SLUG CATCHER SIZING

.
Item

SLUG CATCHER

Designation

V-100

- DATA OPERATING CONDITIONS

SEPARATOR DATA

Pressure

102.4

Bar g

ID (Note 4)

2 000

mm

r = L / ID 3

Temperature

69.18

L (TL/TL (Note 4)

6 000

mm

Demister NA

FLUID DATA

DEMISTER DATA

GAS (Provision) (Note 1,2)


Std Flowrate

66

MMSCFD

Mass flowrate

Mass flowrate

64,410

kg/h

Density

Mol. weight

21.06

g/mol

Compr. factor Z

0.82

Actual density

93.1

Viscosity

0.016

Type
K factor

LIQUID (Note 1,2)

kg/m

15 200

kg/h

547.6

kg/m

Vol. flowrate (1)

27.8

Am/h

Viscosity

0.16

cP

Vol. flowrate

4 190

NA
0.12

(Note 5)

Abbl/d

cP

- CALCULATIONS -

LIQUID SECTION
Level

height

Area

Vol.

D vol

Dt

(mm)

(mm)

(m)

(m)

(m)

(min)

LALL

200

200

0.16

0.98

0.98

2.12

LAL

600

400

0.79

4.76

3.78

8.16

NLL

750

150

1.08

6.46

1.70

3.68

LAH

900

150

1.37

8.23

1.77

3.83

1 000

100

1.57

9.42

1.20

2.59

LAHH

(Note 3)

18.85
GAS SECTION
To LAHH

Level

Height

Area

Volume

vc

vg max

vg

(mm)

(mm)

(mm)

(m)

(m)

(m/s)

value

(m/s)

(m/s)

(%)

1 000

1 000

1.57

9.42

2.21

0.12

0.27

0.12

46%

vg/vgmax

NOTES / REMARKS
1. Slug Catcher sizing is designed based on 170 MMSCFD of gas and 72m3/day of liquid.
2. No margin is considered on gas and liquid flow.
3. 11.3 bbl (1.8 m3) of slug size is considered from NLL to LAH.
4. Slug Catcher dimensions considered here are for information only. Internals are not considered for sizing Slug Catcher.
Vendor to advise specialized internals to be incorporated in the slug catcher design for efficient separation and size
optimization. Final Slug Catcher size to be confirmed by Vendor.
5. K Factor value of 0.12 taken from GPSA Sec 7 Fig 7-9

HORIZONTAL 2 PHASES SEPARATOR SIZING

Item

036-V-0650

Designation

MEREN GGCP Slug Catcher

- DATA OPERATING CONDITIONS

SEPARATOR DATA (Note 4)

Pressure

2.42

Bar g

ID (Note 4)

Temperature

25.2

L (TL/TL) (Note 4

3 500

mm

r = L / ID 3.3

11 500

mm

Demister NA

FLUID DATA

DEMISTER DATA

GAS (Provision) (Note 1,2)


Std Flowrate

120

Mass flowrate
Mol. weight

125100
20.94

Compr. factor Z

Type
K factor

LIQUID (Note 2)
MMSCFD

Mass flowrate

2 308

kg/h

kg/h

Density

887.6

kg/m

g/mol

Vol. flowrate (1)

2.6

Am/h

0.9876

Actual density

2.928

kg/m

Viscosity

0.011

cP

Viscosity

0.75

Vol. flowrate

392

NA
0.12

(Note 5)

cP
Abbl/d

- CALCULATIONS -

LIQUID SECTION
Level

height

Area

Vol.

D vol

Dt

(mm)

(mm)

(m)

(m)

(m)

(min)

LALL

300

300

0.40

4.59

4.59

105.93

LAL

600

300

1.10

12.62

8.03

185.39

NLL

800

200

1.66

19.06

6.43

148.42

LAH

1 250

450

3.08

35.47

16.42

378.89

LAHH

1 500

250

3.94

45.29

9.82

226.61

(Note 3)

GAS SECTION
To LAHH

Level

Height

Area

Volume

vc

vg max

vg

(mm)

(mm)

(mm)

(m)

(m)

(m/s)

value

(m/s)

(m/s)

(%)

1 500

2 000

5.68

65.35

17.38

0.12

2.09

2.09

100%

vg/vgmax

NOTES / REMARKS
1. 120 MMSCFD of gas has been considered as Slug Catcher operating case. The operating case is based on Process HYSYS
Simulations Case 1 Production Year 2014 Stream 01 & 02 combined flow.
2. No margin is considered on gas and liquid flow.
3. 100 bbl (15.9 m3) of slug size is considered from NLL to LAH.
4. Slug Catcher dimensions considered here are for information only. Internals are not considered for sizing Slug
Catcher. Vendor to advise specialized internals to be incorporated in the slug catcher design for efficient separation
and size optimization. Final Slug Catcher size to be confirmed by Vendor.
5. K Factor value of 0.12 taken from GPSA Sec 7 Fig 7-9