SE-704 MANUAL
EARTH-LEAKAGE MONITOR
REVISION 7-C-082814
Page i
Rev. 7-C-082814
Page ii
Rev. 7-C-082814
TABLE OF CONTENTS
SECTION
LIST OF FIGURES
PAGE
General....................................................................... 1
Operation................................................................... 1
2.1 Configuration-Switch Settings ................................... 1
2.1.1 Relay Operating Mode ................................... 1
2.1.2 Filter Selection................................................ 1
2.1.3 CT Verification............................................... 1
2.1.4 Reset Mode ..................................................... 1
2.1.5 Analog Output ................................................ 1
2.2 Front-Panel Controls .................................................. 1
2.2.1 Earth-Leakage Trip Level .............................. 1
2.2.2 Earth-Leakage Trip Time............................... 1
2.2.3 Reset................................................................ 1
2.2.4 Test.................................................................. 3
2.3 Front-Panel Indication ................................................ 3
2.3.1 Power .............................................................. 3
2.3.2 Trip.................................................................. 3
2.3.3 CT Verification............................................... 3
2.4 Analog Outputs........................................................... 3
2.5 Self Diagnostics .......................................................... 3
3
Installation................................................................. 3
4
SE-704 Compatibility............................................... 5
5
Technical Specifications ........................................ 11
5.1 SE-704 ...................................................................... 11
5.2 Current Sensors ........................................................ 13
6
Ordering Information............................................ 14
7
Warranty ................................................................. 14
8
Earth-Fault Performance Test ............................. 15
Appendix A SE-704 Revision History........................ 16
1
2
FIGURE
1
2
3
4
5
6
7
8
9
10
PAGE
LIST OF TABLES
PAGE
TABLE
1
2
DISCLAIMER
Specifications are subject to change without notice.
Littelfuse Startco is not liable for contingent or
consequential damages, or for expenses sustained as a
result of incorrect application, incorrect adjustment, or a
malfunction.
Page iii
Rev. 7-C-082814
2. OPERATION
2.1 CONFIGURATION-SWITCH SETTINGS
See Fig. 1.
2.1.1 RELAY OPERATING MODE
Switch 1 is used to set the operating mode of the output
relay. In the fail-safe mode, the output relay energizes
when the earth-leakage circuit is not tripped. In the failsafe mode, non-volatile memory retains the trip status of
the SE-704. If tripped, and the supply voltage is cycled,
the SE-704 will remain tripped, with the trip relay deenergized and the TRIP LED on, until reset.
In the non-fail-safe mode, the output relay energizes
when an earth-leakage trip occurs. In the non-fail-safe
mode, trip status is not retained in non-volatile memory.
2.1.2 FILTER SELECTION
Switch 2 is used to select the filtering algorithm for a
fixed-frequency (50/60 Hz) or variable-frequency
application, for earth-leakage trip levels of 500 mA or
less. The peak-detection algorithm is used for settings
greater than 500 mA, regardless of the filter selection.
The FIXED FREQUENCY setting uses a DFT filter
that allows lower trip levels to be used by rejecting
harmonics that can cause nuisance tripping.
The
VARIABLE FREQUENCY setting uses a peak-detection
algorithm with a wider band width for fault detection in
variable-frequency drive applications.
Page 1
Rev. 7-C-082814
2.1.3 CT VERIFICATION
Switch 3 is used to enable CT verification. In the
ON position, a trip will occur if the SE-CS30 current
sensor is disconnected.
2.1.4 RESET MODE
Switch 4 is used to select autoreset or latching trips.
See Section 2.2.3.
2.1.5 ANALOG OUTPUT
Switch 5 is used to select analog-output scaling.
Selecting % OF 5A results in full scale output (1 mA or
5 V) when earth-fault current is 5 A. Selecting
% OF SETTING results in full scale output when earthfault current equals the trip-level setting. See Section
2.4.
2.2 FRONT-PANEL CONTROLS
2.2.1 EARTH-LEAKAGE TRIP LEVEL
The LEVEL (mA) selection switch is used to set the
earth-leakage trip level. For earth-leakage detection, the
earth-leakage trip level must be substantially below the
prospective earth-fault current. To avoid sympathetic
tripping, the trip level must be above the charging current of
the protected feeder.
2.2.2 EARTH-LEAKAGE TRIP TIME
The SE-704 has a definite-time trip characteristic. The
TIME (ms) selector switch is used to set the earth-leakage
trip time for coordination with upstream and downstream
earth-fault devices. Coordination requires the same trip
level for all earth-leakage devices in a system and the trip
time to progressively increase upstream. The amount of
equipment removed from the system will be a minimum if
the first earth-leakage device to operate is the one
immediately upstream from the fault.
2.2.3 RESET
If the Reset Mode switch is in the LATCHING
position, a trip remains latched until the RESET button
is pressed or the remote-reset terminals (6 and 7) are
momentarily connected. In the non-fail-safe relay
operating mode, cycling the supply voltage will also
reset the SE-704.
If the Reset Mode switch is in the AUTORESET
position, a trip will reset when the fault is removed.
The reset circuit responds only to a momentary
closure so that a jammed or shorted button will not
prevent a trip. The front-panel RESET button is
inoperative when the remote-reset terminals are
connected.
Page 2
Rev. 7-C-082814
55.0
(2.17)
37.5
(1.48)
8.7
(0.34)
CONFIGURATION
SWITCHES
RESET MODE
LATCHING
CT VERIFICATION
OFF
FILTER SELECTION
FIXED
FREQUENCY
% OF SETTING
AUTORESET
% OF 5 A
% OF SETTING
RESET MODE
LATCHING
AUTORESET
CT VERIFICATION
OFF
ON
FILTER SELECTION
FIXED
FREQUENCY
VARIABLE
FREQUENCY
FAIL-SAFE
NON-FAIL-SAFE
NOTE 2
61.2
(2.41)
75.0
(2.95)
CONFIGURATION
SWITCHES
ANALOG OUTPUT
% OF 5 A
ANALOG OUTPUT
ON
VARIABLE
FREQUENCY
NON-FAIL-SAFE
S1 S2 RS
1
4C4T. 5
MOUNTING DETAIL
0-1 mA 0- 5 V
ANALOG OUTPUT
113.0 (NOTE 3)
(4.45)
110.0
(4.33)
TOP
55.0
(2.17)
LITTELFUSE STARTCO
EARTH-LEAKAGE MONITOR
CT
100
80
60
30
300
SE-704
TRIP
500
1000
3000
5000
10
LEVEL (mA)
300
200
100
55
400
500
1000
1500
2000
30
TIME (ms)
TEST
75.0
(2.95)
PWR
6.3
(0.25)
RESET
SIDE
FRONT
NOTES:
9 1 0 1 1 1 2 13 1 4 1 5 16
LN2 L 1
BOTTOM
6.9
(0.27)
NOTE 5
Page 3
Rev. 7-C-082814
3. INSTALLATION
NOTE: Mounting, terminal-block connections and wiring
must conform to applicable local electrical codes. Check
all applicable codes prior to installation.
This earth-leakage monitoring system consists of an
SE-704 Earth-Leakage Monitor and an SE-CS30-series
current sensor connected as shown in Figs. 2 and 3.
An SE-704 can be surface or DIN-rail mounted. See
Fig. 1. Panel mounting requires a PMA-55 or PMA-60
Panel-Mount Adapter. See Figs. 7 and 8.
Use terminal 11 (L1) as the line terminal on ac systems
or the positive terminal on dc systems. Use terminal 10
(L2/N) as the neutral terminal on ac systems or the
negative terminal on dc systems. Connect terminal 9 ( )
to earth.
Pass the phase conductors through the CT window and
position them in the centre of the openingfor 4-wire
and single-phase systems also pass the neutral conductor
through the CT window, as shown in Figs. 2 and 3. Do
not pass earth conductors through the CT window. In
applications that require shields or drain wires to pass
through the CT window, return them through the CT
window before connecting them to earth. Connect the
SE-CS30-series current sensor to terminals 4 and 5,
connect the shield to terminal 5, and earth terminal 5. See
Figs. 4, 5, and 6 for SE-CS30 current-sensor dimensional
drawings.
Remove the connection to terminal 9 for dielectricstrength testingall inputs and outputs have ANSI/IEEE
C37.90 surge protection circuits that conduct above
300 Vac.
Page 4
Rev. 7-C-082814
SE-CS30 SERIES
A
B
SE-CS30 SERIES
SE-CS30 SERIES
L
N
N
11
S1
S2
S1
S2
SE-704
L2
N
L1
13
15
ISOLATED CONTACTS
1-PHASE
CONNECTION
16
SE-704
REMOTE RESET
6
14
RS
RESET
7
LEAKAGE
ANALOG
OUTPUT
PGA-05CV PGA-0500
NOTE:
INDICATION
G
PWR
CT
TRIP
SE-CS30 SERIES
A
B
C
N
4
S1
S2
13
14
START
STOP
11
REMOTE RESET
6
1M
16
L1
SE-704
L2
N
10
RS
RESET
7
LEAKAGE
O/L
1M
ISOLATED CONTACTS
15
ANALOG
OUTPUT
PGA-0500
NOTE 1
INDICATION
G
PWR
CT
TRIP
NOTES:
9
5
S2
SE-704
3-PHASE, 4-WIRE
CONNECTION
10
4
S1
14
N
14
Page 5
Rev. 7-C-082814
Fail-safe
Non-fail-safe
00
Yes
Yes
No
Trip LED: Off
Trip relay: Energized
Trip flag: Red
Trip LED: Off
Trip relay: De-energized
Trip flag: Red
01
Yes
No
Yes
Trip LED: On
Trip relay: De-energized
Trip LED: Off
Trip relay: De-energized
Page 6
Rev. 7-C-082814
68.0
(2.68)
34.0
(1.34)
68.0
(2.68)
M4 OR 8-32 TAP
26.5
(1.04)
52.5
(2.07)
42.6
(1.68)
17.0
(0.67)
MOUNTING DETAIL
TOP
(0.43)
110.0 MAX
M5 SCREWS
25.0
(0.98)
26.5
(1.04)
SE-CS30-26
CURRENT SENSOR
R
LR 53428
US
4.0 (0.16)
.
26
RECESSED FOR
7-mm HEX NUT
3.0 (0.12) DEEP
2)
7.0
.0
(1
58.0
(2.28)
(0.87)
34.0
(1.34)
72.0
(2.83)
5.0
(0.20)
5.0
(0.20)
52.5
(2.07)
FRONT
SIDE
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL A).
MOUNTING FOOT
INSTALLA TION
TOOL
DETAIL A
Page 7
Rev. 7-C-082814
121.0
(4.76)
121.0
(4.76)
20.5
80.0
(3.15)
56.0
(2.21)
46.0
(1.81)
30.0
(1.18)
(0.81)
NOTE 3
M5 SCREWS
TOP
MOUNTING DETAIL
25.0
(0.98)
(1.18)
30.0
SE-CS30-70
CURRENT SENSOR
R
LR 53428
22.0
5.0 (0.20)
RECESSED FOR
8-mm HEX NUT
1.0 (0.04) DEEP
5.5
110.0
5.5
(0.22)
(4.33)
(0.22)
56.0
(2.21)
SIDE
FRONT
MOUNTING FOOT
INSTALLATION
TOOL
126.0
69.
8
(2.7
5)
(4.96)
US
(0.87)
(5.43)
138.0 MAX
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. PRESS MOUNTING FEET IN PLACE USING
INSTALLATION TOOL PROVIDED (DETAIL A).
3. MOUNTING SCREWS: M4 OR 8-32.
DETAIL A
4. RoHS COMPLIANT.
5. EN 60044-1 COMPLIANT.
Page 8
Rev. 7-C-082814
C
D
14.0
(0.55)
72.0
(2.83)
MOUNTING DETAIL
NOTES:
SE-CS30-8
OUTLINE
4. CE COMPLIANT.
DIMENSIONS
I
L
D
C
BOTTOM
FRONT
1.7
(0.07)
FLUX
CONDITIONER
SE-CS30-4
SE-CS30-5
SE-CS30-8
95.0 (3.74)
130.0 (5.12)
200.0 (7.87)
141.0 (5.55)
82.0 (3.22)
32.0 (1.26)
32.0 (1.26)
34.0 (1.34)
17.5 (0.69)
11.0 (0.43)
11.0 (0.43)
15.0 (0.59)
13.3 (0.52)
13.3 (0.52)
33.0 (1.30)
34.0 (1.34)
43.0 (1.69)
9.0 (0.35)
11.0 (0.43)
11.5 (0.45)
40.0 (1.57)
40.0 (1.57)
50.0 (1.97)
5.3 (0.21)
7.0 (0.28)
7.0 (0.28)
Page 9
Rev. 7-C-082814
110.0
(4.33)
85.0
(3.35)
PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)
CT
100
80
60
30
300
TRIP
500
1000
3000
5000
10
LEVEL (mA)
300
200
100
55
400
500
1000
1500
2000
30
TIME (ms)
TEST
75.0
(2.95)
PWR
SE-704
85.0
(3.35)
42.5
(1.67)
6-32
LITTELFUSE STARTCO
EARTH-LEAKAGE MONITOR
6-32
RESET
BRACKET
(0.37)
6.0
(0.24)
(2.36)
79.0
(3.11)
INSTALLATION INSTRUCTIONS:
1. REMOVE BEZEL AND LATCH MONITOR TO
BRACKET.
2. INSERT BRACKET THROUGH FRONT OF PANEL
CUTOUT AND SECURE WITH FLAT WASHERS AND
LOCKNUTS PROVIDED.
60.0
42.5
(1.67)
30.0
(1.18)
6.0
(0.24)
85.0
(3.35)
72.0
(2.83)
60.0
(2.36)
SIDE VIEW
9.5
FRONT VIEW
55 mm (2.2) WIDE
MONITOR
ALTERNATE
CONFIGURATIONS
NOTE:
9.5
(0.37)
Page 10
Rev. 7-C-082814
116.0
(4.57)
99.0
PANEL THICKNESS
1.6 (0.06) TO 4.8 (0.19)
(3.90)
CT
100
80
60
30
300
SE-704
TRIP
500
1000
3000
5000
10
LEVEL (mA)
300
200
100
55
400
500
1000
1500
2000
30
TIME (ms)
TEST
75.0
(2.95)
PWR
88.0
(3.46)
44.0
(1.73)
M4
LITTELFUSE STARTCO
EARTH-LEAKAGE MONITOR
M4
RESET
BRACKET
TRANSPARENT
COVER (NOTE 2)
FRONT VIEW
6.0
(0.24)
60.0
(2.36)
79.0
(3.11)
44.0
(1.73)
30.0
(1.18)
SIDE VIEW
INSTALLATION INSTRUCTIONS:
9.5
(0.37)
6.0
(0.24)
99.0
(3.90)
72.0
(2.83)
60.0
(2.36)
55 mm (2.2) WIDE
MONITOR
ALTERNATE
CONFIGURATIONS
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
9.5
(0.37)
Page 11
Rev. 7-C-082814
67.5
(2.657)
67.5
(2.657)
48.0
(1.890)
66.0
(2.598)
R1.25(0.049)
MAXIMUM
NOTES:
1. CONVERSION KIT FOR 0-5 V ANALOG
OUTPUT. SEE PGA-0500 DOCUMENTATION.
2. DIMENSIONS IN MILLIMETRES (INCHES).
TOP
MOUNTING CUTOUT
NOTE 1
100
20
65.0
(2.559)
60
40
71.0
(2.795)
80
0
PGA-0500
ANALOG % CURRENT METER
FRONT
SIDE
REAR
5. TECHNICAL SPECIFICATIONS
5.1 SE-704
Supply:
0U Option ..............................5 VA, 120 to 240 Vac,
(+20, -55%) 50/60 Hz,
2 W, 100 to 240 Vdc,
(+20, -25%)
0D Option ..............................2 W, 12 to 30 Vdc,
(+20, -25%)
0T Option ...............................2 W, 40 to 55 Vdc,
(+20, -25%)
03 Option ...............................2.5 VA, 24 Vac,
(+15%, -40%), 50/60 Hz
Trip-Level Settings ......................10, 30, 60, 80, 100, 300,
500, 1,000, 3,000, and
5,000 mA
Trip-Time Settings.......................30, 55, 100, 200, 300, 400,
500, 1,000, 1,500, and
2,000 ms
Accuracies: (1, 2)
Trip Level: (3, 4)
1,000 to 5,000 mA ............. + 2, -10% (60 Hz)
+ 0, -12% (50 Hz)
60 to 500 mA...................... + 0, -10%, 10 mA min
30 mA ................................. + 0, -6 mA
10 mA ................................. + 4, -1 mA
Trip Time (5) ........................... 5% of setting, 20 ms min
Input:
Algorithms (6) ......................... DFT Digital or Peak
DFT 3 dB Frequency
Response ................................ 32 to 86 Hz (<1,000 mA)
Peak 3 dB Frequency
Response ................................ 20 to 420 Hz (<1,000 mA)
Peak 3 dB Frequency
Response ................................ 20 to 120 Hz (1,000 mA)
CT ............................................ SE-CS30-Series Current
Sensor
CT Detection ...................... Open-Circuit Detection
Thermal Withstand:
Continuous ......................... 25 A Earth-Fault Current
1-Second ............................. 400 A Earth-Fault Current
Page 12
Rev. 7-C-082814
3,000 m (9,843) ............ 40 to 55C
(-40 to 131F)
5,000 m (16,404) .......... 40 to 50C
(-40 to 122F)
Storage Temperature ........... 55 to 80C
(-67 to 160F)
Humidity ................................85% Non-Condensing
Altitude...................................5,000 m (16,404)
maximum
PWB Conformal Coating ............MIL-1-46058 qualified
UL QMJU2 recognized
Surge Withstand ..........................ANSI/IEEE 37.90.1-1989
(Oscillatory and Fast
Transient)
Vibration ......................................EN60255-21-1
(Vibration, Shock, and
Seismic)
EN60255-21-2 (Shock
and Bump)
EMC Tests:
Verification tested in accordance with EN 50263:2000
Radiated and Conducted
Emissions................................CISPR 11:2009,
CISPR 22:2008,
EN55022:2010
Class A
Current Harmonics and
Voltage Fluctuation ................IEC 61000-3-2 and
IEC 61000-3-3
Class A
Electrostatic Discharge ..........IEC 61000-4-2
6 kV contact discharge
(direct and indirect)
8 kV air discharge
Radiated RF Immunity...........IEC 61000-4-3
10 V/m, 80-1000 MHz,
80% AM (1 kHz)
10 V/m, 900 MHz,
200 Hz pulse modulated
Fast Transient .........................IEC 61000-4-4
4 kV on AC mains and
I/O lines
Page 13
Rev. 7-C-082814
UL Listed
Australia
N11659
FCC
NOTES:
Detection limit (A) = (setting in mA 5,610)/-1.4.
(2)
At 50 or 60 Hz unless otherwise noted.
(3)
SE-CS30-series current sensor included.
(4)
Maximum lead resistance of 2 .
(5)
Trip Time at 3 x trip-level setting.
(6)
Peak algorithm for trip-level setting 1,000 mA.
(1)
Page 14
Rev. 7-C-082814
7. WARRANTY
SE-704-0 -
Conformal Coating:
Blank Partial Conformal Coating
CC Full Conformal Coating
Supply:
3 24-Vac Supply
U Universal 120/240-Vac/Vdc Supply
D 12/24-Vdc Supply
T 48-Vdc Supply
Page 15
Rev. 7-C-082814
SE-CS30
FROM
POWER
SOURCE
LOAD
R1 L
N
ITEST
11
10
L1
L2/N
L
N
3
5
OP1
8
9
OP2
12
L1
L2
REMOTE
TEST
SE-704
R2
11
S1 S2
SE-400
RMT1
RMT2
R1 = 1 , 10 W, 1%
R2 = 0.1 , 10 W, 1%
ITEST = 1/10 SE-400 SETTING
TEST RESULTS
Page 16
Rev. 7-C-082814
MANUAL
RELEASE DATE
APPENDIX A
SE-704 REVISION HISTORY
MANUAL
PRODUCT REVISION
REVISION
(REVISION NUMBER ON PRODUCT LABEL)
7-C-082814
7-B-052114
April 8, 2013
7-A-040813
04