Escolar Documentos
Profissional Documentos
Cultura Documentos
LESSON 2
PERFORMANCE OF SYNCHRONOUS
MACHINES
INTRODUCTION
This lesson carries on from work completed on the basics of
synchronous machines in an earlier module entitled Electrical
Power Systems and Machines. It will review machine equations
and describe tests to determine the parameters of a machine.
Performance in terms of power v load angle will be presented and
synchronising power discussed. This then leads naturally to the
effects of a sudden short-circuit on the terminals of such a
machine and prepares the way to the next lesson in the topic
Electrical Generation entitled Power System Stability.
YOUR AIMS
As a result of undertaking this lesson you should be able to:
University of Sunderland
Page 1
Page 2
University of Sunderland
Phase A
'
'
(a)
Fa
Fr
(b)
n=
where
f
revs 1
p
m
rotor and stator to produce the phasor E, N a
dt
University of Sunderland
Page 3
Mathematically:
r
r
r
Fr = Ff + Fa
r
f
r
m
+(
r
a
to generate E, and
Page 4
University of Sunderland
EFFECTS OF LEAKAGE
Armature
winding
Field winding
fL
m
aL
(a)
total
oL
(b)
Figure 2: Flux components on load: (a) flux pattern; (b) phasor diagram
Xs =
Na
d( al + a )
= x al + X m
dia
University of Sunderland
Page 5
jX muIa
jX alIa
E
Ra Ia
Ff
Ia
Fa m
Fr
al
Figure 3: Generator phasor diagram; unsaturated machine
jI X
a s
RI
aa
90
(a)
Ia
Ia
Xs
Ef
Ra
V 0o
Page 6
University of Sunderland
(b)
EFFECT OF SATURATION ON XS
The open-circuit characteristic is the graph of generated voltage
against field current with the machine on open circuit and running
at synchronous speed. The short-circuit characteristic is the graph
of stator current against field current with the terminals shortcircuited. Figure 5 illustrates these curves.
Air gap line
D
1.5
1.5
1.0
0.5
Statorcurrent
currentp.u.
p.u.
Stator
Open circuit
curve
Saturation line
1.0
Short circuit
curve
0.5
G H
1 p.u.
0
A
K
2 p.u.
FK
. With operation near nominal voltage,
CK
University of Sunderland
Page 7
k fs
kf
(X su xal ) + xal
where xal is the leakage reactance for the machine, kf is the air gap
line slope kf and kfs is the slope of the average saturation line. In
k
some texts the ratio f is termed k, the saturation factor.
k fs
Page 8
University of Sunderland
E0
ob / 2
X'=
E0
oa / 2
Xs =
E0
oc / 2
University of Sunderland
Page 9
Time
a phase
Armature current
b phase
b
c phase
c
Instant of
short circuit
(a )
Envelope of 50 Hz waveform
Armature current
Instant of
short circuit
10
0 .2 (s)
1 2 cycles
Time(s)
(b )
Figure 6:
(a) Oscillograms of the currents in the three phases of a generator when a sudden short
circuit is applied
(b) Trace of a short-circuit current when direct-current component is removed
Page 10
University of Sunderland
A
Lamp
M/c
2
Incoming
C1
A1
A1 B1 C1
C2
M/c
1
B2
B1
(b)
(a)
Figure 7: Synchronising
University of Sunderland
Page 11
I
A
EA
E
Z
(a)
(b )
(c)
Figure 8:
(a) Two generators in parallel equivalent circuit
(b) Machine A in phase advance of machine B
(c) Machine B in phase advance of machine A
I=
ER
is produced.
ZA + ZB
Page 12
University of Sunderland
a s
T
E
infinite
Ia busbar
90 +
(a)
(b)
power delivered =
sin
Xs
University of Sunderland
Page 13
P
P max
P
o
90o
180o
Electrical degrees
Page 14
University of Sunderland
IaXs
Ia
V
Figure 11: Phasor diagram for the synchronous machine at
the steady state limit of stability
University of Sunderland
Page 15
E1
1
I1 X
(a)
V
I1
Lagging Power
factor generation
(over-excited)
E2
2
I2 X
(b)
V
Constant power
current locus
(Icos = constant)
I2
E3
I3 X
I3
(c)
3
Leading Power
factor generation
(under-excited)
Ef
I1 XS
Locus of Ef
Ef
I2
I1
I2XS
Page 16
University of Sunderland
P
Ef
Locus IXS
(circle centre O)
V
O q
(a)
Generating
+P
Practical limit
of stability
3EV
f
X
3 VI
3 VI cos
Excitation or
field limit
O
3V 2
Xs
3 VI sin
-Q
(b)
+Q
-P
Motoring
Figure 14: (a) Phasor diagram of synchronous generator and
(b) Construction of performance chart
(each phasor scaled by 3V/XS giving a vertical axis of
real power and a horizontal axis of reactive power)
Figure 14(a) shows the phasor diagram for the machine and
indicates the simple scaling exercise to create a chart with axes of
real power (X axis) and reactive power (Y axis). If line voltage
values or per-unit quantities are employed in the scaling process,
the values of real and reactive power are those for a three-phase
machine rather than on a per-phase basis.
Figure 14(b) shows a typical operating power chart for a
synchronous generator that results when this construction is
University of Sunderland
Page 17
1 (kV ) 2
1 (11.8) 2
= 2.94 / phase
0.63 Sbase 0.63
75
150
Ef = 2.5 p
.u.
Ef = 2 p. u
100
e
a Ef = 1 p.u.
b
50
MVA
Od
O
Leading
50
100
Lagging
Page 18
University of Sunderland
MVAr
VE f
11800 2 2.3
sin = 60 10 6 =
sin
2.94
Xs
from which
= 33.3
University of Sunderland
Page 19
Eo = no load emf
Output
voltage at
constant
excitation
Unity p.f.
Zero p.f.
lagging
cos= 0
Irated
Iload
E0 V
V
Page 20
(i)
(ii)
(iii)
(iv)
University of Sunderland
2.7
3.6
4.3
4.75
5.1
5.6
100
150
200
250
300
400
VLINE 6.6 kV
=
= 3.81 kV
3
3
University of Sunderland
Page 21
SOLUTION
It is assumed that this machine produces a line voltage of 6.6 kV
when on full load at a power factor of 0.9 lag.
Ff
Fa
= cos -1 0. 9
(90 - )
V = 3.81 kV
(phase voltage)
Fr
Fr = 165 N f
Page 22
5.0 3.81
= 0.325 p.u.
3.81
University of Sunderland
Plot of O.C.C.
E = 5.05 kV
f
4
Machine
phase
voltage
(kV)
3
PH
= 3.81 kV
F =165A
r
F magnitude is 290 A
= cos
-1
0.9 = 25.84
100
200
290
University of Sunderland
Page 23
Variable
reactive load
Irated
If
Vrated
Ef
Rotation
at synchronous
speed
Figure 19: (a) Zero power factor test arrangement
Ef
jX m
jX a l
V ra te d
Fa
Fr
Ir a te d
Ff
Figure 19: (b) Machine phasor diagram for the
Potier point condition
Page 24
University of Sunderland
OC
Air-gap
line
Zero PF
@ rated I
T
Machine
rated
voltage
V S
P
Potier point
(zero PF @ rated
current & voltage)
Make PV = Ao
Draw VT // Air-gap line
TS = IXal, SP = Fa
EXAMPLE 3
Find the regulation of a 1000 kVA, 2000 V, 50 Hz, 3-phase
synchronous a.c. generator at rated load and 0.8 p.f. lag.
The machine open-circuit voltage values with their associated
excitation levels expressed in percentage terms are shown in the
table below.
Excitation
(%)
Open-Circuit
Voltage (%)
25
80
100
125
160
200
35
90
100
110
120
128
An excitation of 80% is required for rated load current on shortcircuit, and 200% for rated current at rated voltage with zero
power factor lagging.
SOLUTION
(a) Figure 21 shows a plot of the open-circuit curve for the
machine.
(b) The Potier point is then established (V = 100% and excitation
= 200%).
(c) An excitation current of 80% was required to produce rated
load current from the machine so point V is established at
120%, 80% excitation away from the Potier point.
University of Sunderland
Page 25
Page 26
Ef V
V
100 =
University of Sunderland
123 100
100 = 23%
100
Saturation line
Air-gap line
14 0
Ff = 176%
12 0
Open
circuit
curve
Ef = 123%
T
V%
E = 108%
10 0
IL X L
Rated V = 100%
V
11%
P, Potier
point
Fa =72%
90%
80
60
40
Fr = 120 %
20
80%
0
0
50
100
(Sh ort-circuit V= 0)
Excitation %
150
20 0
IXL =11%
3
Vrated
4
6
Ff =176%
Fa= 72%
Fr = 120%
f rom cur ve
100
7
= cos -1 0.8 1
8
Irat ed
E f = 123%
University of Sunderland
Page 27
X ss =
kf
( X su x al ) + x al
where xal is the leakage reactance for the machine, kf is the air gap
line slope and kfs is the slope of the average saturation line. In
some texts the ratio kf/kfs is termed k, the saturation factor. The
phasor diagram is then used to predict the internal emf Eo to
produce rated terminal voltage and current so that the regulation
calculation may be made. The following tutorial example uses the
same machine test information as Example 3 and demonstrates
this calculation method.
EXAMPLE 4
Calculate the percentage voltage regulation using the adjusted
synchronous impedance method for the machine of Example 3.
SOLUTION
For the machine data of the last tutorial example, Ixal = 11% and
the resulting air-gap excitation voltage after phasor addition was
108%. This establishes the slope of the saturation line given the
open-circuit characteristic results. (E = 108% gives a
corresponding excitation level Fr = 120%)
Given that an excitation current of 80% is required for rated load
current (100%), on short-circuit, examination of the open-circuit
characteristic will reveal a corresponding excitation voltage of
90% for the 80% excitation current level. This means that the
unsaturated synchronous reactance (ignoring stator resistance) is
simply:
X su =
90%
= 0.9 p.u.
100%
Page 28
35
= 1. 4
25
University of Sunderland
108
= 0.9
120
X ss =
kf
k fs
k fs
kf
1. 4
= 1.556
0.9
( X su xal ) + xal =
(0.9 0.11)
+ 0.11 = 0.618 p.u.
1.556
1.456
= 162%
0.9
( F f + Fa )
R
University of Sunderland
Page 29
Fq
Rq
( F f + Fd )
Rd
1
R
= Pq Fq + Pd ( F f + Fd )
Note that this is a phasor sum since Fq and Fd are at right angles to
each other.
The equation for
where
Fr = KFq + F f + Fd and K =
Pq
Pd
pole arc
pole pitch
Figure 23 illustrates the geometry and defines the terms pole arc
and pole pitch. Basically, the pole arc is the amount of the rotor
surface covered by steel.
K depends mainly on the ratio
Page 30
University of Sunderland
pole arc
pole pitch
Pole pitch
Po
le
a
r
c
Figure 24 shows the mmf and emf diagram for a salient pole
generator.
Fq
e
Ef
Kfq
d
c F
a
Fd
Fo
E
Fr
IX
V
Id
Iq
Figure 24: MMF and EMF diagram for salient pole machine
Notes:
1. Id and Iq do not, strictly speaking, exist since current I is a
function of time, while the d and q axes are a function of
space.
2.
ed ab
=
=K
ec ac
University of Sunderland
Page 31
jIq Xq
Ef
jI Xs
j Id Xd
IR
I
Iq
Id
Figure 25: Comparison of phasor diagrams for the round
rotor and salient pole synchronous generators
Note:
E'f and ' are the values for a round rotor (i.e. Xs=Xd = Xq)
The value of Ef and E'f are similar, but ' > , i.e. saliency gives
lower values of load angle.
Page 32
University of Sunderland
Xd =
Vmax
V
and X q = min
I min
I max
max
Vmin
Armature
volts
50Hz
Quadrature
axis
Direct
axis
Imax
Armatur e
curr ent
Imin
Vmax
= Xd
I min
Vmin
= Xq
I max
Figure 26: Armature voltage and current waveforms from a slip test
University of Sunderland
Page 33
IX
q q
IX
d d
Now
I d X q = V sin , hence I q =
similarly
I d X d = E f V cos
and hence
Id =
V sin
Xq
E f V cos
Xd
per phase
Xq
Xd
Xd
P=
VE f
Xd
sin +
V 2 sin 2
2
Xd Xq
X X
d
q
sin 2
2
per phase
Note that the first term is identical to the expression for power
generated by a round rotor machine and the second term has no Ef
variable in the expression, indicating a distortion to the power ~
load angle curve due to the inequality of the direct and quadrature
axes reactances. This is reflected in a typical plot of the curve
shown in Figure 28, which reveals a stiffer form of machine
power ~ load angle curve in the stable region but with a reduced
maximum load angle limit for stable operation.
Page 34
University of Sunderland
P ower/
torque
VEf
sin
Xd
Excitation
component
Component due to
saliency
V 2 sin 2 X d X q
2
X d X q
EXAMPLE 5
A 6.6 kV, 6 pole, 50 Hz, star-connected synchronous generator
has reactance values Xd = 8.7 /phase and Xq = 4.35 /phase. If
the excitation is adjusted to give an emf of 11 kV and the load
angle is 30, determine:
(a) Output power and current and power factor.
(b) Load angle corresponding to maximum power.
SOLUTION
6.6
11
V phase =
= 3.81kV and E phase =
= 6.35kV
3
3
Figure 29 shows the construction of the phasor diagram given
these voltages and load angle. (Note that a lagging power factor
load is assumed for the generator because of the overexcitation
condition for Ef.)
University of Sunderland
Page 35
d
c
IqXq
Ef
6.35
kV
b
30
O
V = 3.81 kV
30
IdX d
a
I
Ef = Og cos 30 o , hence Og =
6.35
= 7.35kV
0.866
3060
= 352 A
8.7
cg = Og sin 30 = 3.675 kV
bg = ag sin 30 = 1.77 kV
hence
1.905
= 438 A
4.35
I
tan 1 d
I
q
438
Page 36
and
cos = 0.991lagging
University of Sunderland
SUMMARY
This lesson has extended the coverage of synchronous machines from the second level module
entitled Electrical Power and Machines and has shown the development of phasor diagrams to
represent the machines electrical performance, so that indices of performance such as voltage
regulation might be calculated by engineers. To improve the accuracy of estimation of regulation,
the topic of magnetic saturation and its effect on the machine reactance were discussed together
with four methods of estimating regulation and their corresponding accuracy. Practical tests were
described to measure machine parameters and linked to the regulation prediction methods.
Linked to the machines non-linear magnetic circuit behaviour is its impedance under fault
conditions where, at different points after a short-circuit fault on its terminals, a machine can be
viewed to have a variable reactance dependent on time with three distinct periods; a subtransient
reactance during the first 10 or 12 mains cycles after the fault; a transient reactance in the
following period of up to several second; then a steady state reactance in the period following.
The behaviour of the machine when in parallel with another machine was discussed to bring out
the feature of inherent synchronising stability that this form of electrical machine possesses, and
what happens when such machines are attached to systems containing what might appear to be an
infinite number of generators of the same form. The mathematical expression for the power
generated into this 'infinite bus' was developed. This shows the machine relationship between
generated power and what was termed the 'load angle', which is the electrical phase angle
between the internally induced emf and the terminal voltage of the machine.
Engineers must be aware of the electrical boundaries of operation of the synchronous generator to
avoid overtaxing the machine or causing it to lose synchronism with the power system to which it
is attached. The synchronous generator operating chart is a means of giving visual indication of a
generator's electrical operating state, given a set of electrical load conditions. Although only
presented as a graphical exercise in this text, such indications are directly available on a control
engineer's desk within a power station to ensure generation conformity.
A final section on a salient pole generators discussed the primary differences in construction to
those for a round rotor machine and developed the equations for the machine's phasor diagram
and power generation so that a graphical comparison of power against load angle could be made.
University of Sunderland
Page 37
Page 38
University of Sunderland
SELF-ASSESSMENT QUESTIONS
QUESTION 1
(Separation method)
A 5 MVA, 6.6 kV, 3-phase, 50 Hz, star connected turbo alternator has a resistance per phase of
0.1145 . Test figures for line volts on open circuit and for line volts with rated current and zero
power factor are:
Field
Current
(A)
V1
O/C
(kV)
V1
ZPF
(kV)
40 60
80
100
120
160
200
240
4.7
5.4
6.55
7.3
7.78 8.06
0.7 1.75
2.7
4.3
5.45 5.15
280
5.5
Find the excitation current required to deliver rated output at 0.8 p.f. lagging and the p.u.
regulation.
QUESTION 2
(Same question as Q1 but using ampere turn method for comparison purposes)
Using the information provided in Q1 find the excitation and p.u. regulation using the ampere
turn method.
QUESTION 3
(Separation method taking into account saturation effect on synchronous reactance)
(a) Explain what information can be derived from:
(i) open-circuit characteristic
(ii) short-circuit characteristic
(iii) zero power factor at rated current characteristic
The following data were obtained for the O/C characteristic of a 13 529 kVA, 13.8 kV, 60
Hz, 3-phase, two pole turbine generator:
Line
Voltage
(kV)
Exciting
Current
(A)
50
100
150
200
250
300
University of Sunderland
Page 39
(b) The excitation current required to give rated kVA at ZPF and rated voltage is 368 A, and
rated current on short-circuit is 188 A. Ignoring resistance, complete the following tasks:
(i) Draw the Potier triangle and determine the leakage or Potier reactance x and the
component of field current to overcome the mmf of armature reaction.
(ii) Calculate the value of the saturated armature reactance by using the saturation factor k
and the regulation of the synchronous generator, when delivering rated load at 0.85 power
factor current lagging.
QUESTION 4
Construct a performance chart for a 22 kV, 500 MVA, 0.9 p.f. generator having a short-circuit
ratio of 0.55. Assume a 10% stability margin and a rotor excitation limit of 2.5 p.u.
QUESTION 5
Two three-phase, 6.6 kV, star connected generators supply a load of 3000 kW at 0.8 p.f. lagging.
The synchronous impedance per phase of machine A is 0.5 + j10 and of machine B is 0.4 + j12
. The excitation of machine A is adjusted so that it delivers 150 A at a lagging power factor, and
the governors are so set that the load is shared equally between the machines. Determine the
current, power factor, induced emf and load angle of each machine.
QUESTION 6
A salient pole synchronous generator has Xd = 0.9 per unit and Xq = 0.6 per unit. The machine is
operating at full-load, 0.8 p.f. lagging. Calculate the value of excitation in terms of the terminal
voltage. Calculate also the load angle and the values of direct and quadrature-axis currents.
Neglect resistance and saturation.
Page 40
University of Sunderland
Series 2
Series 1
240
200
40
60
Air-gap
line
80
100
E = 7.2 kV
120
160
Fg = 197A Fo = 236A
(S)
(V)
IXL
(T)
Ef = 7.74 kV
= 880 V
Fa = 48A
280
Potier
point
(P)
ANSWER 1
Line
voltage
(kV)
University of Sunderland
Page 41
The plot of the data given in Q1 is shown in Figure 30. The first step is to establish the Potier
point (6.6 kV, 280 A). The excitation on short-circuit to give rated current from the machine is 60
A and a line scaled to this equivalent length is drawn horizontally from the Potier point back
towards the vertical axis. This establishes point (V) on Figure 30. A line is then drawn parallel to
the initial slope of the open-circuit characteristic and intersects the latter at point (T). A vertical
line dropped from this point to the 6.6 kV line gives Ixal = 880 V (length T-S). Length S-P is then
the armature reaction effect Fa = 48 A.
Use is then made of the phasor relationship between V, Ixal and E in Figure 31 to establish the
latter at 7.2 kV.
(Use may be made of the stator resistance quoted in the question but it makes very little practical
difference to the answer:
I line =
5000
3 6.6
= 437.4 A
The machine is star connected so that this current is also the phase current and the voltage drop
due to resistance is
437.4 0.1145 = 50 V.
Adding this level of voltage makes very little difference to the resultant phasor diagram and so
can be ignored).
Fa = 48A 6
F f=236A
7
Fr=197A
(from curve)
5
IX L=880V
3
4
E = 7.2 kV
Vrated=6.6 kV(LINE)
2
Irated
= cos-1 0.8
1
Return is then made to Figure 30 using E to give the corresponding excitation, Fr, of 197 A.
Reverting back to Figure 31, the values of Fr(197 A) and Fa(48 A) are then added vectorially
to produce the excitation level Ff (236 A).
Using this value of Ff of 236 A, the open-circuit characteristic reveals a voltage of Ef = 7.74
kV at this level of excitation, i.e. this machine, when delivering rated current at a power factor
Page 42
University of Sunderland
of 0.8 lagging, requires an excitation current level of 236 A to produce a rated line voltage of
6.6 kV at its terminals. On open circuit this excitation produces a line voltage of 7.74 kV,
which means that the regulation will be:
7.74 - 6.6
Regulation =
= 0.17 p.u.
6.6
ANSWER 2
This approach underestimates regulation by ignoring the leakage reactance voltage drop. Fullload current is obtained on short-circuit when the excitation is Fa = 60 A. The terminal line
voltage is 6.6 kV and the corresponding excitation current to produce this voltage is Fr = 163 A.
The load power factor is 0.8 lag so the phasor addition of Fr and Fa shown in Figure 32 gives Ff =
205 A. This level of excitation would give an open-circuit voltage of 7.36 kV and hence a
regulation figure of:
7.36 6.6
= 0.115
6.6
Compare this to the previous question where the excitation level was 236 A and regulation 0.17
p.u. and these may be seen to be an underestimation.
Ff
Fa
=cos-1 0.8
Fr
V= 2.81 kV
(Phase voltage)
Fa 60A
Fr 163A
By phasor addition
Ff 205A
University of Sunderland
Page 43
ANSWER 3
(a)
(i) Refer back to Figure 5 and its use in conjunction with the short-circuit test (giving Xsu ) to
predict machine voltage regulation and required excitation level. The air gap line and average
saturation line may be drawn if the leakage reactance xal and load conditions are known. This
gives the ratio kfs/kf which is the reduction factor to apply to the unsaturated magnetising
impedance value (Xsu - xal), giving
X ss =
k fs
kf
( X su x al ) + x al
(ii) The short-circuit test contributes the excitation required to produce rated current from
the machine on short-circuit output conditions. This value is then used, in conjunction with
the open-circuit characteristic, to predict the internal voltage source level present during the
short-circuit test. The impedance Zsu Xsu if resistance is ignored, and equals the ratio of this
voltage to rated current.
(iii) The zero power factor test is the most accurate of the three test methods for predicting
machine voltage regulation since it incorporates an allowance for leakage reactance (ignored
by the ampere turn method) and also magnetic saturation. (Synchronous impedance method
using an unsaturated value of Xs, or Xsu in previous discussions on the effects of saturation).
(b)
(i) Figure 33 shows a plot of the open-circuit
characteristic(OCC) and the Potier point established at d.If(SC) = 188 A, which measured back
from point d gives point a. The air-gap line may be drawn as shown and a line drawn parallel
to it from point a to intersect the OCC at point c. This then establishes the leakage reactance
voltage drop xalI, (distance cb = 2000 V), and the component of field current to overcome the
mmf of armature reaction (distance bd = 168 A).
The rated current for the machine is:
I=
13529
3 13.8
= 566 A
hence the leakage reactance (some texts use the term Potier reactance, xp, from the technique
of derivation) equals:
x al =
Page 44
2000
3 566
= 2.04
University of Sunderland
Potier
point
400
300
350
386 A
200
Field excitation A
250
If (sc) = 188 A
Fa 168 A
315 A
150
173 A
18
16
14
12
10
100
50
14
Voltage
line-toline
kV
20
E = 14,950 V
air-gap
line
Saturation
line
Ef = 18.3 kV
142 A
University of Sunderland
Page 45
V =
13800
3
= 7960V
so that using the terminal voltage as the reference phasor 79600V, current then becomes
566(0.85-j0.527) A, given the 0.85 lag power factor of the load.
173
= 1.22
142
The unsaturated synchronous reactance is given by the voltage taken from the air-gap line for
an excitation current of 188 A, which is the excitation current to produce rated current of 577
A on short-circuit. This voltage, taken from an extended air-gap line is 19 800 V.
X su =
19800
3 566
= 20.2
X ss =
k fs
kf
( X su x al ) + x al
( X su x al )
+ x al
k
20.2 2.04
+ 2.04 = 16.9
1.22
Page 46
University of Sunderland
If the armature resistance is neglected, the induced voltage to give rated terminal voltage is:
E f V + jX ss I = 7960 + j16.9 566(0.85 j 0.527)
=15320 32V
The line-to-line magnitude of this voltage is:
3 E f = 26600 V
The excitation current obtained for this value on the line 0X of Figure 33 is 315 A, which
produces a line-to-line voltage on the open-circuit characteristic of 18 300 V. The regulation
is therefore,
regulation =
18.3 13.8
= 0.326
13.8
ANSWER 4
Xs =
1
1
1
=
= p.u.
Z base
SCR 0.55
0.55
1
(kV )2
0.55 Sbase
1
(22) 2
= 1.76 / phase
0.55 500
University of Sunderland
Page 47
Power MW
Excitation boundary
E = 2.5
5 00
450 MW
a
b
Ef =V= 1p.u.
c
MVA limit
= 33
0
Leading
Lagging
500
MVar
After selecting a centre point O, a semicircle based on this point is drawn at radius 500 MVA.
This is the MVA boundary. A horizontal line is then drawn parallel to the x axis at a distance
equivalent to 450 MW. This is the machine power output boundary. A new centrepoint O' is then
calculated, the offset from O being:
(22) 2
= 275 MVAr
1.76
A second semicircle, based on O', is then drawn of radius 2.5 275 =687.5 MVA to represent the
excitation boundary. As can be seen, this just clips the MVA boundary at point h and forms part
of the operating chart boundary, between h and the horizontal axis. The practical stability
boundary to the left of the vertical axis is formed by allowing a 10% safety margin between the
theoretical steady state stability power limit and a practical working level. This ensures that the
steady state load angle is always at a practical level below that of the theoretical level of 90.
(sin10.9 = 73 in this example). The point on the boundary of the operating chart for the practical
stability limit is found by the intersection of radii based on centre O' and associated horizontal
parallel lines drawn on the chart such as that illustrated in Figure 34. For example radius O'a
corresponds to an excitation level and terminal voltage of 1 p.u. or 275 MVA and the associated
90% power level (90% of 275 MW to give a 10% margin) is the line bc. The radius O'a intersects
Page 48
University of Sunderland
the line at point c giving the maximum practical stability point with a 10% safety margin. The
load angle of 73 is that subtended between O' and point c.
As an example of the use of the chart, the full-load operating point at g, (450 MW, 0.90 p.f.
lagging) will require an excitation Ef of 2.3 p.u. and the measured load angle is 33. This can be
checked by using:
power =
VE f
sin = 450 10 6
Xs
22 10 3 2.3 10 3
sin
1.76
ANSWER 5
For Machine A:
Pt
1500
2
cos A =
=
3 VL I A
3 6.6 150
= 0.874
A=
Total current =
-29
3000
3 6.6 0.8
(cos 1 0.8)
= 328(36.87)
= 262 - j197 A
IA = 150 -29 = 131 -j72.6 A
IB = (262 - j197) - (131 -j72.6)
= 131 -j124.4
= 181 -(cos-10.723) A
cos
= -43.7
University of Sunderland
Page 49
EA =V + I AZ A
6.6
E A =
0 + (131 j 72.6)(0.5 + j10) 10 3
3
E A = 4.6 + j1.27 kV
A = tan 1
Load angle
1.27
= 15.4
4. 6
EB =V + I BZ B
6.6
E B =
0 + (131 j124.4)(0.4 + j12) 10 3
3
E B = 5.35 + j1.52 kV
Load angle
B:
B = tan 1
1.52
= 15.9
5.35
Page 50
University of Sunderland
EB = 5 .56 15 .5 kV
E A = 4.77 15 .4 k V
A = 1 5.4 , B= 15 .8
A= - 29
=
-c os -1 (0 .8)
V = 6 .6
= -36 .87
0 kV
I = 1 50 - 29 A
A
= - 43.7
B
IB = 18 1 - 43. 7 A
IT = 328
-3 6.8 7 A
ANSWER 6
Referring to Figure 36 and taking V as phasor reference at 1 per-unit, full-load current as 1 perunit:
V sin = X q I q = 0.6 I a cos( + )
University of Sunderland
Page 51
where
= cos 1 (0.8)
In per-unit:
E f = cos19.4 + 0.9 sin( 36.9 + 19.4)
E f = 0.942 + 0.9 0.833 = 1.69 per unit
I q = I a cos(36.9 + 19.4)
I q = 1 0.55 = 0.555 per unit
IqX q
Vsin
= Iq X q
Iq = Ia cos ( + )
Id Xd
= E f - V cos
Ia
Id = Ia sin ( + )
Figure 36: Phasor diagram for Self-assessment Question 6
Page 52
University of Sunderland