Contents
Diagram 1
Single standard supply air grilles with blades in straight
position and undisturbed supply air stream (free air stream): 3
Minimum distances, selection example
Diagram 1, grille height H = 50, 150, 250 mm
4
Diagram 1, grille height H = 100, 200, 300 mm
5
Blades positions
Definitions, spread of air stream, throw, correction factor for
diagrams 1 and 2, calculation example
6
Diagram 2
Single standard supply air grilles, blades in straight
position, installed at ceiling level (Coanda effect):
Minimum distances, selection example
Diagram 2, grille height H = 50, 150, 250 mm
Diagram 2, grille height H = 100, 200, 300 mm
7
8
9
Diagram 3
Continous supply air grilles, undisturbed supply air stream
(free air stream), calculation example
10
Diagram 4
Continous supply air grilles, undisturbed supply air stream
(Coanda effect), calculation example
11
12
Air stream drop at temperature variations
12
Diagram 10
Single grilles and unobstructed spread of air stream (free
air stream), calculation example
13
14
Diagram 12
Continous supply air grilles, undisturbed supply air
stream (free air stream), calculation example
15
Note:
In plants with large air change rates, it is not always possible to keep the occupied zone free of draughts. The good
controllability of the TROX HESCO diffusion grilles with the
individually adjustable air control blades makes it possible
to guide the primary air movement so that draughts can be
avoided at the main points where people are present.
The air control blades can be altered using a DG blade adjusting key.
20
21
22/23
24/25
26/27
31/32
Explanatory note
The following calculation principles are based on tests and
experience and are valid for the dimensioning of
TROX HESCO diffusion grilles. The diagrams and data on
the minimum distances are designed so that, when the dimensioning is correct, no draughts occur in the occupied
zone (as long as no air stream gradients due to temperature
differences are present).
Diagram 11
Single and continous supply air grilles installed at ceiling
level (Coanda effect), calculation example
30
Ge
B
(min. Dh/2)
~Dh
Rau
RB =
vL = 0.5 m/s
vL = 0.35 m/s
Technical Data
Seitenwand
~ 0.25 RT
~ 0.5 RT
Wurfweite(free
L0.5 = 0.75
RT
Diagram 1, undisturbed supply air stream
air stream)
Raumtiefe
RT grilles) of the types: DG..., DGR..., DGL..., DGX...,
This diagram is applicable for TROX HESCO standard supply air
grilles (single
Raumlnge
RL air stream spreading.
DGSELF and DGVAR (without DG13) with blades in straight positions and
unobstructed
20
1.8 m
Occupied zone
Side wall
Secondary air
Primary air
vK
vL = 0.35 m/s
vL = 0.5 m/s
vL = 0.35 m/s
B
~Dh
~ 0.25 RT
~ 0.5 RT
Opposite wall
~Dh
(min. Dh/2)
B
vL = 0.35 m/s
vL = 0.5 m/s
Dh
veff
(min. Dh/2)
RB = x B + (x + 1) Dh
Room width RB
Room heigth RH
RH ~ 1.8 + (0.28 RT) + H
min. height EH
EH ~ 1.8 + (0.176 RT)
>
~ 0.18 RT H Dh = 0.18 RT
Side wall
Throw L0.5 = 0.75 RT
Room depth RT
Room length RL
For grilles with blades in straight position, the air stream leaving the outlet diverges in the horizontal or vertical plane by the
angle = 20, Distance Dh = 0.10 RT
Calculation example
Given
Room length RL = 8.5 m, room width RB = 5 m, room height RH = 4.5 m, mounting height EH = 3.0 m,
air flow rate = 1240 m/h, resp. 344.4 l/s
Wanted
Grille dimension B x H, room depth RT, outlet velocity veff, distance Dh, pressure drop ps,
sound power level LwA, LwNC, LwNR
Solution
The large room height allows to select the air outlet according to diagram 1, page 4 (unobstructed air stream spreading)
Result
2 off DG1, 600 150 mm, room depth RT = 8.4 m, outlet velocity veff = 2.6 m/s, Dh = RT 0.1 = 8.4 0.1 = 0.84 m,
pressure drop ps ~ 2.5 Pa, (diagram page 19,
sound power level LwA = 17 + 2 = 19 dB(A),
LwNC = 19 - 4 = 15, LwNR = 19 - 2 = 17.
More exact details for LwA and Dps see page 21.
min 0.84 m
0.6 m min 0.42 m
min 0.42 m 0.6 m
Technical Data
1)
611.1
2100
583.3
2000
555.6
1900
527.8
1800
500.0
1700
472.2
1600
444.4
1500
416.7
1400
388.9
1300
361.1
1200
333.3
1100
305.6
1000
277.8
900
250.0
x2
750
900
x
2200
15
638.9
0x
2300
18
de
pth
14
50
14
Roo
16
15
md
ept
Ro
hR
om
16
T [m
]
Recommended
working range
60
RT
[m
]
15
18
20
20
22
75
0x
15
22
90
666.6
2400
25
2500
694.4
Diagram 1
0x
722.2
1)
60
2600
250
750.0
50
1)
2700
12
194.4
600
10
8
4
138.9
200
100
0
om
Ro
83.3
th
dep
RT
[m]
400
x 50
x 50
300 x
50
200 x 50
55.6
2
27.8
0
x5
300
111.1
400
500
500
x5
600
166.6
50
x1
700
0
75
222.2
0
30
800
15
10
12
40
Technical Data
500.0
1700
472.2
1600
444.4
1500
416.7
1400
388.9
1300
361.1
1200
333.3
1100
305.6
1000
277.8
900
250.0
1800
20
527.8
0x
1900
60
555.6
20
0
2000
0x
583.3
75
2100
20
0
611.1
26
2200
x3
00
638.9
90
0x
2300
[m
x
0
40
18
75
10
12
00
14
10
60
x1
12
00
10
50
0x
222.2
600
pt
194.4
700
40
800
om
de
RT
300
400
111.1
200
100
200
14
x 10
x 10
12
83.3
x 10
250
138.9
Air flow rate [l/s]
500
10
[m
Ro
166.6
300
x1
Roo
md
epth
16
RT [
m]
14
Ro
om
de
pth
20
RT
Recommended
working range
16
20
90
10
22
18
50
20
24
666.6
600
2400
24
694.4
x 30
2500
Diagram 1
900
722.2
22
2600
1)
20
750.0
1)
2700
10
8
55.6
6
27.8
4
2
gerade
20
Technical Data
44
44
110
84
gegeneinander
140
position des lamelles divergentes 140 position oppose par paire des lamelles
60
80
90
180
20
Distanz Dh
0.10 RT
horizontal
ausblasend
22
22 42 55
55 42
gerade
gerade
RT84
0.29
RT4422 0.42
70 5542
42
5570 0.6 RT110
22
Distanz Dv
Blades
positions
=
1/7 = =
1) 1/7
vertikal
ausblasend
*)
0.10 RTg
R1/9
1/7 1/70.25 RT
1/9 1/9 1.25 R
1/9 1/9
1/9 1/9
T441/9 1/9
0.25 RTg
1) 0.76
3.26 RT140
1.07
RT84
T110
The divergence of the air stream and with its throw, can be controled by adjusting the vertical blades at the front of the grille.
prem.
et dern.
fente
couverte
The adjustment is made with a specially
'DG-key'
which
is being
supplied at no cost. The air stream drop can be
RT designed
Raumtiefe
affected
by adjusting the horizontal
RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT
RT grille.
RT44back
Diagr.blades
1 und at
2 the
= 0.77ofthe
fr die
SomeFaktoren
important
positions of the vvertical
blades
veff 44= 1.18
eff = 1,0
eff. Ausblasgeschw. veff
veff110= 1.52
22
parallles1)
Angle d'talement
du jet
841/3
1/3
60
20
22
gerade
1/344
44
80
gerade
Distance Dv
0.25 RT
22
55 42
diffusion
verticale
*)22 42 55
= local
=
=
1/7 1/7 du
1)Profondeur
0.76
RT44
70
22
5542
gerade
blades
position
blades position 140 diverging
Distance
Dh 110 diverging
0.42 RT84
0.10 RT
0.29 RT44
diffusion horizontales
70
42
22
1.07
55
RT84
42
22
1/5
1/5
110
1)
gerade
22 42
1/5
1/5
140
90
opposes
180
1/5
20
0.10 RTg
0.6 RT110
1.25 RT110
3.26 RT140
0.25 RTg
RT
1/9 1/9 1/9 1/9 1/9 1/9 1/9 1/9 1/9
Diagr. 1 et 2 1) RT44 = 0.77 RT RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT
1/7 1/7
veff = 1,0
44
84
110
140
opposed
20
60
80
90
180
20
Distance Dh
horizontal blowing out
0.10 RT
0.29 RT44
0.42 RT84
0.6 RT110
0.10 RTg
Distanz Dv
vertical blowing out *)
0.25 RT
0.76 RT44
1.07 RT84
1.25 RT110
Room depth
Faktor of the
outlet velocity veff
3.26 RT140
0.25 RTg
RT
Diagr. 1 and 2 RT44 = 0.77 RT RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT
veff = 1,0
Gege
vL = 0.35 m/s
Technical Data
(min. Dh/2)
~Dh
Rau
RB = x
vL = 0.5 m/s
~ 0.18 RT H + 0.025
/2 ~ 10
vL = 0.5 m/s
vL = 0.35 m/s
vL = 0.5 m/s
vL = 0.35 m/s
vL = 0.5 m/s
vL = 0.35 m/s
Occupied zone
(min. Dh/2)
1.8 m
Secondary air
vK
(min. Dh/2)
Opposite wall
veff
Side wall
Dh
Primary air
B
~Dh
RB = x B + (x + 1) Dh
Room width RB
~Dh
Room height RH
Seitenwand
~ 0.25 RT
Diagram 2, grilles installed~ 0.5
at R
ceiling
level (Coanda effect)
T
This diagram is applicable for TROX HESCO standard
supply
grilles
Wurfweite
L0.5 =air
0.75
RT (single grilles) of the types: DG..., DGR..., DGL...,
DGX..., DGSELF and DGVAR (without DG13) with blades inRaumtiefe
straight position,
grilles installed at ceiling level.
RT
Raumlnge RL
Minimum distances
~ 0.25 RT
~ 0.5 RT
Side wall
Throw L0.5 = 0.75 RT
Room depth RT
Room length RL
For grilles with blades in straight position, the air stream leaving the outlet diverges in the horizontal or vertical plane by the
angle /2 = 10, distance Dh = 0.10 RT
Calculation example
Given
Room length RL = 12 m, room width RB = 4.0 m, room height RH = 4.0 m,
air flow rate = 1060 m/h resp. 294.4 l/s,
Wanted
Grille dimension B x H, room depth RT, outlet velocity veff,
distance Dh, pressure drop ps, sound power level LwA,
LwNC, LwNR
min 1.15 m
Solution
Air outlet just under the ceiling, in diagram 2, page 9, has the result by per grille = 530 m/h.
Result
2 off DG6 600 100 mm, damper position 50%, veff = 3.3 m/s, room depth RT = 11.5 m, distance Dh = RT 0.1 =
11.5 0.1 = min. 1.15 m. According diagram page19, follows: ps50 ~ 15 Pa, sound power level LwA = 37 dB(A), LwNC
= 37 - 4 = 33, LwNR = 37 - 2 = 35. More exact details for LwA and Dps see page 25.
7
Technical Data
1900
527.8
1800
500.0
1700
472.2
1600
444.4
1500
416.7
1400
388.9
555.6
15
2000
0x
583.3
75
2100
611.1
15
2200
0x
638.9
250
2300
600
x
666.6
15
x
277.8
900
250.0
15
x
0
50
20
166.6
12
12
600
600
10
194.4
700
300
200
100
111.1
om
Ro
T
th R
dep 10
[m]
400
83.3
55.6
x5
x 50
x 50
300 x
50
200 x 50
4
2
27.8
0
500
12
8
4
400
138.9
Air flow rate [l/s]
500
50
10
222.2
0x
75
800
15
x
00
1000
18
305.6
16
1100
14
333.3
26
24
22
20
18
1200
15
16
361.1
00
14
1300
60
m
Ro
o
T [m
]
24
22
Roo
md
ept
hR
Recommended
working range
26
de
p
2 th
RT
30
2400
250
694.4
Diagram 2
1)
[m
]
2500
750
x
722.2
2600
x 25
750.0
900
2700
1)
90
1)
Technical Data
1000
277.8
0
10
0
26
75
24
22
12
RT
[m
de
10
300
250
138.9
111.1
300
83.3
200
400
100
55.6
27.8
10
14
12
200
500
10
o
Ro
166.6
600
x
0
]
[m
RT
pth
de
om
Ro
14
h
pt
194.4
700
x1
x
00
10
222.2
800
00
0
50
250.0
900
40
22
20
18
20
305.6
18
1100
16
333.3
16
1200
60
14
361.1
10
12
1300
16
00
x1
x 10
x 10
22
388.9
20
0
1400
20
0
416.7
20
0
1500
60
0x
444.4
0x
1600
50
472.2
x1
00
1700
Recommended
working range
90
0
500.0
1800
20
527.8
0x
1900
75
555.6
300
2000
900
x
583.3
600
x
2100
30
611.1
28
2200
300
638.9
900
x
2300
30
666.6
28
2400
T [m]
694.4
26
2500
Diagram 2
pth R
722.2
m de
2600
Roo
750.0
24
2700
200
1)
1)
18
277.8
D
>
D = 0.1
1000
16
250.0
14
700
paroi m]
Luftvolumenstrom fr 1 m Gitterlnge [m/h,
wall
grille 222.2
800
vue12
sur la grille
1m
194.4
10
166.6
600
[
Diagram 3, unobstructed air stream spreading, continuousRgrilles
(free air stream)
T
200
83.3
D
300
Empfohlener
Arbeitsbereich
55.6
2
1m
388.9
1300
361.1
1200
333.3
1100
305.6
1000
277.8
900
250.0
800
222.2
700
194.4
1400
20
10
22
N
om
.s
ize
20
of
gr
ille
18
[m
50
16
14
600
500
400
300
200
100
0
12
166.6
10
138.9
de
pt
om
111.1
RT
[m
Ro
83.3
4
Recommended
working range
55.6
27.8
0
800
700
600
500
400
300
200
100
15
25
30
416.7
1500
Front6view on grille
7
Technical Data
900
900
gaine dair
1000
22
222.2
plafond
700
194.4
18
16
600grille 166.6
500
Technical Data
]
[m
T
R
vue
fe sur la grille
tie
14
1m
138.9
20
800
gaine dair
um
12 B
Diagram 4, unobstructed air stream spreading, continuous
Ra grilles (Coanda effect)
This diagram400
is applicable
grilles (B/H > 16), types: DG1, 3, 5P, 6 and 8, with blades in
111.1forTrox Hesco continuous supply air10
straight position, grilles installed at ceiling level.
300
6
recommandation
for the montage
see page 16, p.1.3
Empfohlener
ceiling
55.6
Arbeitsbereich
H
200
supply air
100
duct
83.3
27.8
grille
0
1m
2
388.9
1300
361.1
1200
333.3
1100
305.6
15
0
1400
20
416.7
30
1500
0
25
0
10
1000
277.8
900
250.0
800
222.2
700
194.4
Air flow rate per 1 m grille length [l/s, m]
om
.s
ize
500
300
200
100
0
ille
[m
26
m
]
50
22
20
18
16
14
138.9
400
gr
24
166.6
600
of
12
T
hR
[m
pt
om
de
Ro
10
111.1
8
83.3
6
Recommended
working range
55.6
27.8
0
Note: In a light cooling case (transition period) and 2-speed operation veff >
= 1.5 m/s
Calculation example:
Total air flow rate = 1800 m/h, resp. 500 l/s, room length RL = 11.0 m, room width RB = 5.0 m, grille length B ~RB,
therefore air flow rate per m grille length = 360 m/h,m, resp. 100.0 l/s, therefore grille dimension DG1, 5000 50 mm,
room depth RT = 9.0 m, veff = 2.7 m/s, pressure drop Dps, sound power level LwA and LwNC, LwNR according to diagram
page 19, drop of the air stream according to diagram page 14. More exact details for LwA and Dps see page 21.
11
250.0
900
Raumtiefe RT
ef
fe
tC
av
ec
d'
air
Technical Data
10
jet
12
6
4
= S R
L0.5 0.176
16
14
Co
an
d
12
ith
10
tw
Je
18
ef
fe
ct
Diagram 9
(RT 0.176) + y
~1.8
Fre
e je
EH ~ (RT t 0.176) + 1.8 m + y
0
7
4
5
6
2
3
1
Calculation example
Vitesse dinsufflation veff [m/s]
1 off DG1 600 100 mm, blades in straight position,free stream, air flow rate: = 500 m/h, resp. 139 l/s, outlet velocity
veff = 3.1 m/s. It follows of diagram 9: L0.5 / = 8.5 [L0.5 = 8.5 = 4250 m/h, resp. 1180 l/s]
TS
= S R
L0.5 0.176
4
5
6
2
3
Outlet velocity veff [m/s]
y
(RT 0.176) + y
TS
~1.8
If the temperature in the air stream is warmer or cooler, the air stream will rise or drop accordingly. This drop or rise of the air
stream can bewidely controlled by adjusting the horizontal blades of the diffusion grille. Divergently set diffusion grilles reduce
the air stream deviation y.
Diagram 9 shows that the mixing of primary air with secondary air is very intensive. This results in a temperature adjustment between non-isothermal air stream and room temperature. So is i.e. the difference of temperature in the axial air
stream after reaching the throw of air QL0.5 = 0.35 Q/v".
Room depth RT
12
L0.5 0.176
= S R
~1.8
TS
(RT 0.176) + y
Throw L0.5
Notation
QS = Air stream temperature at the
grille (supply air)
QR = Room temperature
Q = Difference of temperatur
(temperature supply air to
room temperature)
y
= air stream drop in cooling case
(air stream rise in heating case)
RT = Room depth acc. diagram
(pages 4+5, 8+9, 10+11)
L0.5 = Throw
ligne de rfrence
Einzelgitter
Technical Data
chute du jet10
son extrmit
Diagram
4.0
3.0
Grille individuelle
Drop of the axial flow stream at the terminal point at Q, straight blades, single grille, unobstructed air stream spreading.
0.5
0.4
2
900 x 150
600
500
400
300
750 x 200
600
500
400
900 x 250
750
600
900 x 300
600
Single grille
1.5
0.3
900 x 100
600
500
400
300
250
200 x 100
600 x 50
500
400
300
200 x 50
0.5
0.1
0.2
8
Nominal dim.
of the grille
B x H [mm]
0.08
Auxiliary line
2.0
3.0
4.0
5.0
Factor 1
Factor 0.4...0.5
Factor 0.2...0.3
Factor 0.1...0.2
Factor 0.5...1.0
Recommendation
a) In the heating and/or cooling cases veff >
= 1.5 m/s (always use divergent control blade arrangement)
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m
Calculation example
Air flow rate = 330 m/h, resp. 91.7 l/s, DG1, 600 100 mm, room depth RT = 4.8 m, diagram 1, page 5, veff = 2 m/s.
Q at the grille is 4 K(-), therefore air stream drop Y20 = 1.15 m.
Problems are mainly encountered where cooled air is to be supplied through grilles. To avoid undue drop of the cold
air stream in the occupied zone, following rules can help:
Select grilles with outlet velocity as high as possible. Select several small grilles iinstead of one or two large ones.
Install grilles as high as possible above floor at alternative levels. Incline the horizontal blades at the back of the grille
in order to compensate for any air stream drop or direct the cold air along ceiling level (refer also to following explanations 'Grilles installed at ceiling level'). Adjust the vertical blades at the grille front in opposed positions, to increase air
entrainment and hence to achieve better mixing of the cold air stream with secondary air (drop at the air stream terminal point y ~ 0,85 Y20 ).
13
Hilfslinie
Technical Data
Einzelgitter und
DG-Bnder
Diagram 11
(relating to diagrams 2 + 4)
Single and continuous grilles, installed at ceiling level. (Coanda effect)
Cold air stream grilles installed close or at ceiling level have a tendency to adhere to the ceiling and do not drop under
certain conditions, which depend onTemperaturdifferenz
temperature difference,
size
and
velocity. It is important to ensure that the
amgrille
Gitter
[K]outlet
(Khlfall)
Grilles is
individuelles
ceiling
absolutelyetflat, already small obstructions like light fittings, beams etc. can deflect the air stream and cause draft
sous forme
de occupied
bande14 zone.
effects
in the
6
5
3
4
7
10 9 8
2
12
600 x 300
900 x 300
300
200
150
250
Nom. height of the grille H [mm]
100
50
Continuous grilles B/H > 16
0.5
400 x 200
500
600
750
200 x 50
300
400
500
600
200 x 100
250
300
400
500
600
900
300 x 150
400
500
600
900
600 x 250
750
900
Single grille
Auxiliary line
12
10 9
Recommendation
> 1.5 m/s (always use divergent control blade arrangement)
a) In the heating and/or cooling cases veff =
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m
Calculation example
Air flow rate = 410 m/h, resp. 113.9 l/s, room depth RT = 9.0 m, diagram 2, page 9, DG1,
600 100 mm, veff = 2.5 m/s,
Q at the grille is 5 K (), from diagram 11 we can see: No cold air stream drop will occur.
14
ligne de prfrence
Technical Data
DG - Bnder
diffrence de temprature la grille [K]
1
5 6 7 8 9 101214
Diagram 12
(relating to diagram 3)
Continuous grilles with blades in straight position, unobstructed air stream spreading (free air stream), drop of the
0.8
5.0 6.0 7.0 8.0 10.0
1.0 1.2 1.4 1.6 1.8 2.0
4.0
axial air streams. Valig for grille dimension about3.0
5000 mm.
Y20 values forchute
otherdu
grille
on request.
jet dimensions
dair son extrmit
pour une
Grilles sous forme de bande
( monte du jet d'air en cas de chauffage )
temprature de 20C = y20 [m]
Continuous grilles
100
200 150
50
Auxiliary line
0.8
1.0
3.0
4.0
5 6 7 8 9 101214
5.0
10.0
Recommendation
> 1.5 m/s (always use divergent control blade arrangement)
a) In the heating and/or cooling cases veff =
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m
15
Technical Data
Application examples for various DG-grilles
1. Supply air
1.1 Air flow direction in duct = outlet direction by the grille, e.g. branch ducts.
For single grille at the duct terminal point, select: DG1 or DG6
dgl 12
vk1
[m]
vk1
veff
vk1
vk1
veff
vk1
veff
veff
Where small air velocities vk1 and small pressure differences in the duct prevail DG1. Minor air flow adjustments are
possible by turning horizontal blades (< 20 Pa).
Where pressure and velocity fluctuations are to be expected, select grilles with volume control devices: DG6.
1.2 Air flow direction in the duct is perpendicular to the air discharge direction at the grille
If a grille or several diffusion grilles are built into an air duct in this way, then on the one hand the air must be discharged
evenly over the entire grille area and, on the other hand, the same volumetric air flow be discharged from all grilles. It is
possible to satisfy these conditions in all cases when the various diffusion grille types are correctly employed.
vk2
We differentiate between
a) Pressure duct
veff
veff
veff
Ducts with large cross sectional area. Air velocity in duct is smaller than the outlet velocity at the grille
vk2 < v", therefore: DG6
Ideal air distribution at the grille:
vk2 < 0.5 veff
Efficient air distribution at the grille: vk2 < 0.8 veff
b) Flow duct
(see also description of prospectus DG5)
Ducts with large cross sectional area. Air velocity in duct is larger than the outlet velocity at the grille
vk2 > v", therefore: DG5, DG7 oder DG17
DG5
Suitable for airconditioning systems, offers wide volume control.
Ideal air distribution at the grille:
vk2 < 2.5 veff
Efficient air distribution at the grille:
vk2 < 5.2 veff
DG7 and DG17
Suitable for warm air heating systems and industrial applications.
Ideal air distribution at the grille:
vk2 < 1.8 veff
Efficient air distribution at the grille:
vk2 < 3.5 veff
vk2
veff
veff
veff
1.3 In supply air grilles, we recommend setting up active and passive zones, e.g. 1 m active, 1 m passive 1 m active and so
on. This reduces the room depth (air throw) by as much as 66% (depending on the nominal height H).
1.4 Diffusion grille DGVAR or DGSELF with temperature-dependent air stream deflection.
We recommend the use of the DGVAR or DGSELF type when the room height RH >
= 4.0 m.
2.
Exhaust air
2.1 Single grilles: DG3 or DG1, eventually DG13. Several grilles for one duct, with small pressure differentials only: DG1
(Minor air flow adjustments are possible by changing the position of the horizontal blades at the grille front). Several
grilles for one duct: DG8 or DG7.
16
50 mm
DG
DGR
DGRA
Technical Data
1400
560
280
*100
450
1800
140
180
355
710
1120
224
900
*250
*315
*800 *1000 *1250
*160
*400
*125
*200
*500
1600
*630
2000
=
* =
rayon extrme
diamtre de gaine selon EN 1506 et EN 12220
(avant: DIN 24 154 feuille 2 srie prfrentielle)
3. Duct - respectez
- range la
forprofondeur
the DGR...
types pour DGR5 / 7 / 17
de -montage
The following table shows for which duct diameter range the appropriate nominal grille height H may be used.
250
1) DG
DGR
DGRA
200
DG
DGR
DGRA
150
DGR
DGRA
100
DG
DGR
DGRA
DG
50
Nominal dimension H
DG
DGR
DGRA
1400
560
*100
280
450
1800
140
180
355
710
1120
224
900
*250
*315
*800 *1000 *1250
*160
*400
*125
*200
*500
1600
*630
2000
=
* =
extreme range
duct diameter as per EN 1506 and EN 12220
(former: DIN 24 154 sheet 2 preference series)
check depth of opening for DGR5 / 7 / 17
B = Nennbreite
200
300
400
500
600
750
1) Nominal height of the grille H = 250 mm is for the types DGR and DGRA not available on stock.
DGR5 und DGRA5
90
100
110
115
125
145
T DGR7 / 17 und DGRA7 / 17
max.155 (100% offen)
DGR5 et DGRA5
DGR7 / 17 et DGRA7 / 17
90
[mm]
170
[mm]
[mm]
300
400
600
750
900 2)
[mm]
100
110
115
125
max.155 (100% ouvert)
145
170
[mm]
500
900 2)
[mm]
B
B = nominal width
200
300
400
600
750
900 2)
[mm]
90
100
110
115
125
max.155 (100% open)
145
170
[mm]
500
[mm]
2) Nominal width of the grille B = 900 mm is for th types DGR and DGRA not available on stock.
17
0
0
Beispiel von S. 7
Technical Data
Beispiel von S. 3
Beispiel von S. 6
min. Einbauhhe
1.00
10
11
13
12
14
15
16
- Isothermal case
- Free air stream (undisturbed spreading out of the air flow)
- Discharge immediately below and along the ceiling
5.00
d'talement
isothermheight
/2 (env.
Formula for the angle
calculation
of the mounting
EH < 10)
4.50
Lgende
RT case
= profondeur du local [m] = L0.35
for a cooling
EH
= min. hauteur de la montage [m]
EH(-)
= 1.8 + (RT 0.1763)
y [m]grille)
(OK +
FB...UK
tan (10)
= 0.1763
[m]
3.50
Formulas for the calculation of the room depth RT for various blade positions (divergences)
3.00
[m]
2.00
1.80
RT44 blades position 44 diverging
1.00
(EH - 1.8)
0.7 0.1763
[m]
Exemple page 6
RT44 =
RT84 =
0
(EH - 1.8)
0.5 0.1763
1
[m]
3
RT110 =
(EH - 1.8)
0.4 0.1763
Exemple page 7
Tstraight
Exemple page 3
2.50 R
[m]
(EH - 1.8)
1.2 0.1763
RTopp =
8
10
11
12
[m]
13
14
15
16
5.00
Legend
RT
EH
4.50
tan (10)
3.50
3.00
2.50
0
0
18
example page 3
1.00
example page 7
2.00
1.80
example page 6
4.00
10
11
12
13
14
15
16
Technical Data
Sound power level LwA and pressure drop ps for diffusion grilles (overall view)
LwA valid for nom. dimension B x H = 600 x 100 mm, nom. surface of ref. A0 = 0.06, sound power level of ref. W0 = 10-12 W
Supply air
veff [m/s] 2
2.5
3.5
4.5
5.5
6.5
7
vk1
DG1
DG5
DG6
1.5
ps [Pa]
LwA [dB(A)] 12
2.4
2.8
10
13
15
18
16
20
24
28
31
34
36
38
41
44
14
ps [Pa]
LwA [dB(A)] 36
21
27
35
43
55
64
73
82
93
110
40
43
46
50
52
54
55.5
57
58.5
60
20
ps [Pa]
LwA [dB(A)] 48
28
35
43
51
64
74
85
97
110
125
50
52
54
56
58
59
60
61
62
63
30
ps [Pa]
LwA [dB(A)] 56
38
48
56
64
75
86
98
108
116
132
57
58
59
60
61
62
63
64
65
66
1.5
ps [Pa]
LwA [dB(A)] 12
2.5
3.5
12
14
17
21
24
16
21
25
29
33
36
39
41
43
45
5
ps [Pa]
LwA [dB(A)] 21
13
17
21
24
30
37
43
51
60
29
35
38
41
43
45
48
51
53
55
DG17
other position of blades:
110 div.: veff 1.1
opp.
: veff 1.2
140 div.: veff 1.35
vk2 = 3 m/s
vk2 = 6 m/s
vk2 = 9 m/s
vk1
100 %
vk1
50 %
18
ps [Pa]
LwA [dB(A)] 46
23
29
36
42
52
60
67
75
82
90
48
50
52
54
55.5
57
58
59
60
61
26
ps [Pa]
LwA [dB(A)] 55
31
39
45
52
61
70
78
85
94
104
56
57
58
59
60
61
62
63
64
65
9.3
ps [Pa]
LwA [dB(A)] 28
14
20
28
35
45
55
67
78
90
105
32
36
41
43
47
51
53
54
56
58
-13
-16
-20
-24
-28
-32
vk2 = 6 m/s
vk2 = 9 m/s
vk1
DG13
Exhaust air
vk3
DG8
ps [Pa]
LwA [dB(A)]
-2.5
-4.4
-6
-8
-10.5
13
17
21
25
29
32
35
37.5
40
42.5
45
ps [Pa]
LwA [dB(A)]
-18
-23
-27
-32
-37
-42
-47
-52
-57
-62
-68
39
40.5
42
44
46
47.5
49
50.5
52
53
54
ps [Pa]
LwA [dB(A)]
-28
-33
-38
-43
-48
-53
-58
-63
-68
-78
-88
52
53
54
55
56
57
58
59
60
61
62
ps [Pa]
LwA [dB(A)]
-10.5
-16
-23
-32
-40
-52
-63
-76
-91
-105
-120
35
38
42
47
49
52
56
58
60
61.5
63
veff [m/s]
2.5
3.5
4.5
5.5
6.5
100 %
DG13
+9
+6
+3
0
-3
-6
-9
Lw2 [dB]
DG7
0.25
0.5
f1 = A
Ao
vk4 = 6 m/s
vk4 = 9 m/s
vk3
LwNC, LwNR:
LwNC = LwA - 4
LwNR = LwA - 2
19
Technical Data
Example (to page 19)
Given
Wanted
a) pressure drop ps (static pressure drop in the duct in front of the diffuser)
b) sound power level LwA of one diffuser, LwNC, LwNR
Solution
Page 19
Handling: veff corr. = 2.9 1.2 = 3.48 m/s (count with f4, because the blades ar in opposed position).
By DG5, veff corr. = 3.48 m/s and vk2 = 6.0 m/s can be determined ps and LwA.
Conclusion
= 2.9 m/s
= DG5
= 600 50 mm
= opposed position
= 6.0 m/s
a) pressure drop ps = 43 Pa (static pressure drop in the duct in front of the diffuser)
b) sound power level LwA = 54 dB(A). This value corresponds to a grille B x H = 600 x 100 mm. Of the table
'correction of the grille dimension' we see:
f1 = A = 0.03 = 0.5
Ao 0.06
The result is a correction of -3 dB.
Sound power level LwA = 54 - 3 = 51 dB(A) / diffuser, LwNC = 51 - 4 = 47 dB(A), LwNR = 51 - 2 = 49 dB(A)
H [mm]
20
dgl = 2 x B x H [m]
(B + H)
B [mm]
200
250
300
400
500
50
0.080
0.083
0.086
0.089
0.091
100
0.133
0.143
0.150
0.160
150
0.171
0.188
0.200
200
0.200
0.222
250
0.222
300
0.240
600
750
900
0.092
0.094
0.095
[m]
0.167
0.171
0.176
0.180
[m]
0.218
0.231
0.240
0.250
0.257
[m]
0.240
0.267
0.286
0.300
0.316
0.327
[m]
0.250
0.273
0.303
0.333
0.353
0.375
0.391
[m]
0.273
0.300
0.343
0.375
0.400
0.429
0.450
[m]
Technical Data
Sound power level DG1 supply air (without quantity adjustments)
1. Sound power level LwA and pressure drop pt; ps, DG1, B H = 600 100 mm,
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
50 60 70 [Pa]
60
Sound power level LwA [dB(A)]
pt 2
60
50
40
30
20
15
10
40
30
20
50 60 70 [Pa]
60
50
50
40
40
30
30
A)
B(
> dgl 12
DG1, 600 x 100 mm
Ao = 0.06 m
20
v"
ps
pt
15
20
15
60
60
50
50
50
40
40
40
60
pt 2
d
Bla
2
1.5
14
rg.
ive
Hz
00
80
50 60 70 [Pa]
8
.
g
7
r
ive
d
6
0
1
40
s.
rg. 1
ive
.
erg
d
4
es
d
0
12
po
iv
44
ig
tra
ss
15
30
20
ht
Hz
10
00
Hz
0
50
12
50 60 70 [Pa]
8
7
rg.
e
iv
d
6
Hz
15
00
z
125H
40
12
20
20
20
15
30
Hz
20
250H
30
00
30
10
100 mm
.06 m
d
Bla
d
ose
s.
po
op
2
1.5
1.5
50 60 70 [Pa]
ps
10
15
20
25 30
40
50 60 70 [Pa]
3. Correction factor
for DG3
ps DG3 = 0.8 x ps DG1
Lw2 [dB]
+9
+6
+3
0
-3
-6
-9
0.25
0.5
f1 = A
Ao
21
Technical Data
Sound power level DG5 supply air
1. Sound power level LwA and pressure drop pt; ps, DG5, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
pt 7 8 9 10
70
60
20
15
25 30
50 60
40
80 100
50
150
40
70
60
vk1
40
)
B(A
30
[Pa]
Direct stream
(
50
DG5
600 x 100 mm
Ao = 0.06 m
veff
ps
30
20
pt
> dgl 12
20
60
60
50
50
40
40
8 9 10
15
30
vk2
20
ps
20
80
40
00
00
Hz
Hz
00
00
20
Hz
Hz
250
z
0H
50
20
30
Hz
125
10
30
50
40
60 70 80
100
170 pt [Pa]
130
90 110
150
pt
In the stream duct
13
10
8 9 10
15
20
30
60 70 80
50
40
15
12
12
8 9 10
15
20
30
60 70 80
50
40
5
4
100 130
170 ps [Pa]
150
90 110
15
6
2
ty
ti
an
Qu
100 130
170 pt [Pa]
150
90 110
Direct stream
0%
10
%
50
t
en
tm
jus
ad
tity
an
Qu
en
tm
s
dju
4
3
0
110
geg.
140
1.5
7
0
0
11eg.
g 0
14
22
8
6
4
0
11 13 15 17
21 25 29
33
37 45 53
61
88 108
69
148
ps [Pa]
98
168
77
128
Direct stream
veff
Technical Data
2. Correction 'dimension of the grille'
+9
+6
+3
0
-3
-6
-9
Lw2 [dB]
0.25
0.5
f1 = A
Ao
Duct dimensions:
300 x 50
200 x 50
0.585
BxH
200 x 100
250 x 100
0.638
0.647
400 x 50
500 x 50
600 x 50
750 x 50
0.599
0.606
0.610
0.613
0.616
300 x 100
400 x 100
500 x 100
600 x 100
750 x 100
[mm]
[-]
0.653
0.661
0.666
0.669
0.672
BxH
300 x 150
400 x 150
500 x 150
600 x 150
750 x 150
0.673
[-]
0.695
900 x 200 [mm]
[-]
0.706
0.681
0.686
0.690
0.693
BxH
400 x 200
500 x 200
600 x 200
750 x 200
0.692
0.697
0.701
0.704
BxH
600 x 250
750 x 250
0.707
0.711
5. Examples
5.1 Direct stream (
Given
Wanted
a) LwA in dB(A), LwNC, LwNR
b) ps + pt in Pa
c) vk1 in m/s
Solution
a) LwA = 37 - 3 = 34 dB(A), LwNC = 34 - 4 = 30, LwNR = 34 - 2 = 32
b) ps = 19 Pa, pt = 22 Pa
c) vK1 = 3.2 0.613 = 2.0 m/s
veff
ps
pt
> dgl 12
vk2
Wanted
a) LwA in dB(A), LwNC, LwNR
b) ps + pt in Pa
Solution
a) LwA = 54 - 3 = 51 dB(A), LwNC = 51 - 4 = 47, LwNR = 51 - 2 = 49
b) ps = 43 Pa, pt = 64 Pa
ps
pt
veff
23
Technical Data
Sound power level DG6 supply air - damper 100% open
1. Sound power level LwA and pressure drop pt; ps, DG6, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
Dpt 2
70
60
20
15
20
v"
[Pa]
7
6
50
50
40
40
30
30
20
20
15
z
0H
1.5
[Pa]
80 100
z
5H
12
15
z
0H
50
10
20
Dps
[Pa]
7
6
5
4
3
8 10
15
20 25 30
40 50 60
80 100
[Pa]
Lw2 [dB]
24
80 100
1.5
rg.
e
div
1.5
0.25
40 50 60
s.
.
po
erg 110
div
.
s
rg 84
s
de
ive
os.
d
Bla
dp
44
e
s
po
op
es
d
a
l
+B
rg.
e
v
di
0
14
ht
+9
+6
+3
0
-3
-6
-9
30
ig
tra
15
70
60
20
70
60
Dpt 2
3
5 6
4
7
Damper 100% open
6
Dps
Dpt
15
25
80 100
> dgl ? 12
0Hz
30
30
dB
800
40
(A)
30
50
40
0H
70
60
[Pa]
70
60
40
400
15
80 100
50
Hz
20
40 50 60
50
00
100 mm
0.06 m
30
20
20
30
10
Hz
40
5 6
00
50
10
[Pa]
70
60
80 100
f1 = A
Ao
Technical Data
Sound power level DG6 supply air - damper 75% + 50% open
1. Sound power level LwA and pressure drop pt; ps, DG6, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
g.
0 100
0 100
20
4
3
2
1.5
[Pa]
[Pa]
7
6
5
4
3
2
1.5
0 100 [Pa]
20
15
70
60
50
70
60
50
40
40
30
30
20
20
pt 2
8 10
3
4 5 6
7
6
Damper 75% open
5
4
3
2
1.5
ps
2 3
5 6
8 10
0Hz
30 40 50 60 80 100
20
.
s.
erg
po
rg.
ht
div
g
i
ive
a
4
d
r
t
4
0
ss
11
de
rg.
Bla
s.
e
iv
po
d
sed
84
o
pp
so
de
a
l
B
.+
erg
v
i
d
0
14
20 25 30 40 50 60 80 100
15
30 40 50 60 80 100
20
de
3
2
40
2 3
5 6
8 10
15
20
erg
div
ht
aig
tr
ss
Bla
1.5
ps
15
800
z Hz
z
0H 25H 00
5
5
1
2
0H
15
15
pt 2
8 10
3
4 5 6
7
6 Damper 50% open
5
4 10
44 8 1
v"
ps
pt
15
[Pa]
7
6
5
30
> dgl 12
400
20
30
Hz
30
40
A)
B(
00
40
40
30 40 50 60 80 100 [Pa]
70
60
50
20
20
70
60
50
8 10
5 6
Hz
15
00
20
10
30
0 100
40
0 mm
6 m
0 100 [Pa]
70
60
50
pt 2
70
60
50
+B
es
lad
os.
op
d
ose
s.
po
[Pa]
7
6
5
4
3
2
1.5
[Pa]
4 10
44 8 1
[Pa]
7
6
5
4
3
2
1.5
30 40 50 60 80 100 [Pa]
25
40
9.4 [Pa]
30
ps
20
40
40
30
30
Hz
125
20
Hz
25
pt (-)
1.4
Hz
50
2.6
20
3.9
7.3
9.4 [Pa]
5
20 [Pa]
ps (-)
4
3
Pressure drop ps [Pa]
10
15
20 [Pa]
Lw2 [dB]
26
Exhaust air
DG8, 600 x 100 mm
Ao = 0.06 m
pt
A)
B(
20
+9
+6
+3
0
-3
-6
-9
40
[Pa]
> dgl 12
20
Hz
20
15
10
30
40
30
00
20
10
30
ps (-)
20
Technical Data
0.25
0.5
f1 = A
Ao
Technical Data
Sound power level DG8 exhaust air - damper 50% open
1. Sound power level LwA and pressure drop pt; ps, DG8, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
ps (-)
[Pa]
Sound power level LwA [dB(A)]
60
50
40
30
> dgl 12
pt
ps
Extraction
DG8, 600 x 100 mm
Ao = 0.06 m
20
40
30
26
35
44 53
50 60
[Pa]
50
50
40
40
30
> dgl 12
pt
ps
20
Exhaust air
DG8, 600 x 100 mm
Ao = 0.06 m
20
50
50
40
40
z
0H
z
5H
12
z
0H
50
30
30
25
20
pt (-)
09
0H
0
10
20
13
18
26
35
44 53
[Pa]
2
40
50 60
60
dB
[Pa]
[Pa]
ps (-)
10
15
20
30
40
50 60
[Pa]
Lw2 [dB]
30
40
(A)
Hz
20
30
30
50
60
20
10
Hz
50 60
00
40
20
30
0.25
0.5
f1 = A
Ao
27
Technical Data
Determination of volume air flow rate at TROX HESCO diffusion grilles
Supply air
Tests have shown that the most reliable measurements are obtained using a rotating vane anemometer. Care should be taken
that the anemometer head lies on the grille blades. The figure shows the exact position of the head containing the vanes:
* B/2; but between two blades !
*B/2
1
Einstellung der
vorderen Lamellen
1 = 22
1.07
1 = 42
0.98
1 = 55
0.80
44
1.03
0.93
0.88
0.80
84
0.89
0.88
0.84
0.73
110
0.74
0.77
0.76
0.70
140
0.56
0.62
0.59
0.60
gegeneinander
0.57
0.55
0.54
0.50
0 gerade
0.74
0.77
[m/s]
0.55
0.76
0.70
0.59
0.60
0.54
0.50
The size of the correction factor f2 is dependent on the setting of the air control blades.
This applies to all DG types (DG1, DG3, DG5, DG6, DG7, DG8, DG17, DGL, DGX and DGR).
Setting of the
blades in front
1 = 22
1.07
1 = 42
0.98
1 = 55
0.80
44
1.03
0.93
0.88
0.80
84
0.89
0.88
0.84
0.73
110
0.74
0.77
0.76
0.70
140
0.56
0.62
0.59
0.60
opposed
0.57
0.55
0.54
0.50
0 straight
The supply air volume flow ZL of an air diffuser is calculated according to the formula below.
ZL = veff A 3600 r
= vgem f2 A 3600 r
= vgem f2 A 2'700
28
[m/h]
Technical Data
Example
Given
DG1, 600 100 mm, Blades in straight position.
vgem (taken of measuring) = 2.8 m/s
Wanted
Luftvolumenstrom
[m/h]
Luftgeschwindigkeit vk2
max. [m/s]
Calculated
bis 1000 ZL = veff A 3600
3 r
bis 4000
= vgem f2 A 3600 r
= 2.8 1.13 0.6 0.1 3600 0.77 0.974
bis 1500
bis 5500
= 515 m/h, 3.5
diffuser
bis 2000
bis 7000
5
5.2
5.5
Exhaust air
Tests have shown
the most reliable measurements
are obtained using
rotating vane anemometer. Care
bisthat
2500
4.2
bis a10000
6 should be taken
that the anemometer head lies on the grille blades (as shown in the figure).
3000 air velocity v, the measured
4.5
10000 by a correction factor
7 f .
be multiplied
To calculate thebis
exhaust
value vgem has to ber
3
The correction factor f3 is 1.053. This is valid for all DG types (DG... and DGR...1 to 8, DG17, DGL..., and DGX...) with straight
blade positions.
The exhaust air volume flow AL of an air diffuser is calculated according to the formula below.
Dbit d'air
Dbit d'air
Vitesse d'air vk2
[m/h]
[m/h]
max. [m/s]
1000
3
AL = veff A 3600 r
= vgem f3 A 3600 r
A 2'700
= vgem 1.053
3.5
1500
2000
4000
[m/h]
5500
5.2
7000
5.5
4.2
2500
10000systems (pipes and ducts)
6
Maximum air
velocity in ventilation
and air conditioning
3000
plus 10000 services
Explanatory note:
Recommendations from4.5
diverse energy-saving consultancy
until 1000
until 4000
until 1500
3.5
until 5500
5.2
until 2000
until 7000
5.5
until 2500
4.2
until 10000
until 3000
4.5
more than10000
29
Technical Data
Definitions
Throw L0.5 [m]
The throw is the horizontal or vertical axial distance vL0.5 that an air stream travels from the air outlet before the maximum
stream velocity is reduced to 0.5 m/s. The average stream velocity at this point is approx. ~ 0.3 m/s. The throw varies depending on the grille size, grille configuration, outlet velocity, blades position as well as the outlet arrangement within the room.
Room depth RT [m] = L0.35
To prevent draughts, the air velocity at the opposite wall should not exceed 0.35 m/s on the axis of the air stream. In the diagrams 1, 2, 3 and 4 for the dimensioning of the grille, the room depths are determined for an air throw of L0.35. The mean air
velocity at this point is 0.15...0.2 m/s.
Outlet velocity veff [m/s]
Our diagrams are based on the effective air velocity at the free area of the air outlet with blades in straight position. Refer also
pages 28 + 29: Determination of volume flow rate at TROX HESCO diffusion grilles.
v" = /(A r 3600) [m/s]. Whereas: = air flow rate [m/h], A = nominal area [m], = contraction factor = 0.974,
r = free area/nominal area = 0.77.
Standard single grilles
Standard single grilles are those outlets which we keep on stock and include grilles whose aspect ratio (grille length/height ) or
B/H is less than 16. Calculation according to diagram 1, pages 3, 4, 5 and diagram 2, pages 7, 8 and 9.
Continuous grilles
These are single grilles which are joint together to form continuous grille. Calculation according to diagram 3 and 4, pages 10
and 11, provided that the aspect ration B/H is greater than 16. For supply air grilles we recommend setting up alternating active and passive zones, e.g. 1 m active, 1 m passive, 1 m active and so on.
Positioning of the grilles
The supply air grilles must be positioned as to avoid that the primary air stream reaches the occupied zone and that light fittings, beams, columns, etc. obstruct or deflect the air stream.
Distance D [m]
In the calculation examples above, the minimum distances D necessary between grille and side wall and between grille and
ceiling are given.
Note
Due to design changes the aerodynamic data and noise information may be subject to change.
30
Technical Data
Legend
Symbol
Unit
Designation
Ao
Nominal surface of reference in the acoustics = 0.06 m (DG... 600 x 100 mm)
< - Grad
mm, m
< - Grad
dgl
div.
Dh
mm, m
Distance of horizontal discharge between the DGs and distance between grille and
side wall
Dv
mm, m
Distance of vertical discharge between the DGs and distance from the side wall
DG
EH
f1
f2
f3
mm, m
LwA
dB(A)
LwNC
Maintained noise rating curve of the sound power level spectrum, LwNC = LwA-4 dB
LwNR
Maintained noise rating curve of the sound power level spectrum, LwNR = LwA-2 dB
Lw2
dB
L0.5
Air throw for a final velocity of 0.5 m/s on the air stream axis
L0.35
Air throw for a final velocity of 0.35 m/s on the air stream axis (^=room depth RT)
OK FB
UK DG
ps
Pa
Pressure drop
pt
Pa
RH
RT
RT44...140
RTg
RB
RL
A
)
( AA ) = ( 0.06
o
31
Technical Data
Symbol
Unit
Designation
K, Kelvin
QL0.5
K, Kelvin
Temperature difference Theta at the end of the air stream (on the stream axis) for
L0.5
QS
C, Celsius
QR
C, Celsius
mm
veff
m/s
Air velocity at the DG, referred to the net cross-section area when the blades are in
the straight position.
veff 44...140
m/s
veff geg
m/s
vL
m/s
L0.5
m/h
m/h
ABL
m/h
ZUL
m/h
vgem
m/s
vk
m/s
vk1
m/s
Incident air stream velocity in the supply air duct (pressure duct)
vk2
m/s
Transfer air stream velocity in the supply air duct (flow duct)
vk3
m/s
vk4
m/s
y, y'
Air stream drop in the cooling case or air stream rise in the heating case
y20
32