sheet metal
42 (1) / 43 (2)
38 (1)
-20~20 / 24 (3)
25~80
-20~43
45~75
R-134a / 1.430
12.7
9.52
G 1 (female)
200~20
1~/50/220-240
20

Detailed technical drawings


HXHD-A8
HXHD-A

If required (e.g. Wall xation)


Pressure gauge can be removed from waterlter, maximum distance
between waterlter and pressure gauge 600 mm

Detail A
Scale 1/3

Left Installation

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

Right installation

Remote control (delivered as accessory)


Installation location is outside the unit
Discharge pipe connection 12.7 solder (R410a)
Liquid pipe connection 9.5 solder (R410a)
R134a Service ports 5/16 are (2x)
Pressure gauge
Blow off valve
Drain valve water circuit
Air purge
Shut-off valves (2x)
Water lter
Water in connection G 1 (female)
Water out connection G 1 (female)
Control wiring intake (knock-out hole 37)
Power supply wiring intake (knock-out hole 37)
Knock-out holes for refrigerant piping and water piping
Levelling feet
Discharge stop valve 12.7 solder (R410a)
Liquid stop valve 9.5 solder (R410a)

3TW59914-1B(1)

HXHD-A8
HXHD-A

Left Installation

Upwiring

Right installation

Screw xation of top plate


(both sides)

Model
HXHD-A8

A
355

B
270

C
300

Min. 600
(Space required for switch box removal)

3TW59914-1B(2)

213

Hot Water

Detail A

Detailed technical drawings


HXHD-A

ESP [kPa]

HXHD-A8

120
110
100
90
80
70
60
50
40
30
20
10
0
5

11

13

15

17

19

21 23 25
Flow [l/min]

27

29

31

33

35

37

39

41

3D097621

214

EKHTS-AC

Domestic hot water tank


Stackable stainless steel domestic hot water tank
The indoor unit and domestic hot water tank can be stacked to
save space, or installed next to each other, if only limited height is
available
Available in 200 and 260 liters
Heat loss is reduced to a minimum thanks to the high quality
insulation
At necessary intervals, the indoor unit can heat up the water to
60C to prevent the risk of bacteria growth
Efficient temperature heat-up: from 10C to 50C in only 60
minutes

Dimensions

Weight
Tank

Heat exchanger

EKHTS
Colour
Material
Unit

EKHTS260AC

200AC

260AC
Metallic grey
Galvanised steel (precoated sheet metal)

Height

Integrated on
indoor unit

mm

Width
Depth
Empty

Unit
Water volume
Material
Maximum water temperature
Insulation
Heat loss
Quantity
Tube material
Face area
Internal coil volume

2,010

mm
mm
kg
l

2,285
600
695

70
200

78
260
Stainless steel (EN 1.4521)
75

C
kWh/24h

1.2

1.5
1
Duplex steel (EN 1.4162)
1.56
7.5

m
l

Hot Water

Accessory
Casing

EKHTS200AC

EKHWP-B/PB

Domestic hot water tank


Plastic domestic hot water tank with solar support
Available in 300 and 500 liters
Large hot water storage tank to provide domestic hot water at any
time
Heat loss is reduced to a minimum thanks to the high quality
insulation
Space heating support possible (500l tank only)
Tank designed for connection with pressured thermal solar system

EKHWP300B-PB

Pressured
Accessory
Dimensions
Weight
Tank

Heat exchanger

Unit

Width
Depth
Empty

Unit
Water volume
Maximum water temperature
Insulation
Heat loss
Domestic hot
Tube material
water
Face area
Internal coil volume
Operating pressure
Average specifc thermal output
Charging
Tube material
Face area
Internal coil volume
Operating pressure
Average specifc thermal output
Auxiliary solar
Tube material
heating
Face area
Internal coil volume
Operating pressure
Average specifc thermal output

EKHWP
mm
mm
kg
l
C
kWh/24h
m
l
bar
W/K
m
l
bar
W/K
m
l
bar
W/K

300PB
595
615
58
294

Unpressured
500PB
790
790
89
477

300B
595
615
59
300

500B
790
790
93
500

85
1.5
1.7
Stainless steel (DIN 1.4404)
5.600
5.800
27.1
29.0
6
2,790
2,825
Stainless steel (DIN 1.4404)
3
4
13
19
3
1,300
1,800
Stainless steel (DIN 1.4404)
1
2
280

1.3

1.4
Stainless steel

5.8
27.9

6
29
6

2,790

2,900
Stainless steel

2.7
13.2

3.8
18.5
3

1,300

1,800
Stainless steel

3
-

0.5
2.3
280

215

EKSRPS4A

Pump station
Save energy and reduce CO2 emissions with a solar system for
domestic hot water production
Pump station connectable to unpressurised solar system
Pump station and control provide the transfer of solar heat to the
domestic hot water tank

EKSRPS4

Pump station for pressureless tank


Dimensions
Unit
Weight
Unit
Power supply
Phase
Frequency
Voltage

HeightxWidthxDepth

EKSRPS4A
815x142x230
6
1~
50
230

mm
kg
Hz
V

EKS(V/H)-P

Solar collector
Thermal solar collector for hot water production
Solar collectors can produce up to 70% of the energy needed for
hot water production - a major cost saving
Vertical and horizontal solar collectors for domestic hot water
production
High efficiency collectors transfer all the short-wave solar radiation
into heat as a result of their highly selective coating
Easy to install on roof tiles

EKSV21P

EKSH26P

Solar collector
Mounting
Dimensions
Weight
Volume
Surface

Coating
Absorber
Glazing
Allowed roof angle
Operating pressure
Stand still temperature
Thermal performance

216

EKSV21P
Unit
Unit

HeightxWidthxDepth

Outer
Aperture
Absorber

Min.~Max.
Max.
Max.
collector efficiency (col)
Zero loss collector efficiency 0
Heat loss coefficient a1
Temperature dependence of the heat loss coefficient a2
Thermal capacity

mm
kg
l
m
m
m

bar
C
%
%
W/m.K
W/m.K
kJ/K

EKSV26P

EKSH26P
Horizontal
2,000x85x1,300

Vertical
1,006x85x2,000
33
1.3
2.01
1.800
1.79

42
1.7

2.1
2.60
2.360
2.35
Micro-therm (absorption max. 96%, Emission ca. 5% +/-2%)
Harp-shaped copper pipe register with laser-welded highly selective coated aluminium plate
Single pane safety glass, transmission +/- 92%
15~80
6
192
61
0.781
0.784
4.240
4.250
0.006
0.007
4.9
6.5

217
Hot Water

Biddle air curtains


Biddle air curtains provide highly efficient
solutions for retailers and consultants to
combat the issue of climate separation across
their outlet or office doorway.

218

Biddle air curtains

Biddle air curtains


connected to Daikin Heat Pumps
Open Door Trading

High efficiency and low


CO2 emission

Although the customer friendly aspects of open


door trading are widely appreciated by retail and
commercial outlet managers, open doors can also
give rise to massive losses in conditioned warm
or cold air and hence, energy. Biddle air curtains
however, not only preserve indoor temperatures and
generate significant economies, they also represent
an invitation for customers, to enter a pleasant
trading and working environment.

An efficient outdoor/indoor climate separation limits


heat loss through the door opening and enhances
the efficiency of the air conditioning system.
Combining Biddle air curtains with Daikin heat
pumps can lead to savings up to 72% compared to
electric air curtains and a paypack period of less than
1.5 years!

Air curtain size selector


Door height (m)

2.5

2.4

2.15

2.75
2.0

2.3

2.5

Favourable

Normal

Unfavourable

Covered shopping mall or

No opposite open doors,

Location at a corner or

revolving door entrance

little direct wind, building

square, multiple floors and/

with ground floor only

or open stairwell

Biddle Air Curtains

3.0
2.3

Biddle comfort air curtian nomenclature


CYVS150DK80FSC
Controller (standard)
Color. B=White (RAL6010), S: Grey (RAL9006)
Installation type: F=Freehanging, C=Cassette, R=Recessed
Capacity class (kW)
Daikin direct expansion
Door width (cm)
Range. S=small, M=Medium, L=Large, XL= Extra Large
Connectable to VRV
Biddle comfort air curtain

Portfolio
Type

Product name

Biddle air curtain free hanging

CYV S/M/L-DK-F

Biddle air curtain cassette

CYV S/M/L-DK-C

Biddle air curtain recessed

CYV S/M/L-DK-R

A payback time of less than 1.5 years compared to


electrical air curtains
Easy and quick installation
Maximum energy efficiency thanks to rectifier
technology
85% air separation efficiency
Cassette model (C): mounted into a false ceiling
enhancing aesthetics
Free-hanging model (F): easy wall mounted
installation
Recessed model (R) : neatly concealed in the ceiling
219

CYVS/M/L-DK-F/C/R

Biddle air curtain for VRV

Packtime of lessthan 1.5 years

electric air curtain


12000
10000

total cost
(installation + running cost) in

Connectable to VRV heat recovery and heat pump


VRV is among the first DX systems suitable for
connection to air curtains
Free-hanging model (F): easy wall mounted
installation
Cassette model (C): mounted into a false ceiling
leaving only the decoration panel visible
Recessed model (R): neatly concealed in the ceiling
Provides virtually free air curtain heating via
recovered heat from indoor units in cooling mode
(in case of VRV heat recovery)
Easy and quick to install at reduced costs since
no additional water sytems, boilers and gas
connections are required
PATENTED TECHNOLOGY: Maximum energy efficiency
stemming from almost zero down flow turbulence,
optimised air flow and the application of advanced
discharge rectifier technology
Around 85% air separation efficiency, greatly
reducing both heat loss and required indoor unit
heating capacity

8000
Daikin heat pump
with Biddle air curtain*

6000
4000
2000
0
1

years

VRV
Network Solution

Biddle comfort
air curtain (CY)
Integration in a VRV total solution

* Payback period and gains calculated based upon the following: Air curtain is 9hrs/day 156 days year (1,404 hrs/year) in use. Annual energy consumption for an electric air
curtain: 3,137EUR (COP = 0.95). Typical installation cost: 1,000EUR; Typical equipment cost: 2,793EUR. Annual energy consumption for CYQS200DK100FBN and ERQ100AV: 748EUR
(COP 4.00). Typical installation cost: 2,000EUR; Typical equipment cost: 5,150EUR. Calculation based upon electricity cost: 0,1705EUR /kWh

220

Biddle air curtain for VRV

CYVM150DK80CSN

CYVM150DK80RSN

Small

Heating capacity
Power input
Delta T
Casing
Dimensions

Speed 3
Fan only
Heating
Speed 3
Colour
Unit

Nom.
Nom.

Height F/C/R
Width F/C/R
Depth F/C/R

Required ceiling void >


Door height
Max.
Door width
Max.
Weight
Unit
Fan-Air flow rate
Heating
Speed 3
Sound pressure level
Heating
Speed 3
Refrigerant
Type / GWP
Piping connections
Liquid/OD/Gas/OD
Required accessories (should be ordered separately)
Power supply
Voltage

kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m/h
dBA
mm
V

Medium

CYVS100DK80
*BN/*SN

CYVS150DK80
*BN/*SN

CYVS200DK100
*BN/*SN

7.40
0.23
0.23
19

9.0
0.35
0.35

11.6
0.46
0.46

CYVS250DK140
*BN/*SN

CYVM100DK80
*BN/*SN

CYVM150DK80
*BN/*SN

CYVM200DK100
*BN/*SN

CYVM250DK140
*BN/*SN

16.2
9.2
11.0
13.4
19.9
0.58
0.37
0.56
0.75
0.94
0.58
0.37
0.56
0.75
0.94
15
16
17
14
13
15
BN: RAL9010 / SN: RAL9006
270/270/270
1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548
590/821/561
420
2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3)
1.0
1.5
2.0
2.5
1.0
1.5
2.0
2.5
56
66
83
107
57
73
94
108
1,164
1,746
2,328
2,910
1,605
2,408
3,210
4,013
47
49
50
51
50
51
53
54
R-410A / 2.087,5
9.52/16.0
9.52/19.0
9.52/16.0
9.52/19.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230
Large

Heating capacity
Power input
Delta T
Casing
Dimensions

Speed 3
Fan only
Heating
Speed 3
Colour
Unit

Nom.
Nom.

Height F/C/R
Width F/C/R
Depth F/C/R

Required ceiling void >


Door height
Max.
Door width
Max.
Weight
Unit
Fan-Air flow rate
Heating
Speed 3
Sound pressure level
Heating
Speed 3
Refrigerant
Type / GWP
Piping connections
Liquid/OD/Gas/OD
Required accessories (should be ordered separately)
Power supply
Voltage

kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m/h
dBA
mm
V

CYVL200DK250*BN/*SN
CYVL250DK250*BN/*SN
29.4
31.1
1.50
1.88
1.50
1.88
15
14
12
BN: RAL9010 / SN: RAL9006
370/370/370
1,000/1,000/1,048
1,500/1,500/1,548
2,000/2,000/2,048
2,500/2,500/2,548
774/1,105/745
520
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
1.0
1.5
2.0
2.5
76
100
126
157
3,100
4,650
6,200
7,750
53
54
56
57
R-410A / 2,087.5
9.52/16.0
9.52/19.0
9.52/22.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230

CYVL100DK125*BN/*SN
15.6
0.75
0.75

CYVL150DK200*BN/*SN
23.3
1.13
1.13

(1) Favorable conditions: covered shopping mall or revolving door entrance (2) Normal conditions: little direct wind, no opposite open doors, building with ground floor only (3) Unfavorable conditions: location at a corner or square, multiple floors and/or
open stairway

221

Biddle Air Curtains

CYVM150DK80FSC

Detailed technical drawings


CYVS_DK_FBN/FSN / CYVM_DK_FBN/FSN / CYVL_DK_FBN/FSN
CYVS_DK_FBN/FSN
CYVM_DK_FBN/FSN
CYVL_DK_FBN/FSN

500
250

250

40

100

197

O9.2

Suction grid
with filter

98

27

Type
CYVS-DK-FBN/FSN
CYVM-DK-FBN/FSN
CYVL-DK-FBN/FSN

L
1,000 - 1,500
2,000 - 2,500
1,000 - 1,500
2,000 - 2,500

270

590

93

171

119

370

774

124.5 245.5

200

CU0954X-000

REMARKS

The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.

CYVS_DK_CBN/CSN / CYVM_DK_CBN/CSN / CYVL_DK_CBN/CSN


CYVS_DK_CBN/CSN
CYVM_DK_CBN/CSN
CYVL_DK_CBN/CSN

500
250

250
40

100

197

O9.2

The finishing profiles are


supplied separately.
Suction grid
with filter

98

27

Screw-eye M6

Number of suction grids per device

CYVL-DK-CBN/CSN

270

821

93

171

119

250

411

260

L
1,000 - 1,500
2,000 - 2,500
1,000 - 1,500
2,000 - 2,500

Type
CYVS-DK-CBN/CSN
CYVM-DK-CBN/CSN

*1 drain grid per device

Suction grid length


1,000 / 1,500
1,000 / 1,250

370

1,105 124.5 245.5

200

181.5 563.5

Device length Number


1000 / 1500
1
2000 / 2500
2

360

REMARKS

222

The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.

The mounting holes for finishing profiles in a lowered ceiling (L+8) x (D+8) mm

CU0955X-000

Detailed technical drawings


CYVS_DK_RBN/RSN / CYVM_DK_RBN/RSN / CYVL_DK_RBN/RSN
CYVS_DK_RBN/RSN
CYVM_DK_RBN/RSN
CYVL_DK_RBN/RSN

500
250

No ducts are supplied

250

40

100

197

O9.2

No ducts are supplied

The finishing profiles are


supplied separately.
K

Suction grid
with filter

98

1500

2000

2500

10

12

101.5

1000

Number of suction grids per device


Number
1
2

*1 drain grid per device

Suction grid length


1,000 / 1,500
1,000 / 1,250

Type
L
H
CYVS-DK-RBN/RSN
CYVM-DK-RBN/RSN 1,000 - 1,500 270
2,000 - 2,500
CYVL-DK-RBN/RSN 1,000 - 1,500
2,000 - 2,500 370

561

80125

90

171

119

92

139

260

745

80125 121.5 245.5 200 123.5 170

360

T
1048-1548
20482548
1048-1548
1044-1544
408 250 2044-2544 20482548
308 160 1044-1544
2044-2544

Device length
1000 / 1500
2000 / 2500

Type
CYVS-DK-RBN/RSN
CYVM-DK-RBN/RSN
CYVL-DK-RBN/RSN

Number of ducts per device

27

L
M

CU0956X-000

The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.

Holes (for finishing profiles) - drain (L+8) x (E+8) mm - suction (L+8) x (G+8) mm.

Biddle Air Curtains

REMARKS

223

Ventilation
& air handling
Daikin offers the widest range in DX
ventilation in the market.
With a variety of ventilation solutions from
small heat recovery ventilation to large scale
air handling units we help provide a fresh,
healthy and comfortable environment in
offices, hotels, stores and other commercial
environments.

224

Ventilation
& air handling
Ventilation
Heat reclaim ventilation
VAM-FC228
VKM-GB(M)240

Air handling applications


Overview & control possibilities
253
VRV254
ERQ255
Expansion valves and control boxes
256

Ventilation & Air Handling

NEW

225

Which system offers me the best solution?

Ventilation
Energy
recovery

Five components of
indoor air quality

Humidification

Ventilation: ensures the provision of fresh air


Energy recovery: recovers heat and moisture

Air
processing

from the outgoing air to maximise comfort


and efficiency
Air processing: Pre-heats or pre-cools incoming
fresh air maximising comfort and minimising the
load on the air conditioning installation
Humidification: optimises the balance between
indoor and outdoor humidity
Filtration: removes dust, pollution and odours
from the air

Filtration

Air flow rate (m3/h)


Type Product name

Model

PG

200

400 600

800 1,000 2,000 4,000 10,000 25,000

140,000

Components of
indoor air quality

VAM-FC

Heat reclaim
ventilation

VKM-GB

Air Handling
Unit (application)

VKM-GBM

DX total fresh air


package

Ventilation with heat recovery as standard


Energy saving ventilation
Maximise floor space for furniture,
decoration and fittings
Free cooling
Reduced energy consumption
thanks to DC inverter fan motor
Optional CO2 sensor saves energy
while improving indoor air quality

Pre heating or cooling of fresh air for


lower load on the air conditioning system
Energy saving ventilation
Creates a high quality indoor environment
Maximise floor space for furniture,
decoration and fittings
Free cooling
Reduced energy consumption
thanks to DC inverter fan motor

Pre heating, cooling and humidification


for optimum comfort
Energy saving ventilation
Creates a high quality indoor environment
Balance your indoor humidity level
Maximise floor space for furniture,
decoration and fittings
Free cooling

Fully customised solution for


ventilation and air handling
Inverter technology
Heat pump and heat recovery
Provides virtually free heating
Room temperature via Daikin control
Large range of expansion valve kits

Daikin AHU connected to Daikin chiller solution

226

Ventilation
Energy recovery

228

Ventilation
Energy recovery
Air processing

240

Ventilation
Energy recovery
Air processing
Humidification
240

251

(1)

Ventilation
Energy recovery
Air processing
Humidification
Filtration

Ventilation

VAM - HEAT RECLAIM VENTILATION

Ventilation & Air Handling

DAIKIN AIR HANDLING UNIT AND ERQ/VRV PLUG & PLAY CONNECTION

227

VAM-FC

Heat reclaim ventilation

Clean outdoor air

Total heat
exchanged
foul air

Ventilation with heat recovery as standard


Energy saving ventilation using indoor heating, cooling and
moisture recovery
Ideal solution for shops, restaurants or offices requiring maximum
floor space for furniture, decorations and fittings
Free cooling possible when outdoor temperature is below indoor
temperature (eg. during nighttime)
Reduced energy consumption thanks to specially developed DC
fan motor
Prevent energy losses from over-ventilation while maintaining
indoor air quality with optional CO2 sensor
Can be used as stand alone unit or integrated in the VRV system
Wide range of units: air flow rate from 150 up to 2,000 m/h
High efficiency filters available in M6 ,F7, F8 grades
Shorter installation time thanks to easy adjustment of nominal
air flow rate, so less need for dampers compared with traditional
installation.
Specially developed heat exchange element with High Efficiency
Paper (HEP)
No drain piping needed
Can operate in over- and under pressure
Total solution for fresh air with Daikin supply of both VAM and
electrical heaters

Foul indoor air

Total heat
exchanged
clean air

High efficiencies filters available


in M6, F7, F8 grades

Prevent energy losses from over ventilation with CO2 sensor


Enough fresh air is needed to create an enjoyable environment, but ventilating constantly is leading to energy waste. Therefore an optional
CO2 sensor can be installed which throttles or even switches off the ventilation system when there is enough fresh air in the room, thus
saving energy.

Example of CO2 sensor operation in a meeting room:

9 AM

12 PM

5 PM

Decrease in air volume and more energy


saving compared to fixed ventilation rate

Increase in air
volume and
better comfort
compared to fixed
ventilation rate

10

When many people are in the room,


more fresh air is brought in to maintain
comfortable CO2 levels. When fewer
people are in the room, energy is saved
by bringing in less fresh air.

11

Morning meeting

12

13

Lunch time

14

15

16

Meeting

17

18

19

hour

CO2 level
Fixed ventilation rate
Ventilation amount

Using CO2 sensors has the most energy-saving potential in buildings where occupancy fluctuates during a 24-hour period, is unpredictable and peaks at a high level. For example
office buildings, government facilities, retail stores and shopping malls, movie theaters, auditoriums, schools, entertainment clubs and nightclubs. The ventilation unit's reaction to
fluctuations in CO2 can be easily adjusted through a field setting.

228

Heat recovery ventilation

High Efficiency Paper


OUTDOOR

Operation of the high


efficiency paper.

INDOOR

30.6C
62% RH

Cross flow of air to

32C
70% RH

exchange heat and


moisture.

SA
27.4C
63% RH

RA
26C
50% RH

Integrally-formed liner

Temperature
and humidity is
exhanged between
the layers

SA

RA

Ventilation
Power input - 50Hz
Temperature
exchange efficiency
- 50Hz
Enthalpy exchange
efficiency - 50Hz

Heat exchange mode Nom.


Bypass mode
Nom.
Ultra high
High
Low
Cooling
Ultra high
High
Low
Heating
Ultra high
High
Low

Ultra high
Ultra high

Operation mode
Heat exchange system
Heat exchange element
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Heat exchange mode Ultra high
Fan-Air flow rate 50Hz
Bypass mode
Ultra high
Fan-External static
Ultra high/High/Low
pressure - 50Hz
Air filter
Type
Sound pressure level Heat exchange mode Ultra high
- 50Hz
Bypass mode
Ultra high
Operation range
Min./Max.
Relative humidity
Refrigerant
Type / GWP
Connection duct diameter
Power supply
Phase/Frequency/Voltage
Current
Maximum fuse amps (MFA)

VAM
kW
kW
%
%
%

mm
kg
m/h
m/h
Pa

dBA
dBA
CDB
%
mm
Hz/V
A

150FC
0.132
0.132
77.0 (2) / 72.0 (3)
78.3 (2) / 72.3 (3)
82.8 (2) / 73.2 (3)
60.3 (2)
61.9 (2)
67.3 (2)
66.6 (2)
67.9 (2)
72.4 (2)

250FC
0.161
0.161
74.9 (2) / 69.5 (3)
76.0 (2) / 70.0 (3)
80.1 (2) / 72.0 (3)
60.3 (2)
61.2 (2)
64.5 (2)
66.6 (2)
67.4 (2)
70.7 (2)

350FC
500FC
650FC
800FC
1000FC
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
78.0 (2) / 71.6 (3) 77.0 (2) / 70.2 (3) 77.0 (2) / 69.8 (3) 77.0 (2) / 67.8 (3) 78.0 (2) / 70.2 (3)
79.3 (2) / 71.9 (3) 78.8 (2) / 70.7 (3) 79.1 (2) / 71.2 (3) 78.2 (2) / 68.8 (3) 78.6 (2) / 71.1 (3)
84.1 (2) / 73.0 (3) 80.9 (2) / 71.3 (3) 81.1 (2) / 72.9 (3) 79.1 (2) / 69.6 (3) 80.2 (2) / 73.4 (3)
63.4 (2)
60.3 (2)
60.3 (2)
62.4 (2)
63.4 (2)
65.0 (2)
63.4 (2)
64.0 (2)
63.6 (2)
64.2 (2)
70.7 (2)
66.9 (2)
67.3 (2)
64.6 (2)
66.3 (2)
67.6 (2)
64.5 (2)
65.5 (2)
67.6 (2)
68.6 (2)
68.9 (2)
67.6 (2)
67.7 (2)
68.8 (2)
69.4 (2)
73.7 (2)
71.1 (2)
69.7 (2)
69.8 (2)
71.5 (2)
Heat exchange mode, bypass mode, fresh-up mode
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
364x1,000x1,160
285x776x525
301x828x816
364x1,000x868
24.0
33.0
51.0
54.0
63.0
Galvanised steel plate
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
90 (4)/87 (4) 70 (4)/63 (4) 103 (1)/93 (1) 83 (1)/57 (1) 100 (1)/73 (1) 109 (1)/94 (1) 147 (1)/135 (1)
40 (4)
25 (4)
51 (1)
35 (1)
49 (1)
78 (1)
100 (1)
Multidirectional fibrous fleeces
27.0
28.0
32.0
33.0
34.5
36.0
36.0
27.0
28.0
32.0
33.5
34.5
36.0
36.0
-15/50
80% or less
100

150
15

200
1~/50/60/220-240/220

250

1500FC
0.617 (1)
0.617 (1)
78.0 (2) / 69.5 (3)
79.6 (2) / 70.3 (3)
80.8 (2) / 71.0 (3)
63.4 (2)
65.0 (2)
66.2 (2)
68.6 (2)
69.7 (2)
70.5 (2)

2000FC
0.685 (1)
0.685 (1)
78.0 (2) / 70.2 (3)
79.6 (2) / 71.3 (3)
80.6 (2) / 74.6 (3)
63.4 (2)
64.5 (2)
67.8 (2)
68.6 (2)
69.5 (2)
72.1 (2)

726x1,510x868 726x1,510x1,160
128
145
1,500 (1)
2,000 (1)
1,500 (1)
2,000 (1)
116 (1)/97 (1) 132 (1)/118 (1)
80 (1)
77 (1)
39.5
40.5

40.0
40.0

350

16

(1) Measured on fan curve 15. Refer to fan curves. (2) Measured according to JIS B 8628 (3) Measured according to EN308 : 1997 (4) Clean the filter when this icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and
for the units energy efficiency. (5) In accordance with commission regulation (EU) No 1254/2014 (6) Products with an air flow rate 250m/h must comply to commission regulation (EU) No.1254/2014 for RVUs, products with an air flow rate > 250m/h must
comply to commission regulation (EU) No.1253/2014 for NRVUs.

229

Ventilation & Air Handling

RH: Relative Humidity SA: Supply Air (to room) RA: Return Air (from room)

VH

Preheater for VAM


Total solution for fresh air with Daikin supply of both VAM

and preheaters

Increased comfort in low outdoor temperature thanks

to the heated outdoor air

Integrated electrical heater concept (no additional accesso-

ries required)

Standard dual flow and temperature sensor


Flexible setting with adjustable setpoint
Increased safety with 2 cut-outs: manual & automatic
BMS integration thanks to:
- Volt free relay for error indication
- 0-10VDC input for setpoint control

PREHEATER FOR VAM


Supply voltage
Output current (maximum)
Temperature sensor
Temperature control range
Control fuse
LED indicators

VH

(VH)
220/250V ac 50/60 Hz. +/-10%
19A at 40C (ambient)
5k ohms at 25C (table 502 1T)
0 to 40C / (0-10V 0-100%)
20 x 5mm 250mA

Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red

Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input

98mm x 181mm centres 5 mm holes


35C (during operation)
100C Pre-set
125C Pre-set
1A 120V AC or 1A 24V DC
0-10VDC

VH
Capacity
Duct diameter
Connectable VAM

kW
mm

1B
1
100
VAM150FC
-

For the selection of the appropriate capacity, please refer to the VAM selection software.

230

2B
1
150
VAM250FC
VAM350FC

3B
1
200
VAM500FC
VAM650FC

4B
1.5
250
VAM800FC
VAM1000FC

4/AB
2.5
250
VAM800FC
VAM1000FC

5B
2.5
300
VAM1500FC
VAM2000FC

Detailed technical drawings


VAM150FA
VAM150FA
Maintenance space for the heat exchange elements, the air
filters and fans

Switch box

Ceiling hook
4-14x40 oval hole

Inspection hole
450

285
600

Maintenance over

104

120.3

67

20

149

Supply air fan

120~250

269

SA

104

124

288
560

EA
Exhaust air to outdoors

718

Sealing

20

120

Fresh air from outdoors


(Outdoor air)

Return air from room


Sealing

164

509

RA

288
124 164

OA

Supply air to room

Damper plate

149

Exhaust air fan

(Maintenance cover)

Exhaust spacer

(Switch box)
145

760

97
200

145

Air filters

Heat exchange elements

NOTE

Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.
3TW27874-1

VAM250FA
VAM250FA
Maintenance space for the heat exchange elements, the air
filters and fans

Switch box

Ceiling hook
4-14x40 oval hole

Inspection hole
450

285

Maintenance over

120.3

67

20

104

Ventilation & Air Handling

600

Supply air fan

120~250

269
149

SA
509

124
288
560
164

RA

OA
288
124 164

Supply air to room

EA

Return air from room


104

Sealing

718

20

120

Exhaust air to outdoors


Sealing

Fresh air from outdoors


(Outdoor air)

Damper plate

149

Exhaust air fan

(Maintenance cover)
760

145
97
200

(Switch box)
145

Heat exchange elements

Air filters

NOTE

Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.
3TW27884-1

231

Detailed technical drawings


VAM350FC
VAM350FB

Ceiling hook
4 12 x 40 oval hole
Sealing

Exhaust air fan

Damper plate

RA
Return air from room

EA
Exhaust air to outdoors

SA
Supply air to room
Supply air fan

OA
Fresh air from outdoors
(outdoor air)

Switch box

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

3D081162

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

VAM500FC
VAM500FB

Ceiling hook
4 12 x 40 oval hole
Sealing

Exhaust air fan

Damper plate

RA
Return air from room

EA
Exhaust air to outdoors

SA
Supply air to room

OA
Fresh air from outdoors
(outdoor air)

Supply air fan

Switch box

Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

1. Be sure to provide the inspection hole to inspectthe air lters, the exchange elements and fans.

232

3D081163

Detailed technical drawings


VAM650FC
VAM650FB
Sealing

Ceiling hook
4 12 x 40 oval hole
Damper plate
Exhaust air fan
RA
Return air from room

EA
Exhaust air to outdoors

SA
Supply air to room

OA
Fresh air from outdoors
(outdoor air)

Supply air fan


Switch box
Inspection hole

Maintenance space for the heat exchange


element, the air lters and fans

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

3D081164

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

VAM800FC
VAM800FB
Sealing

Ceiling hook
4 12 x 40 oval hole
Damper plate
Exhaust air fan

Ventilation & Air Handling

RA
Return air from room

EA
Exhaust air to outdoors

SA
Supply air to room

OA
Fresh air from outdoors
(outdoor air)

Supply air fan


Switch box
Inspection hole

Maintenance space for the heat exchange


element, the air lters and fans

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

3D081165

233

Detailed technical drawings


VAM1000FC
VAM1000FB

Ceiling hook
4 12 x 40 oval hole

Sealing

Damper plate
Exhaust air fan

RA
Return air from room

EA
Exhaust air to outdoors

SA
Supply air to room

OA
Fresh air from outdoors
(outdoor air)

Supply air fan


Switch box

Maintenance space for the heat exchange


element, the air lters and fans

Inspection hole

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

3D081166

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

VAM1500FC

VAM1500FB

Sealing

Ceiling hook
4 14 x 40 oval hole
Exhaust air fan (2x)

Damper plate

EA
Exhaust air to outdoors

RA
Return air from room

OA
Fresh air from outdoors
(outdoor air)

SA
Supply air to room
Supply air fan (2x)

Switch box

Maintenance space for the heat exchange


element, the air lters and fans

Inspection hole

Heat exchange element

Maintenance cover

Air lters

Switchbox

NOTES

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

234

3D081167

Detailed technical drawings


VAM2000FC
VAM2000FB
Sealing

Ceiling hook
4 14 x 40 oval hole
Damper plate

Exhaust air fan (2x)

RA

EA
Exhaust air to outdoors

Return air from room

SA
Supply air to room

OA
Fresh air from outdoors
(outdoor air)

Supply air fan (2x)


Switch box

Maintenance space for the heat exchange


element, the air lters and fans

Inspection hole

Heat exchange element

Maintenance cover

Air lters

Switchbox

VAM150FC
NOTES

3D081168

1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.

VAM150FC
250

20m

15m

150

Ventilation & Air Handling

External static pressure [Pa]

200

Ultra-high
10m

100

High
5m

Low

50

100
Pipe length
0
0

50

100
150
Air flow rate [m/h]

200

250

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

4D100379

235

VAM250FC

Detailed technical drawings


VAM250FC
250

External static pressure [Pa]

200

Ultra-high
150

150
Pipe length
High

100

40m
30m

Low

20m

50

10m
0
0

50

100

150
200
Air flow rate [m/h]

250

300

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

4D100380

VAM350FC

VAM350FC
200

40m

UH15
H15

150

UH8

20m

External static pressure [Pa]

30m

200

150
External static pressure [Pa]

External static pressure [Pa]

250

200

Ultra-high speed

300

100

50

50

15

10m

H1

L8
L1

150

250
350
Air flow rate [m/h]

150
Pipe length

100

200
300
Air flow rate [m/h]
Ultra-high speed
High speed
Low speed

Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

=
=
=
=
=
=
=
=
=

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

400

150

250

350
Air flow rate [m/h]

450

500

External static pressure [Pa]

100

450

Low speed

0
0

100

UH1

L15
50

150

15

H8

100

High speed

50

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

0
150

250

15

350
Air flow rate [m/h]

450

3D100381

236

VAM500FC

Detailed technical drawings

200

200

200
Pipe length

VAM500FC

200

Ultra-high speed

High speed

VAM500FC

50m

150

UH15

40m

UH8
H8

100

L8

50

L1

30m

H1

L15

L8

50

H15

UH1

20m

H1

L15

L1

10m

100

30m

20m

200

High speed150
External static pressure [Pa]

H15

UH1

External static pressure [Pa]

H8

100

50m

External static pressure [Pa]

UH8
150

150
Ultra-high
speed

40m

150

100

External static pressure [Pa]

200
200
Pipe length

UH15

External static pressure [Pa]

External static pressure [Pa]

200
150

50

10m

100

50

100

50
50

100

200

100

300

200

400

500

300
400
500
Air
flow
rate
[m/h]600
Air flow
rate
[m/h]

700

600

700
200

Ultra-high speed
Ultra-high speed
High speed
Low speed
High speed

H15
UH1

500
300
Air flow rate [m/h]

100

=
=
=
=
=
=
=
=
=

Low speed lower limit


Low speed factory setting
limit
= Low speed
Low upper
speed
lower limit
High speed lower limit
= High speed
Low speed
factory setting
factory setting
= High speed
Low speed
upper limit
upper limit
lower
limit limit
= Ultra-high
Highspeed
speed
lower
factory setting
= Ultra-high
Highspeed
speed
factory setting
Ultra-high speed upper limit

=
=

High speed upper limit


Ultra-high speed lower limit

NotesUH8
=
Ultra-high speed factory setting
1. The fan speeds are valid for 230V, 50Hz power supply.

UH15

Ultra-high speed upper limit

50

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

300
600

15

600
200

400700
500
Air flow rate [m/h]

700300

15

400
500
Air flow rate [m/h]

600

700

Low speed

50

200

400 700
500 200
Air flow rate [m/h]

600

Low100speed

Low speed

External static pressure [Pa]

Legend
L1
Legend
L8
L15L1
H1
L8
H8
L15
H15
UH1H1
UH8
H8
UH15

400
200

300

15

15

External static pressure [Pa]

300

400

15

500

Air flow rate [m/h]

3D100382
0
VAM650FC

200

VAM650FC

300

400

15

500

Air flow rate [m/h]

300

250

60m

250

Ultra-high speed

High speed

3D100382

50m

250

200

200

UH15
150

UH1

30m

UH8

H15

20m

L15

100
H8
L8

50

H1

10m

150

100

100

50

50

200
Pipe length

L1

150

Ventilation & Air Handling

200

External static pressure [Pa]

40m
External static pressure [Pa]

15

0
0

200

400

600

800

Air flow rate [m/h]

0
250

350

450

550
650
750
Air flow rate [m/h]
150

Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

=
=
=
=
=
=
=
=
=

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

External static pressure [Pa]

External static pressure [Pa]

850

250

350

450

550
650
750
Air flow rate [m/h]

15

850

Low speed

100

50

0
250

450

15

650
Air flow rate [m/h]

850

3D100383

237

Detailed technical drawings

VAM800FC

VAM800FC
300

250

250

UH8
H15

200

UH15

H8

100m

L15
UH1

150

200

150

100

L8

H1

100

0
200

50
15

20m

150

50

40m

L1

50

200

80m
60m

100

High speed

250

External static pressure [Pa]

300

External static pressure [Pa]

350

External static pressure [Pa]

300

Ultra-high speed

400

400
600
Air flow rate [m/h]

800

1000

300

250
Pipe length

900

300

1100

500

700
Air flow rate [m/h]

15

900

1100

Low speed

250

External static pressure [Pa]

=
=
=
=
=
=
=
=
=

700
Air flow rate [m/h]

300

Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

500

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

200

150

100

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

50

0
300

500

15

700
Air flow rate [m/h]

900

1100

3D100384
VAM800FC

VAM1000FC
300

250

250

UH8
H15

200

UH15

H8

100m

L15
UH1

150

L8

H1

150

100

20m

0
0

200

150

100

15

400
600
Air flow rate [m/h]

800

1000

0
300

250
Pipe length

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

700
Air flow rate [m/h]

300

900

0
300

1100

500

700
Air flow rate [m/h]

900

15

1100

Low speed

250

External static pressure [Pa]

=
=
=
=
=
=
=
=
=

500

Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

200

50

50

40m

L1

50

200

80m
60m

100

High speed

250

External static pressure [Pa]

300

External static pressure [Pa]

350

External static pressure [Pa]

300

Ultra-high speed

400

200

150

100

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

50

0
300

500

700
Air flow rate [m/h]

15

900

1100

3D100384

238

Detailed technical drawings


VAM800FC

VAM1500FC
300

250

250

UH8
UH15

H15

200

H8

100m

L15
UH1

150

L8

H1

150

100

150

100

15

20m

0
0

200

200

50

50

40m

L1

50

200

80m
60m

100

High speed

250

External static pressure [Pa]

300

External static pressure [Pa]

350

External static pressure [Pa]

300

Ultra-high speed

400

400
600
Air flow rate [m/h]

800

1000

300

900

300

1100

500

700
Air flow rate [m/h]

15

900

1100

Low speed

250

External static pressure [Pa]

=
=
=
=
=
=
=
=
=

700
Air flow rate [m/h]

300

Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

500

250
Pipe length

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

200

150

100

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

50

300

500

15

700
Air flow rate [m/h]

900

1100

3D100384

VAM2000FC
VAM2000FC

200

External static pressure [Pa]

UH15
150
H15

UH8

H8
100

250

250

200

200

150

100

High speed

150

100

UH1

L15
H1

50

50

50
L8
L1
0
1000

1500

2000
Air flow rate [m/h]

2500

0
1200

1700
2200
Air flow rate [m/h]
160

Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15

=
=
=
=
=
=
=
=
=

Low speed lower limit


Low speed factory setting
Low speed upper limit
High speed lower limit
High speed factory setting
High speed upper limit
Ultra-high speed lower limit
Ultra-high speed factory setting
Ultra-high speed upper limit

Notes
1. The fan speeds are valid for 230V, 50Hz power supply.

0
1200

15

2700

1700
2200
Air flow rate [m/h]

15

2700

Low speed

140
120
External static pressure [Pa]

External static pressure [Pa]

250

300

Ultra-high speed

Ventilation & Air Handling

300

External static pressure [Pa]

300

100
80
60
40
20
0
1
1200

15

1700
2200
Air flow rate [m/h]

2700

3D100387

239

VKM-GB/VKM-GBM

Heat reclaim ventilation and air


processing
Pre heating or cooling of fresh air for lower load on the air
conditioning system
Energy saving ventilation using indoor heating, cooling and

moisture recovery
Creates a high quality indoor environment by pre conditioning

incoming fresh air


Humidification of the incoming air results in comfortable indoor

humidity level, even during heating


Ideal solution for shops, restaurants or offices requiring

maximum floor space for furniture, decorations and fittings


Free cooling possible when outdoor temperature is below

indoor temperature (eg. during nighttime)


Low energy consumption thanks to DC fan motor
Prevent energy losses from over-ventilation while maintaining

indoor air quality with optional CO2 sensor


Shorter installation time thanks to easy adjustment of nominal

air flow rate, so less need for dampers compared with traditional
installation.
Specially developed heat exchange element with High
Efficiency Paper (HEP)
Can operate in over- and under pressure

Operation example: humidification & air processing (heating mode)1

Exhaust Fan

Heat Exchanger
Elements

Damper Motor

DX coil (Direct expansion coil)

Damper

EA
(Exhaust air to outdours)
OA
(Fresh air from outdoors)

RA
(Return air from room)

Air Supply Fan

SA (Supply air to room)

Electronics Box (Control box)

Float switch

Humidifier element:
Utilizing the principle of capillary action, water is
permeated throughout the humidifier element.
The heated air from the DX coil passes through the
humidifier and absorbs the moisture.

water

AIRFLOW

Drain pan
1

VKM-GM example

240

Solenoid
valve

Drain

SA

VKM-GM example

Heat recovery ventilation,


humidification & air processing

Heat exchange mode


Nom.
Bypass mode
Nom.
Cooling
Heating
Ultra high/High/Low

VKM-GB/VKM-GBM
Ultra high
kW
Ultra high
kW
kW
kW
%

Fresh air conditioning


load
Temperature exchange
efficiency - 50Hz
Enthalpy exchange
Cooling
Ultra high/High/Low
Heating
Ultra high/High/Low
efficiency - 50Hz
Operation mode
Heat exchange system
Heat exchange element
Humidifier
System
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Fan-Air flow rate Heat exchange mode Ultra high
Bypass mode
Ultra high
50Hz
Fan-External static
Ultra high
High
pressure - 50Hz
Low
Air filter
Type
Sound pressure level Heat exchange mode Ultra high
Bypass mode
Ultra high
- 50Hz
Operation range
Around unit
Supply air
Return air
On coil
Cooling
Max.
Heating
Min.
temperature
Refrigerant
Type
Control
GWP
Connection duct diameter
Piping connections
Liquid
OD
Gas
OD
Water supply
Drain
Power supply
Phase/Frequency/Voltage
Current
Maximum fuse amps (MFA)

%
%

76/76/77.5

mm
kg

387x1,764x832
94

m/h
m/h
Pa
Pa
Pa

500
500

dBA
dBA
CDB
CDB
CDB
CDB
CDB

39
40

mm
mm
mm
mm

200

Hz/V
A

78/78/79

64/64/67
67/67/69

210
170
140

74/74/76.5

Heat reclaim ventilation,


air processing and humidification
50GBM
80GBM
100GBM
0.270
0.330
0.410
0.270
0.330
0.410
4.71 / 1.91 / 3.5
7.46 / 2.96 / 5.6
9.12 / 3.52 / 7.0
5.58 / 2.38 / 3.5
8.79 / 3.79 / 5.6
10.69 / 4.39 / 7.0
76/76/77.5

78/78/79

74/74/76.5

66/66/68
62/62/66
64/64/67
66/66/68
62/62/66
71/71/73
65/65/69
67/67/69
71/71/73
65/65/69
Heat exchange mode / Bypass mode / Fresh-up mode
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Natural evaporating type
387x1,764x1,214
387x1,764x832
387x1,764x1,214
110
112
100
119
123
Galvanised steel plate
750
950
500
750
950
750
950
500
750
950
150
200
205
110
160
100
150
155
70
110
70
120
105
60
Multidirectional fibrous fleeces
41.5
41
38
40
41.5
41
39
41
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
-15
43
43
R-410A
Electronic expansion valve
2,087.5
250
200
250
6.35
12.7
6.4
PT3/4 external thread
1~/50/220-240
15

241

Ventilation & Air Handling

Ventilation
Power input - 50Hz

Heat reclaim ventilation


and air processing
50GB
80GB
100GB
0.270
0.330
0.410
0.270
0.330
0.410
4.71 / 1.91 / 3.5
7.46 / 2.96 / 5.6
9.12 / 3.52 / 7.0
5.58 / 2.38 / 3.5
8.79 / 3.79 / 5.6
10.69 / 4.39 / 7.0

Detailed technical drawings


VKM50GB
VKM50GB

Air discharge grille


(locally procured)

Air suction grille


(locally procured)

Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)

Branch duct
(locally procured)

Control box
Maintenance space for the heat exchanger
elements the air filters and fans

Inspection
hatch

Inspection
hatch

More than 600

Round shape hood


(Locally procured)
OA
(Fresh air from outdoors)

Flexible duct
(locally procured)

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)

Refrigerant piping (Gas pipe)


( 12.7 flare connection)

A gradient of
more than 1/30

Refrigerant piping (Liquid pipe)


( 6.4 flare connection)

200
Nominal diameter
(locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100

Inspection hatch
(locally procured)

Suspention bolt
(locally procured)

RA
(Return air from room)

SA
(Return air to room)

NOTES

1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.

3D083014

242

Detailed technical drawings


VKM50GBM
VKM50GBM

Air discharge grille


(locally procured)

Air suction grille


(locally procured)

Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Round shape hood
(locally procured)
OA
(Fresh air to outdoors)
Control box
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier

Inspection
hatch

Inspection
hatch

More than 600

Branch duct
(locally procured)

Flexible duct
(locally procured)

Heat insulated
(locally procured)

Air discharge grille


(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)
Cistern tank

Water supply shut-off valve


(locally procured)
A gradient of
more than 1/30

250
Nominal diameter
(locally procured)

Drain valve
(locally procured)
Strainer
(locally procured)

Refrigerant piping (Gas pipe)


( 12.7 flare connection)
Refrigerant piping (Liquid pipe)
( 6.4 flare connection)

OA
(Fresh air to outdoors)

Sloping downwards at
a gradient of the 1/100

450 - 600

Inspection hatch
(locally procured)

Suspention bolt
(locally procured)
RA
(Return air from room)

SA
(Return air from room)

NOTES

1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 )
7. Make sure the supply water is between 5C and 40C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0C.
12. Do not use a bent cap or a round hoodas the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13.In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14.Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the
air filter is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)

3D083011

243

Ventilation & Air Handling

EA
(Exhaust air to outdoors)

Detailed technical drawings


VKM80GB
VKM80GB

Air suction grille


(locally procured)

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

EA
(Exhaust air to outdoors)

Branch duct
(locally procured)

Round shape hood


(Locally procured)
OA
(Fresh air from outdoors)

Inspection
hatch

Inspection
hatch

More than 600

Silencer
(locally procured)
Control box

Maintenance space for the heat exchanger


elements the air filters and fans

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

Flexible duct
(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)

200
Nominal diameter

Refrigerant piping (Gas pipe)


( 12.7 flare connection)

A gradient of
more than 1/30

Refrigerant piping (Liquid pipe)


( 6.4 flare connection)

(locally procured)

OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100

450 600

Inspection hatch
(locally procured)

Suspention bolt
(locally procured)

RA
(Return air from room)

SA
(Return air to room)

NOTES

1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.

3D083015

244

Detailed technical drawings


VKM80GBM
VKM80GBM

Air suction grille


(locally procured)

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

EA
(Exhaust air to outdoors)

Branch duct
(locally procured)

Heat insulated
(locally procured)

Round shape hood


(locally procured)

Control box
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier

Inspection
hatch

Inspection
hatch

More than 600

OA
(Fresh air to outdoors)

Silencer
(locally procured)
Flexible duct
(locally procured)

Air discharge grille


(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)
Cistern tank

Water supply shut-off valve


(locally procured)
A gradient of
more than 1/30

250

Drain valve
(locally procured)
Strainer
(locally procured)

Refrigerant piping (Gas pipe)


( 12.7 flare connection)
Refrigerant piping (Liquid pipe)
( 6.4 flare connection)

Nominal diameter
(locally procured)
OA
(Fresh air to outdoors)

Sloping downwards at
a gradient of the 1/100

450 - 600

Inspection hatch
(locally procured)

Suspention bolt
(locally procured)
RA
(Return air from room)

SA
(Return air from room)

Ventilation & Air Handling

EA
(Exhaust air to outdoors)

NOTES

1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 )
7. Make sure the supply water is between 5C and 40C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0C.
12. Do not use a bent cap or a round hoodas the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13.In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14.Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the
air filter is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)

3D083012

245

Detailed technical drawings


VKM100GB
VKM100GB

Air suction grille


(locally procured)

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

EA
(Exhaust air to outdoors)

Branch duct
(locally procured)

Round shape hood


(Locally procured)
OA
(Fresh air from outdoors)

Inspection
hatch

Inspection
hatch

More than 600

Silencer
(locally procured)
Control box

Maintenance space for the heat exchanger


elements the air filters and fans

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

Flexible duct
(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)

Refrigerant piping (Gas pipe)


( 12.7 flare connection)

A gradient of
more than 1/30

Refrigerant piping (Liquid pipe)


( 6.4 flare connection)

250
Nominal diameter
(locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100

450 600

Inspection hatch
(locally procured)

Suspention bolt
(locally procured)

RA
(Return air from room)

SA
(Return air to room)

NOTES

1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.

3D083016

246

Detailed technical drawings


VKM100GBM
VKM100GBM

Air suction grille


(locally procured)

Heat insulator
(locally procured)

Air discharge grille


(locally procured)

EA
(Exhaust air to outdoors)

Branch duct
(locally procured)

Round shape hood


(Locally procured)

Control box
Inspection
hatch

Maintenance space for the heat exchanger


fans and
elements the air

Inspection
hatch

More than 600

OA
(Fresh air from outdoors)

Heat insulator
(locally procured)

Silencer
(locally procured)
Flexible duct
(locally procured)

Air discharge grille


(locally procured)

360 (in case of 450 inspection hatch)


140 (in case of 600 inspection hatch)
Cistern tank

Water supply shut-off valve


(locally procured)
A gradient of
more than 1/30

250
Nominal diameter

Drain valve
(locally procured)
Strainer
(accessory)

Refrigerant piping (Gas pipe)


( 12.7
connection)
Refrigerant piping (Liquid pipe)
connection)
( 6.4

(locally procured)
OA
(Fresh air from outdoors)

Sloping downwards at a
gradient of the 1/100

450 600

Inspection hatch
(locally procured)

Suspension bolt
(locally procured)

RA
(Return air from room)

SA
(Return air to room)

NOTES

1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air
heat exchange elements, fans, and
elements can easily be inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water. Also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection.
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2).
7. Make sure the supply water is between 5 C and 40 C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the
will not drop below 0 C.
12. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)

3D083013

247

Ventilation & Air Handling

EA
(Exhaust air to outdoors)

Detailed technical drawings


VKM50GB
VKM50GB

50Hz, 220V-240V
Operating air flow rate range

Temp
e

rature

Enth

alpy

Enth

exch

exch

nge e

fficien

effic

ange

cy

ienc

y (he

effic

ating

ienc

y (co

oling

Ultra High

Operating air flow rate range

Operating air flow rate range

Operating air flow rate range

Air flow rate (m3/h)


Low

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

200
Pipe
length
External static pressure (Pa)

External static pressure (Pa)

alpy

ange

excha

Exchange
efficiency
(%)

High
Low

Air flow rate (m3/h)


[Reading of Performance Characteristics]

2) Rated point:
3) The characteristic of each tap becomes a setup of the
characteristic of the same code number.

1) For example: 19(29)- -07


Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

3D082904

VKM50GBM
VKM50GBM

Exchange efficiency
(%)
Operating air flow rate range

50Hz, 220V-240V

Temp
e

rature

Enth

alpy

Enth

exch

exch

nge e

effic

ange

fficien

ienc

cy

y (he

effic

ating

ienc

y (co

oling

Ultra High

Operating air flow rate range

Operating air flow rate range

Operating air flow rate range

Air flow rate (m3/h)


Low

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

200
Pipe
length

External static pressure (Pa)

External static pressure (Pa)

alpy

ange

VKM50GBM
excha

High

Low

Air flow rate (m3/h)


[Reading of Performance Characteristics]
1) For example: 19(29)- -07
Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

248

2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.

3D082901

Detailed technical drawings


VKM80GB
VKM80GB

50Hz, 220V-240V

Exchange
efficiency
(%)

Operating air flow rate range

eratu

re ex

Enth

alpy

Enth

External static pressure (Pa)

alpy

chan

ge e

exch

ange

exch

ange

Operating air flow rate range

Operating air flow rate range

fficie

ncy

effic

ienc

y (he

effic

ating

ienc

y (co

oling

Ultra High
High

250
Pipe
length

External static pressure (Pa)

Tem
p

Operating air flow rate range

Low

Air flow rate (m3/h)


Low

Air flow rate (m3/h)

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

[Reading of Performance Characteristics]


2) Rated point:
3) The characteristic of each tap becomes a setup of the
characteristic of the same code number.

1) For example: 19(29)- -07


Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

3D082905

VKM80GBM
VKM80GBM

Exchange efficiency
(%)

50Hz, 220V-240V
Operating air flow
rate range

Operating air flow rate range

Operating air flow rate range

Operating air flow rate range

Tempera

ture exch

alpy

Enth

alpy

External static pressure (Pa)

ange effic

exch

ange

exch

iency

effic

ange

ienc

y (he

effic

ating

ienc

y (co

oling

Ultra High

250
Pipe
length

External static pressure (Pa)

Enth

Ventilation & Air Handling

VKM80GBM

High

Low

Air flow rate (m3/h)

Air flow rate (m3/h)


Low

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

[Reading of Performance Characteristics]


1) For example: 19(29)- -07
Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.

3D082902

249

Detailed technical drawings


VKM100GB
VKM100GB

50Hz, 220V-240V

Exchange
efficiency
(%)
Operating air flow rate range
Operating air flow rate range
erat

Ent

ure

External static pressure (Pa)

halp

y ex

Ent

halp

cha

y ex

exc

han

nge

cha

nge

ge e

Operating air flow rate range

Operating air flow rate range

fficie

effic

ienc

ncy

y (h

effic

ienc

eatin

y (c

g)

ooli

ng)

External static pressure (Pa)

Tem
p

250
Pipe
length

Ultra High
High

Low

Air flow rate (m3/h)


Low

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

Air flow rate (m3/h)


[Reading of Performance Characteristics]
2) Rated point:
3) The characteristic of each tap becomes a setup of the
characteristic of the same code number.

1) For example: 19(29)- -07


Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

3D082906

VKM100GBM
VKM100GBM
Exchange efficiency
(%)

50Hz, 220V-240V

Operating air flow rate


range

En

era

External static pressure (Pa)

tha

lpy

En

VKM100GBM

tha

lpy

ture

exc

han

exc

ge

han

ge

exc

han

effi

ge e

ncy

cie

Operating air flow rate range

Operating air flow rate range

Air flow rate (m3/h)


Low

Air flow rate (m3/h)


High

Air flow rate (m3/h)


Ultra High

fficie

cie

effi

Operating air flow rate range

ncy

(he

ncy

atin

(co

g)

olin

g)

Ultra High
High

250
Pipe
length

External static pressure (Pa)

Tem
p

Low

Air flow rate (m3/h)

[Reading of Performance Characteristics]


1) For example: 19(29)- -07
Mode no. : 19(29)
First code: (Supply 2 Exhaust 3 )

Second code no. : 07

250

2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.

3D082903

Air handling unit applications

Air handling unit applications


Wide range of air flows
For applications that require big volumes of treated
fresh air (large atriums, banquet halls, etc) air
handling units represent the ideal solution.
Daikins wide range of air handling units treat
air volumes from 500 m/h up to 144,000 m/h.

The air handling unit can be designed to deliver


whatever air flow you require, via the specific
dimensions of flow section available at the
installation.

Air flow (m3/h x 1,000)

Professional

Professional

Pre-configured sizes
Tailored to the individual

140

customer

120

Modular construction

Energy
100

Energy

High-end solution for optimised

90

energy consumption
High efficiency components
Strong Return on Investment

80

Modular

70

Plug & play, with factory

mounted controls

60

Pre-configured sizes
EC Fan Technology
High Efficiency Heat Wheel
Compact Design

50

40

20

750 m3/h
up to
144,000 m3/h

Modular
750 m3/h
up to
100,000 m3/h

500m3/h
up to 25,000 m3/h

Selection software

Return on investment

ASTRA is the powerful software that Daikin has developed to offer a


quick and comprehensive service for the customer in order to make
the technical choice and the economic valorization
of each AHU. It is a complete tool that can configure any type of
product and respond exactly to the strictest design needs.
The result is a comprehensive economic offer including all the
technical data and drawings, the psychrometric diagram with the
relative air treatment and the fans performance curves. The ASTRA
software features a specific DX heat pump coil section able to
calculate cooling and heating performances with the automatic
selection of the appropriate Daikin expansion valve.
The complementary Xpress software allows the correct ERQ or VRV
outdoor unit to be selected.

The air handling unit (AHU) is critical to an effective climate control


system and the savings generated by our advanced designs and
operating efficiencies guarantee a rapid return on the investment
made. Our AHU Energy series has been designed to deliver
exceptional performance thus driving down the energy consumed
and so lowering energy bills. Taken over the expected 15-year
life-span of the equipment, this will result in a substantial saving,
especially in a time of ever increasing energy prices.

Dainkin fresh air package - plug & play


The D-AHU Modular series provide a complete solution including
unit control (EKEXV, EKEQ, DDC controller) factory mounted
and configured, plug & play with our VRV and ERQ condensing
units. The easiest solution as you save time and only
have one point of contact!

Pre-defined sizes
27 fixed sizes are available, optimised to reach
the optimum combination between value for money
and manufacturing standardisation. Daikins section by section
design means that units can be sized by 1cm increments and
assembled on site, without welding, to suit the space constraints
of the installation.

High efficiency components


All Daikin air handling units have been designed for optimum
energy efficiency. Polyurethane or Mineral wool panels guarantee
excellent thermal insulation performance. And the widest range of
filters are provided to meet even the most strict demands.

251

Ventilation & Air Handling

Air handling unit applications

Why use VRV and ERQ condensing units for connection


to air handling units?
High Efficiency
Daikin heat pumps are renowned for their high
energy efficiency. Integrating the AHU with a heat
recovery system is even more effective since
an office system can frequently be in cooling mode

while the outdoor air is too cold to be brought


inside in an unconditioned state. In this case heat
from the offices is merely transferred to heat up
the cold incoming fresh air.

Outside air = 10C

Fresh air supplied at 21C.


The temperature difference with
the outdoor air is heated up for free
by heat recovery via A/C system

Indoor temperature 22C,


needs cooling because of solar
radiation.
The excessive heat can be
transferred to the AHU.

Fast response to changing loads


resulting in high comfort levels
Daikin ERQ and VRV units respond rapidly
to fluctuations in supply air temperature, resulting
in a steady indoor temperature and resultant high
comfort levels for the end user. The ultimate is
the VRV range which improves comfort even more
by offering continuous heating, also during defrost.

Easy Design and Installation


The system is easy to design and install since
no additional water systems such as boilers,
tanks and gas connections etc. are required.
This also reduces both the total system investment
and running cost.

Daikin Fresh air package


VRV IV or ERQ condensing unit

Factory fitted and welded


fresh air package

Electronic expansion

252

valve

Control box

(EKEXV)

(EKEQ)

Flexible control possibilities for air handling units

In order to maximise installation flexibility,


4 types of control systems are offered
W control: Off the shelf control of air temperature (supply air
temperature, return air temperature, room temperature) via any
DDC controller, easy to setup
X control: Precise control of air temperature (supply air temperature,
return air temperature, room temperature) requiring
a preprogrammed DDC controller (for special applications)

W control (TS/TR/TROOM control):

Air temperature control via DDC controller


Room temperature is controlled as a function of the air handling
unit return air or supply air (customer selection). The DDC controller
is translating the temperature difference between set point
and return air temperature (or supply air temperature or room
temperature) into a proportional 0-10V signal which is transferred
to the Daikin control box (EKEQFCBA). This voltage modulates the
capacity requirements of the outdoor unit.

0-10V

TTEXT
EXT

Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA

TTRR

DDC
DDC

TS
T
S

0-10V

TTEXT
EXT

Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA

Y control (TE/TC control):

TEXT

Control box
Control
box
EKEQFCBA
EKEQFCBA

4.

Z control (TR/TROOM control):

Control your AHU just like a VRV indoor unit with 100% fresh air
Allows the possibility to control the AHU just like a VRV indoor
unit. Meaning temperature control will be focused on return air
temperature from the room into the AHU. Requires BRC1D52 or
BRC1E52A/B for operation. This the only control that allows
the combination of other indoor units to the AHU at the same time.
AHU
AHU

TRR
+
TETC

TTOA
OA

TS
T
S

TTROOM
ROOM

BRC1D*
BRC1D*
BRC1E*
BRC1E*

TTEXT
EXT

Control box
box
Control
EKEQMCBA (VRV
EKEQMCBA
(VRVIV)
IV)
EKEQDCB
(ERQ)
EKEQDCB (ERQ)

OR
OR

TR = Return air temperature

TOA = Outdoor air temperature

TEXT = Extraction air temperature

TE = Evaporating temperature

TC = Condensing temperature

Option kit
EKEQFCBA

Possibility Z

EKEQDCB
EKFQMCBA*

T
TR

+
TETC

TTOA
OA

TS = Supply air temperature

Possibility W
Possibility X
Possibility Y

TS
T
S

TTROOM
ROOM

By fixed evaporating /condensing temperature


A fixed target evaporating or condensing temperature can be set
by the customer. In this case, room temperature is only indirectly
controlled. A Daikin wired remote control (BRC1D52 or BRC1E52A/B
- optional) have to be connected for initial set-up but not required
for operation.

BRC1D*
BRC1D*
BRC1E*
BRC1E*

TTRR
+

TETC

TTOA
OA

TTROOM
ROOM

3.

OR
OR

AHU
AHU

TETC

TTOA
OA

X control (TS/TR/TROOM control):

Precise air temperature control via DDC controller


Room temperature is controlled as a function of the air handling
unit return air or supply air (customer selection). The DDC controller
is translating the temperature difference between set point
and return air temperature (or supply air temperature or room
temperature) into a reference voltage (0-10V) which is transferred
to the Daikin control box (EKEQFCBA). This reference voltage will be
used as the main input value for the compressor
frequency control.

OR
OR

AHU
AHU

DDC
DDC

2.

TS

TTROOM
ROOM

TROOM = Room air temperature

Features
Off-the-shelf DDC controller that requires no pre-configuration
Pre-configured DDC controller required
Using fixed evaporating temperature, no set point can be set using remote control
Using Daikin infrared remote control BRC1D52 or BRC1E52A/B
Temperature control using return air temperature or room temperature (via remote sensor)

* EKEQMCB (for multi application)

253

Ventilation & Air Handling

1.

Z control: Control of air temperature (return air temperature, room


temperature) via Daikin control (no DDC controller needed)
Y control: Control of refrigerant (Te/Tc) temperature via Daikin
control (no DDC controller needed)

VRV- Air handling application

- for larger capacities (from 8 to 54HP)


An advanced solution for both pair and multi application
Inverter controlled units
Heat recovery, heat pump
R-410A
Control of room temperature via Daikin control
Large range of expansion valve kits available
BRC1E52A/B is used to set the set point temperature
(connected to the EKEQMCBA).
Connectable to all VRV heat recovery and
heat pump systems

W, X, Y control for VRV IV heat pump

Z control for all VRV outdoor units

Refrigerant piping
F1-F2
other communication

254

ERQ - Air handling application

ERQ - for smaller capacities


(from 100 to 250 class)

A basic fresh air solution for pair application


Inverter controlled units
Heat pump
R-410A
Wide range of expansion valve kits available
Perfect for the Daikin Modular air handling unit
The Daikin Fresh Air Package provides a complete Plug & Play Solution including
AHU, ERQ or VRV Condensing Unit and all unit control (EKEQ, EKEX, DDC controller)
factory mounted and configured. The easiest solution with only one point of contact.

ERQ-AW1

Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m/min
Heating
Nom.
m/min
Sound power level Cooling
Nom.
dBA
Sound pressure Cooling
Nom.
dBA
Heating
Nom.
dBA
level
Operation range Cooling
Min./Max.
CDB
Heating
Min./Max.
CWB
On coil
Heating Min.
CDB
CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Drain
OD
mm
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A

100AV1

125AV1

140AV1

4
11.2
12.5
2.81
2.74

5
14.0
16.0
3.51
3.86

6
15.5
18.0
4.53
4.57
3.42
3.94

Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m/min
Heating
Nom.
m/min
Sound power level Nom.
dBA
Sound pressure level Nom.
dBA
Operation range Cooling
Min./Max.
CDB
Heating
Min./Max.
CWB
On coil
Heating Min.
CDB
CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A

125AW1

200AW1

250AW1

5
14.0
16.0
3.52
4.00
3.98
4.00
1,680x635x765
159
95
95
72
54

8
22.4
25.0
5.22
5.56
4.29
4.50

10
28.0
31.5
7.42
7.70
3.77
4.09

3.99
4.56

4.15
1,345x900x320
120
106
105
67
51
53
-5/46
-20/15.5
10
35
R-410A / 2.087,5
4.0/8.4
9.52

69
53
55

15.9

19.1

Ventilation & Air Handling

102
66
50
52

26x3
1N~/50/220-240
32.0

6.2/12.9
15.9

1,680x930x765
187
171
171

240
185
185
78

57

58

-5/43
-20/15
10
35
R-410A / 2.087,5
7.7/16.1
9.52
19.1

8.4/17.5
22.2

3N~/50/400
16

25

255

Overview of expansion valves and control boxes

Integration of ERQ and VRV in third party air handling units


a wide range of expension valve kits and control boxes

Combination table
Control box

ERQ100
1-phase ERQ125
ERQ140
ERQ125
3-phase ERQ200
ERQ250
VRV III
VRV IV H/P /
VRV IV W-series
VRV IV S-series
VRV IV H/R
VRV IV i-series



Expansion valve kit

EKEQDCB EKEQFCBA EKEQMCBA


Z control W,X,Y control Z control
P
P
P
P
P
P
P
P
P
P
P
P
n1

EKEXV50
n1

EKEXV63
P
P
P
n1

EKEXV80
P
P
P
P
n1

EKEXV100
P
P
P
P
P
n1

EKEXV125
P
P
P
P
P
P
n1

EKEXV140
P
P
P
P
P
n1

EKEXV200
P
P
n1

EKEXV250
P
P
n1

EKEXV400
n1

EKEXV500
n1

Mixed connection with


VRV indoor units

Not possible

Mandatory

P (1 -> 3)

n2

n2

n2

n2

n2

n2

n2

n2

n2

n2

n2

Possible (not
mandatory)

n1

n1

n1

n1

n1

n1

n1

n1

n1

n1

n1

Mandatory

P (pair application): combination depends on the capacity of the air handling unit
n1 (multi application) - Combination of AHUs and VRV DX indoors (mandatory). To determine the exact quantity please refer to the engineering data book.
n2 (multi application) - Combination of AHUs and VRV DX indoors (not mandatory). To determine the exact quantity please refer to the engineering data book.data book
Control box EKEQFA can be connected to some types of VRV IV outdoor units (with a maximum of 3 boxes per unit). Do not combine EKEQFA control boxes with VRV DX indoor units, RA indoor units or hydroboxes

Capacity table
Cooling

EKEXV Class
50
63
80
100
125
140
200
250
400
500

Allowed heat exchanger capacity (kW)


Minimum
5.0
6.3
7.9
10.0
12.4
15.5
17.7
24.7
35.4
49.6

Standard
5.6
7.1
9.0
11.2
14.0
16.0
22.4
28.0
45.0
56.0

Heating

Maximum
6.2
7.8
9.9
12.3
15.4
17.6
24.6
30.8
49.5
61.6

Allowed heat exchanger capacity (kW)

EKEXV Class

Minimum
5.6
7.1
8.9
11.2
13.9
17.4
19.9
27.8
39.8
55.1

50
63
80
100
125
140
200
250
400
500

Saturated evaporating temperature: 6C


Air temperature: 27C DB / 19C WB

Standard
6.3
8.0
10.0
12.5
16.0
18.0
25.0
31.5
50.0
63.0

Maximum
7.0
8.8
11.1
13.8
17.3
19.8
27.7
34.7
55.0
69.3

Saturated condensing temperature: 46C


Air temperature: 20C DB

EKEXV - Expansion valve kit for air handling applications


Ventilation
Dimensions
Unit
Weight
Unit
Sound pressure level Nom.
Operation range On coil
Heating Min.
temperature Cooling Max.
Refrigerant
Type / GWP
Piping connections Liquid
OD

EKEXV
mm
kg
dBA
CDB
CDB

50

63

80

100

125
140
401x215x78
2.9
45
10 (1)
35 (2)

200

250

400

500

12.7

15.9

R-410A / 2.087,5

mm

6.35

9.52

(1) The temperature of the air entering the coil in heating mode can be reduced to -5CDB. Contact your local dealer for more information. (2) 45% Relative humidity.

EKEQ - Control box for air handling applications


Ventilation
Application
Outdoor unit
Dimensions
Weight
Power supply

EKEQ

Unit
Unit
Phase/Frequency/Voltage

mm
kg
Hz/V

FCBA
See note
ERQ / VRV

DCB
Pair
ERQ
132x400x200

3.9

MCBA
Multi
VRV
3.6

1~/50/230

The combination of EKEQFCBA and ERQ is in pair application. The EKEQFCBA can be connected to some type of VRV IV outdoor units with a maximum of 3 control boxes. The combination with DX indoor units,
hydroboxes, RA outdoor units, ... is not allowed. Refer to the combination table drawing of the outdoor unit for details.

256

Controllers

WIRED REMOTE CONTROL


BRC1E52A

Ventilation & Air Handling

INTELLIGENT
TOUCH MANAGER
DCM601A51

INFRARED REMOTE
CONTROLLER
257

Market leading
controls for 2016
INTUITIVE & USER-FRIENDLY INTERFACE
CROSS PILLAR INTEGRATION
CLOUD CONTROL
SMART ENERGY MANAGEMENT
INTEGRATION OF DAIKIN AND THIRD PARTY PRODUCTS

Mini BMS for medium


to large commercial buildings
Price competitive mini BMS
Cross-pillar integration of Daikin products
Integration of third party equipment

via WAGO or BACnet/IP


Connect up to 512 indoor units groups

more information on page 268

Table

Advanced centralised controller


with Cloud connection
Simply control your entire building centrally
Total solution concept (integration of Split, Sky Air, VRV, ventila-

tion, air curtains and hot water)


Stylish optional screen fits any interior
Cloud connection offers additional services

such as online control, energy monitoring, comparison of energy consumption of multiple sites
Connect up to 32 indoor units

more information on page 266

Find out more on www.daikineurope.com

258

Control Systems
Control Systems 
Requirements tables per application

Remote monitoring and maintenance


278

260

Options & Accessories


Individual control systems
Wired / infrared remote controls

262

Wireless room temperature sensor


Wired room temperature sensor
Other integration devices

280
280
281

Centralised control systems


Centralised remote control /
Unified ON/OFF control / Schedule timer
264
DTA113B51265
265
NEW

DCC601A51266
Mini building management system
268

Standard protocol interfaces


Modbus interface
KNX Interface
BACnet Interface
LonWorks Interface

270
273
274
275

Find out more about our control


systems online: www.daikineurope.

Daikin configurator software


EKPCCAB3


276

com/commercial/needs/controls

Network solutions

Screen
Integration

Control

Monitoring

Options

Other

Floor plan
Touch screen
Mini BMS for heating, air conditioning, applied systems and refrigeration units
3rd party equipment integration (BACnet and WAGO)
Basic control functions: on/off, temp setting, air flow settings
Refrigerant containment check
Set point limitation
Setback
Automatic changeover
Weekly schedule and special day pattern
Timer extension
Emergency stop function
Basic control functions: ON/OFF status, operation mode, set point temp. , room temp.
Filter status
Malfunction code
History (operation, malfunction)
Data visualisation
Multi site
PPD
Web access and control
HTTP option
Interlock (Set any preferred logic)
Pre-cool/heat
Sliding temperature
i-Net
Maximum indoor unit groups

(1) Via Daikin Cloud Service

BACNET

Control Systems

intelligent intelligent
Tablet
Touch
LONWORKS
Controller Manager

Type

(1)
(1)
(1)

32

Std

512

64

4x64

259

Control solutions summary

Requirement tables per application


Daikin offers various control solution adapted to the requirements of even the most
demanding commercial application.
Basic control solutions for those customers with few
requirements and limited budget
Integrating control solutions for those customers
that would like to integrate Daikin units into their
existing BMS system

Advanced control solutions for those customers


that expect Daikin to deliver a mini BMS solution,
including advance energy management

NEW

Shop

Unit control
BRC1E52A/B
BRC1E53A/B/C

Automatic control of A/C


Limited control possibilities for shop staff

Integrating control

RTD-20

1 remote
controller for
1 indoor unit
(group)

1 gateway for
1 indoor unit
(group)

Create zones within the shop


Interlock with eg. Alarm, PIR sensor

RTD-Net

KLIC-DI

Advanced control
EKMBDXA

1 gateway for 1 1 gateway for 1 1 gateway for


indoor unit
indoor unit
max. 64 indoor
(group)
unit(s) (groups)
& 10 outdoors

DCM601A51

1 unit for 32
indoor unit(s)

1 iTM for 64
indoor unit(s)
(groups) (1)

Integrate Daikin units into existing BMS via Modbus

DCC601A51

Integrate Daikin units into existing BMS via KNX

(2)
(2)

Monitor energy consumption


Advanced energy management
Allows free cooling
Integrate Daikin products cross pillars
into Daikin BMS

(2)
(2)

Integrate third party products into Daikin BMS


Online control
Manage multiple sites
Floorplan
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via cloud control

Hotel

Unit control
BRC2/3E52C

Integrating control
RTD-HO

1 remote controller
1 gateway for 1
for 1 indoor unit
indoor unit (group)
(group)
Hotel guest can control & monitor basic functionalities from his room
Limited control possibilities for hotel guests
Interlock with window contact
Interlock with key-card
Integrate Daikin units into existing BMS via Modbus

(2)
(2)

DCS601C51

DCM601A51

1 gateway for 1
indoor unit

1 iTC for 64 indoor


unit(s) (groups)

1 iTM for 64 indoor


unit(s) (groups) (1)

Integrate Daikin units into existing BMS via KNX


Integrate Daikin units into existing BMS via HTTP
Monitor energy consumption
Advanced energy management
Integrate Daikin products cross pillars into Daikin BMS
Integrate third party products into Daikin BMS
Online control
Floorplan
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Via BRP7A51/52/53/54 adapter

260

Advanced control

KLIC-DI

Control solutions summary

Office

Unit control
BRC1E52A/B
BRC1E53A/B/C
1 remote
controller for
1 indoor unit
(group)

Automatic control of A/C

Centralised control for management


Local control for office workers
Limited control possibilities for office workers

Integrating control
EKMBDXA

DMS504B51

Advanced control
DMS502A51 /
DAM412B51

1 gateway for
1 gateway for
1 R/C for max.
1 gateway for
max. 64 indoor
128 indoor
64 groups, 128
64 indoor unit(s)
unit(s) (groups)
unit(s) (groups), indoor units, 10
(groups)
& 10 outdoors
20 outdoors (2)
outdoors

(3)

DCS601C51

DCM601A51

1 iTC for 64
indoor unit(s)
(groups)

1 iTM for 64
indoor unit(s)
(groups) (1)

Integrate Daikin units into existing BMS via Modbus

Integrate Daikin units into existing BMS via HTTP

Integrate Daikin units into existing BMS via LonTalk

Integrate Daikin units into existing BMS via BACnet


Energy consumption read out

DCS302C51 /
DST301B51

(4)
(5)

Monitor energy consumption (PPD)


Advanced energy management
Integrate Daikin products cross pillars into Daikin
BMS
Integrate third party products into Daikin BMS
Online control

(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems)
(2) : extension needed to go to 256 indoor unit(s) (groups), 40 outdoors
(3) : ON/OFF only
(4) : with Sky Air pair units only
(5 ): DMS502A51 only

NEW

Infrastructure cooling

Automatic control of A/C


Back-up operation
Duty rotation
Limited control possibilities in the technical cooling room

Unit

Integrating

Advanced

BRC1E53A/B/C

RTD-10

DCM601A51

1 remote
controller for
1 indoor unit
(group) (2)

1 gateway for
1 indoor unit
(group)
Up to 8
gateways
can be linked
together

1 iTM for 64
indoor unit(s)
(groups) (1)

If room temperature above max., then show alarm & start standby
unit.
If an error occurs, an alarm will be shown.

Control Systems

launch Spring
2016

(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Infrastructure cooling functions only
compatible with indoor units connected to Seasonal Smart outdoor units.

261

Individual control systems


BRC1E52A/B

User friendly remote control with contemporary design


A series of energy saving functions that
can be individually selected

Graphical display of indicative


electricity consumption

Temperature range limit


Setback function
Presence & floor sensor connection
(available on round flow and fully flat cassette)
kWh indication (1)
Set temperature auto reset
Off timer

Temperature range limit avoids excessive


heating or cooling

(Function available in
combination with FBQ-D,
FCQG and FCGHQ)

Save energy by constraining the lower temperature


limit in cooling and upper temperature limit in
heating mode.
note : Also available in auto cooling/heating change over mode.

kWh indication keeps track of


your consumption(1)
The kWh indication shows an indicative electricity
consumption of the last day/month/year.

BRC1E53A/B/C

Other functions
Up to 3 independent schedules can be set,
so the user can easily change the schedule himself
throughout the year (e.g. Summer, winter, mid-season)
Possibility to individually restrict menu functions
Easy to use: all main functions directly accessible
Easy setup: clear graphical user interface for
advanced menu settings
Real time clock with auto update to daylight
saving time
Built-in backup power: when a power failure occurs
all settings remain stored
Supports multiple languages:
English, German, Dutch, Spanish, Italian, Portuguese,
French, Greek, Russian, Turkish, Polish (BRC1E52A)
English, German, Czech, Croatian, Hungarian,
Romanian, Slovenian, Bulgarian, Slovak, Serbian and
Albanian (BRC1E52B)

(1) for Sky Air FBQ-D, FCQG and FCQHG pair combinations only

COMING
SPRING 2016

User friendly remote control incl. infrastructure cooling functions


Replaces BRC1E52A/B in Spring 2016 and includes
following additional functionalities:
Duty rotation and back-up for infrastructure
cooling
Remote control save mode : screen will turn off
when unit is OFF
Demand control: decreases the power
consumption to 70 or 40 % when other large
applicances need to be switched on
Selection of quiet mode function for the outdoor
unit

Choice between standard and symbol driven


display
Supports multiple languages:

BRC1E53A: English, German, French, Dutch,


Spanish, Italian, Portugese
BRC1E53B: English, Czech, Croation, Hungarian,
Romanian, Slovenian, Bulgarian
BRC1E53C: English, Greek, Russian, Turkish,
Hungarian, Slovak, Albanian

BRC2E52A / BRC3E52A

Simplified wired remote control developed for hotel applications


Symbol driven interface for intuitive control
Functions restricted to basic customer needs
Contemporary design
Energy saving thanks key card, window contact

integration (BRP7A51) and set point limitation


Flexible setback function ensures room temperaBRC2E52A

ture remains within comfortable limits to ensure


guest comfort

Heat recovery type

Key card and


window contact
integration

BRC3E52A
Heat pump type

262

P1 P2

Flat backpanel for easy installation


Easy commissioning: intuitive interface

for advanced menu settings


2 versions available:
Heat pump type: temperature, fan speed, ON/
OFF
Heat recovery type: temperature, mode, fan
speed, ON/OFF
Replaces existing BRC2C51 & BRC3A61

Adaptator
(BRP7A51)

Key card (field supply)

Window contact
(field supply)

Individual control systems

BRC073

Wired remote control


for residential use

BRC073

Fo
comb r
ina
with S tion
pli
indoo t
r
units

User friendly remote control with


contemporary design
Easy to use: all main functions directly accessible
Easy commissioning: intuitive interface
for advanced menu settings
Optimise your air conditioning system by activating
a series of energy saving functions (temperature
range limit, setback function, off timer, )
Set up to 3 independent schedules, so the user can
easily change the schedule himself throughout
the year (e.g. summer, winter, mid-season)
Real time clock with auto update to daylight
saving time

Supports multiple languages (English, German,


French, Italian, Spanish, Portuguese, Dutch,
Czech, Croatian, Hungarian, Slovenian, Romanian,
Bulgarian, Russian, Greek, Turkish, Polish, Serbian
and Slovak) (depending on language package)
Possibility to individually restrict:
menu fucntions
buttons
operation modes
When a power failure occurs all settings
remain stored thanks to the built-in backup power
Setback operation maintains the indoor
temperature at your specified comfort level during
absence, thus saving energy
Note : Cable for wired remote control BRCW901A03 (3m) or
BRCW901A08 (8m) required

BRC1D52

Wired remote control


Display
Operating mode
Heat Recovery Ventilation (HRV) in operation
Cool / heat changeover control
Centralised control indication
Group control indication
Set temperature
Air flow direction
Programmed time
Inspection test / operation
Fan speed
Clean air filter
Defrost / hot start
Malfunction
Control Systems

BRC1D52

Schedule timer:
Five day actions can be set as follows:
-- set point: unit is switched ON and normal
operation is maintained
-- OFF: unit is switched OFF1
-- limits: unit is switched ON and min./max. control
(cf. limit operation for more details)
Home leave (frost protection): during absence, the
indoor temperature can be maintained at a certain
level. This function can also switch the unit ON/OFF
User friendly HRV function, thanks to
the introduction of a button for ventilation mode
and fan speed
Immediate display of fault location and condition
Reduction of maintenance time and costs

ARC4*/BRC4*/BRC7*

Infrared remote control


Operation buttons: ON/OFF, timer mode start/stop,
timer mode on/off, programme time, temperature
setting, air flow direction (1), operating mode, fan
speed control, filter sign reset (2), inspection (2)/test
indication (2)
Display: Operating mode, battery change, set
temperature, air flow direction (1), programmed time,
fan speed, inspection/test operation (2)
ARC466A1

1. Not applicable for FXDQ,


FXSQ, FXNQ, FBDQ, FDXS, FBQ
2. For FX** units only
3. For all features of the remote
control, refer to the operation
manual

BRC4*/BRC7*

263

Centralised control systems

Centralised control of the Sky Air and VRV system can be achieved via 3 user friendly compact remote
controllers. These controls may be used independently or in combination with 1 group = several (up to 16)
indoor units in combination and 1 zone = several groups in combination.
A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation,
enabling indoor units to be classified in groups per tenant (zoning).
The schedule timer programmes the schedule and operation conditions for each tenant and the control can
easily be reset according to varying requirements.

DCS302C51

Centralised remote control


Providing individual control of 64 groups (zones) of indoor units.
a maximum of 64 groups (128 indoor units, max. 10 outdoor

units) can be controlled


a maximum of 128 groups (128 indoor units, max. 10 outdoor

units) can be controlled via 2 centralised remote controls in


separate locations
zone control
group control
malfunction code display
maximum wiring length of 1,000m (total: 2,000m)
air flow direction and air flow rate of HRV can be controlled
expanded timer function

DST301B51

Schedule timer
Enabling 64 groups to be programmed.
a maximum of 128 indoor units can be controlled
8 types of weekly schedule
a maximum of 48 hours back up power supply
a maximum wiring length of 1,000m (total: 2,000m)

DCS301B51

Unified ON/OFF control


Providing simultaneous and individual control of 16 groups
of indoor units.
a maximum of 16 groups (128 indoor units) can be controlled
2 remote controls in separate locations can be used
operating status indication (normal operation, alarm)
centralised control indication
maximum wiring length of 1,000m (total: 2,000m)

264

Centralised control systems

DTA113B51
Basic solution for control of Sky Air and VRV in infrastructure cooling applications
adapter - DTA113B51

Rotation function
Backup operation function.

BRC1E53A/B/C
Up to 4 units (groups)/ 1 adapter

DCS601C51
Detailed & easy monitoring and operation of VRV systems (max. 64 indoor units groups).

third party controller (domotics, BMS, etc.) via http interface

Fire alarm

Ethernet
Forced OFF contact input

DIII-NET
Indoor units

HRV

DCS601C51

System layout
Up to 64 indoor units can be

controlled
Touch panel (full colour LCD

via icon display)

Control
Individual control

(set point, start/stop,


fan speed)
(max. 64 groups/indoor units)
Set back shedule
Enhanced scheduling function
(8 schedules, 17 patterns)
Flexible grouping in zones
Yearly schedule
Fire emergency stop control
Interlocking control
Increased HRV monitoring
and control function
Automatic cooling / heating
change-over
Heating optimization
Temperature limit
Password security: 3 levels
(general, administration
& service)
Quick selection and full
control
Simple navigation

Monitoring
Visualisation via Graphical

User Interface (GUI)


Icon colour display change

function
Indoor units operation mode
Indication filter replacement
Multi PC
Cost performance
Free cooling function
Labour saving
Easy installation
Compact design: limited

Open interface
Communication to any third

party controller (domotics,


BMS, etc.) is possible via
open interface (http option
DCS007A51)
Connectable to
VRV
HRV
Sky Air
Split (via interface adapter)

installation space
Overall energy saving

265

Control Systems

Languages
English
French
German
Italian
Spanish
Dutch
Portuguese

NEW Centralised control systems


Table

DCC601A51

Advanced

Intuitive and user-friendly interface


Flexible concept for stand alone

centralised
controller

and multi site applications


Total solution thanks to
integration of 3rd party equipment
Monitor & control your small
commercial building, no matter

with Cloud connection

where you are

2 solutions:
Local solution
Offline centralised control

Cloud solution
Flexible online control from any device (Laptop,

via stylish optional screen

tablet...)

Stylish interface fits any interior

Monitor & control one or multiple sites


Benchmark the energy consumption of different

installations
Energy consumption follow-up to comply

with local regulations

System layout
Local solution

Online control from any device

Alarm

Window
contact
Daikin supplied screen
(optional) (for local control)

Pulse input

Z380C-1A023A

or
Digital input

Local network
Daikin supplied router
(optional) 4G-N12

Table

DCC601A51

WAGO power
supply

CPU module

I/O module

Split,
,
VAM, ventilation,
air curtains
266

Centralised control systems NEW

Total solution
Total solution thanks to a large integration of

Daikin products and 3rd party equipment


Connect a wide range of Daikin units (Split, Sky Air,

VRV, Ventilation, air curtains)

From one to sites

Simply control your entire building centrally


Increased customer shopping experience by bet-

ter management of your shop comfort level

Daikin Cloud Services

LOCAL
CONTROL

Control your building no matter where you are


Monitor and control multiple sites
Installer or technical manager can remotely login

to the site in case of malfunctions for first


troubleshooting
Benchmark the energy consumption
of different installations
Manage & track your energy use
Monitor the long time operating units to keep
the consumption under control

DAIKIN CLOUD
SERVICE

Installer/
technical manager

Customer

User friendly touch control


Stylish Daikin supplied optional screen

for local control fits any interior


Intuitive and user-friendly interface
Full solution with simple control
Easy commissioning

Flexible
Inputs via digital and pulse input for 3rd party

equipment such as kWh meters, emergency


input, window contact,
Modular concept allows your cloud to grow
with your business
Control up to 32 indoor unit groups , with a maximum of 32 indoor units

Pulse input
Digital input

Indoor uit

Functions overview

System layout

Local solution

Cloud solution

32

32

EN, FR, DE, IT, ES, NL, PT


N of connectable indoor units

Control Systems

Languages

Multiple sites control


Monitoring &
control

Basic control functions (ON/OFF, mode, filter sign, setpoint, fan


speed, ventilation mode, room temperature, )
Remote control prohibition
All devices ON/OFF
Group control
Weekly schedule
Interlock control
Set point limitation
Visualisation of energy use per operation mode
Error e-mail

Connectable to

DX split, Sky Air, VRV


VAM, VKM ventilation
Air curtains

267

Check on
https://www.youtube.com/
DaikinEurope

DCM601A51

Mini BMS

Price competitive mini BMS


Cross-pillar integration of Daikin products
Integration of third party equipment

with full integration


across all product pillars
System overview

Web Access

CLOUD
Internet
Extranet
LAN
3G

Integration of third
party equiqment

Full control of Daikin


HVAC-R portfolio
DCM601A51

ITM plus adaptor line

Max. 7
adapters

Di/Pi line

Fire alarm

Max. 200m

DCM601A52
Di/Pi port

kWh meter

Direct plug & play connection!


Split

I/O module

Pump

Sensor

Multi state objects

Elevator

268

Air handling unit

Alarm

I/O module

Fan

air curtain,
hydrobox,

Analog/digital/pulse objects

Lighting

indoor units,

air handling units

Refrigeration

WAGO
interface

Chillers and AHU

protocol

Fan coil units

BACnet/IP

User friendliness

Intuitive user interface


Visual lay out view and direct access to indoor unit

main funtions
All functions direct accessible via touch screen

or via web interface

Smart energy management


Monitoring if energy use is according to plan
Helps to detect origins of energy waste
Powerful schedules guarantee correct operation

Plug & play

throughout the year


Save energy by interlocking A/C operation with

other equipment such as heating

Flexibility
Split

Fan coils

Chillers and AHU

Refrigeration

Cross-pillar integration (heating, air conditioning,

applied systems, refrigeration, air handling units)


BACnet protocol for 3rd party products integration
I/O for integration of equipment such as lights,

BACnet/IP
protocol

pumps on WAGO modules


Modular concept for small to large applications
Control up to 512 indoor unit groups via one ITM
and combine multiple ITM via web interface

Lighting
Lighting

Sensor
Pump

Fan

Sensor

Air handling
unit

Elevator

Alarm

WAGO I/O

Easy servicing and commissioning

Lighting

Pump

Fan

Sensor

Remote refrigerant containment check reducing

on site visit
Simplified troubleshooting
Save time on commissioning

Flexibility in size

thanks to the pre-commissioning tool


Auto registration of indoor units

64 up to 512 groups

Functions overview

English

Management

Control

French

Web access

Individual control

German

Power Proportional

Italian
Spanish
Dutch
Portuguese

Distribution (option)
Operational history
(malfunctions, )

(512 groups)
Schedule setting (Weekly

Connectable to
- DX Split, Sky Air, VRV
- Chillers
(via POL638.70 controller)
- Daikin AHU

schedule, yearly calender,

- Fan coils

seasonal schedule)

- Daikin Altherma Flex type

Interlock control

- LT and HT hydroboxes

- monitor if energy use is

Setpoint limitation

- Biddle Air curtains

System layout

according to plan

Temperature limit

- WAGO I/O

Up to 512 unit groups can be

- detect origins of energy

controlled

Smart energy management

waste

(ITM plus Integrator + 7 iTM

Setback function

Plus adapters)

Sliding temperature

- BACnet/IP protocol

WAGO Interface
Modular integration of 3rd
party equipment
- WAGO coupler (interface
between WAGO and iTM)
- Di module
- Do module
- Ai module
- Ao module
- Thermistor module
- Pi module

269

Control Systems

Languages

Standard protocol interfaces

Modbus Interface
RTD

RTD-RA
Modbus interface for monitoring and control
of residential indoor units

RTD-NET
Modbus interface for monitoring and control
of Sky Air, VRV, VAM and VKM

RTD-10
Advanced integration into BMS of Sky Air, VRV,
VAM and VKM through either:
- Modbus
- Voltage (0-10V)
- Resistance
Duty/standby function for server rooms

RTD-20
Advanced control of Sky Air, VRV, VAM/VKM
and air curtains
Clone or independent zone control
Increased comfort with integration of CO2 sensor
for fresh air volume control
Save on running costs via
- pre/post and trade mode
- set point limitation
- overall shut down
- PIR sensor for adaptive deadband

RTD-HO
Modbus interface for monitoring and control of
Sky Air, VRV, VAM and VKM
Intelligent hotel room controller

RTD-W
Modbus interface for monitoring and control of
Daikin Altherma Flex Type, VRV HT hydrobox and
small inverter chiller

270

Overview functions

Main functions

RTD-RA

Dimensions
HxWxD
mm
Key card + window contact
Set back function
Prohibit or restrict remote control functions (setpoint limitation, ...)
Modbus (RS485)
Group control
0 - 10 V control
Resistance control
IT application
Heating interlock
Output signal (on/defrost, error)
Retail application
Partitioned room control
Air curtain

RTD-NET

RTD-10

80 x 80 x 37,5

RTD-20
100 x100 x 22

(1)

**

***

***

****

RTD-HO

(1): By combining RTD-RA devices

Control functions

RTD-RA

RTD-NET

RTD-10

RTD-20

RTD-HO

On/Off
Set point
Mode
fan
Louver
HRV Damper control
Prohibit/Restrict functions
Forced thermo off

M,C
M
M
M
M

M
M
M
M
M
M
M

M,V,R
M,V,R
M,V,R
M,V,R
M,V,R
M,V,R
M,V,R

M
M
M
M
M
M
M

M*
M*
M*
M*
M*
M*

RTD-RA

RTD-NET

RTD-10

RTD-20

RTD-HO

M
M
M
M
M

M
M
M
M
M
M
M
M
M
M
M
M
M
M
M

M
M
M
M
M
M
M
M
M
M
M
M
M
M
M

M
M
M
M
M
M
M
M
M
M
M
M
M
M
M

M
M
M
M
M
M
M
M
M
M
M
M
M
M
M

M
M

Monitoring functions
On/Off
Set point
Mode
fan
Louver
RC temperature
RC mode
nbr units
Fault
Fault code
Return air temperature (Average /Min/Max)
Filter alarm
Termo on
Defrost
Coil In/Out temperature

M
M
M
M
M

Main functions
Dimensions
On/off prohibition
Modbus RS485
Dry contact control
Output signal (operation error)
Space heating / cooling operation
Domestic hot water control
Smart Grid control

RTD-W
HxWxD

mm

100x100x22

Control functions
On/Off Space heating/cooling
Set point leaving water temperature (heating / cooling)
Room temperature setpoint
Operation mode
Domestic Hot water ON
Domestic Hot Water reheat
Domestic Hot Water reheat setpoint
Domestic Hot Water storage
Domestic Hot Water Booster setpoint
Quiet mode
Weather dependent setpoint enable
Weather dependent curve shift
Fault/pump info relay choice
Control source prohibition

M,C
M,V
M
M
M,C
M
M,C
M
M
M

Smart grid mode control

Monitoring functions

On/Off Space heating/cooling


Set point leaving water temperature (H/C)
Room temperature setpoint
Operation mode
Domestic Hot Water reheat
Domestic Hot Water storage
Number of units in the group
Average leaving water temperature
Remocon room temperature
Fault
Fault code
Circulation pump operation
Flow rate
Solar pump operation
Compressor status
Desinfection operation
Setback operation
Defrost/ start up
Hot start
Booster Heater operation
3-Way valve status
Pump running hours accumulated
Compressor running hours accumulated
Actual leaving water temperature
Actual return water temperature
Actual DHW tank temperature (*)
Actual refrigerant temperature
Actual outdoor temperature

M,C
M
M
M
M
M
M
M
M
M,C
M
M

M
M
M
M

M
M
M

Control Systems

Prohibit Space heating/cooling


Prohibit DHW
Prohibit Electric heaters
Prohibit All operation
PV available for storage
Powerful boost

M : Modbus / R : Resistance / V : Voltage / C: control


* : only when room is occupied / ** : setpoint limitation / (*) if available
*** : no fan speed control on the CYV air curtain / **** : run & fault

271

Standard protocol interfaces

DIII-net Modbus interface


EKMBDXA
Integrated control system for seamless connection between
Split, Sky Air, VRV and small inverter chillers and BMS systems
Communication via Modbus RS485 protocol
Detailed monitoring and control of the VRV total solution
Easy and fast installation via DIII-net protocol
As the Daikin DIII-net protocol is being used, only one modbus interface is needed for a group of Daikin systems (up to 10 outdoor unit
systems).

VRV network
DIII- NET

EKMBDXA

VRV Outdoor unit

Biddle air curtain


*via EKEQ box

HRV
up to 64 units connectable per interface

Sky Air network*

Split network*

KRP928BB2S

Small inverter chiller network

Building
control
network

Fire alarm

Security

Power supply facility

Lighting

Pump

* Additional centralized controller might be required. For more information contact your local dealer.
EKMBDXA7V1
Maximum number of connectable indoor units
Maximum number of connectable outdoor units
Communication
DIII-NET - Remark
Protocol - Remark
Protocol - Type
Protocol - Max. Wiring
length
Dimensions
HeightxWidthxDepth
Weight
Ambient temperature - operation
Max.
Min.
Installation
Power supply
Frequency
Voltage

272

64
10
DIII-NET (F1F2)
2 wire; communication speed: 9600 bps or 19200 bps
RS485 (modbus)
m
mm
kg
C
C
Hz
V

500
124x379x87
2.1
60
0
Indoor installation
50
220-240

Elevator

Standard protocol interfaces

KNX interface
KLIC-DD
KLIC-DI

Integration of Split, Sky Air and VRV in HA/BMS systems


Connect split indoor units to KNX interface
for Home Automation system

Concept

light

house
Domotica

shutter control

Controller

Interface Daikin protocol/ KNX

tv

Connect Sky Air / VRV indoor units to


KNX interface for BMS integration
light

Concept

shop
shutter control

Domotica

tv

Controller

Interface Daikin protocol/ KNX

KNX interface line-up


The integration of Daikin indoor units through
the KNX interface allows monitoring and control
of several devices, such as lights and shutters, from
one central controller. One particularly important
feature is the ability to programme a scene
- such as Home leave - in which the end-user selects

a range of commands to be executed simultaneously


once the scenario is selected. For instance in
Home leave , the air conditioner is off, the lights are
turned off, the shutters are closed and the alarm is on.

KLIC-DD Size 45x45x15mm


Split
Basic control
On/Off
Mode
Temperature
Fan speed levels
Swing
Advanced functionalities
Error management
Scenes
Auto switch off
Temperature limitation
Initial configuration
Master and slave configuration

Sky Air

Control Systems

KNX interface for

KLIC-DI Size 90x60x35mm


VRV

Auto, heat, dry, fan, cool

Auto, heat, dry, fan, cool

Auto, heat, dry, fan, cool

3 or 5 + auto
Stop or movement

2 or 3
Stop or movement

2 or 3
Swing or fixed positions (5)

Communication errors, Daikin unit errors

273

Standard protocol interfaces

BACnet Interface
DMS502A51 / EKACBACMSTP / EKCMBACIP / EKCMBACMSTP
Integrated control system for seamless connection between VRV,
applied systems, air handling units and BMS systems
BMS

Interface for BMS system


Communication via BACnet protocol
(connection via Ethernet)
Unlimited sitesize
Easy and fast installation
PPD data is available
on BMS system (only for VRV)

VRV network

BACNET / ETHERNET

DIII- NET

DMS502A51

Local Control
VRV Outdoor unit

HRV
up to 256 units connectable per interface
Remote Control

Applied systems network


Serial Card
BACnet MSTP

EKACBACMSTP
Serial sequencing
panel

EKCM200J

EKCM200J

EKCM200J

EKDSSP-S

Air handling unit network

EKCMBACIP
EKCMBACMSTP

Fire alarm

Security

Pump

Lighting

Power supply facility

Building
control
network

274

Elevator

Standard protocol interfaces

LonWorks Interface
DMS504B51 / EKACLONP
Open network integration of VRV and applied systems
monitoring and control functions into LonWorks networks
LON BMS

VRV network

adapter

LonTalk

DIII- NET

ETHERNET (TCP/IP)

DMS504B51

Local Control
VRV
Outdoor
unit

HRV

up to 64 units connectable per interface

Remote Control

Applied systems network


Serial card
LON FTT 10
adapter

LonTalk
EKACLONP
Serial sequencing
panel

EKCM200J

EKCM200J

EKCM200J

EKDSSP-S

adapter

LonTalk
LonPoint

LonPoint

Security

Fire alarm

Control Systems

Interface for Lon connection to


LonWorks networks
Communication via Lon protocol
(twisted pair wire)
Unlimited sitesize
Quick and easy installation

Building
control
network

System

275

Daikin Configurator Software

Daikin Configurator Software


EKPCCAB3
Simplified commissioning:
graphical interface to configure, commission
and upload system settings

Simplified commissioning
The Daikin configurator for Daikin Altherma and
VRV is an advanced software solution that allows for
easy system configuration and commissioning:

Less time is required on the roof configuring


the outdoor unit
Multiple systems at different sites can be managed
in exactly the same way, thus offering simplified
commissioning for key accounts
Initial settings on the outdoor unit can be easily
retrieved

276

Simplified

Retrieve initial

commissioning

system settings

277

Control Systems

What is I-Net?

A service based on our global remote


monitoring technology, keeping your system
trouble-free and working with top efficiency.
CLOUD

I-Net
performance monitoring
and analysis

24/7

What does I-Net offer you

I-Net Services

Safeguarding the lifelong optimum operation of


your air conditioning system means getting geared
up to operate the system in a energy efficient way
and reduce unexpected breakdowns and costs to
the absolute minimum. This is where I-Net helps
to improve the effectiveness of your building
management.

i-Net consists of 2 main services: the VRV Cloud and


I-Net performance monitoring and analysis.

I-Net is about being connected with Daikin,


the Internet-based link between you, your air
conditioning system and Daikins Remote Monitoring
Centre. This allows you to monitor your energy
consumption and Daikins expert service engineers to
monitor your entire systems status non-stop, all year
round. Through predicting malfunctions and offering
technical advice from data analysis, you can maximise
equipment uptime, as well as controlling energy
costs with no sacrifice in comfort levels. By doing this,
i-Net will prevent problems, prolong your systems
service life while reducing the energy bill.

278

VRV Cloud
The VRV Cloud puts you in the driving seat of your
energy management. The easy-to-use energy data
trending and analytic tools puts you in control and
shows you CO2 footprint reduction opportunities
and energy savings of up to 15%.
Saving starts by measuring. Enhance your companys
sustainability !

I-Net performance monitoring and analysis


Focus on your core business and hand the HVAC
over to Daikin. Daikin I-Net connects your system
continuously with Daikin. It notifies alarms and
early warnings of system deviations to maximise
system uptime and the comfort of the people in the
building. Service providers have webbased access to
operation data so that they are fully prepared when
they arrive on-site. Specialists run trend analyses.
All of which boosts your systems reliability by
ensuring that it is running at optimum efficiency.

Data server

Performance supervision

Internet

and analysis

24/7
Prediction analysis
Data trend logging

Information to:

customers
service company

CLOUD

Controller

Monitor your energy


managment.

Connection with I-Net via


ITM, PCASO, ...

Helps you manage your energy through Daikin


technology.
Intelligent energy visualization tool that helps you
with your energy management
24/7 online monitoring by the customer from any
location.
User friendly visualization of VRV energy
management (kWh)
Analysis support of waste operation
Multiple site monitoring

Performance monitoring
Daikins unique I-Net Service aims to prevent
the equipment coming to an unexpected stop or
needing emergency repair.

Fast response, better prepared


If an alarm does occur, the service provider is
immediately alerted and receives all crucial
information.
Early fault indication (predictions) : operation data
are 24/7 checked by I-Net prediction algorithms
to act as early as possible, averting unscheduled
breakdowns.

Performance Supervision by Daikin experts


enhances a maintenance plan.
This service aims to enhance the service level, to
respond fast and accurate, to save on unexpected
repair costs and assure the peace of mind.
Repetitive interventions and disturbance of building
tenants and maintenance teams are kept to a
minimum.

Long lifetime systems


I-Net will maximise the installations lifetime, by
assuring the equipment runs in optimal conditions
and avoid unnecessary stress on components.

Analysis

Control Systems

Daikin VRV Cloud

Be connected with Daikins experts, this gives you


a clear overview of operability and use of the air
conditioning system.
Daikin continuously monitors energy, operation
and comfort data. Thanks to periodic analysis of
the data, Daikin can suggest ways of improving
performance.
if there is a problem, Daikin specialists will analyse
the operation data history to provide remote
support.

279

Room sensors

Wireless room temperature sensor


K.RSS

Flexible and easy installation


Accurate temperature measurement thanks to flexible

placement of the sensor


No need for wiring
No need to drill holes
Ideal for refurbishment

Connection diagram Daikin indoor unit PCB (FXSQ-P example)


Power supply X35, X13

Air sensor X16A, X19

Rf Receiver

RF sender

Specifications
Dimensions
Weight
Power supply
Battery life
Battery type
Maximum range
Operation range
Communication

mm
g

m
C
Type
Frequency

MHz

Wireless room temperature sensor kit (K.RSS)


Wireless room temperature receiver
Wireless room temperature sensor
50 x 50
75
40
60
16VDC, max. 20 mA
N/A
N/A
+/- 3 years
N/A
3 Volt Lithium battery
10
0~50
RF
868.3

Room temperature is sent to the indoor unit every 90 seconds or if the temperature difference is 0.2C or larger.

Wired room temperature sensor


KRCS01-1B
KRCS01-4B

Accurate temperature measurement,

thanks to flexible placement of the sensor

Specifications
Dimensions (HxW)
Weight
Length of branch wiring

280

mm
g
m

60 x 50
300
12

Other integration devices

ADAPTER PCBs
Simple solutions for unique requirements
Concept and benefits

Low cost option to satisfy simple control


requirements
Deployed on single or multiple units

Connectable to:
Split

(E)KRP1B*
adapter for wiring

KRP2A*/KRP4A*
Wiring adapter for
electrical appendices

KRP58M3

SB.KRP58M51

KRP58M51

Sky Air

VRV

Facilitates integration of auxiliary heating apparatus, humidifiers, fans, damper


Powered by and installed at the indoor unit

Remotely start and stop up to 16 indoor units (1 group) (KRP2A* via P1 P2)
Remotely start and stop up to 128 indoor units (64 groups) (KRP4A* via F1 F2)
Alarm indication/ fire shut down
Remote temperature setpoint adjustment
Cannot be used in combination with a central controller

Low noise and demand control option for RZQ200/250C

Low noise and demand control option for RZQG and RZQSG single phase
Includes mounting plate EKMKSA1

Low noise and demand control option for RZQG1 and RZQSG 3 phase

DTA104A*
Outdoor Unit External
Control Adapter

Individual or simultaneous control of VRV system operating mode


Demand control of individual or multiple systems
Low noise option for individual or multiple systems

DCS302A52
Unification adapter for
computerized control

KRP928*

Enables unified display (operation/malfunction) and unified control (ON/OFF) from BMS system
Must be used together with Intelligent Touch Controller or intelligent Touch Manager
Cannot be combined with KRP2/4*
Can be used for all VRV indoor models

Allows integration of split units to Daikin central controls


External contacts for monitoring/control

KRP413*
Wiring adapter normal
open contact / normal
open pulse contact

KRP980*
Adapter for split units
without an S21 port

Connect a wired remote control


Connect to Daikin central controls
Allow external contact

Interface adapter for


DIII-net

Switch off auto restart after power failure


Indication of operation mode / error
Remotely start /stop
Remotely change operation mode
Remotely change fan speed

Control Systems

Some adapters require an installation box, refer to the option lists for more information

Accessories
EKRORO

External ON/OFF or forced off


Example: door or window contact

EKRORO 3

External ON/OFF or forced off


F1/F2 contact
Example: door or window contact

KRC19-26A

Mechanical cool/heat selector


Allows switching over an entire system between cooling/heating/fan only
Connects to the A/B/C terminals of the unit

BRP2A81

Cool/heat selector PCB


Required to connect KRC19-26A to a VRV IV outdoor unit

281

Options & accessories

AUTO-CLEANING PANEL

FILTERS

INTELLIGENT SENSORS

282

Options &
accessories
284
288
292
294
296

Options & Accessories

VRV outdoor
VRV indoor
Stylish indoor
Ventilation & Hot Water
Control Systems

283

Options & accessories -

outdoor

Multi-module connection kit (obligatory) - Connects multiple modules into a single


refrigerant system

VRV IV Heat Recovery


REYQ 8~12T

REYQ 14~20T

REMQ5T

2-module systems

3-module systems

BHFQ23P907

BHFQ23P1357

Extended level difference kit - Allows outdoor unit to be more than 50m
above indoor units
Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain
water from all bottom plate outlets into a single outlet. In cold areas should be heated by
a field-supplied heater to prevent drain water from freezing in the drain pan.
Heater tape kit - Optional electrical heater to guarantee trouble-free operation in
extremely cold and humid climates (one per outdoor unit needed)
External control adapter for outdoor unit - Allows to activate Low Noise Operation and
three levels of demand control, limiting power consumption via external dry contacts.
Connects to the F1/F2 communication line and requires power supply from an indoor unit*,
BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating pressures in the
system as Standard, or expansion valve positions and temperature sensor data in a special
service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or one BS-box
of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C
terminals of the outdoor unit / BS-box.
EBRP2B - Cool/heat selector PCB
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560*
Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and
Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKCHSC - Cool/heat selector cable
EKPCCAB3
VRV configurator
BPMKS967A2/A3
Branch provider (for connection of 2/3 RA indoor units)
EKDK04
Drain plug kit
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
DTA109A51
DIII-net expander adapter

Special order unit


-

EKBPH012T +
EKBHPCBT

EKBPH020T +
EKBHPCBT

EKBPH012T +
EKBHPCBT

DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units

1 kit
per system

1 kit
per system

VRV IV S-series
RXYSCQ-T

RXYSQ4-6TV1

RXYSQ4-6TY1

RXYSQ8-12TY1

Multi-module connection kit (obligatory) - Connects multiple modules into a single


refrigerant system

Extended level difference kit - Allows outdoor unit to be more than 50m
above indoor units

Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain
water from all bottom plate outlets into a single outlet. In cold areas should be heated by
a field-supplied heater to prevent drain water from freezing in the drain pan.

Heater tape kit - Optional electrical heater to guarantee trouble-free operation in


extremely cold and humid climates (one per outdoor unit needed)

External control adapter for outdoor unit - Allows to activate Low Noise Operation and
three levels of demand control, limiting power consumption via external dry contacts.
Connects to the F1/F2 communication line and requires power supply from an indoor unit*,
BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating pressures in the
system as Standard, or expansion valve positions and temperature sensor data in a special
service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or one BS-box
of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C
terminals of the outdoor unit / BS-box.
EBRP2B - Cool/heat selector PCB
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560*
Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and
Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKCHSC - Cool/heat selector cable
EKPCCAB3
VRV configurator
BPMKS967A2/A3
Branch provider (for connection of 2/3 RA indoor units)
EKDK04
Drain plug kit
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
DTA109A51
DIII-net expander adapter

284

VRV IV with continuous heating

VRV IV without continuous heating

RYYQ8-12T

RYYQ14-20T

RYMQ8-12T

RYMQ14-20T

2-module systems 3-module systems

BHFQ22P1007

EKBPH012T + EKBPHPCBT EKBPH020T + EKBPHPCBT EKBPH012T + EKBPHPCBT EKBPH020T + EKBPHPCBT

RXYQ8-12T (9)

RXYQ14-20T

2-module systems 3-module systems

BHFQ22P1517

BHFQ22P1007

BHFQ22P1517

EKBPH012T
+ EKBPHPCBT

EKBPH020T
+ EKBPHPCBT

DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units

1 kit
per system

1 kit
per system

1 kit
per system

1 kit
per system

VRV IV i-series
SB.RKXYQ

VRV III-C Cold Region VRV

VRV Classic

RDXYQ5

RKXYQ5

RTSYQ 10PA

RTSYQ 14~16PA

RTSYQ 20PA

RXYCQ8A

RXYCQ10-14A

RXYCQ16-20A

BHFQ22P1007

KWC26B280

KWC26B450

2x KWC26B280

KWC26B160

KWC26B280

KWC26B450

EKDPRH1RDX

BEH22A10Y1L

BEH22A18Y1L

2x BEH22A10Y1L

Options & Accessories

DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units

285

Options & accessories -

outdoor
VRV IV-Q Heat Pump Replacement VRV
RQYQ 140P

RXYQQ8-12T

RXYQQ14-20T

2-module systems

3-module systems

Multi-module connection kit (obligatory)


Connects multiple modules into a single refrigerant system

BHFQ22P1007

BHFQ22P1517

Central drain pan kit - Installs onto the underside of the outdoor unit and collects
drain water from all bottom plate outlets into a single outlet. In cold areas should
be heated by a field-supplied heater to prevent drain water from freezing in the
drain pan.

KWC26B160

Heater tape kit - Optional electrical heater to guarantee trouble-free operation in


extremely cold and humid climates (one per outdoor unit needed)

EKBPH012T +
EKBPHPCBT

EKBPH020T +
EKBPHPCBT

External control adapter for outdoor unit - Allows to activate Low Noise
Operation and three levels of demand control, limiting power consumption via
external dry contacts. Connects to the F1/F2 communication line and requires
power supply from an indoor unit*, BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating
pressures in the system as Standard, or expansion valve positions and
temperature sensor data in a special service mode. Connect to the outdoor unit
PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or
one BS-box of a Heat Recovery system between cooling, heating and fan only.
Connects to the A-B-C terminals of the outdoor unit / BS-box.
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560* - Cool/heat selector PCB mounting plate (only required when cool/
heat selector PCB and Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKPCCAB3
VRV configurator
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor
units.
DTA109A51
DIII-net expander adapter

Heat Recovery systems (3-pipe)

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

Refnet Joints
Capacity index
Capacity index
200 x < 290
290 x < 640

Capacity index
> 640

Capacity index
< 290

Refnet Headers
Capacity index
290 x < 640

KHRQM23M20T

KHRQM23M29T

KHRQM23M64T

KHRQM23M75T

KHRQM23M29H

KHRQM23M64H

KHRQ23M20T

KHRQ23M29T9

KHRQ23M64T

KHRQ23M75T

KHRQ23M29H

KHRQ23M64H

Sound reduction kit (sound insulation)

Mechanical cool/heat selector allows to switch an entire Heat Pump system, or


one BS-box of a Heat Recovery system between cooling, heating and fan only.
Connects to the A-B-C terminals of the outdoor unit / BS-box.

Installation box for remote cool/heat selector KRC19-26

Closed pipe kit

Joint kit

Quiet kit

KHRQM22M20T

KHRQM22M29T

KHRQM22M64T

KHRQM22M75T

KHRQM22M29H

KHRQM22M64H

KHRQ22M20T

KHRQ22M29T9

KHRQ22M64T

KHRQ22M75T

KHRQ22M29H

KHRQ22M64H

Imperial-size connections

Heat Pump systems


(2-pipe)

Capacity index
< 200
Metric-size connections

286

DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units

Metric-size connections

Imperial-size connections

VRV III-Q Heat Recovery Replacement VRV

VRV-W IV Water-cooled VRV


Heat Pump application
Heat Recovery application
2-module systems
3-module systems
2-module systems
3-module systems

RQEQ 140~212

2-module systems

3-module systems

4-module systems

RWEYQ8-10T8

BHFP26P36C

BHFP26P63C

BHFP26P84C

BHFQ22P1007

BHFQ22P1517

BHFQ23P907

BHFQ23P1357

KWC26B160

1 kit per module

1 kit per module

1 kit per module

DTA104A53/61/62
Installation in the RWEYQ outdoor unit possible. For installation in indoor units, use appropriate type (DTA104A53/61/62) for particular indoor unit. See Options & Accessories of indoor units

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

1 kit per system

Heat Recovery Branch Selector Boxes (BS-Boxes)


4-port
6-port
6-port
8-port
-

Capacity index
> 640

1-port
-

1-port
-

4-port
-

KHRQM23M75H

KHRQ23M75H

BS1Q-A

BSVQ-P8B

BS4Q14A

BSV4Q100PV

EKBSVQLNP

EKBSVQLNP

KRC19-26

10-port
-

12-port
-

16-port
-

BS6Q14A

BSV6Q100PV

BS8Q14A

BS10Q14A

BS12Q14A

BS16Q14A

KRC19-26
1 kit per port
necessary

KRC19-26
1 kit per port
necessary

KJB111A

KJB111A

KJB111A

KHFP26A100C

KHFP26A100C

KHFP26A100C

KHFP26A100C

KHFP26A100C

KHFP26A100C

KHRP26A1250C

KHRP26A1250C

KHRP26A1250C

KHRP26A1250C

KHRP26A1250C

KHRP26A1250C

KDDN26A4

KDDN26A8

KDDN26A8

KDDN26A12

KDDN26A12

KDDN26A16

KHRQM22M75H

KHRQ22M75H

Options & Accessories

287

Options & accessories -

indoor
Ceiling mounted cassette units
Round flow
(800x800)
FXFQ 20~125A

BRC1E52A/B
Premium wired remote control with full-text interface and
back-light
BRC1D52
Standard wired remote control with weekly timer

Infrared remote control including receiver

BRC2E52C
Simplified wired remote control for heat recovery system
BRC3E52C
Simplified wired remote control for heat pump system
DCS302C51
Central remote control
DCS301B51
Unified ON/OFF control
DST301B51
Schedule timer
DCC601A51
Adapters and control

Centralized controller with cloud connection


DCM601A51
Intelligent Touch Manager
External wired temperature sensor

2-way blow

FXZQ 15~50A

FXCQ 20~40A

FXCQ 50~63A

FXCQ 80 ~125A

*4

*4

*4

*4

*4

BRC7FA532F

BRC7F530W *9*10
(white panel)
BRC7F530S *9*10
(grey panel)
BRC7EB530 *9*10
(standard panel)

BRC7C52

BRC7C52

BRC7C52

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

K.RSS
External wireless temperature sensor

Adaptor for wiring (interlock for fresh air intake fan)

Wiring adapter for external monitoring/control via dry


contacts and setpoint control via 0-140

KRP4A53 *2*7

KRP4A53 *2

KRP4A51

KRP4A51

KRP4A51

Wiring adapter for external central monitoring/control


(controls 1 entire system)

KRP2A52

KRP2A51

KRP2A51

KRP2A51

Wiring adapter with 4 output signals


(Compressor / Error, Fan, Aux. heater, Humidifier output)

EKRP1C11 *2*7

EKRP1B2

EKRP1B2

EKRP1B2

EKRP1B2

Wiring adapter with 2 output signals


(Compressor / Error, Fan output)

KRP1B57 *2*7

KRP1B57

Adapter for multi-tenant applications


(24VAC PCB power supply interface)

DTA114A61

DTA114A61

DTA104A61

DTA104A61

DTA104A61

External control adapter for outdoor unit


Installation box / Mounting plate for adapter PCBs
(For units where there is no space in the switchbox)

KRP1H98 *7

KRP1A101

KRP1C96

KRP1C96

KRP1C96

Connector for forced-off contact

Standard

Standard

Standard

Standard

Standard

Connection to centralized control

Standard

Standard

Standard

Standard

Standard

KJB212A
Electrical box with earth terminal (2 blocks)
KJB311A
Electrical box with earth terminal (3 blocks)

KJB411A
Electrical box with earth terminal

BRP7A51 *2/11
Digital input adaptor

BYBCQ40H

BYBCQ63H

BYBCQ125H

Decoration panel
(obligatory for cassette units, optional for others, rear panel for FXLQ)
Kit for mounting of decoration panel direct onto unit

BYCQ140DG (self clean) *5/*6


BYFQ60CW (white panel)
BYCQ140DGF *5/*6
BYFQ60CS (grey panel)
BYCQ140DW (white) *3
BYFQ60B3 (Standard panel)
BYCQ140D7W1 (Standard)
-

KDBQ44B60
(Standard panel)

KDBHQ55B140 *7

BDBHQ44C60 (white & grey panel)

KDDQ55B140-1 +
KDDQ55B140-2 *7*8

KDDQ44XA60

Air discharge adapter for round duct

Filter chamber for bottom suction

KDDFP53B50

KDDFP53B80

KDDFP53B160

KAFP551K160

KAFQ441BA60

KAFP531B50

KAFP531B80

KAFP531B160

Standard

Standard

Standard

Standard

Standard

BRYQ140A

BRYQ60AW (white panel)


BRYQ60AS (grey panel)

Panel spacer for reducing required installation height


Sealing kit for 3-directional or 2-directional air discharge
Others

4-way (600x600)

Fresh air intake kit

Replacement long life filter


Drain pump kit
Sensor kit
KEK26-1A
Noise filter (for electromagnetic use only)

*2 Installation box is necessary for these adapters


*3 The BYCQ140D7W1W has white insulation
Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt"
*4 Not recommended because of the limitation of the functions
*5 To be able to control the BYCQ140D7GW1 the controller BRC1E is needed
*6 The BYCQ140DGW1 is not compatible with Multi and Split Non-Inverter Outdoor units
*7 Option not available in combination with BYCQ140D7GW1
*8 Both parts of the fresh air intake are needed for each unit
*9 Sensing function not available
*10 Independently controllable flaps function not available
*11 Only possible in combination with simplified remote control BRC2/3E

288

Options & accessories -

indoor

Concealed ceiling units (duct units)


Small

Slim

Standard

FXKQ 25~40

FXKQ 63

FXDQ 20~25 M9

FXDQ 15~63A

FXSQ 15~32

FXSQ 40~50

FXSQ 63~80

FXSQ 100~125

FXSQ 140

*4

*4

*4

*4

*4

*4

*4

*4

*4

BRC4C61

BRC4C61

BRC4C62

BRC4C65

BRC4C65

BRC4C65

BRC4C65

BRC4C65

BRC4C65

KRCS01-1

KRCS01-1

KRCS01-1

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

KRP4A51

KRP4A51

KRP4A51

KRP4A54

KRP4A52*2

KRP4A52*2

KRP4A52*2

KRP4A52*2

KRP4A52*2

KRP2A51

KRP2A51

KRP2A51

KRP2A53

KRP2A51*2

KRP2A51*2

KRP2A51*2

KRP2A51*2

KRP2A51*2

KRP1B61

KRP1B61

EKRP1B2

KRP1B56

EKRP1B2*2

EKRP1B2*2

EKRP1B2*2

EKRP1B2*2

EKRP1B2*2

EKMTAC

DTA114A61

DTA114A61

DTA114A61

DTA114A61

DTA114A61

DTA114A61

DTA104A61

DTA104A61

DTA104A61

DTA104A53

DTA104A61

DTA104A61

DTA104A61

DTA104A61

DTA104A61

KRP1B101

KRP1BA101/
KRP1B100

KRP1BA101/
KRP1B100

KRP1BA101/
KRP1B100

KRP1BA101/
KRP1B100

KRP1BA101/
KRP1B100

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

BYK45F

BYK71F

KDAP25A36A

KDAP25A56A

KDAP25A71A

KDAP25A140A

Standard

Standard

KDAJ25K56

Standard

Standard

Standard

Standard

Standard

Standard

Options & Accessories

Corner (1-way blow)

289

Options & accessories -

indoor and hot water


Concealed ceiling units (duct units)
High efficiency
FXMQ 50~80
FXMQ 100~125

BRC1E52A/B
Premium wired remote control with full-text interface and back-light
BRC1D52
Standard wired remote control with weekly timer
Infrared remote control including receiver
BRC2E52C
Simplified wired remote control for heat recovery system
BRC3E52C
Simplified wired remote control for heat pump system
DCS302C51
Central remote control
DCS301B51
Unified ON/OFF control
DCS601C51
Schedule timer

Adapters and control

DCC601A51
Centralized controller with cloud connection
DCM601A51
Intelligent Touch Controller
External wired temperature sensor

Large
FXTQ50~63

FXTQ80~100

*4

*4

*4

*4

*4

BRC4C65

BRC4C65

BRC4C65

BRC4C65

BRC4C65

KRCS01-4

KRCS01-4

KRCS01-1

KRCS01-4

KRCS01-1

Wiring adapter for external monitoring/control via dry contacts and setpoint
control via 0-140

KRP4A51

KRP4A51

KRP4A51

KRP4A52 *2

KRP4A51

Wiring adapter for external central monitoring/control


(controls 1 entire system)

KRP2A51

KRP2A51

KRP2A51

KRP2A51 *2

KRP2A51

Wiring adapter with 4 output signals


(Compressor / Error, Fan, Aux. heater, Humidifier output)

EKRP1B2

EKRP1B2

KRP1B61

EKRP1B2 *2

KRP1B61

K.RSS
External wireless temperature sensor

Wiring adapter with 2 output signals (Compressor / Error, Fan output)

Others

FXMQ 200~250

Adapter for multi-tenant applications (24VAC PCB power supply interface)

DTA114A61

DTA114A61

DTA114A61

External control adapter for outdoor unit

DTA104A61

DTA104A61

DTA104A61

DTA104A61

DTA104A61

Installation box / Mounting plate for adapter PCBs


(For units where there is no space in the switchbox)

KRP4A96

KRP4A96

KRP1BA101 / KRP1B100

Connector for forced-off contact

Standard

Standard

Standard

Standard

Standard

Connection to centralized control

Standard

Standard

Standard

Standard

Standard

KJB212A
Electrical box with earth terminal (2 blocks)

KJB311A
Electrical box with earth terminal (3 blocks)

KJB411A
Electrical box with earth terminal

BRP7A51 *2 / 11
Digital input adaptor

Decoration panel
(obligatory for cassette units, optional for others, rear panel for FXLQ)

Kit for mounting of decoration panel direct onto unit

Panel spacer for reducing required installation height

Sealing kit for 3-directional or 2-directional air discharge

Decorationpanel for air discharge

Fresh air intake kit

KDAJ25K71

KDAJ25K140

KDAP25A140A

Air discharge adapter for round duct


Replacement long life filter

Standard

Standard

Standard

Sensor kit

KEK26-1
Noise filter (for electromagnetic use only)

L-type piping kit (for upward direction)

Drain pump kit

*2 Installation box is necessary for these adapters


*3 The BYCQ140D7W1W has white insulation
Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt
*4 Not recommended because of the limitation of the functions
*5 To be able to control the BYCQ140D7GW1 the controller BRC1E is needed
*6 The BYCQ140DGW1 is not compatible with Mini VRV, Multi and Split Non-Inverter Outdoor units
*7 Option not available in combination with BYCQ140D7GW1
*8 Both parts of the fresh air intake are needed for each unit
*9 Sensing function not available
*10 Independently controllable flaps function not available
*11 Only possible in combination with simplified remote control BRC2/3E

290

Options & accessories Wall mounted


units

Ceiling suspended units

indoor and hot water

Floor standing units

1-way blow
FXHQ 63A

FXHQ 71~100A

4-way blow
FXUQ 71~100A

FXAQ 15~63

Concealed
FXNQ 20~63

FXLQ 20~25

Free-standing
FXLQ 32~40

FXLQ 50~63

*4

*4

*4

*4

*4

*4

*4

*4

*4

BRC7G53

BRC7G53

BRC7G53

BRC7C58

BRC7EB518

BRC4C65

BRC4C65

BRC4C65

BRC4C65

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-4

KRCS01-1

KRSC01-4

KRCS01-1

KRCS01-1

KRCS01-1

KRP4A52

KRP4A52

KRP4A52

KRP4A53 *2

KRP4A51

KRP4A54

KRP4A51

KRP4A51

KRP4A51

KRP2A62

KRP2A62

KRP2A62

KRP2A51

KRP2A53

KRP2A51

KRP2A51

KRP2A51

KRP1B56

KRP1B61

KRP1B61

KRP1B61

KRP1B54

KRP1B54

KRP1B54

DTA114A61

DTA114A61

EKMTAC

EKMTAC

EKMTAC

DTA104A62

DTA104A62

DTA104A62

DTA104A61

KRP1D93A

KRP1D93A

KRP1D93A

KRP1B97

KRP4A93

EKRORO4

EKRORO4

EKRORO4

EKRORO5

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

Standard

EKRDP25A

EKRDP40A

EKRDP63A

KDBHP49B140

KDBTP49B140

KDDQ50A140

KDDQ50A140

KDDQ50A140

KAFP501A56

KAFP501A80

KAFP501A160

KAFP551K160

KDU50P60

KDU50P140

KDU50P140

K-KDU572EVE

KHFP5M35

KHFP5N63

KHFP5N160

HXY080-1258

HXHD1258

EKHBDPCA2
EKRP1HBAA
EKRP1AHTA

EKRUAHTB

EKBUHAA6(W1/V3)
EKRTWA
EKRTR1
EKRTETS

Domestic hot water tank - standard


(stacked on top of hydrobox)

EKHTS200AC
EKHTS260AC

Domestic hot water tank - with possibility for solar connection


Solar collector *1
Pump station

EKHWP500B
EKSV26P (vertical) EKSH26P (horizontal)
EKSRPS

Drain pan
Digital I/O PCB
Demand PCB - Required to connect room thermostat
Remote user interface (remocon) - Same controller as supplied with cascade unit
can be mounted parallel or on other location. If 2 controllers are installed, the
installer needs to select 1 master & 1 slave
Back-up heater
Wired room thermostat - Requires demand PCB EKRP1AHTA
Wireless room thermostat - Requires demand PCB EKRP1AHTA
Remote sensor for room thermostat - Requires demand PCB EKRP1AHTA

Options & Accessories

FXHQ 32A

*1 pump station is necessary for this option

291

Options & accessories - stylish indoor


INDOOR UNITS

Wired remote control

FTXG-LW/S

CTXS15-35K
FTXS20-25K

FTXS35-50K

FTXS-G

FVXG-K

FVXS-F

FDXS-F(9)

FLXS-B(9)

BRC073 (3)

BRC073 (3)

BRC073 (3)

BRC073 (3)

BRC073 (3)

BRC073 (3)

BRC1D52
BRC1E52A
BRC1E52B (4)

BRC073 (3)

Wireless remote control

BRC4C65

Simplified remote control

BRC2E52C

BRC3E52C

Cord for wired remote control - 3m

Remote control for hotel use

BRCW901A03

BRCW901A03

BRCW901A03

BRCW901A03

BRCW901A03

BRCW901A03

BRCW901A03

Cord for wired remote control - 8m

BRCW901A08

BRCW901A08

BRCW901A08

BRCW901A08

BRCW901A08

BRCW901A08

BRCW901A08

Adaptor PCB for interlock (key card, ...)


(Only in combination with BRC2/3E52C)

BRP7A54

Wiring adapter normal open contact /


normal open pulse contact

KRP413A1S (1)

KRP413A1S (1) (5)

KRP413A1S (1)

KRP413A1S (1)

KRP413A1S (1)

KRP413A1S (1)

KRP413A1S (1)

Centralised control board - up to 5 rooms

KRC72 (2)

KRC72 (2)

KRC72 (2)

KRC72 (2)

KRC72 (2)

KRC72 (2)

KRC72 (2)

Anti-theft protection for remote control

KKF910A4

KKF910A4

KKF910A4

KKF910A4

KKF910A4

KKF917AA4

Interface adapter for wired remote control

KRP980A1

Wiring adapter for electrical appendices

KRP4A54

Remote sensor

KRCS01-4

Installation box for adapter PCB

KRP1BA101

Electric box with earth terminal 3 blocks

KJB311A

Electric box with earth terminal 2 blocks

KJB212A

Interface adapter for DIII-net

KRP928A2S

KRP928A2S (5)

KRP928A2S (5)

KRP928A2S

KRP928A2S

KRP928A2S

KRP928A2S

Online controller

standard (6)

BRP069A43

BRP06942

BRP069A42

BRP069A42

BRP069A42

BRP069A42

Modbus gateway

RTD-RA

RTD-RA (5)

RTD-RA

RTD-RA

RTD-RA

RTD-RA

RTD-NET

KNX gateway

KLIC-DD

KLIC-DD (5)

KLIC-DD

KLIC-DD

KLIC-DD

KLIC-DD

KLIC-DI

KLIC-DD

BKS028

Installation leg

- The BYCQ140DW has white insulations. Be informed that dirt is more visible on white insulation and that it is consequently not advised to install the BYCQ140DW decoration panel in environments
- To be able to control BYCQ140D/W/DG(F), the controller BRC1E is needed and cannot be combined with VRV IV S-series outdoor units.
Notes:
(1) Wiring adapter supplied by Daikin. Time clock and other devices : to be purchased locally;
(2) Wiring adapter is also required for each indoor unit;
(3) Cord for wired remote control BRCW901A03 or BRCW901A08 required;
(4) Standard there is no remote control delivered with this indoor unit. Wired or wireless control to be ordered separately;
(5) Interface adapter KRP980A1 required;
(6) No option needed, functionality is included with the product
(7) Option not available in combination with BYCQ140D*G*;
(8) Both parts of the fresh air intake are needed for each unit;
(9) This option is intended exlusively for usage in fine dust environments (clothing shops). Do not use this option in high humidity and/or greasy environments.;
(10) Installation box for adapter PCB is necessary;
(11) Option not available in combination with BYCQ140*G;
(12) Electrical heater, humidifier and hour meter are field supply. These parts should not be installed inside the equipment;
(13) Sensing function is not available;
(14) Independently controllable flaps function is not available;
(15) With the infrared remote control, the individual flap control and automatic air volume control cannot be controlled;
(16) Including following languages: pack 1: English, German, French, Dutch, Spanish, Italian, Portuguese with PC cable EKPCCAB3 in combination with the Updater PC software, you can additionally change
the language to : language pack 2: English, Bulgarian, Croatian, Czech, Hungarian, Romanian and Slovenian. Language pack 3: English, Greek, Polish, Russian, Serbian, Slovak and Turkish;
(17) These options require mounting plate KRP4A96, maximally 2 optional PCBs can be mounted;
(18) When installing electrical heaters, an optional PCB for external electric heaters EKRP1B2A is required for each indoor unit;
(19) For directly mounting the decoration panel on the unit, decoration panel option EKBYBSD is required.

292

Options & accessories - stylish indoor


INDOOR UNITS
Description

FCQHG-F

FCQG-F

FFQ-C

FDBQ-B

FBQ-D

FHQ-C

BRC1D52
BRC1E53A/B/C (16)

BRC1D52
BRC1E53A/B/C (16)

BRC1D528
BRC1E53A/B/C (16)

BRC1D52
BRC1E53A/B/C (16)

BRC1D52
BRC1E53A/B/C (16)

BRC1D52
BRC1E53A/B/C (16)

BRC2E52C
Simplified remote control (with operation
mode selector button)

BRC3E52C
Simplified remote control (without operation
mode selector button)

DCM601A5A
Intelligent touch manager

BRC7FA532F (11) (15)

BRC7FA532F (11) (15)

BRC7EB530W (13) (14) (15)


BRC7F530W (13) (14) (15)
BRC7F530S (13) (14) (15)

BRC4C65

BRC7G53

DCS302C51
Centralised remote control

DCS301B51
Unified ON/OFF control

DST301B51
Schedule timer

DCC601A51
Centralised controller with cloud connection
Wired remote control

Infrared remote control (heat pump)

Adapter for wiring


(interlock for fresh air intake fan)

KRP1BA59

KRP1B57 (11)
KRP4A53 (11)

KRP1B57
KRP4A53 (11)

KRP1B57
KRP4A53 (11)

KRP4A52 (18)
KRP2A51 (18)

KRP1B54
KRP4A52 (10)

Adapter for wiring (hour meter) (10) (12) (18)

EKRP1C11 (11)

EKRP1C11 (11)

EKRP1B2 (17)

EKRP1B2 (17)

KRP1H98 (11)

KRP1H98 (11)

KRP1B101
KRP1BA101

KRP1B101
KRP1BA101

KRP1D93A

BRP7A53

BRP7A53

BRP7A53

BRP7A54

BRP7A51 (17)

BRP7A52

EKRP1B2A
Options PCB for external electrical heater,
humidifier and/or hour meter (12)

Mounting plate for adapter PCB

KKSAP50A56 (35-50)

KRCS01-4
Remote sensor

Remote ON/OFF, forced OFF kit

EKRORO4

KJB311A
Electrical box with earth terminal (3 blocks)

KJB212A
Electrical box with earth terminal (2 blocks)

KJB411A
Electrical box with earth terminal

DTA112B51
Interface adapter for Sky Air
Installation box for adapter PCB
Digital input adapter (10) (17) (18)

Replacement long-life filter

Drain pump kit

L-type piping kit (upward direction)

Sealing member
of air discharge outlet
Decoration panel for air discharge

KAFP551K160

KAFP551K160

KAFQ441BA60

KAFP501A56
(35-50 class)
KAFP501A80
(60-71 class)
KAFP501A160
(100-125 class)

Standard

Standard

Standard

Standard

KDU50P60
(35-60 class)
KDU50P140
(71-125 class)

KHFP5M35
(35 class)
KHFP5N63
(50-60 class)
KHFP5N160
(71-125 class)

KDBHQ55B140 (19)

KDBHQ55B140 (19)

BDBHQ44C60

BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (9)

BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (9)

BYFQ60B3
BYFQ60C2W1W
BYFQ60C2W1S

KDDQ55B140-1 (7)(8)
+
KDDQ55B140-2 (7)(8)

KDDQ55B140-1 (7)(8)
+
KDDQ55B140-2 (7)(8)

KDDQ44XA60

KDDQ50A140

Air discharge adapter for round duct

KDAP25A56A (35-50 class)


KDAP25A71A (60-71 class)
KDAP25A140A (100-140 class)

Panel spacer

KDBQ44B60

Decoration panel

Fresh air intake kit (direct installation type)

Sensor kit

BRYQ140A

BRYQ140A

BRYQ60A2W
BRYQ60A2S

Noise filter

Options & Accessories

Adapter for external ON/OFF and monitoring/


for electrical appendices (10)

293

Options & accessories - Ventilation

Dust filters

VAM
150FC

VAM
250FC

VAM
350FC

VAM
500FC

VAM
650FC

VAM
800FC

VAM
1000FC

EN779 Medium M6

EKAFV50F6

EKAFV50F6

EKAFV80F6

EKAFV80F6

EKAFV100F6 EKAFV100F6 x2 EKAFV100F6 x2

EN779 Fine F7

EKAFV50F7

EKAFV50F7

EKAFV80F7

EKAFV80F7

EKAFV100F7 EKAFV100F7 x2 EKAFV100F7 x2

EN779 Fine F8

EKAFV50F8

EKAFV50F8

EKAFV80F8

EKAFV80F8

EKAFV100F8 EKAFV100F8 x2 EKAFV100F8 x2

Model name

KDDM24B50

KDDM24B100 KDDM24B100
x2
x2

Nominal pipe
Diameter (mm)

200

200

BRYMA65

BRYMA65

BRYMA65

VH1B

VH2B

VH2B

VH3B

VH3B

Silencer

CO2 sensor
VH electrical heater for VAM

Individual control systems


Wired remote control
VAM wired remote control

Centralised control systems

VAM
1500FC

KDDM24B100 KDDM24B100 KDDM24B100

VAM
2000FC

VKM
VKM
VKM
50GB(M) 80GB(M) 100GB(M)

KDDM24B100 KDDM24B100

250

250

250

250

250

250

BRYMA100

BRYMA100

BRYMA200

BRYMA200

BRYMA65

BRYMA100

BRYMA200

VH5B

VH5B

VH4B / VH4/AB VH4B / VH4/AB

VAM-FC

VKM-GB(M)

EKEQFCBA 2

EKEQDCB 2

EKEQMCBA 2

BRC1E52A/B / BRC1D52

BRC1E52A/B / BRC1D52

BRC1E52A/B / BRC1D52

BRC1E52A/B / BRC1D52 1

BRC1E52A/B / BRC1D52 1

BRC301B61

VAM-FC

VKM-GB(M)

EKEQFCBA 2

EKEQDCB 2

EKEQMCBA 2

Centralised remote control

DCS302C51

DCS302C51

Unied ON/OFF control

DCS301B51

DCS301B51

Schedule timer

DST301B51

DST301B51

DCC601A51

DCC601A51

DCC601A51

DCM601A51

DCM601A51

DCM601A51

DCM601A51

DCM601A51

Modbus DIII adapter

Intelligent Touch Manager

EKMBDXA7V1

EKMBDXA7V1

EKMBDXA7V1

EKMBDXA7V1

EKMBDXA7V1

BACnet interface

DMS502A51

DMS502A51

LonWorks interface

DMS504B51

DMS504B51

VAM150-250FC

VAM350-2000FC

VKM-GB(M)

EKEQFCBA 2

EKEQDCB 2

EKEQMCBA 2

Wiring adapter for electrical appendices


(note 7)

Others

KRP2A51

KRP2A51 (note 3)

BRP4A50A (note 4/5)

Adapter PCB for humidifier

KRP50-2

KRP1C4 (note 4/6)

BRP4A50A (note 4/5)

Adapter PCB for 3rd party heater

BRP4A50

BRP4A50A (note 4/5)

BRP4A50A (note 4/5)

KRCS01-1

Remote sensor
Notes

(1) Cool/heat selector required for operation


(2) Unless otherwise specified DIII-net devices cannot be connected to the system
(3) Installation box KRP1BA101 needed.
(4) Fixing plate EKMPVAM additionally needed for VAM1500-2000FB.
(5) 3rd party heater and 3rd party humidifier cannot be combined
(6) Installation box KRP50-2A90 needed.
(7) For external control and monitoring (ON/OFF control, operation signal, error indication)

VH electrical heater for VAM


Supply voltage
Output current (maximum)
Temperature sensor
Temperature control range
Run on timer
Control fuse

220/250V ac 50/60 Hz. +/-10%


19A at 40C (ambient)
5k ohms at 25C (table 502 1T)
0 to 40C / (0-10V 0-100%)
Adjustable from 1 to 2 minutes (factory set at 1.5 minutes)
20 X5 mm 250 m A

LED indicators

Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red

Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input

Vh electrical heater for vam


Capacity
Duct diameter
Connectable VAM

294

kW
mm

98mm X 181mm centres 5 mm holes


35C (during operation)
100C Pre-set
125C Pre-set
1A 120V AC or 1A 24V DC
0-10VDC

vH1B

VH2B

VH3B

VH4B

VH4/AB

VH5B

1
100
VAM150FC
-

1
150
VAM250FC
VAM350FC

1
200
VAM500FC
VAM650FC

1.5
250
VAM800FC
VAM1000FC

2.5
250
VAM800FC
VAM1000FC

2.5
350
VAM1500FC
VAM2000FC

D-AHU Professional
Construction type
Aluminium
Profile

Panel insulation

FP 50

FP 25

standard

standard

Anodized aluminium

option

option

option

option

option

option

option

option

option

option

option

option

Glass fibre reinforced nylon

standard

standard

standard

standard

Polyurethane foam density 45 kg/m3 thermal


conductivity 0.020 W/m*K fire reaction class 1

standard

standard

standard

standard

option

option

option

option
standard

Mineral wool density 90 kg/m3 thermal conductivity


0.037 W/m*K (referred to 20C) fire reaction class 0
Grey Plastisol covered galvanized steel

External sheet
material

SP 45
standard

Aluminium with thermal break


Anodized aluminium with thermal break

Corner

SP 65
standard

standard

standard

standard

Pre-coated galvanized steel

option

option

option

option

Galvanized steel

option

option

option

option

Aluminium

option

option

option

option

AISI 304 stainless steel

option

option

option

option

standard

standard

standard

standard

option

option

option

option

option

option

option

option

Galvanized steel
Pre-coated galvanized steel
Internal sheet material Grey Plastisol covered galvanized steel
Aluminium
AISI 304 stainless steel
Aluminium
Base frame
Galvanized steel
Handle

Glass fibre reinforced nylon

Type

Hinge function type


(possibility to remove door)

Compression type

option

option

option

option

option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard

option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard

option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard

option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard

standard

standard

standard

standard

option

option

option

option

D-AHU Easy
Aluminium

Corner

Glass fibre reinforced nylon

Panel insulation

Polyurethane foam thermal conductivity 0.024 W/m*K

DS 50

DS 25

Standard

Standard

Standard

Standard

Standard (density 45 kg/m3)

standard (density 47 kg/m3)

External sheet material

Pre-coated galvanized steel (RAL 9002)

Standard

Standard

Internal sheet material

Galvanized steel

Standard

Standard

Base frame

Aluminium

Standard

Standard

Handle

Glass fibre reinforced nylon

Standard

Standard

Type

Compression type

Standard

Standard

Options & Accessories

Construction type
Profile

295

Options - Control systems

DCC601A51
Options for local control

Cloud options

Software

Zenpad 8 Tablet for local control

Z380C

Asus 4G-N12 router

4G-N12

Online control - for remote montoring and control

DCC001A51

Multi site for remote monitoring, control and comparison


of multiple sites (needed for each site)

DCC002A51

Energy saving activates automatic energy saving


function

DCC003A51

Full contains packs DCC001/002/003A51

DCC004A51

App for tablet Application to run on Z380C tablet (download from Play
store, Android only)
Commisioning tool
Software update tool

Intelligent Touch Manager


Options & software
iTM plus adapter Allows connection of an additional 64
indoor units/groups. Up to 7 adapters can be connected

DCM601A52

iTM ppd software Allows distribution of used kWh by


indoor units connected to the iTM

DCM002A51

iTM energy navigator Energy management option

DCM008A51

iTM BACnet Client option Enables integration of third


party devices to the iTM via the BACnet/IP protocol. (This is
not a gateway and cannot replace DMS502B51)

DCM009A51

Standard protocol interfaces


Interface adapter for connection to RA units
Interface adapter for connection to R-407C/R-22 Sky Air units
Interface adapter for connection to R-410A Sky Air units
DIII board
Digital input/output

296

KRP928A2S
DTA102A52
DTA112B51
DAM411B51
DAM412B51

DMS504B51

DMS502A51

LonWorks Interface

BACnet Interface

Power supply
T1
V1
VE
V3
VM
W1
Y1

=
=
=
=
=
=
=

3~, 220V, 50Hz


1~, 220-240V, 50Hz
1~, 220-240V/220V, 50Hz/60Hz*
1~, 230V, 50Hz
1~, 220~240V/220~230V, 50Hz/60Hz
3N~, 400V, 50Hz
3~, 400V, 50Hz

* For VE power supply only 1~, 220-240V, 50Hz data


is displayed in this catalogue.

Conversion table
refrigerant piping
inch
1
/4
3
/8
1
/2
5
/8
3
/4
7
/8
1 1/8
1 3/8
1 5/8
1 3/4
2
2 1/8
2 5/8

mm
6.4 mm
9.5 mm
12.7 mm
15.9 mm
19.1 mm
22.2 mm
28.5 mm
34.9 mm
41.3 mm
44.5 mm
50.8 mm
54 mm
66.7 mm

F-gas regulation
For fully/partially charged equipment: contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit
construction, details can be found on the unit labels.
For non pre-charged equipment (Chillers: split chiller (SEHVX/SERHQ), condensing units and condenserless chillers + refrigeration
(LCBKQ-AV1, JEHCCU/JEHSCU and ICU): Its functioning relies on fluorinated greenhouse gases.

Measuring conditions
Air conditioning
1) Nominal cooling capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference
2) Nominal heating capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference

27CDB/19CWB
35CDB
7.5m - 8/5m VRV
0m
20CDB
7CDB/6CWB
7.5m - 8/5m VRV
0m

Options & Accessories

The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value,
depending on the distance and acoustic environment (for measuring conditions: please refer to the technical databooks).
The sound power level is an absolute value indicating the power which a sound source generates.
For more detailed information please consult our technical databooks.

297

Were here to help you!


Online and offline

http://literature.daikinpromoshop.eu

General catalogue

2016

-45C

298

0C

80C

Tools and
platforms

299

Tools & Platforms

Literature overview 300


Supporting tools, software and apps
302
30 years of history
304
Resarch & development
306

Commercial market - literature overview


for professional network
Solution
guides:

Reference
books:

Product
profiles:

VRV IV range
VRV IV
360 efficiency

Detailed VRV IV standards


and technologies benefits.
Main features and specs of
VRV IV product range

VRV IV i-series

Keep looking
youll never find me

Water-to-air heat pump

Main benefits,
application examples
and specs of VRV IV
i-series product range

VRV IV heat pumps for indoor installation

16-207

Detailed info on VRV IV Wseries, application


examples, technical system
design background
Second half 2016

VRV IV S-series

VRV IV heat recovery, heat pump, replacement


and water cooled

15-206

Keep looking
youll never find me

Compact VRV IV heat pumps


for residential and light commercial applications

16-209

Main benefits,
application examples
and specs of VRV IV
S-series product range
16-208

for installers

Technical cooling
RELIABLE,
C

Replacement
technology

Replacement
Technology

Clear installer benefits


of VRV replacement
technology
For

The quick and quality way of upgrading R-22 and R-407C systems

Product
flyers:
Real time clock

Supports multiple languages

Restrict some of all functions on the remote


control to void misuse in e.g. hotels, shops, offices

Other features

English, German, French, Spanish, Italian,


Portuguese, Greek, Dutch, Russian, Turkish
and Polishr (BRC1E52A)

Built-in back-up power. When a power failure occurs,


all settings remain stored up to 48 hours

English, German, Czech, Croation, Hungarian,


Romanian, Slovenian, Bulgarian, Slovak, Serbian,
Albanian (BRC1E52B)

Backlight display

User friendly
remote control
with contemporary
design

Specifications / Functions
Specifications

BRC1E52A / BRC1E52B

Dimensions (HxWxD)

3.120x120x19 mm40
Display size (HxW)

LCD

43.2x68.85 mm

Type

Full dot (160x255)

Colour

Fresh white

Cover for operation part

No

Max. wiring length

500m

Connectable indoor units

All VRV and Sky Air indoor units

Functions

BRC1E52A / BRC1E52B
Set sensor behavior

Energy saving
functions

Temperature range limit

Setback function

Split, Sky Air, VRV, Chillers,


Refrigeration, Daikin Altherma

Detailed info on
BRC1E52A/B remote
control

Modbus
Interface

RTD modbus interface


Detailed info on RTD
controls and applications

RTD

English, German, Czech, Croation, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian

Clock (time display)

Real time clock with auto update to daylight saving time

Backlight

Contrast adjustment

Weekly schedule timer

Holiday function

Key lock

Restrict buttons
Built-in back-up power

Each menu individually


Each button individually (ON/OFF, operation mode selector, temperature adjustment, fan speed / air flow direction)
When a power failure occurs, all settings remain stored up to 48 hours

Easy to use: all main functions directly accessible


Daikin Europe N.V.

16-140

Room temperature display

Access control Restrict menus


Memory

server rooms, telecom shelters, laboratories, IT applications

15-214

English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, Polishr

Help menu

Timer

Clear installer benefits


why to choose Daikin for
technical cooling

BRC1E52A/B

Set point auto reset


Off timer
Multilingual display

Display

Infrastructure
cooling solution

Wired Remote Control

Possibility to individually restrict menu


functions/buttons

Real time clock with auto update to daylight saving


time

TINUOUS O
ON

RATION
PE

Focus
topics:

Naamloze Vennootschap Zandvoordestraat 300 8400 Oostende Belgium www.daikin.eu BE 0412 120 336 RPR Oostende (Responsible Editor)

FSC
ECPEN15 - 306

Easy commissioning: intuitive interface for advanced


menu settings
Optimise your air conditioning system by activating a
series of energy saving functions (temperature range
limit, setback function, off timer, )

180 11/14
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from
or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.

Keep track of your energy consumption with the


kWh indication showing an indicative electricity
consumption

The present publication supersedes ECPEN12-306. Printed on non-chlorinated paper.

Product
catalogues:

Set up to 3 independent schedules, so the user can


easily change the schedule himself throughout the
year (e.g. summer, winter, mid-season)
Real time clock with auto update to daylight saving
time

Integration of Daikin portfolio in BMS system via Modbus

Supports multiple languages


Possibility to individually restrict menu functions
When a power failure occurs all settings remain stored
up to 48 hours thanks to the built-in backup power

Indoor unit control


via 0~10 volt, dry contact
or resistance contact

15-306

VRV Catalogue

Sky Air Catalogue


Sky Air
Product catalogue
for installers 2015

Detailed technical
information & benefits
on Sky Air/Ventilation/
Biddle Air Curtain/Control
systems/AHU

Retail applications
Hotel applications
IT applications
Heating interlock
Alarm signal

Detailed technical
information & benefits of
the VRV total solution

VRV
Product catalogue 2016
for professionals

15-308

Ventilation Catalogue
Ventilation
Product catalogue 2016
for professionals

Detailed info on
Ventilation products

Full

LIBRA
OF BIM RY
OBJEC
TS
FOR

Your business is our concern

Product
portfolios:

16-100

Product portfolio

Sky Air

Sky Air product


portfolio

Overview of Sky air


product range

VRV

Minimum running costs, maximum flexibility.


Fast installation, top reliability, perfect comfort.

16-200

Fresh air for the residential and commercial sector


Heat reclaim ventilation and air handling applications

VRV product portfolio


Product portfolio

VRV

Overview of VRV total


solution product range

Product Portfolio

Controls

16-203

Controls systems
portfolio

Overview of all Daikin


control systems

22

16-101

300

16-201

15-301

for your customers


Green Buiding Solutions

Commercial Solutions

Daikin offers solutions for


commercial applications

Commercial solutions
for small to large applications

Green building
solutions

Clear building owner/investor


benefits why to choose Daikin
for a green building, with
emphasis on BREEAM

365-days climate comfort for every business

15-216

15-100
Sustainable design
with Daikin HVAC-R systems

Reference
catalogue

Hotel Solutions

Daikin commercial
and industrial
references

Hotel solutions
for hotel owners

Heating - air conditioning - hot water - ventilation - refrigeration - control

Clear building owner/investor


benefits why to choose Daikin
for a hotel
15-218

14-213

Intelligent Touch Manager


Control systems

Intelligent Touch
Manager

Mini Building Management System

15-302

SPLIT, SKY AIR, VRV, CHILLERS

The phase-out period for


R-22 is over.

Act now!

tablet

Detailed benefits of
Intelligent Touch Manager

intelligent
Tablet Controller

Advanced centralised controller with cloud connection

DCC601A51

Detailed benefits of DCC601A51


and Daikin Cloud Service

16-303

Replacement technology

Clear building owner/investor


benefits of replacement
technology

Avoid loss of business and replace your air conditioning


system now!

15-215

Sky Air product leaflets


FNQ-A, FXNQ-A

Designed to be concealed in walls

Powerful mode

Ideal for installation in offices, hotels and residential


applications
Its low height enables the unit to fit perfectly beneath
a window

Concealed
ceiling unit
with medium
ESP
FBQ-D, FXSQ-A

Home leave

Home leave
operation

VRV product leaflets

Single page leaflet with the


main benefits and technical
specifications of each
individual Sky Air unit. Ideal for
quotations

Single page leaflet with the


main benefits and technical
specifications of each individual
VRV unit. Ideal for quotations

Optimum comfort guaranteed no matter the


length of ductwork or type of grilles

operation

Discretely concealed in the wall, leaving only the


suction and discharge grilles visible
Requires very little installation space as the depth is
only 200mm
High ESP allows flexible installation

Powerful mode

Multi tenant

Multi tenant (FXSQ)

(FXNQ-A)

Cassette mini catalogue

Giving overview of our cassette


unit product solutions

(incl. Round flow cassette FCQ(H)G-F/FXFQ-A,


Fully flat cassette FFQ-C/FXZQ-A, FUQ-C/
FXUQ-A, ACQ-C)

16-110

Top efficiency in the market


Automatic air flow adjustment function measures the
air volume and static pressure and adjusts it towards
the nominal air flow, whatever the length of duct,
making installation easier and guaranteeing comfort.
Moreover, the ESP can be changed via the wired
remote control to optimize the supply air volume
Slimmest unit in class, only 245mm
Discretely concealed in the ceiling: only the suction
and discharge grilles are visible
Low sound level

Medium external static pressure up to 150Pa facilitates


using flexible ducts of varying lengths
Reduced energy consumption thanks to specially
developed DC fan motor
Flexible installation, as the air suction direction can be
altered from rear to bottom suction
Standard built-in drain pump increases flexibility and
installation speed
No optional adapter needed for DIII-connection, link
your unit into the wider building management system

Concealed ceiling unit


mini catalogue

Ceiling suspended, wall mounted, floor


standing units mini catalogue

(incl. FDXS-F(9), FBQ-D, FDQ-C, FDQ-B, FXDQ-M9,


FXDQ-A, FXSQ-A, FXMQ-P7, FXMQ-MA)

(incl. FXHQ-A,FHQ-C, FXAQ-A, FAQ-C, FXNQ-A, FNQ-A,


FXLQ-P, FVQ-C)

Catalogue giving overview of our


concealed ceiling unit product
solutions

16-106

Catalogue giving overview of our Ceiling


suspended, wall mounted and floor standing
product solutions.

16-101

Technical documentation:
All latest Daikin catalogues are available in
a convenient library on the internet:
www.daikineurope.com/support-and-manuals/catalogues

301

Tools & Platforms

Concealed
floor standing
unit

Supporting

tools, software and apps

www.daikineurope.com/
support-and-manuals/
software-downloads

Software
Solutions seasonal simulator, simulate
& compare
With this software tool you can simulate and
the seasonal efficiency, the annual power
consumption and CO2 emission for a given climate,
load profile (cooling, heating, heat recovery,
covalent, bivalent...) and combination of systems.
With its intuitive and graphical appealing interface,
a simulation, comparison and ROI calculation can be
made in a matter of minutes.

Xpress, Quick Quotation tool


Xpress is a software tool that allows creating on
the spot quotations for a Daikin VRV system.
It provides a result in 6 steps to enable a professional
budget quotation in the fastest possible way:
Select indoor units
Connect outdoor units to indoor units
Automatic generation of piping diagram with

joints
Automatic generation of wiring diagram
Select possible centralised control systems
Visualise result in MS Word, MS Excel and AutoCAD

Ventilation Xpress
Selection tool for ventilation devices (VAM, VKM).
The selection is based on given supply/extract
airflows (including fresh up), and given ESP of
the supply/extract ducting:

Determines size of electrical heaters


Visualisation of psychrometric chart
Visualisation of selected configuration
Required field settings mentioned in the report

Supporting tools
NEW Building Information Modelling

http://bimobject.
com/en/
product/
?freetext=daikin

(BIM) support

BIM is improving efficiency in the design

and built phase


Daikin is among the first

to supply a full library of BIM objects


for its VRV products
NEW VRV CAD 2D

Possibilty to make a VRV pipe design on a Autocad

2D floorplan
Improves efficiency and reduces time being spent
on the project.
Calculation of correct pipe diameters and refnets

302

Determines outdoor unit size


Validates VRV pipe rules
Calculates the extra refrigerant charge, including a

max. room concentration check

https://my.daikin.
eu/content/denv/
en_US/home/
applications/
software-finder/
vrvcad.html

Other interesting apps


Some of our most used apps:
Error code app: quickly know the meaning of fault
codes for each product family
Load calculation tool: helps you to calculate
the heat and cool laod of your building
Astra: AHU design software

Online support

Internet

NEW Business portal


Experience our new extranet that
thinks with you at my.daikin.eu
Find information in seconds
via a powerful search
Customise the options so you
see only info relevant for you
Access via mobile device or desktop

my.daikin.eu
AT
C U S TO M E

ON
THE
R OA D
RS

Find our solution for different applications:


Supermarket

Technical
Restaurant

Hotel

Store &
shop

Home

Bank

Office

Industry
Sport &
Leisure

Get more commercial details on our flagship


products via our dedicated minisites

www.daikineurope.com/
commercial/applications
www.daikineurope.com/
industrial/applications
See our references

AT THE OFFICE

www.daikineurope.com/references
303

Tools & Platforms

HOTEL PORTA FIRA

Over 30 years of

VRV History
1987

1998

2004

2008

Introduction the original VRV air


conditioning system to Europe,
invented by Daikin in 1982
Up to 6 indoor units connected
to 1 outdoor unit

Launch inverter series with


R-407C
Up to 16 indoor units connected to 1 outdoor unit

Expand to light commercial sector with


VRVII-S
Available in 4, 5, 6HP capacities
1 system can be installed in up to 9 rooms

Launch of heat pump


optimised for heating
(VRV III-C)
Extended operation
down to -25C
2-stage compressor
systems

1987

1991

1994

1998

2003

2004

2005

2003
1991
Introduce VRV heat
recovery
Simultaneous cooling and
heating

304

1994
Awarded ISO9001 certification

Introduce VRVII-- the first R-410A


VRF system
Available in cooling, heat pump and
heat recovery
40 units connected to single
refrigerant circuit

2005
Extends VRVII inverter
range with water cooled
VRV-WIII
Available in heat pump and
heat recovery

2006-20

2008

2011

Extends VRVIII range


with water cooled VRV-WIII
Geothermal version available
Operate down to -10C in heating mode

Launch total solution concept


Integrate hot water production and
Biddle air curtains into VRV system
Connectable to Daikin Emura and
Nexura
400,000 outdoors units sold
2.2 million indoor units sold

2009

2010

2011

2015

2012

Launch of VRV IV S-series

Most compact unit in the market


Widest range in the market

2015

2006-2007
Launch the extensively
re-engineered VRVIII
Available in cooling, heat
pump and heat recovery
Automatic charging and
testing
Up to 64 units
connected to 1 system

2010
Launch of replacement VRV
(VRVIII-Q)
Upgrade to replace older VRV units
using R-22 refrigerant

2012-2014
Setting new standards with the
launch of VRV IV
28% improved seasonal efficiency
Continuous heating on heat pumps
Available in heat pump, heat
recovery, water-cooled and
replacement series

2015
Launch of VRV IV i-series

The invisible VRV


Unique product concept

305

Tools & Platforms

007

2009

Research & development


Creating value through innovative
technologies
R&D is essential for the creation of products that
enrich people's lives. As symbolised by the VRV,
Daikin is at the forefront of innovative technology
and the development of market leading products:
the result of our advanced R&D system.

Superior products from multi-part


development approach
To create more advanced functions with added value,
Daikin has set up the 'Environmental Technology
Research Laboratory' and the 'Solution Product
Development Center'. Working with the Product
Development Group, the three divisions cooperate
closely to ascertain and meet the customers' needs
and to enable commercialisation of products
incorporating advanced technology.

Intensive research on environmental impact


The diverse needs in different countries encountered
during the accelerating globalisation of our air
conditioning business have presented us with
increased research challenges particularly in terms
of environmental impact. To promote energy savings
in and to lower the environmental impact of our air
conditioners, we have developed technologies based
on fundamental research into motor inverters and
many other areas.

IT and air conditioners: the obvious solution


With advances in computerisation and networking,
we have integrated IT into our air conditioners
including communication technology and advanced
software for total control.
Our new control systems enable users to develop
comfortable environments with superior energy
savings by networking air conditioners to enable
them to exchange information with each other and
with our service centres.
306

Development
Product Development Group

IT
Solution Product
Development Center

Development
Environmental Technology
Research laboratory

Environment
Five-year results for the environmental
action plan 2010
Under the five-year FUSION 10 strategic management plan,
which targeted fiscal year 2010, the Daikin Group strove to
develop and promote the use of environmentally conscious
products and services on a basic policy of actively contributing
to solving global environmental problems and expanding
business. Our environmental measures were conducted under
our Environmental Action Plan 2010.

Europe
Fifteen-fold increase in heat-pump hot water and space
heating
We have successfully promoted the use of the Daikin Altherma
hot water and space heating system in the process contributing
to the reduction of 210,000 tons of CO2 emissions.

Reducing Environmental Impact from products


Five year result

Proliferating results

Promote and expand the use of environmentally conscious


products to meet the particular needs of each world region.

Units of Daikin ALtherma


sold in Europe

We have developed and provided air conditioner products


and services that meet the environmental needs of each world
region in terms of weather, culture, and economy.

Heat pump heaters as


percentage of all heaters sold

Five years target

in Europe

Daikin will continue to provide air conditioning products and


services that meet the environmental needs of each world
region. Particularly in developing countries, which are growing
fast but where increasing environmental impact is a problem,
Daikin will provide products and technologies that contribute to
economic progress yet still protect the environment.

Reduction of
210,000 tons of
CO2 emissions
compared
to using
combustiontype heaters

15 times

2006

2010

HEAT PUMP
HEATERS 4%

FY 2010

FY

307

Tools & Platforms

Promote the use of environmentally conscious products,


particularly in rapidly growing developing countries

Keep looking
youll never find me

The city secret


Unseen in the best places
Our VRV IV i-series offers you a truly unique solution for installations where
you need a totally invisible system. It is compact and easy to hide indoors,
with only the grilles being visible outside. Split into two lightweight
components, the compressor can be installed at floor level in a storage room
or technical area, and the heat exchanger unit, which is only 400 mm high,
can be installed in a standard false ceiling. The VRV IV i-series has a patented
V-shaped heat exchanger which boosts efficiency. So your customer can
now enjoy all the power of a fully invisible VRV system.

i
Find out more at www.daikineurope.com/citysecret
Daikin Europe N.V. Naamloze Vennootschap Zandvoordestraat 300 8400 Oostende Belgium www.daikin.eu BE 0412 120 336 RPR Oostende (Responsible Editor)
Daikin Europe N.V. participates in the Eurovent Certification
programme for Liquid Chilling Packages (LCP), Air handling
units (AHU), Fan coil units (FCU) and variable refrigerant flow
systems (VRF) Check ongoing validity of certificate online:
www.eurovent-certification.com or using: www.certiflash.com

ECPEN16-200

xxx 01/16
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from
or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.
The present publication supersedes ECPEN15-200A. Printed on non-chlorinated paper.