Você está na página 1de 4

Analisis Perhitungan Struktur Gelagar Chiller

Layout Gelagar Chiller

Pembebanan Chiller

Pembebanan Pada Gelagar


P1 = 2210 Kg P1 = 1,2 x 2210 Kg = 2652 Kg
P2 = 3060 Kg P2 = 1,2 x 3060 Kg = 3660 Kg

P1 = 2652 Kg
P2 = 3660 Kg

P1 = 2652 Kg

P2 = 3660 Kg

Hasil Analisa Dengan Bantuan Program Staad Pro


Diagram Momen yang Terjadi :

Hasil Momen Maksimum

Analisa Lentur Balok


Momen Nominal
Mu = 32,93 kNm 3,36 tm
Mu 3,36

0
,
9
0,9 = 3,734 tm
Mn =
Profil yang digunakan adalah Profil WF 300.150.9.6,5 dengan Mutu baja BJ 37 (Fy = 240 MPa)
Data Teknis :

D
B
Tf
To
Tw
Zx
Zy

= 300 mm
= 150 mm
= 9 mm
= 13 mm
= 6,5 mm
= 481 cm3
= 67,7 cm3

= d 2 (To + Tf)
= 300 2 (13 + 9)
= 256 mm

Cek Kelangsingan Penampang

f = = = 8,33
w = = = 39,38
p = = = 108,44

Penampang Kompak

Momen Plastis
Mp

= Zx . fy
= 481.000 mm3 x 240 MPa
= 115.440.000 Nmm 11,768 tm

Mp > Mn Aman