Escolar Documentos
Profissional Documentos
Cultura Documentos
KFD2-STC4-Ex2
Assembly
Features
Front view
Removable terminals
blue
1 2
4 5
Function
3
6
KFD2-STC4-Ex2
LED green:
Power supply
PWR
7 8 9
10 11 12
13 14 15
Removable terminals
green
Application
The device supports the following SMART protocols:
HART
BRAIN
Foxboro
7-
3-
8+
250
II
4+
10-
6-
11+
250
12
14+
15-
Zone 0, 1, 2
Div. 1, 2
24 V DC
Power Rail
HART
1+
HART
HART
KFD2-STC4-Ex2
HART
132952_eng.xml
Connection
24 V DC
Zone 2
Div. 2
Technical data
KFD2-STC4-Ex2
General specifications
Signal type
Analog input
Supply
Connection
Rated voltage
Ripple
20 ... 35 V DC
within the supply tolerance
Power loss
1.9 W
Power consumption
2.8 W
Input
Connection
Input signal
0/4 ... 20 mA
Available voltage
Output
Connection
Load
0 ... 550
Output signal
Ripple
50 A rms
Transfer characteristics
Deviation
0.25 A/K
field side into the control side: band width with 1 Vpp signal 0 ... 7.5 kHz (-3 dB)
safe area to hazardous area: band width with 1 VSS signal 0.3 ... 7.5 kHz (-3 dB)
Settling time
200 s
20 s
Electrical isolation
Output/power supply
Output/Output
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
EN 61326-1:2006
Conformity
Electromagnetic compatibility
NE 21:2006
Degree of protection
IEC 60529:2001
UL 61010-1:2012
Ambient conditions
Ambient temperature
Mechanical specifications
Degree of protection
IP20
Mass
approx. 150 g
Dimensions
Mounting
132952_eng.xml
II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I
Input
Voltage
Current
Power
Supply
Maximum safe voltage
Statement of conformity
Uo
Io
Po
Um
25.2 V
93 mA
0.586 W
250 V (Attention! The rated voltage can be lower.)
TV 99 ATEX 1499 X , observe statement of conformity
II 3G Ex nA II T4 [device in zone 2]
Electrical isolation
Input/Output
Input/power supply
Directive conformity
Directive 94/9/EC
International approvals
UL approval
Control drawing
IECEx approval
116-0173 (cULus)
IECEx BAS 04.0015
Technical data
Approved for
KFD2-STC4-Ex2
General information
Supplementary information
Accessories
Power feed module KFD2-EB2
The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 150 individual devices depending on the power consumption of the devices. Collective error messages received
from the Power Rail activate a galvanically-isolated mechanical contact.
Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical insert and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.
Profile Rail K-DUCT with Power Rail
The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
Due to this assembly no additional cable guides are necessary.
132952_eng.xml
Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!