Table of contents
VRV, the solution for the
commercial sector
16
Benefits
24
NE W
S-serie
s
i-serie
s
Outdoor units
34
Wide
range st
on
the
marke
t
Indoor units
122
Hot water
208
218
NE W
contro
possib l
il
for AH ity
U
224
NEW
DCC60
1A51
Control Systems
258
282
298
NE W
busine
portalss
ARGUE CARDS
Best comfort
Variable Refrigerant Temperature preventing cold draughts
True continuous heating, during defrost
15 class units for small, well insulated rooms (cassette, wall, concealed ceiling models)
Low sound indoor and outdoor units
Presence and floor sensors direct the air flow away from persons, while ensuring
an even temperature distribution
Top reliability
True technical cooling
Gas-cooled PCB
Most extensive testing before new units leave the factory
Widest support network and after sales service
All spare parts available in Europe
Preventive maintenance via i-Net
presence sensor
floor sensor
VRV Intro
FXUQ
7-segment display
Heat pump
Heat recovery
Replacement
Water cooled
The VRV air conditioning system is the worlds first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trademark of Dakin Industries Ltd, which is derived from the technology we call variable refrigerant volume. BREEAM is a registered trademark of BRE
(the Building Research Establishment Ltd. Community Trade Mark E5778551). The BREEAM marks, logos and symbols are the Copyright of BRE and are reproduced by
permission
In the spotlight
BIM: Building Information Modelling
What is BIM?
BIM is an intelligent model-based process that
provides insight to help you plan, design, construct
and manage buildings and infrastructure
Collaboration
and clash control
BIM uses a 3D model to provide the right information, to the right people, at the right time. This
process improves efficiency throughout the design
and building phases and increases savings by
discovering clashes during the design phase, rather
than later on during the building phase.
Expertise
ECPEN15-216A.indd 5
Case: Velocity, UK
Energy performace certificate B
VRV heat recovery ensures an energy cost
of 9 euro/m3 compared to a typical cost of
29 euro/m3
/m
energy cost
vs 29/m for
a CIBSE
typical office
BREEAM is a registered trademark of BRE (the Building Research Establishment Ltd. Community Trade Mark E5778551).
14/04/15 17:30
VRV Intro
More details
on page 76
You can install highly efficient, reliable Daikin air conditioning systems in
the most demanding locations while remaining invisible from street level.
Invisible
Only the grilles are visible
Seamless integration into surrounding
architecture
Low operation sound
Intelligent
Patented V-shape heat exchanger for the most
compact unit ever
Connectable to all VRV indoor units
Total solution when combined with ventilation
units, Biddle air curtains and controls
Intuitive
Total flexibility as the outdoor unit is split
up in parts
Easy and quick to transport and install
Easy servicability, all components can be easily
reached
uniqu
e
paten
ted
conce
pt
More details
on page 58
823mm
1615mm
10/12 HP
8 HP
4/5/6 HP
Mo
co m p s t
a
on the c t unit
m
823m arket
m hig
& 88k h
g
4/5 HP
presence sensor
Flexible installation
with individual flap control
Unique design
floor sensor
Most
quiet
unit in
th
marke e
t
(25dBA
More details
on page 136
Intelligent sensors and flap control on round flow and fully flat cassette
Top efficiency
Top comfort
VRV Intro
More details
on page 100
VRV-Q
1
2
3
4
5
6
7
1 Recover refrigerant
2 Remove units
Recover refrigerant
Remove units
Remove refrigerant pipes
Install new piping and wiring
Install new units
Leak test
Vacuum drying
8 Refrigerant charging
9 Collect contamination
10 Test operation
Up to 45% shorter
installation time
The Daikin
low-cost upgrade solution
R-407C (RSXYP-L7)
R-410A (RXYQQ-T)
Up to 48%
less consumption
More details
on page 224
In situations where Daikin Heat Reclaim Ventilation units cannot satisfy the ventilation requirement, Daikin air handling units
represent the ideal solution, offering large fresh air volumes and high ESPs enabling the use of extensive ductwork runs.
ventilation device
No additional work at installer side to design the
total system
VRV IV or ERQ
condensing unit
Electronic expansion
valve
Control box
(EKEXV)
(EKEQ)
Which VRV
system offers me the best solution?
Heat recovery or heat pump?
VRV Heat recovery
Addit
io
credit nal
s
BREEA for
certifi M
cate
North
Cooling
+
Hot water
Heating
Outdoor unit
Indoor unit
3-pipe
refrigerant
piping
Outdoor unit
10
Indoor unit
2-pipe
refrigerant
piping
South
VRV Intro
Outdoor unit
Indoor unit
Refrigerant piping
Water Cooled
Suitable for high rise and large buildings because of
the nearly unlimited possibilities of water piping
Not affected by outdoor temperature/climate
conditions
Reduce CO2 emmisions thanks to the use of
geothermal energy as a renewable energy source
Allows heat recovery in the entire building thanks
to the storage of energy in the water circuit
Lower refrigerant levels thanks to the limited
distance between outdoor and indoor units
Addit
io
credit nal
s
BREEA for
certifi M
cate
Components:
Outdoor unit
Indoor unit
Refrigerant piping
(Geothermal)
water loop
Geothermal application
11
Which applications?
Heating
Cooling
Refrigeration
Hot water
Infrastructure
cooling
Underfloor heating
Air curtains
Ventilation
Controls
units
Refrigeration 3%
Lighting
Ventilation 4%
Integrate
third party
equipment
Kitchen
Office
Other
70%
Hot water 9%
Other
Office
equipment
48%
Lighting
Space cooling 9%
Space heating 31%
12
Ventilation 5%
Integrate
third party
equipment
VRV Intro
One system,
multiple applications for hotels, offices,
retail, home
Heating and cooling
Low-temperature hydrobox
Ventilation
VRV
for offices and banks
VRV
for hotels
Check on
www.youtube.com/
DaikinEurope
14
Check on
www.youtube.com/
DaikinEurope
Hotel
Bank / Retail
VRV Intro
VRV
for retail
VRV
for residential use
Commercial solutions
for small to large applications
Check on
www.youtube.com/
DaikinEurope
Residential
15
16
VRV IV
Standard & Technologies
VRV IV =
3 revolutionary standards
Variable Refrigerant Temperature
Continuous comfort during defrost
VRV configurator
17
temperature
UNIQUE
Cooling requirement
System
capacity
Design point
Refrigerant temperature
building
Variable Te
Efficiency up
20
25
30
Success story
Real test: up to 46% less energy consumed
A field trial was carried out in a shop of a fashion chain in
Germany and showed that the innovative Daikin VRV IV
delivers dramatically better energy efficiency compared
with previous models.
The trial results showed that the new VRV IV system
consumed up to 60% less energy than the VRV III system,
particularly during cooling. Overall energy savings during
heating averaged 20%.
18
Adjust capacity by
Te control to meet
the load (avoid over
capacity and ON/OFF
operation)
Fixed Te
Seasonal efficiency
temperature can be
the higher the efficiency
UNIQUE
Daikin VRV IV
Variable Refrigerant Temperature control for energy
saving in partial load condition.
The capacity is controlled by the inverter compressor
and variation of the evaporating (Te) and condensing
(Tc) temperature of the refrigerant in order to
achieve the highest seasonal efficiency.
Evaporating temperature can vary between 3 and 16
which is the widest on the market.
VRF standard
Capacity is controlled only with the variation of the
inverter compressor
temperature,
35
Outdoor temperature
VRV IV
Standard & Technologies
Check on
8 Different modes to
maximise efficiency
and comfort
https://www.youtube.com/
DaikinEurope
Step 1
Step 2
Automatic*
Powerful
6
pa
te nt s
Top efficiency
High sensible
Target Te can be selected between 7Cto 11C
Top efficiency
Basic
Quick
Mild *
Powerful
Quick
Mild
Eco
No submodes
Gives customer choice for fixing coil temperature which avoids cold draughts.
A quick reaction speed to changing load has priority, with temporarily colder
outblow as a result.
This is how most other VRF systems work and can be used for all general type of
applications. Suitable for computer rooms.
Suitable for low ceiling rooms.
* Factory setting
Avg (kWh/Month)
2.797
1.502
Total (KWh)
33.562
18.023
Total ()
6.041
3.244
9,9
5,3
Period
Yearly (operation
cost/m (/m)
Measured data
Fashion store Unterhaching (Germany)
Floor space: 607m
Energy cost: 0,18 /kWh
System taken into account for consumption:
- VRV IV heat pump with continuous heating
- Round flow cassettes (without auto cleaning panel)
- VAM for ventilation (2x VAM2000)
- Biddle Air curtain.
19
Real continuous
heating
during defrost mode
VRV IV continues to provide heating even when
in defrost mode, providing an answer to any
perceived disadvantages of specifying a heat
pump as a monovalent heating system.
Check on
https://www.youtube.com/
DaikinEurope
Room temperature
VRV IV
VRF benchmark
Time
Alternate defrost
while indoors
a comfortable temperature
is maintained.
Available on:
Available on:
Heat pump
Heat pump
Heat recovery
even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat
Replacement VRV
RYYQ8-20T
RYYQ16-54T
REYQ10-54T
RXYQQ16-42T
RXYQ16-54T
Water cooled VRV has no defrost cycles
20
RQCEQ280-848P
VRV IV
Standard & Technologies
VRV Configurator
Check on
https://www.youtube.com/
DaikinEurope
Simplified
commissioning
7-segment display
for quick and accurate error diagnosis
Outdoor unit display for quick on-site settings and
easy read out of errors together with the indication of
service parameters for checking basic functions.
easy-to-read error report
clear menu indicating quick and easy on-site
settings
indication of basic service parameters to quickly
check basic functions: high pressure, low
pressure, frequency and operation time history of
compressors, temperature of discharge/suction
pipe.
No need to unmount the big front panel of the unit
thanks to the service access
Available on:
Heat recovery
Heat pump
Replacement VRV
REYQ-T
RYYQ-T
RXYQQ-T
RXYQ-T(9)
RXYSCQ-TV1 (only configurator, no 7 segment display)
RXYSQ-TV1/TY1 (only configurator, no 7 segment display)
SB.RKXYQ-T (only configurator, no 7 segment display)
21
Unique VRV IV
core technologies
Newly developed
37
compressor
patents
High efficiency 6-pole motor
Full inverter
efficiency
start-up currents
Stepless capacity control
Thixocasting process
Refrigerant-cooled PCB
Reliable cooling because it is not influenced by
UNIQUE
patents
efficiency
22
10
patents
Target
Predictive Control
Function (PCF)
General VRF:
Double time against VRV IV
2t
(VRV IV)
(general VRF)
Half time
against
general
VRF
DC fan motor
UNIQUE
Outer rotor DC motor for higher efficiency
DC fan motor
Stator
Stator
Rotor
I-demand function
In 85C
In 85C
43C
55C
27C
55C
27C
60C
50C
55C
Out 45C
Out 45C
Power consumption
Predefined limit
Time
23
VRV IV
Standard & Technologies
UNIQUE
24
Benefits
VRV
Latest technology, highest efficiency
VRV, a total commercial solution
Drastically reducing your running costs
26
Top reliability
Up to 6 times greater resistance against corrosion
28
Maximum flexibility
30
32
25
ON
ON
OFF
ON
OFF
Performed tests:
VDA Wechseltest
Contents of 1 cycle (7 days):
24 hours salt spray test SS DIN 50021
96 hours humidity cycle test KFW
DIN 50017
48 hours room temperature & room humidity
Aluminium
Heat exchanger
Corrosion-resistant
Acrylic resin
Degree
of corrosion
8
7
6
5
4
3
2
1
0
1 2 3 4 5
Cycle
Bare aluminium
DAIKIN P.E.
Degree of
corrosion
10
9
8
7
6
5
4
3
2
1
0
1 2 3 4 5 6 10 20 30 40 50 60 70
Cycle
26
Benefits
ALL
Sequential Start
Up to 3 outdoor units can be connected to 1 power
supply and can be turned on sequentially. This allows
the number of breakers and their capacities to remain
small and simplifies wiring (for models of 10HP or less).
1 v/d 2 kiezen
Top quality
Only brazed connections
Flare or flange
27
Cooling
Time
VRV SERIES (DAIKIN indoor unit (PID controlled))
Note: The graph shows the data, measured in a test room assuming
actual heating load. The thermostat can control stable room
16
Continuous heating
During defrost
Indoor comfort not effected via the unique heat
accumulating element or alternate defrost
The best alternative to traditional heating systems
VRV IV
VRF benchmark
Time
Back-up function
In the event of a compressor malfunction another
compressor or outdoor unit will take over in order
to maintain 8 hour interim capacity, allowing time
for maintenance or repair while comfort remains
guaranteed.
Single outdoor unit
with multiple compressors
28
Benefits
db(A)
Perceived loudness
Treshold of hearing
Sound
-
20
Extremely soft
Rustling leaves
40
Very soft
Quiet room
60
Moderately loud
Normal conversation
80
Very loud
100
Extremely loud
Symphonic orchestra
120
Threshold of feeling
emura
19dB(A)
25.5dB(A)
10 hrs
50%
Capacity* %
Load %
Operation Sound dBA
Night mode
Step 1
Step 2
<
00000
29
Maximum flexibility
Wide operation range
Air cooled
Water cooled
-10C
-20C DB
52C DB
-25C WB
15.5C WB
45C
* Ethylene glycol should be added to the water when the water inlet
45C
temperature is below 5C
Cooling mode
Heating mode
even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat
90m piping
length after first
branch
VRV-W
VRV-W
even checken in de
infographics map: ik denk
dat er een tekening van
een VRV bestaat
Indoor installation
Unlimited water piping length
VRV IV example
Air cooled
Total piping length
Water cooled
1000m
300m
165m (190m)
120m (140m)
90m1
40m (90m1)
90m
50m (40m)
30m
15m
1 Contact your local dealer or consult technical literature for more information and restrictions
2 In case outdoor unit is located below indoor units
Phased installation
Installation of the VRV system can be implemented
floor by floor, so that sections of the building can
be put into use very quickly, or enabling the air
conditioning system to be commissioned and
operated in stages, rather than on final completion of
the project.
30
Under construction
VRV system
Installation
floor by floor
Indoor installation
Water cooled
Air cooled
ESP up to
78.4 Pa
Benefits
Multiple tenants,
one outdoor unit
The multi tenant function ensures that the entire VRV
system does not shut down when the main power
supply of an indoor is switched off.
This means that the indoor units main power supply
can be turned off when a part of the building is
closed or is being serviced without affecting the rest
of the building.
operation
in holiday
in service
operation
multi tenant
No structural
reinforcement necessary
Thanks to the vibration-free and sufficient light
construction of the outdoor units, floors do not need
to be reinforced, reducing the overall cost of the
building when compared to a chiller.
31
1 v/d 2 kiezen
Calculate extra
Check on regular
Stop manually
refrigerant volume
filling process
to check weight of
Manual
refrigerant
Automatic
Push button
on the PCB
Connect bottle
Filling procedure
stops automatically:
charging function
close valves
R410-A
10% undercharged
calculation:
2.2 kg extra refrigerant required
0.5 kg
Real installation
76 m refrigerant piping
Compliance to
F-gas regulation
When activating the refrigerant containment check, the unit switches into cooling
mode and duplicates certain reference conditions based on memory data.
The result indicates whether or not refrigerant leakage has occurred.
The refrigerant volume of the complete system is calculated for the following data:
Outdoor temperature
Reference system temperatures
Reference pressure temperatures
Refrigerant density
Types and number of indoor units
32
push buttons
Benefits
1 v/d 2 kiezen
1 v/d 2 kiezen
Compact design
The compact design of the outdoor units is sufficient
to allow them to be taken up to the top of a
building in a commercial elevator, overcoming site
transportation problem, particularly when outdoor
units need to be installed on each floor.
foto in crkeltje zou ik
behouden
Push button
on the PCB
Push button
on the PCB
R410-A
REFNET joint
T-joint
REFNET joint
REFNET
header
Daikin Europe N.V. advises only to use Daikin REFNET piping system.
33
34
Overview of
Widest
range of
BS boxes
Unique
continuous
heating
Widest
range
VRVIV
VRVIV
VRVIV
heat
heat pump VRV IV
Heat
pump with without
S-series
recovery continuous continuous (compact)
heating
heating
Unique
product
VRV IV
i-series
VRV III-C
VRV
Classic
Replacement
VRVIV
heat pump
Replacement
VRV III
Heat
recovery
Water
cooled
VRVIV
REYQ-T
RYYQ-T
RXYQ-T(9)
RXYSCQ-TV1
RXYSQ-TV1
RXYSQ-TY1
SB.RKXYQ-T
RTSYQ-PA
RXYCQ-A
RQYQ-P
RXYQQ-T
RQCEQ-P
RWETQ-T8
Page
40
50
50
58
76
88
94
99
99
110
Continuous heating
(alternate defrost)
Continuous heating
(heat accumulating element)
VRV configurator
7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode
Low noise function
Connectable to stylish indoor units
(Daikin Emura, Nexura)
(1)
not available on
RXYSQ4,5,6,8TY1
functions
(1)
35
Outdoor units
Products overview
VRV IV heat recovery
Model
Product name
Best efficiency & comfort solution
Fully integrated solution with heat recovery for maximum efficiency
Covers all thermal needs of a building via a single point of contact: accurate
temperature control, ventilation, hot water, air handling units and Biddle air
curtains
Free heating and hot water through heat recovery
The perfect personal comfort for guests/tenants via simultaneous cooling and
heating
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature and continuous heating
Allows technical cooling
Widest range of BS boxes on the market
PG
8 10 12 13 14 16 18 20 22 24 26 28
REYQ-T
VRVIV-S
series
Compact
NEW
VRVIV-S
series
NEW
RXYQ-T(9)
temperature control, ventilation, air handling units and Biddle air curtains
Either connect VRV of stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as Variable Refrigerant
temperature
RXYSCQ-TV1
temperature control, ventilation, air handling units and Biddle air curtains
Either connect VRV of stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as Variable Refrigerant
temperature
58
Compact
RXYSQ-TV1/
TY1
TV1
65
TY1
SB.RKXYQ-T*
82
temperature
Covers all thermal needs of a building via a single point of contact: accurate
temperature control, ventilation and Biddle air curtains
VRV Classic
heat recovery
RTSYQ-PA
RXYCQ-A
RQCEQ-P*
88
94
99
RXYQQ-T*
103
RWEYQ-T8*
110
Single unit
Multi combination
50
Compact and lightweight single fan design saves space and is easy to install
Covers all thermal needs of a building via a single point of contact: accurate
heat pump
Replacement
Reduced CO
Water cooled
50
36
VRV IVheat
pump for
indoor installation
NEW
RYYQ-T
44
accurate temperature control, ventilation, hot water, air handling units and
Biddle air curtains
Connectable to stylish indoor units (Daikin Emura, Nexura)
Incorporates VRV IV standards & technologies such as
Variable Refrigerant temperature and continuous heating
AHU connection
EKEXV- + EKEQMCBA
AHU connection
EKEXV- + EKEQFCBA
HT Hydrobox HXHD-A
LT Hydrobox HXY-A
O O
with LT Hydroboxes
O O O
Remarks
O O O O
O O O O
O O O O O O
O O O O O O
O O O O
with HT hydrobox
... connection of indoor unit possible, but not neccessarily simultaneously with other allowed indoor units
... connection of indoor unit possible even simultaneously with other checked units in the same row
O ... connection of indoor not possible on this outdoor unit system
37
Capacity (HP)
30 32 34 36 38 40 42 44 46 48 50 52 54 Description / Combination
Outdoor units
VRV Outdoor
PARK PHI
BREEAM EXCELLENT OFFICE BUILDING
WATERCOOLED VRV
38
VRV Outdoor
VRV IV S-SERIES
39
22
Air curtain
system
Control systems
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode
Low noise function
VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort
Continuous heating
The new standard in heating comfort
VRV configurator
Software for simplified commissioning,
configuration and customisation
40
3-pipte
North
Cooling
Hot water
+
South
Heating
Maximum comfort
A VRV heat-recovery system allows simultaneous
cooling and heating.
For hotel owners, this means a perfect
environment for guests as they can freely
choose between cooling or heating.
For offices, it means a perfect working indoor
climate for both north and south-facing offices.
Cooling load
Improved efficiency
Improved mix
mode control
Ambient
temperature
Heating load
Optimised Partition
of Heat Exchanger for
highest seasonal efficiency
in heat recovery mode
30%
70%
During heating, the bottom of the heat exchanger stays hot,
Wide heating
operation range
-15
-10
-5
-20
-15
-10
-5
-20CWB
15
15
15.5CWB
Heating
-25
-20
-20
-15
-10
-25CDB -20CDB
-25
-20
-5
43 45
-5CDB
-15
-10
Technical Cooling
-5
43CDB
43 45
Cooling
41
Advantages
of 3-pipe technology
More free heat
Daikin 3-pipe technology needs less energy to
recover heat, meaning significantly higher efficiency
during heat recovery mode. Our system can recover
heat at a low condensing temperature because it has
dedicated gas, liquid and discharge pipes.
5
moreto 15%
efficie
in hea
nt
t reco
ver
Pressure
comp
a
red to
Condensing 55 C
Condensing 45 C
system
y mod
e
2-pipe
Up
more to 5%
co
capac oling
ity
av
Pressure
2-pipe system
ailable
a
piping t longer
length
comp
s
ared t
o 2-pip
e
system
Pipe length
Save on refrigerant
Smaller diameter pipes and 3-pipe system results
1000m
165m (190m)
90m1
90m1
30m
42
90m maximum
Fully redesigned
BS boxes
Maximum design flexibility
and installation speed
Quickly and flexibly design your system with a
Outdoor Unit Product Range
Single port
Unique to the market
Compact and light to install
No drain piping needed
Ideal for remote rooms
Technical cooling function
Connect up to 250 class unit (28 kW)
Allows multi-tenant applications
Multi port: 4 6 8 10 12 16
Up to 55% smaller and 41% lighter than
previous range
Faster installation thanks to a reduced number
of brazing points and wiring
All indoor units connectable to one BS box
Fewer inspection ports needed
Up to 16 kW capacity available per port
Connect up to 250 class unit (28kW) by
combining 2 ports
No limit on unused ports, permitting
phased installation
Allows multi-tenant applications
BS 4 Q14 A
BS 6, 8 Q14 A
BS 10, 12 Q14 A
BS 16 Q14 A
Maximum comfort at
all times
With the VRV BS box, any indoor unit not being used
to switch between heating and cooling maintains
the constant desired temperature. This is because
our heat recovery system does not need to equalise
pressure over the entire system after a change-over.
Off
BS box
43
REYQ-T
Up to 30m indoor unit
height difference
Outdoor system
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
GWP
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
8T
8
22.4 (1) / 22.4 (2)
22.4 (3) / 22.40 (4)
25.0 (3)
5.31 (1) / 4.56 (2)
4.75 (3) / 4.47 (4)
5.51 (3)
4.22 (1) / 4.92 (2)
7.41
6.25
kW 4.72 (3) / 5.01 (4)
kW
4.54 (3)
100
200
260
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
mm
m
Hz/V
A
REYQ
HP
kW
kW
kW
kW
kW
kW
kW
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
Continuous heating
44
Actual
REYQ
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
Actual
mm
mm
mm
m
A
210
162
78
10T
10
28.0 (1) / 28.0 (2)
28.0 (3) / 28.00 (4)
31.5 (3)
7.15 (1) / 6.19 (2)
6.29 (3) / 5.47 (4)
7.38 (3)
3.92 (1) / 4.52 (2)
7.37
5.78
4.45 (3) / 5.12 (4)
4.27 (3)
12T
14T
12
14
33.5 (1) / 33.5 (2) 40.0 (1) / 40.0 (2)
33.5 (3) / 33.5 (4) 40.0 (3) / 40.00 (4)
37.5 (3)
45.0 (3)
9.23 (1) / 8.31 (2) 10.7 (1) / 9.61 (2)
8.05 (3) / 6.83 (4) 9.60 (3) / 9.37 (4)
9.43 (3)
11.3 (3)
3.63 (1) / 4.03 (2) 3.74 (1) / 4.16 (2)
6.84
7.05
5.36
5.45
4.16 (3) / 4.90 (4) 4.17 (3) / 4.27 (4)
3.98 (3)
64 (5)
150
175
300
350
390
455
125
250
325
1,685x930x765
218
175
79
58
304
223
185
81
61
16T
16
45.0 (1) / 45.0 (2)
45.0 (3) / 45.00 (4)
50.0 (3)
12.8 (1) / 11.9 (2)
11.2 (3) / 9.88 (4)
12.9 (3)
3.52 (1) / 3.79 (2)
6.63
5.14
4.02 (3) / 4.56 (4)
3.88 (3)
18T
18
50.4 (1)
50.4 (3)
56.5 (3)
15.2
12.3 (3)
14.3
3.32
6.26
4.84
4.10 (3)
3.95
200
225
400
450
520
585
1,685x1,240x765
305
260
251
86
64
65
20T
20
56.0 (1)
56.0 (3)
63.0 (3)
18.6
14.9 (3)
17.5
3.01
5.68
4.39
3.76 (3)
3.60
250
500
650
337
261
88
66
-5.0~43.0
-20~15.5 (6)
R-410A
9.7
20.2
9.8
20.5
9.9
20.7
11.8
24.6
2,087.5
12.7
9.52
19.1
15.9
22.2
19.1
20
125
250
325
9.52
22.2
1,000
3N~/50/380-415
32
25
10T
13T
16T
REMQ5T
REMQ5T
REYQ8T
10
13
16
28.0
36.4
44.8
28.0
36.4
44.8
32.0
41.0
50.0
6.34
8.48
10.62
5.42
7.46
9.50
6.50
8.76
11.02
4.42
4.29
4.22
7.77
7.54
7.41
6.55
6.36
6.25
5.17
4.88
4.72
4.92
4.68
4.54
162.5
325.0
422.5
18T
REYQ8T
REYQ10T
18
50.4
50.4
56.5
12.46
11.04
12.89
4.04
7.38
5.98
4.57
4.38
200
400
520
225
450
585
12.7
28.6
19.1
22.2
500
40
15.9
28.6
22.2
20T
28.6
40
50
22T
24T
26T
28T
30T
32T
REYQ10T REYQ8T
REYQ12T
REYQ16T
REYQ12T
REYQ16T REYQ14T REYQ16T REYQ18T REYQ16T
20
22
24
26
28
30
32
55.9
61.5
67.4
73.5
78.5
83.9
90.0
55.9
61.5
67.4
73.5
78.5
83.9
90.0
62.5
69.0
75.0
82.5
87.5
94.0
100.0
14.54
16.38
18.11
19.93
22.03
24.43
25.6
12.80
14.34
15.95
17.65
19.25
20.35
22.4
14.94
16.81
18.41
20.73
22.33
23.73
25.8
3.84
3.75
3.72
3.69
3.56
3.43
3.52
7.06
7.07
6.87
6.95
6.72
6.48
6.63
5.68
5.54
5.46
5.41
5.23
5.03
5.14
4.37
4.29
4.23
4.16
4.08
4.12
4.02
4.18
4.10
4.07
3.98
3.92
3.96
3.88
64 (5)
250
275
300
325
350
375
400
500
550
600
650
700
750
800
650
715
780
845
910
975
1,040
15.9
19.1
34.9
28.6
1,000
50
63
80
v
Cooling
Hot water
+
Heating
REYQ-T
Liquid pipe
Gas pipe
Discharge gas pipe
F1, F2 communication
Hot water
25C - 75C
BS-Box
Domestic hot
water tank
45C - 75C
BS-Box
Heating only
hydrobox for VRV
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
REYQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
Continuous heating
Outdoor unit module
Dimensions
Unit
Weight
Unit
Fan
Air flow rate
Sound power level
Cooling
Sound pressure level
Cooling
Operation range
Cooling
Heating
Refrigerant
Type
Charge
Power supply
Current - 50Hz
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
425
850
1,105
Actual
GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
mm
mm
mm
m
A
450
900
1,170
38T
40T
42T
REYQ8T
REYQ10T
REYQ12T
REYQ18T
38
40
42
106.3
111.9
118.0
106.3
111.9
118.0
119.0
125.5
131.5
29.74
31.58
32.75
25.10
26.64
28.69
29.24
31.11
33.18
3.57
3.54
3.60
6.66
6.68
6.79
5.25
5.20
5.28
4.24
4.20
4.11
4.07
4.03
3.96
475
950
1,235
500
1,000
1,300
525
1,050
1,365
34.9
28.6
80
44T
46T
REYQ12T REYQ14T
REYQ16T
REYQ16T
44
46
123.5
130.0
123.5
130.0
137.5
145.0
34.83
36.3
30.45
32.00
35.23
37.1
3.55
3.58
6.68
6.75
5.20
5.23
4.06
3.90
3.91
64 (5)
550
575
1,100
1,150
1,430
1,495
19.1
41.3
34.9
1,000
100
48T
50T
REYQ16T
48
135.0
135.0
150.0
38.4
33.6
38.7
3.52
6.63
5.14
4.02
3.88
50
140.4
140.4
156.5
40.8
34.7
40.1
3.44
6.49
5.03
4.05
3.90
600
1,200
1,560
625
1,250
1,625
52T
54T
REYQ18T
REYQ18T
REYQ18T
52
54
145.8
151.2
145.8
151.2
163.0
169.5
43.2
45.6
35.8
36.9
41.5
42.9
3.38
3.32
6.37
6.26
4.93
4.84
4.07
4.10
3.93
3.95
650
1,300
1,690
675
1,350
1,755
125
v
Height/Width/Depth
Cooling
Nom.
Nom.
Min.~Max.
Min.~Max.
34T
36T
REYQ16T
REYQ18T REYQ20T
34
36
95.4
101.0
95.4
101.0
106.5
113.0
28.0
31.4
23.5
26.1
27.2
30.4
3.41
3.22
6.43
6.06
4.97
4.70
4.06
3.87
3.92
3.72
Nom.
REMQ
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
Hz/V
A
5T
1,685/930/765
210
162
77
56
-5.0~43.0
-20~15.5
R-410A
9.7
20.2
2,087.5
3N~/50/380-415
20
(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (2) Nominal cooling capacities are based on: indoor
temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (3) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (4) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level
difference: 0m. Data for high efficiency series, Eurovent certified (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
(6) Technical cooling setting, refer to the installation manual for more information | Contains fluorinated greenhouse gases
45
106
Detail
B
107
112
353
134
4-15x22.5mmOblong hole
Foundation bolt hole
Detail B
4-15x22.5mmOblong hole
Foundation bolt hole
125
112
10
10
4-15x22.5mmOblong hole
Foundation bolt hole
125
View C
View C
11
1685
Detail A
729
70
11
66
160
353
134
70
100 AC
Detail
A
AC
View C
107
106
10
70
66
160
729
Detail B
729
AA
100
AA
AB
106
AC
Detail A
339
66
339
hole
Foundation bolt hole
160
3
AB
Pitch 4-15x22.5mm
of foundation bolt holes
Oblong
766
100
112
Detail B
AA
AC
339
REMQ5T / REYQ8-12T
3
REMQ5T
Detail A
REYQ8-12T
125
66
106
technical
drawings
2
1
AB
REMQ5T
100Detailed
REYQ8-12T
160
353
134
107
AA
112
339
AB
729
REYQ8-12T
11
9
1685
122
179
131
259
97
137
930
DETAIL B
Model
AC
AA
AB
RYYQ8T, RXYQ8T, RXYQQ8T
248
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T 195
RYMQ8T 5
248
208 Model
240
REMQ5T, RYMQ10-12T, REYQ8-12T
RXYQ8T,
240
195RYYQ8T,
208
107
DETAIL A
272
RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T
328
107
131
97
765
76
373
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
B
DETAIL
A
272
2.DETAIL
Knockout
hole.
Items 4 - 10:
137
Model
AA
RYYQ8T, RXYQ8T, RXYQQ8T
248
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T 195
RYMQ8T
248
REMQ5T, RYMQ10-12T, REYQ8-12T
195
515
122
373
259
259
179
Notes
76
328
76
276
3. Gas pipe
connection
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T
: 19.1 brazing
76
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
REMQ5T, REYQ8-12T
:
25.4 brazing connection
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 28.6 brazing connection
765
Notes
76
Liquid pipe
131
515
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.
276
Notes
272
515
765
DETAIL A
122
DETAIL B
107
276
97
137
179
76
76
131
2591685
179
276
515
122
11
1685
930
328
3. Gas pipe
Inside of the switch box (M8)
11 Grounding terminal
5
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T 373: 19.1
97 brazing
107 connection
10 Pipe routing hole (bottom)
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
DETAIL
B
272 connection
REMQ5T, REYQ8-12T
: DETAIL A 25.4930
brazing
9 Pipe routing hole (front)
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 28.6 brazing connection
65
8 Power cord routing hole (bottom)
328
Notes RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T : 22.2 brazing connection
Liquid pipe
7 Power cord routing hole (front)
11 Grounding terminal
27
Equalising pipe
REMQ5T, REYQ8-12T
:
25.4 brazing connection
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
373
10 Pipe routing hole (bottom)
DetailRYYQ12T,
A and detail
B indicate
theRXYQQ12T
dimensions
after
fixing
the
attached piping.
6
1.
65
Power
cord
routing
hole
(front)
RYMQ12T,
RXYQ12T,
:
28.6
brazing
connection
RYMQ8-10T :
19.1 brazing connection
9.5 brazing connection
Q8-10T, REMQ5T, REYQ8-12T
2. ItemsLiquid
Knockout hole.
4 - 10:
9 Pipe routing hole (front)
80
Power cord routing hole (front)
pipe
Inside of the switch box (M8)
11 Grounding5terminal
RYMQ12T :
930
:
22.2 brazing connection
8 Power cord routing hole (bottom)
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
10 Pipe routing
(bottom)
65
4 holePower
cord routing hole (side)
3. Gas pipe
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 12.7 brazing connection
REYQ14-20T
9.5 brazing connection
High pressure/low
pressure gasQ8-10T,
pipe REMQ5T, REYQ8-12T
9 Pipe routing hole (front)
7 Power cord routing hole (front)
RYYQ8T,
RYMQ8T, RXYQ8T, RXYQQ8T
: 19.1 brazing connection
See
note
3.
Equalising
pipe
Equalising
pipe
connection
port
:
1 connection
2 : 22.2
RXYQ12T,
19.1 brazing
REMQ5T, REYQ8-12T : RYYQ10T,
65
3 routing hole (bottom)
8 Power
brazing
connection
RYYQ12T,
RYMQ12T,RXYQ10T,
RXYQQ12T
: 12.7
brazing
connection
RYMQ10T,
RXYQQ10T
6 Power cord routing hole (front)
Pitch of foundation
boltcord
holes
High pressure/low pressure gas pipe
19.1 brazing connection
RYMQ8-10T :
7 Power cord routing hole (front)
27
Equalising
pipe
REMQ5T,
REYQ8-12T
:
25.4 brazing connection
1076
5 Power cord routing hole (front)
RYMQ12T :
See note 3.
2
Gashole
pipe
connection port
22.2
brazing
connection
6
65
Power
cord
routing
(front)
RYMQ8-10T
:
19.1
brazingbrazing
connection
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T
: 28.6
connection
4 Power cord routing hole (side)
REYQ14-20T
80
5
Power
cord
routing
hole
(front)
Liquid
pipe
connection
port
High
pressure/low
pressure
gas
pipe
1
See note 3.
RYMQ12T :
22.2 brazing connection
Liquid pipe
Inside of the switch box (M8) Equalising pipe connection port
11 Grounding terminal 65
1
4 Power cord routing
(side)
2
3
19.1 brazing connection
name
REMQ5T, REYQ8-12T :
Remark
No. Parthole
High pressure/low pressure gas pipe
3
Pitch of foundation bolt holes
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
High pressure/low pressure gas pipe
See note 3.
10 Pipe routing hole (bottom)
Equalising pipe connection port
19.1
brazing
connection
REMQ5T, REYQ8-12T :
3
9.5
brazing
connection
393
1076
Q8-10T, REMQ5T, REYQ8-12T
High pressure/low pressure gas pipe
9 Pipe routing hole (front)
2 Gas pipe connection port
:
See note 3.
2 Gas pipe connection port
65
8 Power cord routing hole (bottom)
1 Liquid pipe connection port
134
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T : 12.7 brazing connection
1 Liquid pipe connection port
See note 3.
3
No. Part name
7 Power cord routing holeRemark
27
(front)
No. Part name
Equalising pipe
8
125
6 Power cord routing hole (front)
65
393
19.1 brazing connection
RYMQ8-10T :
80
5 Power cord routing hole (front)
RYMQ12T :
22.2 brazing connection
134
65
4 Power cord routing hole (side)
High pressure/low pressure gas pipe
REYQ14-20T
See note 3.
Equalising pipe connection port
8
REMQ5T, REYQ8-12T :
125
1
2 19.1 brazing connection
3
76
Detail B
Detail A
100
71
134
Detail B
Detail A
Remark
10
70
393
10
View C
125
View C
10
11
AA
See note 3.
107
112
See note 3.
70
106
160
107
112
729
2D079532B
107
AB
AA
729
2D0
70
106
Detail
B
Detail A
160
729
71
AA
192
310
106
2
1
No.
112
192
160
100
71
100
192
AB
310
AB
REYQ14-20T
310
View C
11
1685
11
1685
4
1685
515
122
Notes
Notes
76
76
76
RYMQ18-20T
46
131
259
122
Model
RYMQ14-16T, RXYQQ14-16T, REY
RYMQ18-20T, RXYQQ18-20T
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20
179
179
122
22.2
brazing
connection
RYMQ14-16T
:RXYQQ18-20T
15.9
brazing
connection
RYYQ18-20T,RXYQ14-16T,
RYMQ18-20T, RXYQ18-20T,
RYMQ18-20T
:
28.6
brazing connection
connection
RYYQ18-20T,
RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T
: 15.9 brazing
: :
131131
259
276
276
Liquid pipe
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T : 12.7 brazing connection
Equalising pipe
97
28.6
brazing
connection
22.2 brazing
connection
22.2 brazing connection
DETAIL A
DETAIL A
AA
AB
Model
RYMQ18-20T, RXYQQ18-20T
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T 240
205
RYMQ18-20T, RXYQQ18-20T
240
210
107
272
DETAIL A
328
97
76
High pressure/low
pressure gas pipe
RYMQ14-16T
259
DETAIL B
REYQ14-20T
Equalising pipe
RYMQ18-20T
RYMQ14-16T
179
276
515
137
765
515
76
76
97
107
107
272
373
5
1240
272
328
328
373
373
C C
1240 1240
11
10
9
8
7
6
5
4
3
11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
Grounding terminal
7
Pipe routing hole (bottom) Power cord routing hole (front)
11 Grounding terminal
Pipe routing hole (front)6 Power cord routing hole (front)
10 Pipe routing
hole (bottom)
5(bottom)
Power cord routing hole (front)
Power cord routing hole
Pipe routing
hole (front)
9
4(front)
Power cord routing hole (side)
Power cord routing hole
8 routing
Power
cord
routing hole
(bottom)
Power cord
hole
(front)
Equalising
pipe
connection port
3
7routing
Power cord
hole
(front)
Power
cord
routing
hole (front)
High
pressure/low
pressure gas pipe
Power cord
hole (side)
6 routing
Power
cordGas
routing
(front) port
pipehole
connection
2
Equalising pipe connection port
5 Power 1
cordLiquid
routing
hole
(front)
pipe connection port
High pressure/low pressure gas pipe
4 PowerNo.
cordPart
routing
hole (side)
name
65
27
65
80
65
See note 3.
See note 3.
See note 3.
65
27
Inside of the
switch box (M8)
65
65
27
65
80
65
80
65
See note 3.
See note 3.
See note 3.
Remark
See note 3.
Remark
See note 3.
2D079533B
See note 3.
Remark
<Front>
200 or more
<Front>
400 or more
200 or more
400 or more
500 or more
100 or more
50 or more
50 or more 50 or more
100 or more
<Front>
500 or more
50 or
more
<Unit: mm>
REYQ-T
For centralized group layout
<Pattern1>
<Pattern1>
<Pattern1>
<Suction side>
<Front>
REYQ-T
300 or more
<Front>
300 or more
300 or more
REYQ-T
For single unit installation
<Pattern1>
<Pattern1>
300 or more
300 or more
<Front>
500 or more
20 or more
<Front>group
20 or more
For
centralized
layout10 or more
10 or more
10 or more
NOTES
<Pattern2>
100 or more
500 or more
10 or more
<Front>
<Pattern2>
100
300orormore
more
10 or more
<Front>300 or20more
or more
20 or more
600 or more
<Pattern1>
10 or more 10 or more
10 or more
<Front>
500 or more
300 or more
20 or more
10 or more
<Front>
10 or more
20 or more
500 or more
900 or more
10 or more
500
or more
10 or more
20 or more
10 or more
500 or more
500 or more
1. Heights of walls in case of Patterns 1 and 2:
10 or more
20 or more
10 or more
<Front>
Front: 1500mm
<Pattern2>
Suction side: 500mm
50 or
or more
<Front> 20 or100
50 or more
50 or more 10 or100
50 or10more
<Front>
<Front>
moreor more 10 or
10 or more
20 or more
or more
<Front> 20 or more
10 or more
<Front>
<Front>
more
10 or more 10 or more
20 or
more unrestricted
more 10 or more
more
10 or more
20 or more
Side:
500Height
or more
500 or more
10 or more
500 or more
500 or more
500 or more
500 or more
100
100
600 or more
900 or more <Front>
Installation space as shown on this drawing is based on the cooling operation
or more at 35 degrees outdoor air temperature.
or more
<Pattern3>
<Pattern3>
When the design outdoor
air temperature exceedsWall
35 degrees
or the load exceeds maximum ability because of much generation load of heat in all outdoor units, take the suction side space
height unrestricted
50 or more
50 or
<Front>
<Front>
50 or
100 or more
100 or more
50 or more
more broadly than the space as shown in this drawing.
<Pattern2>
50 or more
<Pattern2>
500 or more
more
50 or
500 or more
more
Wall height
100 or more
300 above
or more wall
300 or
moreh1/2 should be added to the front and
600 or more
300 orsuction
more side service space respectively as shown in the figure on the right.
2. If the
heights are exceeded then
h2/2
and
100 or more
100 or more
more
<Front>
unrestricted 10 or more
10 or more
20 or more
100
10 or more
20 or morealways500bearing
10 or more
3. When installing the units most appropriate
shown above in order to obtainorthe
in mind
the need to leave
more best fit in the space available
500pattern
or more should be selected from those
or
more
10 or more
20 or more
10 or more
<Front>
enough space for a person to pass between units and wall and for the air50toor more
circulate<Front>
freely. (If more
50 or to
morebe installed than are catered for in the above patterns your layout should take
100 or moreunits are
<Front>
<Front>
400 or more
400 or more
100 or more
50 or
50 or more 50 or more
500 or more
50 or more
<Front>
100 or more
account
of the possibility of short
circuits.)
<Pattern2>
200 or more
200 or more
more
500 or more
4. The units
50 or to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
100 or more
100should
or morebe installed
<Front>
50 or more
50 or more 50 or more
<Front>
more
<Unit:
mm>
500 or more
500 or more
Wall height
unrestricted
50 or more
300 or more
<Front>
300 or more
<Front>
200 or more
400 or more
200 or more
<Front>
400 or more
<Suction side>
<Pattern3>
100
or more
50 or more
<Front>
100
or more
<Front>
500 or more
100 or more
50 or
more
50 or
more
<Front>
500 or more
100 or more
50 or more
50 or more
100 or more
100
or more
<Front>
500 or more
100 or more
50 or more
50 or more
100 or more
50 or more 50 or more
100 or more
500 or more
600 or more
50 or
more
<Front>
50 or
more
500 or more
<Unit: mm>
<Suction side>
<Front>
NOTES
NOTES
3D079542
3D079542
3D079542
47
<Pattern3>
BS1Q-A
Indoor unit
Power input
Cooling
Nom.
Heating
Nom.
Maximum number of connectable indoor units
Maximum capacity index of connectable indoor units
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Piping connections
Outdoor unit
Liquid
OD
Gas
OD
Discharge gas OD
Indoor unit
Liquid
OD
Gas
OD
Sound absorbing thermal insulation
Power supply
Phase
Frequency
Voltage
Total circuit
Maximum fuse amps (MFA)
48
BS
kW
kW
mm
kg
mm
mm
mm
mm
mm
Hz
V
A
BS1Q-A
1Q10A
1Q16A
0.005
0.005
6
15 < x 100
1Q25A
8
100<x160
207x388x326
12
160<x250
15
22.2
19.1
22.2
BS-Q14AV1
Unique range of single and multi BS boxes for flexible and fast
design
Major reduction in installation time thanks to wide range,
compact size and light weight multi BS boxes
Up to 70% smaller and 66% lighter than previous series
Faster installation thanks to a reduced number of brazing points
and wiring
All indoor units connectable to one BS box
Less inspection ports needed compared to installing single BS
boxes
Up to 16kW capacity available per port
Connect up to 250 class unit (28kW) by combining 2 ports
No limit on unused ports allowing phased installation
Faster installation thanks to open port connection
Allows multi-tenant applications
Connectable to REYQ-T, RQCEQ-P3 and RWEYQ-T8 VRV IV heat
recovery units
Indoor unit
Power input
Cooling
Nom.
Heating
Nom.
Maximum number of connectable indoor units
Maximum number of connectable indoor units per branch
Number of branches
Maximum capacity index of connectable indoor units
Maximum capacity index of connectable indoor units per branch
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Piping connections
Outdoor unit
Liquid
OD
Gas
OD
Discharge gas OD
Indoor unit
Liquid
OD
Gas
OD
Drain
Sound absorbing thermal insulation
Power supply
Phase
Frequency
Voltage
Total circuit
Maximum fuse amps (MFA)
BS
kW
kW
BS6,8Q14AV1
4Q14AV1
0.043
0.043
20
6Q14AV1
0.064
0.064
30
8Q14AV1
0.086
0.086
40
4
400
6
600
10Q14AV1
0.107
0.107
50
12Q14AV1
0.129
0.129
60
16Q14AV1
0.172
0.172
64
12
16
5
750
140
mm
kg
298x370x430
17
24
mm
mm
mm
mm
mm
9.5
22.2 / 19.1
19.1 / 15.9
12.7
28.6 / 22.2
19.1 / 22.2
Hz
V
A
10
298x580x430
298x820x430
26
35
38
Galvanised steel plate
12.7 / 15.9
15.9
15.9 / 19.1
28.6
28.6 / 34.9
19.1 / 22.2 / 28.6
28.6
9.5 / 6.4
15.9 / 12.7
VP20 (I.D. 20/O.D. 26)
Urethane foam, polyethylene foam
1~
50
220-440
15
298x1,060x430
50
19.1
34.9
49
49
Indoor units
VRV type indoor units
Residential type indoor units
(such as Daikin Emura)
Hot water
Low temperature hydrobox
Control systems
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
7 segment indicator
Automatic refrigerant charge
Refrigerant containment check
Night quiet mode
VRV IV standards:
Variable refrigerant
temperature
Connectable to LT hydrobox
Continuous heating
VRV configurator
DC fan motor
50
M ix o
R A un
its
& VR
V unit
s
FXSQ-A
VRV indoor unit
FXFQ-A
VRV indoor unit
FVXG-K
Nexura
BPMKS967A2
FTXG-LW
Daikin Emura
20 CLASS
25 CLASS
35 CLASS
FTXG20LW
FTXG20LS
FTXG25LW
FTXG25LS
FTXG35LW
FTXG35LS
FTXS20K
FTXS25K
FTXS35K
CTXS35K
FVXG25K
FVXG35K
FVXG50K
FVXS25F
FVXS35F
FVXS50F
FLXS25B
FLXS35B9
FLXS50B
CTXS15K
42 CLASS
50 CLASS
60 CLASS
71 CLASS
FTXS60G
FTXS71G
FTXG50LW
FTXG50LS
FTXS42K
FTXS50K
FLXS60B
51
VRV IV
proven in practice:
40% more efficient
A field trial at a German fashion chain store
demonstrated how the innovative features
of VRV IV have improved energy efficiency
dramatically over previous models.
Average daily
consumption
during working
hours in kWh
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
-2
-1
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
Difference between average daily room temperature and outdoor temperature during opening hours
Avg (kWh/Month)
2.797
1.502
Total (KWh)
33.562
18.023
Total ()
6.041
3.244
9,9
5,3
Period
Yearly (operation
cost/m (/m)
Measured data
Fashion store Unterhaching (Germany)
Floor space: 607m
Energy cost: 0,18 /kWh
System taken into account for consumption:
- VRV IV heat pump with continuous heating
- Round flow cassettes (without auto cleaning panel)
- VAM for ventilation (2x VAM2000)
- Biddle Air curtain.
Free combination of
outdoor units
Freely combine outdoor units to optimise for
small footprint, continuous heating, highest
efficiency or any other combination
1000m
165m (190m)
90m1
90m1
30m
90m maximum
53
RYYQ-T/RXYQ-T(9)
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
RYYQ/RXYQ
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
8T/8T9
8
22.4 (1) / 22.4 (2)
22.4 (3) / 22.40 (4)
25.0 (3)
5.21 (1) / 4.47 (2)
4.75 (3) / 4.47 (4)
5.51 (3)
4.30 (1) / 5.01 (2)
7.53
6.37
kW 4.72 (3) / 5.01 (4)
kW
4.54 (3)
100
200
260
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A
RYYQ/RXYQ
10T
10
28.0 (1) / 28.0 (2)
28.0 (3) / 28.00 (4)
31.5 (3)
7.29 (1) / 6.32 (2)
6.29 (3) / 5.47 (4)
7.38 (3)
3.84 (1) / 4.43 (2)
7.20
5.67
4.45 (3) / 5.12 (4)
4.27 (3)
12T
12
33.5 (1) / 33.5 (2)
33.5 (3) / 33.50 (4)
37.5 (3)
8.98 (1) / 8.09 (2)
7.77 (3) / 6.59 (4)
9.10 (3)
3.73 (1) / 4.14 (2)
6.96
5.50
4.31 (3) / 5.08 (4)
4.12 (3)
125
250
325
1,685x930x765
252/194
175
79
58
243/187
162
78
5.9
12.3
6
12.5
150
300
390
14T
14
40.0 (1) / 40.0 (2)
40.0 (3) / 40.0 (4)
45.0 (3)
11.0 (1) / 9.88 (2)
9.52 (3) / 9.30 (4)
11.2 (3)
3.64 (1) / 4.05 (2)
6.83
5.31
4.20 (3) / 4.30 (4)
4.02 (3)
64 (5)
175
350
455
185
223
22T
10T
12T
251
64
65
261
88
66
10.4
21.7
11.7
24.4
11.8
24.6
86
-5~43
-20~15.5
R-410A
10.3
21.5
2,087.5
12.7
15.9
28.6
1,000
3N~/50/380-415
32
25
24T/24T9
8T
16T
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
22
61.5
61.5
69.0
16.27
14.06
16.48
3.77
7.07
5.58
4.37
4.19
24
67.4
67.4
75.0
18.2
15.85
18.31
3.70
6.81
5.42
26T
14T
26
73.5
73.5
82.5
20.0
17.29
20.30
3.68
6.89
5.39
4.25
4.10
250
500
650
391/314
260
81
61
6.3
13.2
20T
20
56.0 (1)
56.0 (3)
63.0 (3)
18.5 (1)
14.5 (3)
17.0 (3)
3.03 (1)
5.67
4.42
3.86
3.71
200
225
400
450
520
585
1,685x1,240x765
22.2
20
18T
18
50.4 (1)
50.4 (3)
56.5 (3)
15.0 (1)
12.6 (3)
14.6 (3)
3.36 (1)
6.38
4.97
4.00
3.87
356/305
9.52
19.1
16T
16
45.0 (1) / 45.0 (2)
45.0 (3) / 45.0 (4)
50.0 (3)
13.0 (1) / 12.10 (2)
11.1 (3) / 9.8 (4)
12.8 (3)
3.46 (1) / 3.73 (2)
6.50
5.05
4.05 (3) / 4.59 (4)
3.91 (3)
28T
12T
16T
30T
32T
18T
30
83.9
83.9
94.0
24.0
20.4
23.7
3.5
6.60
5.17
4.1
40
50
36T
16T
34T
16T
18T
32
90.0
90.0
100.0
26.0
22.2
25.6
3.46
6.50
5.05
4.05
3.91
34
95.4
95.4
106.5
28.0
23.7
27.4
3.4
6.44
5.01
4.0
3.9
36
101.0
101.0
113.0
31.5
25.6
29.8
3.21
6.02
4.68
3.95
3.79
400
800
1,040
425
850
1,105
450
900
1,170
20T
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
54
Actual
RYYQ/RXYQ
HP
kW
kW
kW
kW
kW
kW
kW
28
78.5
78.5
87.5
22.0
18.87
21.90
3.57
6.69
5.23
4.16
4.06
4.00
38T/38T9
8T
10T
20T
38
106.3
106.3
119.0
29.2
25.1
29.2
3.6
6.36
5.03
4.2
4.1
40T
10T
12T
18T
40
111.9
111.9
125.5
31.3
26.7
31.1
6.74
5.29
4.0
64
275
550
715
Actual
mm
mm
m
A
300
600
780
325
650
845
350
700
910
375
750
975
15.9
475
950
1,235
500
1,000
1,300
19.1
28.6
34.9
41.3
1,000
63
80
100
FXSQ-A
VRV indoor unit
FXFQ-A
VRV indoor unit
FVXG-K
Nexura
BPMKS967A2
FTXG-LW
Daikin Emura
RYYQ-T/RXYQ-T(9)
20 CLASS
25 CLASS
35 CLASS
FTXG20LW
FTXG20LS
FTXG25LW
FTXG25LS
FTXG35LW
FTXG35LS
FTXS20K
FTXS25K
FTXS35K
CTXS35K
FVXG25K
FVXG35K
FVXG50K
FVXS25F
FVXS35F
FVXS50F
FLXS25B
FLXS35B9
FLXS50B
CTXS15K
42 CLASS
50 CLASS
60 CLASS
71 CLASS
FTXS60G
FTXS71G
FTXG50LW
FTXG50LS
FTXS42K
FTXS50K
FLXS60B
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
RYYQ/RXYQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Nom.
Nom.
Max.
Cooling
Heating
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
Actual
Power supply
Current - 50Hz
GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
44T
12T
46T
14T
16T
48T
50T
16T
52T
42
118.0
118.0
131.5
33.3
28.49
32.98
44
123.5
123.5
137.5
35.0
29.97
34.70
6.65
5.19
4.14
3.99
6.62
5.17
4.12
3.96
46
130.0
130.0
145.0
37.0
31.72
36.8
3.51
6.60
5.13
4.10
3.94
525
1,050
1,365
550
1,100
1,430
575
1,150
1,495
3.54
mm
mm
m
A
RYMQ
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
Hz/V
A
48
135.0
135.0
150.0
39.0
33.3
38.4
3.46
6.50
5.05
10T
1,685/930/765
195
175
79
188
162
78
4.05
3.91
64
600
1,200
1,560
19.1
41.3
1,000
6
12.5
20
25
54
151.2
151.2
169.5
45.0
37.8
43.8
3.40
6.38
4.97
4.0
3.90
625
1,250
1,625
650
1,300
1,690
675
1,350
1,755
16T
18T
1,685/1,240/765
20T
125
12T
14T
185
223
309
81
61
58
5.9
12.3
18T
52
145.8
145.8
163.0
43.0
36.3
42.0
3.4
6.42
4.99
50
140.0
140.0
156.0
40.7
34.6
40.0
3.44
6.46
5.02
100
8T
54T
18T
18T
16T
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
42T
10T
6.3
13.2
-5~43
-20~15.5
R-410A
10.3
21.5
2,087.5
3N~/50/380-415
32
319
260
251
64
65
261
88
66
10.4
21.7
11.7
24.4
11.8
24.6
86
40
50
(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (2) Nominal cooling capacities are based on: indoor
temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m. Data for high efficiency series, Eurovent certified (3) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m. Data for standard efficiency series (4) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m,
level difference: 0m. Data for high efficiency series, Eurovent certified (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% <= CR <=
130%) | The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | The AUTOMATIC ESEER value corresponds with normal VRV4 Heat Pump operation, taking into
account advanced energy saving operation functionality ( variable refrigerant temperature control operation) | Contains fluorinated greenhouse gases
55
Detail A
4-15x22.5mmOblong hole
Foundation bolt hole
Detail B
100
160
107
353
134
106
AC
Detail A
107
10
4-15x22.5mmOblong hole
Foundation bolt hole
66
125
125
View C
10
View C
70
AA
AB
339
AC
70
106
353
134
112
66
Detail B
160
112
100
125
70
106
729
AC
Detail A
66
AA
AB
339
RYYQ8-12T
RYMQ8-12T
100
RXYQ8-12T
RXYQQ8-12T
160
353
134
112
729
AA
339
AB
729
107
3 1
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T
Detail B
11
10
4-15x22.5mmOblong hole
Foundation bolt hole
View C
1685
11
11
1685
1685
122
122
122
131
A
930272
11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
930
8 Power cord routing hole (bottom)
Inside of the switch box (M8)
Grounding terminal
93011
(front)
10 Pipe routing7holePower
(bottom)cord routing hole11
Grounding terminal
(front) cord routing hole (front)
9 Pipe routing6holePower
10 Pipe routing hole (bottom)
65
hole (bottom)
8 Power cord5routing
Power
cord routing hole (front)
(front)
9 Pipe routing hole
7 Power cord routing
27
hole (front)
cord routing hole (side)
4 Power
Pitch of foundation bolt holes 6 Power cord routing hole (front)
8 Power cord routing
65 hole (bottom)
Equalising
pipe connection port
80 hole (front)
5 Power cord3routing
hole (front)
1076
7 Power cord routing
High
pressure gas pipe
holepressure/low
(side)
65
4 Power cord routing
6 Power cord routing hole (front)
See note 3.
Equalising pipe
2 connection
Gas pipeport
connection port
3
5 Power cord routing hole (front)
High pressure/low pressure gas pipe
1 Liquid pipe connection port Power cord routing hole (side)
4
See note 3.
2 Gas pipe connection port
No. Part name
1 Liquid pipe connection port
note 3.
Equalising pipeSee
connection
port
3
Remark
No. Part name
High pressure/low
pressure gas134
pipe
2 Gas pipe connection port
1 Liquid pipe connection port
Pitch of foundation bolt holes
No. Part name
71
71
100
106
AB
192
729
160
310
729
AA
Detail B
Detail A
11
71
100
106
160
192
Detail B
240
65
27
65
80
65
65
27
65
80
65
See note 3.
See note 3.
See note 3.
Remark
393
See note 3.
See note 3.
125
See note 3.
2D079532B
Remark
2D079532B
393
134
10
393
134
125
125
View C
8
10
View C
70
Detail A
AB
310
106
70
1076
3
100
RYYQ14-20T
RYMQ14-20T
160
RXYQ14-20T
RXYQQ14-20T
AA
AB
208
208
107
373
112
AB
328
70
373
107
328
112
179
276
259
131
DETAIL
272
RXYQQ14-20T
192
310
97
5
107373
97
DETAIL B DETAIL A
DETAIL B
112
137
137
765 765
3. Gas pipe
Notes
Notes
RYYQ8T, RYMQ8T,
RXYQ8T, RXYQQ8T
:
19.1 brazing connection
Detail A andRXYQQ10T
detail B indicate: the dimensions after
fixing
thebrazing
attached piping.
RYYQ10T, RYMQ10T, 1.RXYQ10T,
22.2
A and
detail B indicateKnockout
the dimensions
after
fixing the connection
attached piping.
1. Detail
2. Items
hole.
4 - 10:
REMQ5T, REYQ8-12T
:
2. Items
Knockout hole. 25.4 brazing connection
4 -pipe
10:
Gas
RYYQ12T, RYMQ12T,3.RXYQ12T,
RXYQQ12T :
28.6
brazing
connection
RYMQ8T, RXYQ8T, RXYQQ8T
:
19.1 brazing connection
pipe
3. Gas RYYQ8T,
RYYQ14-20T
Liquid pipe
RYYQ10T, RYMQ10T, RXYQ10T, RXYQQ10T :
22.2 brazing connection
RYYQ8T,
RYMQ8T,
RXYQ8T, RXYQQ8T
:
19.1 brazing connection
RYMQ14-20T
REMQ5T,
REYQ8-12T
:
25.4 brazing connection
RYYQ8-10T, RYMQ8-10T,
RXYQ8-10T,
RXYQ
RYYQ10T,
RYMQ10T,
RXYQ10T,
RXYQQ10T
: brazing connection
RYYQ12T,
RYMQ12T, RXYQ12T,
RXYQQ12T
: 9.5
22.2
brazing connection
RXYQ14-20T
28.6 brazing
connection
Q8-10T, REMQ5T, REYQ8-12T
1
REMQ5T,
REYQ8-12T2
:
25.4 brazing connection
Liquid pipe
:
RXYQQ14-20T
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T
: brazing connection
RYYQ12T, RYMQ12T,
RXYQ12T,
RXYQQ12T
:
RYYQ8-10T,
RYMQ8-10T,
RXYQ8-10T,
RXYQ 12.7
28.6 brazing connection
9.5 brazing connection
Q8-10T, REMQ5T, REYQ8-12T
Equalising pipe
Liquid
: pipe
12.7 brazing connection
RYYQ12T, RYMQ8-10T,
RYMQ12T, RXYQ12T,
RXYQQ12T
: 19.1 brazing
RYYQ8-10T,
RXYQ8-10T,
RXYQ
RYMQ8-10T :
connection
3
9.5 brazing connection
Equalising
pipe
Q8-10T,
REMQ5T,
REYQ8-12T
RYMQ12T :
22.2 brazing connection
RYMQ8-10T :
19.1 brazing connection
:
High pressure/low pressure
gas pipe
12.7
brazing connection
RYMQ12T
:
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T :
22.2 brazing
connection
19.1 brazing connection
REMQ5T, REYQ8-12T
: High pressure/low pressure gas pipe
RYYQ14-20T
Equalising pipe
19.1 brazing connection
REMQ5T, REYQ8-12T :
RYMQ14-20T
RYMQ8-10T :
19.1 brazing connection
RXYQ14-20T
RYMQ12T :
1
2
22.2 brazing connection
AA
248
195
248
195
AA
248
195
248
195
107
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.
C
107
328
76
76
107
272
Model
RYYQ8T, RXYQ8T, RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T
729
76
76
Model
RYYQ8T, RXYQ8T, RXYQQ8T
RYYQ10-12T, RXYQ10-12T, RXYQQ10-12T
RYMQ8T
REMQ5T, RYMQ10-12T, REYQ8-12T
Model
Notes
97
DETAIL A
179
DETAIL B
765
259
276
515
137
9
131
259
179
515
276
515
76
76
10
AA
Detail B
Detail A
View C
1685
11
11
1685
1685
515
122
Notes Notes
Liquid pipe
Detail1.ADetail
and detail
B indicate
the
dimensions
fixing
theattached
attached
piping.
1. RYMQ14-16T,
A and
detail
B indicate
the
dimensionsafter
after
fixing the
RYYQ14-16T,
RXYQ14-16T,
RXYQQ14-16T,
REYQ14-20T
: piping.
12.7 brazing connection
Knockout
hole.
2. Items2.4 Items
Knockout
hole.
- 10: 4 - 10:
RYMQ18-20T
56
179
131
107
272
328
373
97
AA RXYQQ18-20T
AB
Model
RYMQ18-20T,
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
240
205
RYMQ18-20T, RXYQQ18-20T
240
210
C
107
272
1240
5
328
373
1240
1240
:
28.6 brazing connection
Equalising pipeRYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
Liquid pipe
: 22.2
brazing
connection
RYMQ14-16T Liquid pipe
RYYQ14-16T, RYMQ14-16T,: RXYQ14-16T, RXYQQ14-16T, REYQ14-20T
12.7 brazing
connection
RXYQQ14-16T, REYQ14-20T
: brazing
12.7
brazing connection
RYMQ18-20T RYYQ14-16T, RYMQ14-16T, RXYQ14-16T,
:
28.6
connection
RYYQ18-20T,
RYMQ18-20T,
RXYQ18-20T, RXYQQ18-20T
High pressure/low
pressure gas
pipe
Equalising pipe
REYQ14-20T
:
RYMQ14-16T
:
Equalising pipe
RYMQ18-20T
:
RYMQ14-16T
:
328
373
DETAIL A
DETAIL A
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
272
97
DETAIL B
25.4
brazing
DETAIL
B connection
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T
107
131
276
259
Notes
179
276
765
259 122
515
DETAIL B
97
DETAIL A
515
137
131
259
179
276
76
122
76
11
10
9
8
7
6
5
4
3
11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
7 Power cord routing hole (front)
Grounding terminal
6 Power cord routing hole (front)
Pipe routing hole (bottom)
11 Grounding
terminal
5 Power
cord routing hole (front)
Pipe routing hole (front) 10 Pipe routing hole (bottom)
4 Power cord routing hole (side)
Power cord routing hole (bottom)
routing hole (front)
9 Pipe pipe
Equalising
connection port
Power cord routing hole (front)
3
8 pressure/low
Power cord routing hole (bottom)
High
pressure gas pipe
Power cord routing hole
(front)
7 Power cord routing hole (front)
Power cord routing
(front)
Gas
pipe connection port
2 hole
6 Power cord routing hole (front)
Power cord routing hole (side)
Liquid
pipe connection port
1
Equalising pipe connection
5 port
Power cord routing hole (front)
Part name
No.
High pressure/low
pressure
pipe cord routing hole (side)
4 gas
Power
65
27
65
80
65
See note 3.
See note 3.
2 Gas pipe connection port
Equalising pipe connection port
3
1 Liquid pipe connection port
High pressure/low pressure gas pipeSee note 3.
Remark
No. Part name
65
27
65
Inside of the switch box (M8)
80
65
See note 3.
65
27
65
80
Remark
65
See note 3.
2D079533B
See note 3.
See note 3.
2D079533B
See note 3.
See note 3.
Remark
2D079533B
RYYQ-T
RYMQ-T
RXYQ-T
RXYQQ-T
RYYQ-T / RXYQ-T(9)
For single unit installation
(Pattern 1)
300 or more
(Pattern 1)
300 or more
10 or
more
(FRONT)
500 or more
(Pattern 2)
10 or
more
20 or more
(FRONT)
500 or more
20 or more
10 or more 10 or more
300 or more
(FRONT)
600 or more
20 or more
(FRONT)
500 or more
20 or more
10 or more
10 or more
(FRONT)
500 or more
10 or more
10 or more
300 or more
(FRONT)
20 or more
10 or more 10 or more
500 or more
10 or more
20 or more
900 or more
(Pattern 2)
100 or more
50 or more
300 or more
(FRONT)
500 or more
100 or more
50 or
more 50 or more
(Pattern 3)
300 or more
(FRONT)
200 or more
10 or more
20 or more
10 or more
10 or more
20 or more
(FRONT)
500 or more
10 or more
(Pattern 2)
100 or more
(Pattern 3)
Wall height
unrestricted
(FRONT)
500 or more
100 or more
50 or more
100 or
more
50 or more
300 or more
400 or more
200 or more
(FRONT)
400 or more
50 or more
(FRONT)
500 or more
(FRONT)
500 or more
100 or more
100 or more
100 or
more
50 or
more 50 or more
100 or
more
50 or more
50 or more
(FRONT)
(FRONT)
500 or more
100 or more
50 or more
50 or more
100 or more
500 or more
600 or more
50 or more
10 or more
300 or more
100 or more
50 or more 50 or more
100 or more
(FRONT)
500 or more
50 or more
<Suction side>
<Front>
<Unit = mm>
NOTES
3D079542
57
22
Control systems
Indoor units
VRV type indoor units
Residential type indoor units
(such as Daikin Emura)
RXYSCQ4, 5TV1
Air curtain
Biddle Air curtain for VRV (CYV)
RXYSQ4, 5, 6TV1/TY1
Ventilation
Heat Reclaim ventilation
(VAM/VKM) AHU
connection kit
VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort
VRV configurator
Software for simplified commissioning,
configuration and customisation
58
823mm
1615mm
8 HP
4/5/6 HP
4/5 HP
Outdoor Unit Product Range
10/12 HP
Compact:
Easy for a two person crew
to move and install.
Low height make the unit invisible from inside and unnoticeable from the outside
1,685mm
823mm
765mm
320mm
460mm
900mm
940mm
930mm
59
FXZQ-A
FXSQ-A
FXAQ-P
FCQG-F
BPMKS967A2
BPMKS967A2
FVXG-K - Nexura
CTXS-K
20 CLASS
25 CLASS
FTXG-L
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L
FTXS-K
FTXS-K
FVXG-K
FVXS-F
FLXS-B(9)
35 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L
CTXS-K
FTXS-K
FHQ-C
FVXG-K
FVXS-F
FLXS-B(9)
For more info about Daikins stylish indoor units, please check our indoor unit-portfolio
* VRV indoor units and stylish indoor units cannot be combined.
* To connect stylish indoor units a BPMKS unit is needed
60
42 CLASS
50 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
FTXG-L
60 CLASS
FCQG-F
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
71 CLASS
FTXS-K
FTXS-K
FTXS-G
FTXS-G
FHQ-C
FVXG-K
FVXS-F
FLXS-B(9)
FHQ-C
FLXS-B(9)
Cooling
4.001
Heating
4.522
0 1 2 3 4 5
2m
15m
40m
40m
5m
50m (40m1)
30m
15m
15m
40m maximum
250m
300m
150m (175m)
Stylish indoors
connected
VRV indoors
connected
61
VRV IV S-series
technologies
Refrigerantcooled PCB
New
Air streams
collide and
generate loss
Compressor
Separate
Collision
Air streams
are smoothed around V-cut
and reduces air flow loss
In 85C
In 85C
43C
55C
27C
I-demand function
55C
27C
60C
50C
55C
Out 45C
Out 45C
Power consumption
Predefined limit
Time
62
Mini VRV
PARAPET INSTALLATION
63
RXYSCQ-TV1
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Actual
RXYSCQ
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
RXYSCQ-TV1
4TV1
4
12.1
12.1
14.2
3.43
3.18
4.14
3.53
3.81
3.43
5TV1
5
14.0
14.0
16.0
4.26
3.91
5.00
3.29
3.58
3.20
64 (1)
50
62.5
-
130
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A
162.5
823x940x460
94
91
68
51
69
52
-5~46
-20~15.5
R-410A
3.7
7.7
2,087.5
9.52
15.9
1~/50/220-240
32
(1) Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
(2) Contains fluorinated greenhouse gases
64
RXYSQ-TV1/RXYSQ-TY1
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
RXYSQ-TV1/RXYSQ-TY1
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
EER
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
mm
kg
m/min
dBA
dBA
CDB
CWB
4TV1
4
12.1
12.1
14.2
3.03
2.68
3.43
4.00
4.52
4.14
5TV1
5
14.0
14.0
16.0
3.73
3.27
4.09
3.75
4.28
3.91
6TV1
6
15.5
15.5
18.0
4.56
3.97
5.25
3.40
3.90
3.43
4TY1
4
12.1
12.1
14.2
3.03
2.68
3.43
4.00
4.52
4.14
50
62.5
70
50
130
162.5
68
50
69
182
130
1,345x900x320
104
106
70
68
50
-5~46
51
5TY1
5
14.0
14.0
16.0
3.73
3.27
4.09
3.75
4.28
3.91
64 (1)
62.5
162.5
69
6TY1
6
15.5
15.5
18.0
4.56
3.97
5.25
3.40
3.90
3.43
8TY1
8
22.4
22.4
25.0
6.12
5.20
6.22
3.66
4.31
4.02
10TY1
10
28.0
28.0
31.5
8.24
6.60
8.33
3.40
4.24
3.78
12TY1
12
33.5
33.5
37.5
10.15
8.19
10.25
3.30
4.09
3.66
70
100
125
150
182
260
1,430x940x320
144
140
73
70
51
55
325
390
1,615x940x460
175
180
182
74
76
57
-5~52
-20~15.5
R-410A
kg
TCOeq
3.6
7.5
4.5
9.4
7
14.6
8
16.7
22.2
12.7
25.4
2,087.5
Actual
mm
mm
m
Hz/V
A
15.9
19.1
9.52
15.9
19.1
-
1N~/50/220-240
32
(1) Actual number of units depends on the indoor unit type (VRV DX indoor, RA DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
(2) Contains fluorinated greenhouse gases
3N~/50/380-415
16
25
32
65
Grounding terminal
Inside of the switch box (M5)
30
37
52
485
460
30
M12
60
101
170
620
40
150
940
2
1
823
3
5
88
19
19
100
151
53 95
60
53 95
289
313
17
62 59 118 102
104
17
52
69
80
20
216
130
21
32
98
89
3D098107
RXYSQ4-6TV1
RXYSQ-TV1
RXYSQ4-6TY1
1
140
M12
620
140
320
30
350
(345~355)
Drain outlet
Model
59
43
30
40
94
900
30
RMXS140E8V1B
RMXS160E8V1B
RXYSQ4PA7V1B
4
3
RXYSQ6PA7V1B
ERX140A9V1B
GCA100BD4
1345
GCA125BD4
GCA140BD4
RXYSQ4PA7Y1B
ERX125A9V1B
RXYSQ5PA7V1B
ERX100A9V1B
RMXS112E8V1B
RXYSQ5PA7Y1B
RXYSQ6PA7Y1B
5
52
55
223
148
55
95
80
84
13
19
54
19
89
142
71
54
67
145
70
58
102
117
16
16
89
24
95
60
423
430
45
5
376
191
Model
A
RA indoor unit
RXYSQ4(P8/T7)V1B
RXYSQ5(P8/T7)V1B
RXYSQ6(P8/T7)V1B
RXYSQ4(P8/T7)Y1B
RXYSQ5(P8/T7)Y1B
RXYSQ6(P8/T7)Y1B
3TW30374-1D
66
30
61
48
320
M12
350
(345-355)
30
44
96
160
620
30
160
940
1430
8
7
8
54 95
52
80
19
13
145
142
9
16
16
68 67
151
68
90
19
54
89
84 55
95
60
55
223
53 95
89
67
Grounding terminal
47
395
191
3D098108
RXYSQ10-12TY1
52
30
460
490
(485-495)
64
49
30
RXYSQ10-12TY1
97
620
170
150
940
40
5
4
3
2
633
95
53
100 22
95
6
53
88
28
60
626
1615
19
80
154
62
59 118 102
52
216
20
130
21 89
98
32
Grounding terminal
Inside of the switch box (M8)
3D098109
67
68
RXYSCQ-TV1
69
70
RXYSQ-TV1 / / RXYSQ4-6TY1
71
72
RXYSQ-8TY1
73
74
RXYSQ10-12TY1
75
uniqu
e
paten
ted
conce
pt
Air curtain
Biddle Air curtain for VRV (CYV)
22
Indoor units
VRV type indoor units
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
Control systems
VRV IV standards:
Variable refrigerant
temperature
Customize your VRV for best seasonal
efficiency & comfort
VRV configurator
76
Invisible
Consider a wider range of properties because
installation
Quiet
Highly suited to densely populated areas such as
Lightweight parts
can be installed
by two people
<
Dedicated modes reduce sound further to comply
77
2. The compressor is
compact and easy to
hide, this element can
be installed at floor
level, in a back office,
storage room, technical
area or in a kitchen.
This means that the air conditioning system is completely invisible and does not take up expensive commercial floor space.
Max. 70 m
Max. 30 m
Compressor unit
78
79
High flexibilty
The other way around: install the modules
where if fits your customer, not where it is
the best fit for the outdoor unit
If there is no flat roof or backgarden available for
installation of the outdoor unit, VRV IV i-series offers
the solution.
The suction and exhaust can be installed at the
faade or at the rear of the building as the inverter
fans allows ESP to be adjusted to the length of the
ductwork.
The compressor module can be installed up to 30 m
from the heat exchanger unit in a storage room, ....
80
Example 2
short distance
Example 3
Other VRF
technical
aera
stock
kitchen
VRV IV i-series
sound
cage
Other VRF
VRV IV i-series
=
stock
kitchen
SHOP
SHOP
81
Patented V-shape
heat exchanger
for best surface to volume ratio
Optimised air flow and
temperature distribution
Best performance for defrost (tested in high humidity
down to -20C).
patents
Patented
perforated
and insulated
partition plate
Reduces conductivity and
prevents cold bridges
Only
400mm
high
Fits easily in
any false ceiling
Super efficient
centrifugal fans
Standard delivered filter
with the unit to prevent dirt from entering the
heat exchanger
82
Rotating switchbox
For easy access to all compressor parts
Only
77 kg
Tube-in-tube
subcool heat
exchanger
This patented heat
exchanger increases the
capacity of the system by
ensuring optimal state
of refrigerant in the heat
exchanger module. This
in turn increases overall
efficiency.
No drain connection
needed
Thanks to natural evaporation
Minimized cold surface to reduce
dew formation
Fast and easy installation
Non welded
bottom casing
Avoids any corrosion risk
Small footprint
Maximizes useable floor space (600 x 550 mm)
Can easily be mounted in a storage room, back office,
83
SB.RKXYQ-T
SB.RKXYQ5T
Max. 70 m
Max. 30 m
VRV Indoor
units
Compressor unit
SB.RKXYQ
Compressor unit
Heat exchanger unit
Nom.
Nom.
Max.
Cooling
Heating
35CDB
6CWB
6CWB
Nom.
Nom.
Max.
EER
COP
at nom. capacity
at nom. capacity
at max. capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Fan
External static
Max.
Nom.
pressure
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Temperature
Min.
Max.
around casing
Piping connections
Between Compressor
Liquid
module (CM) and heat
Gas
exchanger module (HM)
35CDB
6CWB
6CWB
35CDB
6CWB
6CWB
HP
kW
kW
kW
kW
kW
kW
kW/kW
kW/kW
kW/kW
OD
OD
Pa
Pa
CDB
CWB
CDB
CDB
mm
mm
OD
mm
OD
mm
Actual
System
2016
5T
RKXYQ5T
RDXYQ5T
5
14.0
14.0
16.0
4.38
3.68
4.71
3.20
3.80
3.40
10 (1)
62.5
162.5
150
60
-5~46
-20~15.5
5
35
12.7
19.1
22.2
9.5
9.52
15.9
19.1
140
300
compressor module
RKXYQ5T
RKXYQ8T
701/600/554
701/760/554
77
100
47
56
R-410A
R-410A
2
4
4.2
8.4
2,087.5
2,087.5
3N~/50/380-415
3N~/50/380-415
16
-
(1) Actual number of units depends on the indoor unit type (VRV DX indoor, etc.) and the connection ratio restriction for the system (being; 50% CR 130%).
Power supply
Current - 50Hz
Unit
Unit
Type
Air flow rate
Discharge direction
Cooling
Cooling
Type
Charge
Height/Width/Depth
Cooling
Nom.
Nom.
GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
84
Nom.
mm
kg
m/min
dBA
dBA
kg
TCOeq
Hz/V
A
8T
RKXYQ8T
RDXYQ8T
8
22.4
22.4
(1)
100
260
150
-5~46
-20~15.5
5
35
12.7
lf
239
62
255
149
45
View A
5
239
705
1044
Suspension position
9 (4x)
4
149
1456
1498
Suspension position
45
View A
9 (4x)
1196
99
1456
1498
Suspension position
8
1196
117
2
25
102
27
25
117
298
397
99
26
67
27
659
102
716
659
716
9 Hook
9 Hook
8 Service door
8 Service door
wiring)
5 Wiring intake (low voltage
Drain outlet
3
wiring)
4 Wiring intake (high voltage
connection port
2 Gas pipe
3 Drain outlet
2D098826
2D098826
RKXYQ-T
RKXYQ5T7Y1B
600
4x O17
554
118
View A
57
101
8
57
Indoor unit
701
54
6
337
365
4
Heat exchanger unit
426
Pitch of foundation bolt holes
88
120
55
516
59
85
8 Handle
7 Pipe routing hole
6 Wiring intake (low voltage wiring)
5 Wiring intake (high voltage wiring)
15
Knockout hole.
Transmission wiring connection
Power supply connection
15.9 brazing connection
9.5 brazing connection
19.1 brazing connection
12.7 brazing connection
Remark
3D098827
85
100 or more
100 or more
10 or more
500 or more
3D098834
RKXYQ-T
10 or more
10 or more
500 or more
10 or more
10 or more
RKXYQ5T7Y1B
Front view
Top view
3D098835
86
Keep looking
youll never find me
i
Find out more at www.daikineurope.com/citysecret
87
VRVIII-C
VRV heat pump
Indoor units
VRV type indoor units
Control systems
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
ump
at p
he
dard
2.00
Stan
1.00
0.00
-25
-20
-15
-10
-5
Outdoor temp. (WB)
10
Heating mode
Cooling mode
VRVIII-C
Standard VRV
-25CWB
-20CWB
15.5C
43CDB
-5C
Outdoor Temp.
Outdoor Temp.
(kW) 35
30
heating capacity
25
20
15
10
5
0
-25
-20
-15
-10
-5
0
Outdoor temp. (CWB)
Heating capacity 10HP outdoor unit
10
89
60
50
30
30
25
20
10
20
Indoor temperature C
40
50% reduction
-10
-20
-5
5 6
10
Elapsed time (min.)
Indoorpositie
temperatureblauwe
VRVIII-C
lijnen:
15
14 15
20
X +10
10m
40m (90m1)
50m (40m)
90
15m
90m maximum
500m
165m (190m)
RTSYQ-PA
Heating
capacity
High
Liquid injection
Gas-liquid
separator
Middle
Pressure
Gas injection
Low
Input power
Evaporator capacity
Enthalpy
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
RTSYQ
Outdoor unit module 1
Outdoor unit module 2
Function unit
Nom.
Nom.
Cooling
Heating
10PA
RTSQ10PAY1
14PA
RTSQ14PAY1
-
10
28.0
31.5 (1) / 28.0 (2)
7.90
7.78 (1) / 8.18 (2)
3.54
4.05 (1) / 3.42 (2)
21
125
250
325
60/62
9.52
22.2
14
40.0
45.0 (1) / 40.0 (2)
12.6
11.4 (1) / 12.8 (2)
3.17
3.95 (1) / 3.13 (2)
30
175
350
455
61/63
16PA
RTSQ16PAY1
20PA
RTSQ8PAY1
RTSQ12PAY1
16
45.0
50.0 (1) / 45.0 (2)
14.9
13.0 (1) / 15.0 (2)
3.02
3.85 (1) / 3.00 (2)
34
200
400
520
20
56.0
63.0 (1) / 55.9 (2)
15.4
15.4 (1) / 18.7 (2)
3.64
4.09 (1) / 2.99 (2)
43
250
500
650
BTSQ20PY1
Nom.
Nom.
EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Sound pressure level
Cooling
Nom./Max.
Piping connections
Liquid
OD
Gas
OD
Oil equalizing
OD
Total piping length
System
Actual
Current - 50Hz
Maximum fuse amps (MFA)
HP
kW
kW
kW
kW
kW
kW
dBA
mm
mm
mm
m
A
63/65
12.7
15.9
28.6
19.1
500
25
35
40
50
(1) Heating: Indoor temp. 20CDB; outdoor temp. 7CDB,6CWB (2) Heating: Indoor temp. 20CDB; outdoor temp. -10CWB
Power supply
Current - 50Hz
Height/Width/Depth
Cooling
Nom.
Min.~Max.
Min.~Max.
GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Nom.
RTSQ
mm
kg
m/min
dBA
CDB
CWB
BTSQ20P
1,570/460/765
110
-
kg
TCOeq
Hz/V
A
8PA
10PA
1,680/930/765
205
12PA
200
14PA
16PA
1,680/1,240/765
338
344
233
239
10.9
22.8
11.7
24.4
257
185
-5~43
-25~15.5
R-410A
9.4
19.6
10.5
21.9
2,087.5
3~/50/380-415
20
25
35
40
91
Outdoor unit
NOTES
300 or more
(Pitch of foundation
bolt holes)
10 or more
10 or more
(Front)
500 or more
Function unit
500mm
<Suction side>
<Front>
1500mm
50~100mm
System
Outdoor unit
DWG. No.
Function unit
DWG. No.
RTSYQ10PA
RTSQ10PA
3D076289
BTSQ20P
3D060838
3D076286
RTSYQ14,16PA
RTSYQ14,16PA
500mm
<Suction side>
<Front>
300 or more
(Pitch of foundation bolt holes)
Outdoor unit
1500mm
NOTES
10 or more
(Front)
500 or more
Function unit
System
Outdoor unit
DWG. No.
Function unit
DWG. No.
RTSYQ14PA
RTSQ14PA
3D076291
BTSQ20P
3D060838
RTSYQ16PA
RTSQ16PA
3D076291
BTSQ20P
3D060838
10 or more
3D076287
92
Outdoor unit 2
20mm
For installation in rows
< Pattern 1 >
500 or more
<Front>
<Front>
10 or more
50 or more
300 or more
500 or more
<Front>
20 or more
10 or more
50 or more10 or more
500 or more
500 or more
<Front>
100 or more
<Suction side>
<Front>
<Front>
500
100orormore
more
50 or more
10
or more
System
Outdoor unit 1
RTSYQ20PA
50 or more
50 or more
500 or more
<Front>
400 or more
100 or more
RTSQ12PA
10 or more
50 or more
10 or more
300 or more
10 or
more
or more
10 or10
more
20 or more
Outdoor unit 2
10 or more
3D076290
<Front>
20 or moreRTSQ8PA
DWG. No.
Function unit
100 or more
3D076290
50 or more
<Front>
<Front>
50 or more
50 or more
10 or more
100 or more
500 or more
50 or more
10 or more
<Front>
100 or more
300 or more
500 or more
10 or more
50 or more
<Front>
20 or more
<Front>
100 or more
or more
500 600
or more
100 or more
100 or more
100 or more
10 or more
10 or more
50 or more
<Front>
10 or more
50 or more
10 or more
50 or more
50 or more
< Unit: mm >
20 or more
100 or more
500 or more
10 or more
<Front>
300 or more
100 or more
500 or more
<Front>
50 or more
10 or more
10 or more
<Front>
50 or more
50 or more
20 or more
100 or more
50 or more
50 or more
< Unit: mm >
300 or
more
50 or more
500 or more
<Front>
3D076288
10 or more
50 or more
100 or more
<Front>
10 or more
100 or more
For installation in rows
<Front>
100 or more
500 or more < Pattern 1 >
<Front>
50 or more
10 or more
100 or more
300 or
more
20 or more
200 or more
20 or more
No.
3D060838
20 or more
<Front>
200 or more
500 or more
50 or
more
10 DWG.
or more
BTSQ20P
10 or more
400 or more
300 or
more
50 or more
50 or
or more
20
more
DWG. No.
500 or more
200 or more
200 or more
<Front>
500 or more
<Front>
100 or more
20 or more
50 or
more
<Front>
10 or more
10 or more
600 or more
300 or more
RTSYQ-PA
RTSYQ-PA
1500mm
1500mm
50 or
more
20 or more
10 or more
100 or more
20 or more
300 or more
10 or more
600 or more
500mm
10 or
more
10 or more
10 or more
10 or more
(Front)
20 or more
20 or more
10 or more
10 or more
20 or more
50 or more
< Pattern 2 >
10 or more
100 or more
100 or more
10 or more
10 or more
300 or more
50 or more
400 or more
<Front>
<Front>
100 or more
500 or more
200 or more
50 or more
10 or more
50 or more
<Front>
500 or more
500mm
300 or more
< Pattern 1 >
20 or more
50~100mm
RTSYQ-PA
For single unit installation
Function unit
1500mm
RTSYQ-PA
10 or
more
Outdoor unit 1
10 or more
< Pattern 1 >
NOTES
(Pitch of foundation
bolt holes)
500mm
50 or more
100 or more
<Front>
200 or more
100 or more
10 or more
3D059348C
1.
2.
If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.
3.
When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough space for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take
account of the possibility of short circuits.)
4.
The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
5.
Installation of snowbreak hood (field supply; ask you dealer for details) is recommended in case there expected an effect from snow and space between outdoor unit and function unit is more
than 100 mm.
NOTES
1.
100 or more
50 or more
50 or more
500mm
50 or more
100 or more
<Front>
500 or more
1500mm
50 or more
NOTES
3D059348C
93
RTSYQ20PA
Indoor units
VRV type indoor units
Ventilation
Heat Reclaim ventilation (VAM/VKM)
Control systems
Benefits
For projects with standard cooling & heating
requirements
Fits any building as also indoor installation is
possible as a result of high external static pressure
of up to 78.4 Pa. Indoor installation leads to less
piping length, lower installation costs, increased
efficiency and better visual aesthetics
The ability to control each conditioned zone
300m
135m (155m)
40m (90m1)
30m
15m
95
RXYCQ-A
VRV Classic
Classic VRV configuration
For standard cooling & heating requirements
Connectable to all standard VRV indoor units, controls and
ventilation
Contains all standard VRV features
RXYCQ14-20A
Outdoor unit
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Nom.
Nom.
Cooling
Heating
Nom.
Nom.
EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
96
Actual
RXYCQ
HP
kW
kW
kW
kW
kW
kW
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
mm
mm
m
Hz/V
A
8A
8
20.0
22.4
6.60
5.80
3.03
3.86
10A
10
25.0
28.0
6.74
7.00
3.71
4.00
100
200
200
1,680x635x765
159
95
78
58
125
250
250
187
171
59
12A
12
30.0
33.6
8.77
8.62
3.42
3.90
150
300
360
1,680x930x765
240
185
81
61
6.2
12.9
7.7
16.1
8.4
17.5
15.9
9.52
19.1
22.2
14A
14
35.0
31.5
11.4
8.18
3.07
3.85
64
175
350
420
16A
16
40.0
44.8
12.9
11.8
3.10
3.80
200
400
480
196
64
-5~43
-20~15.5
R-410A
8.6
18
2,087.5
18A
18
45.0
50.4
15.0
13.8
3.00
3.65
225
450
540
1,680x1,240x765
316
233
86
65
11.3
23.6
11.5
24
12.7
25
250
500
600
324
239
88
66
11.7
24.4
15.9
28.6
300
3N~/50/380-415
16
20A
20
50.4
56.5
17.9
16.1
2.81
3.50
40
(knock-out hole)
(knock-out hole)
(knock-out hole)
No.
1
2
3
4
5
6
7
8
9
10
(knock-out hole)
Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)
NOTES
Remarks
9.5 Brazing connection
15.9 Brazing connection
Inside of switch box (M8)
62
45
27
50
27
1. Detail for front side and detail for bottom side indicate the dimensions
after fixing the attached piping.
3D080764
RXYCQ10-14A
RXYCQ10-14A
(Pitch of foundation
bolt holes)
(for 10HP)
(knock-out hole)
(knock-out hole)
(knock-out hole)
(knock-out hole)
No.
1
2
3
4
5
6
7
8
9
10
Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)
(knock-out hole)
Remarks
See note 2
See note 2
Inside of switch box (M8)
62
45
27
65.5
27
NOTES
1. Detail for front side and detail for bottom side indicate the dimensions after fixing the
attached piping.
2. Gas pipe:
19.1 Brazing connection: RXYCQ10
22.2 Brazing connection: RXYCQ12
28.6 Brazing connection: RXYCQ14
Liquid pipe:
9.5 Brazing connection: RXYCQ10, RXYCQ12
28.6 Brazing connection: RXYCQ14
3D080763
97
(knock-out hole)
Model.
RXYCQ16
RXYCQ18
RXYCQ20
(knock-out hole)
No.
1
2
3
4
5
6
7
8
9
10
AA
83
83
63
AB
179
179
160
(knock-out hole)
Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)
Remarks
See note 2
See note 2
Inside of switch box (M8)
62
45
27
65.5
27
NOTES
1. Detail for front side and detail for bottom side indicate the dimensions after fixing the
attached piping.
2. Gas pipe:
28.6 Brazing connection: RXYCQ16,18,20
Liquid pipe:
12.7 Brazing connection: RXYCQ20
9.5 Brazing connection: RXYCQ16,18
3D080767
RXYCQ-A
RXYCQ-A
For single unit installation
< Pattern 1 >
300 or more
10 or more
< Pattern 2 >
50 or more
300 or more
10 or more 10 or more
20 or more
50 or more 50 or more
300 or more
300 or more
20 or more
10 or more
300 or more
10 or more
20 or more
10 or more
10 or more
10 or more
20 or more
10 or more
20 or more
< Front >
10 or more
100 or more
100 or more
100 or more
300 or more
10 or more
20 or more
10 or more
50 or more
< Pattern 2 >
100 or more
100 or more
300 or more
400 or more
200 or more
400 or more
50 or more
100 or more
50 or more
50 or more
50 or more
100 or more
50 or more
50 or more
100 or more
100 or more
< Front >
50 or more
100 or more
50 or more
98
h1
500 mm
1500 mm
NOTES
h2
3D051451W
Replacement VRV
Quick & quality replacement for R-22
and R-407C systems
Air curtain
Biddle Air curtain for VRV (CYV)
Indoor units
VRV type indoor units
22
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
Control systems
VRV III
VRV IV
Heat pump
VRV configurator
DC fan motor
I demand function
99
Replacement
technology
The quick and quality way of
upgrading R-22 and R-407C systems
These benefits will convince your customer
Drastically improve your efficiency, comfort and reliability
Avoid loss of business
Up to 48%
less consumption
!
100
R-407C (RSXYP-L7)
R-410A (RXYQQ-T)
Conventional solution
VRV-Q
1
2
3
4
5
6
7
1 Recover refrigerant
2 Remove units
Recover refrigerant
Remove units
Remove refrigerant pipes
Install new piping and wiring
Install new units
Leak test
Vacuum drying
8 Refrigerant charging
9 Test operation
Easy as one-two-three
Up to 45% shorter
installation time
One touch
convenience:
Measure and charge
refrigerant
Automatic pipe
cleaning
Test operation
101
Replacement VRV
Cost effective and fast replacement as only the outdoor and
indoor unit needs to be replaced, meaning almost no work has to
be carried out inside the building
Efficiency gains of more than 70% can be realized, by virtue of
technological developments in heat pump technology and the
more efficient R-410A refrigerant
Less intrusive and time consuming installation compared
to installing a new system, as the refrigerant piping can be
maintained
Unique automatic refrigerant charge eliminates the need to
calculate refrigerant volume and allows safe replacement of
competitor replacement
Automatic cleaning of refrigerant piping ensures a clean piping
network, even when a compressor breakdown has occurred
Accurate temperature control, fresh air provision, air handling
units and Biddle air curtains all integrated in a single system
requiring only one single point of contact
Incorporates VRV IV standards & technologies: Variable Refrigerant
Temperature and full inverter compressors (for RXYQQ-T units)
Possibility to add indoor units and increase capacity without
changing the refrigerant piping
Possibility to spread the various stages of replacement thanks to
the modular design of the VRV system
Free combination of outdoor units to meet installation space or
efficiency requirements (for RXYQQ-T units)
Contains all standard VRV features
Outdoor system
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
RQCEQ
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Nom.
Nom.
Cooling
Heating
HP
kW
kW
kW
kW
kW
kW
Nom.
Nom.
EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Sound pressure level
Cooling
Nom.
Piping connections
Liquid
OD
Gas
OD
Discharge gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
Actual
dBA
mm
mm
mm
m
A
RQCEQ712-848P
280P3
360P3
460P3
500P3
540P3
636P3
712P3
744P3
816P3
848P3
RQEQ140P3 RQEQ180P3
RQEQ140P3
RQEQ180P3 RQEQ212P3
RQEQ140P3
RQEQ180P3 RQEQ212P3
RQEQ140P3 RQEQ180P3 RQEQ140P3
RQEQ180P3
RQEQ212P3
RQEQ180P3
RQEQ212P3
RQEQ180P3
RQEQ212P3 RQEQ180P3
RQEQ212P3
RQEQ212P3
10
13
16
18
20
22
24
26
28
30
28.0
36.0
45.0
50.0
54.0
63.6
71.2
74.4
81.6
84.8
32.0
40.0
52.0
56.0
60.0
67.2
78.4
80.8
87.2
89.6
7.04
10.3
12.2
13.9
15.5
21.9
21.2
23.3
27.1
29.2
8.00
10.7
13.4
14.7
16.1
17.7
20.7
21.2
23.1
23.6
3.98
3.48
3.77
3.61
3.48
2.90
3.36
3.19
3.01
2.90
4.00
3.72
3.89
3.80
3.72
3.79
3.80
3.81
3.77
3.79
21
28
34
39
43
47
52
56
60
64
140
180
230
250
270
318
356
372
408
424
280
360
500
540
636
712
744
816
848
364
468
598
650
702
827
926
967.0
1,061
1,102
57
61
62
63
64
63
64
65
66
9.52
12.7
15.9
19.1
22.2
25.4
28.6
34.9
19.1
22.2
25.4
28.6
300
30
40
50
60
70
80
90
Power supply
Current - 50Hz
102
Height/Width/Depth
Cooling
Nom.
Nom.
Nom.
Min.~Max.
Min.~Max.
GWP
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
RQEQ
mm
kg
m/min
dBA
dBA
CDB
CWB
140P3
kg
TCOeq
10.3
21.5
Hz/V
A
180P3
1,680/635/765
212P3
175
179
95
54
15
110
58
-5~43
-20~15.5
R-410A
10.6
22.1
2,087.5
3~/50/380-415
20
60
11.2
23.4
22.5
Replacement VRV
RXYQQ8-12T
Outdoor unit
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
RXYQQ-T
Outdoor unit module 1
Nom.
Nom.
Max.
Cooling
Heating
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Fan
Air flow rate
Cooling
Nom.
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Cooling
Min.~Max.
Heating
Min.~Max.
Refrigerant
Type
Charge
Piping connections
Power supply
Current - 50Hz
Outdoor unit
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
GWP
Liquid
OD
Gas
OD
Total piping length
System
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
HP
kW
kW
kW
kW
kW
kW
kW
kW
kW
mm
kg
m/min
dBA
dBA
CDB
CWB
kg
TCOeq
Actual
Nom.
Nom.
Max.
EER
ESEER - Automatic
ESEER - Standard
COP at nominal capacity
COP at maximum capacity
Maximum number of connectable indoor units
Indoor index
Min.
connection
Nom.
Max.
Piping connections
Liquid
OD
Gas
OD
Total piping length
System
Current - 50Hz
Maximum fuse amps (MFA)
8T
10T
12T
8
22.4
22.4
25.00
5.21
4.75
5.5
4.30
7.53
6.37
4.72
4.54
10
28.0
28.0
31.50
7.29
6.29
7.38
3.84
7.20
5.67
4.45
4.27
12
33.5
33.5
37.50
8.98
7.77
9.1
3.73
6.96
5.50
4.31
4.12
100
200
260
125
250
325
1,685x930x765
194
175
79
58
150
300
390
14T
14
40.0
40.00
45.00
11.0
9.52
11.2
3.64
6.83
5.31
4.20
4.02
64
175
350
455
185
223
6
12.5
6.3
13.2
187
162
78
11.1
23.2
5.9
12.3
15.9
9.52
19.1
16T
18T
20T
16
45.0
45.0
50.00
13.0
11.1
12.8
3.46
6.50
5.05
4.05
3.91
18
50.4
50.4
56.50
15.0
12.6
14.6
3.36
6.38
4.97
4.00
3.87
20
56.0
56.0
63.00
18.5
14.50
17.0
3.03
5.67
4.42
3.86
3.71
200
225
400
450
520
585
1,685x1,240x765
305
81
61
-5~43
-20~15.5
R-410A
250
500
650
314
260
251
64
65
261
88
66
10.4
21.7
11.7
24.4
11.8
24.6
86
10.3
21.5
2,087.5
mm
mm
m
Hz/V
A
RXYQQ-T
Nom.
Nom.
Max.
Cooling
Heating
RQYQ140P
RQYQ140P
5
14.0
16.0
3.36
3.91
4.17
4.09
10
62.5
125
162.5
1,680x635x765
175
95
54.0
kW
kW
Actual
mm
mm
m
A
3~/50/380-415
15
20
12.7
22.2
25
15.9
28.6
300
3N~/50/380-415
32
40
50
22T
24T
26T
28T
30T
32T
34T
36T
38T
40T
42T
RXYQQ10T RXYQQ8T
RXYQQ12T
RXYQQ16T
RXYQQ8T
RXYQQ10T
RXYQQ12T RXYQQ16T RXYQQ14T RXYQQ16T RXYQQ18T RXYQQ16T RXYQQ18T RXYQQ20T RXYQQ10T RXYQQ12T RXYQQ16T
RXYQQ20T RXYQQ18T RXYQQ16T
22
24
26
28
30
32
34
36
38
40
42
61.5
67.4
73.5
78.5
83.9
90.0
95.4
101.0
106.3
111.9
118.0
69.0
75.0
82.5
87.5
83.9
100.0
95.4
113.0
106.3
111.9
131.5
94.0
106.5
119.0
125.5
16.27
18.21
19.98
21.98
24.0
26.0
28.0
31.5
29.2
31.3
33.29
16.48
18.31
20.30
21.90
20.4
25.6
23.7
29.8
25.1
26.7
32.98
23.7
27.4
29.2
31.1
3.78
3.70
3.68
3.57
3.5
3.4
3.2
3.6
3.54
7.07
6.81
6.89
6.69
6.60
6.50
6.44
6.02
6.36
6.74
6.65
5.58
5.42
5.39
5.23
5.17
5.05
5.01
4.68
5.03
5.29
5.19
4.37
4.25
4.16
4.10
4.05
4.00
3.95
4.2
4.14
4.19
4.10
4.06
4.00
3.91
3.90
3.79
4.1
4.0
3.99
64
275
300
325
350
375
400
425
450
475
500
525
550
600
650
700
750
800
850
900
950
1,000
1,050
715
780
845
910
975
1,040
1,105
1,170
1,235
1,300
1,365
15.9
19.1
28.6
34.9
41.3
300
63
80
100
Contains fluorinated greenhouse gases | The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality | The AUTOMATIC ESEER value corresponds with normal VRV4
Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation) | Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor,
etc.) and the connection ratio restriction for the system (50% <= CR <= 130%)
103
Oblong holes
Outdoor unit 1
Outdoor unit 2
or more
(Front)
or more
Unit:mm
Model name
RQCEQ280P3
RQCEQ360P3
or more
or more
or more
or more
Outdoor unit 1
RQEQ140P3
RQEQ180P3
Drawing N.
3D066441A
3D066441A
Outdoor Unit 2
RQEQ140P3
RQEQ180P3
Drawing N.
3D066441A
3D066441A
NOTES
1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
3D066856A
104
Oblong holes
Oblong holes
(Foundation bolt hole)
Outdoor Unit 2
Outdoor Unit 3
Outdoor Unit 1
or more
or more
or more
or more
or more
or more
or more
or more
Unit:mm
Model name
RQCEQ460P3
RQCEQ500P3
RQCEQ540P3
RQCEQ636P3
Outdoor unit 1
RQEQ180P 3
RQEQ180P3
RQEQ180P3
RQEQ212P 3
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
Outdoor Unit 2
RQEQ140P3
RQEQ180P3
RQEQ180P3
RQEQ212P3
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
Outdoor unit 1
RQEQ140P3
RQEQ140P3
RQEQ180P3
RQEQ212P3
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
NOTES
1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
3D066860A
105
Oblong holes
(Foundation bolt hole)
Oblong holes
(Foundation bolt hole)
Oblong holes
Oblong holes
Outdoor Unit 1
Outdoor Unit 2
Outdoor Unit 3
Outdoor Unit 4
or more
or more
or more
or more
or more
or more
or more
or more
or more
or more
Unit: mm
Model name
RQCEQ712P3
RQCEQ744P3
RQCEQ816P3
RQCEQ848P3
Outdoor unit 1
RQEQ212P3
RQEQ212P3
RQEQ212P3
RQEQ212P3
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
Outdoor Unit 2
RQEQ180P3
RQEQ212P3
RQEQ212P3
RQEQ212P3
Drawing N.
3D0664413
3D0664413
3D0664413
3D0664413
Outdoor unit 3
RQEQ180PA
RQEQ180PA
RQEQ212PA
RQEQ212PA
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
Outdoor unit 4
RQEQ140P3
RQEQ140P3
RQEQ180P3
RQEQ212P3
Drawing N.
3D066441A
3D066441A
3D066441A
3D066441A
NOTES
1. Heights of walls
Front: 1500mm
Suction side: 500mm
Side: Height unrestricted
The installation space shown in this figure is based on the condition of cooling operation at the outdoor air temperature of 35C.
The installation space of suction side shown above must be expanded in the following case.
- Design outdoor temperature becomes over 35C.
- Operating over Max. operating load
(In case of causing a heavy heating load at indoor unit side)
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the following figure.
3. When installing the units the most appropriate pattern should be selected from those shown above in order to obtain the best fit in the space available always bearing in mind the need to leave
enough room for a parson to pass between nuits and wall for the air to circulate freely. (If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits.)
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
3D066865A
106
RQYQ140P
(knock-out hole)
(knock-out hole)
(knock-out hole)
(knock-out hole)
(knock-out hole)
No.
1
2
3
4
5
6
7
8
9
10
Parts name
Liquid pipe connection port
Gas pipe connection port
Grounding terminal
Power cord routing hole (side)
Power cord routing hole (front)
Power cord routing hole (front)
Power cord routing hole (bottom)
Wire routing hole (front)
Pipe routing hole (front)
Pipe routing hole (bottom)
Remarks
9.5 Brazing connection
See note 3.
Inside of switch box (M8)
62
45
27
50
27
See note 2.
See note 2.
3D066442
NOTES
For piping connection method (front and bottom sides) see the installation manual.
Gas pipe
15.9 Brazing connection: RQYQ140P
107
RXYQ8-12T
RXYQQ8-12T
Detailed technical
drawings
2
Detail A
729
Detail B
Detail A
4-15x22.5mmOblong hole
Foundation bolt hole
Detail B
107
107
112
112
134
353
134
125
125
4-15x22.5mmOblong hole
Foundation bolt hole
70
125
10
View C
10
View C
10
10
4-15x22.5mmOblong hole
Foundation bolt hole
11
107
70
112
729
4-15x22.5mmOblong hole
Foundation bolt hole
4-15x22.5mmOblong hole
353
134
70
66
729
729
Detail B
106
AC
353
125
70
Detail B
Detail A
160
66
106
106
107
AC
100
Detail A
AC
66
106
160
160
112
100
353
134
View C
11
View C
11
11
1685
AB
AA
AC
Detail B
729
339
66
100
66
106
AA
Detail A
339
AC
AA
AB
AA
339
AB
160
160
100
339
AB
AA
RYYQ8-12T
RYMQ8-12T
RXYQ8-12T
RXYQQ8-12T
AB
RXYQQ8-12T3
339
1 2
RYYQ8-12T
RYMQ8-12T
RYYQ8-12T
RYYQ8-12T
RXYQ8-12T
RYMQ8-12T
RYMQ8-12T
1
RXYQQ8-12T
RXYQ8-12T
RXYQ8-12T
RXYQQ8-12T
RXYQQ8-12T
100
11
1685
122
131
179
Model
RYYQ8T, RXYQ8T, RXYQQ8T
Model
76
76
5
97
272 107
97
179
259
276
131
179
259
276
122
179 131
DETAIL A
DETAIL B
Notes
107
259
76
DETAIL B
137
76
9
6
122
122
137
97
276
76
131
259
276
515
76
259 179
276
515
515
515
76
6
7
1075
97
137
765
515
76
1685
122
1685
1685
DETAIL B
DETAIL A
AA
248
AB
-
AC
-
RYYQ10-12T, RXYQ10-12T,
RXYQQ10-12T
195
RYYQ8T,
RXYQ8T,
RXYQQ8T
Model
AC
AA
AB
248
208
240
RXYQ10-12T,
RYYQ8T,RYMQ8T
RXYQ8T, RXYQQ8T RYYQ10-12T,248
- RXYQQ10-12T
195
208
240
REMQ5T,
RYMQ10-12T,
REYQ8-12T
RYYQ10-12T,
RXYQ10-12T,
RXYQQ10-12T
195
RYMQ8T
RYMQ8T
248
208 REYQ8-12T
240
REMQ5T, RYMQ10-12T,
5 REYQ8-12T
107REMQ5T, RYMQ10-12T,
240
195
208 Model
272
328
AA
248
195
248
195
131
765
137
DETAIL B
A
272
DETAILBAindicateDETAIL
272
373
328
the
dimensions after fixing the attached piping.
1. Detail A and detail
Notes
765
765
2. Items 4 - 10:
Knockout
hole.
328
328
373
NotesBNotes
930
indicate the dimensions after fixing the attached piping.
1. Detail A and detail
11 Grounding terminal
3. Gas pipe
2. RYYQ14-20T
Knockout hole.
Items 4 - 10:
373
373
76
A and detail
indicate
the dimensions
after fixingafter
the attached
piping.
76 the dimensions
1. Detail
A andBdetail
B indicate
fixing the
attached piping.
1. Detail
930
RYMQ14-20T
5 11 connection
RYYQ8T, RYMQ8T, RXYQ8T, RXYQQ8T 97
:
10 Pipe routing hole (bottom)
19.1 brazing
107
Inside of the switch box (M8)
2. Items
KnockoutKnockout
hole.
4 - 10: 4 - 10:
Grounding terminal
3. Gas pipe
2. Items
hole.
930
RXYQ14-20T
RYYQ10T,
RYMQ10T,
RXYQ10T,
RXYQQ10T
:
930
22.2 brazing
connection
9 Pipe routing hole (front)
137
1 : 2
RYYQ8T, RYMQ8T,
RXYQ8T,
Pipe routing
hole (bottom) Grounding terminal
pipe
Inside of the switch box (M8)
19.1 brazing connection
terminal
1110Grounding
3. Gas
Gas pipe RXYQQ8T
Inside of the switch box (M8)
DETAIL
B
11
3.
Pitch of foundation
bolt holes
RXYQQ14-20T
DETAIL: A
272
REMQ5T, REYQ8-12T
RYYQ10T, RYMQ10T,
RXYQ10T,
RXYQQ10T
:
25.4
brazing
connection
8 Power cord routing hole (bo
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
:
109 Pipe
routing
holehole
(bottom)
Pipe
routing
(front)
19.1
brazing
connection
: 22.2 brazing
connection
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
10
Pipe
routing
hole
(bottom)
19.1
brazing
connection
1076
765brazing
RYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :
RYYQ10T, RYMQ10T,
RXYQQ10T :
REMQ5T, REYQ8-12T
: RXYQ10T,
routing
hole
(front) hole (bottom)
22.2connection
brazing connection
9 8 Pipe
28.6 brazing
connection
25.4
65
7 Power cord routing hole (fro
Power
cord
routing
RYYQ10T, RYMQ10T,
RXYQ10T, RXYQQ10T
:
22.2 brazing connection
9 Pipe routing hole (front)
328
REMQ5T,
REYQ8-12T
Notes
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T ::
25.4
brazing
connection
65
Power
cord
routing
hole
(bottom)
8
28.6
brazing
connection
Liquid pipe
7 Power cord routing hole
27
REMQ5T,
REYQ8-12T
: :
6 Power cord routing hole (fro
25.4 brazing connection
65
Power cord routing hole (bottom)
8 (front)
RYYQ12T,
RYMQ12T,
RXYQ12T, RXYQQ12T
28.6
brazing
connection
7
27
cord routing hole (front)
Liquid pipe
RYYQ12T,
RXYQQ12T
3 fixing: the attached piping.
6 Power
RYYQ8-10T, RYMQ8-10T, RXYQ8-10T, RXYQ
65
373
Power
cord routing hole
(front)
5 Power cord routing hole (fro
28.6 brazing connection
A and
detail B RYMQ12T,
indicate theRXYQ12T,
dimensions
after
1. DetailLiquid
7
27
Power
cord
routing
hole
(front)
pipe
6 connection
65 80
cord routing hole (front)
9.5 brazing
RYYQ8-10T,
RYMQ8-10T,
RXYQ
Q8-10T, REMQ5T,
REYQ8-12T
5 Power
Power cord routing hole
RYYQ14-20T
2. Items
Knockout hole.
4 - 10:
LiquidRXYQ8-10T,
pipe
4 Power cord routing hole (sid
6 (front)
Power cord routing hole (front)
RYYQ8-10T,
RYMQ8-10T, RXYQ8-10T,
RXYQ
393 65
9.5 brazing connection
80
5 Power cord routing hole (front)
Q8-10T, REMQ5T,
REYQ8-12T
930
:
9.5 brazing connection
65
4 Power cord routing hole5 (side)
RYYQ8-10T,
RYMQ8-10T,
RXYQ8-10T,
RXYQ
Q8-10T,
REMQ5T,
REYQ8-12T
RYMQ14-20T
80
routing hole
(front)
12.7 brazing
connection
Inside of the switch box (M8)
Grounding
terminal
cord routing hole (side) Power
65
4 Power
11cord
:
3. Gas pipe
Equalising pipe connection
9.5 brazing connectionRYYQ12T, RYMQ12T, RXYQ12T, RXYQQ12T :
:
Q8-10T,
REMQ5T,
REYQ8-12T
3
12.7
brazing
connection
See
note
3.
134
Equalising pipe connection Power
port cord routing hole (side)
RYYQ12T, RYMQ12T,
RXYQ12T,
RXYQQ12T
:
65
RXYQ14-20T
12.7 brazing
See note 3.
High pressure/low pressure
Equalising pipe connection 4
port
RYYQ12T,
RYMQ12T,
RXYQ12T,
RXYQQ12T ::
RYYQ8T,
RYMQ8T,
RXYQ8T,
RXYQQ8T
10
Pipe routing hole (bottom)
19.1connection
brazing connection Equalising pipe
3
1
2
:
3
High pressure/low pressurepipe
gas pipe
1 RYYQ12T,
2
High pressure/low pressure gas Equalising
Pitch of8foundation bolt holes
Equalising RYYQ10T,
pipe Equalising
12.7 brazing connection
See note 3.
pipe routing
connection
port
RYMQ12T,
RXYQ12T,
RXYQQ12T
:
RYMQ10T,
RXYQ10T,
RXYQQ10T
:
pipe
hole
(front)
Pitch of foundation bolt holes
22.2
brazing connection RYMQ8-10T RXYQQ14-20T
9 Pipe
2 Gas pipe connection port
125
3
19.1 brazing
connection
:
2 Gas
Gas
pipe
connection
port
See note See
3. note 3.
2
High
pressure/low
pressure
gas
pipe
pipe
connection
port
1076
RYMQ8-10T
:
19.1
brazing
connection
19.1
brazing
connection
RYMQ8-10T
:
REMQ5T,Equalising
REYQ8-12T
:
pipe
1076
25.4 brazing connection RYMQ12T :
65
8 Power cord routing hole (bottom)
1 Liquid pipe connection port
Liquid
pipe
connection
1
See
note
3.
Liquid
pipe
connection
port2port
22.2
brazing
connection
1
See
note
3.
RYMQ12TRYYQ12T,
:
RYMQ12T
:
See note 3.
Gas pipe connection port
connection
RYMQ12T,: RXYQ12T, RXYQQ12T : 22.2 brazing
22.2
brazing
connection
RYMQ8-10T
19.1
brazing
connection
28.6
brazing
connection
No. Part name
7 Power cord routing holeRemark
27
(front) Remark
name
Part
name
No.
No.Part
High pressure/low pressure gas pipe
High
pressure/low
pressure gas pipe
1 Liquid pipe connection port
High pressure/low
pressure
gas pipe
See note 3.
22.2 brazing connection
Liquid pipeRYMQ12T : 3
6
65
19.13brazing connection
19.1
brazing connection
REMQ5T,: REYQ8-12T :
REMQ5T, REYQ8-12T :
19.1 brazing
connection
Remark
No. Part namePower cord routing hole (front)
REMQ5T,
REYQ8-12T
RYYQ14-20T
High pressure/low pressure gas pipe
71
160
100
106
70
106
160
AA
AA
Detail B
View C
134
125
393
134
107
125
View C
10
11
View C
View C
11
1685
Detail A
Remark
10
Detail B
Detail A
107
112
107
70
729
Detail B
2D079532B
See note 3.
70
71
100
10
2D079532B
2D079532B
See note 3.
393
112
Detail A
10
Part name
107
AA
4-15x22.5mm - Oblong hole
Foundation bolt hole
106
112
11
729
310
Detail B
192
AB
192
AB
AA
Detail A
160
See note 3.
125
71
100
106
160
393
70
71
80
65
134connection port
Equalising pipe
High pressure/low pressure gas pipe
2
1
No.
112
4-15x22.5mm
- Oblong hole
Pitch of foundation
bolt holes
1076 Foundation bolt hole
729
AB
Detail B
100
310
Detail A
310
192
AB
192
310
RXYQQ14-20T
Equalising pipe
160
RYYQ14-20T
RYMQ8-10T :
RYMQ14-20T
AA
RYMQ12T :
RXYQ14-20T
1
High
pressure/low
pressure
gas pipe 2
RXYQQ14-20T
REMQ5T, REYQ8-12T :
5
4
729
9.5
connection
brazing
19.1 brazing
connection
71
12.7 brazing connection
106
192
AB
310
REMQ5T, REYQ8-12T
REYQ8-12T :
RYMQ14-20T
Q8-10T, REMQ5T,
:
RXYQ14-20T
1 RXYQQ12T
2
RYYQ12T, RYMQ12T,
:
100 RXYQ12T,
RXYQQ14-20T
YYQ14-20T
YMQ14-20T
XYQ14-20T
XYQQ14-20T
4
11
11
122
1685
1685
RYMQ18-20T
3. Gas pipe
Equalising pipe :
REYQ14-20T
RYMQ14-16T
Equalising pipe
RYMQ14-16T
108
RYMQ18-20T
122
97
C5
DETAIL B
179
11 Grounding terminal
10 Pipe routing hole (bottom)
9 Pipe routing hole (front)
8 Power cord routing hole (bottom)
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
7 Power cord routing hole (front)
2. Items 4 - 10:
hole. 5
1240
97 107 Knockout
6 Power cord routing hole (front)
3. Gas pipe
5 Power cord routing hole (front)
272
DETAIL A
25.4 brazing connection
REYQ14-20T
:
4
Notes
272
328
373
1240
765
107
328
65
27
65
80
65
8
7
6
5
4
Remark
AB
205
210
AB
205
210
373
1240
11
Grou
2D079533B
10
See note 3.
3 connection port
See note 3.
2 Gas pipe
High pressure/low pressure gas pipe
11 Grounding terminal
portport
Seenote
note
1 Liquid2 pipe
Gasconnection
pipe connection
10
3. 3.
Pipe routing
holeconnection
(bottom) See
22.2
brazing
Remark
No. Part name
note 3.
1 Liquid pipe connection port
9 Pipe routing hole (front) See
AA
240
240
Model
RYMQ14-16T, RXYQQ14-16T,
RYMQ18-20T, RXYQQ18-20T
272
DETAIL A
AA
240
240
97
137
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T
76
76
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T
122
1240
107
131
179
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
15.9 brazing connection
RYYQ18-20T, RYMQ18-20T, RXYQ18-20T, RXYQQ18-20T
:
2. Items 4 - 10:
Knockout hole.
22.2 brazing connection
:
373
DETAIL A
Notes
Equalising pipe
25.4 brazing connection
:
indicate the dimensions
piping.
1. Detail A and detail B 76
22.2 brazing connection
RYMQ14-16T
: after fixing the attached 76
Items 4 - 10: RXYQQ14-20T
Knockout hole.
RYYQ14-20T, RYMQ14-20T,2.RXYQ14-20T,
:
28.6 brazing connection
RYMQ18-20T
:
28.6 brazing connection
Gas pipe
3.
137
Liquid pipe
DETAIL
25.4
brazing B
connection
REYQ14-20T
:
High pressure/low
pressure gas pipe
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :
12.7 brazing connection
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T,
RXYQQ14-20T
:
28.6
brazing
connection
REYQ14-20T
: 765
22.2
brazing
connection
15.9 brazing connection
RYYQ18-20T, RYMQ18-20T, RXYQ18-20T,
RXYQQ18-20T
:
Notes Liquid pipe
Equalising pipe
RYMQ14-16T
131
259
276
515
328
272
276
137
107
259
the dimensions
after fixing
the attached
piping.
1. Detail A and detail B indicate
RYYQ18-20T,
RYMQ18-20T,
RXYQ18-20T,
RXYQQ18-20T
765
2. Items 4 - 10:
Knockout hole.
3. Gas pipe
REYQ14-20T
97
131
515
Notes
179
328
276
272
7
373
122
131
107
259
DETAIL A
259
276
Notes
131
259
97
DETAIL B
1. Detail A and detail B indicate the dimensions after fixing the attached piping.
2. Items 4 - 10:
Knockout hole.
76
76 pipe
3. Gas
REYQ14-20T
:
137
DETAIL B :
RYYQ14-20T, RYMQ14-20T, RXYQ14-20T, RXYQQ14-20T
765
Liquid pipe
76
76
RYYQ14-16T, RYMQ14-16T, RXYQ14-16T, RXYQQ14-16T, REYQ14-20T :
515
137
765
1685
122
4
179
515
76
179
1685
276
515
4
76
Model
RYMQ14-16T, RXYQQ14-16T, REYQ14-20T
RYMQ18-20T, RXYQQ18-20T
65
27
65
80
65
2D079533B
2D079533B
9
8
7
6
5
4
3
Pipe
Pipe
Powe
Pow
Pow
Powe
Pow
Equa
High
2 Gas
1 Liqui
No. Part
(Pattern 1)
(Pattern 1)
(Pattern 1)
300 or more
300 or more
RQYQ140P
10 or
more
10 or
more
(FRONT)
500 or more
50 or
more 50 or more
(FRONT)
500 or more
(Pattern103)
or more
500
or more
300 or more
10 or more
20 or more
(FRONT)
500 or more(PATTERN 1)
(Pattern 2)
300 or more
100 or more
(Pattern 3)
Wall height
unrestricted
100 or more
(FRONT)
500 or more
10 or more
10 or more
(FRONT)
500 or more
10 or more
10 or more
300 or more
20 or more
10 or more 10 or more
100 or
more
900 or more
50 or more
(Front)
500
or more
50 or more
100 or
more
50 or
more 50 or more
100 or more
500
or more
100 or more
10 or more
50 or more
400 or more
(FRONT)
10 or more
20 or more
500 or more
(FRONT)(PATTERN 1)
600100
or more
or more
100 or more
(FRONT)
500 or more
20 or more
100 or more
500 or more
500
or more
(FRONT)
500 or more
100 or
more
10 or more
50 or more
50 or more
20 or more
10 or more
10 or more
50(Front)
or more
50 or more
100 or more
10 or more
or more
100 or20 more
(PATTERN 3)
100 or more
50 or more
(Front)
500 or more
100 or more
50 or more
50 or more
500 or more
500 or more
RYYQ-T
RYMQ-T (Front)
RXYQ-T 200 or more
RXYQQ-T
(Unit : mm)
100 or more
50 or more
(Front)
400 or more
50 or more
400 or more
100 or more
50 or more
100 or more
100 or more
50 or more
500 or more
(Front)
50 or more
(Front)
100 or more
50 or more
(Unit : mm)
500
or more
<Front>
400 or more
50 or more
600 or more
(Front)
200 or more
500 or more
<Unit = mm>
(Front)
50 or more
Wall height
unrestricted
300 or more
(Front)
10 or more
500
or (FRONT)
more
50 or more
(PATTERN 2)
100 or more
(Front)
50 or more
600 or more
100 or more
(PATTERN 2)
100 or more
900
or more
20 or more
10 or
or more
50
more 50 or more
(Front)
(PATTERN 3)
10 or more
20 or more
100 or more
300
(PATTERN 2)
50 or more
500 or more
(FRONT)
10 or more
10 or more
500
or more
(Front)
(Front)
10 or more
(Front)
100 or more
50 or more
(FRONT)
500 or more
300 or more
400 or more
200 or more
10 or more
300 or more
20 or more
10 or more
(PATTERN 2)
(FRONT)
200 or more
(PATTERN
1)
20 or more
300 or more
(Front)
(Front)
100 or more
10 or more
20 or more
50 or more
10 or more
Wall
height unrestricted
20
or more
20 or more
500 or more
20 or more
(PATTERN 2)
50 or more
10 or more
(PATTERN 1)
(Front)
10 or more
20 or more
(FRONT)
600 or more
100 or more
(PATTERN 1)
50 or more
10 or more 10 or more
500 or more
(FRONT)
(Pattern 2)
100 or more
For single unit installation
300
or more
20 or more
(FRONT)
500 or more
300 or more
<Suction side>
(Pattern 2)
20 or more
300 or more
50 or more
(Unit : mm)
3D066327
NOTES
(Pattern 1)
(Pattern 1)
(Pattern 1)
Heights of walls in case of patterns 1 and 2: Front: 1500mm. Suction side: 500 mm. Side: Height unrestricted. Installation space to be shown in this drawing
300
or
more
300 or outdoor
more
300 or more
is based on the cooling operation at 35 degrees
air temperature. When the design outdoor
air temperatur exceeds 35 degrees300oror the
more load exceeds
NOTES
maximum ability because of much generation load heat in all outdoor unit, take the suction side space more broadly than the space to be shown in this drawing.
500 or more
(FRONT)
of walls
in case
of patterns
1then
andh2/2
2: and h1/2 should be added to the front and suction side service spaces respectively as shown in the gure on
10 or
10 orare
2 1. 10Heights
Ifor more
the above
wall heights
exceeded
more
more
(FRONT)
20 or more
20 or more
10 or more 10 or more
20 or more
(FRONT)
10 or more
(FRONT)
20 or more
10 or more 10 or more
(FRONT)
Front:
1500mm
the right.
500 or more
500 or more
10 or more
500 or more
(Front)
20 or more
600 or more
10 or more
(Suction side)
10 or more
RQYQ140P
Suction
side: 500mm
900 or more
When installing
the units the most appropriate pattern should be selected from those shown above in order to obtain the best t in the space available always
Side:
Height
unrestricted
(Pattern
(Pattern
2) room for a person to pass between units and wall and for the air to circulate freely. (If more units are to be installed
bearing
in2)mind
the need to leave
enough
RYYQ-T
100 orfor
more
Installation
space
asin shown
on patterns
this drawing
is 100
based
on the
at 35 degrees
outdoor
air temperature.
or more
than are catered
the above
your layouts
should
takecooling
accountoperation
of the possibility
of
short circuits.)
300 or more
or more
20 or more
10 or more
(FRONT)
RYMQ-Tthe design outdoor air temperature exceeds 35 degrees or the load 10exceeds
10 or take
more the
20 suction
or more
500 orspace
more 10more
or more
of much
all outdoor
unit,
side
500 or more
10 or more load of heat
20 orinmore
10 or more
4 When
The units should be installed to leave sufcient space at the front for the on site refrigerant maximum
piping
workability
to be carried
outgeneration
comfortably.
(FRONT)
RXYQ-T
broadly than the space as shown on this drawing.
(Pattern 2)
50 or
RXYQQ-T
2. 50Iforthe
wall heights
and h1/2 should
to the front and suction side service spaces respectively as shown in the figure on the right.
more above(FRONT)
50 or exceeded
more
more are
100 orthen
more h2/2 (FRONT)
100 or morebe added
50 or more
500 or more
or more be selected from those shown above in order to obtain the best fit in the
3. When installing
the units most appropriate pattern500should
100 or
500 or more
(FRONT)
100 or
more and also for the air to circulate freely.
space (Pattern
available.
Always keep in(Pattern
mind 3)the need to leave enough space for amore
person to pass between units and wall
RXYQQ-T
3)
height
unrestricted
(If more units are to be installed than are catered for inWallthe
above
patterns50your
should take
account50
ofor the possibility
of short 100
circuits).
or morelayout(FRONT)
more 50 or more
50 or more
100 or more
or more
(FRONT)
Wall height
50 or more
500 or more
4. The
should
beunrestricted
installed to leave sufficient
spaceinatrows
the front for the on site For
refrigerant
piping
worklayout
to be carried out comfortably.
500 or more
50 or more
Forunits
single
For installation
centralized
group
100 or more
300 unit
or more installation
3
300 or more
10 or
more
10 or
more
(FRONT)
500 or more
20 or more
(FRONT)
500 or more
For single
(Patternunit
2) installation
(Pattern 2)
100 or more
50 or more
(FRONT)
500 or more
50 or
more 50 or more
10 or more
(Pattern 3)
300 or more
(FRONT)
200 or more
NOTES
10 or more 10 or more
Wall height
unrestricted
300 or more
(FRONT)
500 or3)
more
(Pattern
50 or more
100 or more
(FRONT)
50010orormore
more
20 or more
300 or more
400 or more50 or
(FRONT)
(FRONT)
200 or more more 50 or more
500 or more
(Pattern 3)
300 or more
(FRONT)
500 or more
20 or more
100
20 orormore
(FRONT)
500 or more more
50 or more
100 or more
400 or more
100 or more
(Pattern 3)
Wall height
unrestricted
20 or more
10 or more
10 or more
(Pattern 1)
(Pattern 2)
(Pattern 2)
100 or more
50 or more 50 or more
(FRONT)
500 or more
20 or more
50 or more
(FRONT)
500 or
or more
more
500
100 or more
(FRONT)
10 or more 10 or more
10 or more
10 or more
300 or more
20 or more
300 or more
10 or more 10 or more
(FRONT)
500 or more
10 or more
10 or more
50 or more
(FRONT)
500 or more
100 or more
100 or
20more
or more
50 or
more 50 or more
(FRONT)
500 or more
100
or more2)
(Pattern
50 or more
20 or more
100 or
more
50 or more
50 or more
10 or more
10 or more
(FRONT)
500 or more
100 or more
(FRONT)
500 or more
10 or more
10 or more
300 or more
20 or more
50 or more
50 or more
20 or more
300 or more
100 or more
50 or more 50 or more
(FRONT)
500 or more
100 or more
50 or
more 50 or more
10 or more
(FRONT)
500 or more
900 or more
10 or more
600 or more
20 or more
(FRONT)
100 or more
50 or more
500 or more
(FRONT)
500 or more
100 or more
(FRONT)
(FRONT)
500 or more
10 or more
20 or more
100 or more
10 or more
500 or more
500 or more
(FRONT)
10 or more 10 or more
100 or
more
100 or
more
50 or more
20 or more
(FRONT)
300 or more
(FRONT)
600 or more
100 or more
10 or more
(FRONT)
500 or more
10 or more
20 or more
900 or more
50 or more
(Pattern 2)
100 or more
10 or more
300 or more
10 or
more
(FRONT)
600 or more
100 or more
300 or more
<Unit = mm>
20 or more
100 or more
(Pattern 1)
600 or more
300 or more
<Suction side>
10 or more
400 or more
100 or
more
50 or more
50 or more
(Pattern(FRONT)
1)
50 or more
100 or more
500 or more
300 or more
<Front>
(Pattern 1)
(FRONT)
200300
or or
more
more
RYYQ-T
(Pattern 1)
RYMQ-T
400 or more
(FRONT)
200 or more
RXYQ-T
300 or more
RXYQQ-T
50 or more
500 or more
<Unit = mm>
50 or more
50 or more
100 or more
3D07954250 or more
<Suction side>
<Front>
<Front>
50 or more
<Suction side>
600 or more
1. Heights of walls in case of patterns 1 and 2:
100 or
more
Front: 1500mm
300 or more
50 or more
(FRONT)
50 or more
100 or more
400 or more
400 or more
(FRONT)
(FRONT)
500 or more
100 or more
50 or more
50 or more 50 or more
Suction side: 500mm
(FRONT)
100 or more
200 or more
200 or more
500 or more
Side: Height unrestricted
Installation space as shown on this drawing is based on the cooling operation at 35 degrees outdoor air temperature.
<Unit = mm>
When the design outdoor air temperature exceeds 35 degrees or the load exceeds maximum ability of much generation load of heat in all outdoor unit, take the suction side space more
broadly than the space as shown on this drawing.
2. If the above wall heights are exceeded then h2/2 and h1/2 should be added to the front and suction side service spaces respectively as shown in the figure on the right.
3. When installing the units most appropriate pattern should be selected from those shown above in order to obtain the best fit in the
space available. Always keep in mind the need to leave enough space for a person to pass between units and wall and also for the air to circulate freely.
(If more units are to be installed than are catered for in the above patterns your layout should take account of the possibility of short circuits).
4. The units should be installed to leave sufficient space at the front for the on site refrigerant piping work to be carried out comfortably.
NOTES
10 or more
109
Water cooled
VRV IV W-series
Ideal for high rise buildings,
using water as heat source
Unified
r
for hea ange
t pump
& heat
rec
and sta overy
n
& geoth dard
ermal
series
22
Air curtain
Biddle Air curtain for VRV (CYV)
Indoor units
VRV type indoor units OR
Residential type indoor units*
(such as Daikin Emura, ...)
Hot water
High temperature hydrobox*
Control systems
Ventilation
Heat Reclaim ventilation (VAM/VKM)
AHU connection kit
VRV IV standards:
Variable refrigerant temperature
Customize your VRV for best seasonal efficiency & comfort
Full inverter compressors
Reluctance brushless DC compressor
Sine wave DC inverter
Manual demand function
For more information on these features refer to the VRV IV technologies tab
* on request. Contact your local sales representative for more information
110
Geothermal operation
and advantages
Geothermal operation uses the more stable
temperature of the ground around the building,
eliminating the need for another heat source. It
reduces CO2 emissions and is an infinitely renewable
energy source.
-10C
45C
Heating
6C
45C
* Ethylene glycol should be added to the water when the water inlet
temperature is below 5C
Cooling
111
stage 2
stage 1
VRV-W
VRV-W
VRV-W
Indoor units
Heat absorbed from loop
mainly heating,
partly cooling
VRV-W
112
Ceiling height
3,200mm
or higher
Floor level
* for 8HP unit
100-300mm
Inverter Pump
Connections
PHE connections
Mesh size
Design Pressure
Design Temp.
Glycol resistance
Pressure drop
Specifications
G1
G1
Max. particle diam. 0,5mm
2.0MPa
Max. 80oC
Up to 40% ethylene glycol
See below graph
113
Single port
Unique to the market
Compact and light to install
No drain piping needed
Ideal for remote rooms
Technical cooling function
Connect up to 250 class unit (28 kW)
Allows multi-tenant applications
Multi port: 4 6 8 10 12 16
Up to 55% smaller and 41% lighter than
previous range
BS 4 Q14 A
BS 6, 8 Q14 A
BS 10, 12 Q14 A
BS 16 Q14 A
combining 2 ports
No limit on unused ports, permitting
phased installation
Allows multi-tenant applications
VRV-W
Level difference
between the VRV-W
120m (140m)
40m (90m1)
50m (40m)
300m
VRV-W
15m
Indoor installation
114
VRV-WIII geothermal system, Daikin Altherma HT, Sky Air, aircooled chiller with heat recovery, iManager,
iTouch Manager, i-Net
Application
examples
Dry cooler used for cooling, Chiller used for heating
Dry Cooler
Chiller
Expansion tank
Circulator Pump
Flow valve
or flow control valve
Stop valve
Strainer
Heat exchanger
Flow switch
Cooling mode
Heating mode
Refrigerant flow
116
Dry Cooler
Boiler
Expansion tank
Circulator Pump
Flow valve
or flow control valve
Stop valve
Strainer
Heat exchanger
Flow switch
Cooling mode
Heating mode
Refrigerant flow
117
Geothermal operation
Ground loop
Expansion tank
Circulator Pump
Heat exchanger
Buffer tank
Flow valve
or flow control valve
Liquid heater
Strainer
Cooling mode
Heating mode
Refrigerant flow
118
Flow switch
Stop valve
Three way valve
Ground loop
Examples
Open system
Conditions:
At 20 m depth water has a constant temperature
Uses water from a well or surface water (river, lake). The water is
pumped back to a second well or surface water
O
Water should be tested for acidity, mineral
content, organic content and corosiveness:
O
In many areas open systems are prohibited
due to environmental concerns
Closed system
Uses water pipes that are buried in the ground and exchange
heat with the ground
Vertical system conditions
Typical depth: 30-140 m. Below 15 m, the
temperature of the ground is constant around
10C
119
RWEYQ-T8
Launc
12HP u h of
n
exten it and
t
the ra ion of
nge u
p to
36HP
2nd ha
lf 2016
RWEYQ8-10T8
VRV-W
VRV-W
Indoor installation
Unlimited water piping length
Outdoor unit
System
Capacity range
Cooling capacity
Heating capacity
Power input - 50Hz
Power supply
Current - 50Hz
Water piping
Refrigerant piping
Standard operation
RWEYQ
Nom.
Nom.
EER
COP
Maximum number of connectable indoor units
Indoor index
Min.
Nom.
connection
Max.
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Sound power level
Cooling
Nom.
Sound pressure level
Cooling
Nom.
Operation range
Inlet water
Cooling
Min.~Max.
Heating
Min.~Max.
temperature
Refrigerant
Type
Charge
Piping connections
Geothermal operation
GWP
Liquid
Gas
Discharge gas
Water
OD
OD
OD
Inlet/Outlet
Actual
HP
kW
kW
kW
kW
kW
kW
mm
kg
dBA
dBA
CDB
CWB
kg
TCOeq
8T8
RWEYQ8T
8
22.4 (1) / 22.4 (2)
25.0 (3) / 25.0 (4)
4.42 (1) / 4.45 (2)
4.21 (3) / 4.30 (4)
5.07 (1) / 5.03 (2)
5.94 (3) / 5.81 (4)
10T8
RWEYQ10T
10
28.0 (1) / 27.5 (2)
31.5 (3) / 31.5 (4)
6.14 (1) / 6.35 (2)
6.00 (3) / 6.20 (4)
4.56 (1) / 4.33 (2)
5.25 (3) / 5.08 (4)
100
125
200
250
260
325
1,000x780x550
137
16T8
18T8
20T8
RWEYQ8T
RWEYQ10T
RWEYQ8T
RWEYQ10T
16
18
20
44.8 (1) / 44.8 (2) 50.4 (1) / 49.9 (2) 56.0 (1) / 55.0 (2)
50.0 (3) / 50.0 (4) 56.5 (3) / 56.5 (4) 63.0 (3)/ 63.0 (4)
8.8 (1) / 8.9 (2) 10.6 (1) / 10.8 (2) 12.3 (1) / 12.7 (2)
8.4 (3) / 8.6 (4) 10.2 (3) / 10.5 (4) 12.0 (3) / 12.4 (4)
5.07 (1) / 5.03 (2) 4.77 (1) / 4.62 (2) 4.56 (1) / 4.33 (2)
5.94 (3) / 5.81 (4) 5.53 (3) / 5.38 (4) 5.25 (3) / 5.08 (4)
36 (5)
200
225
250
400
450
500
520
585
650
24T8
26T8
RWEYQ8T
RWEYQ8T
RWEYQ8T
24
26
67.2 (1) / 67.2 (2) 72.8 (1) / 72.3 (2)
75.0 (3) / 75.0 (4) 81.5 (3) / 81.5 (4)
13.3 (1) / 13.4 (2) 15.0 (1) / 15.3 (2)
12.6 (3) / 12.9 (4) 14.4 (3) / 14.8 (4)
5.07 (1) / 5.03 (2) 4.86 (1) / 4.74 (2)
5.94 (3) / 5.81 (4) 5.65 (3) / 5.51 (4)
300
600
780
-
30T8
RWEYQ10T
RWEYQ10T
RWEYQ10T
28
30
78.4 (1) / 77.4 (2) 84.0 (1) / 82.5 (2)
88.0 (3) / 88.0 (4) 94.5 (3) / 94.5 (4)
16.7 (1) / 17.2 (2) 18.4 (1) / 19.1 (2)
16.2 (3) / 16.7 (4) 18.0 (3) / 18.6 (4)
4.69 (1) / 4.51 (2) 4.56 (1) / 4.33 (2)
5.43 (3) / 5.27 (4) 5.25 (3) / 5.08 (4)
325
650
845
28T8
350
700
910
375
750
975
50
51
53
54
55
10~45
-10 / 10.0~45
56
R-410A
3.5
7.3
4.2
8.8
mm
9.52
mm 19.10 (6)
22.2 (6)
mm 15.9 (7) / 19.10 (8) 19.1 (7) / 22.10 (8)
ISO 228 - G1 1/4 B External
Thread/ISO 228 - G1 1/4 B
External Thread
m
Hz/V
3N~/50/380-415
A
20
2,087.5
15.9
12.7
19.1
34.9 (6)
28.6 (7) / 34.90 (8)
28.6 (6)
22.2 (7) / 28.60 (8)
300
32
50
(1) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol) (2) Cooling: Indoor temp. 27CDB; 19CWB; inlet water temp.: 30C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol. (3) Heating: Indoor temp. 20CDB; inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 100% water (no glycol). (4) Heating: Indoor temp. 20CDB;
inlet water temp.: 20C; equivalent refrigerant piping: 7,5m; level difference: 0m. Rated values are with 30% glycol. (5) Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio
restriction for the system (50% <= CR <= 130%) (6) In case of heat pump system, gas pipe is not used (7) In case of heat recovery system (8) In case of heat pump system | Contains fluorinated greenhouse gases
120
Bottom view
Item
Rear view
Part name
Remark
Liquid pipe
See table 1
Suction pipe
See table 1
Gas pipe
See table 1
Water in connection
Drain outlet
Grounding terminal
M5
29
Cable inlet
29
RWEYQ-T8
NOTES
Manufacturer label
Table 1
Model
Operation system
Liquid pipe
Suction pipe
Gas pipe (high/low pressure)
Connection method
Liquid pipe
Suction pipe
Gas pipe (high/low pressure)
In case of a heat pump, the suction pipe is not used.
RWEYQ8
Heat pump
9.5
Heat recovery
9.5
19.1
15.9
19.1
Flare connection
Heat pump
9.5
RWEYQ10
22.2
Heat recovery
9.5
22.2
19.1
Brazed connetion
3D085178B
RWEYQ-T
Service space
(rear)
For installation
in a row
Secure 300mm or more of service space
even not using for rear side take-out
Service space
(rear)
Service space
(rear)
Outside unit
Outside unit
500 or more
500 or more
RWEYQ-T8
390 or more
Outside unit
Water piping
installation space
Secure enough
space for removing
front plate
350 or less
20 or more
Space for
installation in
a row
Front view
20 or more
Space for
installation in
a row
350 or more
20 or more
Space for
installation in
a row
Service space
(front)
300 or more
Service space
(front)
900 or more
H: free
W: 179 mm
250 or less
Service space
(front)
20 or more
Space for
installation in
a row
900 or more
20 or more
Space for
installation in
a row
100 or more
Water piping installation space
3D048341F
121
122
UNIQUE
UNIQUE
BPMKS
Accessory to connect stylish indoor units
191
SLIMMEST
IN CLASS
UNIQUE
DESIGN UNIT
UNIQUE
RADIATING PANEL
Wall mounted
FTXG-LS/LW192
CTXS-K / FTXS-K
196
Floor standing
FVXG-K200
FVXS-F203
Flexi type unit
FLXS-B(9) 205
UNIQUE
SLIMMEST
IN CLASS
123
Indoor Units
Indoor units
Products overview
Type Model
FXFQ-A
133
FXZQ-A
136
2-way blow
ceiling
mounted
cassette
FXCQ-A
139
Ceiling
mounted
corner
cassette
FXKQ-MA
142
Small
concealed
ceiling unit
FXDQ-M9
144
Slim
concealed
ceiling
unit
FXDQ-A
146
Concealed Slimmest yet most powerfull medium static pressure unit on the market!
ceiling
Slimmest unit in class, only 245mm
Low operating sound level
unit
Medium external static pressure up to 150Pa facilitates using flexible ducts of
with
varying lengths
medium
Automatic air flow adjustment function measures the air volume and static
ESP
pressure and adjusts it towards the nominal air flow, guaranteeing comfort
FXSQ-A
152
FXMQ-P7
162
FXMQ-MB
162
FXTQ-A
170
FXAQ-P
175
For wide rooms with no false ceilings nor free floor space
Ideal for comfortable air flow in wide rooms thanks to Coanda effect
Rooms with ceilings up to 3.8m can be heated or cooled very easily!
Can easily be installed in both new and refurbishment projects
Can even be mounted in corners or narrow spaces without any problem
Reduced energy consumption thanks to DC fan motor
FXHQ-A
178
FXUQ-A
181
FXLQ-P
183
FXNQ-A
188
UNIQUE
Round flow
cassette
Floor standing
UNIQUE
Fully flat
cassette
Ceiling
suspended
unit
Unique Daikin unit for high rooms with no false ceilings nor free floor space
Rooms with ceilings up to 3.5m can be heated up or cooled down very easily!
4-way blow Can easily be installed in both new and refurbishment projects
Can be partly recessed in the ceiling if a small ceiling void is available (88mm)
ceiling
suspended Flexibility to suit every room layout
Reduced energy consumption thanks to DC fan motor
unit
Concealed
floor
standing
unit
UNIQUE
Floor
standing
unit
1.7 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0
1.9 2.5 3.2 4.0 5.0 6.3 8.0 9.0 10.0 12.5 16.0 18.0 25.0 31.5
124
(1) Nominal cooling capacities are based on: indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDB, equivalent refrigerant piping: 5m, level difference: 0m
(2) Nominal heating capacities are based on: indoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB, equivalent refrigerant piping: 5m, level difference: 0m
overview
Depending on the application, Split and Sky Air
indoor units can be connected to our VRV IV
and VRV IV S-series outdoor units. Refer to the
outdoor unit portfolio for combination restrictions.
Fully flat
cassette
FFQ-C
FDBQ-B
FDXS-F(9)
FBQ-D
Daikin Emura
Wall mounted unit
FTXG-LW/LS
192
CTXS-K
FTXS-K
196
FTXS-G
196
FHQ-C
FVXG-K
200
FVXS-F
203
FLXS-B(9)
205
Model
Product name
PG
15
20
25
Ceiling
mounted
cassette
Concealed
ceiling
Wall
mounted
Ceiling
suspended
Floor
standing
42
50
60
71
2
3
35
For RXYS(C)Q units a mix of RA indoor units and VRV indoor units is not allowed
VRV IV W-series on special order. Consult your local sales representative for more information
125
Indoor Units
RWEYQ-T84
Type
RXYQ-T(9)
FCQG-F
RYYQ-T
RXYSCQ-TV1 /
RXYSQ-TV1 /
RXYSQ-TY13
VRV Indoor
126
Indoor Units
VRV Indoor
127
Indoor units
We care
Benefits overview
Inverter technology
Fan only
The air conditioner can be used as fan, blowing air without cooling or heating
Air treatment
Whisper quiet
When starting to warm up or when the thermostat is off, the air discharge direction is set horizontally and the fan to
low speed, to prevent draught. After warming up, air discharge and fan speed are set as desired
Daikin indoor units are whisper quiet. Also the outdoor units are guaranteed not to disturb the quiet of the
neightbourhood
Air filter
Humidity
control
Comfort
Draught prevention
The filter automatically cleans itself once a day. Simplicity of upkeep means optimum energy efficiency and maximum
comfort without the need for expensive or time-consuming maintenance
The presence sensor directs the air away from any person detected in the room. The floor sensor detects the average
floor temperature and ensures an even temperature distribution between ceiling and floor
Dry programme
Other funtcions
Air flow
128
The air discharge of the indoor unit is specially designed to prevent air being blown against the ceiling to prevent
ceiling stains
Possibility to select automatic vertical moving of the air discharge louvre, for uniform air flow and temperature
distribution
Individual flap control via the wired remote controller makes it simple to fix the position of each flap individually,
to suit any new room configuration. Optional closure kits are available as well
Weekly timer
Timer can be set to start and stop operation anytime on a daily or weekly basis
Infrared remote control with LCD to remotely control your indoor unit
Centralised control
Centralised control to to control several indoor units from one single point
Auto-restart
The unit restarts automatically at the original settings after power failure
Self-diagnosis
Multi tenant
The indoor units main power supply can be turned off when leaving the building or for servicing purposes
FXFQ-A
FXZQ-A
FXCQ-A
G1
F8
(optional)
G1
Wall
mounted
unit
FXKQ-MA FXDQ-M9
Ceiling suspended
units
FXDQ-A
FXSQ-A
FXMQ-P7
FXMQ-MB
FXTQ-A
FXAQ-P
FXHQ-A
FXUQ-A
FXNQ-A
FXLQ-P
Indoor Units
G1
G1
F8
(optional)
G1
F8
(optional)
G1
G1
G1
G1
3 (50~63)
2 (80~100)
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Optional
Optional
Standard
( )
( )
( )
( )
Standard (50~63)
Optional
Optional (80~100)
( )
129
ARGUE CARDS
FCQG-F/FCQHG-F/FXFQ-A
BYCQ140DW
BYCQ140D
Auto-cleaning auto-cleaning
panel
panel with
fine mesh
filter
BYCQ140DGF
White panel
Standard
panel
White with
grey louvers
Full white
White with
grey louvers
White with
grey louvers
References
Wolverhampton, UK
Running costs were reduced
by up to 50% compared
with standard solutions
thanks to daily filter cleaning.
Energy consumption
(kWh)
9000
8000
7000
6000
Standard round
flow cassette
Up to 50% savings
thanks to
auto-cleaning panel
5000
4000
3000
2000
1000
0
July
Aug.
Sept.
Oct.
Nov.
Cumulative energy comparison over 12 months
130
Dec.
Jan.
Feb.
March
April
May
June
July
Indoor Units
floor sensor
* available as an option
Flexible installation
Flaps can be individually controlled or closed
using the wired remote control, to suit room
configuration.
Optional closure kits are also available.
Marketing tools
Visit the website: www.daikineurope.com/minisite/
round-flow-cassette/
www.youtube.com/DaikinEurope
131
132
FXFQ-A
FXFQ20-63A
BRC1E52A/B
BRC7FA532F
Indoor Units
675mm
/////////////////////////
///////////////////
Main unit
Branch discharge
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Decoration panel
Main discharge
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 2
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 3
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 4
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
FXFQ
kW
kW
kW
kW
mm
mm
mm
kg
20A
2.2
2.5
25A
2.8
3.2
32A
3.6
4.0
0.038
0.038
19
mm
kg
mm
mm
Hz/V
A
63A
7.1
8.0
0.061
0.061
80A
9.0
10.0
0.092
0.092
100A
11.2
12.5
0.115
0.115
246
125A
14.0
16.0
0.186
0.186
288
840
840
mm
kg
dBA
dBA
dBA
50A
5.6
6.3
0.053
0.053
204
mm
kg
mm
kg
m/min
m/min
40A
4.5
5.0
12.5/10.6/8.8
12.5/10.6/8.8
49/31/29/28
31/29/28
20
21
24
26
Galvanised steel plate
BYCQ140D7GFW1 - auto cleaning panel with fine mesh filter
Pure White (RAL 9010)
130x950x950
10.3
BYCQ140D7GW1 - auto cleaning panel
Pure White (RAL 9010)
130x950x950
10.3
BYCQ140D7W1W - full white
Pure White (RAL 9010)
50x950x950
5.4
BYCQ140D7W1 - white with grey louvers
Pure white (RAL 9010)
50x950x950
5.4
13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9
13.6/11.6/9.5 15.0/12.8/10.5 16.5/13.5/10.5 22.8/17.6/12.4 26.5/19.5/12.4 33.0/26.5/19.9
Resin net with mold resistance
51/53/55/60/61/33/31/29
35/33/30
38/34/30
43/37/30
45/41/36
33/31/29
35/33/30
38/34/30
43/37/30
45/41/36
R-410A
2,087.5
6.35
9.52
12.7
15.9
VP25 (O.D. 32 / I.D. 25)
1~/50/60/220-240/220
16
BRC7FA532F
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
The BYCQ140D7W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140D7W1W decoration panel in environments exposed to concentrations of dirt. |
BYCQ140D7W1: pure white standard panel with grey louvers; BYCQ140D7W1W: pure white standard panel with white louvers; BYCQ140D7GFW1: pure white auto cleaning panel.
133
134
Indoor Units
135
ARGUE CARDS
FFQ-C /FXZQ-A
Marketing tools
Visit the website: www.daikineurope.com/fullyflat
Unique design
Differentiating in technology
Optional presence sensor
When the room is empty, it can adjust the set
temperature or switch off the unit saving energy.
When people are detected, the direction of
the airflow is adapted to avoid cold draughts being
directed towards occupants.
Optional floor sensor
Detects the temperature difference and
re-directs the airflow to ensure even
temperature distribution.
Top efficiency
When the room is empty, the sensor option can
adjust the set temperature or switch off the unit
saving up to 27% energy.
Individual flap control: easily control one or more
flaps via the wired remote controller (BRC1E52)
when rearranging the room. When fully closing or
blocking the flaps, the option Sealing member of
air discharge outlet is needed.
* for FFQ25,35C in combination with RXS25,35L3
136
www.youtube.com/
DaikinEurope
FXZQ-A
FXZQ-A
BRC1E52A/B
BRC7F530W/S
/////////////////////////
Indoor Units
Main discharge
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
Weight
Casing
Decoration panel
Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 2
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Decoration panel 3
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
(1) Dimensions do not include control box (2) Contains fluorinated greenhouse gases
FXZQ
kW
kW
kW
kW
mm
mm
mm
kg
mm
kg
mm
kg
mm
kg
m/min
m/min
dBA
dBA
dBA
mm
mm
Hz/V
A
15A
1.7
1.9
20A
2.2
2.5
0.043
0.036
25A
2.8
3.2
32A
3.6
4.0
0.045
0.038
40A
4.5
5.0
0.059
0.053
50A
5.6
6.3
0.092
0.086
260
575
575
15.5
16.5
Galvanised steel plate
BYFQ60CW
White (N9.5)
46x620x620
2.8
BYFQ60CS
White (N9.5) + Silver
46x620x620
2.8
BYFQ60B3W1
White (RAL9010)
55x700x700
2.7
8.5/7/6.5
8.7/7.5/6.5
9/8/6.5
10/8.5/7
11.5/9.5/8
8.5/7/6.5
8.7/7.5/6.5
9/8/6.5
10/8.5/7
11.5/9.5/8
Resin net with mold resistance
49/50/51/54/31.5/28/25.5
32/29.5/25.5
33/30/25.5
33.5/30/26
37/32/28
31.5/28/25.5
32/29.5/25.5
33/30/25.5
33.5/30/26
37/32/28
R-410A
2,087.5
6.35
12.7
VP20 (I.D. 20/O.D. 26)
1~/50/220-240
16
BRC7F530W (white panel) / BRC7F530S (grey panel) / BRC7EB530 (standard panel)
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
18.5
14.5/12.5/10
14.5/12.5/10
60/43/40/33
43/40/33
137
138
FXCQ-A
FXCQ20-40A
BRC1E52A/B
BRC7C52
/////////////////////////
Indoor Units
///////////////////
Main unit
Branch discharge
Main discharge
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Decoration panel
Nom.
Nom.
Cooling
Heating
Unit
Unit
Material
Model
Colour
Dimensions
Weight
Cooling
Nom.
Nom.
Height
Width
Depth
HeightxWidthxDepth
High/Nom./Low
Air filter
Type
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
FXCQ
kW
kW
kW
kW
mm
mm
mm
kg
20A
2.2
2.5
0.031
0.028
0.039
0.035
40A
4.5
5.0
0.041
0.037
50A
5.6
6.3
0.059
0.056
63A
7.1
8.0
0.063
0.060
80A
9.0
10.0
0.090
0.086
125A
14.0
16.0
0.149
0.146
305
990
1,445
620
19
10.5/9/7.5
dBA
dBA
32.0/30.0/28.0
32.0/30.0/28.0
Hz/V
A
32A
3.6
4.0
775
mm
kg
m/min
mm
mm
25A
2.8
3.2
22
25
33
38
Galvanised steel plate
BYBCQ40HW1
BYBCQ63HW1
BYBCQ125HW1
Fresh white (6.5Y 9.5/0.5)
55x1,070x700
55x1,285x700
55x1,740x700
10
11
13
11.5/9.5/8
12/10.5/8.5
15/13/10.5
16/14/11.5 26/22.5/18.5 32/27.5/22.5
Resin net with mold resistance
34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0
34.0/31.0/29.0 34.0/32.0/30.0 36.0/33.0/31.0 37.0/35.0/31.0 39.0/37.0/32.0 42.0/38.0/33.0 46.0/42.0/38.0
R-410A
2,087.5
6.35
9.52
12.7
15.9
VP25 (O.D. 32 / I.D. 25)
1~/50/220-240
16
BRC7C52
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
139
FXCQ50A
140
Indoor Units
FXCQ63A
FXCQ80-125A
141
FXKQ-MA
FXKQ-MA
Downward discharge
Frontal discharge
BRC1E52A/B
BRC4C61
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Decoration panel
Power supply
Current - 50Hz
Control systems
Nom.
Nom.
Cooling
Heating
Unit
Unit
Material
Model
Colour
Dimensions
HeightxWidthxDepth
Weight
Cooling
High/Low
Type
Cooling
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
142
Nom.
Nom.
Height
Width
Depth
FXKQ
kW
kW
kW
kW
mm
mm
mm
kg
mm
kg
m/min
dBA
mm
mm
Hz/V
A
25MA
2.8
3.2
32MA
3.6
4.0
40MA
4.5
5.0
0.076
0.056
0.066
0.046
63MA
7.10
8.00
0.105
0.085
215
1,110
1,310
710
31
Galvanised steel plate
BYK45FJW1
White
70x1,240x800
8.5
11/9
13/10
Resin net with mold resistance
38.0/33.0
40.0/34.0
R-410A
2,087.5
6.35
12.7
VP25 (O.D. 32 / I.D. 25)
1~/50/60/220-240/220
15
BRC4C61
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
34
BYK71FJW1
70x1,440x800
9.5
18/15
42.0/37.0
9.52
15.9
200 mm or more
200 mm or more
20 mm or more
Nr.
1
2
3
4
5
6
7
Suspension bolt
9
1,000 or more
Required installation space
10
Description
NOTES
Indoor Units
4-M4 hole
Name
3D038840
FXKQ63MA
FXKQ63MA
1,500 mm or
more
20 mm or more
Nr.
1
2
3
4
5
1,350 (Suspension position)
1,400 (Ceiling opening)
6
7
8
Suspension bolt
1,000 or more
(Required
installation space)
6-M4 hole
10
200 mm or more
Name
Description
NOTES
143
FXDQ-M9
For easy mounting, the drain pan can be located to the left or
right of the unit
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
144
FXDQ-M9
BRC1E52A/B
FXDQ
kW
kW
kW
kW
mm
mm
mm
mm
kg
20M9
2.2
2.5
m/min
m/min
6.7/5.2
6.7/5.2
dBA
dBA
dBA
mm
mm
Hz/V
A
BRC4C62
25M9
2.8
3.2
0.050
0.050
230
652
502
250
17
Unpainted
Galvanised steel
7.4/5.8
7.4/5.8
Part name
Liquid pipe connection ( 6.35)
Gas pipe connection ( 12.7)
Drain hole (o.d. 27.2 - i.d. 21.6)
Transmission wiring port
Power supply wiring port
Service space
Switch box
Nameplate
250 or more
(Suspension position)
Nr
1
2
3
4
5
6
7
8
Indoor Units
300 or more
3TW25774-1
145
FXDQ-A
FXDQ15-32A
BRC1E52A/B BRC4C65
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
146
FXDQ
kW
kW
kW
kW
mm
mm
mm
mm
kg
15A
1.7
1.9
20A
2.2
2.5
25A
2.8
3.2
32A
3.6
4.0
0.071
0.068
40A
4.5
5.0
0.078
0.075
50A
5.6
6.3
0.099
0.096
63A
7.1
8.0
0.110
0.107
200
750
950
1,150
26
29
620
240
22
Galvanised steel / Non painted
m/min
7.5/7.0/6.4
Pa
dBA
dBA
mm
mm
Hz/V
A
8.0/7.2/6.4
30/10
50
32/31/27
10.5/9.5/8.5
12.5/11.0/10.0
16.5/14.5/13.0
44/15
54
36/34/30
15.9
Indoor Units
FXDQ15-32A
FXDQ40-50A
147
FXDQ15A
3D081424A
148
Indoor Units
FXDQ20-25A
FXQQ32A
149
FXDQ50A
150
Indoor Units
FXDQ60A
151
FXSQ-A
//////////////////////////////////////////
//////////////////////////////////////////
152
BRC1E52A/B BRC4C65
FXSQ-A
Automatic Airflow
Adjustment function
Fan characteristic
curves
Why?
After installation the real ducting will frequently differ from the
initially calculated air flow resistance the real air flow may be
much lower or higher than nominal , leading to a lack of capacity or
uncomfortable air temperature
Duct resistance
curves
matic adjustment )
/min)
Indoor Units
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Fan-Air flow rate 50Hz
Nom.
Nom.
Cooling
Heating
Unit
Unit
Colour
Material
Cooling
Heating
High/Nom.
Nom.
Nom.
Height
Width
Depth
High/Nom./Low
High/Nom./Low
Fan-External static
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
FXSQ
kW
kW
kW
kW
mm
mm
mm
kg
15A
1.7
1.9
m/min 8.7/7.5/6.5
m/min 8.7/7.5/6.5
Pa
dBA
dBA 29.5/28/25
dBA 31.5/29/26
mm
mm
Hz/V
A
20A
2.2
2.5
0.041
0.038
25A
2.8
3.2
32A
3.6
4.0
0.045
0.042
40A
4.5
5.0
0.092
0.089
50A
5.6
6.3
63A
7.1
8.0
0.095
0.092
80A
9.0
10.0
0.121
0.118
100A
11.2
12.5
0.157
0.154
125A
14.0
16.0
0.214
0.211
140A
16.0
18.0
0.243
0.240
245
550
23.5
9/7.5/6.5
9/7.5/6.5
700
1,000
1,400
1,550
800
24
28.5
29
35.5
36.5
46
47
51
Not painted (galvanised)
Galvanised steel plate
9.5/8/7.0 15/12.5/11 15.2/12.5/11 21.0/18/15 23/19.5/16 32/27/23 36/31.5/26 39/34/28
9.5/8/7 15/12.5/11 15.2/12.5/11 21/18/15 23/19.5/16.0 32/27/23 36/31.5/26 39/34/28
150/30
54
30/28/25
32/29/26
150/40
150/50
153
FXSQ15-32A
Detailed technical drawings
FXSQ15-32A
69
KJ
800
301
KC
KH
KE
110
245
178
38
100
65
50
140
25
40
300 or more
Service space
550
342
210
Suspension bolt
2x65= 130
( Knockout hole.
109
O100
170
ARROW VIEW A
365
32
KF
179.2
50
500 or more
Service space
KD
504
145
150
145
95
KA
210
2x140= 280
126 P.C.D.
4-M4 (CLASS 2)
50
KK
Suspension position
KB
ARROW VIEW A
630
KG
Item
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
/
/
VP20 (OD 26, ID 20)
/
/
/
/
Notes
3D094888A
FXSQ40-50A
69
25
40
492
38
KJ
800
301
KC
KE
KH
110
178
245
140
100
65
50
210
700
Suspension bolt
2x65= 130
(Knockout hole.
109
O100
170
300 or more
Service space
FXSQ40-50A
ARROW VIEW A
3x140= 420
126 P.C.D.
515
4-M4 (CLASS 2)
32
KF
500 or more
Service space
179
50
50
KK
KD
654
4x145= 590
95
KA
210
KB
ARROW VIEW A
42
Item
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
155
130
130 120
KG
5-O4.7 HOLE
/
/
VP20 (OD 26, ID 20)
/
/
/
/
Notes
3D094919A
154
FXSQ63-80A
69
40
301
38
65
KE
KH
110
245
KC
KJ
178
100
50
140
800
300 or more
Service space
1000
792
210
Suspension bolt
2x65= 130
(Knockout hole.
109
O100
170
ARROW VIEW A
32
5x146= 730
126 P.C.D.
KF
500 or more
Service space
815
4 x M4 (CLASS 2)
179
50
50
KK
KD
954
6x145= 890
95
KA
210
11x65= 715
KB
42
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
135
125
100
KG
8-O4.7 HOLE
/
/
Indoor Units
Item
ARROW VIEW A
KG
/
/
/
/
Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3D094916A
FXSQ100-125A
FXSQ100-125A
65
100
KJ
800
301
KC
KE
KH
110
178
245
140
25
69
40
50
300 or more
Service space
1400
1192
210
Suspension bolt
2x65= 130
( Knockout hole.
109
O100
38
170
ARROW VIEW A
KK
32
7x156= 1092
KF
179
50
KD
500 or more
Service space
1215
50
126 P.C.D.
4 x M4 (CLASS 2)
1354
8X150= 1200
95
KA
KB
42
Item
150
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
150
KG
ARROW VIEW A
226
16x65= 1040
KG
10xO4.7 HOLE
/
/
VP20 (OD 26, ID 20)
/
/
/
/
Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3D094917A
155
1550
Suspension bolt
69
1342
40
25
KJ
800
301
KC
KE
KH
110
245
178
140
100
65
50
210
2x65= 130
(Knockout hole.
38
62
109
O100
170
300 or more
Service space
FXSQ140A
ARROW VIEW A
126 P.C.D.
32
179
1504
9x150= 1350
60
95
210
18x65= 1170
KD
50
Suspension position
1588
60
KF
500 or more
Service space
4 x M4 (CLASS 2)
50
KK
8x156= 1248
1365
KA
630 Suspension position
KB
42
Item
151
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
151
KG
KG
ARROW VIEW A
10xO4.7 HOLE
/
/
VP20 (OD 26, ID 20)
/
/
/
/
Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3D094928A
FXSQ15A
FXSQ15A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
*1
MTap*1
UpperlimitofESP
HTap*2
LTap*1
L T (*1)
L T*2 (*1)
UpperlimitofESP
MTap*2
LTap*2
50
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
100
*3
*2
LowerlimitofESP
HTap*3
UpperlimitofESP
MTap*3
LTap*3
*3
LowerlimitofESP
0
5,5
Mark
*1
*2
*3
6,5
MAX
STD
ESP[Pa]
150
100
50
7,5
Airflowrate[m/min]
8,5
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
0
5,5
9,5
6,5
7,5
Airflowrate[m/min]
8,5
9,5
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
7,5
Airflowrate[m/min] 8,5
9,5
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
156
1.
*1
LowerlimitofESP
Externalstaticpressure[Pa]
UpperlimitofESP
150
150
3D096999
FXSQ20-25A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
150
150
UpperlimitofESP
1.
*1
MTap*1
UpperlimitofESP
100
HTap*2
LTap*1
*2
MTap*2
UpperlimitofESP
*2
LowerlimitofESP
LTap*2
50
HTap*3
*3
UpperlimitofESP
MTap*3
LTap*3
100
5,5
MTap
*3
6,5
Mark
*1
*2
*3
ESP[Pa]
150
100
30
MAX
STD
7,5
8,5
HTap
50
LTap
LowerlimitofESP
5,5
9,5
6,5
7,5
8,5
9,5
Airflowrate[m/min]
Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
2.
LowerlimitofESP
Airflowraterange(H)
Indoor Units
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
*1
LowerlimitofESP
10
Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095680A
FXSQ32A
FXSQ32A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
150
150
*2
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
*1
LowerlimitofESP
HTap*2
LTap*1
UpperlimitofESP
MTap*2
LTap*2
*2
LowerlimitofESP
50
*3
HTap*3
UpperlimitofESP
LTap*3
MTap*3
6,5
Externalstaticpressure[Pa]
Mark
*1
*2
*3
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
MAX
STD
ESP[Pa]
150
100
30
7,5
100
HTap
MTap
LTap
50
2.
*3
LowerlimitofESP
LowerlimitofESP
0
5,5
1.
*1
MTap*1
UpperlimitofESP
100
UpperlimitofESP
8,5
9,5
10,5
5,5
Airflowrate[m/min]
6,5
7,5
8,5
9,5
10,5
Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)
10
11
Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095681A
157
FXSQ40A
200
200
Fancharacteristics (3)
Airflowautoadjustment
Fancharacteristics (1)
HTap*1
150
150
UpperlimitofESP
*1
1.
*1
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
LowerlimitofESP
MTap*1
UpperlimitofESP
100
HTap*2
LTap*1
*2
MTap*2
*2
UpperlimitofESP
LowerlimitofESP
LTap*2
50
HTap*3
*3
UpperlimitofESP
MTap*3
LTap*3
HTap
MTap
LTap
50
2.
*3
LowerlimitofESP
LowerlimitofESP
0
9
10
Mark
*1
*2
*3
Externalstaticpressure[Pa]
100
11
13
14
15
16
17
10
Airflowrate[m/min]
ESP[Pa]
150
100
30
MAX
STD
12
12
13
14
15
16
17
Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
11
Airflowraterange(H)
13
14
15
16
17
Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095682A
FXSQ50A
FXSQ50A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
150
150
UpperlimitofESP
1.
*1
*1
LowerlimitofESP
MTap*1
HTap*2
LTap*1
MTap*2
*2
UpperlimitofESP
*2
LowerlimitofESP
LTap*2
50
*3
UpperlimitofESP
HTap*3
MTap*3
LTap*3
*3
LowerlimitofESP
0
9
Mark
*1
*2
*3
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
UpperlimitofESP
100
10
MAX
STD
11
12
13
Airflowrate[m/min]
ESP[Pa]
150
100
30
14
15
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
16
17
10
11
12
13
Airflowrate[m/min]
14
15
16
17
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Airflowraterange(H)
13
14
15
16
17
Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
158
3D095688A
FXSQ63A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
UpperlimitofESP
150
150
1.
*1
LowerlimitofESP
*1
Externalstaticpressure[Pa]
HTap*2
LTap*1
L T
(*1)
*2
*2
MTap*2
UpperlimitofESP
50
LowerlimitofESP
LTap*2
*3
UpperlimitofESP
HTap*3
MTap*3
LTap*3
*3
LowerlimitofESP
0
12
Mark
*1
*2
*3
13
14
15
ESP[Pa]
150
100
30
MAX
STD
16
17
Airflowrate[m/min]
18
19
20
21
22
23
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
0
24
12
13
14
15
16
17
18
Airflowrate[m/min]
19
20
21
22
23
24
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Airflowraterange(H)
Indoor Units
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
MTap*1
UpperlimitofESP
100
18
19
20
Airflowrate[m/min]
21
22
23
24
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095690A
FXSQ80A
FXSQ80A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
150
150
MTap*1
Externalstaticpressure[Pa]
UpperlimitofESP
100
HTap*2
LTap*1
*2
*2
LowerlimitofESP
LTap*2
*3
UpperlimitofESP
HTap*3
MTap*3
LTap*3
LowerlimitofESP
0
13,5
Mark
*1
*2
*3
Externalstaticpressure[Pa]
MTap*2
UpperlimitofESP
50
14,5
MAX
STD
15,5
16,5
ESP[Pa]
150
100
40
17,5
18,5
1.
LowerlimitofESP
Externalstaticpressure[Pa]
*1
UpperlimitofESP
*1
19,5
Airflowrate[m/min]
20,5
21,5
22,5
23,5
24,5
*3
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
0
25,5
13,5
26,5
14,5
15,5
16,5
17,5
18,5
19,5
20,5
Airflowrate[m/min]
21,5
22,5
23,5
24,5
25,5
26,5
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
Airflowraterange(H)
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
19,5
20,5
21,5
22,5
Airflowrate[m/min]
23,5
24,5
25,5
26,5
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095692A
159
FXSQ100A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
*1
LowerlimitofESP
MTap*1
100
HTap*2
LTap*1
*2
MTap*2
UpperlimitofESP
*2
LowerlimitofESP
LTap*2
*3
50
UpperlimitofESP
HTap*3
MTap*3
LTap*3
*3
LowerlimitofESP
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5
19,5 20,5 21,5 22,5 23,5 24,5 25,5 26,5 27,5 28,5 29,5 30,5 31,5 32,5 33,5 34,5 35,5 36,5
Airflowrate[m/min]
Airflowrate[m/min]
Externalstaticpressure[Pa]
Mark
*1
*2
*3
MAX
STD
ESP[Pa]
150
100
40
1.
*1
Externalstaticpressure[Pa]
UpperlimitofESP
Externalstaticpressure[Pa]
UpperlimitofESP
150
150
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
Airflowraterange(H)
27
28
29
30
31
32
33
34
35
36
37
Airflowrate[m/min]
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D095696A
FXSQ125A
FXSQ125A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
UpperlimitofESP
150
150
*1
MTap*1
UpperlimitofESP
1.
*1
LTap*1
HTap*2
*2
MTap*2
UpperlimitofESP
*2
LTap*2
50
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
LowerlimitofESP
100
LowerlimitofESP
*3
UpperlimitofESP
HTap*3
MTap*3
LTap*3
*3
LowerlimitofESP
0
22
23
Mark
*1
*2
*3
24
MAX
STD
25
26
ESP[Pa]
150
100
50
27
28
29
30
31
Airflowrate[m/min]
32
33
34
35
36
37
38
39
40
100
HTap
MTap
LTap
50
2.
LowerlimitofESP
41
22
23
24
25
26
27
28
29
30
31
32
Airflowrate[m/min]
33
34
35
36
37
38
39
40
41
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
Externalstaticpressure[Pa]
Airflowraterange(H)
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
30,5
31,5
32,5
33,5
34,5
35,5
Airflowrate[m/min]
36,5
37,5
38,5
39,5
40,5
41,5
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
160
3D095697A
FXSQ140A
200
200
Fancharacteristics (1)
Fancharacteristics (3)
Airflowautoadjustment
HTap*1
150
150
MTap*1
*1
*1
LowerlimitofESP
Externalstaticpressure[Pa]
Externalstaticpressure[Pa]
UpperlimitofESP
100
HTap*2
LTap*1
MTap*2
*2
*2
LowerlimitofESP
UpperlimitofESP
50
LTap*2
*3
HTap*3
MTap*3
UpperlimitofESP
1.
UpperlimitofESP
*3
LTap*3
LowerlimitofESP
100
HTap
MTap
50
LTap
2.
LowerlimitofESP
0
25
Mark
*1
*2
*3
26
27
MAX
STD
28
ESP[Pa]
150
100
50
29
30
31
32
33
Airflowrate[m/min]
34
35
36
37
38
39
40
41
42
23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
Airflowrate[m/min]
1. UpperlimitofESPbyairflowautoadjustment
2. LowerlimitofESPbyairflowautoadjustment
Fancharacteristics (2)
Fieldsettingwithremotecontrol
Indoor Units
Externalstaticpressure[Pa]
Airflowraterange(H)
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
35
36
37
38
Airflowrate[m/min]
39
40
41
42
Notes
1. Thefancharacteristicsshownarein"fanonly"mode.
2. ESP:ExternalStaticPressure
3D096688A
161
FXMQ-P7/FXMQ-MB
FXMQ40P7
BRC1E52A/B BRC4C65
///////////////////////////////////////////////////////////////////////////////////////
162
FXMQ-P7/FXMQ-MB
Automatic Airflow
Adjustment function
Fan characteristic
curves
Why?
After installation the real ducting will frequently differ from the
initially calculated air flow resistance the real air flow may be
much lower or higher than nominal , leading to a lack of capacity or
uncomfortable air temperature
Duct resistance
curves
Indoor Units
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
FXMQ-P7/FXMQ-MB
kW
kW
kW
kW
mm
mm
mm
mm
kg
50P7
5.6
6.3
0.110
0.098
63P7
7.1
8.0
0.120
0.108
80P7
9.0
10.0
0.171
0.159
300
100P7
11.2
12.5
0.176
0.164
1,000
125P7
14.0
16.0
0.241
0.229
200MB
22.4
25.0
0.895
0.895
250MB
28.0
31.5
1.185
1.185
470
1,380
1,100
132
-
1,400
700
350
35
46
Unpainted
m/min
m/min
Pa
18/16.5/15
18/16.5/15
25/22.5/20
25/22.5/20
200/100
dBA
dBA
dBA
61/41/39/37
41/39/37
mm
mm
6.35
12.7
Hz/V
A
19.5/17.8/16
19.5/17.8/16
58/54.0/50
72/67.0/62
-/-/-
270/160
270/170
-/48/-/45
-/-/-
70/44/42/40
44/42/40
9.52
15.9
VP25 (I.D. 25/O.D. 32)
1~/50/60/220-240/220
19.1
22.2
PS1B
1~/50/220-240
16
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
163
DETAIL B
VIEW A-A
350 or more
(Service space)
Suspension bolt
500 or more
6 x M5 (On circumference)
DETAIL B
(Service space)
Item
1
2
3
4
5
6
7
8
9
10
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Remote control wiring connection
Power supply connection
Drain hole
Air filter
Air suction side
Air discharge side
Nameplate
Description
6.35 Flare connection
12.70 Flare connection
VP25 (0D 32, ID 25)
VP20 (0D 32, ID 25)
-
3TW32694-1
NOTES
Refer to outlook drawing for installing optional accessories when installing optional accessories.
The required ceiling depth varies according to the configuration of the specific system.
For maintenance of the air filter, it is necessary to provide a service access panel.
Refer to the filter installation method drawing.
FXMQ63-80P7
FXMQ63-80P7
(Knock out hole)
Fresh air intake position
350 or more
(Service space)
Suspension bolt
Detail B
500 or more
(Service space)
(On circumference)
Item Name
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Remote control wiring connection
5
Power supply connection
6
Drain hole
7
Air filter
8
Air suction side
9
Air discharge side
10 Nameplate
390 or more
(Service space)
(Ceiling opening)
Description
9.52 Flare connection
15.90 Flare connection
VP25 (OD 32, ID 25)
VP25 (OD 32, ID 25)
-
Detail B
(Ceiling opening)
NOTES
View A-A
3TW31234-1B
164
350 or more
(Service space)
Suspension bolt
Detail B
500 or more
(Service space)
(On circumference)
Item Name
1
Liquid pipe connection
2
Gas pipe connection
3
Drain pipe connection
4
Remote control wiring connection
5
Power supply connection
6
Drain hole
7
Air filter
8
Air suction side
9
Air discharge side
10 Nameplate
Detail B
Description
9.52 Flare connection
15.90 Flare connection
VP25 (OD 32, ID 25)
VP25 (OD 32, ID 25)
-
Indoor Units
View A-A
(Ceiling opening)
(Ceiling opening)
390 or more
(Service space)
NOTES
1.
2.
3.
4.
With decoration panel
3TW31254-1B
FXMQ-MB
165
H (max ESP)
Lower limit of ESP
(max ESP)
M (max ESP)
L (max ESP)
M (std ESP)
H (std ESP)
L (std ESP)
FXMQ50P7
M
L
Airflow [m3/min]
Airflow [m3/min]
Airflow [m3/min]
3TW32698-1
NOTES
1.
2.
FXMQ63P7
Fan characteristics (1)
H (max ESP)
Upper limit of ESP
(max ESP)
M (max ESP)
Lower limit of ESP
(max ESP)
L (max ESP)
H (std ESP)
M (std ESP)
Lower limit of ESP
(std ESP)
L (std ESP)
Airflow [m3/min]
FXMQ63P7
H
M
L
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
1.
2.
166
NOTES
3TW32708-1
H (max ESP)
Upper limit of ESP
(max ESP)
M (max ESP)
Lower limit of ESP
(max ESP)
L (max ESP)
H (std ESP)
M (std ESP)
Lower limit of ESP
(std ESP)
L (std ESP)
FXMQ80P7
H
M
L
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
Indoor Units
Airflow [m3/min]
1.
2.
3TW32718-1
NOTES
FXMQ100P7
Fan characteristics (1)
H (max ESP)
Upper limit of ESP
(max ESP)
M (max ESP)
L (max ESP)
Upper limit of ESP
(std ESP)
H (std ESP)
M (std ESP)
Lower limit of ESP
(std ESP)
L (std ESP)
Airflow [m3/min]
FXMQ100P7
L
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
1.
2.
3TW32728-1
NOTES
167
H (max ESP)
Upper limit of ESP
(max ESP)
M (max ESP)
L (max ESP)
H (std ESP)
M (std ESP)
Airflow [m3/min]
FXMQ125P7
L
Lower limit of ESP
Airflow [m3/min]
Airflow [m3/min]
1.
2.
NOTES
FXMQ200MB
168
3TW32738-1
Indoor Units
FXMQ250MB
169
FXTQ-A
FXTQ50A
BRC1E51A/B BRC4C65
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Fan-Air flow rate - 50Hz
Fan-External static pressure - 50Hz
Sound power level
Sound pressure level
Refrigerant
Piping connections
Power supply
Current - 50Hz
Control systems
Nom.
Nom.
Cooling
Heating
Unit
Nom.
Nom.
Height
Width
Depth
Unit
Material
Cooling
High/Low
High/Nom.
Cooling
Nom.
Cooling
High/Low
Type
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Simplified wired remote control for hotel applications
Wired remote control
170
FXTQ
kW
kW
kW
kW
mm
mm
mm
kg
50A
5.6
6.3
0.214
0.211
63A
7.1
8.0
0.243
0.240
80A
8.7
10.0
1.294
1.294
245
1,400
100A
11.2
12.5
1.465
1.465
470
1,380
1,100
137
1,550
800
47
51
36/26
150/50
39/28
140/50
39/33
42/34
58/50
221/132
72/62
270/191
48/45
R-410A
9.52
15.9
VP20
19.1
22.2
PS1B
1~/50/60/220-240/220
16
15
BRC4C65
BRC2E52C (heat recovery) / BRC3E52C (heat pump)
BRC1D52 / BRC1E52A/B
FXTQ50A
FXTQ50A
65
KC
KE
KH
110
245
800
301
KJ
178
100
50
140
25
69
40
300 or more
Service space
1400
1192
210
Suspension bolt
2x65= 130
( Knockout hole.
38
O100
109
170
ARROW VIEW A
KK
32
7x156= 1092
KF
179
50
50
126 P.C.D.
KD
500 or more
Service space
1215
4 x M4 (CLASS 2)
1354
8X150= 1200
95
KA
KB
630 Suspension position
KG
42
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
150
KG
ARROW VIEW A
10xO4.7 HOLE
/
/
Indoor Units
Item
150
226
16x65= 1040
/
/
/
/
Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3. Editable data for this drawing are available in the GDE (E-BOM) system.
3D098385
FXTQ63A
1550
Suspension bolt
40
50
25
KJ
800
301
KC
KE
KH
110
245
178
140
69
1342
210
100
65
2x65= 130
(Knockout hole.
38
62
109
O100
170
300 or more
Service space
FXTQ63A
ARROW VIEW A
8x156= 1248
1365
126 P.C.D.
32
500 or more
Service space
4 x M4 (CLASS 2)
1588
179
50
1504
9x150= 1350
Suspension position
18x65= 1170
KD
60
95
210
60
KF
50
KK
KA
630 Suspension position
KB
42
Item
151
Name
Description
KA
KB
KC
KD
Wiring connection
KE
KF
Drain outlet
KG
Air filter
KH
KJ
KK
Nameplate
151
KG
ARROW VIEW A
KG
10xO4.7 HOLE
/
/
VP20 (OD 26, ID 20)
/
/
/
/
Notes
1. When installing optional accessories, refer to their respective documentation.
2. The ceiling depth varies according to the documentation of the specific system.
3. Editable data for this drawing are available in the GDE (E-BOM) system.
3D098386
171
Gas side
Liquid side
FXTQ80A7VEB
9.5
FXTQ100A7VEB
9.5
1148
9
32 - O4.7
1380
1296
11 x 100 = 1100
11 x 100 = 1100
Name
Description
Flare connection
Brazed connection
Grounding terminal
Control box
5
6
Hook
10
Accessory pipe
11
Nameplate
12
Brazed connection
Internal pipe thread PS1B
Largest diameter 33, 349
Smallest diameter 30, 391
13
32 - O4.7
Water inlet
245
1100 Minimum
Service space
250
3 x 100 = 300
11 x 100 = 1100
1200
1230
13
11
30
6
VIEW A
32 - O7
30
1100
12
200
250
50
613
760
3 x 100 = 300
3 x 100 = 300
470
330
30
360
296
25
330
360
u 150
650 Minimum
Service space
Inspection hole
q600 Minimum
390
10
60
5 x 200 1000
1200
1230
16 - O8
3D098090
FXTQ50A
Applicable models
FXTQ50A
FXTQ50A2VEB
200
200
*1
Upper limit of ESP
M-Tap *1
*1
Lower limit of ESP
100
L-Tap *1
H-Tap *2
*2
Upper limit of ESP
M-Tap *2
*2
Lower limit of ESP
L-Tap *2
150
1.
H-Tap
100
M-Tap
2.
L-Tap
50
50
H-Tap *3
*3
Upper limit of ESP
M-Tap *3
L-Tap *3
*3
Lower limit of ESP
0
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
22
41
23
24
25
MAX
STD
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
26
ESP [Pa]
150
100
50
2.
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
30.5
31.5
32.5
33.5
34.5
35.5
36.5
37.5
38.5
39.5
40.5
41.5
Notes:
1. Fan characteristics as shown are in "fan only" mode.
2. ESP: External static pressure.
3. Editable data for this dwg. are available in GDE (e-bom) system.
172
3D098396
FXTQ63A
Applicable models
FXTQ63A
FXTQ63A2VEB
200
200
150
1.
M-Tap *1
*1
Lower limit of ESP
*1
Upper limit of ESP
H-Tap *2
100
L-Tap *1
M-Tap *2
*2
Lower limit of ESP
*2
Upper limit of ESP
L-Tap *2
*3
Upper limit of ESP
50
H-Tap
100
M-Tap
L-Tap
H-Tap *3
2.
50
M-Tap *3
*3
Lower limit of ESP
L-Tap *3
0
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
23
24
25
26
27
28
29
30
31
Mark
*1
*2
*3
MAX
STD
ESP [Pa]
150
100
50
32
33
34
35
36
37
38
39
40
41
42
43
44
45
1.
2.
150
140
130
120
110
100
90
80
70
60
Indoor Units
160
50
40
FXTQ80A
30
20
10
0
35
36
37
38
39
40
41
42
Notes:
1. Fan characteristics as shown are in "fan only" mode.
2. ESP: External static pressure.
3. Editable data for this dwg. are available in GDE (e-bom) system.
3D098397
FXTQ80A
FXTQ80A
300
High
High ESP
FXTQ80A
P
ES
of
it
im
rl P
pe ES
p
Low
h
U ig
H
High ESP
300
P
ES
of
it
il m
P
r
pe ES
Low
Up igh
H
High
SPESP
of
P
ES
300
High
High ESP
w E
Lo i g h
H
to
mi
r li SP
e
w E
Lo i g h
H
High
Standard ESP
fE
to P
i
m
r li d ES
e
p
r
Up nda
High
Sta
SP
Standard ESP
f E Low
it o
lim ESP
r
Standard
ESP
e rd
p
p
200
U nda
Sta
100
Low
Standard ESP
S
of E
mit
er li EPSP
LowndarfdES
Setralimit oSP
100
P
ES
of
it
lim P
r
pe ES
Low
Up igh
H
High ESP
SP
fE
to
mi
r li P
we ES
Lo i g h
H
SP
fE
200
200
t
High
mi
r li SP
High eESP
High
Standard ESP
SP
fE
it o
lim ESP
r
pe rd
Up nda
Sta
Low
Standard ESP
100
SP
of E
mit SP
er li
Lowndard E
Sta
Lowndard E
Sta
0
48
50
55
58
60
65
1.The remote controller can be used to switch between 'high' and 'low'.
48
48
5050
55
55 58
6058
60
65
Notes
Notes
1.The remote controller can be used to switch between 'high' and 'low'.
remote
can
be used Ittois switch
'high' and
'low'.ESP'
1.The
air flowcontroller
is factory-set
to 'standard'.
possiblebetween
to switch between
'standard
2.The
and 'high ESP' by remote controller setting.
2.The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP'
4D098100
173
FXTQ100A
FXTQ100A
FXTQ100A
High
High ESP
SP
fE
it o
im
rl P
pe S
Up igh E
H
Low
SP
f E High ESP
it o
im
rl P
pe E S
p
U igh
P
H f ES
Low
it o
lim SP High ESP
200
200
E
per
Up ndard
Sta
SP
fE
it o
r lim ESP
e
p
Up ndard
Sta
Low
Standard ESP
300
High
High ESP
to
mi
r li
we ESP
o
L gh
Hi
200
SP High
fE
o
it
Standard ESP
im
rl
we SP
L o gh E
Hi
High
Standard ESP
Low
Standard ESP
100
High
High ESP
SP
fE
300
SP
fE
it o
lim
r
we SP
L o gh E
Hi
High
Standard ESP
SP
fE
it o
lim SP
E
per
Up ndard
Sta
Low
Standard ESP
100
P
of ES
r limit
Lowe ard ESP
d
Stan
P
of ES
r limit
Lowe ard ESSPP
d
Stanlimit of E
100
SP
fE
it o
lim
r
P
pe S
Up igh E
H
Low
High ESP
r
Lowe ard ESP
d
Stan
0
60
62
65
70
72
75
80
00
60
60
1.The remote controller can be used to switch between 'high' and 'low'.
62
62
65 65
70
72
70
7275
75
Notes
Notes
1.The remote controller can be used to switch between 'high' and 'low'.
remote
can
be used Ittois switch
'high' and
'low'.ESP'
1.The
air flowcontroller
is factory-set
to 'standard'.
possiblebetween
to switch between
'standard
2.The
and 'high ESP' by remote controller setting.
2.The air flow is factory-set to 'standard'. It is possible to switch between 'standard ESP'
4D098101
4D098101
4D098101
174
FXAQ-P
FXAQ20-32P
BRC7EB518
Indoor Units
BRC1E52A/B
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Fan-Air flow rate 50Hz
Air filter
Sound power level
Sound pressure level
Refrigerant
Piping connections
Power supply
Current - 50Hz
Control systems
Nom.
Nom.
Cooling
Heating
Unit
Unit
Colour
Cooling
Nom.
Nom.
Height
Width
Depth
FXAQ
kW
kW
kW
kW
mm
mm
mm
kg
15P
1.7
1.9
0.017
0.025
20P
2.2
2.5
0.019
0.029
25P
2.8
3.2
0.028
0.034
32P
3.6
4.0
0.030
0.035
290
40P
4.5
5.0
0.020
0.020
795
50P
5.6
6.3
0.033
0.039
63P
7.1
8.0
0.050
0.060
1,050
238
11
14
White (3.0Y8.5/0.5)
High/Low
Type
Cooling
High/Nom.
Cooling
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
m/min
dBA
dBA
mm
mm
Hz/V
A
7.0/4.5
52.0/34.0/29.0
7.5/4.5
8/5
8.5/5.5
12/9
15/12
19/14
65.0/47.0/39.0
9.52
15.9
175
30 or more
(Required space)
Approx 400
Dimensions for
full open front panel
50 or more
(Required space)
90 or more
Piping direction
Piping direction
Piping direction
(Required space)
50 or more
(Required space)
Outside line
120 or less
2500 or more
For installation
in high spaces
Approx 475
Approx 460
(Filter part)
Approx 290
(Flexible tube part)
Filter part
80 hole
Approx 415
Mounting location
Nr
1
2
3
4
5
6
7
8
9
Name
Description
Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole
80 hole
Piping and
Wiring intake
3D065064A
NOTES
In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.
FXAQ40-50P
FXAQ40-50P
30 or more
(Required space)
Approx 400
(Required space)
90 or more
Piping direction
Dimensions for
full open front panel
Piping direction
Piping direction
(Required space)
Outside line
2500 or more
50 or more
For installation
(Required space) in high spaces
120 or less
Approx 475
Approx 460
(Filter part)
Filter part
80 hole
Approx 290
(Flexible tube part)
Approx 415
80 hole
Piping and
Wiring intake
Mounting location
Nr
1
2
3
4
5
6
7
8
9
176
Name
Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole
Description
3D065065A
NOTES
In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.
90 or more
(Required space)
Piping direction
30 or more
(Required space)
Approx 400
Dimensions for
full open
front panel
Piping direction
Piping direction
50 or more
50 or more
(Required space)
(Required space)
Outside line
2500 or more
For installation
in high spaces
120 or less
Approx 475
Approx 460
Filter part
Filter part
80 hole
Approx 415
Mounting location
Name
Front panel
Front grill
Air outlet
Gas pipe
Liquid pipe
Drain hose
Grounding terminal
Right side pipe connection hole
Left side pipe connection hole
Description
3D065066A
NOTES
In case of using infrared remote control, this position will be a signal receiver. Refer to the drawing of
infrared remote control in detail.
Indoor Units
Nr
1
2
3
4
5
6
7
8
9
80 hole
Piping and
Wiring intake
177
FXHQ-A
FXHQ63A
Air inlet
30 or more
(Service space)
////////////////////////////
Obstruction
////////////////////////////////////
Air outlet
BRC7G53
////////////////////////////////////////////
//////////////////////
//////////////////////
30 or more
(Service
space)
BRC1E52A/B
300
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Weight
Casing
Nom.
Nom.
Height
Width
Depth
Unit
Colour
Material
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound power level
Cooling
Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
(1) Contains fluorinated greenhouse gases
178
FXHQ
kW
kW
kW
kW
mm
mm
mm
kg
32A
3.6
4.0
0.107
0.107
m/min
m/min
14.0/12.0/10.0
14.0/12.0/10.0
dBA
dBA
dBA
36.0/34.0/31.0
36.0/34.0/31.0
mm
mm
6.35
12.7
Hz/V
A
960
24
63A
7.1
8.0
0.111
0.111
235
1,270
690
33
Fresh White
Resin
20.0/17.0/14.0
20.0/17.0/14.0
Resin net with mold resistance
37.0/35.0/34.0
37.0/35.0/34.0
R-410A
2,087.5
100A
11.2
12.5
0.237
0.237
1,590
39
29.5/24.0/19.0
29.5/24.0/19.0
44.0/37.0/34.0
44.0/37.0/34.0
9.52
15.9
VP20 (I.D. 20/O.D. 26)
1~/50/220-240
16
BRC7G53
BRC1E52A/B / BRC1D52
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
Indoor Units
FXHQ32A
FXHQ63A
179
3D069633D
180
FXUQ-A
4-way blow
ceiling suspended unit
Unique Daikin unit for high rooms with
no false ceilings nor free floor space
Even rooms with ceilings up to 3.5m can be heated up or cooled
down very easily without capacity loss
Can easily be installed in both new and refurbishment projects
Recessed installation possible in small ceiling voids (88 mm)
Individual flap control: flexibility to suit every room layout without
changing the location of the unit!
FXUQ-A
BRC1E52A/B
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Nom.
Nom.
Cooling
Heating
Unit
Weight
Casing
Nom.
Nom.
Height
Width
Depth
Unit
Colour
Material
Fan-Air flow rate Cooling
High/Nom./Low
50Hz
Heating
High/Nom./Low
Air filter
Type
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
FXUQ
kW
kW
kW
kW
mm
mm
mm
kg
BRC7C58
VP20
500
//////////////////////////////////////////////
71A
8.0
9.0
0.090
0.073
100A
11.2
12.5
0.200
0.179
198
950
950
26
27
Fresh White
Resin
m/min
m/min
22.5/19.5/16.0
22.5/19.5/16.0
dBA
dBA
40.0/38.0/36.0
40.0/38.0/36.0
31.0/26.0/21.0
31.0/26.0/21.0
Resin net with mold resistance
mm
mm
Hz/V
A
47.0/44.0/40.0
47.0/44.0/40.0
R-410A
2,087.5
9.52
15.9
I.D. 20/O.D. 26
1~/50/60/220-240/220-230
16
BRC7C58
BRC1E52A/B / BRC1D52
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
181
182
FXLQ-P
>20mm
1750mm
100mm
////////////////////////////////
Floor standing
///////////////////////////////////////////////////////////
///////////////////////////////////////////////////////////
>20mm
//////////////////
FXLQ20,25P
BRC1E52A/B BRC4C65
////////////////////////////////
Wall mounted
Indoor Units
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Fan-Air flow rate 50Hz
Air filter
Sound power level
Sound pressure level
Refrigerant
Piping connections
Power supply
Current - 50Hz
Control systems
Nom.
Nom.
Cooling
Heating
Unit
Unit
Colour
Cooling
Nom.
Nom.
Height
Width
Depth
High/Low
Type
Cooling
Nom.
Cooling
High/Low
Heating
High/Low
Type
GWP
Liquid
OD
Gas
OD
Drain
Phase/Frequency/Voltage
Maximum fuse amps (MFA)
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
FXLQ
kW
kW
kW
kW
mm
mm
mm
kg
m/min
dBA
dBA
dBA
20P
2.2
2.5
25P
2.8
3.2
0.049
0.049
32P
3.6
4.0
40P
4.5
5.0
50P
5.6
6.3
0.090
0.090
600
1,140
232
32
Fresh white (RAL9010) / Dark grey (RAL7011)
1,000
27
7/6
8/6
63P
7.1
8.000
0.110
0.110
1,420
38
11/8.5
14/11
16/12
38/33
38/33
39/34
39/34
40/35
40/35
Resin net
35/32
35/32
R-410A
2,087.5
mm
mm
Hz/V
A
6.35
12.7
O.D. 21 (Vinyl chloride)
1~/50/60/220-240/220
15
BRC4C65
BRC1D52 / BRC1E52A/B
BRC2E52C (heat recovery type) / BRC3E52C (heat pump type)
9.52
15.9
183
20 or more
100 or more
1750 or more
100 or more
Discharge
Suction
Front of face
1000 or more
Base
Item
1
2
3
4
5
Name
Liquid pipe connection
Gas pipe connection
Drain pipe connection
Switch box
Air f lter
Description
6.4 Flare connection
12.7 Flare connection
O.D.21
3TW32294-1
FXLQ32-40P
);/43
RUPRUH
RUPRUH
RUPRUH
RUPRUH
'LVFKDUJH
6XFWLRQ
)URQWRIIDFH
RUPRUH
%DVH
5HTXLUHGLQVWDOODWLRQVSDFH
3LSLQJKROHUHDU
[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ
/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\
[0
[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU
:LULQJKROHERWWRP
3LSLQJKROHERWWRP
,WHP
1DPH
/LTXLGSLSHFRQQHFWLRQ
*DVSLSHFRQQHFWLRQ
'UDLQSLSHFRQQHFWLRQ
6ZLWFKER[
$LUIOWHU
'HVFULSWLRQ
)ODUHFRQQHFWLRQ
)ODUHFRQQHFWLRQ
2'
7:
184
RUPRUH
RUPRUH
'LVFKDUJH
6XFWLRQ
)URQWRIIDFH
RUPRUH
%DVH
5HTXLUHGLQVWDOODWLRQVSDFH
3LSLQJKROHUHDU
0RGHO
);/
);/
/HYHODGMXVWLQJVFUHZLQVWDQGDUGDFFHVVRU\
[0
$
%
Indoor Units
[2EORQJKROH
+ROHIRUIHDUPRXQWLQJ
[2EORQJKROH
+ROHIRUI[LQJWRWKHIRRU
:LULQJKROHERWWRP
3LSLQJKROHERWWRP
,WHP
1DPH
/LTXLGSLSHFRQQHFWLRQ
*DVSLSHFRQQHFWLRQ
'UDLQSLSHFRQQHFWLRQ
6ZLWFKER[
$LUIOWHU
'HVFULSWLRQ
$)ODUHFRQQHFWLRQ
%)ODUHFRQQHFWLRQ
2'
7:
185
FXNQ-A
FXNQ-A
BRC1E52A/B
BRC4C65
Its low height (620 mm) enables the unit to fit perfectly beneath a
window
High ESP allows flexible installation
Indoor unit
Cooling capacity
Heating capacity
Power input - 50Hz
Dimensions
Weight
Casing
Fan-Air flow rate 50Hz
Nom.
Nom.
Cooling
Heating
Unit
Unit
Colour
Material
Cooling
Heating
High/Nom.
Nom.
Nom.
Height
Width
Depth
High/Nom./Low
High/Nom./Low
Fan-External static
pressure - 50Hz
Air filter
Type
Sound power level
Cooling
High/Nom.
Sound pressure level Cooling
High/Nom./Low
Heating
High/Nom./Low
Refrigerant
Type
GWP
Piping connections
Liquid
OD
Gas
OD
Drain
Power supply
Phase/Frequency/Voltage
Current - 50Hz
Maximum fuse amps (MFA)
Control systems
Infrared remote control
Wired remote control
Simplified wired remote control for hotel applications
186
FXNQ
kW
kW
kW
kW
mm
mm
mm
kg
m/min
m/min
Pa
dBA
dBA
dBA
mm
mm
Hz/V
A
20A
2.2
2.5
25A
2.8
3.2
0.071
0.068
32A
3.6
4.0
40A
4.5
5.0
0.078
0.075
50A
5.6
6.3
0.099
0.096
63A
7.1
8.00
0.110
0.107
950
1,150
27.5
32
200
23.5
8.0/7.2/6.4
8.0/7.2/6.4
41/10
Unpainted
Galvanised steel plate
10.5/9.5/8.5
10.5/9.5/8.5
42/10
52/15
12.5/11/10.0
12.5/11/10.0
16.5/14.5/13.0
16.5/14.5/13.0
59/15
55/15
54/35/33/32
35/33/32
9.52
15.9
300
ARROW VIEW B
170
156
80
4x150=600
ARROW VIEW A
200
620
680
662
14-M4
740
20 or more
Suspension position
100
16-O4.7 HOLE
5x100= 500
130
63
330
179.4
100
KD
KF
48
KK
300 or more
Service space
KJ
5x100= 500
790
50
10
42
50
240 or more
90
KH
8.4
ARROW VIEW
A
620
100 or more
500
KC
723
KA
Suspension position
KH
310
4-M8~M10
48
24
60
Suspension bolt
KB
57.5
20 or more
12.5
19.5
Inspection door
KJ
KE
46
16-O4.3 HOLE
601
171
ARROW VIEW B
Front suction
KG
180
116
100
4-O5 HOLE
5x100= 500
601
16-O4.3 HOLE
810
830
Item
Bottom suction
Description
KB
KC
KD
Drain hose
ID 25
KE
Control box
KF
Transmission line
KG
KH
Suspension bracket
KJ
Air filter
KK
Mounting foot
Indoor Units
Name
KA
Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.
3D096749A
FXNQ40-50A
FXNQ40-50A
990
300
ARROW VIEW B
880
620
862
4x150= 600
90
156
200
170
18-M4
12.5
20 or more
57.5
ARROW VIEW A
Inspection door
19.5
80
90
940
Suspension position
20 or more
8x100= 800
KD
63
310
723
KF
KJ
48
8.4
KK
300 or more
Service space
42
50
KJ
KE
7x100= 700
50
990
10
240 or more
90
130
KH
330
KH
100
179.4
100 or more
500
KC
620
KA
48
24
Suspension position
4-M8~M10
ARROW VIEW
A
100
22-O4.7 HOLE
60
Suspension bolt
KB
801
46
20-O4.3 HOLE
ARROW VIEW B
171
Front suction
7x100= 700
116
100
4-O5 HOLE
180
KG
801
1010
20-O4.3 HOLE
1030
Bottom suction
Item
Name
Description
KA
KB
KC
KD
Drain hose
ID 25
KE
Control box
KF
Transmission line
KG
KH
Suspension bracket
KJ
Air filter
KK
Mounting foot
Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.
3D096747
187
300
200
80
156
170
57.5
19.5
12.5
1080
1060
6x150= 900
620
1190
ARROW VIEW A
Inspection door
18-M4
20 or more
1140
Suspension position
20 or more
10x100= 1000
130
63
330
100
179.4
620
KF
KK
300 or more
Service space
1190
50
KJ
9x100= 900
1001
KE
46
24-O4.3 HOLE
171
10
42
50
240 or more
KH
KD
48
8.4
ARROW VIEW
A
723
100 or more
500
KC
Suspension position
KH
KA
48
90
310
4-M8~M10
100
24
26-O4.7 HOLE
60
Suspension bolt
KB
KJ
ARROW VIEW B
Front suction
KG
180
116
100
4-O5 HOLE
9x100= 900
1001
24-O4.3 HOLE
75
1210
1230
Item
Bottom suction
Name
Description
KA
KB
KC
KD
Drain hose
ID 25
KE
Control box
KF
Transmission line
KG
KH
Suspension bracket
KJ
Air filter
KK
Mounting foot
Notes
1. When installing optional accessories, refer to their respective documentation.
2.The ceiling depth varies according to the documentation of the specific system.
3D096740A
FXNQ20-25A
188
Indoor Units
FXNQ32A
FXNQ40A
189
FXNQ63A
190
FXSQ-A
VRV indoor unit
FXFQ-A
FVXG-K
Nexura
BPMKS967A2
FTXG-LW
Indoor Units
RYYQ-T
RXYQ-T(9)
Daikin Emura
BPMKS967A2
BPMKS967A2
FVXG-K - Nexura
RXYSQ-TV1
RXYSQ-TY1
* Special order unit, contact your local sales representative for more information
RWEYQ-T8*
BPMKS967A
Branch provider
To connect Split and Sky Air indoor units
to VRV outdoor units
Branch provider
BPMKS967B2
BPMKS967B2
mm
kg
BPMKS967B3
1~2
1~3
14.2
71+71
20.8
60+71+71
180x294x350
191
ARGUE CARDS
emura
Daikin Emura
Form. Function. Redesigned
192
Benefits
FTXG-LW/S
FTXG-LW
FTXG-LS
Indoor Units
ARC466A1
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
Unit
Type
Cooling
Heating
Cooling
Heating
Sound pressure level Cooling
HeightxWidthxDepth
High/Nom./Low/Silent
operation
m/min
High/Nom./Low/Silent
operation
m/min
Heating
Control systems
Power supply
FTXG
mm
kg
High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation
20LW
20LS
Hz / V
25LS
35LW
35LS
303x998x212
12
Removable / washable / mildew proof
8.9/6.6/4.4/2.6
40/34/28/19
50LW
50LS
10.9/7.8/4.8/2.9
10.9/8.9/6.8/3.6
12.4/9.6/6.9/4.1
12.6/10.5/8.1/5.0
54
56
59
59
60
60
38/32/25/19
45/34/26/20
46/40/35/25
45/37/29/20
47/41/35/25
10.2/8.4/6.3/3.8
dBA
dBA
dBA
dBA
25LW
11.0/8.6/6.3/3.8
41/34/28/19
ARC466A1
1~ / 50 / 220-240
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.
193
FTXG50LW/S
194
195
Indoor Units
C/FTXS-K
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
Unit
Type
Cooling
Heating
Cooling
Heating
Sound pressure level Cooling
HeightxWidthxDepth
Control systems
Power supply
CTXS15K
ARC466A6
CTXS35K
20K
289x780x215
8
High/Nom./Low/Silent
operation
m/min
7.9/6.3/
4.7/3.9
9.2/7.2/
5.2/3.9
8.8/6.7/
4.7/3.9
High/Nom./Low/Silent
operation
m/min
9.0/7.5/
6.0/4.3
55
10.1/8.1/
6.3/4.3
59
9.5/7.8/
6.0/4.3
Heating
FTXS
mm
kg
C/FTXS-K
High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation
dBA
dBA
dBA
dBA
42K
50K
298x900x215
11
Removable / washable / mildew proof
9.1/7.0/
11.2/8.5/
11.2/9.1/
11.9/9.6/
5.0/3.9
5.8/4.1
7.0/4.1
7.4/4.5
10.0/8.0/
6.0/4.3
58
58
35K
12.1/9.3/
6.5/4.2
12.4/10.0/
7.8/5.2
59
59
60G
71G
290x1,050x250
12
13.3/10.8/
8.4/5.5
16.0/16.0/
11.3/10.1
17.2/17.2/
11.5/10.5
17.2/14.9/
12.6/11.3
19.5/16.7/
14.2/12.6
63
62
60
60
46/40/34/23
59
45/41/36/33 46/42/37/34
Hz / V
25K
ARC466A6
ARC466A9
1~ / 50 / 220-240
ARC452A3
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.
196
CTXS15K / FTXS20-25K
Indoor air flow
30MIN
Rear side
780
Left side
Right side
50MIN
50MIN
Service space
217
215
Signal receiver
Operation lamp
Service space
Nameplate
Liquid pipe 6.4 CuT
The length of the pipe outside the unit is 400mm.
289
Timer lamp
Intelligent Eye lamp
Flap
Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.
780
16
Up/down (automatic)
6
172
47.3
15v
21.5
45v
59.5
Left/right (manual)
59
65 Hole
5v
v
45
45v
Indoor Units
45v
Fan
47.3
45v
189
106
5v
5v
Signal transmitter
58.5
549
Dry
Heating
289
Cooling
45v
Blade angle
3D092255
FTXS35-42K
FTXS35-42K
/ CTXS35K
30 MIN.
Rear side
900
Left side
Right side
50 MIN.
50 MIN.
Service space
Service space
217
215
Nameplate
Signal receiver
Operation lamp
298
Timer lamp
Intelligent Eye lamp
Flap
Auxiliary flap
Located inside of the unit
Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.
58.5
60v
10v
30v
60v
189
60v
60v
10v
21.5
10v
Fan
60v
65v
Left/right (automatic)
10v
45v
60v
191.5
10v
10v
48
Signal transmitter
900
633
298
10v
Dry
Heating
v
45
66
Hole for embedded piping
65 Hole
106
48
Cooling
14.5
Nameplate
65 Hole
Blade angle
3D092256
197
FTXS50K
Indoor air flow
30 MIN.
Rear side
900
Left side
Right side
50 MIN.
50 MIN.
Service space
Service space
217
215
Nameplate
Signal receiver
Operation lamp
298
Timer lamp
Intelligent Eye lamp
Flap
Auxiliary flap
Located inside of the unit
Drain hose
Connecting part
Inside diameter: 14mm
Outside diameter: 16mm
The length of the connection hose outside the unit is 450mm.
58.5
10v
30v
60v
189
60v
60v
10v
21.5
10v
Fan
60v
65v
Left/right (automatic)
10v
45v
60v
191.5
298
60v
900
633
10v
48
Signal transmitter
Dry
Heating
10v
v
45
66
Hole for embedded piping
65 Hole
106
48
Cooling
10v
14.5
Nameplate
65 Hole
Blade angle
3D092257
FTXS60G
198
Indoor Units
FTXS71G
199
Logo grijs
ARGUE CARDS
Pure comfort
and design
radiant
heat
Comfort is key
Nexura makes your world a comfortable one.
The coolness of a summer breeze or the cosiness of
an extra heat source brings a feeling of well-being
to your living space all year round. Its unobtrusive
yet stylish design with a front panel that radiates
additional heat, its low noise level and reduced air
flow turn your room into a haven.
Benefits
Vertical autoswing
Weekly timer
Guaranteed operation down to -25C (with
RXLG-M)
Online controller
200
FVXG-K + RXG-L
FVXG-K
Indoor Units
ARC466A2
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
Unit
Type
Cooling
Heating
Cooling
Heating
Sound pressure level Cooling
HeightxWidthxDepth
High/Nom./Low/Silent
operation
m/min
High/Nom./Low/Silent
operation
m/min
Heating
Control systems
Power supply
FVXG
mm
kg
High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation/Radiant heat
dBA
dBA
dBA
dBA
Hz / V
25K
35K
600x950x215
22
Removable / washable / mildew proof
50K
8.9/8.9/5.3/4.5
9.1/9.1/5.3/4.5
10.6/10.3/7.3/6.0
10.2/8.0/5.8/5.0
12.2/10.0/7.8/6.8
9.9/7.8/5.7/4.7
52
53
58
60
38/32/26/23
39/33/27/24
44/40/36/32
39/32/26/22/19
40/33/27/23/19
46/40/34/30/26
ARC466A2
1~ / 50 / 220-240
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.
201
FVXG50K
202
FVXS-F + RXS-L(3)
FVXS-F
Indoor Units
ARC452A1
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
Unit
Unit
Type
Cooling
Heating
Cooling
Heating
Sound pressure level Cooling
HeightxWidthxDepth
High/Nom./Low/Silent
operation
m/min
High/Nom./Low/Silent
operation
m/min
Heating
Control systems
Power supply
FVXS
mm
kg
High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation
dBA
dBA
dBA
dBA
Hz / V
25F
35F
600x700x210
14
Removable / washable / mildew proof
50F
8.2/8.2/4.8/4.1
8.5/8.5/4.9/4.5
10.7/10.7/7.8/6.6
8.8/6.9/5.0/4.4
9.4/7.3/5.2/4.7
11.8/10.1/8.5/7.1
52
52
60
60
38/32/26/23
39/33/27/24
44/40/36/32
38/32/26/23
39/33/27/24
45/40/36/32
ARC452A1
1~ / 50 / 220-240
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.
203
unit (mm)
Timer lamp
Signal receiver
Air outlet
selection
switch
(Inside)
95 (Half concealed)
Signal transmitter
Name plate
Drain
socket
85
Air flow
Required space
For performance
50 MIN
(for
maintenance)
(for
performance)
Up/down (automatic)
Cool, dry
Cooling
/ dry
Heat
(Heat pump model)
Right/left (manual)
Upper air outlet
(Wall hole)
(Wall hole)
50 MIN
VP20
I.D. J20
O.D. J26
L 220
3D056135A
FVXS50F
FVXS50F
unit (mm)
Timer lamp
Signal receiver
Air outlet
selection
switch
(Inside)
95 (Half concealed)
Signal transmitter
Name plate
Drain
socket
For performance
50 MIN
(for
performance)
Right/left (manual)
Upper air outlet
(Wall hole)
(Wall hole)
50 MIN
(for
maintenance)
Required space
Up/down (automatic)
Cooling / dry Cool, dry
Heat
(Heat pump model)
Upward air flow
limit (OFF)
204
VP20
I.D. J20
O.D. J26
L 220
85
Air flow
3D056136A
FLXS-B(9) + RXS-L(3)
FLXS-B(9)
Indoor Units
ARC433B67
Indoor unit
Dimensions
Weight
Air filter
Fan - Air flow rate
HeightxWidthxDepth
High/Nom./Low/Silent
operation
m/min
Heating
High/Nom./Low/Silent
operation
m/min
Cooling
Heating
Sound pressure level Cooling
Heating
25B
35B9
50B
60B
490x1,050x200
16
17
Removable / washable / mildew proof
Control systems
Power supply
FLXS
mm
kg
Unit
Unit
Type
Cooling
High/Nom./Low/Silent
operation
High/Nom./Low/Silent
operation
dBA
dBA
dBA
dBA
7.6/7.6/6.0/5.2
8.6/7.6/6.6/5.6
11.4/11.4/8.5/7.5
12.0/10.7/9.3/8.3
9.2/8.3/7.4/6.6
12.8/10.4/8.0/7.2
12.1/9.8/7.5/6.8
12.8/10.6/8.4/7.5
51
51
53
59
59
37/34/31/28
38/35/32/29
47/43/39/36
48/45/41/39
37/34/31/29
46/36/33/30
46/41/35/33
47/42/37/34
1~ / 50/60 / 220-240/220-230
1~ / 50 / 220-240
60
ARC433B67
Hz / V
1~ / 50/60 / 220-240/220-230
(1) EER/COP according to Eurovent 2012, for use outside EU only (2) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical
data drawing.
205
FLXS50-60B
206
Indoor Units
FLXS25-35B(9)
FLXS50-60B
207
Hot water
Efficient hot water production for underfloor
heating, radiators and air handling units, or
for producing hot water for sinks, baths and
showers. Integrating heat recovery into the
VRV system means that the production of hot
water is virtually free.
208
Hot water
Low temperature hydrobox
HXY-A8210
High temperature hydrobox
HXHD-A8212
215
Hot Water
Hydrobox range
Capacity class (kW)
Type
Product name
Model
HXY-A8
Ideal for hot or cold water in underfloor loops, air handling units, low temperature
radiators
Hot/cold water from 5 to 45C
Large operation range (down to -20C and up to 43C)
Fully integrated water-side components save time on system design
Space saving contemporary wall hung design
HXHD-A8
Ideal for sanitary hot water (e.g. bathrooms, sinks) and space heating (e.g. underfloor
heating, radiators, air handling units)
Hot water from 25 to 80C
"Free" heating and hot water through heat recovery
Uses heat pump technology to produce hot water efficiently, providing up to 17%
savings compared to a gas boiler
Possibility to connect thermal solar collectors
80
125
Leaving water
temperature range
5 C - 45 C
25 C - 80 C
Low
temperature
hydrobox
High
temperature
hydrobox
209
HXY-A8
Liquid pipe
Gas pipe
F1, F2 communication
Hot/cold water
Indoor unit
Cooling capacity
Heating capacity
Dimensions
Weight
Casing
Operation range
Nom.
Nom.
Unit
Unit
Colour
Material
Heating
Domestic hot
water
Refrigerant
Refrigerant circuit
Water circuit
Power supply
Current
Ambient
Water side
Ambient
Water side
Type / GWP
Gas side diameter
Liquid side diameter
Piping connections diameter
Phase/Frequency/Voltage
Recommended fuses
210
HeightxWidthxDepth
Min.~Max.
Min.~Max.
Min.~Max.
Min.~Max.
HXY
kW
kW
mm
kg
C
C
CDB
C
mm
mm
inch
Hz/V
A
080A8
8.0
9.00
125A8
12.5
14.00
890x480x344
44
White
Precoated sheet metal
-20~24
25~45
N/A
N/A
R-410A / 2.087,5
15.9
9.5
G 11/4 (female)
1~/50/220-240
6~16
HXY-A8
Service door
3D079938
90
85
80
HXY-A8 75
70
ESP (kPa)
HXY-A8
65
95
60
90
55
85
50
80
45
75
40
ESP (kPa)
70
35
65
30
60
25
55
15
17.5
20
22.5
25
27.5
30
32.5
35
37.5
40
30
32.5
35
37.5
40
Flow (l/min)
50
45
40
35
30
25
15
17.5
20
22.5
25
27.5
Flow (l/min)
3D097625
211
Hot Water
Switchbox terminals
95
HXHD-A8
HXHD-A8
EKHWP-B
EKHWP-B
45C - 75C
Daikin
solar panel
25C - 75C
VRV indoor units
BS-Box
Domestic hot
water tank
45C - 75C
BS-Box
Heating only
hydrobox for VRV
45C - 75C
Daikin
solar panel
25C - 75C
Air handling unit
Domestic hot
water tank
45C - 75C
Liquid pipe
Gas pipe
Discharge gas pipe
F1, F2 communication
Hot water
Indoor unit
Heating capacity
Dimensions
Weight
Casing
Nom.
Unit
Unit
Colour
Material
Sound pressure level Nom.
Night quiet mode
Operation range
Heating
Domestic hot
water
Refrigerant
Refrigerant circuit
Water circuit
Power supply
Current
HeightxWidthxDepth
Level 1
Ambient
Water side
Ambient
Water side
Type / GWP
Gas side diameter
Liquid side diameter
Piping connections diameter
Heating water system
Water volume
Phase/Frequency/Voltage
Recommended fuses
Min.~Max.
Min.~Max.
Min.~Max.
Min.~Max.
Max.~Min.
HXHD
kW
mm
kg
dBA
dBA
C
C
CDB
C
mm
mm
inch
l
Hz/V
A
(1) Sound levels are measured at: EW 55C; LW 65C (2) Sound levels are measured at: EW 70C; LW 80C (3) Field setting (4) Contains fluorinated greenhouse gases
212
125A8
14.0
705x600x695
92
Metallic grey
Precoated sheet metal
42 (1) / 43 (2)
38 (1)
-20~20 / 24 (3)
25~80
-20~43
45~75
R-134a / 1.430
12.7
9.52
G 1 (female)
200~20
1~/50/220-240
20
Detail A
Scale 1/3
Left Installation
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Right installation
3TW59914-1B(1)
HXHD-A8
HXHD-A
Left Installation
Upwiring
Right installation
Model
HXHD-A8
A
355
B
270
C
300
Min. 600
(Space required for switch box removal)
3TW59914-1B(2)
213
Hot Water
Detail A
ESP [kPa]
HXHD-A8
120
110
100
90
80
70
60
50
40
30
20
10
0
5
11
13
15
17
19
21 23 25
Flow [l/min]
27
29
31
33
35
37
39
41
3D097621
214
EKHTS-AC
Dimensions
Weight
Tank
Heat exchanger
EKHTS
Colour
Material
Unit
EKHTS260AC
200AC
260AC
Metallic grey
Galvanised steel (precoated sheet metal)
Height
Integrated on
indoor unit
mm
Width
Depth
Empty
Unit
Water volume
Material
Maximum water temperature
Insulation
Heat loss
Quantity
Tube material
Face area
Internal coil volume
2,010
mm
mm
kg
l
2,285
600
695
70
200
78
260
Stainless steel (EN 1.4521)
75
C
kWh/24h
1.2
1.5
1
Duplex steel (EN 1.4162)
1.56
7.5
m
l
Hot Water
Accessory
Casing
EKHTS200AC
EKHWP-B/PB
EKHWP300B-PB
Pressured
Accessory
Dimensions
Weight
Tank
Heat exchanger
Unit
Width
Depth
Empty
Unit
Water volume
Maximum water temperature
Insulation
Heat loss
Domestic hot
Tube material
water
Face area
Internal coil volume
Operating pressure
Average specifc thermal output
Charging
Tube material
Face area
Internal coil volume
Operating pressure
Average specifc thermal output
Auxiliary solar
Tube material
heating
Face area
Internal coil volume
Operating pressure
Average specifc thermal output
EKHWP
mm
mm
kg
l
C
kWh/24h
m
l
bar
W/K
m
l
bar
W/K
m
l
bar
W/K
300PB
595
615
58
294
Unpressured
500PB
790
790
89
477
300B
595
615
59
300
500B
790
790
93
500
85
1.5
1.7
Stainless steel (DIN 1.4404)
5.600
5.800
27.1
29.0
6
2,790
2,825
Stainless steel (DIN 1.4404)
3
4
13
19
3
1,300
1,800
Stainless steel (DIN 1.4404)
1
2
280
1.3
1.4
Stainless steel
5.8
27.9
6
29
6
2,790
2,900
Stainless steel
2.7
13.2
3.8
18.5
3
1,300
1,800
Stainless steel
3
-
0.5
2.3
280
215
EKSRPS4A
Pump station
Save energy and reduce CO2 emissions with a solar system for
domestic hot water production
Pump station connectable to unpressurised solar system
Pump station and control provide the transfer of solar heat to the
domestic hot water tank
EKSRPS4
HeightxWidthxDepth
EKSRPS4A
815x142x230
6
1~
50
230
mm
kg
Hz
V
EKS(V/H)-P
Solar collector
Thermal solar collector for hot water production
Solar collectors can produce up to 70% of the energy needed for
hot water production - a major cost saving
Vertical and horizontal solar collectors for domestic hot water
production
High efficiency collectors transfer all the short-wave solar radiation
into heat as a result of their highly selective coating
Easy to install on roof tiles
EKSV21P
EKSH26P
Solar collector
Mounting
Dimensions
Weight
Volume
Surface
Coating
Absorber
Glazing
Allowed roof angle
Operating pressure
Stand still temperature
Thermal performance
216
EKSV21P
Unit
Unit
HeightxWidthxDepth
Outer
Aperture
Absorber
Min.~Max.
Max.
Max.
collector efficiency (col)
Zero loss collector efficiency 0
Heat loss coefficient a1
Temperature dependence of the heat loss coefficient a2
Thermal capacity
mm
kg
l
m
m
m
bar
C
%
%
W/m.K
W/m.K
kJ/K
EKSV26P
EKSH26P
Horizontal
2,000x85x1,300
Vertical
1,006x85x2,000
33
1.3
2.01
1.800
1.79
42
1.7
2.1
2.60
2.360
2.35
Micro-therm (absorption max. 96%, Emission ca. 5% +/-2%)
Harp-shaped copper pipe register with laser-welded highly selective coated aluminium plate
Single pane safety glass, transmission +/- 92%
15~80
6
192
61
0.781
0.784
4.240
4.250
0.006
0.007
4.9
6.5
217
Hot Water
218
2.5
2.4
2.15
2.75
2.0
2.3
2.5
Favourable
Normal
Unfavourable
Location at a corner or
or open stairwell
3.0
2.3
Portfolio
Type
Product name
CYV S/M/L-DK-F
CYV S/M/L-DK-C
CYV S/M/L-DK-R
CYVS/M/L-DK-F/C/R
total cost
(installation + running cost) in
8000
Daikin heat pump
with Biddle air curtain*
6000
4000
2000
0
1
years
VRV
Network Solution
Biddle comfort
air curtain (CY)
Integration in a VRV total solution
* Payback period and gains calculated based upon the following: Air curtain is 9hrs/day 156 days year (1,404 hrs/year) in use. Annual energy consumption for an electric air
curtain: 3,137EUR (COP = 0.95). Typical installation cost: 1,000EUR; Typical equipment cost: 2,793EUR. Annual energy consumption for CYQS200DK100FBN and ERQ100AV: 748EUR
(COP 4.00). Typical installation cost: 2,000EUR; Typical equipment cost: 5,150EUR. Calculation based upon electricity cost: 0,1705EUR /kWh
220
CYVM150DK80CSN
CYVM150DK80RSN
Small
Heating capacity
Power input
Delta T
Casing
Dimensions
Speed 3
Fan only
Heating
Speed 3
Colour
Unit
Nom.
Nom.
Height F/C/R
Width F/C/R
Depth F/C/R
kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m/h
dBA
mm
V
Medium
CYVS100DK80
*BN/*SN
CYVS150DK80
*BN/*SN
CYVS200DK100
*BN/*SN
7.40
0.23
0.23
19
9.0
0.35
0.35
11.6
0.46
0.46
CYVS250DK140
*BN/*SN
CYVM100DK80
*BN/*SN
CYVM150DK80
*BN/*SN
CYVM200DK100
*BN/*SN
CYVM250DK140
*BN/*SN
16.2
9.2
11.0
13.4
19.9
0.58
0.37
0.56
0.75
0.94
0.58
0.37
0.56
0.75
0.94
15
16
17
14
13
15
BN: RAL9010 / SN: RAL9006
270/270/270
1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548 1,000/1,000/1,048 1,500/1,500/1,548 2,000/2,000/2,048 2,500/2,500/2,548
590/821/561
420
2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.3 (1) / 2.15 (2) / 2.0 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3) 2.5 (1) / 2.4 (2) / 2.3 (3)
1.0
1.5
2.0
2.5
1.0
1.5
2.0
2.5
56
66
83
107
57
73
94
108
1,164
1,746
2,328
2,910
1,605
2,408
3,210
4,013
47
49
50
51
50
51
53
54
R-410A / 2.087,5
9.52/16.0
9.52/19.0
9.52/16.0
9.52/19.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230
Large
Heating capacity
Power input
Delta T
Casing
Dimensions
Speed 3
Fan only
Heating
Speed 3
Colour
Unit
Nom.
Nom.
Height F/C/R
Width F/C/R
Depth F/C/R
kW
kW
kW
K
mm
mm
mm
mm
m
m
kg
m/h
dBA
mm
V
CYVL200DK250*BN/*SN
CYVL250DK250*BN/*SN
29.4
31.1
1.50
1.88
1.50
1.88
15
14
12
BN: RAL9010 / SN: RAL9006
370/370/370
1,000/1,000/1,048
1,500/1,500/1,548
2,000/2,000/2,048
2,500/2,500/2,548
774/1,105/745
520
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
3.0 (1) / 2.75 (2) / 2.5 (3)
1.0
1.5
2.0
2.5
76
100
126
157
3,100
4,650
6,200
7,750
53
54
56
57
R-410A / 2,087.5
9.52/16.0
9.52/19.0
9.52/22.0
Daikin wired remote control (BRC1E52A/B or BRC1D52)
230
CYVL100DK125*BN/*SN
15.6
0.75
0.75
CYVL150DK200*BN/*SN
23.3
1.13
1.13
(1) Favorable conditions: covered shopping mall or revolving door entrance (2) Normal conditions: little direct wind, no opposite open doors, building with ground floor only (3) Unfavorable conditions: location at a corner or square, multiple floors and/or
open stairway
221
CYVM150DK80FSC
500
250
250
40
100
197
O9.2
Suction grid
with filter
98
27
Type
CYVS-DK-FBN/FSN
CYVM-DK-FBN/FSN
CYVL-DK-FBN/FSN
L
1,000 - 1,500
2,000 - 2,500
1,000 - 1,500
2,000 - 2,500
270
590
93
171
119
370
774
124.5 245.5
200
CU0954X-000
REMARKS
The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.
500
250
250
40
100
197
O9.2
98
27
Screw-eye M6
CYVL-DK-CBN/CSN
270
821
93
171
119
250
411
260
L
1,000 - 1,500
2,000 - 2,500
1,000 - 1,500
2,000 - 2,500
Type
CYVS-DK-CBN/CSN
CYVM-DK-CBN/CSN
370
200
181.5 563.5
360
REMARKS
222
The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.
The mounting holes for finishing profiles in a lowered ceiling (L+8) x (D+8) mm
CU0955X-000
500
250
250
40
100
197
O9.2
Suction grid
with filter
98
1500
2000
2500
10
12
101.5
1000
Type
L
H
CYVS-DK-RBN/RSN
CYVM-DK-RBN/RSN 1,000 - 1,500 270
2,000 - 2,500
CYVL-DK-RBN/RSN 1,000 - 1,500
2,000 - 2,500 370
561
80125
90
171
119
92
139
260
745
360
T
1048-1548
20482548
1048-1548
1044-1544
408 250 2044-2544 20482548
308 160 1044-1544
2044-2544
Device length
1000 / 1500
2000 / 2500
Type
CYVS-DK-RBN/RSN
CYVM-DK-RBN/RSN
CYVL-DK-RBN/RSN
27
L
M
CU0956X-000
The 2,500mm large devices have 3 suspension brackets, where the third bracket is mounted at half the length of the device.
Holes (for finishing profiles) - drain (L+8) x (E+8) mm - suction (L+8) x (G+8) mm.
REMARKS
223
Ventilation
& air handling
Daikin offers the widest range in DX
ventilation in the market.
With a variety of ventilation solutions from
small heat recovery ventilation to large scale
air handling units we help provide a fresh,
healthy and comfortable environment in
offices, hotels, stores and other commercial
environments.
224
Ventilation
& air handling
Ventilation
Heat reclaim ventilation
VAM-FC228
VKM-GB(M)240
NEW
225
Ventilation
Energy
recovery
Five components of
indoor air quality
Humidification
Air
processing
Filtration
Model
PG
200
400 600
140,000
Components of
indoor air quality
VAM-FC
Heat reclaim
ventilation
VKM-GB
Air Handling
Unit (application)
VKM-GBM
226
Ventilation
Energy recovery
228
Ventilation
Energy recovery
Air processing
240
Ventilation
Energy recovery
Air processing
Humidification
240
251
(1)
Ventilation
Energy recovery
Air processing
Humidification
Filtration
Ventilation
DAIKIN AIR HANDLING UNIT AND ERQ/VRV PLUG & PLAY CONNECTION
227
VAM-FC
Total heat
exchanged
foul air
Total heat
exchanged
clean air
9 AM
12 PM
5 PM
Increase in air
volume and
better comfort
compared to fixed
ventilation rate
10
11
Morning meeting
12
13
Lunch time
14
15
16
Meeting
17
18
19
hour
CO2 level
Fixed ventilation rate
Ventilation amount
Using CO2 sensors has the most energy-saving potential in buildings where occupancy fluctuates during a 24-hour period, is unpredictable and peaks at a high level. For example
office buildings, government facilities, retail stores and shopping malls, movie theaters, auditoriums, schools, entertainment clubs and nightclubs. The ventilation unit's reaction to
fluctuations in CO2 can be easily adjusted through a field setting.
228
INDOOR
30.6C
62% RH
32C
70% RH
SA
27.4C
63% RH
RA
26C
50% RH
Integrally-formed liner
Temperature
and humidity is
exhanged between
the layers
SA
RA
Ventilation
Power input - 50Hz
Temperature
exchange efficiency
- 50Hz
Enthalpy exchange
efficiency - 50Hz
Ultra high
Ultra high
Operation mode
Heat exchange system
Heat exchange element
Dimensions
Unit
HeightxWidthxDepth
Weight
Unit
Casing
Material
Heat exchange mode Ultra high
Fan-Air flow rate 50Hz
Bypass mode
Ultra high
Fan-External static
Ultra high/High/Low
pressure - 50Hz
Air filter
Type
Sound pressure level Heat exchange mode Ultra high
- 50Hz
Bypass mode
Ultra high
Operation range
Min./Max.
Relative humidity
Refrigerant
Type / GWP
Connection duct diameter
Power supply
Phase/Frequency/Voltage
Current
Maximum fuse amps (MFA)
VAM
kW
kW
%
%
%
mm
kg
m/h
m/h
Pa
dBA
dBA
CDB
%
mm
Hz/V
A
150FC
0.132
0.132
77.0 (2) / 72.0 (3)
78.3 (2) / 72.3 (3)
82.8 (2) / 73.2 (3)
60.3 (2)
61.9 (2)
67.3 (2)
66.6 (2)
67.9 (2)
72.4 (2)
250FC
0.161
0.161
74.9 (2) / 69.5 (3)
76.0 (2) / 70.0 (3)
80.1 (2) / 72.0 (3)
60.3 (2)
61.2 (2)
64.5 (2)
66.6 (2)
67.4 (2)
70.7 (2)
350FC
500FC
650FC
800FC
1000FC
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
0.071 (1)
0.147 (1)
0.188 (1)
0.320 (1)
0.360 (1)
78.0 (2) / 71.6 (3) 77.0 (2) / 70.2 (3) 77.0 (2) / 69.8 (3) 77.0 (2) / 67.8 (3) 78.0 (2) / 70.2 (3)
79.3 (2) / 71.9 (3) 78.8 (2) / 70.7 (3) 79.1 (2) / 71.2 (3) 78.2 (2) / 68.8 (3) 78.6 (2) / 71.1 (3)
84.1 (2) / 73.0 (3) 80.9 (2) / 71.3 (3) 81.1 (2) / 72.9 (3) 79.1 (2) / 69.6 (3) 80.2 (2) / 73.4 (3)
63.4 (2)
60.3 (2)
60.3 (2)
62.4 (2)
63.4 (2)
65.0 (2)
63.4 (2)
64.0 (2)
63.6 (2)
64.2 (2)
70.7 (2)
66.9 (2)
67.3 (2)
64.6 (2)
66.3 (2)
67.6 (2)
64.5 (2)
65.5 (2)
67.6 (2)
68.6 (2)
68.9 (2)
67.6 (2)
67.7 (2)
68.8 (2)
69.4 (2)
73.7 (2)
71.1 (2)
69.7 (2)
69.8 (2)
71.5 (2)
Heat exchange mode, bypass mode, fresh-up mode
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
364x1,000x1,160
285x776x525
301x828x816
364x1,000x868
24.0
33.0
51.0
54.0
63.0
Galvanised steel plate
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
150 (4)
250 (4)
350 (1)
500 (1)
650 (1)
800 (1)
1,000 (1)
90 (4)/87 (4) 70 (4)/63 (4) 103 (1)/93 (1) 83 (1)/57 (1) 100 (1)/73 (1) 109 (1)/94 (1) 147 (1)/135 (1)
40 (4)
25 (4)
51 (1)
35 (1)
49 (1)
78 (1)
100 (1)
Multidirectional fibrous fleeces
27.0
28.0
32.0
33.0
34.5
36.0
36.0
27.0
28.0
32.0
33.5
34.5
36.0
36.0
-15/50
80% or less
100
150
15
200
1~/50/60/220-240/220
250
1500FC
0.617 (1)
0.617 (1)
78.0 (2) / 69.5 (3)
79.6 (2) / 70.3 (3)
80.8 (2) / 71.0 (3)
63.4 (2)
65.0 (2)
66.2 (2)
68.6 (2)
69.7 (2)
70.5 (2)
2000FC
0.685 (1)
0.685 (1)
78.0 (2) / 70.2 (3)
79.6 (2) / 71.3 (3)
80.6 (2) / 74.6 (3)
63.4 (2)
64.5 (2)
67.8 (2)
68.6 (2)
69.5 (2)
72.1 (2)
726x1,510x868 726x1,510x1,160
128
145
1,500 (1)
2,000 (1)
1,500 (1)
2,000 (1)
116 (1)/97 (1) 132 (1)/118 (1)
80 (1)
77 (1)
39.5
40.5
40.0
40.0
350
16
(1) Measured on fan curve 15. Refer to fan curves. (2) Measured according to JIS B 8628 (3) Measured according to EN308 : 1997 (4) Clean the filter when this icon appears on the controller screen. Regular filter cleaning is important for delivered air quality and
for the units energy efficiency. (5) In accordance with commission regulation (EU) No 1254/2014 (6) Products with an air flow rate 250m/h must comply to commission regulation (EU) No.1254/2014 for RVUs, products with an air flow rate > 250m/h must
comply to commission regulation (EU) No.1253/2014 for NRVUs.
229
RH: Relative Humidity SA: Supply Air (to room) RA: Return Air (from room)
VH
and preheaters
ries required)
VH
(VH)
220/250V ac 50/60 Hz. +/-10%
19A at 40C (ambient)
5k ohms at 25C (table 502 1T)
0 to 40C / (0-10V 0-100%)
20 x 5mm 250mA
Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red
Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input
VH
Capacity
Duct diameter
Connectable VAM
kW
mm
1B
1
100
VAM150FC
-
For the selection of the appropriate capacity, please refer to the VAM selection software.
230
2B
1
150
VAM250FC
VAM350FC
3B
1
200
VAM500FC
VAM650FC
4B
1.5
250
VAM800FC
VAM1000FC
4/AB
2.5
250
VAM800FC
VAM1000FC
5B
2.5
300
VAM1500FC
VAM2000FC
Switch box
Ceiling hook
4-14x40 oval hole
Inspection hole
450
285
600
Maintenance over
104
120.3
67
20
149
120~250
269
SA
104
124
288
560
EA
Exhaust air to outdoors
718
Sealing
20
120
164
509
RA
288
124 164
OA
Damper plate
149
(Maintenance cover)
Exhaust spacer
(Switch box)
145
760
97
200
145
Air filters
NOTE
Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.
3TW27874-1
VAM250FA
VAM250FA
Maintenance space for the heat exchange elements, the air
filters and fans
Switch box
Ceiling hook
4-14x40 oval hole
Inspection hole
450
285
Maintenance over
120.3
67
20
104
600
120~250
269
149
SA
509
124
288
560
164
RA
OA
288
124 164
EA
Sealing
718
20
120
Damper plate
149
(Maintenance cover)
760
145
97
200
(Switch box)
145
Air filters
NOTE
Be sure to provide the inspection hole (450x450 mm) to inspect the air filters, the exchange elements and fans.
3TW27884-1
231
Ceiling hook
4 12 x 40 oval hole
Sealing
Damper plate
RA
Return air from room
EA
Exhaust air to outdoors
SA
Supply air to room
Supply air fan
OA
Fresh air from outdoors
(outdoor air)
Switch box
Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans
Maintenance cover
Air lters
Switchbox
NOTES
3D081162
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
VAM500FC
VAM500FB
Ceiling hook
4 12 x 40 oval hole
Sealing
Damper plate
RA
Return air from room
EA
Exhaust air to outdoors
SA
Supply air to room
OA
Fresh air from outdoors
(outdoor air)
Switch box
Inspection hole
Maintenance space for the heat exchange
element, the air lters and fans
Maintenance cover
Air lters
Switchbox
NOTES
1. Be sure to provide the inspection hole to inspectthe air lters, the exchange elements and fans.
232
3D081163
Ceiling hook
4 12 x 40 oval hole
Damper plate
Exhaust air fan
RA
Return air from room
EA
Exhaust air to outdoors
SA
Supply air to room
OA
Fresh air from outdoors
(outdoor air)
Maintenance cover
Air lters
Switchbox
NOTES
3D081164
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
VAM800FC
VAM800FB
Sealing
Ceiling hook
4 12 x 40 oval hole
Damper plate
Exhaust air fan
RA
Return air from room
EA
Exhaust air to outdoors
SA
Supply air to room
OA
Fresh air from outdoors
(outdoor air)
Maintenance cover
Air lters
Switchbox
NOTES
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
3D081165
233
Ceiling hook
4 12 x 40 oval hole
Sealing
Damper plate
Exhaust air fan
RA
Return air from room
EA
Exhaust air to outdoors
SA
Supply air to room
OA
Fresh air from outdoors
(outdoor air)
Inspection hole
Maintenance cover
Air lters
Switchbox
NOTES
3D081166
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
VAM1500FC
VAM1500FB
Sealing
Ceiling hook
4 14 x 40 oval hole
Exhaust air fan (2x)
Damper plate
EA
Exhaust air to outdoors
RA
Return air from room
OA
Fresh air from outdoors
(outdoor air)
SA
Supply air to room
Supply air fan (2x)
Switch box
Inspection hole
Maintenance cover
Air lters
Switchbox
NOTES
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
234
3D081167
Ceiling hook
4 14 x 40 oval hole
Damper plate
RA
EA
Exhaust air to outdoors
SA
Supply air to room
OA
Fresh air from outdoors
(outdoor air)
Inspection hole
Maintenance cover
Air lters
Switchbox
VAM150FC
NOTES
3D081168
1. Be sure to provide the inspection hole to inspect the air lters, the exchange elements and fans.
VAM150FC
250
20m
15m
150
200
Ultra-high
10m
100
High
5m
Low
50
100
Pipe length
0
0
50
100
150
Air flow rate [m/h]
200
250
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
4D100379
235
VAM250FC
200
Ultra-high
150
150
Pipe length
High
100
40m
30m
Low
20m
50
10m
0
0
50
100
150
200
Air flow rate [m/h]
250
300
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
4D100380
VAM350FC
VAM350FC
200
40m
UH15
H15
150
UH8
20m
30m
200
150
External static pressure [Pa]
250
200
Ultra-high speed
300
100
50
50
15
10m
H1
L8
L1
150
250
350
Air flow rate [m/h]
150
Pipe length
100
200
300
Air flow rate [m/h]
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
=
=
=
=
=
=
=
=
=
400
150
250
350
Air flow rate [m/h]
450
500
100
450
Low speed
0
0
100
UH1
L15
50
150
15
H8
100
High speed
50
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
0
150
250
15
350
Air flow rate [m/h]
450
3D100381
236
VAM500FC
200
200
200
Pipe length
VAM500FC
200
Ultra-high speed
High speed
VAM500FC
50m
150
UH15
40m
UH8
H8
100
L8
50
L1
30m
H1
L15
L8
50
H15
UH1
20m
H1
L15
L1
10m
100
30m
20m
200
High speed150
External static pressure [Pa]
H15
UH1
H8
100
50m
UH8
150
150
Ultra-high
speed
40m
150
100
200
200
Pipe length
UH15
200
150
50
10m
100
50
100
50
50
100
200
100
300
200
400
500
300
400
500
Air
flow
rate
[m/h]600
Air flow
rate
[m/h]
700
600
700
200
Ultra-high speed
Ultra-high speed
High speed
Low speed
High speed
H15
UH1
500
300
Air flow rate [m/h]
100
=
=
=
=
=
=
=
=
=
=
=
NotesUH8
=
Ultra-high speed factory setting
1. The fan speeds are valid for 230V, 50Hz power supply.
UH15
50
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
300
600
15
600
200
400700
500
Air flow rate [m/h]
700300
15
400
500
Air flow rate [m/h]
600
700
Low speed
50
200
400 700
500 200
Air flow rate [m/h]
600
Low100speed
Low speed
Legend
L1
Legend
L8
L15L1
H1
L8
H8
L15
H15
UH1H1
UH8
H8
UH15
400
200
300
15
15
300
400
15
500
3D100382
0
VAM650FC
200
VAM650FC
300
400
15
500
300
250
60m
250
Ultra-high speed
High speed
3D100382
50m
250
200
200
UH15
150
UH1
30m
UH8
H15
20m
L15
100
H8
L8
50
H1
10m
150
100
100
50
50
200
Pipe length
L1
150
200
40m
External static pressure [Pa]
15
0
0
200
400
600
800
0
250
350
450
550
650
750
Air flow rate [m/h]
150
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
=
=
=
=
=
=
=
=
=
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
850
250
350
450
550
650
750
Air flow rate [m/h]
15
850
Low speed
100
50
0
250
450
15
650
Air flow rate [m/h]
850
3D100383
237
VAM800FC
VAM800FC
300
250
250
UH8
H15
200
UH15
H8
100m
L15
UH1
150
200
150
100
L8
H1
100
0
200
50
15
20m
150
50
40m
L1
50
200
80m
60m
100
High speed
250
300
350
300
Ultra-high speed
400
400
600
Air flow rate [m/h]
800
1000
300
250
Pipe length
900
300
1100
500
700
Air flow rate [m/h]
15
900
1100
Low speed
250
=
=
=
=
=
=
=
=
=
700
Air flow rate [m/h]
300
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
500
200
150
100
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
50
0
300
500
15
700
Air flow rate [m/h]
900
1100
3D100384
VAM800FC
VAM1000FC
300
250
250
UH8
H15
200
UH15
H8
100m
L15
UH1
150
L8
H1
150
100
20m
0
0
200
150
100
15
400
600
Air flow rate [m/h]
800
1000
0
300
250
Pipe length
700
Air flow rate [m/h]
300
900
0
300
1100
500
700
Air flow rate [m/h]
900
15
1100
Low speed
250
=
=
=
=
=
=
=
=
=
500
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
200
50
50
40m
L1
50
200
80m
60m
100
High speed
250
300
350
300
Ultra-high speed
400
200
150
100
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
50
0
300
500
700
Air flow rate [m/h]
15
900
1100
3D100384
238
VAM1500FC
300
250
250
UH8
UH15
H15
200
H8
100m
L15
UH1
150
L8
H1
150
100
150
100
15
20m
0
0
200
200
50
50
40m
L1
50
200
80m
60m
100
High speed
250
300
350
300
Ultra-high speed
400
400
600
Air flow rate [m/h]
800
1000
300
900
300
1100
500
700
Air flow rate [m/h]
15
900
1100
Low speed
250
=
=
=
=
=
=
=
=
=
700
Air flow rate [m/h]
300
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
500
250
Pipe length
200
150
100
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
50
300
500
15
700
Air flow rate [m/h]
900
1100
3D100384
VAM2000FC
VAM2000FC
200
UH15
150
H15
UH8
H8
100
250
250
200
200
150
100
High speed
150
100
UH1
L15
H1
50
50
50
L8
L1
0
1000
1500
2000
Air flow rate [m/h]
2500
0
1200
1700
2200
Air flow rate [m/h]
160
Ultra-high speed
High speed
Low speed
Legend
L1
L8
L15
H1
H8
H15
UH1
UH8
UH15
=
=
=
=
=
=
=
=
=
Notes
1. The fan speeds are valid for 230V, 50Hz power supply.
0
1200
15
2700
1700
2200
Air flow rate [m/h]
15
2700
Low speed
140
120
External static pressure [Pa]
250
300
Ultra-high speed
300
300
100
80
60
40
20
0
1
1200
15
1700
2200
Air flow rate [m/h]
2700
3D100387
239
VKM-GB/VKM-GBM
moisture recovery
Creates a high quality indoor environment by pre conditioning
air flow rate, so less need for dampers compared with traditional
installation.
Specially developed heat exchange element with High
Efficiency Paper (HEP)
Can operate in over- and under pressure
Exhaust Fan
Heat Exchanger
Elements
Damper Motor
Damper
EA
(Exhaust air to outdours)
OA
(Fresh air from outdoors)
RA
(Return air from room)
Float switch
Humidifier element:
Utilizing the principle of capillary action, water is
permeated throughout the humidifier element.
The heated air from the DX coil passes through the
humidifier and absorbs the moisture.
water
AIRFLOW
Drain pan
1
VKM-GM example
240
Solenoid
valve
Drain
SA
VKM-GM example
VKM-GB/VKM-GBM
Ultra high
kW
Ultra high
kW
kW
kW
%
%
%
76/76/77.5
mm
kg
387x1,764x832
94
m/h
m/h
Pa
Pa
Pa
500
500
dBA
dBA
CDB
CDB
CDB
CDB
CDB
39
40
mm
mm
mm
mm
200
Hz/V
A
78/78/79
64/64/67
67/67/69
210
170
140
74/74/76.5
78/78/79
74/74/76.5
66/66/68
62/62/66
64/64/67
66/66/68
62/62/66
71/71/73
65/65/69
67/67/69
71/71/73
65/65/69
Heat exchange mode / Bypass mode / Fresh-up mode
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Natural evaporating type
387x1,764x1,214
387x1,764x832
387x1,764x1,214
110
112
100
119
123
Galvanised steel plate
750
950
500
750
950
750
950
500
750
950
150
200
205
110
160
100
150
155
70
110
70
120
105
60
Multidirectional fibrous fleeces
41.5
41
38
40
41.5
41
39
41
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
-15
43
43
R-410A
Electronic expansion valve
2,087.5
250
200
250
6.35
12.7
6.4
PT3/4 external thread
1~/50/220-240
15
241
Ventilation
Power input - 50Hz
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Branch duct
(locally procured)
Control box
Maintenance space for the heat exchanger
elements the air filters and fans
Inspection
hatch
Inspection
hatch
Flexible duct
(locally procured)
Heat insulator
(locally procured)
A gradient of
more than 1/30
200
Nominal diameter
(locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100
Inspection hatch
(locally procured)
Suspention bolt
(locally procured)
RA
(Return air from room)
SA
(Return air to room)
NOTES
1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.
3D083014
242
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Round shape hood
(locally procured)
OA
(Fresh air to outdoors)
Control box
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier
Inspection
hatch
Inspection
hatch
Branch duct
(locally procured)
Flexible duct
(locally procured)
Heat insulated
(locally procured)
250
Nominal diameter
(locally procured)
Drain valve
(locally procured)
Strainer
(locally procured)
OA
(Fresh air to outdoors)
Sloping downwards at
a gradient of the 1/100
450 - 600
Inspection hatch
(locally procured)
Suspention bolt
(locally procured)
RA
(Return air from room)
SA
(Return air from room)
NOTES
1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 )
7. Make sure the supply water is between 5C and 40C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0C.
12. Do not use a bent cap or a round hoodas the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13.In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14.Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the
air filter is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)
3D083011
243
EA
(Exhaust air to outdoors)
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Branch duct
(locally procured)
Inspection
hatch
Inspection
hatch
Silencer
(locally procured)
Control box
Heat insulator
(locally procured)
Flexible duct
(locally procured)
200
Nominal diameter
A gradient of
more than 1/30
(locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100
450 600
Inspection hatch
(locally procured)
Suspention bolt
(locally procured)
RA
(Return air from room)
SA
(Return air to room)
NOTES
1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.
3D083015
244
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Branch duct
(locally procured)
Heat insulated
(locally procured)
Control box
Maintenance space for the heat exchanger
elements the air filters, fans and humidifier
Inspection
hatch
Inspection
hatch
OA
(Fresh air to outdoors)
Silencer
(locally procured)
Flexible duct
(locally procured)
250
Drain valve
(locally procured)
Strainer
(locally procured)
Nominal diameter
(locally procured)
OA
(Fresh air to outdoors)
Sloping downwards at
a gradient of the 1/100
450 - 600
Inspection hatch
(locally procured)
Suspention bolt
(locally procured)
RA
(Return air from room)
SA
(Return air from room)
EA
(Exhaust air to outdoors)
NOTES
1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2 )
7. Make sure the supply water is between 5C and 40C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the umidifier will not drop below 0C.
12. Do not use a bent cap or a round hoodas the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13.In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14.Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the
air filter is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)
3D083012
245
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Branch duct
(locally procured)
Inspection
hatch
Inspection
hatch
Silencer
(locally procured)
Control box
Heat insulator
(locally procured)
Flexible duct
(locally procured)
A gradient of
more than 1/30
250
Nominal diameter
(locally procured)
OA
(Fresh air from outdoors)
EA
(Exhaust air to outdoors)
Sloping downwards at a
gradient of the 1/100
450 600
Inspection hatch
(locally procured)
Suspention bolt
(locally procured)
RA
(Return air from room)
SA
(Return air to room)
NOTES
1. L eave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air filters, heat exchange elements, and fans can easily be
inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water, also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
5. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
6. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
7. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
8. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
filter is very dirty.
3D083016
246
Heat insulator
(locally procured)
EA
(Exhaust air to outdoors)
Branch duct
(locally procured)
Control box
Inspection
hatch
Inspection
hatch
OA
(Fresh air from outdoors)
Heat insulator
(locally procured)
Silencer
(locally procured)
Flexible duct
(locally procured)
250
Nominal diameter
Drain valve
(locally procured)
Strainer
(accessory)
(locally procured)
OA
(Fresh air from outdoors)
Sloping downwards at a
gradient of the 1/100
450 600
Inspection hatch
(locally procured)
Suspension bolt
(locally procured)
RA
(Return air from room)
SA
(Return air to room)
NOTES
1. Leave space for servicing the unit and include inspection hatch. (Always open a hole on the side of the control box so that the air
heat exchange elements, fans, and
elements can easily be inspected and serviced.)
2. Install the two outdoor ducts with down slope (slope of 1/30 or more) to prevent entry of rain water. Also, provide insulation for three ducts (outdoor ducts and indoor supply air duct) to
prevent dew condensation. (Material: glass wool of 25mm thick)
3. Do not turn the unit upside down.
4. Use city water or clean water.
Include water supply piping with strainer, a water supply shut-off valve, and a drain valve (both locally procured) somewhere along the water supply piping that can be reached from the
inspection.
5. It is impossible to connect the water supply piping directly to public piping. Use a cistern tank (of the approved type), if you need to get your water supply from public piping.
6. Make sure the supply water 0.02MPa to 0.49MPa (0.2 kg/cm2 to 5 kg/cm2).
7. Make sure the supply water is between 5 C and 40 C in temperature.
8. Insulate the water supply piping to prevent condensation from forming.
9. Make sure to install drain piping, and insulate drain piping to prevent dew condensation.
10. Keep the drain pipe short and sloping downwards at a gradient of at least 1/100 to prevent air from forming.
11. Install in a location where the air around the unit or taken into the
will not drop below 0 C.
12. Do not use a bent cap or a round hood as the outdoor hood if they might get rained on directly (we recommend using a deep hood) (optional accessory).
13. In areas where freezing may occur, always take steps to prevent the pipes from freezing.
14. Do not place something which shouldnt get wet at the below of this unit. The dew would fall at following case, where humidity is 80% more, or the exit of drain socket is choked up, or the air
is very dirty.
15. Feed clean water. If the supply water is hard water, use a water softener because of short life.
Life of humidifying element is about 3 years (4,000 hours), under the supply water conditions of hardness: 150 mg/L. (Life of humidifying element is about 1 years (1500 hours), under the
supply water conditions of hardness: 400 mg/L.)
3D083013
247
EA
(Exhaust air to outdoors)
50Hz, 220V-240V
Operating air flow rate range
Temp
e
rature
Enth
alpy
Enth
exch
exch
nge e
fficien
effic
ange
cy
ienc
y (he
effic
ating
ienc
y (co
oling
Ultra High
200
Pipe
length
External static pressure (Pa)
alpy
ange
excha
Exchange
efficiency
(%)
High
Low
2) Rated point:
3) The characteristic of each tap becomes a setup of the
characteristic of the same code number.
3D082904
VKM50GBM
VKM50GBM
Exchange efficiency
(%)
Operating air flow rate range
50Hz, 220V-240V
Temp
e
rature
Enth
alpy
Enth
exch
exch
nge e
effic
ange
fficien
ienc
cy
y (he
effic
ating
ienc
y (co
oling
Ultra High
200
Pipe
length
alpy
ange
VKM50GBM
excha
High
Low
248
2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.
3D082901
50Hz, 220V-240V
Exchange
efficiency
(%)
eratu
re ex
Enth
alpy
Enth
alpy
chan
ge e
exch
ange
exch
ange
fficie
ncy
effic
ienc
y (he
effic
ating
ienc
y (co
oling
Ultra High
High
250
Pipe
length
Tem
p
Low
3D082905
VKM80GBM
VKM80GBM
Exchange efficiency
(%)
50Hz, 220V-240V
Operating air flow
rate range
Tempera
ture exch
alpy
Enth
alpy
ange effic
exch
ange
exch
iency
effic
ange
ienc
y (he
effic
ating
ienc
y (co
oling
Ultra High
250
Pipe
length
Enth
VKM80GBM
High
Low
2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.
3D082902
249
50Hz, 220V-240V
Exchange
efficiency
(%)
Operating air flow rate range
Operating air flow rate range
erat
Ent
ure
halp
y ex
Ent
halp
cha
y ex
exc
han
nge
cha
nge
ge e
fficie
effic
ienc
ncy
y (h
effic
ienc
eatin
y (c
g)
ooli
ng)
Tem
p
250
Pipe
length
Ultra High
High
Low
3D082906
VKM100GBM
VKM100GBM
Exchange efficiency
(%)
50Hz, 220V-240V
En
era
tha
lpy
En
VKM100GBM
tha
lpy
ture
exc
han
exc
ge
han
ge
exc
han
effi
ge e
ncy
cie
fficie
cie
effi
ncy
(he
ncy
atin
(co
g)
olin
g)
Ultra High
High
250
Pipe
length
Tem
p
Low
250
2) Rated point:
3) The characteristic of each tap becomes a setup of the characteristic of the
same code number.
3D082903
Professional
Professional
Pre-configured sizes
Tailored to the individual
140
customer
120
Modular construction
Energy
100
Energy
90
energy consumption
High efficiency components
Strong Return on Investment
80
Modular
70
mounted controls
60
Pre-configured sizes
EC Fan Technology
High Efficiency Heat Wheel
Compact Design
50
40
20
750 m3/h
up to
144,000 m3/h
Modular
750 m3/h
up to
100,000 m3/h
500m3/h
up to 25,000 m3/h
Selection software
Return on investment
Pre-defined sizes
27 fixed sizes are available, optimised to reach
the optimum combination between value for money
and manufacturing standardisation. Daikins section by section
design means that units can be sized by 1cm increments and
assembled on site, without welding, to suit the space constraints
of the installation.
251
Electronic expansion
252
valve
Control box
(EKEXV)
(EKEQ)
0-10V
TTEXT
EXT
Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA
TTRR
DDC
DDC
TS
T
S
0-10V
TTEXT
EXT
Control
box box:
Daikin
control
EKEQFCBA
EKEQFCBA
TEXT
Control box
Control
box
EKEQFCBA
EKEQFCBA
4.
Control your AHU just like a VRV indoor unit with 100% fresh air
Allows the possibility to control the AHU just like a VRV indoor
unit. Meaning temperature control will be focused on return air
temperature from the room into the AHU. Requires BRC1D52 or
BRC1E52A/B for operation. This the only control that allows
the combination of other indoor units to the AHU at the same time.
AHU
AHU
TRR
+
TETC
TTOA
OA
TS
T
S
TTROOM
ROOM
BRC1D*
BRC1D*
BRC1E*
BRC1E*
TTEXT
EXT
Control box
box
Control
EKEQMCBA (VRV
EKEQMCBA
(VRVIV)
IV)
EKEQDCB
(ERQ)
EKEQDCB (ERQ)
OR
OR
TE = Evaporating temperature
TC = Condensing temperature
Option kit
EKEQFCBA
Possibility Z
EKEQDCB
EKFQMCBA*
T
TR
+
TETC
TTOA
OA
Possibility W
Possibility X
Possibility Y
TS
T
S
TTROOM
ROOM
BRC1D*
BRC1D*
BRC1E*
BRC1E*
TTRR
+
TETC
TTOA
OA
TTROOM
ROOM
3.
OR
OR
AHU
AHU
TETC
TTOA
OA
OR
OR
AHU
AHU
DDC
DDC
2.
TS
TTROOM
ROOM
Features
Off-the-shelf DDC controller that requires no pre-configuration
Pre-configured DDC controller required
Using fixed evaporating temperature, no set point can be set using remote control
Using Daikin infrared remote control BRC1D52 or BRC1E52A/B
Temperature control using return air temperature or room temperature (via remote sensor)
253
1.
Refrigerant piping
F1-F2
other communication
254
ERQ-AW1
Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m/min
Heating
Nom.
m/min
Sound power level Cooling
Nom.
dBA
Sound pressure Cooling
Nom.
dBA
Heating
Nom.
dBA
level
Operation range Cooling
Min./Max.
CDB
Heating
Min./Max.
CWB
On coil
Heating Min.
CDB
CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Drain
OD
mm
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A
100AV1
125AV1
140AV1
4
11.2
12.5
2.81
2.74
5
14.0
16.0
3.51
3.86
6
15.5
18.0
4.53
4.57
3.42
3.94
Ventilation
ERQ
Capacity range
HP
Cooling capacity Nom.
kW
Heating capacity Nom.
kW
Power input
Cooling
Nom.
kW
Heating
Nom.
kW
EER
COP
Dimensions
Unit
mm
Weight
Unit
kg
Fan-Air flow rate Cooling
Nom.
m/min
Heating
Nom.
m/min
Sound power level Nom.
dBA
Sound pressure level Nom.
dBA
Operation range Cooling
Min./Max.
CDB
Heating
Min./Max.
CWB
On coil
Heating Min.
CDB
CDB
temperature Cooling Max.
Refrigerant
Type / GWP
Charge
kg/ TCO2Eq
Piping
Liquid
OD
mm
Gas
OD
mm
connections
Power supply
Phase/Frequency/Voltage
Hz/V
Current
Maximum fuse amps (MFA)
A
125AW1
200AW1
250AW1
5
14.0
16.0
3.52
4.00
3.98
4.00
1,680x635x765
159
95
95
72
54
8
22.4
25.0
5.22
5.56
4.29
4.50
10
28.0
31.5
7.42
7.70
3.77
4.09
3.99
4.56
4.15
1,345x900x320
120
106
105
67
51
53
-5/46
-20/15.5
10
35
R-410A / 2.087,5
4.0/8.4
9.52
69
53
55
15.9
19.1
102
66
50
52
26x3
1N~/50/220-240
32.0
6.2/12.9
15.9
1,680x930x765
187
171
171
240
185
185
78
57
58
-5/43
-20/15
10
35
R-410A / 2.087,5
7.7/16.1
9.52
19.1
8.4/17.5
22.2
3N~/50/400
16
25
255
Combination table
Control box
ERQ100
1-phase ERQ125
ERQ140
ERQ125
3-phase ERQ200
ERQ250
VRV III
VRV IV H/P /
VRV IV W-series
VRV IV S-series
VRV IV H/R
VRV IV i-series
EKEXV50
n1
EKEXV63
P
P
P
n1
EKEXV80
P
P
P
P
n1
EKEXV100
P
P
P
P
P
n1
EKEXV125
P
P
P
P
P
P
n1
EKEXV140
P
P
P
P
P
n1
EKEXV200
P
P
n1
EKEXV250
P
P
n1
EKEXV400
n1
EKEXV500
n1
Not possible
Mandatory
P (1 -> 3)
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
n2
Possible (not
mandatory)
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
n1
Mandatory
P (pair application): combination depends on the capacity of the air handling unit
n1 (multi application) - Combination of AHUs and VRV DX indoors (mandatory). To determine the exact quantity please refer to the engineering data book.
n2 (multi application) - Combination of AHUs and VRV DX indoors (not mandatory). To determine the exact quantity please refer to the engineering data book.data book
Control box EKEQFA can be connected to some types of VRV IV outdoor units (with a maximum of 3 boxes per unit). Do not combine EKEQFA control boxes with VRV DX indoor units, RA indoor units or hydroboxes
Capacity table
Cooling
EKEXV Class
50
63
80
100
125
140
200
250
400
500
Standard
5.6
7.1
9.0
11.2
14.0
16.0
22.4
28.0
45.0
56.0
Heating
Maximum
6.2
7.8
9.9
12.3
15.4
17.6
24.6
30.8
49.5
61.6
EKEXV Class
Minimum
5.6
7.1
8.9
11.2
13.9
17.4
19.9
27.8
39.8
55.1
50
63
80
100
125
140
200
250
400
500
Standard
6.3
8.0
10.0
12.5
16.0
18.0
25.0
31.5
50.0
63.0
Maximum
7.0
8.8
11.1
13.8
17.3
19.8
27.7
34.7
55.0
69.3
EKEXV
mm
kg
dBA
CDB
CDB
50
63
80
100
125
140
401x215x78
2.9
45
10 (1)
35 (2)
200
250
400
500
12.7
15.9
R-410A / 2.087,5
mm
6.35
9.52
(1) The temperature of the air entering the coil in heating mode can be reduced to -5CDB. Contact your local dealer for more information. (2) 45% Relative humidity.
EKEQ
Unit
Unit
Phase/Frequency/Voltage
mm
kg
Hz/V
FCBA
See note
ERQ / VRV
DCB
Pair
ERQ
132x400x200
3.9
MCBA
Multi
VRV
3.6
1~/50/230
The combination of EKEQFCBA and ERQ is in pair application. The EKEQFCBA can be connected to some type of VRV IV outdoor units with a maximum of 3 control boxes. The combination with DX indoor units,
hydroboxes, RA outdoor units, ... is not allowed. Refer to the combination table drawing of the outdoor unit for details.
256
Controllers
INTELLIGENT
TOUCH MANAGER
DCM601A51
INFRARED REMOTE
CONTROLLER
257
Market leading
controls for 2016
INTUITIVE & USER-FRIENDLY INTERFACE
CROSS PILLAR INTEGRATION
CLOUD CONTROL
SMART ENERGY MANAGEMENT
INTEGRATION OF DAIKIN AND THIRD PARTY PRODUCTS
Table
such as online control, energy monitoring, comparison of energy consumption of multiple sites
Connect up to 32 indoor units
258
Control Systems
Control Systems
Requirements tables per application
260
262
280
280
281
DCC601A51266
Mini building management system
268
270
273
274
275
276
com/commercial/needs/controls
Network solutions
Screen
Integration
Control
Monitoring
Options
Other
Floor plan
Touch screen
Mini BMS for heating, air conditioning, applied systems and refrigeration units
3rd party equipment integration (BACnet and WAGO)
Basic control functions: on/off, temp setting, air flow settings
Refrigerant containment check
Set point limitation
Setback
Automatic changeover
Weekly schedule and special day pattern
Timer extension
Emergency stop function
Basic control functions: ON/OFF status, operation mode, set point temp. , room temp.
Filter status
Malfunction code
History (operation, malfunction)
Data visualisation
Multi site
PPD
Web access and control
HTTP option
Interlock (Set any preferred logic)
Pre-cool/heat
Sliding temperature
i-Net
Maximum indoor unit groups
BACNET
Control Systems
intelligent intelligent
Tablet
Touch
LONWORKS
Controller Manager
Type
(1)
(1)
(1)
32
Std
512
64
4x64
259
NEW
Shop
Unit control
BRC1E52A/B
BRC1E53A/B/C
Integrating control
RTD-20
1 remote
controller for
1 indoor unit
(group)
1 gateway for
1 indoor unit
(group)
RTD-Net
KLIC-DI
Advanced control
EKMBDXA
DCM601A51
1 unit for 32
indoor unit(s)
1 iTM for 64
indoor unit(s)
(groups) (1)
DCC601A51
(2)
(2)
(2)
(2)
Hotel
Unit control
BRC2/3E52C
Integrating control
RTD-HO
1 remote controller
1 gateway for 1
for 1 indoor unit
indoor unit (group)
(group)
Hotel guest can control & monitor basic functionalities from his room
Limited control possibilities for hotel guests
Interlock with window contact
Interlock with key-card
Integrate Daikin units into existing BMS via Modbus
(2)
(2)
DCS601C51
DCM601A51
1 gateway for 1
indoor unit
260
Advanced control
KLIC-DI
Office
Unit control
BRC1E52A/B
BRC1E53A/B/C
1 remote
controller for
1 indoor unit
(group)
Integrating control
EKMBDXA
DMS504B51
Advanced control
DMS502A51 /
DAM412B51
1 gateway for
1 gateway for
1 R/C for max.
1 gateway for
max. 64 indoor
128 indoor
64 groups, 128
64 indoor unit(s)
unit(s) (groups)
unit(s) (groups), indoor units, 10
(groups)
& 10 outdoors
20 outdoors (2)
outdoors
(3)
DCS601C51
DCM601A51
1 iTC for 64
indoor unit(s)
(groups)
1 iTM for 64
indoor unit(s)
(groups) (1)
DCS302C51 /
DST301B51
(4)
(5)
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems)
(2) : extension needed to go to 256 indoor unit(s) (groups), 40 outdoors
(3) : ON/OFF only
(4) : with Sky Air pair units only
(5 ): DMS502A51 only
NEW
Infrastructure cooling
Unit
Integrating
Advanced
BRC1E53A/B/C
RTD-10
DCM601A51
1 remote
controller for
1 indoor unit
(group) (2)
1 gateway for
1 indoor unit
(group)
Up to 8
gateways
can be linked
together
1 iTM for 64
indoor unit(s)
(groups) (1)
If room temperature above max., then show alarm & start standby
unit.
If an error occurs, an alarm will be shown.
Control Systems
launch Spring
2016
(1) : 7 iTM plus adapters (DCM601A52) can be added to have 512 indoor groups and 80 outdoor (systems) (2) Infrastructure cooling functions only
compatible with indoor units connected to Seasonal Smart outdoor units.
261
(Function available in
combination with FBQ-D,
FCQG and FCGHQ)
BRC1E53A/B/C
Other functions
Up to 3 independent schedules can be set,
so the user can easily change the schedule himself
throughout the year (e.g. Summer, winter, mid-season)
Possibility to individually restrict menu functions
Easy to use: all main functions directly accessible
Easy setup: clear graphical user interface for
advanced menu settings
Real time clock with auto update to daylight
saving time
Built-in backup power: when a power failure occurs
all settings remain stored
Supports multiple languages:
English, German, Dutch, Spanish, Italian, Portuguese,
French, Greek, Russian, Turkish, Polish (BRC1E52A)
English, German, Czech, Croatian, Hungarian,
Romanian, Slovenian, Bulgarian, Slovak, Serbian and
Albanian (BRC1E52B)
(1) for Sky Air FBQ-D, FCQG and FCQHG pair combinations only
COMING
SPRING 2016
BRC2E52A / BRC3E52A
BRC3E52A
Heat pump type
262
P1 P2
Adaptator
(BRP7A51)
Window contact
(field supply)
BRC073
BRC073
Fo
comb r
ina
with S tion
pli
indoo t
r
units
BRC1D52
BRC1D52
Schedule timer:
Five day actions can be set as follows:
-- set point: unit is switched ON and normal
operation is maintained
-- OFF: unit is switched OFF1
-- limits: unit is switched ON and min./max. control
(cf. limit operation for more details)
Home leave (frost protection): during absence, the
indoor temperature can be maintained at a certain
level. This function can also switch the unit ON/OFF
User friendly HRV function, thanks to
the introduction of a button for ventilation mode
and fan speed
Immediate display of fault location and condition
Reduction of maintenance time and costs
ARC4*/BRC4*/BRC7*
BRC4*/BRC7*
263
Centralised control of the Sky Air and VRV system can be achieved via 3 user friendly compact remote
controllers. These controls may be used independently or in combination with 1 group = several (up to 16)
indoor units in combination and 1 zone = several groups in combination.
A centralised remote control is ideal for use in tenanted commercial buildings subject to random occupation,
enabling indoor units to be classified in groups per tenant (zoning).
The schedule timer programmes the schedule and operation conditions for each tenant and the control can
easily be reset according to varying requirements.
DCS302C51
DST301B51
Schedule timer
Enabling 64 groups to be programmed.
a maximum of 128 indoor units can be controlled
8 types of weekly schedule
a maximum of 48 hours back up power supply
a maximum wiring length of 1,000m (total: 2,000m)
DCS301B51
264
DTA113B51
Basic solution for control of Sky Air and VRV in infrastructure cooling applications
adapter - DTA113B51
Rotation function
Backup operation function.
BRC1E53A/B/C
Up to 4 units (groups)/ 1 adapter
DCS601C51
Detailed & easy monitoring and operation of VRV systems (max. 64 indoor units groups).
Fire alarm
Ethernet
Forced OFF contact input
DIII-NET
Indoor units
HRV
DCS601C51
System layout
Up to 64 indoor units can be
controlled
Touch panel (full colour LCD
Control
Individual control
Monitoring
Visualisation via Graphical
function
Indoor units operation mode
Indication filter replacement
Multi PC
Cost performance
Free cooling function
Labour saving
Easy installation
Compact design: limited
Open interface
Communication to any third
installation space
Overall energy saving
265
Control Systems
Languages
English
French
German
Italian
Spanish
Dutch
Portuguese
DCC601A51
Advanced
centralised
controller
2 solutions:
Local solution
Offline centralised control
Cloud solution
Flexible online control from any device (Laptop,
tablet...)
installations
Energy consumption follow-up to comply
System layout
Local solution
Alarm
Window
contact
Daikin supplied screen
(optional) (for local control)
Pulse input
Z380C-1A023A
or
Digital input
Local network
Daikin supplied router
(optional) 4G-N12
Table
DCC601A51
WAGO power
supply
CPU module
I/O module
Split,
,
VAM, ventilation,
air curtains
266
Total solution
Total solution thanks to a large integration of
LOCAL
CONTROL
DAIKIN CLOUD
SERVICE
Installer/
technical manager
Customer
Flexible
Inputs via digital and pulse input for 3rd party
Pulse input
Digital input
Indoor uit
Functions overview
System layout
Local solution
Cloud solution
32
32
Control Systems
Languages
Connectable to
267
Check on
https://www.youtube.com/
DaikinEurope
DCM601A51
Mini BMS
Web Access
CLOUD
Internet
Extranet
LAN
3G
Integration of third
party equiqment
Max. 7
adapters
Di/Pi line
Fire alarm
Max. 200m
DCM601A52
Di/Pi port
kWh meter
I/O module
Pump
Sensor
Elevator
268
Alarm
I/O module
Fan
air curtain,
hydrobox,
Analog/digital/pulse objects
Lighting
indoor units,
Refrigeration
WAGO
interface
protocol
BACnet/IP
User friendliness
main funtions
All functions direct accessible via touch screen
Flexibility
Split
Fan coils
Refrigeration
BACnet/IP
protocol
Lighting
Lighting
Sensor
Pump
Fan
Sensor
Air handling
unit
Elevator
Alarm
WAGO I/O
Lighting
Pump
Fan
Sensor
on site visit
Simplified troubleshooting
Save time on commissioning
Flexibility in size
64 up to 512 groups
Functions overview
English
Management
Control
French
Web access
Individual control
German
Power Proportional
Italian
Spanish
Dutch
Portuguese
Distribution (option)
Operational history
(malfunctions, )
(512 groups)
Schedule setting (Weekly
Connectable to
- DX Split, Sky Air, VRV
- Chillers
(via POL638.70 controller)
- Daikin AHU
- Fan coils
seasonal schedule)
Interlock control
- LT and HT hydroboxes
Setpoint limitation
System layout
according to plan
Temperature limit
- WAGO I/O
controlled
waste
Setback function
Plus adapters)
Sliding temperature
- BACnet/IP protocol
WAGO Interface
Modular integration of 3rd
party equipment
- WAGO coupler (interface
between WAGO and iTM)
- Di module
- Do module
- Ai module
- Ao module
- Thermistor module
- Pi module
269
Control Systems
Languages
Modbus Interface
RTD
RTD-RA
Modbus interface for monitoring and control
of residential indoor units
RTD-NET
Modbus interface for monitoring and control
of Sky Air, VRV, VAM and VKM
RTD-10
Advanced integration into BMS of Sky Air, VRV,
VAM and VKM through either:
- Modbus
- Voltage (0-10V)
- Resistance
Duty/standby function for server rooms
RTD-20
Advanced control of Sky Air, VRV, VAM/VKM
and air curtains
Clone or independent zone control
Increased comfort with integration of CO2 sensor
for fresh air volume control
Save on running costs via
- pre/post and trade mode
- set point limitation
- overall shut down
- PIR sensor for adaptive deadband
RTD-HO
Modbus interface for monitoring and control of
Sky Air, VRV, VAM and VKM
Intelligent hotel room controller
RTD-W
Modbus interface for monitoring and control of
Daikin Altherma Flex Type, VRV HT hydrobox and
small inverter chiller
270
Overview functions
Main functions
RTD-RA
Dimensions
HxWxD
mm
Key card + window contact
Set back function
Prohibit or restrict remote control functions (setpoint limitation, ...)
Modbus (RS485)
Group control
0 - 10 V control
Resistance control
IT application
Heating interlock
Output signal (on/defrost, error)
Retail application
Partitioned room control
Air curtain
RTD-NET
RTD-10
80 x 80 x 37,5
RTD-20
100 x100 x 22
(1)
**
***
***
****
RTD-HO
Control functions
RTD-RA
RTD-NET
RTD-10
RTD-20
RTD-HO
On/Off
Set point
Mode
fan
Louver
HRV Damper control
Prohibit/Restrict functions
Forced thermo off
M,C
M
M
M
M
M
M
M
M
M
M
M
M,V,R
M,V,R
M,V,R
M,V,R
M,V,R
M,V,R
M,V,R
M
M
M
M
M
M
M
M*
M*
M*
M*
M*
M*
RTD-RA
RTD-NET
RTD-10
RTD-20
RTD-HO
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
Monitoring functions
On/Off
Set point
Mode
fan
Louver
RC temperature
RC mode
nbr units
Fault
Fault code
Return air temperature (Average /Min/Max)
Filter alarm
Termo on
Defrost
Coil In/Out temperature
M
M
M
M
M
Main functions
Dimensions
On/off prohibition
Modbus RS485
Dry contact control
Output signal (operation error)
Space heating / cooling operation
Domestic hot water control
Smart Grid control
RTD-W
HxWxD
mm
100x100x22
Control functions
On/Off Space heating/cooling
Set point leaving water temperature (heating / cooling)
Room temperature setpoint
Operation mode
Domestic Hot water ON
Domestic Hot Water reheat
Domestic Hot Water reheat setpoint
Domestic Hot Water storage
Domestic Hot Water Booster setpoint
Quiet mode
Weather dependent setpoint enable
Weather dependent curve shift
Fault/pump info relay choice
Control source prohibition
M,C
M,V
M
M
M,C
M
M,C
M
M
M
Monitoring functions
M,C
M
M
M
M
M
M
M
M
M,C
M
M
M
M
M
M
M
M
M
Control Systems
271
VRV network
DIII- NET
EKMBDXA
HRV
up to 64 units connectable per interface
Split network*
KRP928BB2S
Building
control
network
Fire alarm
Security
Lighting
Pump
* Additional centralized controller might be required. For more information contact your local dealer.
EKMBDXA7V1
Maximum number of connectable indoor units
Maximum number of connectable outdoor units
Communication
DIII-NET - Remark
Protocol - Remark
Protocol - Type
Protocol - Max. Wiring
length
Dimensions
HeightxWidthxDepth
Weight
Ambient temperature - operation
Max.
Min.
Installation
Power supply
Frequency
Voltage
272
64
10
DIII-NET (F1F2)
2 wire; communication speed: 9600 bps or 19200 bps
RS485 (modbus)
m
mm
kg
C
C
Hz
V
500
124x379x87
2.1
60
0
Indoor installation
50
220-240
Elevator
KNX interface
KLIC-DD
KLIC-DI
Concept
light
house
Domotica
shutter control
Controller
tv
Concept
shop
shutter control
Domotica
tv
Controller
Sky Air
Control Systems
3 or 5 + auto
Stop or movement
2 or 3
Stop or movement
2 or 3
Swing or fixed positions (5)
273
BACnet Interface
DMS502A51 / EKACBACMSTP / EKCMBACIP / EKCMBACMSTP
Integrated control system for seamless connection between VRV,
applied systems, air handling units and BMS systems
BMS
VRV network
BACNET / ETHERNET
DIII- NET
DMS502A51
Local Control
VRV Outdoor unit
HRV
up to 256 units connectable per interface
Remote Control
EKACBACMSTP
Serial sequencing
panel
EKCM200J
EKCM200J
EKCM200J
EKDSSP-S
EKCMBACIP
EKCMBACMSTP
Fire alarm
Security
Pump
Lighting
Building
control
network
274
Elevator
LonWorks Interface
DMS504B51 / EKACLONP
Open network integration of VRV and applied systems
monitoring and control functions into LonWorks networks
LON BMS
VRV network
adapter
LonTalk
DIII- NET
ETHERNET (TCP/IP)
DMS504B51
Local Control
VRV
Outdoor
unit
HRV
Remote Control
LonTalk
EKACLONP
Serial sequencing
panel
EKCM200J
EKCM200J
EKCM200J
EKDSSP-S
adapter
LonTalk
LonPoint
LonPoint
Security
Fire alarm
Control Systems
Building
control
network
System
275
Simplified commissioning
The Daikin configurator for Daikin Altherma and
VRV is an advanced software solution that allows for
easy system configuration and commissioning:
276
Simplified
Retrieve initial
commissioning
system settings
277
Control Systems
What is I-Net?
I-Net
performance monitoring
and analysis
24/7
I-Net Services
278
VRV Cloud
The VRV Cloud puts you in the driving seat of your
energy management. The easy-to-use energy data
trending and analytic tools puts you in control and
shows you CO2 footprint reduction opportunities
and energy savings of up to 15%.
Saving starts by measuring. Enhance your companys
sustainability !
Data server
Performance supervision
Internet
and analysis
24/7
Prediction analysis
Data trend logging
Information to:
customers
service company
CLOUD
Controller
Performance monitoring
Daikins unique I-Net Service aims to prevent
the equipment coming to an unexpected stop or
needing emergency repair.
Analysis
Control Systems
279
Room sensors
Rf Receiver
RF sender
Specifications
Dimensions
Weight
Power supply
Battery life
Battery type
Maximum range
Operation range
Communication
mm
g
m
C
Type
Frequency
MHz
Room temperature is sent to the indoor unit every 90 seconds or if the temperature difference is 0.2C or larger.
Specifications
Dimensions (HxW)
Weight
Length of branch wiring
280
mm
g
m
60 x 50
300
12
ADAPTER PCBs
Simple solutions for unique requirements
Concept and benefits
Connectable to:
Split
(E)KRP1B*
adapter for wiring
KRP2A*/KRP4A*
Wiring adapter for
electrical appendices
KRP58M3
SB.KRP58M51
KRP58M51
Sky Air
VRV
Remotely start and stop up to 16 indoor units (1 group) (KRP2A* via P1 P2)
Remotely start and stop up to 128 indoor units (64 groups) (KRP4A* via F1 F2)
Alarm indication/ fire shut down
Remote temperature setpoint adjustment
Cannot be used in combination with a central controller
Low noise and demand control option for RZQG and RZQSG single phase
Includes mounting plate EKMKSA1
Low noise and demand control option for RZQG1 and RZQSG 3 phase
DTA104A*
Outdoor Unit External
Control Adapter
DCS302A52
Unification adapter for
computerized control
KRP928*
Enables unified display (operation/malfunction) and unified control (ON/OFF) from BMS system
Must be used together with Intelligent Touch Controller or intelligent Touch Manager
Cannot be combined with KRP2/4*
Can be used for all VRV indoor models
KRP413*
Wiring adapter normal
open contact / normal
open pulse contact
KRP980*
Adapter for split units
without an S21 port
Control Systems
Some adapters require an installation box, refer to the option lists for more information
Accessories
EKRORO
EKRORO 3
KRC19-26A
BRP2A81
281
AUTO-CLEANING PANEL
FILTERS
INTELLIGENT SENSORS
282
Options &
accessories
284
288
292
294
296
VRV outdoor
VRV indoor
Stylish indoor
Ventilation & Hot Water
Control Systems
283
outdoor
REYQ 14~20T
REMQ5T
2-module systems
3-module systems
BHFQ23P907
BHFQ23P1357
Extended level difference kit - Allows outdoor unit to be more than 50m
above indoor units
Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain
water from all bottom plate outlets into a single outlet. In cold areas should be heated by
a field-supplied heater to prevent drain water from freezing in the drain pan.
Heater tape kit - Optional electrical heater to guarantee trouble-free operation in
extremely cold and humid climates (one per outdoor unit needed)
External control adapter for outdoor unit - Allows to activate Low Noise Operation and
three levels of demand control, limiting power consumption via external dry contacts.
Connects to the F1/F2 communication line and requires power supply from an indoor unit*,
BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating pressures in the
system as Standard, or expansion valve positions and temperature sensor data in a special
service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or one BS-box
of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C
terminals of the outdoor unit / BS-box.
EBRP2B - Cool/heat selector PCB
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560*
Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and
Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKCHSC - Cool/heat selector cable
EKPCCAB3
VRV configurator
BPMKS967A2/A3
Branch provider (for connection of 2/3 RA indoor units)
EKDK04
Drain plug kit
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
DTA109A51
DIII-net expander adapter
EKBPH012T +
EKBHPCBT
EKBPH020T +
EKBHPCBT
EKBPH012T +
EKBHPCBT
DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units
1 kit
per system
1 kit
per system
VRV IV S-series
RXYSCQ-T
RXYSQ4-6TV1
RXYSQ4-6TY1
RXYSQ8-12TY1
Extended level difference kit - Allows outdoor unit to be more than 50m
above indoor units
Central drain pan kit - Installs onto the underside of the outdoor unit and collects drain
water from all bottom plate outlets into a single outlet. In cold areas should be heated by
a field-supplied heater to prevent drain water from freezing in the drain pan.
External control adapter for outdoor unit - Allows to activate Low Noise Operation and
three levels of demand control, limiting power consumption via external dry contacts.
Connects to the F1/F2 communication line and requires power supply from an indoor unit*,
BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating pressures in the
system as Standard, or expansion valve positions and temperature sensor data in a special
service mode. Connect to the outdoor unit PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or one BS-box
of a Heat Recovery system between cooling, heating and fan only. Connects to the A-B-C
terminals of the outdoor unit / BS-box.
EBRP2B - Cool/heat selector PCB
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560*
Cool/heat selector PCB mounting plate (only required when cool/heat selector PCB and
Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKCHSC - Cool/heat selector cable
EKPCCAB3
VRV configurator
BPMKS967A2/A3
Branch provider (for connection of 2/3 RA indoor units)
EKDK04
Drain plug kit
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor units.
DTA109A51
DIII-net expander adapter
284
RYYQ8-12T
RYYQ14-20T
RYMQ8-12T
RYMQ14-20T
BHFQ22P1007
RXYQ8-12T (9)
RXYQ14-20T
BHFQ22P1517
BHFQ22P1007
BHFQ22P1517
EKBPH012T
+ EKBPHPCBT
EKBPH020T
+ EKBPHPCBT
DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units
1 kit
per system
1 kit
per system
1 kit
per system
1 kit
per system
VRV IV i-series
SB.RKXYQ
VRV Classic
RDXYQ5
RKXYQ5
RTSYQ 10PA
RTSYQ 14~16PA
RTSYQ 20PA
RXYCQ8A
RXYCQ10-14A
RXYCQ16-20A
BHFQ22P1007
KWC26B280
KWC26B450
2x KWC26B280
KWC26B160
KWC26B280
KWC26B450
EKDPRH1RDX
BEH22A10Y1L
BEH22A18Y1L
2x BEH22A10Y1L
DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units
285
outdoor
VRV IV-Q Heat Pump Replacement VRV
RQYQ 140P
RXYQQ8-12T
RXYQQ14-20T
2-module systems
3-module systems
BHFQ22P1007
BHFQ22P1517
Central drain pan kit - Installs onto the underside of the outdoor unit and collects
drain water from all bottom plate outlets into a single outlet. In cold areas should
be heated by a field-supplied heater to prevent drain water from freezing in the
drain pan.
KWC26B160
EKBPH012T +
EKBPHPCBT
EKBPH020T +
EKBPHPCBT
External control adapter for outdoor unit - Allows to activate Low Noise
Operation and three levels of demand control, limiting power consumption via
external dry contacts. Connects to the F1/F2 communication line and requires
power supply from an indoor unit*, BSVQ box, or VRV-WIII outdoor unit.
BHGP26A1
Digital pressure gauge kit displays current condensing and evaporating
pressures in the system as Standard, or expansion valve positions and
temperature sensor data in a special service mode. Connect to the outdoor unit
PCB, for installation in the outdoor unit.
KRC19-26A
Mechanical cool/heat selector allows to switch an entire Heat Pump system, or
one BS-box of a Heat Recovery system between cooling, heating and fan only.
Connects to the A-B-C terminals of the outdoor unit / BS-box.
BRP2A81
Cool/heat selector PCB (required to connect KRC19-26A to VRV IV outdoor)
KKSA26A560* - Cool/heat selector PCB mounting plate (only required when cool/
heat selector PCB and Heater tape kit are combined)
KJB111A
Installation box for remote cool/heat selector KRC19-26A
EKPCCAB3
VRV configurator
KKSB2B61*
Demand PCB mounted plate. Needed to mount Demand PCB for some outdoor
units.
DTA109A51
DIII-net expander adapter
Refnet Joints
Capacity index
Capacity index
200 x < 290
290 x < 640
Capacity index
> 640
Capacity index
< 290
Refnet Headers
Capacity index
290 x < 640
KHRQM23M20T
KHRQM23M29T
KHRQM23M64T
KHRQM23M75T
KHRQM23M29H
KHRQM23M64H
KHRQ23M20T
KHRQ23M29T9
KHRQ23M64T
KHRQ23M75T
KHRQ23M29H
KHRQ23M64H
Joint kit
Quiet kit
KHRQM22M20T
KHRQM22M29T
KHRQM22M64T
KHRQM22M75T
KHRQM22M29H
KHRQM22M64H
KHRQ22M20T
KHRQ22M29T9
KHRQ22M64T
KHRQ22M75T
KHRQ22M29H
KHRQ22M64H
Imperial-size connections
Capacity index
< 200
Metric-size connections
286
DTA104A53/61/62
For installation into an indoor unit: exact adapter type depends on type of indoor unit.
See Options & Accessories of indoor units
Metric-size connections
Imperial-size connections
RQEQ 140~212
2-module systems
3-module systems
4-module systems
RWEYQ8-10T8
BHFP26P36C
BHFP26P63C
BHFP26P84C
BHFQ22P1007
BHFQ22P1517
BHFQ23P907
BHFQ23P1357
KWC26B160
DTA104A53/61/62
Installation in the RWEYQ outdoor unit possible. For installation in indoor units, use appropriate type (DTA104A53/61/62) for particular indoor unit. See Options & Accessories of indoor units
Capacity index
> 640
1-port
-
1-port
-
4-port
-
KHRQM23M75H
KHRQ23M75H
BS1Q-A
BSVQ-P8B
BS4Q14A
BSV4Q100PV
EKBSVQLNP
EKBSVQLNP
KRC19-26
10-port
-
12-port
-
16-port
-
BS6Q14A
BSV6Q100PV
BS8Q14A
BS10Q14A
BS12Q14A
BS16Q14A
KRC19-26
1 kit per port
necessary
KRC19-26
1 kit per port
necessary
KJB111A
KJB111A
KJB111A
KHFP26A100C
KHFP26A100C
KHFP26A100C
KHFP26A100C
KHFP26A100C
KHFP26A100C
KHRP26A1250C
KHRP26A1250C
KHRP26A1250C
KHRP26A1250C
KHRP26A1250C
KHRP26A1250C
KDDN26A4
KDDN26A8
KDDN26A8
KDDN26A12
KDDN26A12
KDDN26A16
KHRQM22M75H
KHRQ22M75H
287
indoor
Ceiling mounted cassette units
Round flow
(800x800)
FXFQ 20~125A
BRC1E52A/B
Premium wired remote control with full-text interface and
back-light
BRC1D52
Standard wired remote control with weekly timer
BRC2E52C
Simplified wired remote control for heat recovery system
BRC3E52C
Simplified wired remote control for heat pump system
DCS302C51
Central remote control
DCS301B51
Unified ON/OFF control
DST301B51
Schedule timer
DCC601A51
Adapters and control
2-way blow
FXZQ 15~50A
FXCQ 20~40A
FXCQ 50~63A
FXCQ 80 ~125A
*4
*4
*4
*4
*4
BRC7FA532F
BRC7F530W *9*10
(white panel)
BRC7F530S *9*10
(grey panel)
BRC7EB530 *9*10
(standard panel)
BRC7C52
BRC7C52
BRC7C52
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
K.RSS
External wireless temperature sensor
KRP4A53 *2*7
KRP4A53 *2
KRP4A51
KRP4A51
KRP4A51
KRP2A52
KRP2A51
KRP2A51
KRP2A51
EKRP1C11 *2*7
EKRP1B2
EKRP1B2
EKRP1B2
EKRP1B2
KRP1B57 *2*7
KRP1B57
DTA114A61
DTA114A61
DTA104A61
DTA104A61
DTA104A61
KRP1H98 *7
KRP1A101
KRP1C96
KRP1C96
KRP1C96
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
KJB212A
Electrical box with earth terminal (2 blocks)
KJB311A
Electrical box with earth terminal (3 blocks)
KJB411A
Electrical box with earth terminal
BRP7A51 *2/11
Digital input adaptor
BYBCQ40H
BYBCQ63H
BYBCQ125H
Decoration panel
(obligatory for cassette units, optional for others, rear panel for FXLQ)
Kit for mounting of decoration panel direct onto unit
KDBQ44B60
(Standard panel)
KDBHQ55B140 *7
KDDQ55B140-1 +
KDDQ55B140-2 *7*8
KDDQ44XA60
KDDFP53B50
KDDFP53B80
KDDFP53B160
KAFP551K160
KAFQ441BA60
KAFP531B50
KAFP531B80
KAFP531B160
Standard
Standard
Standard
Standard
Standard
BRYQ140A
4-way (600x600)
288
indoor
Slim
Standard
FXKQ 25~40
FXKQ 63
FXDQ 20~25 M9
FXDQ 15~63A
FXSQ 15~32
FXSQ 40~50
FXSQ 63~80
FXSQ 100~125
FXSQ 140
*4
*4
*4
*4
*4
*4
*4
*4
*4
BRC4C61
BRC4C61
BRC4C62
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC4C65
KRCS01-1
KRCS01-1
KRCS01-1
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRP4A51
KRP4A51
KRP4A51
KRP4A54
KRP4A52*2
KRP4A52*2
KRP4A52*2
KRP4A52*2
KRP4A52*2
KRP2A51
KRP2A51
KRP2A51
KRP2A53
KRP2A51*2
KRP2A51*2
KRP2A51*2
KRP2A51*2
KRP2A51*2
KRP1B61
KRP1B61
EKRP1B2
KRP1B56
EKRP1B2*2
EKRP1B2*2
EKRP1B2*2
EKRP1B2*2
EKRP1B2*2
EKMTAC
DTA114A61
DTA114A61
DTA114A61
DTA114A61
DTA114A61
DTA114A61
DTA104A61
DTA104A61
DTA104A61
DTA104A53
DTA104A61
DTA104A61
DTA104A61
DTA104A61
DTA104A61
KRP1B101
KRP1BA101/
KRP1B100
KRP1BA101/
KRP1B100
KRP1BA101/
KRP1B100
KRP1BA101/
KRP1B100
KRP1BA101/
KRP1B100
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
BYK45F
BYK71F
KDAP25A36A
KDAP25A56A
KDAP25A71A
KDAP25A140A
Standard
Standard
KDAJ25K56
Standard
Standard
Standard
Standard
Standard
Standard
289
BRC1E52A/B
Premium wired remote control with full-text interface and back-light
BRC1D52
Standard wired remote control with weekly timer
Infrared remote control including receiver
BRC2E52C
Simplified wired remote control for heat recovery system
BRC3E52C
Simplified wired remote control for heat pump system
DCS302C51
Central remote control
DCS301B51
Unified ON/OFF control
DCS601C51
Schedule timer
DCC601A51
Centralized controller with cloud connection
DCM601A51
Intelligent Touch Controller
External wired temperature sensor
Large
FXTQ50~63
FXTQ80~100
*4
*4
*4
*4
*4
BRC4C65
BRC4C65
BRC4C65
BRC4C65
BRC4C65
KRCS01-4
KRCS01-4
KRCS01-1
KRCS01-4
KRCS01-1
Wiring adapter for external monitoring/control via dry contacts and setpoint
control via 0-140
KRP4A51
KRP4A51
KRP4A51
KRP4A52 *2
KRP4A51
KRP2A51
KRP2A51
KRP2A51
KRP2A51 *2
KRP2A51
EKRP1B2
EKRP1B2
KRP1B61
EKRP1B2 *2
KRP1B61
K.RSS
External wireless temperature sensor
Others
FXMQ 200~250
DTA114A61
DTA114A61
DTA114A61
DTA104A61
DTA104A61
DTA104A61
DTA104A61
DTA104A61
KRP4A96
KRP4A96
KRP1BA101 / KRP1B100
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
KJB212A
Electrical box with earth terminal (2 blocks)
KJB311A
Electrical box with earth terminal (3 blocks)
KJB411A
Electrical box with earth terminal
BRP7A51 *2 / 11
Digital input adaptor
Decoration panel
(obligatory for cassette units, optional for others, rear panel for FXLQ)
KDAJ25K71
KDAJ25K140
KDAP25A140A
Standard
Standard
Standard
Sensor kit
KEK26-1
Noise filter (for electromagnetic use only)
290
1-way blow
FXHQ 63A
FXHQ 71~100A
4-way blow
FXUQ 71~100A
FXAQ 15~63
Concealed
FXNQ 20~63
FXLQ 20~25
Free-standing
FXLQ 32~40
FXLQ 50~63
*4
*4
*4
*4
*4
*4
*4
*4
*4
BRC7G53
BRC7G53
BRC7G53
BRC7C58
BRC7EB518
BRC4C65
BRC4C65
BRC4C65
BRC4C65
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-4
KRCS01-1
KRSC01-4
KRCS01-1
KRCS01-1
KRCS01-1
KRP4A52
KRP4A52
KRP4A52
KRP4A53 *2
KRP4A51
KRP4A54
KRP4A51
KRP4A51
KRP4A51
KRP2A62
KRP2A62
KRP2A62
KRP2A51
KRP2A53
KRP2A51
KRP2A51
KRP2A51
KRP1B56
KRP1B61
KRP1B61
KRP1B61
KRP1B54
KRP1B54
KRP1B54
DTA114A61
DTA114A61
EKMTAC
EKMTAC
EKMTAC
DTA104A62
DTA104A62
DTA104A62
DTA104A61
KRP1D93A
KRP1D93A
KRP1D93A
KRP1B97
KRP4A93
EKRORO4
EKRORO4
EKRORO4
EKRORO5
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
EKRDP25A
EKRDP40A
EKRDP63A
KDBHP49B140
KDBTP49B140
KDDQ50A140
KDDQ50A140
KDDQ50A140
KAFP501A56
KAFP501A80
KAFP501A160
KAFP551K160
KDU50P60
KDU50P140
KDU50P140
K-KDU572EVE
KHFP5M35
KHFP5N63
KHFP5N160
HXY080-1258
HXHD1258
EKHBDPCA2
EKRP1HBAA
EKRP1AHTA
EKRUAHTB
EKBUHAA6(W1/V3)
EKRTWA
EKRTR1
EKRTETS
EKHTS200AC
EKHTS260AC
EKHWP500B
EKSV26P (vertical) EKSH26P (horizontal)
EKSRPS
Drain pan
Digital I/O PCB
Demand PCB - Required to connect room thermostat
Remote user interface (remocon) - Same controller as supplied with cascade unit
can be mounted parallel or on other location. If 2 controllers are installed, the
installer needs to select 1 master & 1 slave
Back-up heater
Wired room thermostat - Requires demand PCB EKRP1AHTA
Wireless room thermostat - Requires demand PCB EKRP1AHTA
Remote sensor for room thermostat - Requires demand PCB EKRP1AHTA
FXHQ 32A
291
FTXG-LW/S
CTXS15-35K
FTXS20-25K
FTXS35-50K
FTXS-G
FVXG-K
FVXS-F
FDXS-F(9)
FLXS-B(9)
BRC073 (3)
BRC073 (3)
BRC073 (3)
BRC073 (3)
BRC073 (3)
BRC073 (3)
BRC1D52
BRC1E52A
BRC1E52B (4)
BRC073 (3)
BRC4C65
BRC2E52C
BRC3E52C
BRCW901A03
BRCW901A03
BRCW901A03
BRCW901A03
BRCW901A03
BRCW901A03
BRCW901A03
BRCW901A08
BRCW901A08
BRCW901A08
BRCW901A08
BRCW901A08
BRCW901A08
BRCW901A08
BRP7A54
KRP413A1S (1)
KRP413A1S (1)
KRP413A1S (1)
KRP413A1S (1)
KRP413A1S (1)
KRP413A1S (1)
KRC72 (2)
KRC72 (2)
KRC72 (2)
KRC72 (2)
KRC72 (2)
KRC72 (2)
KRC72 (2)
KKF910A4
KKF910A4
KKF910A4
KKF910A4
KKF910A4
KKF917AA4
KRP980A1
KRP4A54
Remote sensor
KRCS01-4
KRP1BA101
KJB311A
KJB212A
KRP928A2S
KRP928A2S (5)
KRP928A2S (5)
KRP928A2S
KRP928A2S
KRP928A2S
KRP928A2S
Online controller
standard (6)
BRP069A43
BRP06942
BRP069A42
BRP069A42
BRP069A42
BRP069A42
Modbus gateway
RTD-RA
RTD-RA (5)
RTD-RA
RTD-RA
RTD-RA
RTD-RA
RTD-NET
KNX gateway
KLIC-DD
KLIC-DD (5)
KLIC-DD
KLIC-DD
KLIC-DD
KLIC-DD
KLIC-DI
KLIC-DD
BKS028
Installation leg
- The BYCQ140DW has white insulations. Be informed that dirt is more visible on white insulation and that it is consequently not advised to install the BYCQ140DW decoration panel in environments
- To be able to control BYCQ140D/W/DG(F), the controller BRC1E is needed and cannot be combined with VRV IV S-series outdoor units.
Notes:
(1) Wiring adapter supplied by Daikin. Time clock and other devices : to be purchased locally;
(2) Wiring adapter is also required for each indoor unit;
(3) Cord for wired remote control BRCW901A03 or BRCW901A08 required;
(4) Standard there is no remote control delivered with this indoor unit. Wired or wireless control to be ordered separately;
(5) Interface adapter KRP980A1 required;
(6) No option needed, functionality is included with the product
(7) Option not available in combination with BYCQ140D*G*;
(8) Both parts of the fresh air intake are needed for each unit;
(9) This option is intended exlusively for usage in fine dust environments (clothing shops). Do not use this option in high humidity and/or greasy environments.;
(10) Installation box for adapter PCB is necessary;
(11) Option not available in combination with BYCQ140*G;
(12) Electrical heater, humidifier and hour meter are field supply. These parts should not be installed inside the equipment;
(13) Sensing function is not available;
(14) Independently controllable flaps function is not available;
(15) With the infrared remote control, the individual flap control and automatic air volume control cannot be controlled;
(16) Including following languages: pack 1: English, German, French, Dutch, Spanish, Italian, Portuguese with PC cable EKPCCAB3 in combination with the Updater PC software, you can additionally change
the language to : language pack 2: English, Bulgarian, Croatian, Czech, Hungarian, Romanian and Slovenian. Language pack 3: English, Greek, Polish, Russian, Serbian, Slovak and Turkish;
(17) These options require mounting plate KRP4A96, maximally 2 optional PCBs can be mounted;
(18) When installing electrical heaters, an optional PCB for external electric heaters EKRP1B2A is required for each indoor unit;
(19) For directly mounting the decoration panel on the unit, decoration panel option EKBYBSD is required.
292
FCQHG-F
FCQG-F
FFQ-C
FDBQ-B
FBQ-D
FHQ-C
BRC1D52
BRC1E53A/B/C (16)
BRC1D52
BRC1E53A/B/C (16)
BRC1D528
BRC1E53A/B/C (16)
BRC1D52
BRC1E53A/B/C (16)
BRC1D52
BRC1E53A/B/C (16)
BRC1D52
BRC1E53A/B/C (16)
BRC2E52C
Simplified remote control (with operation
mode selector button)
BRC3E52C
Simplified remote control (without operation
mode selector button)
DCM601A5A
Intelligent touch manager
BRC4C65
BRC7G53
DCS302C51
Centralised remote control
DCS301B51
Unified ON/OFF control
DST301B51
Schedule timer
DCC601A51
Centralised controller with cloud connection
Wired remote control
KRP1BA59
KRP1B57 (11)
KRP4A53 (11)
KRP1B57
KRP4A53 (11)
KRP1B57
KRP4A53 (11)
KRP4A52 (18)
KRP2A51 (18)
KRP1B54
KRP4A52 (10)
EKRP1C11 (11)
EKRP1C11 (11)
EKRP1B2 (17)
EKRP1B2 (17)
KRP1H98 (11)
KRP1H98 (11)
KRP1B101
KRP1BA101
KRP1B101
KRP1BA101
KRP1D93A
BRP7A53
BRP7A53
BRP7A53
BRP7A54
BRP7A51 (17)
BRP7A52
EKRP1B2A
Options PCB for external electrical heater,
humidifier and/or hour meter (12)
KKSAP50A56 (35-50)
KRCS01-4
Remote sensor
EKRORO4
KJB311A
Electrical box with earth terminal (3 blocks)
KJB212A
Electrical box with earth terminal (2 blocks)
KJB411A
Electrical box with earth terminal
DTA112B51
Interface adapter for Sky Air
Installation box for adapter PCB
Digital input adapter (10) (17) (18)
Sealing member
of air discharge outlet
Decoration panel for air discharge
KAFP551K160
KAFP551K160
KAFQ441BA60
KAFP501A56
(35-50 class)
KAFP501A80
(60-71 class)
KAFP501A160
(100-125 class)
Standard
Standard
Standard
Standard
KDU50P60
(35-60 class)
KDU50P140
(71-125 class)
KHFP5M35
(35 class)
KHFP5N63
(50-60 class)
KHFP5N160
(71-125 class)
KDBHQ55B140 (19)
KDBHQ55B140 (19)
BDBHQ44C60
BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (9)
BYCQ140D
BYCQ140DW
BYCQ140DG
BYCQ140DGF (9)
BYFQ60B3
BYFQ60C2W1W
BYFQ60C2W1S
KDDQ55B140-1 (7)(8)
+
KDDQ55B140-2 (7)(8)
KDDQ55B140-1 (7)(8)
+
KDDQ55B140-2 (7)(8)
KDDQ44XA60
KDDQ50A140
Panel spacer
KDBQ44B60
Decoration panel
Sensor kit
BRYQ140A
BRYQ140A
BRYQ60A2W
BRYQ60A2S
Noise filter
293
Dust filters
VAM
150FC
VAM
250FC
VAM
350FC
VAM
500FC
VAM
650FC
VAM
800FC
VAM
1000FC
EN779 Medium M6
EKAFV50F6
EKAFV50F6
EKAFV80F6
EKAFV80F6
EN779 Fine F7
EKAFV50F7
EKAFV50F7
EKAFV80F7
EKAFV80F7
EN779 Fine F8
EKAFV50F8
EKAFV50F8
EKAFV80F8
EKAFV80F8
Model name
KDDM24B50
KDDM24B100 KDDM24B100
x2
x2
Nominal pipe
Diameter (mm)
200
200
BRYMA65
BRYMA65
BRYMA65
VH1B
VH2B
VH2B
VH3B
VH3B
Silencer
CO2 sensor
VH electrical heater for VAM
VAM
1500FC
VAM
2000FC
VKM
VKM
VKM
50GB(M) 80GB(M) 100GB(M)
KDDM24B100 KDDM24B100
250
250
250
250
250
250
BRYMA100
BRYMA100
BRYMA200
BRYMA200
BRYMA65
BRYMA100
BRYMA200
VH5B
VH5B
VAM-FC
VKM-GB(M)
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52
BRC1E52A/B / BRC1D52 1
BRC1E52A/B / BRC1D52 1
BRC301B61
VAM-FC
VKM-GB(M)
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
DCS302C51
DCS302C51
DCS301B51
DCS301B51
Schedule timer
DST301B51
DST301B51
DCC601A51
DCC601A51
DCC601A51
DCM601A51
DCM601A51
DCM601A51
DCM601A51
DCM601A51
EKMBDXA7V1
EKMBDXA7V1
EKMBDXA7V1
EKMBDXA7V1
EKMBDXA7V1
BACnet interface
DMS502A51
DMS502A51
LonWorks interface
DMS504B51
DMS504B51
VAM150-250FC
VAM350-2000FC
VKM-GB(M)
EKEQFCBA 2
EKEQDCB 2
EKEQMCBA 2
Others
KRP2A51
KRP2A51 (note 3)
KRP50-2
BRP4A50
KRCS01-1
Remote sensor
Notes
LED indicators
Power ON - Yellow
Heater ON - Red (solid or flashing, indicating pulsed control)
Airflow fault - Red
Mounting holes
Maximum ambient adjacent to terminal box
Auto high temp. cutout
Man. reset high temp. cutout
Run relay
BMS setpoint input
294
kW
mm
vH1B
VH2B
VH3B
VH4B
VH4/AB
VH5B
1
100
VAM150FC
-
1
150
VAM250FC
VAM350FC
1
200
VAM500FC
VAM650FC
1.5
250
VAM800FC
VAM1000FC
2.5
250
VAM800FC
VAM1000FC
2.5
350
VAM1500FC
VAM2000FC
D-AHU Professional
Construction type
Aluminium
Profile
Panel insulation
FP 50
FP 25
standard
standard
Anodized aluminium
option
option
option
option
option
option
option
option
option
option
option
option
standard
standard
standard
standard
standard
standard
standard
standard
option
option
option
option
standard
External sheet
material
SP 45
standard
Corner
SP 65
standard
standard
standard
standard
option
option
option
option
Galvanized steel
option
option
option
option
Aluminium
option
option
option
option
option
option
option
option
standard
standard
standard
standard
option
option
option
option
option
option
option
option
Galvanized steel
Pre-coated galvanized steel
Internal sheet material Grey Plastisol covered galvanized steel
Aluminium
AISI 304 stainless steel
Aluminium
Base frame
Galvanized steel
Handle
Type
Compression type
option
option
option
option
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
option
standard
(from size 1 to size 17)
standard
(from size 18 to size 27)
standard
standard
standard
standard
standard
option
option
option
option
D-AHU Easy
Aluminium
Corner
Panel insulation
DS 50
DS 25
Standard
Standard
Standard
Standard
Standard
Standard
Galvanized steel
Standard
Standard
Base frame
Aluminium
Standard
Standard
Handle
Standard
Standard
Type
Compression type
Standard
Standard
Construction type
Profile
295
DCC601A51
Options for local control
Cloud options
Software
Z380C
4G-N12
DCC001A51
DCC002A51
DCC003A51
DCC004A51
App for tablet Application to run on Z380C tablet (download from Play
store, Android only)
Commisioning tool
Software update tool
DCM601A52
DCM002A51
DCM008A51
DCM009A51
296
KRP928A2S
DTA102A52
DTA112B51
DAM411B51
DAM412B51
DMS504B51
DMS502A51
LonWorks Interface
BACnet Interface
Power supply
T1
V1
VE
V3
VM
W1
Y1
=
=
=
=
=
=
=
Conversion table
refrigerant piping
inch
1
/4
3
/8
1
/2
5
/8
3
/4
7
/8
1 1/8
1 3/8
1 5/8
1 3/4
2
2 1/8
2 5/8
mm
6.4 mm
9.5 mm
12.7 mm
15.9 mm
19.1 mm
22.2 mm
28.5 mm
34.9 mm
41.3 mm
44.5 mm
50.8 mm
54 mm
66.7 mm
F-gas regulation
For fully/partially charged equipment: contains fluorinated greenhouse gases. Actual refrigerant charge depends on the final unit
construction, details can be found on the unit labels.
For non pre-charged equipment (Chillers: split chiller (SEHVX/SERHQ), condensing units and condenserless chillers + refrigeration
(LCBKQ-AV1, JEHCCU/JEHSCU and ICU): Its functioning relies on fluorinated greenhouse gases.
Measuring conditions
Air conditioning
1) Nominal cooling capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference
2) Nominal heating capacities are based on:
Indoor temperature
Outdoor temperature
Refrigerant piping length
Level difference
27CDB/19CWB
35CDB
7.5m - 8/5m VRV
0m
20CDB
7CDB/6CWB
7.5m - 8/5m VRV
0m
The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value,
depending on the distance and acoustic environment (for measuring conditions: please refer to the technical databooks).
The sound power level is an absolute value indicating the power which a sound source generates.
For more detailed information please consult our technical databooks.
297
http://literature.daikinpromoshop.eu
General catalogue
2016
-45C
298
0C
80C
Tools and
platforms
299
Reference
books:
Product
profiles:
VRV IV range
VRV IV
360 efficiency
VRV IV i-series
Keep looking
youll never find me
Main benefits,
application examples
and specs of VRV IV
i-series product range
16-207
VRV IV S-series
15-206
Keep looking
youll never find me
16-209
Main benefits,
application examples
and specs of VRV IV
S-series product range
16-208
for installers
Technical cooling
RELIABLE,
C
Replacement
technology
Replacement
Technology
The quick and quality way of upgrading R-22 and R-407C systems
Product
flyers:
Real time clock
Other features
Backlight display
User friendly
remote control
with contemporary
design
Specifications / Functions
Specifications
BRC1E52A / BRC1E52B
Dimensions (HxWxD)
3.120x120x19 mm40
Display size (HxW)
LCD
43.2x68.85 mm
Type
Colour
Fresh white
No
500m
Functions
BRC1E52A / BRC1E52B
Set sensor behavior
Energy saving
functions
Setback function
Detailed info on
BRC1E52A/B remote
control
Modbus
Interface
RTD
English, German, Czech, Croation, Hungarian, Romanian, Slovenian, Bulgarian, Slovak, Serbian, Albanian
Backlight
Contrast adjustment
Holiday function
Key lock
Restrict buttons
Built-in back-up power
16-140
15-214
English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, Polishr
Help menu
Timer
BRC1E52A/B
Display
Infrastructure
cooling solution
TINUOUS O
ON
RATION
PE
Focus
topics:
Naamloze Vennootschap Zandvoordestraat 300 8400 Oostende Belgium www.daikin.eu BE 0412 120 336 RPR Oostende (Responsible Editor)
FSC
ECPEN15 - 306
180 11/14
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from
or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V.
Product
catalogues:
15-306
VRV Catalogue
Detailed technical
information & benefits
on Sky Air/Ventilation/
Biddle Air Curtain/Control
systems/AHU
Retail applications
Hotel applications
IT applications
Heating interlock
Alarm signal
Detailed technical
information & benefits of
the VRV total solution
VRV
Product catalogue 2016
for professionals
15-308
Ventilation Catalogue
Ventilation
Product catalogue 2016
for professionals
Detailed info on
Ventilation products
Full
LIBRA
OF BIM RY
OBJEC
TS
FOR
Product
portfolios:
16-100
Product portfolio
Sky Air
VRV
16-200
VRV
Product Portfolio
Controls
16-203
Controls systems
portfolio
22
16-101
300
16-201
15-301
Commercial Solutions
Commercial solutions
for small to large applications
Green building
solutions
15-216
15-100
Sustainable design
with Daikin HVAC-R systems
Reference
catalogue
Hotel Solutions
Daikin commercial
and industrial
references
Hotel solutions
for hotel owners
14-213
Intelligent Touch
Manager
15-302
Act now!
tablet
Detailed benefits of
Intelligent Touch Manager
intelligent
Tablet Controller
DCC601A51
16-303
Replacement technology
15-215
Powerful mode
Concealed
ceiling unit
with medium
ESP
FBQ-D, FXSQ-A
Home leave
Home leave
operation
operation
Powerful mode
Multi tenant
(FXNQ-A)
16-110
16-106
16-101
Technical documentation:
All latest Daikin catalogues are available in
a convenient library on the internet:
www.daikineurope.com/support-and-manuals/catalogues
301
Concealed
floor standing
unit
Supporting
www.daikineurope.com/
support-and-manuals/
software-downloads
Software
Solutions seasonal simulator, simulate
& compare
With this software tool you can simulate and
the seasonal efficiency, the annual power
consumption and CO2 emission for a given climate,
load profile (cooling, heating, heat recovery,
covalent, bivalent...) and combination of systems.
With its intuitive and graphical appealing interface,
a simulation, comparison and ROI calculation can be
made in a matter of minutes.
joints
Automatic generation of wiring diagram
Select possible centralised control systems
Visualise result in MS Word, MS Excel and AutoCAD
Ventilation Xpress
Selection tool for ventilation devices (VAM, VKM).
The selection is based on given supply/extract
airflows (including fresh up), and given ESP of
the supply/extract ducting:
Supporting tools
NEW Building Information Modelling
http://bimobject.
com/en/
product/
?freetext=daikin
(BIM) support
2D floorplan
Improves efficiency and reduces time being spent
on the project.
Calculation of correct pipe diameters and refnets
302
https://my.daikin.
eu/content/denv/
en_US/home/
applications/
software-finder/
vrvcad.html
Online support
Internet
my.daikin.eu
AT
C U S TO M E
ON
THE
R OA D
RS
Technical
Restaurant
Hotel
Store &
shop
Home
Bank
Office
Industry
Sport &
Leisure
www.daikineurope.com/
commercial/applications
www.daikineurope.com/
industrial/applications
See our references
AT THE OFFICE
www.daikineurope.com/references
303
Over 30 years of
VRV History
1987
1998
2004
2008
1987
1991
1994
1998
2003
2004
2005
2003
1991
Introduce VRV heat
recovery
Simultaneous cooling and
heating
304
1994
Awarded ISO9001 certification
2005
Extends VRVII inverter
range with water cooled
VRV-WIII
Available in heat pump and
heat recovery
2006-20
2008
2011
2009
2010
2011
2015
2012
2015
2006-2007
Launch the extensively
re-engineered VRVIII
Available in cooling, heat
pump and heat recovery
Automatic charging and
testing
Up to 64 units
connected to 1 system
2010
Launch of replacement VRV
(VRVIII-Q)
Upgrade to replace older VRV units
using R-22 refrigerant
2012-2014
Setting new standards with the
launch of VRV IV
28% improved seasonal efficiency
Continuous heating on heat pumps
Available in heat pump, heat
recovery, water-cooled and
replacement series
2015
Launch of VRV IV i-series
305
007
2009
Development
Product Development Group
IT
Solution Product
Development Center
Development
Environmental Technology
Research laboratory
Environment
Five-year results for the environmental
action plan 2010
Under the five-year FUSION 10 strategic management plan,
which targeted fiscal year 2010, the Daikin Group strove to
develop and promote the use of environmentally conscious
products and services on a basic policy of actively contributing
to solving global environmental problems and expanding
business. Our environmental measures were conducted under
our Environmental Action Plan 2010.
Europe
Fifteen-fold increase in heat-pump hot water and space
heating
We have successfully promoted the use of the Daikin Altherma
hot water and space heating system in the process contributing
to the reduction of 210,000 tons of CO2 emissions.
Proliferating results
in Europe
Reduction of
210,000 tons of
CO2 emissions
compared
to using
combustiontype heaters
15 times
2006
2010
HEAT PUMP
HEATERS 4%
FY 2010
FY
307
Keep looking
youll never find me
i
Find out more at www.daikineurope.com/citysecret
Daikin Europe N.V. Naamloze Vennootschap Zandvoordestraat 300 8400 Oostende Belgium www.daikin.eu BE 0412 120 336 RPR Oostende (Responsible Editor)
Daikin Europe N.V. participates in the Eurovent Certification
programme for Liquid Chilling Packages (LCP), Air handling
units (AHU), Fan coil units (FCU) and variable refrigerant flow
systems (VRF) Check ongoing validity of certificate online:
www.eurovent-certification.com or using: www.certiflash.com
ECPEN16-200
xxx 01/16
The present publication is drawn up by way of information only and does not constitute an offer binding upon
Daikin Europe N.V. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No
express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its
content and the products and services presented therein. Specifications are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from