Escolar Documentos
Profissional Documentos
Cultura Documentos
Abstract: The performance and reliability of grounding grids depend on its structural integrity. If grounding conductors are
damaged, it may cause misoperation of protective relay which leads to trip feeders unnecessarily. It can also
cause not only failures on the surroundings such as the grounding grid, secondary circuits cables, and structural
elements but also voltage hazard for human. The circuits may attain unacceptable voltages when short-circuit fault
currents occur in these grids. This paper presents the development of a new technique to monitor the operating
conditions of the grounding grids of high voltage apparatus and systems without any diggings and forced outages.
New concept, principals, a technique and a device shown in the paper have never been described before by the
other authors. The technique is based on the evaluation of the electromagnetic field distribution pattern over the
damaged horizontal elements of the grid.
Keywords: Grounding Safety Monitoring Distribution Short Circuit
Versita sp. z o.o.
1.
Introduction
E-mail: tek.lie@aut.ac.nz
2. Features of processes in
grounding with damaged horizontal
conductors
The theoretical development of the analysis of the
processes in the grounding grids [8, 9] shows that the
patterns of the current distribution in the current carrying
conductor with and without failures and magnetic field
distribution over it are different.
The mathematical analysis is based on a number of
theories including Bio-Savart Law [9], graphs and matrices
analysis.
The distribution of the magnetic field value captured over
the horizontal element can be described thanks to BiotSavart law [9]. In accordance to this law the magnitude
of the magnetic field is proportional to the current in the
conductor and varies as the inverse square of the distance
from the source.
dH =
I sin
dx,
4r 2
(1)
(2)
H=
=
(3)
4
a a2 + l2
4 a a2 + l2
The final expression can be written in relative values
a
x
I
where: a = , x = , I0 =
l
l
l
I0 l2 (1 x)
I0 l(l x l)
=
2
2
2
4 a a l + l
4 a l2 a 2 +12
I0 (1 x)
=
4 a a 2 +1
(4)
When the horizontal element is physically integrated, one
can expect a gradual decrease of the current and magnetic
field values along the element from their maximum to a
minimum range.
In reality, the values of the current and magnetic field
subside down not to absolute zero. It happens because
there are several other horizontal elements in parallel
with their own currents and magnetic fields which create
additional feeding to the element under consideration.
During the network mathematical quasi static analysis,
utilizing graph theory and matrices analysis [9, 10] the
current and potential distribution in the grounding grids
with and without damaged elements were obtained.
Furthermore, for the purpose of more advanced analysis
of the processes, a computer modelling is used. In order
to obtain more specific characteristics of the current and
potential distribution the grounding circuit is narrowed
down to 2 meshes (section A) as shown in Figure 1. It
is possible to do like this since the process of current
dissipation is similar in all meshes: current flows from the
source through the elements into ground.
A modified scheme for the computer modelling is shown
in Figure 2(a) and Figure 2(b). The horizontal element
between meshes I and II is chosen as a damaged one. To
observe a current distribution in the element, ammeters
and oscilloscopes are installed in the circuit.
The
resistance of the middle element is recalculated taking
into account possible failures resistance (which was
evaluated experimentally).
The values of the elements Rme.i and Rleak.i which are
distributed self-resistances and resistances to the leakage
currents of the horizontal conductors Rhor are presented
in [9].
Figure 3 represents the regime when the horizontal
element in the middle of the mesh is damaged. The
resistance of the gap can be varied in a wide range
depending on the soil resistivity.
As it can be seen from Figure 2 and Figure 3, the
character of the current distribution along the conductor
H=
294
Figure 1.
3.
(a)
(b)
Figure 2.
296
(a)
(a)
(b)
(b)
Figure 3.
(b)
Figure 4.
(a)
4. Device for
Investigation
(b)
Figure 5.
the
Grounding
298
Figure 6.
Figure 7.
299
Figure 10.
Figure 8.
Figure 9.
300
Figure 11.
5.
Conclusion
Figure 12.
References
[1] IEEE Std. 80-2000, IEEE Guide for Safety in AC
Substation Grounding, The Institute of Electrical and
Electronic Engineers, New York, 2000
[2] IEEE Std. 81-1984, IEEE Guide for Measuring Earth
Resistivity, Ground Impedance, and Earth Surface
Potentials of a Ground System, IEEE Press, New
York, 1984
[3] IEEE Std. 142-1991, IEEE recommended practice
for grounding of industrial and commercial power
systems, IEEE Press, New York, 1991, GREEN
BOOK, 2007
[4] Ma Y. , Karady G. G., Investigating grounding grid
integrity based on the current injection method, in:
The 41st Annual North American Power Symposium
(NAPS), 2009, 1-5
[5] Zhang B., Zhao Z., Xiang C., Lin L., Diagnosis
of breaks in substations grounding grid by using
301
[6]
[7]
[8]
[9]
302