Metal Enclosed Non-Segregated Bus Duct


Industry Standards

Description
Non-segregated phase bus duct is designed for interconnecting groups of metal-enclosed or metal-clad
switchgear, power transformers or other related
equipment. The bus duct is designed, manufactured,
and tested in accordance with ANSI/IEEE Standard
C37.23.
Bar type copper conductors are provided for 600 volt,
5kV, 15kV and 38kV classes. Aluminum conductors
are available as an option.
All necessary equipment, connection flanges, wall
entrance seals, transformer and/or equipment
terminations, tap boxes, elbows, offsets, wall supports,
splicing materials, terminal connectors, and structural
steel support system included to make a complete
installation.
Custom engineered for each application.

Voltage Class
600V
5 & 15kV
38kV

Continuous
Current
1200 - 6000
Amps
1200 - 6000
Amps
600 - 3000
Amps

Momentary
Withstand kA
Asymmetrical
87 113 133
62 78 98
39 49 62

ANSI/IEEE C37.23
UL/CSA Listed 600V, 5, & 15kV Metal Encl. Bus Syst.
ISO 9001
Seismically/OSHPD Certified

Standard
Aluminum Enclosure with enclosure as ground
600 V bus uses GP0-3 supports
5 and 15 KV bus use polyester supports
38 KV bus uses porcelain supports
Grade 5 Plated Steel Hardware
5-38 KV bus fully insulated with Cycloaliphatic Epoxy

Components/Options
Steel, Galvanized Steel, and Stainless Steel
Enclosure Material Options
Indoor or Outdoor Rated Enclosures
Vertical Elbows
Horizontal Elbows
Special Elbows
Transformer Terminations
Equipment Terminations (Fixed or Flex)
T-Taps
Term Boxes
600V, Half or Full Neutral
1/4 x 2 Copper Internal Ground Bus
Porcelain or High Alumina Ceramic Insulators
Stainless Steel or Silicone Bronze Bus Joint
Hardware
Epoxy Insulation for 600V Systems
Heaters, Heater Monitoring System
Phase Transpositions
Expansion Joints (Indoor or Outdoor)
Wall Entrance Seals
Fire Stops (1, 2, or 3 Hour)
Termination Boots
Trapeze Supports
Column Supports
Seismic Bus and Supports
Option to use in arc res applications
Consult factory for ratings or options not listed to
check for availability.
Made in USA

OPG = B + 2 "

JJ

1 FT - 3 INCH MIN. AND 24


FT. MAX

1"

C
A

2"

48

DUCT
CENTERED IN
WALL OPENING

OPG = A + 4 "

CROSS SECTION

STRAIGHT

HORIZONTAL ELBOW

04-May-04

Resistance

VOLTAGE &
MATERIAL

600

C
O
P
P
E
R
A
L
U
M

5,000
&
15,000

C
O
P
P
E
R
A
L
U
M

38,000

C
O
P
P
E
R
A
L
U
M

Ampere Wt./Ft.
Rating Lbs.
1200
1600
2000
2500
3200
4000
5000
6000
1200
1600
2000
2500
3200
1200
1600
2000
2500
3000
4000
5000
6000
1200
1600
2000
2500
3000
600
1200
1600
2000
2500
3000
600
1200
1600
2000

29
33
47
54
75
111
131
147
21
26
32
37
47
34
41
55
64
85
125
143
162
30
34
41
44
55
84
84
89
93
111
120
78
79
81
82

8
8
10
14
14
14
24
28
8
10
14
14
14
14
14
14
14
14
14
24
28
14
14
14
14
14
24
24
24
24
24
24
24
24
24
24

21
21
21
21
27
36
42
42
21
21
21
27
27
27
27
30
36
36
36
42
42
27
30
36
30
36
51
51
51
51
51
51
51
51
51
51

22
22
22
22
25
25
30
30
22
22
22
25
25
25
25
27
30
30
30
33
33
25
27
30
27
30
37
37
37
37
37
37
37
37
37
37

DIMENSIONS (INCHES)
D
E
F
G
11.38
11.38
12.38
14.38
14.38
14.38
14.38
19.38
11.38
12.38
14.38
14.38
14.38
14.38
14.38
14.38
14.38
14.38
14.38
19.38
21.38
14.38
14.38
14.38
14.38
14.38
24.00
24.00
24.00
24.00
24.00
24.00
24.00
24.00
24.00
24.00

15
15
16
18
18
18
18
23
15
16
18
18
18
18
18
18
18
18
18
23
25
18
18
18
18
18
23
23
23
23
23
23
23
23
23
23

48
48
48
48
60
60
60
60
48
48
48
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
84
84
84
84
84
84
84
84
84
84

22
22
22
22
25
25
30
30
22
22
22
25
25
25
25
27
30
30
30
33
33
25
27
30
27
30
37
37
37
37
37
37
37
37
37
37

18.25
18.25
19.25
21.25
24.25
24.25
28.75
33.75
18.25
19.25
21.25
24.25
24.25
24.25
24.25
25.75
28.75
28.75
28.75
36.75
38.75
24.25
25.75
28.75
25.75
28.75
45.88
45.88
45.88
45.88
45.88
45.88
45.88
45.88
45.88
45.88

28
28
30
34
34
34
34
44
28
30
34
34
34
34
34
34
34
34
34
44
48
34
34
34
34
34
48
48
48
48
48
48
48
48
48
48

17
17
17
17
20
20
25
25
17
17
17
20
20
20
20
22
25
25
25
28
28
20
22
25
22
25
33
33
33
33
33
33
33
33
33
33

PHASE TRANSPOSITION

Watt Loss

Microhms Per Three


Per Phase Phase Foot
Per Foot
10.76
46
8.50
65
5.79
70
4.71
88
3.91
120
3.47
166
2.78
209
2.41
260
13.41
58
8.76
67
6.16
74
5.61
105
4.10
126
15.09
65
8.50
65
5.79
70
4.71
88
4.03
109
3.47
166
2.78
209
2.41
260
13.41
58
8.76
67
6.16
74
5.68
107
4.32
117
15.44
17
15.44
67
10.76
83
8.37
100
4.68
88
3.99
108
25.46
27
17.23
74
13.41
58
11.33
136

WALL ENTRANCE
D

Reactance Impedance Capacitance


Microhms
Per Foot
44.29
43.46
37.05
29.23
31.84
41.93
42.54
24.76
43.46
37.05
28.79
31.84
31.11
56.50
54.37
51.20
48.76
42.88
41.93
42.54
24.76
54.37
51.20
48.32
42.52
41.93
76.97
76.97
68.89
62.93
53.83
53.39
76.97
68.89
68.06
62.28

UPPER ELBOW

Microhms Microfarads
Per Foot Per 1000 Feet
45.58
44.28
37.50
29.61
32.08
42.07
42.63
24.88
45.48
38.07
29.44
32.33
31.38
58.48
55.03
51.53
48.98
43.07
42.07
42.63
24.88
56.00
51.95
48.71
42.89
42.15
78.50
78.50
69.73
63.48
54.03
53.54
81.07
71.01
69.36
63.30

0.022
0.023
0.024
0.024
0.028
0.030
0.023
0.041
0.023
0.024
0.025
0.028
0.029
0.015
0.016
0.019
0.024
0.030
0.030
0.023
0.034
0.016
0.019
0.024
0.025
0.030
0.011
0.011
0.012
0.014
0.017
0.017
0.011
0.012
0.013
0.014

LOWER ELBOW

E
D
VERTICAL ELBOWS
C

UPPER

H
E
LOWER

TRANSITION

G
F
HORIZONTAL TEE
I
E

Notes:
1. Ampere ratings are based upon a maximun conductor rise of 650 C in a 400 C ambient in compliance with the temperature limits of ANSI / IEEE C37.23.
2. Resistance,watt loss,and impedance values are calculated using a maximum conductor temperature rise of 650C and a normal 200C ambient.
3. Weights and dimensions are for standard 3 phase totally enclosed non-ventilated aluminum enclosures.

VERTICAL TEE

Genneral Electric Company


41 Woodford Ave
Plainville, CT 06062
DET-322 09-2015

Você também pode gostar