Você está na página 1de 11

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.

3
Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Project:
Project-No:
Building:
Object:
Contractor:
Owner:
Project engineer:
Date:
Altitude above sealevel:
Regulation rule for calculation of Nitrogen quantities:

Example

Pipe catalogue:
Component catalogue:
Nozzle catalogue:

sbt-fis.rkl
sbt-fis.arm
sbt-fis.noz

11/1/2016
0m
NFPA 2001, Edition 2000

Page: 1
Serial no: N217703
11/1/2016

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 2
Serial no: N217703
11/1/2016

Pipesystem data:
SectionNo:

Startingnode

Endnode
Nozzle

Length
[m]

Height
[m]

Pipetype

Diameter
[mm] **

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

0
4
5
0
1
2
3
6
7
8
9
10
11
11
12
9
13
14
14
15
7
16
17
18
18
19
16
20
21
21
22

4
5
3
1
2
3
6
7
8
9
10
11
11008
12
11007
13
14
11005
15
11006
16
17
18
11004
19
11003
20
21
11002
22
11001

1.500
2.000
1.000
1.500
2.000
1.000
2.000
5.000
3.000
1.000
1.500
2.000
0.500
2.000
0.500
1.500
2.000
0.500
2.000
0.500
1.000
1.500
2.000
0.500
2.000
0.500
1.500
2.000
0.500
2.000
0.500

1.500
0.000
0.000
1.500
0.000
0.000
2.000
0.000
-3.000
0.000
0.000
0.000
-0.500
0.000
-0.500
0.000
0.000
-0.500
0.000
-0.500
0.000
0.000
0.000
-0.500
0.000
-0.500
0.000
0.000
-0.500
0.000
-0.500

11
12
12
11
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
11
11
11
11
11
11
11
11
11

23.4
36.5
42.5
14.3
36.5
42.5
42.5
42.5
16.0
16.0
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
36.5
28.5
28.5
16.0
16.0
16.0
28.5
28.5
16.0
16.0
16.0

* C=Component, B=Bend, T=T-Piece, E=Elbow, R=Restrictor


** If a pipe diameter is equal zero see the extra table of the calculated diameters

Legend of pipetypes
Type Pipeclass

Pipe roughness

11
12

galvanized
hose

Medium Class certified (DIN 2440/2442/2444)


Medium Class certified (DIN 2440/2442/2444)

Fitting
*

B
B
B
B
R
B
T-90
B
T-90
B
T-90
T-0
B
T-90
B
T-90
T-0
B
T-0
T-90
B
T-90
T-0
B
T-90
B
T-90
T-0
B

Component
code
coefficient

Nb of containers
Nitrogen quantity

6.0
0.0
0.0
6.0
0.0
0.0
-1.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 3
Serial no: N217703
11/1/2016

Nozzle data:
No.

Calculation zone

Diameter [mm]

11001
11002
11003
11004
11006
11005
11007
11008

room
room
room
room
double floor
double floor
double floor
double floor

13.0
12.1
13.0
12.1
5.8
5.8
5.8
5.8

Legend of nozzles and restrictor:


Type
Number of
orifices

C1

C2

C3

C4

C5

C6

1 Cerexen Type 2000


Restrictor

-0.284
0.035

0.000
-0.036

0.056
0.000

0.000
0.000

0.000
0.000

0.000
0.000

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 4
Serial no: N217703
11/1/2016

Calculation zone data:


Calculation of design quantity:
Zone

Total
volume
[m3]

Volume of
building
parts [m3]

Calculated
volume
[m3]

Total
surface
[m2]

Max. Overpressure
[mbar]

Design
temp.
[C]

Extinguish- Design
conc.
factor
[% Vol]

Design
conc.
[% Vol]

Design
quantity
[kg]

1 room

147.0

0.0

147.0

182.0

1.000

20.0

34.8

1.30

45.2

103.03

2 double floor

24.5

0.0

24.5

112.0

1.000

20.0

34.8

1.30

45.2

17.17

Regulation rule for calculation of Nitrogen quantities: NFPA 2001, Edition 2000
Altitude above sealevel: 0.0 m

Nitrogen storage input data:

Container volume:

80.0 l

Container pressure:

200.0 bar abs

Storage temperature:

15.0 C

Supplement factor:

1.10

Minimum storage quantity:

132.22 kg

Number of containers:

12

Discharge time (input value):

60.0 s

Pressure downstream restrictor:

60.0 bar

Further information:
Design with included gas discharge time
Design with predeterminated orifice diameters
Design with predeterminated restrictor diameter

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Calculation results:
Nitrogen design data:
Design quantity:
Supplement factor:
Minimum storage quantitiy:

120.20
1.10
132.22

Container volume:
Container pressure:
Nitrogen-mass in one container:
Number of containers:
Actual storage quantity:

80.0 l
200.0 bar abs
17.9 kg
12
214.8 kg

Storage temperature:
Starting container pressure:

15.0 C
200.0 bar abs

Discharge time:
Total discharge time of air and Nitrogen:

30.1 s

System information:
Restrictor diameter:

14.0 mm

Container working pressure:


Total network volume:

162.3 bar abs


25.7 l

Page: 5
Serial no: N217703
11/1/2016

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 6
Serial no: N217703
11/1/2016

Pipe system:
SectionStartingNo:
node

Endnode
Nozzle

Pressure
[bar abs]

Temperature Flowrate
[C]
[kg/s]

Pipedimension
Di [mm]
DN

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

4
5
3
1
2
3
6
7
8
9
10
11
11008
12
11007
13
14
11005
15
11006
16
17
18
11004
19
11003
20
21
11002
22
11001

162.24
162.09
161.84
162.05
161.89
161.84
49.93
48.38
44.58
42.62
38.96
36.58
34.52
35.45
35.16
38.96
36.58
34.52
35.45
35.16
47.61
45.31
44.25
41.56
39.54
35.61
45.25
44.19
41.50
39.49
35.56

7.30
7.29
7.25
7.28
7.26
7.25
-13.13
-13.77
-14.87
-15.80
-16.47
-17.75
-17.82
-18.04
-18.19
-16.47
-17.75
-17.82
-18.04
-18.19
-13.92
-14.09
-14.57
-15.17
-16.99
-19.61
-14.12
-14.60
-15.20
-17.02
-19.63

24.3 *
36.5 *
42.5 *
15.2 *
36.5 *
42.5 *
42.5 *
42.5 *
16.0
16.0
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
12.5 *
36.5 *
28.5 *
28.5 *
16.0
16.0
16.0
28.5 *
28.5 *
16.0
16.0
16.0

0
4
5
0
1
2
3
6
7
8
9
10
11
11
12
9
13
14
14
15
7
16
17
18
18
19
16
20
21
21
22

* Attention! This pipe dimension is not in the pipe catalogue!

0.38
2.30
2.30
0.38
2.30
2.30
4.60
4.60
0.72
0.72
0.36
0.36
0.18
0.18
0.18
0.36
0.36
0.18
0.18
0.18
3.88
1.94
1.94
0.97
0.97
0.97
1.94
1.94
0.97
0.97
0.97

-11/4
11/2
1/2
11/4
11/2
11/2
11/2
1/2
1/2
----------11/4
1
1
1/2
1/2
1/2
1
1
1/2
1/2
1/2

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 7
Serial no: N217703
11/1/2016

Nozzle data:
Calculationzone no:

Nozzle
no.

Nozzle
type

Number of
orifices

Pipeconnection
Di [mm]
DN

Orifice
[mm]

Nitrogen output [kg]

1
1
1
1
2
2
2
2

11001
11002
11003
11004
11006
11005
11007
11008

1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1

16.0
16.0
16.0
16.0
12.5
12.5
12.5
12.5

13.0
12.1
13.0
12.1
5.8
5.8
5.8
5.8

25.3
25.4
25.4
25.4
4.7
4.7
4.7
4.7

1/2
1/2
1/2
1/2
-----

MAX. TRANSPORT TIME DIFF. BETWEEN NOZZLES: 11007./ 11002. IS 0.13 S

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 8
Serial no: N217703
11/1/2016

Concentrations:
Calculationzone no:

O2

1
2

11.5
10.8

Gascomposition after the discharge of the design quantity [%]


AR
N2
0.5
0.5

88.0
88.7

Total flooded design quantity within discharge time: 120.20 kg

Calculationzone no:

O2

1
2

7.2
6.4

Gascomposition after total discharge [%]


AR
N2
0.3
0.3

92.5
93.3

Total flooded Nitrogen mass: 213.7 KG

Pressure relief opening:


Calculationzone no:

Recommended area against overpressure


Area [m]
Overpressure [mbar]

Max. flow [kg/s]

1
2

0.469
0.087

4.80
0.89

1.0
1.0

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 9
Serial no: N217703
11/1/2016

Component list:
Nozzle-type

Number

C1

C2

C3

C4

C5

C6

1
Restrictor

8
1

-0.284
0.035

0.000
-0.036

0.056
0.000

0.000
0.000

0.000
0.000

0.000
0.000

Pipe-type

Di [mm]

DN

Length [m]

11
12
12
11
12
12
12
11
11

24.25
36.50
42.50
15.15
16.00
12.50
28.50
28.50
16.00

-11/4
11/2
-1/2
-1
1
1/2

1.500
5.000
9.000
1.500
4.000
13.000
1.500
5.500
6.000

Number of bends (+) and elbows (-)


Bend-type

Di [mm]

DN

Number

90
90
90
90
90
90

36.50
42.50
16.00
12.50
28.50
16.00

11/4
11/2
1/2
-1
1/2

2
3
1
4
2
2

Number of T-distributors (in- and outdiameter)


Number

Input

90-out

90-out

0-out

1
1
2
1
2
1

42.5
16.0
12.5
36.5
28.5
42.5

16.0
12.5
12.5
28.5
16.0
42.5

0.0
12.5
0.0
28.5
0.0
42.5

36.5
0.0
12.5
0.0
16.0
0.0

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

Page: 10
Serial no: N217703
11/1/2016

Dynamic flooding results


The calculation bases on a mean nozzle pressure!
Flooding
time [s]

Storage
mass [kg]

Flooded
ratio [%]

Flow
[kg/s]

Storage
Pressure downstream Pressure at
pressure [bar] restrictor [bar]
nozzle [bar]

0.0
2.1
2.3
2.6
2.8
3.1
3.3
3.8
4.3
4.8
7.3
9.3
11.0
16.0
21.0
26.0
31.0
36.0
41.0
46.0
51.0
56.0
61.0
66.0
71.0
76.0

214.8
195.8
194.4
193.1
191.8
190.5
189.2
186.7
184.2
181.8
170.0
161.3
153.2
135.3
119.8
106.4
94.7
84.3
75.1
66.9
59.6
53.2
47.4
42.3
37.6
33.5

0.0
8.9
9.5
10.1
10.7
11.3
11.9
13.1
14.3
15.4
20.8
24.9
28.7
37.0
44.2
50.5
55.9
60.8
65.1
68.9
72.2
75.2
77.9
80.3
82.5
84.4

0.00
5.40
5.35
5.28
5.24
5.18
5.13
5.08
4.99
4.90
4.58
4.27
3.98
3.34
2.94
2.53
2.20
1.99
1.76
1.55
1.38
1.23
1.10
0.99
0.89
0.80

200.0
178.6
176.5
174.5
172.4
170.5
168.5
165.5
162.2
158.9
144.6
133.5
123.3
102.3
86.2
73.6
63.7
55.6
48.8
43.2
38.4
34.4
30.9
27.9
25.2
22.8

Discharge meantime at nozzle:

30.1 s

1.0
60.2
59.5
58.8
58.1
57.4
56.8
56.1
55.1
54.0
50.0
46.3
42.7
35.3
30.5
26.0
22.5
20.2
17.7
15.6
13.9
12.4
11.2
10.0
9.1
8.2

1.0
43.0
42.5
42.0
41.5
41.0
40.5
40.0
39.4
38.6
35.7
33.0
30.4
25.1
21.7
18.5
16.0
14.3
12.5
11.0
9.8
8.8
7.9
7.1
6.4
5.8

VdS SCHADENVERHTUNG Nitrogen-Calculationprogram Version 7.3


Licenced to: PT Siemens Cerberus Fire Safety Jakarta, Indonesien
File: C:\N2\projects\Example.prj - Results

225

Storage mass [kg]

Page: 11
Serial no: N217703
11/1/2016

90

200

80

175

70

150

60

125

50

100

40

75

30

50

20

25

10

0
0

6.0

10

20

30

40
Time [s]

50

60

70

80

Flow [kg/s]

Flooded ratio [%]

0
0

200

10

20

30

40
Time [s]

50

60

70

80

30

40
Time [s]

50

60

70

80

40
Time [s]

50

60

70

80

Storage pressure [bar]

175

5.0

150
4.0

125

3.0

100
75

2.0

50
1.0

25

0.0
0

70

10

20

30

40
Time [s]

50

60

70

80

Pressure downstream restrictor [bar]

0
0

45

10

20

Pressure at the nozzle [bar]

40

60

35
50

30

40

25

30

20
15

20

10
10
0
0

5
10

20

30

40
Time [s]

50

60

70

80

0
0

10

20

30

Você também pode gostar