Protection Coordination Report

for
Raw Water Pump House and River Water
Intake Pump House
Client

THE WEST BENGAL POWER DEVELOPMENT


CORPORATION LIMITED

Consultant

DEVELOPMENT CONSULTANTS PVT LTD


Project

SAGARDIGHI THERMAL POWER PROJECT


UNIT 3 & 4 ( 2 X 500 MW) PHASE -II
PLANT WATER SYSTEM (SGPWS-2)
Contractor

L&T Construction
Water & Renewable Energy
L&T DOCUMENTS NO::LT-DG-LE130733-1-E510 REV B ( FOR INTAKE SYSTEM)
LT-DG-LE130733-3-ES513 REV B ( FOR RWPH SYSTEM)

Compiled by
C B Ramesh, Chennai.
9884370326,

Contents

Sl.No

Descriptiion

Page No

Reference Documents River water intake Pump House

Setting calculations for Motor feeders-River water intake Pump House

Setting calculations for Transformer Feeders -River water intake Pump House

Setting calculations for Incomers-River water intake Pump House

10

Single Line Diagram- River Water Intake Pump House

13

Short Circuit Reports-River water Intake Pump House

15

Setting for 11 kV Switch Boards River Water Intake Pump House

20

Setting for 3.3 kV Switch Boards River Water Intake Pump House

35

Setting for 415 V PMCC River Water Intake Pump House

48

10

Time Current Characteristic Curves_ River Water Intake Pump House

54

11

Reference Documents Raw Water Pump House

60

12

Setting calculations for Motor feeders- Raw Water Pump House

62

13

Setting calculations for Transformer Feeders - Raw Water Pump House

64

14

Setting calculations for Incomers- Raw Water Pump House

67

15

Single Line Diagram-Raw Water Pump House

70

16

Short Circuit Reports-Raw Water Pump House

72

17

Setting for 11 kV Switch Board Raw Water Pump House

79

18

Setting for 415 V PMCC Raw Water Pump House

95

19

Setting for 415 V DM PLANT Raw Water Pump House

102

20

Time Current Characteristic Curves_ RAW Water Pump House

106

REFERENCE DOCUMENTS

Reference Documents / Drawings- River Water Intake Pump House


Sl.No

Drawing Title

File reference

Drawing No

SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE

PDF file -LT-DC-LE130733-1-E402-REV 3.3kV.pdf

LT/DC/LE130733/1/E402/REV D/SHEET 2 OF 3
revision D

SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE

PDF file -LT-DC-LE130733-1-E402-REV D LT.pdf

LT/DC/LE130733/1/E402/REV D/SHEET 3 OF 3
revision D

SINGLE LINE DIAGRAM FOR CONTROL METERING & PROTECTION DIAGRAM OF 11kV,3.3kV
AND 415 V SYSTEMS FOR RIVER WATER INTAKE PUMP HOUSE

PDF file -LT-DC-LE130733-1-E402-REV D 11kV.pdf

LT/DC/LE130733/1/E402/REV D/SHEET 1 OF 3
revision D

3.3 kV Switch Board

Pdf file "IntakePH 3.3kV HT Panel Latest.pdf"

(3) G71550-E8172-U001- C issue C

11 kV Switch Board

Pdf file "IntakePH 11kV HT Panel Latest.pdf"

09041-E-BM-CS-DD-0217,sh1-sh175

General Notes on 11 kV and 3.3 kV switch Boards

Pdf file "LT-DG-LE130733-1-E428 & E431.pdf"

SLEF504 sh1-sh24 revision D

General Notes on 415 V PMCCs

Pdf file "LT-DG-LE130733-3-E448.pdf"

SLEE792 sh1-sh19 revision C

GA and Schematic diagram of LT Switchgear Panel at River water intake System

Pdf file "IntakePH LT Scheme.pdf"

LT/DG/LE130733/1/E481/REVD-revision D

Technical Data sheet for 500 kW ,6 pole,3.3kV Vertical Intake Electrical Motor
Characteristic curves of 500 kW , 6pole,3.3kV Vertical Intake Electrical Motor

Pdf file "500kW Motor Datasheet.pdf"


Pdf file"500kW Motor GA dwg.pdf"

L&T doc No LT-DG-LE130733-3-E517 rev 0


L&T doc No LT-DG-LE130733-3-E516 Rev 02

10

SETTING CALCULATIONS FOR MOTOR FEEDERS

Sample Calculations for Relay settings for Motor Feeder


1. Available motor data
500 kW
Sl No
Size
1.01 Power
1.02 Rated voltage
1.03 Motor rated current I A
1.04 Max. starting current (at 100 % Vn)
1.04 Max. starting current (at 80 % Vn)
1.05 Starting time (at 100% Vn
1.06 Starting time (at 80% Vn
1.06 Heating time constant
1.07 Cooling time constant at standstill
1.08 Max. continuous thermal rating current
1.09 Max. blocked rotor time
1.10 Locked rotor Current
1.11 Permissible max.withstanding time ( hot )
1.12 Permissible max.withstanding time ( Cold)
2. General power system data
Parameter
2.01 CurrentTransformer rated current,phase primary
2.02 Transformer rated current, phase secondary
Sample Calculations
Fulload current of Motor I A
CT secondary current corresponding to full load current

Value
500
3300
111.5
4.5 x IA
4.8X IA
1.6
2.9
30
180
117.08
12
501.75
12
15
Value

units
kW
V
A

sec
sec
min
min
A
sec
A
sec
sec

Units
160 A
1A
111.5 A

IA x CT ratio
111.5 x 1/160

Maximum Thermal current 5% more than the full load current


CT secondary current corresponding to Thermal Current
Max. starting current (at 100 % Vn)
Starting Current
CT secondary current corresponding to Starting Current
Over current setting is 10 % more than the full load current
CT secondary current corresponding to Over current
Rounded of to
High set current I>> is normally set 1.3 times the starting current
CT secondary current corresponding to High set Over current I>>
Rounded off to

0.70 A
111.5 x 105/100
117.08 A
117.5 x 1/160
0.73 A
4.5X IA
=4.5 x111.5
501.75 A
=501.75x1 / 160
3.14 A
=111.5 x 110 / 100
122.65 A
=122.65x1/160
0.77
0.77
= 1.3 x501.75
652.275 A
=652 x1/160
6.52
6.5 A

SETTING CALCULATIONS FOR TRANSFORMER FEEDERS

5
7

Setting Calculation for Distribution Transformers TR3 & TR4 in River water Intake Power house

11 kV

3450 V
100/1A

400 /1A

1500 kVA
Transformer capacity

PT

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 3.3 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

1500

11
3.45
100/1
CTRP 100
400/1
CTRS 400
Z
6.25%
7488
4634
78.73
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 78.73/0.95
91.16
Transformer HV side CT Secondary Pick up Current
Isfl
0.91
IDMT setting at 11 kV side
0.91
Setting proposed on HV side Ip
0.9
Curve
Normal Inverse
Transformer LV side current as per name plate
251.00
Relay drop off Ratio
0.95
LV Pick up Current
1.1 x LV Currrent/ Drop off ratio
=1.1 x 251/0.95
290.63
Transformer LV side CT Secondary Pick up Current
=290.63/400
Relay setting for over current
0.726578947
Setting proposed on LV side Ip
0.7
Curve
Normal Inverse
Fault current at 3.3kV Bus as per report,for MINIMUM SOURCE Fault
4634.00
HV side current due to fault at 3.3 kV bus
1453.39
HV side CT Secondary current due to fault at 3.3kV bus
14.53
HV side Current fault at Transformer HV side
7488.00
HV side CT current due to fault at Transformer HV side
74.88
Setting proposed on HV side relay I>>
14.53 x 1.2=17.43
Setting proposed on HV side relay I>>
18.00
Setting proposed on LV side relay I>>
6
However the HV side I>> is set at 3/4 and LV side I>> 2/2.5 to coordinate with 400 Amps fuse in the upstream

kVA
kV
kV

Amps
Amps
Amps

Amps
Amps
Amps
Amps
Amps

Setting Calculation for Distribution Transformers TR1 & TR2 in River water Intake Power house

11 kV

433 V
50/1A

800 /1A

500 kVA
Transformer capacity

PT

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

500

11
0.433
50/1
CTRP 50
800/1
CTRS 800
Z
4.00%
7488
15170
26.24
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 26.24/0.95
30.39
Transformer HV side CT Secondary Pick up Current
Isfl
0.61
IDMT setting at 11 kV side
0.6
Setting proposed on HV side Ip
0.6
Curve
Normal Inverse
Transformer LV side current as per name plate
666.70
Relay drop off Ratio
0.95
LV Pick up Current
1.1 x LV Currrent/ Drop off ratio
=1.1 x 666.7/0.95
771.97
Transformer LV side CT Secondary Pick up Current
=777.1/800
Relay setting for over current
0.964960526
Setting proposed on LV side Ip
1
Curve
Normal Inverse
Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault
15170.00
HV side current due to fault at 0.415 kV bus
597.15
HV side CT Secondary current due to fault at 0.415kV bus
11.94
HV side Current fault at Transformer HV side
7488.00
HV side CT current due to fault at Transformer HV side
149.76
Setting proposed on HV side relay I>>
11.94 x 1.2=14.38
Setting proposed on HV side relay I>>
14.50
Setting proposed on LV side relay I>>
10
However the HV side I>> is set at 6/10 and LV side I>> 5/10 to coordinate with 400 Amps fuse in the upstream

kVA
kV
kV

Amps
Amps
Amps

Amps
Amps
Amps
Amps
Amps

SETTING CALCULATIONS FOR INCOMER FEEDERS

13
10

Setting Calculation for Incomer of Intake Water 11 kV Switchgear


Load connected to BUS A
Transformer 1
Transformer 3
Total Load
Load connected to BUS B
Transformer 2
Transformer 4
Total Load

500 kVA
1500 kVA
2000 kVA
500 kVA
1500 kVA
2000 kVA

Full load current on Bus A

2000/11/1.732
104.9758556

Over load Allowed 20 %


Relay Pick up Current

1.20 x full load current / Drop


off ratio
=1.20x 104.97/0.95
132.59
150/1
132.59/150
0.883933333
0.9

CT ratio for the incomer


Recommended Ip setting

Ip setting
TMS setting
This should be 150 milliseconds greater than fault clearing time of down stream relay
In this case the 1500 kVA Transformer feeder is set at
tms=0.65,Ip=0.9 and CTR=100/1
Fault current-1453 Amps
t=tms x ((0.14)/((If/Is)

0.02

-1))

t=0.65 x ((0.14)/(1453/90)0.02-1))

1.59

required time now


fault current -1453 Amps
CT ratio 150/1
tms=t/ ((0.14)/((If/Is)0.02-1))
tms=1.74/ ((0.14)/(1453/135)0.02-1))
TMS setting
Sending End relay setting details
CT ratio1250/1,plug setting 1.0 and time setting,0.23 and curve :very inverse
The setting proposed at sending end is very high for a load current of 124 A.

1.74

11

0.6
0.6

Amps

Voltage Setting Calculations


10%
15%
20%

As per specifications allowable operating voltage


Therfore , Voltage relay 1st element will be set
Therefore , Voltage relay 2nd element will be set
Overvoltage
In 11 kV switch board ,over voltage 1 Element set at

+15%
115*11000/100
12650
11000/110
110 x 12650/11000
126.5
+20%
120*11000/100
13200
11000/110
110 x 13200/11000
132

PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at

PT ratio
Relay set voltage 1st element
Undervoltage
In 11 kV switch board ,over voltage 1 Element set at

-15%
85*11000/100
9350
9350/110
110 x9350/11000
93.5
-20%
80*11000/100
8800
11000/110
110 x8800/11000
88

PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at

PT ratio
Relay set voltage 1st element

12

Volts

Volts

Volts

Volts

Volts

Volts

Volts

Volts

13

GRID

GRID

RKSR02

CAB11

cab1
PP_boundry

CAB12

cab2
RWIT_boundry

CAB13

cab3

HT Panel River Water

RKSR03

IC2_RWIT

BC_RWIT

IC1_RWIT

50
51

HTP_RWIT_BUS B

50
51

50
51

HTP_RWIT_BUS A
VCB1

VCB3

VCB2
50
51

VCB4

50
51

TR4

50
51

50
51

415V_PMCC_BC

50
51

415V_PMCC_OG1

3.3kV_HTP_OG4
50
51

CAB23

CAB22

CAB21
REL_IC1

VTP2

50
51

VTP3

REL_IC2
IC2
415V_PMCC_BUS B

415V_PMCC_BUS A
50
51

3.3kV_HTP_OG3

50
51

VTP1

415V MCC River Water Intake


IC1

3.3kV_HTP_BUS B

3.3kV_HTP_OG2

3.3kV_HTP_OG1

50
51

3.3kV_HTP_IC2
50
51

50
51

3.3kV_HTP_BUS A

CAB9

BD2

3.3kV_HTP_IC1
50
51

VCB7
50
51

TR2

BD1

CAB8

3.3kV Panel River Intake

VCB6
50
51

CAB7

TR3

50
51

CAB5

cab4

CAB6

TR1

VCB5

50
51

3.3kV_HTP_BC

50
51

50
51

415V_PMCC_OG2

REV. DATE

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMATION

Your Com pany Nam e


Address
Address
Phone and web site

Electrical One-Line Diagram River Water Intake


for Coordination Study
D R AWN B Y/D AT E:

DWG N o.:

E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :

14

SC ALE :

PART No.:
D WG SIZE :

REV.

15

RKSR02
Ik" : 13320.14A

GRID

CAB11

cab1
PP_boundry

CAB12

cab2
RWIT_boundry

CAB13

cab3

HT Panel River Water

RKSR03
Ik" : 13230.54A

GRID

IC2_RWIT

BC_RWIT

IC1_RWIT
50
51

HTP_RWIT_BUS B
Ik" : 5985.61A

50
51

HTP_RWIT_BUS A
Ik" : 6073.41A

50
51

VCB1

VCB3

VCB2
50
51

50
51

TR4

50
51

415V_PMCC_BC

50
51

415V_PMCC_OG1

3.3kV_HTP_OG4
50
51

CAB23

50
51

50
51

CAB22

REL_IC1
IC1

3.3kV_HTP_OG3

50
51

CAB21
VTP1
Ik" : 4441.39A

415V MCC River Water Intake


50
51

3.3kV_HTP_BUS B
Ik" : 4063.72A

3.3kV_HTP_OG2

3.3kV_HTP_OG1

415V_PMCC_BUS A
Ik" : 14887.35A

3.3kV_HTP_IC2
50
51

50
51

3.3kV_HTP_BUS A
Ik" : 4486.58A

VCB7
50
51

CAB9

BD2

3.3kV_HTP_IC1
50
51

50
51

TR2

BD1

CAB8

3.3kV Panel River Intake

VCB6

CAB7

TR3

50
51

CAB5

cab4

CAB6

TR1

VCB5

50
51

3.3kV_HTP_BC

50
51

VCB4

VTP2
Ik" : 4441.39A

50
51

REL_IC2
IC2

50
51

VTP3
Ik" : 4027.31A

415V_PMCC_BUS B
Ik" : 14869.81A
415V_PMCC_OG2

REV. DATE

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMATION

Your Com pany Nam e


Address
Address
Phone and web site

Electrical One-Line Diagram River Water Intake


for Coordination Study
Short Circuit Currents
Source fault level 250 MVA sec
D R AWN B Y/D AT E:

DWG N o.:

E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :

16

SC ALE :

PART No.:
D WG SIZE :

REV.

Short Circuit Detailed Report


River Water Intake
3P Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage

RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
VTP1
3450
VTP2
3450
VTP3
3450
3.3kV_HTP_BUS A
3300
3.3kV_HTP_BUS B
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LL Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage

RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
3.3kV_HTP_BUS A
3300
VTP1
3300
VTP2
3300
3.3kV_HTP_BUS B
3300
VTP3
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LG Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage

RKSR02
11000
RKSR03
11000
HTP_RWIT_BUS A
11000
HTP_RWIT_BUS B
11000
3.3kV_HTP_BUS A
3300
VTP1
3300
VTP2
3300
3.3kV_HTP_BUS B
3300
VTP3
3300
415V_PMCC_BUS A
415
415V_PMCC_BUS B
415
LLG Fault - IEC60909 Method
Bus Name
Pre Fault
Voltage

RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B

11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415

for Max source fault of 250 MVA sec


Peak
Short
Circuit
Current
37675
37422
11986
11776
10959
10959
9893
11148
10043
34382
34319
Peak
Short
Circuit
Current
37611
37387
10765
10587
9721
9554
9554
8765
8632
29888
29838
Peak
Short
Circuit
Current
37399
37271
7957
7900
12213
11790
11790
11317
10956
30364
30334
Peak
Short
Circuit
Current
38991
38758
11186
11022
11904
11509
11509
10954
10604
32931
32876

Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13320
13231
6073
5986
4441
4441
4027
4487
4064
14887
14870

13320
13231
6073
5986
4441
4441
4027
4487
4064
14887
14870

13290
13212
6043
5968
4290
4290
3951
4334
3987
14881
14866

13242
13185
5997
5942
4072
4072
3841
4113
3877
14872
14861

13200
13162
5956
5920
3897
3897
3752
3936
3789
14864
14856

13122
13122
5881
5881
3604
3604
3604
3641
3641
14848
14848

Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13298
13218
5547
5471
3919
3879
3879
3553
3520
12958
12944

13298
13218
5547
5471
3919
3879
3879
3553
3520
12958
12944

13271
13202
5521
5456
3786
3748
3748
3487
3454
12953
12941

13228
13178
5481
5433
3596
3559
3559
3391
3359
12946
12937

13191
13158
5446
5414
3442
3407
3407
3315
3282
12940
12934

13122
13122
5381
5381
3187
3154
3154
3187
3154
12928
12928

0.5 Cycle
Initial
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13223
13177
4081
4057
4854
4745
4745
4521
4427
13267
13259

13223
13177
4081
4057
4854
4745
4745
4521
4427
13267
13259

13207
13168
4073
4052
4735
4630
4630
4459
4366
13264
13257

13183
13154
4060
4045
4561
4462
4462
4368
4277
13260
13255

13162
13142
4049
4039
4417
4322
4322
4294
4205
13256
13253

13122
13122
4028
4028
4169
4083
4083
4169
4083
13249
13249

Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetric Symmetric Symmetric Symmetric Symmetric Symmetric
al
al SC
al SC
al SC
al SC
al SC
SCCurrent Current
Current
Current
Current
Current
13785
13703
5733
5664
4754
4645
4645
4394
4295
14311
14295

17

13785
13703
5733
5664
4754
4645
4645
4394
4295
14311
14295

13757
13686
5709
5650
4624
4518
4518
4329
4231
14306
14292

13713
13661
5673
5629
4437
4334
4334
4234
4137
14297
14287

13675
13640
5641
5612
4285
4185
4185
4158
4062
14289
14282

13603
13603
5582
5582
4030
3936
3936
4030
3936
14275
14275

HT Panel River Water

3.3kV Panel River Intake

415V MCC River Water Intake

SINGLE LINE DIAGRAM-INTAKE WATER PUMP HOUSE


FOR PROTECTION COORDINATION STUDY
SHORT CIRCUIT CURRENTS FOR 500 MVA SEC

18

Short Circuit Detailed Report

River Water Intake

3P Fault - IEC60909 Method


Bus Name

RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B

LL Fault - IEC60909 Method


Bus Name

RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B

LG Fault - IEC60909 Method


Bus Name

RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B

LLG Fault - IEC60909 Method


Bus Name

RKSR02
RKSR03
HTP_RWIT_BUS A
HTP_RWIT_BUS B
3.3kV_HTP_BUS A
VTP1
VTP2
3.3kV_HTP_BUS B
VTP3
415V_PMCC_BUS A
415V_PMCC_BUS B

for Max source fault of 500 MVA sec


Pre Fault Peak Short
Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica
Voltage
Circuit
Current l SCCurrent l SC Current l SC Current l SC Current l SC Current l SC Current
11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415

74788
74535
13837
13649
11441
11240
11240
10337
10176
34873
34829

26442
26352
7488
7405
4635
4586
4586
4212
4172
15171
15161

26442
26352
7488
7405
4635
4586
4586
4212
4172
15171
15161

26411
26334
7460
7388
4482
4435
4435
4135
4096
15168
15159

26364
26307
7416
7363
4262
4217
4217
4025
3986
15162
15156

26322
26284
7377
7342
4085
4042
4042
3937
3897
15158
15154

26243
26243
7306
7306
3789
3749
3749
3789
3749
15149
15149

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica
Voltage
Circuit
Current l SCCurrent l SC Current l SC Current l SC Current l SC Current l SC Current
11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415

74725
74500
12239
12079
9943
9767
9767
8988
8847
30259
30223

26419
26340
6686
6614
4032
3989
3989
3666
3631
13172
13165

26419
26340
6686
6614
4032
3989
3989
3666
3631
13172
13165

26392
26324
6661
6600
3899
3858
3858
3599
3565
13170
13163

26350
26300
6623
6579
3709
3669
3669
3504
3469
13166
13161

26313
26279
6590
6561
3555
3518
3518
3428
3393
13162
13159

26243
26243
6529
6529
3300
3265
3265
3300
3265
13155
13155

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica
Voltage
Circuit
Current l SCCurrent l SC Current l SC Current l SC Current l SC Current l SC Current
11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415

74514
74384
8769
8722
12414
11976
11976
11531
11155
30583
30562

26345
26299
4696
4676
4953
4839
4839
4626
4527
13396
13391

26345
26299
4696
4676
4953
4839
4839
4626
4527
13396
13391

26329
26290
4689
4672
4837
4727
4727
4565
4467
13394
13390

26305
26276
4678
4666
4665
4561
4561
4476
4380
13392
13389

26283
26264
4669
4661
4524
4424
4424
4403
4309
13390
13388

26243
26243
4652
4652
4280
4189
4189
4280
4189
13386
13386

Pre Fault Peak Short


Initial
0.5 Cycle
1 Cycle
3 Cycle
5 cycle
Std
Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica Symmetrica
Voltage
Circuit
Current l SCCurrent l SC Current l SC Current l SC Current l SC Current l SC Current
11000
11000
11000
11000
3300
3300
3300
3300
3300
415
415

77466
77234
12852
12707
12163
11755
11755
11218
10855
33279
33239

27389
27306
6981
6918
4883
4770
4770
4526
4422
14517
14506

19

27389
27306
6981
6918
4883
4770
4770
4526
4422
14517
14506

27360
27290
6959
6905
4754
4643
4643
4461
4358
14513
14504

27317
27265
6926
6886
4568
4461
4461
4367
4265
14508
14501

27278
27244
6896
6870
4417
4313
4313
4291
4191
14503
14498

27206
27206
6842
6842
4164
4066
4066
4164
4066
14494
14494

20

WBPDCL Sagardighi (River Water Intake) 11kV SWITCHBOARD


INCOMER-1 FROM RKSR02 OSC-2 and INCOMER 2 FROM RKSR03 OSD-1
Relay type Siemens Reyrolle 7SR12 06-2HA12-1CA0
7SR12 06-2HA12-1CA0

Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output 10
LEDS,
Standard version include
27/59-Under voltage,Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

Setting

System Frequency

50, 60

50Hz

Setting Dependencies

Enabled, Disabled

Enabled

2 CT/VT CONFIG
Description

Range

Setting

Selects the Power System Frequency from 50 or 60 Hz


When enabled only active settings are displayed and all others hidden

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

1A

Prime

Prime

Phase CT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

150:1

Earth Current Input

1, 5

1A

Earth CT Ratio
Measured
Earth CT ratio to scale primary current instruments
PTs

1:0.2, 1:0.21 ... 5000:6.9, 5000:7


LV Side
PT rated primary
PT rated Secondary

150:1
0~11000 V
110 V

11000V
110V

Range

Setting

Prime

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

Range

Setting

RMS, Fundamental

RMS

Phase CT ratio to scale primary current instruments


Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Gn Undervoltage U/V
Gn Overvoltage O/V
Gn Trip Circuit supervision
Gn Close Circuit Supervision
Gn Circuit Breaker Fail Supervision
Gn CT Supervision
Gn VT Supervision
Gn Thermal Overload

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency

21

Prime

4.1.1 51-1
Description

Range

Setting

Gn 51-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.9

Gn 51-1 Char

IEC-NI

Gn 51-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

4.1.3 50-1
Description

Range

Setting

Gn 50-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-1 Delay

0, 0.01 ... 14300, 14400

0.5

4.1.4 50-2
Description

Range

Setting

Gn 50-2 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-2 Delay

0, 0.01 ... 14300, 14400

0.035

5 DERIVED E/F
5.1 51N-1
Description

Range

Setting

Gn 51N-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.15

Gn 51N-1 Char

IEC-NI

Gn 51N-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI 0.05 ... 1.575, 1.6
0.025,

Gn 51N-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51N-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

5.3 50N-1
Description

Range

Setting

Gn 50N-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50N-1 Delay

0, 0.01 ... 14300, 14400

0.5s

Gn 51-1 Element

Enabled, Disabled

Selects whether the 51-1 IDMTL Overcurrent element is enabled


Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Gn 50-1 Element

Enabled, Disabled

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

Gn 50-2 Element

Enabled, Disabled

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

Gn 51N-1 Element

Enabled, Disabled

Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Gn 50N-1 Element

Enabled, Disabled

Selects whether the DTL derived Earth fault element is enabled


Pickup level

Sets operate delay time

22

Enabled

Prime
135

0.6

Enabled

Enabled

Enabled

Prime
450

Prime
900

Prime
22.5

0.15

Enabled

Prime
150

Over Voltage Protection:59


Setting name
59-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
59 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
under Voltage Protection:27
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
74 TRIP CIRCUIT SUPERVISION
Gn 74TCS-1
Gn 74TCS-1 Delay in sec
Gn 74TCS-2
74 CLOSE CIRCUIT SUPERVISION
Gn 74CCS-1
Gn 74CCS-1 Delay in sec
Gn 74CCS-2
60 CT Supervision
Gn 60CTS-Element
Gn 60CTS Inps
Gn 60CTS Vnps
Gn 60 CTS Delay in sec
60 VT Supervision
Gn 60VTS-Element
Gn 60VTS-Component
Gn 60VTS-V
Gn 60VTS-I
Gn 60VTS-Vpps
Gn 60VTS-Ipps Load
Gn 60VTS-Ipps Fault
Gn 60 VTS Delay in sec

23

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled

Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400

Enabled

Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0
0.03,0.04,..14300,14400

Enabled

Prim Value

126.5
1

12650

5
Any

132
0.5

13200

10
Any
Prime Value

93.5
2
5

9350

88
1

8800

Any

10
Any

0.4 s
Disabled

0.4 s
Disabled

0.10x In
10 V
10s

NPS
7V
0.1x In
15V
0.1x In
10x In
10s

50BF Circuit Breaker fail


Gn 50BF-Element
Gn 50BF-setting
Gn 50BF-I4 setting
Gn 50BF-1Delay in m.sec
Gn 50BF-2Delay in m.sec
49 Thermal Protection
Gn 49-Thermal Overload
Gn 49-Thermal Setting
Gn Capacity Alarm
Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name
Phase angle Setting
Differential Voltage setting
Time set

Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000
Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100
Relay type SKE11
Located in Bus coupler panel
Range
o
5-90
0-10%
0-99sec

24

Enabled
0.2 xIn
0.05 x In
60ms
120ms
Enabled
1.05 xIn
95

Setting
o
20

unit
deg
5%
0.5 sec

BUSCOUPLER

Panel K7

Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0


7SR1003-1HA12-1CA0

Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

Setting

Prime

Description

Range

Setting

Prime

Phase CT ratio to scale primary current instruments

1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
LV Side
PT rated primary
PT rated Secondary

1A
150:1
0~11000 V
110 V

11000V
110V

Range

Setting

Prime

Range

Setting

Prime

Range

Setting

Prime

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies

50, 60
Enabled, Disabled

When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Phase Current Input


Selects
1 or 5 Amp terminals are being used for phase inputs
Phasewhether
CT Ratio

1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7

Earth Current Input


Selects CT
whether
Earth
Ratio1 or 5 Amp terminals are being used for Measured Earth inputs
Measured
Earth CT ratio to scale primary current instruments
PTs

3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement

Selects
4.1.1whether
51-1 the RMS value used by the 51 & 50 elements is True RMS or only calculated

Description

Gn 51-1 Element
Selects
whether
the 51-1 IDMTL Overcurrent element is enabled
Gn 51-1
Setting
Pickup
level
Gn 51-1
Char
Selects
characteristic
curve
to be IEC or ANSI IDMTL or DTL
Gn 51-1
Time Mult
(IEC/ANSI)
Time
multiplier
(applicable
Gn 51-1
Delay
(DTL) to IEC and ANSI curves but not DTL selection)
Delay
(applicable
only when
DTL is selected for characteristic)
Gn 51-1
Min Operate
Time

RMS, Fundamental

Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,
ANSI-MI,
ANSI-VI,
ANSI-EI
0.025,
0.05
... 1.575,
1.6 IEC-NI
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20

Minimum
operate time of element.
4.1.3 50-1

Description

Range

Gn 50-1 Element
Selects
whether
the INST/DTL Overcurrent element is enabled
Gn 50-1
Setting
Pickup
level
Gn 50-1
Delay

Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400

Sets
operate
delay time
4.1.4
50-2

Description

Range

Gn 50-2 Element
Selects
whether
the INST/DTL Overcurrent element is enabled
Gn 50-2
Setting
Pickup
level
Gn 50-2
Delay

Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400

Sets
operate delay
5 DERIVED
E/Ftime

5.1 51N-1
Description

Range

Gn 51N-1 Element
Selects
whether
the 51N-1 IDMTL derived Earth Fault element is enabled
Gn 51N-1
Setting
Pickup
level Char
Gn 51N-1
Selects
characteristic
curve(IEC/ANSI)
to be IEC or ANSI IDMTL or DTL
Gn 51N-1
Time Mult
Time
multiplier
(applicable
Gn 51N-1
Delay
(DTL) to IEC and ANSI curves but not DTL selection)
Delay
(applicable
when Time
DTL is selected for characteristic)
Gn 51N-1
Min only
Operate

Enabled, Disabled
0.05, 0.06 ... 2.49, 2.5
DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,
ANSI-MI,
ANSI-VI,
ANSI-EI
0.025,
0.05
... 1.575,
1.6 IEC-NI
0, 0.01 ... 19.99, 20
0, 0.01 ... 19.99, 20

Minimum operate time of element.

25

50Hz
Enabled

1A
150:1

Enabled
Enabled
Disabled
Disabled

RMS

Enabled
0.8
IEC-NI
0.45
NA
NA

Setting

Enabled
2.5
0.4

Setting

Enabled
5.5
0.03

Setting

Enabled
0.1
IEC-NI
0.14
NA
NA

120

Prime
375

Prime
825

Prime
15

5.3 50N-1
Description

Gn 50N-1 Element
Selects
whether
the DTL derived Earth fault element is enabled
Gn 50N-1
Setting
Pickup
level Delay
Gn 50N-1
Sets
operate
delay time
Check
synchronisationProtection
25
Relay type: Areva SKE 11
Setting name
Phase angle Setting
Differential Voltage setting
Time set

Range

Enabled, Disabled
0.05, 0.06 ... 49.5, 50
0, 0.01 ... 14300, 14400
Relay type SKE11
Located in Bus coupler panel
Range
o
5-90
0-10%
0-99sec

26

Setting

Enabled
0.9
0.5s

Setting
o
20

Prime
150

unit
deg
5%
0.5 sec

BUSCOUPLER Cum Adopter 1

Panel K06

Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output
10 LEDS
Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies

Range

Setting

Prime

Range

Setting

Prime

0~11000 V
110 V

11000V
110V

Setting

Prime

50, 60
Enabled, Disabled

When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description
PTs

LV Side
PT rated primary
PT rated Secondary

3 FUNCTION CONFIG
Description

Range

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

Enabled, Disabled
Range

27

50Hz
Enabled

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Prime Value

93.5
1.5
5

9350

88
0.75
10

8800

Any

Any

BUS PT2

Panel K09

Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary output
10 LEDS version include
Standard

7SR12 04-2HA12-1CA0

7SR12 06-2HA12-1CA0 Standard Version:

27/59-Under voltage, Over Voltage


37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

1 SYSTEM CONFIG
Description

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies

Range

Setting

Prime

Range

Setting

Prime

0~11000 V
110 V

11000V
110V

Setting

Prime

50, 60
Enabled, Disabled

When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description
PTs

LV Side
PT rated primary
PT rated Secondary

3 FUNCTION CONFIG
Description

Range

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

Enabled, Disabled
Range

28

50Hz
Enabled

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Prime Value

93.5
1.5
5

9350

88
0.75
10

8800

Any

Any

OUTGOING-1 to Auxiliary Transformer Feeder 1500 kVA (VCB 3 & VCB 4) Panels K1, K4 ,K6 and K10
Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0
7SR1003-1HA12-1CA0

Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

Setting

Prime

Range

Setting

Prime

CBCT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

50:1

3 FUNCTION CONFIG
Description

Range

Setting

Gn Phase Overcurrent
Gn Derived E/F

Enabled, Disabled
Enabled, Disabled

Enabled
Enabled

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies

50, 60
Enabled, Disabled

When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description

Phase Current Input


Selects
1 or 5 Amp terminals are being used for phase inputs
Phasewhether
CT Ratio
Phase CT ratio to scale primary current instruments
CBCT

1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
1, 5

Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Measured Earth CT ratio to scale primary current instruments

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description

50Hz
Enabled

1A
100:1
1A

Range

Setting

Gn 51/50 Measurement

RMS, Fundamental

RMS

4.1.1 51-1
Description

Range

Setting

Gn 51-1 Element

Enabled, Disabled

Enabled

Gn 51-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.9

Gn 51-1 Char

IEC-NI

Gn 51-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

4.1.3 50-1
Description

Range

Setting

Gn 50-1 Element

Enabled, Disabled

Enabled

Gn 50-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-1 Delay

0, 0.01 ... 14300, 14400

0.35

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency

Selects whether the 51-1 IDMTL Overcurrent element is enabled


Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

29

Prime

Prime

Prime
90

0.65

Prime
300

4.1.4 50-2
Description

Range

Setting

Gn 50-2 Element

Enabled, Disabled

Enabled

Gn 50-2 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-2 Delay

0, 0.01 ... 14300, 14400

0.03

5 DERIVED E/F
5.1 51N-1
Description

Range

Setting

Gn 51N-1 Element

Enabled, Disabled

Enabled

Gn 51N-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.1

Gn 51N-1 Char

IEC-NI

Gn 51N-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51N-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51N-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

5.3 50N-1
Description

Range

Setting

Gn 50N-1 Element

Enabled, Disabled

Enabled

Gn 50N-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50N-1 Delay

0, 0.01 ... 14300, 14400

0.35s

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Selects whether the DTL derived Earth fault element is enabled


Pickup level

Sets operate delay time

30

Prime
400

Prime
10

0.12

Prime
100

Restricted Earth Fault Protection 64R for OUTGOING:


7SR11 03-3HA12-1AA0
7SR11 03-3HA12-1AA0 Standard Version:

RELAY TYPE 7SR1103-3HA12-1AA0


Over current Non Directional relay with E4 case,CT,VT, binary input , binary
Standard version include
50 BF Circuit breaker Fail Supervision ,
64H-High impedance REF,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
74T&C-Trip close circuit supervision
60CTS-CT Supervision
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current

Setting name
Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name
Current Set
Time Delay

31

Range
0.1~1 In
0.00..150.00 s

Setting
0.1
1

Prime Value

Range
0.1~1 In
0.00..150.00 s

Setting
0.1
1.25

Prime Value

10

10

OUTGOING-2 to Distribution Transformer Feeder 500 kVA (VCB 2 & VCB5) Panels K2,K3 and K11
Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0
7SR1003-1HA12-1CA0

Over current Non Directional relay with CT,VT, binary input , binary output
& LEDS

7SR10 03-1HA12-1CA0 Standard Version:

Standard version include


50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

1 SYSTEM CONFIG
Description

Range

Setting

System Frequency

50, 60

50Hz

Setting Dependencies

Enabled, Disabled

Enabled

2 CT/VT CONFIG
Description

Range

Setting

Phase Current Input

1, 5

1A

Phase CT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

50:1

CBCT Current Input

1, 5

1A

CBCT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

50:1

3 FUNCTION CONFIG
Description

Range

Setting

Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

Enabled
Enabled
Disabled
Disabled

Selects the Power System Frequency from 50 or 60 Hz


When enabled only active settings are displayed and all others hidden

Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT ratio to scale primary current instruments
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Measured Earth CT ratio to scale primary current instruments

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description

Range

Setting

Gn 51/50 Measurement

RMS, Fundamental

RMS

4.1.1 51-1
Description

Range

Setting

Gn 51-1 Element

Enabled, Disabled

Enabled

Gn 51-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.6

Gn 51-1 Char

IEC-NI

Gn 51-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

4.1.3 50-1
Description

Range

Setting

Gn 50-1 Element

Enabled, Disabled

Enabled

Gn 50-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-1 Delay

0, 0.01 ... 14300, 14400

0.35

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated
at fundamental frequency

Selects whether the 51-1 IDMTL Overcurrent element is enabled


Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

32

Prime

Prime

Prime

Prime

Prime
30

0.45

Prime
300

4.1.4 50-2
Description

Range

Setting

Gn 50-2 Element

Enabled, Disabled

Enabled

Gn 50-2 Setting

0.05, 0.06 ... 49.5, 50

10

Gn 50-2 Delay

0, 0.01 ... 14300, 14400

0.03

5 DERIVED E/F
5.1 51N-1
Description

Range

Setting

Gn 51N-1 Element

Enabled, Disabled

Enabled

Gn 51N-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.1

Gn 51N-1 Char

IEC-NI

Gn 51N-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51N-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51N-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

5.3 50N-1
Description

Range

Setting

Gn 50N-1 Element

Enabled, Disabled

Enabled

Gn 50N-1 Setting

0.05, 0.06 ... 49.5, 50

0.8

Gn 50N-1 Delay
Sets operate delay time

0, 0.01 ... 14300, 14400

0.35s

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled
Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Selects whether the DTL derived Earth fault element is enabled


Pickup level

33

Prime
500

Prime
5

0.25

Prime
40

Restricted Earth Fault Protection 64R for OUTGOING:


7SR11 03-3HA12-1AA0

RELAY TYPE 7SR1102-3HA12-1AA0


Over current Non Directional relay with E4 case,CT,VT, binary input , binary
output & LEDS,

7SR11 03-3HA12-1AA0 Standard Version:

Standard version include


50 BF Circuit breaker Fail Supervision ,
64H-High impedance REF,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
74T&C-Trip close circuit supervision
60CTS-CT Supervision
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current

Setting name
Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name
Current Set
Time Delay

Range
0.1~1 In
0.00..150.00 s

Setting
0.1
1

Prime Value

Range
0.1~1 In
0.00..150.00 s

Setting
0.1
1

Prime Value

34

35

WBPDCL Sagardighi (River Water Intake) 3.3kV SWITCHBOARD


INCOMER-1 from Aux transformer 1 and INCOMER 2 FROM Aux Transformer 2 Panels L01 and L09
Relay type Siemens Reyrolle 7SR12 06-2HA12-1CA0

Over current Directional relay with E4 case,4CT,3VT,6 binary


input 8 binary output 10 LEDS,
Standard version include
27/59-Under voltage,Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

7SR12 06-2HA12-1CA0

7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Setting

Prime

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

1, 5

1A

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

LV Side
PT rated primary
PT rated Secondary

0~11000 V 3300V
110 V
110V

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

Phase CT ratio to scale primary current instruments

Earth Current Input

Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Earth CT Ratio

Measured Earth CT ratio to scale primary current instruments

PTs

3 FUNCTION CONFIG
Description

Range

Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description

Range

Gn 51/50 Measurement

RMS, Fundamental

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency

36

1A

Prime

Setting

Prime

Setting

Prime

Enabled
Enabled
Disabled
Disabled

RMS

4.1.1 51-1
Description

Range

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.7

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
280 Amps

0.35

Minimum operate time of element.

4.1.3 50-1
Description

Range

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.2

Prime
800 Amps

Sets operate delay time

4.1.4 50-2
Description

Range

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

2.5

0, 0.01 ... 14300, 14400

0.02

Prime
1000 Amps

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Range

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.07

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
28 Amps

0.1

Minimum operate time of element.

5.3 50N-1
Description

Range

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay
Sets operate delay time

37

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0.7

0, 0.01 ... 14300, 14400

0.2

Prime
280 Amps

under Voltage Protection:27


Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
74 TRIP CIRCUIT SUPERVISION
Gn 74TCS-1
Gn 74TCS-1 Delay in sec
Gn 74TCS-2
74 CLOSE CIRCUIT SUPERVISION
Gn 74CCS-1
Gn 74CCS-1 Delay in sec
Gn 74CCS-2
60 CT Supervision
Gn 60CTS-Element
Gn 60CTS Inps
Gn 60CTS Vnps
Gn 60 CTS Delay in sec
60 VT Supervision
Gn 60VTS-Element
Gn 60VTS-Component
Gn 60VTS-V
Gn 60VTS-I
Gn 60VTS-Vpps
Gn 60VTS-Ipps Load
Gn 60VTS-Ipps Fault
Gn 60 VTS Delay in sec

38

Range

Setting

Prime
Value

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled
0.4 s
Disabled

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled
0.4 s
Disabled

Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400

Enabled
0.10x In
10 V
10s

Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0
0.03,0.04,..14300,14400

Enabled
NPS
7V
0.1x In
15V
0.1x In
10x In
10s

93.5
2

2805 Volts

5
Any

88
1
10
Any

2640 Volts

50BF Circuit Breaker fail


Gn 50BF-Element
Gn 50BF-setting
Gn 50BF-I4 setting
Gn 50BF-1Delay in m.sec
Gn 50BF-2Delay in m.sec
49 Thermal Protection
Gn 49-Thermal Overload
Gn 49-Thermal Setting
Gn Capacity Alarm
Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name

Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000

Enabled
0.2 xIn
0.05 x In
60ms
120ms

Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100

Enabled
1.05 xIn
95

Relay type SKE11


Located in Bus coupler panel
Range
5-90 o
0-10%
0-99sec

Phase angle Setting


Differential Voltage setting
Time set

39

Setting
20o

unit
deg
5%
0.5 sec

BUSCOUPLER

Panel L05

Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0


7SR1003-1HA12-1CA0

Over current Non Directional relay with CT,VT, binary


input , binary output & LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Setting

Prime

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

1, 5

1A

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

LV Side
PT rated primary
PT rated Secondary

0~11000 V 11000V
110 V
110V

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

Phase CT ratio to scale primary current instruments

Earth Current Input

Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Earth CT Ratio

Measured Earth CT ratio to scale primary current instruments

PTs

3 FUNCTION CONFIG
Description

Range

Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description

Range

Gn 51/50 Measurement

RMS, Fundamental

1A

Prime

Setting

Prime

Setting

Prime

Setting

Prime

Enabled
Enabled
Disabled
Disabled

RMS

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency

4.1.1 51-1
Description

Range

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Minimum operate time of element.

40

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.6

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

0.05

240 Amps

4.1.3 50-1
Description

Range

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.15

Prime
1600 Amps

Sets operate delay time

4.1.4 50-2
Description

Range

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.03

Prime
2400 Amps

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Range

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.1

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
40 Amps

0.14

Minimum operate time of element.

5.3 50N-1
Description

Range

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay
Sets operate delay time

Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0.9

0, 0.01 ... 14300, 14400

0.5s

Located in Bus coupler panel


Range

Setting

Prime
360

Relay type SKE11

5-90 o
0-10%
0-99sec

Phase angle Setting


Differential Voltage setting
Time set

41

20o

unit
deg
5%
0.5 sec

BUSCOUPLER Cum Adopter 1

Panel L06
Over current Directional relay with E4 case,4CT,3VT,6 binary
input 8 binary output 10 LEDS
Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
Settingthe
Dependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description

PTs

50, 60
Enabled, Disabled

50Hz
Enabled

Setting

Prime

Range

Setting

Prime

LV Side
PT rated primary
PT rated Secondary

3 FUNCTION CONFIG
Description

Range

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

42

0~11000 V 11000V
110 V
110V

Setting

Enabled, Disabled
Range

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

Prime
Prime
Value

93.5
1.5
5

9350 Volts

88
0.75
10

8800 Volts

Sec

Any

Any

Sec

BUS PT1

Panel L04
Over current Directional relay with E4 case,4CT,3VT,6 binary
input 8 binary
output
10 LEDS
Standard
version
include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

7SR12 04-2HA12-1CA0

7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

Range

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
Settingthe
Dependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description

PTs

50, 60
Enabled, Disabled

50Hz
Enabled

Setting

Prime

Range

Setting

Prime

LV Side
PT rated primary
PT rated Secondary

3 FUNCTION CONFIG
Description

Range

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

0~11000 V 11000V
110 V
110V

Setting

Enabled, Disabled
Range

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

93.5
1.5
5

Prime
Prime
Value

Units

9350 Volts

Any
Units

43

88
0.75
10
Any

8800 Volts

Relay Setting details for Pumps


Relay type Siemens 7SR1706 Relay functiional details
Standard version include
27
under voltage,
1. Available
motor data

Detais
Power
Rated voltage
Motor rated current IA
Max. starting current (at 100 % Vn)
Max. starting current (at 80 % Vn)
Starting time (at 100% Vn)
Starting time (at 80% Vn)
Heating Time Constant
Cooling time Constant
Max. blocked rotor time hot @100 %Voltage
Max. blocked rotor time Cold @100% Voltage
Locked rotor Current

Value
500
3.3
111.5
4.5
4.80
1.6
2.9
30
180
12
15
1418

CT/VT CONFIG
Description

Range

Phase Current Input


Selects
1 or 5 Amp terminals are being used for phase inputs
Phasewhether
CT Ratio
Phase
PTs CT ratio to scale primary current instruments

Group 1: Thermal Over Load

Parameter
Thermal Constant T2

Cooling Constant Tr
Thermal Trip
Thermal Alarm
Alarm Threshold
Thermal lockout
Lockout Threshold
Inhibit Trip During Start
Thermal Over load
Reset

3300V
110V

Step

1-360 min

44

0~3300 V
110 V

Value (Range)
1-360 min
1-999 min

0-10

Thermal Constant T1

Prime

1A
160:1

0.2 to 1.5 x In

K Coefficient

Setting

1, 5
1:0.2, 1:0.21 ... 5000:6.9, 5000:7
LV Side
PT rated primary
PT rated Secondary

Enabled/Disabled
Enabled/Disabled
0.2-100 %
Enabled/Disabled
0.2-100 %
Enabled/Disabled
Thermal Model/User Curve
Thermal Model/User Curve

Thermal current threshold I>

Units
kW
kV
A
xIA
xIA
sec
sec
mins
mins
sec
sec
A

Set
Set unit
1 Value 90 mins
1
360 mins

Enable
Enable
0.01
90 %
Enable
0.01
20 %
Enable
Therma
Therma
0.01

0.73 xIn

20 mins

Group 1: Short Circuit

I>1 Function
Current set I>
I> TMS
I>3Function
Current set I>3

Disabled,DT,IEC S inverse,IEC V
Inverse,IEC
0.08
to 15 inE inverse
0.025-1.2

Enabled/Disabled

0.08 to 15 in

Group 1:Negative Sequence Over Current

I2> 1 Status
I2> 1 Current Set
I2> 1 Time Delay
I2> 2 Status
I2> 2 Current Set
I2> 2TMS

Disabled,DT
0.05 to 4 In
0.04 to 200 sec
Disabled,IDMT
0.05 to 4 In
0.07 to 2

Group 1:Derived Earth Fault 50 N & 51 N

IN>1 Function
IN>1 Direction
Current set IN>
IN>1 T Delay

Disabled,DT,IEC S inverse,IEC V
Inverse,IEC E inverse
Non-directional,Directional
FWD
0.08 to 32 In
0.04 to 100 s

Group 1:3 PH Volt Check

Start Low V set

10 to120 V

Group 1:Stall Detection

IEC V
0.1 Inverse
0.77 xIn
0.025
1.2
0.1

52a,I,52a+I
1 to 5 In
1 to 200 sec

Enabled/Disabled

1 to 5 In
0.1 to 60 sec

Group 1:Limit number of Starts

Enabled/Disabled

Hot start Status


Hot start Numbers
Cold start Status
Cold start Numbers
Supervising Time
Time between Starting status
Time between Starting status
Inhibit Start time

1 to 5

Enabled/Disabled

1 to 5
10 to 120 mins

Enabled/Disabled

1 to 120 mins
1 to 120 mins

45

6.5 xIn

DT
0.025
0.01

0.1 xIn
1s
IDMT

0.05
0.025

0.2 xIn
1

DT
Non
0.01 directio
0.08 xIn
0.1
0.1 s
1

Enabled/Disabled

Prolonged Start
Start criteria
Starting current
Prolonged start time
Stall Detection
Stall setting
Stall Time

Enable

88 V

Enable

I
0.5
1
0.5
1

1
1
1
1
1

3 xIn
1.5 s

Enable

Enable

3 xIn
3s

2 Nos

Enable

3 Nos
10 mins

Enable

2 mins
10 mins

Group 1:Voltage Protection


Under Voltage
V< Measurement mode
V< Operate mode
V<1 Function
V<1 VoltageSet
V<1 Time Delay
Over Voltage
V> Measurement mode
V> Operate mode
V>1 Function
V>1 VoltageSet
V>1 Time Delay
Group 1:Circuit Breaker failure

CB Fail 1 status
CB Fail 1Timer

CT Supervision
CTS 1 Status
CTS I VN< Inhibit
CTS1 IN> Set
CTS1 Time Delay

Phase-Neutral,Phse-Phase
Any Phase,Three Phase
Disabled,DT,IDMT
15-120 V
0.04 to 7200 sec

Phase Phase
Any
Phase
DT
1
93 V
0.01
1s

Phase-Neutral,Phse-Phase
Any Phase,Three Phase
Disabled,DT,IDMT
50-200 V
0.04 to 7200 sec

Phase Phase
Any
Phase
DT
1
127 V
0.01
1s

Enabled/Disabled
0 to 10 s

0.01

Enabled/Disabled

0.1 to 0.2 Vn
0.08 to4 In

0 to 10 s

46

0.01
0.01

Enable
0.2 s
Enable

0.05 x Vn
0.2 x In
5s

BUSCOUPLER-1
Relay type Siemens Reyrolle 7SR12 06-2HA12-1CA0

1 SYSTEM CONFIG
Description

Range

Setting

System Frequency

50, 60

50Hz

Setting Dependencies

Enabled, Disabled

Enabled

2 CT/VT CONFIG
Description

Range

Setting

Phase Current Input

1, 5

1A

Phase CT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

Earth Current Input

1, 5

1A

Earth CT Ratio

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

400:1

PTs

LV Side
PT rated primary
PT rated Secondary

0~11000 V 11000V
110 V
110V

Selects the Power System Frequency from 50 or 60 Hz


When enabled only active settings are displayed and all others hidden

Selects whether 1 or 5 Amp terminals are being used for phase inputs
Phase CT ratio to scale primary current instruments
Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs
Measured Earth CT ratio to scale primary current instruments

3 FUNCTION CONFIG
Description

Range

Setting

Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

Enabled
Enabled
Disabled
Disabled

Range

Setting

Gn 51/50 Measurement

RMS, Fundamental

RMS

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Selects whether the RMS value used by the 51 & 50 elements is True RMS or only calculated at fundamental
frequency

4.1.1 51-1
Description

Range

Setting

Gn 51-1 Element

Enabled, Disabled

Enabled

Gn 51-1 Setting

0.05, 0.06 ... 2.49, 2.5

0.6

Gn 51-1 Char

IEC-NI

Gn 51-1 Time Mult (IEC/ANSI)

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

Gn 51-1 Delay (DTL)

0, 0.01 ... 19.99, 20

NA

Gn 51-1 Min Operate Time

0, 0.01 ... 19.99, 20

NA

Selects whether the 51-1 IDMTL Overcurrent element is enabled


Pickup level

Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Time multiplier (applicable to IEC and ANSI curves but not DTL selection)
Delay (applicable only when DTL is selected for characteristic)
Minimum operate time of element.

Range

Setting

Gn 50-1 Element

Enabled, Disabled

Enabled

Gn 50-1 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-1 Delay

0, 0.01 ... 14300, 14400

0.15

Pickup level

Sets operate delay time

4.1.4 50-2
Description

Range

Setting

Gn 50-2 Element

Enabled, Disabled

Enabled

Gn 50-2 Setting

0.05, 0.06 ... 49.5, 50

Gn 50-2 Delay

0, 0.01 ... 14300, 14400

0.03

Selects whether the INST/DTL Overcurrent element is enabled


Pickup level

Sets operate delay time

47

Prime

Prime

Prime

Prime
240

0.05

4.1.3 50-1
Description

Selects whether the INST/DTL Overcurrent element is enabled

Prime

Prime
1600

Prime
2400

48

415 V Intake PumpHouse PMCC


Incomer1 and Incomer 2
Relay type: ALSTOM P143

SCOPE OF FUNCTION
Address

Compt Nos: 4FA and 6FA


Standard version include 50/51/67 -Directional /Non
directional,Instantaneous/ time delayed phase over current (6
stage),50N/51N/67N-Directional /Non directional,Instantaneous/ time
delayed measured earth fault ( 4 stages),64-Restritive earth fault, 51VVoltage controlled over current,27 under voltage,59 -over voltage,37 under
current,46 Negative Phase sequence over current,49 Thermal over load,50
BF Circuit breaker Fail,81U-Under frequency,81O-Overfrequency,81R-rate
of change of frequency Protection,current,60CTS-CT Supervision ,60VTS-VT
Supervision,25-Check synchronising

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

800A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Setting
10
0.025
5
0.2
1
NA
0.05
Standard
Inverse

unit
xIn
s
xIn
s
xIn
s
s

Prime
8000

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

unit
In
s
In
s

Prime
800

Time dial

0.02~1.5

Setting
1
0.2
0.1
NA
Standard
Inverse
0.1

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ie> TMS

49

4000
800

80

Buscoupler
Relay type: ALSTOM P143

SCOPE OF FUNCTION
Address

Compt No:5 FA
Standard version include 50/51/67 -Directional /Non
directional,Instantaneous/ time delayed phase over current (6
stage),50N/51N/67N-Directional /Non directional,Instantaneous/ time
delayed measured earth fault ( 4 stages),64-Restritive earth fault, 51VVoltage controlled over current,27 under voltage,59 -over voltage,37 under
current,46 Negative Phase sequence over current,49 Thermal over load,50
BF Circuit breaker Fail,81U-Under frequency,81O-Overfrequency,81R-rate
of change of frequency Protection,current,60CTS-CT Supervision ,60VTS-VT
Supervision,25-Check synchronising

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

800A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Setting
9
0.015
4
0.15
0.8
NA
0.05
Standard
Inverse

unit
xIn
s
xIn
s
xIn
s
s

Prime
7200

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

unit
In
s
In
s

Prime
640

Time dial

0.02~1.5

Setting
0.8
0.2
0.1
NA
Standard
Inverse
0.15

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ie> TMS

50

3200
640

80

Check synchronisationProtection 25
Relay type: ALSTOM SKE 11

Setting name

Relay type SKE11


Located in Bus coupler panel

Range

Setting

Phase angle Setting

<

5-90 o

20o

Differential Voltage setting


Time set

^V
t

0-10%
0-99sec

Under Voltage Protection:27


Relay type: ALSTOM P94VB

Units

unit

Prim Value

deg
5%
0.5 sec

Standard version include


27 under voltage,
59 -over voltage,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 27
Function 59

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

Other functions are disabled


Power System Data 1
PTs

Parameter

PT rated primary
10..1000 V
PT rated secondary 110..415 V
Value (Range)

415/3 V
110/3 V
Step

Set Value Set unit

V< Measurement mode

PhaseNeutral,PhsePhase

Phase Phase

V< Operate mode

Any Phase,Three
Phase

Any Phase

V<1 Function

Disabled,DT,IDMT

DT

V<1 VoltageSet
V<1 Time Delay

15-120 V
0.04 to 7200 sec

51

99 V
1s

Outgoing 1 and Outgoing 2:MLDB1


Relay type: ALSTOM P141
Compt Nos: 3FA and 7FA
Standard version include 50/51/67 -Directional /Non
directional,Instantaneous/ time delayed phase over current (6
stage),50N/51N/67N-Directional /Non directional,Instantaneous/ time
delayed measured earth fault ( 4 stages),64-Restritive earth fault, 51VVoltage controlled over current,27 under voltage,59 -over voltage,37 under
current,46 Negative Phase sequence over current,49 Thermal over load,50
BF Circuit breaker Fail,81U-Under frequency,81O-Overfrequency,81R-rate
of change of frequency Protection,current,60CTS-CT Supervision ,60VTS-VT
Supervision.

SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

630A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Setting
10
0.01
4
0.05
1
NA
0.05
Standard
Inverse

unit
xIn
s
xIn
s
xIn
s
s

Prime
6300

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

unit
In
s
In
s

Prime
504

Time dial

0.02~1.5

Setting
0.8
0.05
0.1
NA
Standard
Inverse
0.1

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

Ie> TMS

52

2520
630

63

Setting Details Motor feeders only


Location of device

2F-B
2R-H
9R-G

Feeder name:

Drive Rating in kW Motor full


Load Line
current in
Amps
Sludge Slurry Pump 11
22
W
Sludge Slurry Pump 11
22
S
Sludge Slurry Pump 11
22
W

53

Mcomp
CT unit

Mcomp
Relay
setting

12.6-37.8 24
12.6-37.8 24
12.6-37.8 24

54

55

56

57

58

59

REFERENCE DOCUMENTS

3
60

Reference Documents / Drawings - Raw water Pump House


Sl.No
1
2
3
4

Drawing Title
General Notes on 11 kV and 3.3 kV switch Boards
General Notes on 415 V PMCCs
11 kV Switch Board
GA and Schematic diagram of LT Switchgear Panel at RAW WATER PUMP HOUSE

File reference
Pdf file "LT-DG-LE130733-1-E428 & E431.pdf"
Pdf file "LT-DG-LE130733-3-E448.pdf"
Pdf file "RWPH 11kV HT Panel Latest.pdf"
pdf file "RWPH LT Scheme.pdf"

61

Drawing No
SLEF504 sh1-sh24 revision D
SLEE792 sh1-sh19 revision C
(3) G71550-E8170-U001-C- issue C
LT/DG/LE130733/1/E450/REVD- revision D

SETTING CALCULATIONS FOR MOTOR FEEDERS

5
62

Sample Calculations for Relay settings for Motor Feeder


1. Available motor data
110kW VT Pump Motor
Sl No
Size
1.01 Power
1.02 Rated voltage
1.03 Motor rated current I A
1.04 No Load Current
1.05 Max. starting current (at 100 % Vn)
1.06 Max. starting current (at 110 % Vn)
1.07 Starting time (at 100% Vn)
1.08 Starting time (at 80% Vn)
1.09 Heating time constant
1.10 Cooling time constant at standstill
1.11 Max. continuous thermal rating current 105% of I A
1.12 Safe stall time @ 80% Voltage Hot
1.13 Safe stall time @ 100% Voltage Hot
1.14 Safe stall time @ 110% Voltage Hot
1.15 Safe stall time @ 80% Voltage Cold
1.16 Safe stall time @ 100% Voltage Cold
1.17 Safe stall time @ 110% Voltage Cold
1.18 Locked rotor Current
2. General power system data
Parameter
2.01 CurrentTransformer rated current,phase primary
2.02 Transformer rated current, phase secondary
Sample Calculations
Fulload current of Motor I A
CT secondary current corresponding to full load current

Maximum Thermal current 5% more than the full load current


CT secondary current corresponding to Thermal Current
Max. starting current (at 100 % Vn)
Starting Current
CT secondary current corresponding to Starting Current
Over current setting is 10 % more than the full load current
CT secondary current corresponding to Over current
Rounded of to
High set current I>> is normally set 1.3 times the starting current
CT secondary current corresponding to High set Over current I>>
Rounded off to

63

Value
110
0.415
197
75
7.2 x IA
6.6X IA
0.63
1.22
90
360
206.85
37
24
20
76
49
40
1418.4
Value

units
kW
V
A
A

sec
sec
min
min
A
sec
sec
sec
sec
sec
sec
A

Units
300 A
1A
197 A

IA x CT ratio
197 x 1/300
0.66 A
197 x 105/100
206.85 A
206.85 x 1/300
0.69 A
7.2X IA
=7.2 x197
1418.4 A
=1418.4x1 /300
4.73 A
=197 x 110 / 100
216.7 A
=216.7x1/300
0.72
0.72
= 1.3 x1418.4
1843.92 A
=1843.92 x1/300
6.15
6.2 A

SETTING CALCULATIONS FOR TRANSFORMER FEEDERS

5
64

Setting Calculation for Distribution Transformers TR3 & TR4 in Raw water Pump house

11 kV

433 V
100/1A

2500 /1A

1600 kVA

Transformer capacity

PT

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side
Setting proposed on HV side Ip
Curve
Transformer LV side current as per name plate
Relay drop off Ratio
LV Pick up Current

Transformer LV side CT Secondary Pick up Current


Relay setting for over current
Setting proposed on LV side Ip
Curve
Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault
HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
HV side Current fault at Transformer HV side
HV side CT current due to fault at Transformer HV side
Setting proposed on HV side relay I>>
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

65

1600

11
0.433
100/1
CTRP 100
2500/1
CTRS 2500
Z
5.25%
12865
40637
83.97
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 83.97/0.95
97.23
Isfl
0.97
1
1
Normal Inverse
2133.39
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x2133.39/0.95
2470.24
=2470/2500
0.988096421
1
Normal Inverse
40637.00
1599.62
16.00
12865.00
128.65
16 x 1.2=19.2
19.50
8

kVA
kV
kV

Amps
Amps
Amps

Amps
Amps
Amps
Amps
Amps

Setting Calculation for Distribution Transformers TR1 & TR2 in Raw water Pump house

11 kV

433 V
150/1A

4000 /1A

2500 kVA

Transformer capacity

PT

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 11 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

Transformer HV side CT Secondary Pick up Current


IDMT setting at 11 kV side
Setting proposed on HV side Ip
Curve
Transformer LV side current as per name plate
Relay drop off Ratio
LV Pick up Current

Transformer LV side CT Secondary Pick up Current


Relay setting for over current
Setting proposed on LV side Ip
Curve
Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault
HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
HV side Current fault at Transformer HV side
HV side CT current due to fault at Transformer HV side
Setting proposed on HV side relay I>>
Setting proposed on HV side relay I>>
Setting proposed on LV side relay I>>

66

2500

11
0.433
150/1
CTRP 150
4000/1
CTRS 4000
Z
6.25%
12865
53336
131.21
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 104.97/0.95
151.93
Isfl
1.01
1
1
Normal Inverse
3333.52
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x3333.52.41/0.95
3859.87
=3859.87/4000
0.964966316
1
Normal Inverse
53336.00
2099.50
14.00
12865.00
85.77
14 x 1.2=16.8
17.00
7

kVA
kV
kV

Amps
Amps
Amps

Amps
Amps
Amps
Amps
Amps

SETTING CALCULATIONS FOR INCOMER FEEDERS

13
67

Setting Calculation for Incomer of Raw water Pumphouse 11 kV Switchgear


Load connected to BUS A
Transformer 1
Transformer 3
Total Load
Load connected to BUS B
Transformer 2
Transformer 4
Total Load

2500 kVA
1600 kVA
4100 kVA
2500 kVA
1600 kVA
4100 kVA

Full load current on Bus A

4100/11/1.732
215.2005039

Over load Allowed 20 %


Relay Pick up Current

1.20 x full load current / Drop off


ratio
=1.20x 215.20/0.95
271.83
300/1
271.83/300
0.9061
0.9

CT ratio for the incomer change it to 300


Recommended Ip setting

Ip setting
TMS setting
This should be 150 milliseconds greater than fault clearing time of down stream relay
In this case the 2500 kVA Transformer feeder is set at
tms=0.11,Ip=1 and CTR=150/1
Fault current-2099 Amps
0.02

t=tms x ((0.14)/((If/Is)

-1))

t=0.11 x ((0.14)/(2099/150)0.02-1))
required time now
fault current -2099 Amps

0.2842 sec
0.0.4342 sec

CT ratio300/1
tms=t/ ((0.14)/((If/Is)0.02-1))
tms=0.4342/ ((0.14)/(2099/200)0.02-1))
TMS setting
Sending End relay setting details
CT ratio1250/1,plug setting 1.0 and time setting,0.23 and curve :very inverse
The setting proposed at sending end is very high for a load current of 190 A.

68

0.1231
0.13

Amps

Voltage Setting Calculations


As per specifications allowable operating voltage
Therfore , Voltage relay 1st element will be set
Therefore , Voltage relay 2nd element will be set
Overvoltage
In 11 kV switch board ,over voltage 1 Element set at

10%
15%
20%
+15%
115*11000/100
12650
11000/110
110 x 12650/11000
126.5
+20%
120*11000/100
13200
11000/110
110 x 13200/11000
132

PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at

PT ratio
Relay set voltage 1st element
Undervoltage
In 11 kV switch board ,over voltage 1 Element set at

-15%
85*11000/100
9350
9350/110
110 x9350/11000
93.5
-20%
80*11000/100
8800
11000/110
110 x8800/11000
88

PT ratio
Relay set voltage 1st element
In 11 kV switch board ,over voltage 2 Element set at

PT ratio
Relay set voltage 1st element

69

Volts

Volts

Volts

Volts

Volts

Volts

Volts

Volts

70

GRID

RKSR04 OSD2

GRID

cab:IC1

HTP_RWPH_IC1

HTP_RWPH_BUS A
50
51

VCB1

50
51

50
51

50
51

VCB2

HTP_RWPH_BUS B

50
51

VCB3

Cab:TR1_HT

Cab:TR3_HT
TR3
1600 kVA

PT_BC

50
51

PT_IC1

50
51

PTAREA_PMCC_BUS B

50
51

101

RWPH_IC1
50
51

50
51

RWPH_IC2

115

DM PMCC_BUS B

Cab:TR4_LT

PT_OG2

50
51

415V_PMCC_BC
50
51

DM PMCC_BUS A

RWPH PMCC

VCB7

PT_IC2

50
51

97

415V_PMCC_IC2

50
51

Cab:TR4_HT

BD TR2

PT_OG1

50
51

VCB6

TR4
1600 kVA

BD:TR1

50
51

50
51

VCB5

50
51

130

PTAREA_PMCC_BUS A

DM_PMCC_IC

VCB4

82

TR2
2500 kVA

Cab:TR3_LT

PT AREA PMCC

50
51

Cab:TR2_HT

TR1
2500 kVA

34

DM PLANT PMCC

HTP_RWPH_IC2

50
51

50
51

Cab:IC2

HTP_RWPH_BC

HT PANEL RWPH

RKSR02 OSC2

RWPH_PMCC BUS B

RWPH_PMCC BUS A
50
51

RWPH_OG1

50
51

123

124
MLDB1

RWPH_OG2

REV. DATE

TURBINE PUMP

ECO#

DESCRIPTION

DWN APP

THIS DRA WING IS PR OP RIETAR Y INFORMA TION

You r Co mp any Nam e


Add ress
Add ress
Pho ne a nd w eb site

Electrical
Electrical One-Line
One-Line Diagram
Diagram

DRAWN BY/DAT E:

DWG No.:

EN G. APP./ DATE:

MFG. APP./DATE :

71

SCALE :

PART No.:
DWG SIZE:

REV.

72

GRID

RKSR04 OSD2
Ik" : 26243.19A

GRID

cab:IC1

50
51

Cab:IC2

HTP_RWPH_BC

HT PANEL RWPH

HTP_RWPH_IC1

VCB1

50
51

50
51

50
51

VCB2

HTP_RWPH_BUS B
Ik" : 25255.43A

50
51

VCB3

Cab:TR1_HT

Cab:TR3_HT
TR3
1600 kVA

82
Ik" : 24762.36A

TR2
2500 kVA

Cab:TR3_LT

BD:TR1

50
51

PT_IC1

Cab:TR4_LT

50
51

101

RWPH_IC1
50
51

50
51

RWPH_PMCC BUS A
Ik" : 32020.46A
50
51

115

DM PMCC_BUS B
Ik" : 38976.89A

Cab:TR4_HT

50
51

50
51

415V_PMCC_BC
50
51

DM PMCC_BUS A
Ik" : 38974.61A

RWPH PMCC

VCB7

PT_OG2

97

415V_PMCC_IC2

50
51

PTAREA_PMCC_BUS B
Ik" : 48187.61A

PT_OG1

50
51

VCB6

PT_IC2

50
51

50
51

50
51

50
51

TR4
1600 kVA

BD TR2

PTAREA_PMCC_BUS A
Ik" : 47529.32A

DM_PMCC_IC

VCB5

130
Ik" : 50126.3A

PT_BC

PT AREA PMCC

50
51

VCB4

Cab:TR2_HT

TR1
2500 kVA
34
Ik" : 49500.52A

DM PLANT PMCC

HTP_RWPH_IC2

50
51

HTP_RWPH_BUS A
Ik" : 25229.69A
50
51

RKSR02 OSC2
Ik" : 26268.82A

RWPH_OG1

50
51

RWPH_OG2

123

124
MLDB1
Ik" : 15595.1A

RWPH_IC2

RWPH_PMCC BUS B
Ik" : 32674.05A

REV. DATE

TURBINE PUMP
Ik" : 16834.86A

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMATION

Your Com pany Nam e


Address
Address
Phone and web site

Electrical One-Line Diagram for Study


Short Circuit Currents for
Source fault of 500 MVA-sec
D R AWN B Y/D AT E:

DWG N o.:

E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :

73

SC ALE :

PART No.:
D WG SIZE :

REV.

Short Circuit Detailed Report


Raw Water Pump House
3P Fault - IEC60909 Method
Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP

Pre Fault
Voltage

LL Fault - IEC60909 Method


Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP

for Max source fault of 500 MVA sec

11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Peak Short Initial Sym.


Circuit
SC Current
Current
68885
68832
62858
62803
60198
113230
111953
22821
101417
100036
85958
85954
55883
54553
24786

26269
26243
25255
25230
24762
50126
49501
15595
48188
47529
38977
38975
32674
32020
16835

Peak Short Initial Sym.


Circuit
SC Current
Current
68879
68832
62008
61959
59031
98893
97790
19798
88465
87270
74912
74909
48582
47432
21499

26266
26243
25100
25077
24536
43838
43297
13536
42105
41536
34008
34006
28453
27888
14610

74

0.5 Cycle
Sym.SC
Current
26269
26243
25255
25230
24762
50126
49501
15595
48188
47529
38977
38975
32674
32020
16835
0.5 Cycle
Sym.SC
Current
26266
26243
25100
25077
24536
43838
43297
13536
42105
41536
34008
34006
28453
27888
14610

1 Cycle
Sym.SC
Current
26260
26243
25246
25230
24753
49893
49501
15595
47943
47529
38976
38975
32436
32020
16631
1 Cycle
Sym.SC
Current
26258
26243
25092
25077
24528
43636
43297
13536
41894
41536
34007
34006
28247
27888
14434

3 Cycle
Sym.SC
Current
26253
26243
25240
25230
24747
49725
49501
15595
47768
47529
38976
38975
32266
32020
16488
3 Cycle
Sym.SC
Current
26252
26243
25086
25077
24522
43491
43297
13536
41742
41536
34007
34006
28100
27888
14310

5 cycle Sym. Std Sym.SC


SC Current
Current
26248
26243
25235
25230
24742
49589
49501
15595
47626
47529
38975
38975
32130
32020
16373

26243
26243
25230
25230
24737
49461
49501
15595
47493
47529
38975
38975
32002
32020
16266

5 cycle Sym. Std Sym.SC


SC Current
Current
26248
26243
25081
25077
24517
43373
43297
13536
41619
41536
34006
34006
27982
27888
14211

26243
26243
25077
25077
24513
43262
43297
13536
41504
41536
34006
34006
27871
27888
14119

Short Circuit Detailed Report (CONTINUED)


Raw Water Pump House
LG Fault - IEC60909 Method

for Max source fault of 500 MVA sec

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP

26256
26243
24394
24382
23534
55622
55117
10962
48856
48412
39881
39880
24718
24468
11600

Bus Name

Pre Fault
Voltage

LLG Fault - IEC60909 Method


Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
MLDB1
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP

11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Peak Short Initial Sym.


Circuit
SC Current
Current
68859
68832
59365
59339
55499
125337
124311
16624
99493
98616
86818
86816
41377
40890
17681

Peak Short Initial Sym.


Circuit
SC Current
Current
71408
71359
64340
64292
61265
120313
119258
21964
102931
101761
87143
87140
51844
50664
23644

27230
27206
26071
26049
25495
53329
52808
14912
49728
49163
39779
39777
30511
29917
15958

75

0.5 Cycle
Sym.SC
Current
26256
26243
24394
24382
23534
55622
55117
10962
48856
48412
39881
39880
24718
24468
11600
0.5 Cycle
Sym.SC
Current
27230
27206
26071
26049
25495
53329
52808
14912
49728
49163
39779
39777
30511
29917
15958

1 Cycle
Sym.SC
Current
26252
26243
24390
24382
23529
55433
55117
10962
48691
48412
39881
39880
24627
24468
11542
1 Cycle
Sym.SC
Current
27222
27206
26063
26049
25487
53132
52808
14912
49516
49163
39778
39777
30295
29917
15813

3 Cycle
Sym.SC
Current
26248
26243
24387
24382
23526
55298
55117
10962
48573
48412
39881
39880
24562
24468
11500
3 Cycle
Sym.SC
Current
27216
27206
26058
26049
25481
52990
52808
14912
49365
49163
39778
39777
30141
29917
15711

5 cycle Sym. Std Sym.SC


SC Current
Current
26246
26243
24384
24382
23524
55188
55117
10962
48477
48412
39880
39880
24510
24468
11467

26243
26243
24382
24382
23522
55084
55117
10962
48386
48412
39880
39880
24460
24468
11435

5 cycle Sym. Std Sym.SC


SC Current
Current
27211
27206
26053
26049
25476
52874
52808
14912
49241
49163
39777
39777
30016
29917
15630

27206
27206
26049
26049
25472
52764
52808
14912
49124
49163
39777
39777
29899
29917
15554

GRID

RKSR04 OSD2
Ik" : 13121.6A

GRID

cab:IC1

50
51

Cab:IC2

HTP_RWPH_BC

HT PANEL RWPH

HTP_RWPH_IC1

VCB1

50
51

50
51

50
51

VCB2

HTP_RWPH_BUS B
Ik" : 12891.14A

50
51

VCB3

Cab:TR1_HT

Cab:TR3_HT
TR3
1600 kVA

82
Ik" : 12764.27A

TR2
2500 kVA

Cab:TR3_LT

BD:TR1

50
51

PT_IC1

Cab:TR4_LT

50
51

101

RWPH_IC1
50
51

50
51

RWPH_PMCC BUS A
Ik" : 30722.62A
50
51

115

DM PMCC_BUS B
Ik" : 36930.89A

Cab:TR4_HT

50
51

50
51

415V_PMCC_BC
50
51

DM PMCC_BUS A
Ik" : 36923.07A

RWPH PMCC

VCB7

PT_OG2

97

415V_PMCC_IC2

50
51

PTAREA_PMCC_BUS B
Ik" : 45193.14A

PT_OG1

50
51

VCB6

PT_IC2

50
51

50
51

50
51

50
51

TR4
1600 kVA

BD TR2

PTAREA_PMCC_BUS A
Ik" : 44529.89A

DM_PMCC_IC

VCB5

130
Ik" : 46728.76A

PT_BC

PT AREA PMCC

50
51

VCB4

Cab:TR2_HT

TR1
2500 kVA
34
Ik" : 46097.67A

DM PLANT PMCC

HTP_RWPH_IC2

50
51

HTP_RWPH_BUS A
Ik" : 12865.44A
50
51

RKSR02 OSC2
Ik" : 13147.22A

RWPH_OG1

50
51

RWPH_OG2

123

124
MLDB1
Ik" : 15335.34A

RWPH_IC2

RWPH_PMCC BUS B
Ik" : 31381.18A

REV. DATE

TURBINE PUMP
Ik" : 16570.68A

ECO#

DESCRIPTION

DWN APP

THIS DRAWING IS PROPRIETARY INFORMATION

Your Com pany Nam e


Address
Address
Phone and web site

Electrical One-Line Diagram for Study


Short Circuit Currents for
Source fault of 250 MVA-sec
D R AWN B Y/D AT E:

DWG N o.:

E NG . AP P ./D ATE :
MF G. A PP ./ DA TE :

76

SC ALE :

PART No.:
D WG SIZE :

REV.

Short Circuit Detailed Report


Raw Water Pump House
3P Fault - IEC60909 Method
Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1

Pre Fault
Voltage

LL Fault - IEC60909 Method


Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1

for Max source fault of 250 MVA sec

11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Peak Short Initial Sym.


Circuit
SC Current
Current
34469
13147
34416
13122
32898
12891
32844
12865
32160
12764
106534
46729
105238
46098
96267
45193
94870
44530
82116
36931
82104
36923
54336
31381
52987
30723
24498
16571
22525
15335

0.5 Cycle
Sym.SC
Current
13147
13122
12891
12865
12764
46729
46098
45193
44530
36931
36923
31381
30723
16571
15335

1 Cycle
Sym.SC
Current
13138
13122
12882
12865
12755
46495
46098
44949
44530
36928
36923
31142
30723
16365
15335

3 Cycle 5 cycle Sym. Std Sym.SC


Sym.SC
SC Current
Current
Current
13132
13127
13122
13122
13122
13122
12876
12870
12865
12865
12865
12865
12749
12744
12739
46328
46192
46063
46098
46098
46098
44774
44632
44498
44530
44530
44530
36926
36925
36923
36923
36923
36923
30972
30834
30705
30723
30723
30723
16220
16104
15995
15335
15335
15335

Peak Short Initial Sym.


Circuit
SC Current
Current
34463
13144
34416
13122
32661
12849
32613
12826
31822
12703
93746
41217
92628
40671
84520
39801
83313
39228
71977
32439
71968
32434
47408
27469
46243
26900
21282
14412
19575
13341

0.5 Cycle
Sym.SC
Current
13144
13122
12849
12826
12703
41217
40671
39801
39228
32439
32434
27469
26900
14412
13341

1 Cycle
Sym.SC
Current
13136
13122
12841
12826
12695
41014
40671
39589
39228
32437
32434
27262
26900
14234
13341

3 Cycle 5 cycle Sym. Std Sym.SC


Sym.SC
SC Current
Current
Current
13131
13126
13122
13122
13122
13122
12835
12831
12826
12826
12826
12826
12690
12685
12680
40869
40751
40640
40671
40671
40671
39438
39315
39199
39228
39228
39228
32436
32435
32434
32434
32434
32434
27114
26996
26884
26900
26900
26900
14109
14008
13915
13341
13341
13341

77

Short Circuit Detailed Report (CONTINUED)


Raw Water Pump House
LG Fault - IEC60909 Method
Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1

Pre Fault
Voltage

LLG Fault - IEC60909 Method


Bus Name

RKSR02 OSC2
RKSR04 OSD2
HTP_RWPH_BUS B
HTP_RWPH_BUS A
82
130
34
PTAREA_PMCC_BUS B
PTAREA_PMCC_BUS A
DM PMCC_BUS B
DM PMCC_BUS A
RWPH_PMCC BUS B
RWPH_PMCC BUS A
TURBINE PUMP
MLDB1

11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

Pre Fault
Voltage
11000
11000
11000
11000
11000
415
415
415
415
415
415
415
415
415
415

for Max source fault of 250 MVA sec

Peak Short Initial Sym.


Circuit
SC Current
Current
34443
13135
34416
13122
31901
12656
31875
12644
30759
12426
120497
53146
119427
52621
96571
47042
95657
46578
84514
38619
84507
38615
40879
24289
40373
24027
17596
11520
16533
10879

0.5 Cycle
Sym.SC
Current
13135
13122
12656
12644
12426
53146
52621
47042
46578
38619
38615
24289
24027
11520
10879

1 Cycle
Sym.SC
Current
13130
13122
12652
12644
12422
52952
52621
46871
46578
38618
38615
24194
24027
11459
10879

3 Cycle 5 cycle Sym. Std Sym.SC


Sym.SC
SC Current
Current
Current
13127
13124
13122
13122
13122
13122
12649
12646
12644
12644
12644
12644
12418
12416
12413
52812
52698
52591
52621
52621
52621
46748
46648
46554
46578
46578
46578
38617
38616
38615
38615
38615
38615
24126
24071
24020
24027
24027
24027
11416
11382
11349
10879
10879
10879

Peak Short Initial Sym.


Circuit
SC Current
Current
35729
13627
35679
13603
33875
13336
33828
13314
33013
13190
114925
50563
113842
50029
98984
47372
97795
46798
84177
38175
84167
38169
50788
29604
49594
29005
23364
15712
21681
14670

0.5 Cycle
Sym.SC
Current
13627
13603
13336
13314
13190
50563
50029
47372
46798
38175
38169
29604
29005
15712
14670

1 Cycle
Sym.SC
Current
13619
13603
13328
13314
13182
50363
50029
47159
46798
38173
38169
29387
29005
15565
14670

3 Cycle 5 cycle Sym. Std Sym.SC


Sym.SC
SC Current
Current
Current
13613
13608
13603
13603
13603
13603
13323
13318
13314
13314
13314
13314
13177
13172
13168
50219
50102
49991
50029
50029
50029
47006
46881
46763
46798
46798
46798
38172
38170
38169
38169
38169
38169
29232
29107
28989
29005
29005
29005
15461
15379
15302
14670
14670
14670

78

79

WBPDCL Sagardighi (Raw Water Pump House) 11kV SWITCHBOARD


INCOMER-1 FROM RKSR04 OSD2 and INCOMER 2 FROM RKSR02 OSC2
Relay type Siemens Reyrolle 7SR12 06-2HA12-1CA0
7SR12 06-2HA12-1CA0

7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Panel Nos K12 and K5


Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary
output 10 LEDS,
Standard version include
27/59-Under voltage,Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

Range

Setting

Prime

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

300:1

LV Side
PT rated primary
PT rated Secondary

0~11000 V
110 V

11000V
110V

Setting

Prime

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

1A

Prime

Phase CT ratio to scale primary current instruments

PTs

3 FUNCTION CONFIG
Description

Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F
Gn Undervoltage U/V
Gn Overvoltage O/V
Gn Trip Circuit supervision
Gn Close Circuit Supervision
Gn Circuit Breaker Fail Supervision
Gn CT Supervision
Gn VT Supervision
Gn Thermal Overload

Range

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

80

Enabled
Enabled
Disabled
Disabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled
Enabled

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement

Range

RMS, Fundamental

Setting

Prime

Setting

Prime

RMS

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency

4.1.1 51-1
Description

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Range

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.9

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

270

0.13

Minimum operate time of element.

4.1.3 50-1
Description

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.45

Prime
900

Sets operate delay time

4.1.4 50-2
Description

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.045

Prime
2100

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.1

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
30

0.25

Minimum operate time of element.

5.3 50N-1
Description

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0.7

0, 0.01 ... 14300, 14400

0.8s

Sets operate delay time

81

Prime
210

Over Voltage Protection:59


Setting name
59-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
59 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
under Voltage Protection:27
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay in sec
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

o/v

Range

Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

82

Prim
Value

121
1

12100

5
Any

126.5
0.5

12650

10
Any
Prime
Value

99
2

9900

5
Any

93.5
1
10
Any

9350

74 TRIP CIRCUIT SUPERVISION


Gn 74TCS-1
Gn 74TCS-1 Delay in sec
Gn 74TCS-2
74 CLOSE CIRCUIT SUPERVISION
Gn 74CCS-1
Gn 74CCS-1 Delay in sec
Gn 74CCS-2
60 CT Supervision
Gn 60CTS-Element
Gn 60CTS Inps
Gn 60CTS Vnps
Gn 60 CTS Delay in sec
60 VT Supervision
Gn 60VTS-Element
Gn 60VTS-Component
Gn 60VTS-V
Gn 60VTS-I
Gn 60VTS-Vpps
Gn 60VTS-Ipps Load
Gn 60VTS-Ipps Fault
Gn 60 VTS Delay in sec
50BF Circuit Breaker fail
Gn 50BF-Element
Gn 50BF-setting
Gn 50BF-I4 setting
Gn 50BF-1Delay in m.sec
Gn 50BF-2Delay in m.sec
49 Thermal Protection
Gn 49-Thermal Overload
Gn 49-Thermal Setting
Gn Capacity Alarm
Check synchronisationProtection 25
Relay type: Areva SKE 11
Setting name
Phase angle Setting
Differential Voltage setting
Time set

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled

Disabled/Enabled
0,0.02,0.04,..59.96,59.98,60
Disabled/Enabled

Enabled

Disabled/Enabled
0.05,0.1,0.15,0.90,095,1.0
7,8,9,10,108,109,110
0.03,0.04,..14300,14400

Enabled

Disabled/Enabled
NPS,ZPS
7,8,9,10,108,109,110
0.05,0.1,0.15,0.90,095,1.0
1,2,109,110
0.05,0.1,0.15,0.90,095,1.0
0.05,0.1,0.15,19.90,19.95,20.0

Enabled

0.4 s
Disabled

0.4 s
Disabled

0.10x In
10 V
10s

NPS
7V
0.1x In
15V
0.1x In
10x In

0.03,0.04,..14300,14400
Disabled/Enabled
0.05,0.0551.995,2
0.05,0.0551.995,2
20,25,59995,60000
20,25,59995,60000
Disabled/Enabled
0.1,0.11,2.99,3.0
Disabled,50,.99,100
Relay type SKE11
Located in Bus coupler panel
Range
o

5-90
0-10%
0-99sec

83

10s
Enabled
0.2 xIn
0.05 x In
60ms
120ms
Enabled
1.05 xIn
95

Setting
o

20

unit
deg
5%
0.5 sec

BUSCOUPLER

Panel K07

Relay type Siemens Reyrolle 7SR10 03-1HA12-1CA0


7SR1003-1HA12-1CA0
7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Over current Non Directional relay with CT,VT, binary input , binary
output & LEDS
Standard version include
50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

Range

Setting

Prime

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

300:1

1, 5

1A

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

300:1

LV Side
PT rated primary
PT rated Secondary

0~11000 V
110 V

11000V
110V

Setting

Prime

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

1A

Prime

Phase CT ratio to scale primary current instruments

Earth Current Input


Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments

PTs

3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

Range

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

84

Enabled
Enabled
Disabled
Disabled

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description

Range

Gn 51/50 Measurement

RMS, Fundamental

Setting

Prime

Setting

Prime

RMS

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency

4.1.1 51-1
Description

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Range

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.8

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

240

0.1

Minimum operate time of element.

4.1.3 50-1
Description

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

2.5

0, 0.01 ... 14300, 14400

0.35

Prime
750

Sets operate delay time

4.1.4 50-2
Description

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.03

Prime
1800

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.12

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
36

0.2

Minimum operate time of element.

5.3 50N-1
Description

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay
Sets operate delay time

Check synchronisationProtection 25

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0.9

0, 0.01 ... 14300, 14400

0.7

Relay type SKE11

85

Prime
270

Relay type: Areva SKE 11


Setting name

Located in Bus coupler panel


Range

Phase angle Setting


Differential Voltage setting
Time set

5-90 o
0-10%
0-99sec

86

Setting
20o

unit
deg
5%
0.5 sec

BUSCOUPLER Cum Adopter 1

Panel K06

7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description

PTs

3 FUNCTION CONFIG
Description

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

Over current Directional relay with E4 case,4CT,3VT,6 binary input 8 binary


output 10 LEDS
Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

Range

50, 60
Enabled, Disabled

50Hz
Enabled

Setting

Prime

Range

Setting

Prime

0~11000 V
110 V

11000V
110V

Setting

Prime

LV Side
PT rated primary
PT rated Secondary

Range

Enabled, Disabled
Range

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

87

Prime
Value
93.5
1.5
5

9350

88
0.75
10

8800

Any

Any

BUS PT2
Panel K09
7SR12 04-2HA12-1CA0
7SR12 06-2HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency
Selects
Power System Frequency from 50 or 60 Hz
SettingtheDependencies
When
enabled
only active settings are displayed and all others hidden
2 CT/VT
CONFIG

Description

PTs

3 FUNCTION CONFIG
Description

Gn Undervoltage
Setting name
27-1 Element 1
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases
27 Element 2
Gn V Operation
Gn V Setting (Ph-N) Gn V Setting (Ph-Ph)
Gn V Delay
Gn V Hysteresis
Gn V Block Threshold
Gn V O/P Phases

Over current Directional relay with E4 case,4CT,3VT,6 binary input 8


Standard version include
27/59-Under voltage, Over Voltage
37- Under current,
46NPS- Negative Phase sequence over current,
49- Thermal over load,
50 BF- Circuit breaker Fail,
51V-Voltage controlled over current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
64H-High impedance REF,
67/50-Directional instantaneous phase fault over current,
67/50G,67/50N- Directional instantaneous earth fault,
67/50SEF-Directional instantaneous sensitive earth fault,
67/51-Directional time delayes,phase fault over current,
67/51G,67/51N-Directional time delayed earth fault,
67/51SEF-Directional time delayed Sensitive earth fault,
74T&C-Trip close circuit supervision and
81U/O under over frequency

Range

50, 60
Enabled, Disabled

50Hz
Enabled

Setting

Prime

Range

Setting

Prime

0~11000 V
110 V

11000V
110V

Setting

Prime

LV Side
PT rated primary
PT rated Secondary

Range

Enabled, Disabled
Range

Enabled
Setting

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

OFF, O/V, U/V


5.0, 5.580.0200.0
0.00, 0.0120,20.5
100.0,101.0600.0
1,290
OFF,1,25100
Any One, All

u/v

88

Prime
Value
93.5
1.5
5

9350

88
0.75
10

8800

Any

Any

OUTGOING-1 to DM Plant Transformer Feeder 1600 kVA & spare (VCB 2, VCB 5 & VCB 7)
Panel Nos K1,K4 and K11
Over current Non Directional relay with CT,VT, binary input , binary
7SR1003-1HA12-1CA0
output & LEDS
Relay type Siemens Reyrolle 7SR1003-1HA20-1CA0

7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Standard version include


50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

Range

Setting

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

100:1

1, 5

1A

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

100:1

Prime

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

1A

Prime

Phase CT ratio to scale primary current instruments

Earth Current Input


Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments

3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement

Range

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

Range

RMS, Fundamental

Setting

Prime

Setting

Prime

Setting

Prime

Enabled
Enabled
Disabled
Disabled

RMS

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency

4.1.1 51-1
Description

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Range

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Minimum operate time of element.

4.1.3 50-1

89

0.15

100

Description

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.45

Sets operate delay time

90

Prime
600

4.1.4 50-2
Description

Range

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

19.5

0, 0.01 ... 14300, 14400

0.02

Prime
1950

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Range

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.1

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
10

0.15

Minimum operate time of element.

5.3 50N-1
Description

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.35s

Prime
100

Sets operate delay time

Restricted Earth Fault Protection 64R for OUTGOING:


7SR11 03-3HA12-1AA0
7SR11 03-3HA12-1AA0 Standard Version:

RELAY TYPE 7SR1103-3HA12-1AA0


Over current Non Directional relay with E4 case,CT,VT, binary input ,
Standard version include
50 BF Circuit breaker Fail Supervision ,
64H-High impedance REF,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
74T&C-Trip close circuit supervision
60CTS-CT Supervision
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current

Setting name

Range

Setting

Current Set
Time Delay
Sensitive Earth Fault Protection 51NS for OUTGOING:
Setting name

0.1~1 In
0.00..150.00 s

0.1
1

Range

Setting

Current Set
Time Delay

0.1~1 In
0.00..150.00 s

0.1
1

91

Prime
Value
10

Prime
Value
10

OUTGOING-2 to PT AREA Transformer Feeder 2500 kVA (VCB1,VCB3,VCB4 & VCB6)


Panel Nos K2,K3,,K8 and K10
Over current Non Directional relay with CT,VT, binary input , binary
7SR1003-1HA12-1CA0
output & LEDS
Relay type Siemens Reyrolle 7SR1003 iHA20-1CA0

7SR10 03-1HA12-1CA0 Standard Version:

1 SYSTEM CONFIG
Description

System Frequency

Selects the Power System Frequency from 50 or 60 Hz

Setting Dependencies

Standard version include


50 BF Circuit breaker Fail Supervision ,
49-Thermal Overload,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
81HLB2-Inrush restraint
46 NPS-Negative Sequence overcurrent
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current
50SEF-Instantaneous Sensitive Earth Fault
51SEF-Time Delayed sensitive Earth Fault protection

Range

Setting

50, 60

50Hz

Enabled, Disabled

Enabled

Range

Setting

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

150:1

1, 5

1A

1:0.2, 1:0.21 ... 5000:6.9, 5000:7

150:1

Prime

When enabled only active settings are displayed and all others hidden

2 CT/VT CONFIG
Description

Phase Current Input

1, 5

Selects whether 1 or 5 Amp terminals are being used for phase inputs

Phase CT Ratio

1A

Prime

Phase CT ratio to scale primary current instruments

Earth Current Input


Selects whether 1 or 5 Amp terminals are being used for Measured Earth inputs

Earth CT Ratio
Measured Earth CT ratio to scale primary current instruments

3 FUNCTION CONFIG
Description
Gn Phase Overcurrent
Gn Derived E/F
Gn Sensitive E/F
Gn Restricted E/F

4 CURRENT PROTECTION
4.1 PHASE OVERCURRENT
Description
Gn 51/50 Measurement

Range

Enabled, Disabled
Enabled, Disabled
Enabled, Disabled
Enabled, Disabled

Range

RMS, Fundamental

Setting

Prime

Setting

Prime

Setting

Prime

Enabled
Enabled
Disabled
Disabled

RMS

Selects whether the RMS value used by the 51 & 50 elements is True RMS or only
calculated at fundamental frequency

4.1.1 51-1
Description

Gn 51-1 Element

Selects whether the 51-1 IDMTL Overcurrent element is enabled

Gn 51-1 Setting
Pickup level

Gn 51-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51-1 Min Operate Time

Range

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Minimum operate time of element.

4.1.3 50-1

92

0.11

150

Description

Gn 50-1 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-1 Setting
Pickup level

Gn 50-1 Delay

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.3

Sets operate delay time

93

Prime
900

4.1.4 50-2
Description

Range

Gn 50-2 Element

Selects whether the INST/DTL Overcurrent element is enabled

Gn 50-2 Setting
Pickup level

Gn 50-2 Delay

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

17

0, 0.01 ... 14300, 14400

0.04

Prime
2550

Sets operate delay time

5 DERIVED E/F
5.1 51N-1
Description

Range

Gn 51N-1 Element
Selects whether the 51N-1 IDMTL derived Earth Fault element is enabled

Gn 51N-1 Setting
Pickup level

Gn 51N-1 Char
Selects characteristic curve to be IEC or ANSI IDMTL or DTL

Gn 51N-1 Time Mult (IEC/ANSI)


Time multiplier (applicable to IEC and ANSI curves but not DTL selection)

Gn 51N-1 Delay (DTL)

Delay (applicable only when DTL is selected for characteristic)

Gn 51N-1 Min Operate Time

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 2.49, 2.5

0.15

DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI,


ANSI-MI, ANSI-VI, ANSI-EI IEC-NI
IEC-NI
0.025, 0.05 ... 1.575, 1.6

IEC-NI

0, 0.01 ... 19.99, 20

NA

0, 0.01 ... 19.99, 20

NA

Prime
22.5

0.25

Minimum operate time of element.

5.3 50N-1
Description

Gn 50N-1 Element

Selects whether the DTL derived Earth fault element is enabled

Gn 50N-1 Setting
Pickup level

Gn 50N-1 Delay
Sets operate delay time
Restricted Earth Fault Protection 64R for OUTGOING:
7SR11 03-3HA12-1AA0
7SR11 03-3HA12-1AA0 Standard Version:

Range

Setting

Enabled, Disabled

Enabled

0.05, 0.06 ... 49.5, 50

0, 0.01 ... 14300, 14400

0.65

Prime
150

RELAY TYPE 7SR1103-3HA12-1AA0


Over current Non Directional relay with E4 case,CT,VT, binary input ,
Standard version include
50 BF Circuit breaker Fail Supervision ,
64H-High impedance REF,
50N/50G-Instantaneous earth fault,
51-Time delayed phase fault over Current,
51G/51N-Time delayed earth fault,
74T&C-Trip close circuit supervision
60CTS-CT Supervision
46BC-Broken Conductor load Unbalance
50-Instantaneous Phase Over Current

Setting name

Range

Setting

Current Set
Time Delay
Standby Earth Fault Protection 51 NS for OUTGOING:
Setting name

0.1~1 In
0.00..150.00 s

0.1
1

Range

Setting

Current Set
Time Delay

0.1~1 In
0.00..150.00 s

0.1
1

94

Prime
Value
15

Prime
Value
15

95

415 V PT Area PCC


Incomer1 and Incomer 2
Relay type: SIEMENS 7SR22
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase over
current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

4000
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5

Setting
5.5
0.037
3
0.15
1
NA
0.06

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS

96

unit
xIn
s
xIn
s
xIn
s
s

Prime
22000
12000
4000

IEC Curve

Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Standard
Inverse

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Time dial

0.02~1.5

Setting
1
0.5
0.1
NA
Standard
Inverse
0.25

Ie> TMS

97

unit
In
s
In
s

Prime
4000
400

Buscoupler
Relay type: SIEMENS 7SR22
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase over
current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

4000A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Setting
5
0.015
2.5
0.1
0.8
NA
0.05
Standard
Inverse

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

98

unit
xIn
s
xIn
s
xIn
s
s

Prime
20000
10000
3200

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
0.7
0.1
0.07
NA
Standard
Inverse
0.08

unit
In
s
In
s

Prime
2800

Set Value

Set unit

280

Time dial
Ie> TMS
0.02~1.5
Under Voltage Protection:27
Relay type: ALSTOM P94VB
Standard version include
27 under voltage,
59 -over voltage,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 27
Function 59

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

PT rated primary
PT rated secondary

10..1000 V
110..415 V
Value (Range)

415/ 3 V
110/ 3 V
Step

Other functions are disabled


Power System Data 1
PTs

Parameter

V< Measurement mode

PhaseNeutral,PhsePhase
Any Phase,Three
Phase

Phase -Phase

V<1 Function

Disabled,DT,IDMT

DT

V<1 VoltageSet
V<1 Time Delay

15-120 V
0.04 to 7200 sec

V< Operate mode

99

Any Phase

99 V
1s

Outgoing 1 and Outgoing 2 TO 415 V Raw Water PumpHouse PCC


Relay type: SIEMENS 7SR22
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase over
current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault,
51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision.
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

630A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5
Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Setting
9
0.03
6
0.4
1
NA
0.15
Standard
Inverse

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS
IEC Curve

100

unit
xIn
s
xIn
s
xIn
s
s

Prime
5670
3780
630

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Time dial

0.02~1.5

Ie> TMS

101

Setting
1.5
0.35
0.15
NA
Standard
Inverse
0.15

unit
In
s
In
s

Prime
945
94.5

415 V DM PLANT PMCC


Incomer1 and Incomer 2
Relay type: ALSTOM P143

SCOPE OF FUNCTION
Address

Compt No:
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase
over current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

2500
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5

Setting
5
0.015
3
0.3
1
NA
0.08

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS

102

unit
xIn
s
xIn
s
xIn
s
s

Prime
12500
7500
2500

IEC Curve

Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Standard
Inverse

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Time dial

0.02~1.5

Setting
1
0.2
0.1
NA
Standard
Inverse
0.1

Ie> TMS

103

unit
In
s
In
s

Prime
2500
250

Buscoupler
Relay type: ALSTOM P143

SCOPE OF FUNCTION
Address

Compt No:
Standard version include
50/51/67 -Directional /Non directional,Instantaneous/ time delayed phase
over current (6 stage),
50N/51N/67N-Directional /Non directional,Instantaneous/ time delayed
measured earth fault ( 4 stages),
64-Restritive earth fault, 51V-Voltage controlled over current,
27 under voltage,
59 -over voltage,
37 under current,
46 Negative Phase sequence over current,
49 Thermal over load,
50 BF Circuit breaker Fail,
81U-Under frequency,
81O-Overfrequency,
81R-rate of change of frequency Protection,current,
60CTS-CT Supervision ,
60VTS-VT Supervision,
25-Check synchronising
Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Setting
Enabled/Disabled Enabled

Title Setting

Range

Setting

10..50000 A
1A/5A

2500A
1A

Range
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.1~40.00 A
0.00..150.00 s
0.02~1.5

Setting
4
0.015
2
0.2
0.7
NA
0.05

Other functions are disabled


Power System Data 1
CTs
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
50-3 pickup
I>>>
50-3 Delay
T I>>>
50-2 pickup
I>>
50-2 Delay
T I>>
51-1Pickup
I>
51-1Delay
tI>
Time dial
I> TMS

104

unit
xIn
s
xIn
s
xIn
s
s

Prime
10000
5000
1750

IEC Curve

Ground over current Protection: 50N/51 N


Setting name
Units
50N-2 Pickup
Ie>>
50N-2 Delay
Te>>
51N-1Pickup
Ie>
51N-1Delay
TIe>
Delay type

Standard
Inverse(SI) ,Very
Inverse(VI)
,Extremely
Inverse(EI)

Standard
Inverse

Range
0.01 to 8 Ien
0.02..99.00 s
0.002 to1 Ien
0.02..150.00 s

Setting
0.7
0.1
0.07
NA
Standard
Inverse
0.08

Time dial
Ie> TMS
0.02~1.5
Under Voltage Protection:27
Relay type: ALSTOM P94VB
Standard version include
SCOPE OF FUNCTION
Address
Setting Title
Setting Range
Fault Records
Enabled/Disabled
Function 27
Function 59
Other functions are disabled
Power System Data 1
Title Setting
Range
PTs
PT rated primary
10..1000 V
PT rated secondary 110..415 V
Parameter
Value (Range)

V< Measurement mode

Setting
415/3 V
110/3 V
Step

Set Value Set unit


Phase Phase

V<1 Function

Disabled,DT,IDMT

DT

V<1 VoltageSet
V<1 Time Delay

15-120 V
0.04 to 7200 sec

105

175

Setting
Enabled

PhaseNeutral,PhsePhase
Any Phase,Three
Phase

V< Operate mode

Prime
1750

unit
In
s
In
s

Any Phase

93 V
1s

10000
1000
100

PT_OG1
RWPH_OG1

Time in Seconds

10

RWPH_IC

HTP_RWPH_IC1
VCB3

.01

.1

PT_IC1

.5

415 Volt Phase

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

3 - Grid-HTPANEL-VCB3-PTIC1-PTOG1-RWPHIC1-RWPHOG1

1000

10000
03-15-2015
23:03:44
sagardighi_rwph

106

10000
1000
100

RWPH_OG1
RWPH_IC1

10

PT_OG1

Time in Seconds

PT_IC1
VCB3

.01

.1

HTP_RWPH_IC1

.5

415 Volt Ground

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

3 - Grid-HTPANEL-VCB3-PTIC1-PTOG1-RWPHIC1-RWPHOG1

1000

10000
03-15-2015
23:08:00
sagardighi_rwph

107

108

109