Escolar Documentos
Profissional Documentos
Cultura Documentos
7 Maximum Efficiency
It may be shown that the efficiency of a transformer is a maximum
when then the variable copper loss (i.e. I P2 R P + I S2 RS ) is equal to the
constant iron losses.
Example(3.2): A (5 KVA) single-phase transformer has a turns ratio of
(10:1) and is fed from a (2.5 KV) supply. Neglecting losses, determine
(a)The full-load secondary current (b) The primary current at full-load.
Solution:
(a)
N P 10
=
,
NS
1
Secondary voltage
since
N P VP
=
N S VS
N
VS = VP S
NP
1
VS = 2500 = 250 volt
10
5000
= 20 A
250
(b)
NP IS
=
NS IP
1
I P = 20 = 2 A
10
**********************************************************
85
VOC=230 V
VSC=19.1 V
IOC=0.45 A
ISC=8.7 A
POC=30 W
PSC=42.3 W
All data given were taken from the primary side of the transformer.
(a) Find the approximate equivalent circuit of this transformer referred to
the high-voltage side of transformer.
Solution:
Open circuit test:
P = VI cos( )
30
,
230 0.45
= 73.15 o
= cos 1
I C = I o cos( )
I m = I o sin( )
RC =
,
,
230
= 1769 ,
0.13
Xm =
230
= 534.88
0.43
42.3
(8.7 )2
= 0.558
Z eq =
VS .C 19.1
=
= 2.195
I S .C
8.7
X eq =
(2.195)2 (0.558)2
= 2.12
**********************************************************
86
87
V LP
3
voltage by the turns ratio of the transformer. The phase voltage on the
secondary
a1
A2
3 VP
VLP
=a
=
VLS
3 VS
B1
B2
a2
b1
b2
C1
c1
C2
c2
Fig.(3.11)
88
VP
VS
= a ), so the overall
relationship between the line voltage on the primary side of the bank and
the line voltage on the secondary side of the bank is.
V LP
=
V LS
3 VP
a1
A1
V S
A2
B1
VLP
= 3a
VLS
C1
a2
b1
b1
c1
B2
C2
c2
Fig.(3.12)
89
VLP
a
=
VLS
3
A1
a1
A2
B1
a2
b1
B2
C1
b2
c1
C2
c2
- transformer.
Fig.(3.13)
90
VLP VP
=
=a
VLS V .S
A1
a1
A2
B1
a2
b1
B2
C1
b2
c1
C2
c2
- connection has
Fig.(3.14)
91
34.5
3
= 19.9 KV
,Secondary voltage =
13.8
3
= 7.97 KV
19.9
= 2.5
7.97
For - connection
Primary voltage =34.5 KV
Turns ratio =
34.5
= 2 .5
13.8
For - connection
Primary voltage =34.5 KV
Turns ratio =
, Secondary voltage =
13.8
3
= 7.97 KV
34.5
= 4.33
7.97
For - connection
Primary voltage =
Turns ratio =
34.5
3
= 19.9 KV
19.9
= 1.44
13.8
*********************************************************
92
Example(3.5): The following are the light-load test readings on a 3phase, 100 KVA, (400/6600)V, star/delta transformer.
Open circuit: supply to low-voltage side 400 V, 1250 W.
Short-circuit supply to high-voltage side 314 V,1600W, full-load current
Calculate the efficiencies at full-load, 0.8 power factor and at half-full
load, u.p.f. Calculate also the maximum efficiency, u.p.f.
Solution:
=
output
nKVA cos( )
100 =
100
input
nKVA cos( ) + PCore + n 2 ( PCu )
The O.C. test gives the normal PCore loss since rated voltage is applied and
the S.C. test gives the PCu loss at load since rated current is flowing.
For full-load, 0.8 P.f.
=
(1 100 10 3 0.8)
100 = 96.56 0
0
(1 100 10 3 0.8) + 1250 + (1) 2 (1600)
(0.5 100 10 3 1)
100 = 96.8 0
3
2
0
(0.5 100 10 1) + (1250) + (0.5) (1600)
n=
1250
= 0.88
1600
(0.884 100 10 3 1)
100 = 97.25 0
Max. =
0
(0.884 100 10 3 1) + (1250) + (0.884) 2 (1600)
93