1.0INTRODUCTION
2.0GENERAL CONSIDERATIONS
3.0CODES AND STANDARDS
4.0TECHNICAL SPECIFICATIONS
5.0LIST OF MATERIALS
6.0INSTALLATION TO PROTECT- BUILDING
7.0CALCULATION OF PROTECTION SYSTEM
8.0PROTECTION SYSTEM LIGHTNING DISCHARGE
9.0LIST OF MATERIALS

1.0 INTRODUCTION:
This paper describes the calculation memory system lightning protection
and description of materials for the project Insectaria downloads - Iquitos.

2.0 GENERAL:
These calculations are applicable only for the system lightning protection for
building protection considered the Insectaria Project - Iquitos and does not
apply to other facilities and / or staff that may be located near it.

The materials described herein, will be used in the system type Building
Faraday cage protection, they have been selected according to the rules and
calculations in this document.

For the distribution of air terminals and area calculation system protection
against lightning, it will continue as indicated in the regulations for
installation of lightning protection systems: NFPA 780, UNE EN62305.

3.0 CODES AND STANDARDS:


The following are considered:
NFPA National Fire Protection Association
IEC International Electromechanical Commission
UL Underwriter's Laboratories
CNE National Electrical Code.

4.0 TECHNICAL SPECIFICATIONS:


4.1. air terminal

monopuntal metallic element (lightning rod) fixed by the fastener. Performs


load concentration at the tip allowing uptake of atmospheric discharge.
Made of solid copper.
Diameter: 1/2 ''.
Length: 24 '' (about 60 cm.).
It has threaded mounting adapter.
Brand: Thompson.
Product code: 572.
Class 1, Class 2.
UL standard.
Image
Copper Air Terminal

4.2. articulated base

Element articulated ceiling bracket allows installation of the air terminal by


adjusting the position thereof according to the space where it will be
supported.
Made of brass.
Holes for attachment: 1/4 ''.

Threaded adapter for attaching terminal.


TV swivel base for terminal guidance.
Morseto embedded copper cable.
Brand: Thompson.
Product code: 30.
Class 1, Class 2.
standard UL

4.3. Fastening clamp


Metal retaining element for roof, can secure the cable grounding ordered
manner on the support surface.
Made of brass.
Securing one or two copper wires.
Hexagonal steel bolt.
Brand: Thompson.
Product code: 613.
Class 1, Class 2.
UL FormaEstndar

Fastening clamp

4.4. Copper wire

Element metallic conductor of low resistance to facilitate the conduct power


electric shock to the system ground wells.

Bare copper, soft temper


Section 70 mm2 (2/0 AWG equivalence).
Consisting of 19 wires.
Approximate weight 613 kg / km.
Brand: Indeco (suggested).
Class 2.

NTP legislation 370251


5. LIST OF MATERIALS

ITEM
DESCRIPTION
QUANTITY
CODE
1
air terminal
08 pcs
572
2
articulated base
08 pcs
30
3
Fastening clamp
10 pcs
613
4
Bare copper wire 70 mm2
85 m
N/A
5
Pivoting adapter p / pararrayo
08 und
N/A
6
Clamp w / tube 1 "" Screw
06 und
N/A

7
Conduit adapter tube - corrugated tube
02 und
N/A

6. INSTALLATION TO PROTECT - BUILDING

The building to be protected within the project has the following dimensions:
Length: 13,818 m.
Width: 8.36 m.
Height: 9.75 m (approx.)
Equipment to be protected:
- Lab.
- Electronic equipment.
- Switchboard.

Imagende according to the characteristics of the building, protection


mediantes air terminals to be installed on the roof is sufficient to cover the
entire building. The system characteristics are determined according to the
results of the risk assessment method applied design and specifications as
standard.

Você também pode gostar