L-02-5-01e

Diffusion grilles type DG...


Dimensioning
Blowing in horizontally from walls and circular ducts

TROX HESCO Schweiz AG


Walderstrasse 125
Postfach 455
CH - 8630 Rti ZH

Tel. +41 55 250 71 11


Fax +41 55 250 73 10
www.troxhesco.ch
info@troxhesco.ch

Contents
Diagram 1
Single standard supply air grilles with blades in straight
position and undisturbed supply air stream (free air stream): 3
Minimum distances, selection example
Diagram 1, grille height H = 50, 150, 250 mm
4
Diagram 1, grille height H = 100, 200, 300 mm
5
Blades positions
Definitions, spread of air stream, throw, correction factor for
diagrams 1 and 2, calculation example
6
Diagram 2
Single standard supply air grilles, blades in straight
position, installed at ceiling level (Coanda effect):
Minimum distances, selection example
Diagram 2, grille height H = 50, 150, 250 mm
Diagram 2, grille height H = 100, 200, 300 mm

7
8
9

Diagram 3
Continous supply air grilles, undisturbed supply air stream
(free air stream), calculation example
10
Diagram 4
Continous supply air grilles, undisturbed supply air stream
(Coanda effect), calculation example
11
12
Air stream drop at temperature variations

12

Diagram 10
Single grilles and unobstructed spread of air stream (free
air stream), calculation example

13

Determination of volume air flow rate at TROX HESCO


diffusion grilles (measurement on place)
28/29
Definitions
Legend

14

Diagram 12
Continous supply air grilles, undisturbed supply air
stream (free air stream), calculation example

15

Note:
In plants with large air change rates, it is not always possible to keep the occupied zone free of draughts. The good
controllability of the TROX HESCO diffusion grilles with the
individually adjustable air control blades makes it possible
to guide the primary air movement so that draughts can be
avoided at the main points where people are present.
The air control blades can be altered using a DG blade adjusting key.

DGSELF- blade adjusting key


Application examples for various DG-grilles 15/16/17

Determination of the minimal height of the mounting 18
Sound power level LwA and pressure drop Dps
of diffusion grilles (overall view) 19/20
Table: equivalent - dgl

20

Sound power level LwA and pressure drop Dps


of diffusion grilles DG1 (supply air)

21

Sound power level LwA and pressure drop Dps


of diffusion grilles DG5 (supply air)

22/23

Sound power level LwA and pressure drop Dps


of diffusion grilles DG6 (supply air)

24/25

Sound power level LwA and pressure drop Dps


of diffusion grilles DG8 (exhaust air)

26/27

31/32

Explanatory note
The following calculation principles are based on tests and
experience and are valid for the dimensioning of
TROX HESCO diffusion grilles. The diagrams and data on
the minimum distances are designed so that, when the dimensioning is correct, no draughts occur in the occupied
zone (as long as no air stream gradients due to temperature
differences are present).

DG blade adjusting key

Diagram 11
Single and continous supply air grilles installed at ceiling
level (Coanda effect), calculation example

30

Ge
B
(min. Dh/2)

~Dh

Rau

RB =

vL = 0.5 m/s

vL = 0.35 m/s

Technical Data

Seitenwand

~ 0.25 RT
~ 0.5 RT

Wurfweite(free
L0.5 = 0.75
RT
Diagram 1, undisturbed supply air stream
air stream)

Raumtiefe
RT grilles) of the types: DG..., DGR..., DGL..., DGX...,
This diagram is applicable for TROX HESCO standard supply air
grilles (single
Raumlnge
RL air stream spreading.
DGSELF and DGVAR (without DG13) with blades in straight positions and
unobstructed

20
1.8 m

Occupied zone

Side wall

Secondary air
Primary air

vK

Axial flow jet


vL = 0.5 m/s

vL = 0.35 m/s

vL = 0.5 m/s

vL = 0.35 m/s

B
~Dh

~ 0.25 RT
~ 0.5 RT

Opposite wall

~Dh
(min. Dh/2)
B

vL = 0.35 m/s

vL = 0.5 m/s

Dh

veff

Axial flow jet

(min. Dh/2)

RB = x B + (x + 1) Dh

Room width RB

Room heigth RH
RH ~ 1.8 + (0.28 RT) + H
min. height EH
EH ~ 1.8 + (0.176 RT)
>
~ 0.18 RT H Dh = 0.18 RT

Minimum distances for unobstructed air stream spreading

Side wall
Throw L0.5 = 0.75 RT
Room depth RT
Room length RL

For grilles with blades in straight position, the air stream leaving the outlet diverges in the horizontal or vertical plane by the
angle = 20, Distance Dh = 0.10 RT
Calculation example
Given
Room length RL = 8.5 m, room width RB = 5 m, room height RH = 4.5 m, mounting height EH = 3.0 m,
air flow rate = 1240 m/h, resp. 344.4 l/s
Wanted
Grille dimension B x H, room depth RT, outlet velocity veff, distance Dh, pressure drop ps,
sound power level LwA, LwNC, LwNR
Solution
The large room height allows to select the air outlet according to diagram 1, page 4 (unobstructed air stream spreading)
Result
2 off DG1, 600 150 mm, room depth RT = 8.4 m, outlet velocity veff = 2.6 m/s, Dh = RT 0.1 = 8.4 0.1 = 0.84 m,
pressure drop ps ~ 2.5 Pa, (diagram page 19,
sound power level LwA = 17 + 2 = 19 dB(A),
LwNC = 19 - 4 = 15, LwNR = 19 - 2 = 17.
More exact details for LwA and Dps see page 21.
min 0.84 m
0.6 m min 0.42 m
min 0.42 m 0.6 m

Technical Data
1)

611.1

2100

583.3

2000

555.6

1900

527.8

1800

500.0

1700

472.2

1600

444.4

1500

416.7

1400

388.9

1300

361.1

1200

333.3

1100

305.6

1000

277.8

900

250.0

x2
750

900
x

2200

15

638.9

0x

2300

18

de
pth

14

50

14

Roo

16

15

md

ept

Ro

hR

om

16

T [m
]

Recommended
working range

60

RT

[m
]

15

18

20

20

22

75

0x

15

22

90

666.6

2400

TROX HESCO diffusion grilles


of all DG types without DG 13.
Blade position straight,
unobstructed air stream
(free air stream)

25

2500

694.4

Diagram 1

0x

722.2

1)

60

2600

250

750.0

50

1)
2700

12

194.4

600

10
8
4

138.9

200
100
0

om

Ro

83.3

th
dep

RT

[m]

400

x 50
x 50

300 x

50

200 x 50

55.6
2

27.8
0

Outlet velocity veff [m/s]


1) Not available out of stock types DGR...+ DGRA....
Generally: Dimension and types out of stock see price-list.
> 1.5 m/s
Note: In a light cooling case (transition period) and 2-speed operation veff =
4

x5

300

111.1

400

Air flow rate [l/s]

Air flow rate [m/h]

500

500

x5

600

166.6

50

x1

Nominal size of grille B x H [mm]

700

0
75

222.2

0
30

800

15

10

12

40

Technical Data

500.0

1700

472.2

1600

444.4

1500

416.7

1400

388.9

1300

361.1

1200

333.3

1100

305.6

1000

277.8

900

250.0

1800

20

527.8

0x

1900

60

555.6

20
0

2000

0x

583.3

75

2100

20
0

611.1

26

2200

x3
00

638.9

90
0x

2300

TROX HESCO diffusion grilles


of all DG types without DG13.
Blade position straight,
unobstructed air stream
(free air stream)

[m

x
0
40

18

75

10

12

00

14

10

60

x1

12

00

10

50

0x

222.2

600

pt

194.4

700

40

800

om

de

RT

300

400

111.1

200
100

200
14

x 10

x 10

12

83.3

x 10

250

138.9
Air flow rate [l/s]

Air flow rate [m/h]

500

10

[m

Ro

166.6

300

x1

Nominal size of grille B x H [mm]

Roo

md

epth

16

RT [
m]

14

Ro

om

de

pth

20

RT

Recommended
working range

16

20

90

10

22

18

50

20

24

666.6

600

2400

24

694.4

x 30

2500

Diagram 1

900

722.2

22

2600

1)

20

750.0

1)

2700

10
8

55.6
6

27.8

4
2

Outlet velocity veff [m/s]


1) Not available out of stock types DG...5, ...35, ...5P, ...35P and ...7, ...17 and all DGR... + DGRA... types.
Generally: Dimension and types out of stock see price-list.
> 1.5 m/s
Note: In a light cooling case (transition period) and 2-speed operation veff =
5

gerade

position des lamelles divergentes 110


Strahlausbreitung

20

Technical Data

44

44

110

84

gegeneinander

140

position des lamelles divergentes 140 position oppose par paire des lamelles
60
80
90
180
20

Distanz Dh
0.10 RT
horizontal
ausblasend
22
22 42 55
55 42

gerade

gerade

RT84
0.29
RT4422 0.42
70 5542
42
5570 0.6 RT110
22

Distanz Dv
Blades
positions
=
1/7 = =
1) 1/7
vertikal
ausblasend
*)

0.10 RTg

R1/9
1/7 1/70.25 RT
1/9 1/9 1.25 R
1/9 1/9
1/9 1/9
T441/9 1/9
0.25 RTg
1) 0.76
3.26 RT140
1.07
RT84
T110
The divergence of the air stream and with its throw, can be controled by adjusting the vertical blades at the front of the grille.
prem.
et dern.
fente
couverte
The adjustment is made with a specially
'DG-key'
which
is being
supplied at no cost. The air stream drop can be
RT designed
Raumtiefe
affected
by adjusting the horizontal
RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT
RT grille.
RT44back
Diagr.blades
1 und at
2 the
= 0.77ofthe
fr die
SomeFaktoren
important
positions of the vvertical
blades
veff 44= 1.18
eff = 1,0
eff. Ausblasgeschw. veff

blades in straight position

veff 84= 1.35

blades position 44 diverging

veff 140= 1.97 veff geg = 1.97

veff110= 1.52

blades position 84 diverging

22
parallles1)
Angle d'talement
du jet

841/3

1/3

60

20

22

gerade

1/344

44

80

gerade

Distance Dv
0.25 RT
22
55 42
diffusion
verticale
*)22 42 55
= local
=
=
1/7 1/7 du
1)Profondeur

0.76
RT44
70
22
5542

gerade

blades
position
blades position 140 diverging
Distance
Dh 110 diverging
0.42 RT84
0.10 RT
0.29 RT44
diffusion horizontales
70
42
22
1.07
55
RT84

42

22

1/5

1/5

110
1)

gerade

position des lamelles divergentes

22 42

1/5

1/5

140

90

opposes

180

1/5

20

blades in opposed position

0.10 RTg
0.6 RT110
1.25 RT110

3.26 RT140

0.25 RTg

RT
1/9 1/9 1/9 1/9 1/9 1/9 1/9 1/9 1/9
Diagr. 1 et 2 1) RT44 = 0.77 RT RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT

1/7 1/7

Facteur de eff. vitesse


dinsufflation
1) approx.
detailsveff

veff = 1,0

first and last slot covered


veff 44= 1.18
veff 84= 1.35 veff 110= 1.52

veff 140= 1.97 veff geg = 1.97

Correction coefficients to diagram 1 and 2


Blades positions: diverging
straight

44

84

110

140

opposed

20

60

80

90

180

20

Distance Dh
horizontal blowing out

0.10 RT

0.29 RT44

0.42 RT84

0.6 RT110

0.10 RTg

Distanz Dv
vertical blowing out *)

0.25 RT

0.76 RT44

1.07 RT84

1.25 RT110

Divergence of air jet

Room depth
Faktor of the
outlet velocity veff

3.26 RT140

0.25 RTg

RT
Diagr. 1 and 2 RT44 = 0.77 RT RT84 = 0.56 RT RT110 = 0.42 RT RT140 = 0.35 RT RTg = 1.30 RT
veff = 1,0

veff 44= 1.18

veff 84= 1.35 veff 110= 1.52

veff 140= 1.97 veff geg = 1.97

*) Detailed informations look diagram L 2.5-2e


Calculation example
Given
Room length RL = 7.0 m, Room height RH = 5.5 m, height EH = 4.0 m,
air flow rate = 1080 m/h, resp. 300 l/s, unobstructed air stream spreading, blades position 84 diverging
Wanted
Grille dimension B x H, room depth RT und RT84, outlet velocity veff, pressure drop ps, sound power level LwA, LwNC, LwNR
Solution
RT84 = 0.56 RT therefore RT = RT84/0.56 = 7/0.56 ~13 m. With this value you can select the required grille on
diagram 1, page 5: 1 off DG1, 600 x 200 mm, veff = 3.3 m/s. Of diagram page 19 follows: ps = 4 Pa,
has to be corrected to 84 diverging.
Therefore ps84 = 3.3 1.50 = 4.95 m/s 8 Pa, sound power level LwA = 34 + 3 = 37 dB(A), LwNC = 37 - 4 = 33,
LwNR = 37 - 2 = 35. More exact details for LwA and Dps see page 21.
6

Gege

vL = 0.35 m/s

Technical Data

(min. Dh/2)

~Dh

Rau

RB = x

vL = 0.5 m/s

~ 0.18 RT H + 0.025

/2 ~ 10

vL = 0.5 m/s

vL = 0.35 m/s

vL = 0.5 m/s

vL = 0.35 m/s

vL = 0.5 m/s

vL = 0.35 m/s

Occupied zone

(min. Dh/2)

1.8 m

Secondary air

vK

Axial flow jet

(min. Dh/2)

Opposite wall

veff

Side wall

Dh

Primary air

B
~Dh

RB = x B + (x + 1) Dh

Room width RB

~Dh

RH ~ 1.8 + (0.176 RT) + H + 0.025

Room height RH

Seitenwand
~ 0.25 RT
Diagram 2, grilles installed~ 0.5
at R
ceiling
level (Coanda effect)
T
This diagram is applicable for TROX HESCO standard
supply
grilles
Wurfweite
L0.5 =air
0.75
RT (single grilles) of the types: DG..., DGR..., DGL...,
DGX..., DGSELF and DGVAR (without DG13) with blades inRaumtiefe
straight position,
grilles installed at ceiling level.
RT
Raumlnge RL
Minimum distances

~ 0.25 RT
~ 0.5 RT

Side wall
Throw L0.5 = 0.75 RT
Room depth RT
Room length RL

For grilles with blades in straight position, the air stream leaving the outlet diverges in the horizontal or vertical plane by the
angle /2 = 10, distance Dh = 0.10 RT
Calculation example
Given
Room length RL = 12 m, room width RB = 4.0 m, room height RH = 4.0 m,
air flow rate = 1060 m/h resp. 294.4 l/s,
Wanted
Grille dimension B x H, room depth RT, outlet velocity veff,
distance Dh, pressure drop ps, sound power level LwA,
LwNC, LwNR

min 0.58 m 0.6 m

min 1.15 m

0.6 m min 0.58 m

Solution
Air outlet just under the ceiling, in diagram 2, page 9, has the result by per grille = 530 m/h.
Result
2 off DG6 600 100 mm, damper position 50%, veff = 3.3 m/s, room depth RT = 11.5 m, distance Dh = RT 0.1 =
11.5 0.1 = min. 1.15 m. According diagram page19, follows: ps50 ~ 15 Pa, sound power level LwA = 37 dB(A), LwNC
= 37 - 4 = 33, LwNR = 37 - 2 = 35. More exact details for LwA and Dps see page 25.
7

Technical Data

1900

527.8

1800

500.0

1700

472.2

1600

444.4

1500

416.7

1400

388.9

555.6

15

2000

0x

583.3

75

2100

611.1

15

2200

0x

638.9

250

2300

600
x

666.6

TROX HESCO diffusion grilles


of all DG types without DG13.
Blade position straight,
installed at ceiling level
(Coanda effect)

15
x

277.8

900

250.0

15
x
0
50

20

166.6

12

12

600

600

10

194.4

700

300
200
100

111.1

om

Ro

T
th R
dep 10

[m]

400

83.3

55.6

x5

x 50
x 50

300 x

50

200 x 50

4
2

27.8
0

Outlet velocity veff [m/s]


1) Not available out of stock types DGR...+ DGRA....
Generally: Dimension and types out of stock see price-list.
Note: In a light cooling case (transition period) and 2-speed operation veff >
= 1.5 m/s
8

500

12

8
4

400

138.9
Air flow rate [l/s]

Air flow rate [m/h]

500

50

10

222.2

0x

75

800

15

x
00

Nominal size of grille B x H [mm]

1000

18

305.6

16

1100

14

333.3

26
24
22

20
18

1200

15

16

361.1

00

14

1300

60

m
Ro
o

T [m
]

24

22

Roo

md

ept

hR

Recommended
working range

26

de
p
2 th

RT

30

2400

250

694.4

Diagram 2

1)

[m
]

2500

750
x

722.2

2600

x 25

750.0

900

2700

1)

90

1)

Technical Data

1000

277.8

0
10
0

26

75

24

22

12

RT

[m

de

10

300

250

138.9
111.1

300

83.3

200

400

100

55.6
27.8

10

14

12

200

Air flow rate [l/s]

Air flow rate [m/h]

500

10

o
Ro

166.6

600

x
0

]
[m
RT
pth
de
om
Ro

14

h
pt

194.4

700

x1

x
00

10

222.2

800

00

0
50

250.0

900

40

22
20
18

20

305.6

18

1100

16

333.3

16

1200

60

14

361.1

10

12

1300

16

00

x1

x 10

x 10

22

Nominal size of grille B x H [mm]

388.9

20
0

1400

20
0

416.7

20
0

1500

60
0x

444.4

0x

1600

50

472.2

x1
00

1700

Recommended
working range

90
0

500.0

1800

20

527.8

0x

1900

75

555.6

300

2000

900
x

583.3

600
x

2100

30

611.1

28

2200

300

638.9

900
x

2300

30

666.6

28

2400

TROX HESCO diffusion grilles


of all DG types without DG13.
Blade position straight,
installed at ceiling level
(Coanda effect)

T [m]

694.4

26

2500

Diagram 2

pth R

722.2

m de

2600

Roo

750.0

24

2700

200

1)

1)

18

Outlet velocity veff [m/s]


1) Not available out of stock types DG...5, ...35, ...5P, ...35P and ...7, ...17 and all DGR... + DGRA... types.
Generally: Dimension and types out of stock see price-list.
> 1.5 m/s
Note: In a light cooling case (transition period) and 2-speed operation veff =
9

277.8

D
>
D = 0.1

1000

16

250.0
14

700

Luftvolumenstrom fr 1 m Gitterlnge [l/s, m]

paroi m]
Luftvolumenstrom fr 1 m Gitterlnge [m/h,
wall

grille 222.2
800

vue12
sur la grille

1m

194.4

10

166.6

600

[
Diagram 3, unobstructed air stream spreading, continuousRgrilles
(free air stream)
T

fe types: DG1, 3, 5P, 6 and 8, with blades


This diagram is applicable for TROX HESCO continuous supply air grilles (B/H >tie16),
138.9
500
m
8
in straight position and unobstructed air stream spreading. Minimum distance
u D = 0.10 RT (grille to ceiling).
Ra
111.1
400ceiling
6
> 0.18 R
D=
T

200

83.3
D

300

recommandation for the montage see page 16, p.1.3


4

Empfohlener
Arbeitsbereich

55.6

supply air 100


27.8
grille
duct
0

2
1m

388.9

1300

361.1

1200

333.3

1100

305.6

1000

277.8

900

250.0

800

222.2

700

194.4

1400

20

10

22
N

om

.s

ize

20
of

gr

ille

18
[m

50

16
14

Air flow rate per 1 m grille length [l/s, m]

Air flow rate per 1 m grille length [m/h, m]

600
500
400
300
200
100
0

12

166.6

10

138.9

de

pt

om

111.1

RT

[m

Ro

83.3
4

Recommended
working range

55.6
27.8
0

Outlet velocity veff [m/s]


Note: In a light cooling case (transition period) and 2-speed operation veff >
= 1.5 m/s
Calculation examples
Total air flow rate = 1650 m/h, resp. 458.3 l/s, room length RL = 6.0 m, room width RB = 5.0 m, grille length B ~RB,
therefore air flow rate = 330 m/h,m, resp. 91.7 l/s and grille dimension DG1, 5000 50 mm, room depth RT = 5.5 m, veff
= 2.4 m/s, pressure drop Dps, sound power level LwA and LwNC, LwNR according to diagram page 19, drop of the air stream
according to diagram page 15. More exact details for LwA and Dps see page 21.
10

800
700
600
500
400
300
200
100

15

25

30

416.7

Ausblasgeschwindigkeit veff [m/s]

1500

Front6view on grille
7

Dbit d'air par mtre courant de grille [m/h, m]

Technical Data

900

900

gaine dair

1000

22

222.2
plafond
700
194.4

Recommandations au sujet de montage voir page 16, p. 1.3

Luftvolumenstrom fr 1 m Gitterlnge [l/s, m]

18

16

600grille 166.6

500

Technical Data

]
[m
T
R
vue
fe sur la grille
tie

14
1m

138.9

Luftvolumenstrom fr 1 m Gitterlnge [m/h, m]


paroi
wall

20

800

gaine dair

um

12 B
Diagram 4, unobstructed air stream spreading, continuous
Ra grilles (Coanda effect)

This diagram400
is applicable
grilles (B/H > 16), types: DG1, 3, 5P, 6 and 8, with blades in
111.1forTrox Hesco continuous supply air10
straight position, grilles installed at ceiling level.
300

6
recommandation
for the montage
see page 16, p.1.3
Empfohlener

ceiling
55.6

Arbeitsbereich
H

200
supply air
100
duct

83.3

27.8
grille
0

Front view on grille

1m
2

388.9

1300

361.1

1200

333.3

1100

305.6

15
0

1400

20

416.7

30

1500

0
25
0

Ausblasgeschwindigkeit veff [m/s]

10

1000

277.8

900

250.0

800

222.2

700

194.4
Air flow rate per 1 m grille length [l/s, m]

Air flow rate per 1 m grille length [m/h, m]

om

.s

ize

500

300
200
100
0

ille

[m

26
m
]

50

22
20
18
16
14

138.9

400

gr

24

166.6

600

of

12

T
hR

[m

pt

om

de

Ro

10

111.1
8

83.3
6

Recommended
working range

55.6
27.8
0

Outlet velocity veff [m/s]

Note: In a light cooling case (transition period) and 2-speed operation veff >
= 1.5 m/s
Calculation example:
Total air flow rate = 1800 m/h, resp. 500 l/s, room length RL = 11.0 m, room width RB = 5.0 m, grille length B ~RB,
therefore air flow rate per m grille length = 360 m/h,m, resp. 100.0 l/s, therefore grille dimension DG1, 5000 50 mm,
room depth RT = 9.0 m, veff = 2.7 m/s, pressure drop Dps, sound power level LwA and LwNC, LwNR according to diagram
page 19, drop of the air stream according to diagram page 14. More exact details for LwA and Dps see page 21.
11

Dbit d'air par mtre courant de grille [m/h, m]

250.0

900

Raumtiefe RT

ef
fe
tC
av
ec

d'
air

Technical Data

10

jet

L0.5 = Dbit dair lextr

Dbit dair pul

12

6
4

Turbulent air motion


at the
Wurfweite
L0.5end of air stream (L0.5)

= S R
L0.5 0.176

16
14

Co
an
d

12

ith

10

tw

Je

L0.5 = Air flow rate at the end of the jet

Air flow rate supply air

18

ef
fe
ct

Diagram 9

(RT 0.176) + y
~1.8
Fre
e je
EH ~ (RT t 0.176) + 1.8 m + y

0
7
4
5
6
2
3
1
Calculation example
Vitesse dinsufflation veff [m/s]
1 off DG1 600 100 mm, blades in straight position,free stream, air flow rate: = 500 m/h, resp. 139 l/s, outlet velocity
veff = 3.1 m/s. It follows of diagram 9: L0.5 / = 8.5 [L0.5 = 8.5 = 4250 m/h, resp. 1180 l/s]
TS

Profondeur du local R6T


Porte du jet d'air L0.5
4

= S R
L0.5 0.176

Air stream drop at temperature differences

EH ~ (RT 0.176) + 1.8 m + y

4
5
6
2
3
Outlet velocity veff [m/s]
y

(RT 0.176) + y

TS

~1.8

If the temperature in the air stream is warmer or cooler, the air stream will rise or drop accordingly. This drop or rise of the air
stream can bewidely controlled by adjusting the horizontal blades of the diffusion grille. Divergently set diffusion grilles reduce
the air stream deviation y.
Diagram 9 shows that the mixing of primary air with secondary air is very intensive. This results in a temperature adjustment between non-isothermal air stream and room temperature. So is i.e. the difference of temperature in the axial air
stream after reaching the throw of air QL0.5 = 0.35 Q/v".

Room depth RT

12

EH ~ (RT 0.176) + 1.8 m + y

L0.5 0.176

= S R

~1.8

TS

(RT 0.176) + y

Throw L0.5

Notation
QS = Air stream temperature at the
grille (supply air)
QR = Room temperature
Q = Difference of temperatur
(temperature supply air to
room temperature)
y
= air stream drop in cooling case
(air stream rise in heating case)
RT = Room depth acc. diagram
(pages 4+5, 8+9, 10+11)
L0.5 = Throw

ligne de rfrence
Einzelgitter

diffrence de temprature la grille [K]


3 4 5 6 8 10 12
2

Technical Data

( monte du jet d'air en cas de chauffage )


( chute du jet d'air en cas de rafrachissement)

chute du jet10
son extrmit
Diagram

pour une temprature ambiante de 20C = y20 [m]

(relating to diagram 1)0.4


0.8 1.0 1.2 1.4 1.6 2.0
0.2
0.6
Single air grille with unobstructed air stream spreading. (free air stream)

4.0

3.0

5.0 6.0 7.0 8.0

Grille individuelle
Drop of the axial flow stream at the terminal point at Q, straight blades, single grille, unobstructed air stream spreading.

Outlet velocity veff [m/s]

0.5

0.4

2
900 x 150
600
500
400
300

750 x 200
600
500
400

900 x 250
750
600

900 x 300
600

Single grille

1.5

0.3

900 x 100
600
500
400
300
250
200 x 100
600 x 50
500
400
300
200 x 50

0.5

0.1

0.2

8
Nominal dim.
of the grille
B x H [mm]

0.08

Circular equivalent of rectangular duct dgl [m]

Auxiliary line

Temperature difference at the grille [K]


3 4 5 6 8 10 12
2
Air jet drop at the throw terminal point and
at a room temperatur 20C = y20 [m]
0.8 1.0
0.2
0.4
0.6

1.2 1.4 1.8

(air stream rise in heating case)


(air stream drop in cooling case)

2.0

3.0

4.0

5.0

6.0 7.0 8.0

Correction factors for different positions of blades


y at:
y at:
y at:
y at:
y at:

straight position of blades:


position of blades
44 div.:
position of blades
84 div.:
position of blades 110 div.:
opposed position of blades:

Factor 1
Factor 0.4...0.5
Factor 0.2...0.3
Factor 0.1...0.2
Factor 0.5...1.0

Recommendation
a) In the heating and/or cooling cases veff >
= 1.5 m/s (always use divergent control blade arrangement)
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m

Calculation example
Air flow rate = 330 m/h, resp. 91.7 l/s, DG1, 600 100 mm, room depth RT = 4.8 m, diagram 1, page 5, veff = 2 m/s.
Q at the grille is 4 K(-), therefore air stream drop Y20 = 1.15 m.
Problems are mainly encountered where cooled air is to be supplied through grilles. To avoid undue drop of the cold
air stream in the occupied zone, following rules can help:
Select grilles with outlet velocity as high as possible. Select several small grilles iinstead of one or two large ones.
Install grilles as high as possible above floor at alternative levels. Incline the horizontal blades at the back of the grille
in order to compensate for any air stream drop or direct the cold air along ceiling level (refer also to following explanations 'Grilles installed at ceiling level'). Adjust the vertical blades at the grille front in opposed positions, to increase air
entrainment and hence to achieve better mixing of the cold air stream with secondary air (drop at the air stream terminal point y ~ 0,85 Y20 ).

13

Hilfslinie

Technical Data
Einzelgitter und
DG-Bnder

Diagram 11

Abfallen des Kaltluftstromes

Kein Abfallen des Kaltluftstromes

(relating to diagrams 2 + 4)
Single and continuous grilles, installed at ceiling level. (Coanda effect)

Cold air stream grilles installed close or at ceiling level have a tendency to adhere to the ceiling and do not drop under
certain conditions, which depend onTemperaturdifferenz
temperature difference,
size
and
velocity. It is important to ensure that the
amgrille
Gitter

[K]outlet
(Khlfall)
Grilles is
individuelles
ceiling
absolutelyetflat, already small obstructions like light fittings, beams etc. can deflect the air stream and cause draft
sous forme
de occupied
bande14 zone.
effects
in the
6
5
3
4
7
10 9 8
2
12

600 x 300
900 x 300

300
200
150
250
Nom. height of the grille H [mm]

100
50
Continuous grilles B/H > 16
0.5

400 x 200
500
600
750

200 x 50
300
400
500
600
200 x 100
250
300
400
500
600
900
300 x 150
400
500
600
900

Single and continous grilles

600 x 250
750
900

Nom. dim. of the grille B x H [mm]

Single grille

Outlet velocity veff [m/s]


1.5
2

Auxiliary line

The cold air stream will drop

No drop of the cold air stream

Temperature difference at the grille [K] (cooling case)


14

12

10 9

Recommendation
> 1.5 m/s (always use divergent control blade arrangement)
a) In the heating and/or cooling cases veff =
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m

Calculation example
Air flow rate = 410 m/h, resp. 113.9 l/s, room depth RT = 9.0 m, diagram 2, page 9, DG1,
600 100 mm, veff = 2.5 m/s,
Q at the grille is 5 K (), from diagram 11 we can see: No cold air stream drop will occur.

14

ligne de prfrence

Technical Data

DG - Bnder
diffrence de temprature la grille [K]
1

5 6 7 8 9 101214

Diagram 12
(relating to diagram 3)
Continuous grilles with blades in straight position, unobstructed air stream spreading (free air stream), drop of the
0.8
5.0 6.0 7.0 8.0 10.0
1.0 1.2 1.4 1.6 1.8 2.0
4.0
axial air streams. Valig for grille dimension about3.0
5000 mm.
Y20 values forchute
otherdu
grille
on request.
jet dimensions
dair son extrmit
pour une
Grilles sous forme de bande
( monte du jet d'air en cas de chauffage )
temprature de 20C = y20 [m]

Outlet velocity veff [m/s]


2
3
1.5

Nominal height of the grille H [mm]

Continuous grilles

100

200 150

50

Auxiliary line

Temperature difference at the grille [K]


1

0.8

1.0

1.2 1.4 1.6 1.8 2.0

3.0

4.0

5 6 7 8 9 101214

5.0

6.0 7.0 8.0

Air jet drop at the throw terminal point


and at a room temperature of 20C = y20 [m]

10.0

(air stream rise in heating case)

Recommendation
> 1.5 m/s (always use divergent control blade arrangement)
a) In the heating and/or cooling cases veff =
b) Use DGVAR or DGSELF when room height RH >
= 4.0 m

15

Technical Data
Application examples for various DG-grilles

(see also table page 20)

1. Supply air
1.1 Air flow direction in duct = outlet direction by the grille, e.g. branch ducts.
For single grille at the duct terminal point, select: DG1 or DG6

dgl 12
vk1

Continuous grille or several single grilles installed in one duct


(e.g. in the false ceiling, at the balcony sill).
That means: dgl = same diameter value = 2 B H
(B + H)

[m]

vk1

veff

vk1

vk1

veff

vk1

veff

veff

Where small air velocities vk1 and small pressure differences in the duct prevail DG1. Minor air flow adjustments are
possible by turning horizontal blades (< 20 Pa).
Where pressure and velocity fluctuations are to be expected, select grilles with volume control devices: DG6.
1.2 Air flow direction in the duct is perpendicular to the air discharge direction at the grille
If a grille or several diffusion grilles are built into an air duct in this way, then on the one hand the air must be discharged
evenly over the entire grille area and, on the other hand, the same volumetric air flow be discharged from all grilles. It is
possible to satisfy these conditions in all cases when the various diffusion grille types are correctly employed.

vk2

We differentiate between
a) Pressure duct

veff

veff

veff

Ducts with large cross sectional area. Air velocity in duct is smaller than the outlet velocity at the grille
vk2 < v", therefore: DG6
Ideal air distribution at the grille:
vk2 < 0.5 veff
Efficient air distribution at the grille: vk2 < 0.8 veff
b) Flow duct
(see also description of prospectus DG5)
Ducts with large cross sectional area. Air velocity in duct is larger than the outlet velocity at the grille
vk2 > v", therefore: DG5, DG7 oder DG17
DG5
Suitable for airconditioning systems, offers wide volume control.
Ideal air distribution at the grille:
vk2 < 2.5 veff
Efficient air distribution at the grille:
vk2 < 5.2 veff
DG7 and DG17
Suitable for warm air heating systems and industrial applications.
Ideal air distribution at the grille:
vk2 < 1.8 veff
Efficient air distribution at the grille:
vk2 < 3.5 veff

vk2
veff

veff

veff

Note: See page 21 for information on vK2

1.3 In supply air grilles, we recommend setting up active and passive zones, e.g. 1 m active, 1 m passive 1 m active and so
on. This reduces the room depth (air throw) by as much as 66% (depending on the nominal height H).
1.4 Diffusion grille DGVAR or DGSELF with temperature-dependent air stream deflection.
We recommend the use of the DGVAR or DGSELF type when the room height RH >
= 4.0 m.
2.

Exhaust air

2.1 Single grilles: DG3 or DG1, eventually DG13. Several grilles for one duct, with small pressure differentials only: DG1
(Minor air flow adjustments are possible by changing the position of the horizontal blades at the grille front). Several
grilles for one duct: DG8 or DG7.

16

50 mm

DG
DGR
DGRA

Technical Data

1400
560
280
*100
450
1800
140
180
355
710
1120
224
900
*250
*315
*800 *1000 *1250
*160
*400
*125
*200
*500
1600
*630
2000
=
* =

rayon extrme
diamtre de gaine selon EN 1506 et EN 12220
(avant: DIN 24 154 feuille 2 srie prfrentielle)
3. Duct - respectez
- range la
forprofondeur
the DGR...
types pour DGR5 / 7 / 17
de -montage

The following table shows for which duct diameter range the appropriate nominal grille height H may be used.

250

1) DG
DGR
DGRA

200

DG
DGR
DGRA

150

DGR
DGRA

100

DG
DGR
DGRA
DG

50

Nominal dimension H

DG

DGR
DGRA
1400
560
*100
280
450
1800
140
180
355
710
1120
224
900
*250
*315
*800 *1000 *1250
*160
*400
*125
*200
*500
1600
*630
2000

=
* =

extreme range
duct diameter as per EN 1506 and EN 12220
(former: DIN 24 154 sheet 2 preference series)
check depth of opening for DGR5 / 7 / 17

B = Nennbreite
200
300
400
500
600
750
1) Nominal height of the grille H = 250 mm is for the types DGR and DGRA not available on stock.
DGR5 und DGRA5
90
100
110
115
125
145
T DGR7 / 17 und DGRA7 / 17
max.155 (100% offen)

DGR5 et DGRA5
DGR7 / 17 et DGRA7 / 17

90

[mm]

170

[mm]
[mm]

300

400

600

750

900 2)

[mm]

100

110
115
125
max.155 (100% ouvert)

145

170

[mm]

500

Depth of montage T for DGR 5 / 7 / 17 and DGRA...


B = largeur nom.
200

900 2)

[mm]

B
B = nominal width

DGR5 and DGRA5


DGR7 / 17 and DGRA7 / 17

200

300

400

600

750

900 2)

[mm]

90

100

110
115
125
max.155 (100% open)

145

170

[mm]

500

[mm]

2) Nominal width of the grille B = 900 mm is for th types DGR and DGRA not available on stock.

17

0
0

Beispiel von S. 7

Technical Data

Beispiel von S. 3

Beispiel von S. 6

min. Einbauhhe

1.00

10

11

13

12

14

15

16

RT [m] height of the mounting EH OK FB until UK DG


DeterminationRaumtiefe
of the minimal
Basis

- Isothermal case
- Free air stream (undisturbed spreading out of the air flow)
- Discharge immediately below and along the ceiling

5.00

d'talement
isothermheight
/2 (env.
Formula for the angle
calculation
of the mounting
EH < 10)
4.50

for isothermal blowing in

min. hauteur de montage EH [m] OK FB...UK grille)

Lgende
RT case
= profondeur du local [m] = L0.35
for a cooling
EH
= min. hauteur de la montage [m]
EH(-)
= 1.8 + (RT 0.1763)
y [m]grille)
(OK +
FB...UK
tan (10)
= 0.1763

4.00EH(isoth) = 1.8 + (RT 0.1763)

[m]

3.50

Formulas for the calculation of the room depth RT for various blade positions (divergences)
3.00

RTstraight blades in straight position


= (EH - 1.8) = (EH - 1.8)
0.1763
tan (10)

[m]

2.00
1.80
RT44 blades position 44 diverging

1.00

(EH - 1.8)
0.7 0.1763

[m]

Exemple page 6

RT44 =

RT110 blades position 110 diverging

RT84 blades position 84 diverging


0

RT84 =
0

(EH - 1.8)
0.5 0.1763
1

[m]
3

RT110 =

(EH - 1.8)
0.4 0.1763

Exemple page 7

Tstraight

Exemple page 3

2.50 R

[m]

RTopp blades in opposed position

(EH - 1.8)
1.2 0.1763

RTopp =
8

10

11

12

[m]
13

14

15

16

profondeur du local RT [m]

5.00

Angle of air jet by isotherm /2 (ca < 10)

Legend
RT
EH

4.50

tan (10)

3.50
3.00
2.50

0
0

Room depth RT [m]

18

example page 3

1.00

example page 7

2.00
1.80

example page 6

min. mounting height EH [m] OK FB...UK grille)

4.00

= Room depth [m] = L0.35


= min. mounting height [m]
(OK FB...UK grille)
= 0.1763

10

11

12

13

14

15

16

Technical Data
Sound power level LwA and pressure drop ps for diffusion grilles (overall view)

LwA valid for nom. dimension B x H = 600 x 100 mm, nom. surface of ref. A0 = 0.06, sound power level of ref. W0 = 10-12 W

Supply air
veff [m/s] 2

2.5

3.5

4.5

5.5

6.5

7
vk1

DG1

DG5

DG6

other position of blades:


84 div.: veff 1.50
110 div.: veff 1.75
opp.
: veff 2.25
140 div.: veff 2.25

1.5
ps [Pa]
LwA [dB(A)] 12

2.4

2.8

10

13

15

18

16

20

24

28

31

34

36

38

41

44

14
ps [Pa]
LwA [dB(A)] 36

21

27

35

43

55

64

73

82

93

110

40

43

46

50

52

54

55.5

57

58.5

60

other position of blades:

20
ps [Pa]
LwA [dB(A)] 48

28

35

43

51

64

74

85

97

110

125

50

52

54

56

58

59

60

61

62

63

110 div.: veff 1.1


opp.
: veff 1.2
140 div.: veff 1.35

30
ps [Pa]
LwA [dB(A)] 56

38

48

56

64

75

86

98

108

116

132

57

58

59

60

61

62

63

64

65

66

1.5
ps [Pa]
LwA [dB(A)] 12

2.5

3.5

12

14

17

21

24

16

21

25

29

33

36

39

41

43

45

5
ps [Pa]
LwA [dB(A)] 21

13

17

21

24

30

37

43

51

60

29

35

38

41

43

45

48

51

53

55

other position of blades:


84 div.: veff 1.25
110 div.: veff 1.4
opp.
: veff 1.8
140 div.: veff 1.8

DG17
other position of blades:
110 div.: veff 1.1
opp.
: veff 1.2
140 div.: veff 1.35

vk2 = 3 m/s

vk2 = 6 m/s

vk2 = 9 m/s

vk1
100 %

vk1
50 %

18
ps [Pa]
LwA [dB(A)] 46

23

29

36

42

52

60

67

75

82

90

48

50

52

54

55.5

57

58

59

60

61

26
ps [Pa]
LwA [dB(A)] 55

31

39

45

52

61

70

78

85

94

104

56

57

58

59

60

61

62

63

64

65

9.3
ps [Pa]
LwA [dB(A)] 28

14

20

28

35

45

55

67

78

90

105

32

36

41

43

47

51

53

54

56

58

-13

-16

-20

-24

-28

-32

vk2 = 6 m/s

vk2 = 9 m/s

vk1
DG13

Exhaust air
vk3
DG8

ps [Pa]
LwA [dB(A)]

-2.5

-4.4

-6

-8

-10.5

13

17

21

25

29

32

35

37.5

40

42.5

45

ps [Pa]
LwA [dB(A)]

-18

-23

-27

-32

-37

-42

-47

-52

-57

-62

-68

39

40.5

42

44

46

47.5

49

50.5

52

53

54

ps [Pa]
LwA [dB(A)]

-28

-33

-38

-43

-48

-53

-58

-63

-68

-78

-88

52

53

54

55

56

57

58

59

60

61

62

ps [Pa]
LwA [dB(A)]

-10.5

-16

-23

-32

-40

-52

-63

-76

-91

-105

-120

35

38

42

47

49

52

56

58

60

61.5

63

veff [m/s]

2.5

3.5

4.5

5.5

6.5

100 %

DG13

2. Correction dimension of grille


it is: LwA = LwA + Lw2 [dB]
given: Lw2 = 10 log A = 10 log A
Ao
0.06

+9
+6
+3
0
-3
-6
-9

Lw2 [dB]

DG7

0.25

0.5

f1 = A
Ao

vk4 = 6 m/s

vk4 = 9 m/s

vk3

LwNC, LwNR:
LwNC = LwA - 4
LwNR = LwA - 2

19

Technical Data
Example (to page 19)
Given

Outlet velocity veff


Grille type
Grille size B H
Position of blades
Air velocity in the duct vk2

Wanted

a) pressure drop ps (static pressure drop in the duct in front of the diffuser)
b) sound power level LwA of one diffuser, LwNC, LwNR

Solution

Page 19
Handling: veff corr. = 2.9 1.2 = 3.48 m/s (count with f4, because the blades ar in opposed position).
By DG5, veff corr. = 3.48 m/s and vk2 = 6.0 m/s can be determined ps and LwA.

Conclusion

= 2.9 m/s
= DG5
= 600 50 mm
= opposed position
= 6.0 m/s

a) pressure drop ps = 43 Pa (static pressure drop in the duct in front of the diffuser)
b) sound power level LwA = 54 dB(A). This value corresponds to a grille B x H = 600 x 100 mm. Of the table
'correction of the grille dimension' we see:
f1 = A = 0.03 = 0.5
Ao 0.06
The result is a correction of -3 dB.
Sound power level LwA = 54 - 3 = 51 dB(A) / diffuser, LwNC = 51 - 4 = 47 dB(A), LwNR = 51 - 2 = 49 dB(A)

Table same diameter value -

H [mm]

20

dgl = 2 x B x H [m]
(B + H)

B [mm]
200

250

300

400

500

50

0.080

0.083

0.086

0.089

0.091

100

0.133

0.143

0.150

0.160

150

0.171

0.188

0.200

200

0.200

0.222

250

0.222

300

0.240

600

750

900

0.092

0.094

0.095

[m]

0.167

0.171

0.176

0.180

[m]

0.218

0.231

0.240

0.250

0.257

[m]

0.240

0.267

0.286

0.300

0.316

0.327

[m]

0.250

0.273

0.303

0.333

0.353

0.375

0.391

[m]

0.273

0.300

0.343

0.375

0.400

0.429

0.450

[m]

Technical Data
Sound power level DG1 supply air (without quantity adjustments)
1. Sound power level LwA and pressure drop pt; ps, DG1, B H = 600 100 mm,
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
50 60 70 [Pa]
60
Sound power level LwA [dB(A)]

pt 2
60

50
40
30

20
15

10

40

30

20

50 60 70 [Pa]
60

50

50

40

40

30

30

A)
B(

> dgl 12
DG1, 600 x 100 mm
Ao = 0.06 m

20
v"

ps

pt

15

20
15

60

60

50

50

50

40

40

40

Sound power level Lw [dB]

60

pt 2

d
Bla

2
1.5

14

rg.

ive

Hz
00
80

50 60 70 [Pa]
8
.
g
7
r
ive
d
6
0
1

40

s.
rg. 1

ive

.
erg

d
4

es

d
0

12

po

iv

44

Outlet velocity veff [m/s]

ig
tra
ss

15

30

20

ht

Hz

10

00

Hz

0
50

12

50 60 70 [Pa]
8
7
rg.
e
iv
d
6

Hz

15

00

z
125H

40

12

20

20

20

15

30

Hz

20

250H

30

00

30

10

100 mm
.06 m

d
Bla

d
ose

s.

po

op

2
1.5

1.5

50 60 70 [Pa]

ps

10

15

20

25 30

40

50 60 70 [Pa]

Pressure drop ps [Pa]

3. Correction factor
for DG3
ps DG3 = 0.8 x ps DG1

2. Correction dimension of grille


it is: LwA = LwA + Lw2 [dB]

given: Lw2 = 10 log ( A ) = 10 log ( A )


Ao
0.06
4. LwNC - u. LwNR - values
LwNC = LwA - 4
LwNR = LwA - 2

Lw2 [dB]

+9
+6
+3
0
-3
-6
-9

0.25

0.5

f1 = A
Ao

Example: DG1, B x H = 300 x 100 mm; veff = 3 m/s


Diagram ps = 2.8 Pa; LwA0.06 = 20 dB(A)
Lw0.06;125Hz = 23 dB; Lw0.06;250Hz = 26 dB a.s.o.
Correction: A = 0.03 = 0.5 LwA = - 3 dB
Ao 0.06
LwA0.03 = 20 - 3 = 17 dB(A)
Lw0.03;125Hz = 20 dB; Lw0.03;250Hz = 23 dB a.s.o.
LwNC0.03 = 17 - 4 = 13
LwNR0.03 = 17 - 2 = 15

21

Technical Data
Sound power level DG5 supply air
1. Sound power level LwA and pressure drop pt; ps, DG5, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W

pt 7 8 9 10
70
60

20

15

25 30

50 60

40

80 100

50

150

40

70
60

vk1

40

)
B(A

30

[Pa]

Direct stream
(

50

DG5
600 x 100 mm
Ao = 0.06 m

veff
ps

30

20

pt
> dgl 12

20

60

60

In the stream duct

50

50

40

40

8 9 10

15

30

vk2

20

ps

20

80

40

00

00

Hz

Hz
00

00

20

Hz

Hz
250
z
0H
50

20

30

Hz
125

10

Sound power level Lw [dB]

Sound power level LwA [dB(A)]

Tolerances: total level 2 dB, octave level 4 dB

30

50

40

60 70 80

100

170 pt [Pa]

130

90 110

150

pt
In the stream duct

13

Air velocity vk2 in the duct [m/s]

10

8 9 10

15

20

30

60 70 80

50

40

15

12

12

8 9 10

15

20

30

60 70 80

50

40

5
4

Outlet velocity veff [m/s]

100 130
170 ps [Pa]
150
90 110

15

6
2

ty

ti
an

Qu

100 130
170 pt [Pa]
150
90 110

Direct stream

0%

10

%
50

t
en

tm

jus

ad
tity

an

Qu

In the stream duct

en

tm

s
dju

4
3

0
110
geg.
140

1.5
7
0
0
11eg.
g 0
14

22

8
6
4
0

11 13 15 17

21 25 29

Pressure drop ps [Pa]

33

37 45 53

61

88 108
69
148
ps [Pa]
98
168
77
128

Direct stream

veff

Technical Data
2. Correction 'dimension of the grille'

+9
+6
+3
0
-3
-6
-9

Lw2 [dB]

it is: LwA = LwA + Lw2 [dB]


given: Lw2 = 10 log A = 10 log A
0.06
Ao
3. LwNC - u. LwNR - value
LwNC = LwA - 4
LwNR = LwA - 2

0.25

0.5

f1 = A
Ao

3. Conversion factors f for vk1 of veff (Direct stream)


H + 10+2 , B + 15+5
0
0

Duct dimensions:

by DGVAR + DGSELF: H + 10+2 , B + 25+2


0
0
BxH

300 x 50

200 x 50

0.585

BxH

200 x 100

250 x 100

0.638

0.647

400 x 50

500 x 50

600 x 50

750 x 50

0.599

0.606

0.610

0.613

0.616

300 x 100

400 x 100

500 x 100

600 x 100

750 x 100

[mm]
[-]

0.653

0.661

0.666

0.669

0.672

900 x 100 [mm]


[-]
0.674

BxH

300 x 150

400 x 150

500 x 150

600 x 150

750 x 150

900 x 150 [mm]

0.673

[-]
0.695
900 x 200 [mm]
[-]
0.706

0.681

0.686

0.690

0.693

BxH

400 x 200

500 x 200

600 x 200

750 x 200

0.692

0.697

0.701

0.704

BxH

600 x 250

750 x 250

0.707

0.711

900 x 250 [mm]


[-]
0.713

5. Examples
5.1 Direct stream (
Given

veff = 3.2 m/s


DG5, 600 x 50 mm, 100% open, 0 diverging
vk1

Wanted
a) LwA in dB(A), LwNC, LwNR
b) ps + pt in Pa
c) vk1 in m/s
Solution
a) LwA = 37 - 3 = 34 dB(A), LwNC = 34 - 4 = 30, LwNR = 34 - 2 = 32
b) ps = 19 Pa, pt = 22 Pa
c) vK1 = 3.2 0.613 = 2.0 m/s

veff
ps
pt
> dgl 12

5.2 In the stream duct (


)
Given
veff = 2.9 m/s, vK2 = 6.0 m/s

DG5, 300 x 100 mm, 100%, opposed position

vk2

Wanted
a) LwA in dB(A), LwNC, LwNR
b) ps + pt in Pa
Solution
a) LwA = 54 - 3 = 51 dB(A), LwNC = 51 - 4 = 47, LwNR = 51 - 2 = 49
b) ps = 43 Pa, pt = 64 Pa

ps
pt

veff

23

Technical Data
Sound power level DG6 supply air - damper 100% open
1. Sound power level LwA and pressure drop pt; ps, DG6, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
Dpt 2
70
60

20
15

20
v"

[Pa]
7
6

50

50

40

40

30

30

20

20

15

z
0H

1.5
[Pa]

Outlet velocity veff [m/s]

80 100

z
5H

12

15

z
0H

50

10

20

Dps

[Pa]
7
6
5
4
3

8 10

15

20 25 30

40 50 60

80 100

[Pa]

Pressure drop Dps [Pa]

Lw2 [dB]

24

80 100

1.5

Example: DG6, B H = 300 100 mm; veff = 3 m/s


3. Correction factor
Diagram LwA0.06 = 21 dB(A)
for DG8
ps DG8 = 0.8 ps DG6 Lw0.06;125Hz = 22 dB; Lw0.06;250Hz = 27 dB a.s.o.

4. LwNC - u. LwNR - values


LwNC = LwA - 4
LwNR = LwA - 2
0.5

rg.

e
div

1.5

given: Lw2 = 10 log ( A ) = 10 log ( A )


0.06
Ao

0.25

40 50 60

s.
.

po
erg 110
div
.

s
rg 84
s
de
ive
os.
d
Bla
dp
44
e
s
po
op
es
d
a
l
+B
rg.
e
v
di
0
14
ht

2. Correction dimension of grille


it is: LwA = LwA + Lw2 [dB]

+9
+6
+3
0
-3
-6
-9

30

ig
tra

15
70
60

20

70
60

Dpt 2
3
5 6
4
7
Damper 100% open
6

DG6, 600 x 100 mm


Ao = 0.06 m

Dps

Dpt

15

25

80 100

> dgl ? 12

0Hz

30

30

dB

800

40

(A)

30

Sound power level Lw [dB]

50

40

0H

70
60

[Pa]
70
60

40

400

15

80 100

50

Hz

20

40 50 60

50

00

100 mm
0.06 m

30

20

20

30

10

Hz

40

5 6

00

Sound power level LwA [dB(A)]

50

10

[Pa]
70
60

80 100

f1 = A
Ao

Correction: A = 0.03 = 0.5 LwA = - 3 dB


Ao 0.06
LwA0.03 = 21 - 3 = 18 dB(A)
Lw0.03;125Hz = 19 dB; Lw0.03;250Hz = 24 dB a.s.o.
LwNC0.03 = 18 - 4 = 14
LwNR0.03 = 18 - 2 = 16

Technical Data
Sound power level DG6 supply air - damper 75% + 50% open
1. Sound power level LwA and pressure drop pt; ps, DG6, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB

g.

0 100

0 100

20

4
3
2
1.5
[Pa]

[Pa]
7
6
5
4
3
2

1.5
0 100 [Pa]

DG6, 600 x 100 mm


Ao = 0.06 m

20
15

70
60
50

70
60
50

40

40

30

30

20

20

pt 2
8 10
3
4 5 6
7
6
Damper 75% open
5
4
3
2
1.5
ps

2 3

5 6

8 10

0Hz

30 40 50 60 80 100

20

.
s.
erg
po
rg.
ht
div
g
i

ive
a
4
d
r
t
4
0
ss
11
de
rg.
Bla
s.
e
iv
po
d
sed
84
o
pp
so
de
a
l
B
.+
erg
v
i
d
0
14

20 25 30 40 50 60 80 100

15

30 40 50 60 80 100

20

de

3
2

40

2 3

5 6

8 10

15

20

erg

div

ht

aig

tr
ss

Bla

1.5
ps

15

800

z Hz
z
0H 25H 00
5
5
1
2

0H

15

15

pt 2
8 10
3
4 5 6
7
6 Damper 50% open
5

4 10
44 8 1

v"

ps

pt

15
[Pa]
7
6
5

30

> dgl 12

400

20

30

Hz

30

40

A)
B(

00

40

40

30 40 50 60 80 100 [Pa]
70
60
50

20

20

Sound power level Lw [dB]

70
60
50

8 10

5 6

Hz

15

00

20

10

30

Outlet velocity veff [m/sec]

0 100

40

Outlet velocity veff [m/s]

0 mm
6 m

Sound power level LwA [dB(A)]

0 100 [Pa]
70
60
50

pt 2
70
60
50

+B

es
lad

os.

op

d
ose

s.

po

[Pa]
7
6
5
4
3
2
1.5
[Pa]

4 10
44 8 1

[Pa]
7
6
5
4
3
2

1.5
30 40 50 60 80 100 [Pa]

Pressure drop ps [Pa]

25

Sound power level DG8 exhaust air - damper 100% open


1. Sound power level LwA and pressure drop pt; ps, DG8, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
[Pa]
40

40

Sound power level LwA [dB(A)]

9.4 [Pa]

30

ps

20

40

40

30

30

Hz

125

20

Hz

25

pt (-)

Outlet velocity veff [m/s]

1.4

Hz

50

2.6

20

3.9

7.3

9.4 [Pa]
5

Damper 100% open

20 [Pa]

ps (-)

4
3
Pressure drop ps [Pa]

3. LwNC - u. LwNR - value


LwNC = LwA - 4
LwNR = LwA - 2

2. Correction dimension of grille


it is: LwA = LwA + Lw2 [dB]

given: Lw2 = 10 log ( A ) = 10 log ( A )


0.06
Ao

10

15

20 [Pa]

Example: DG8, B H = 300 100 mm; veff = 3 m/s


Diagram LwA0.06 = 21 dB(A)
Lw0.06;125Hz = 26 dB; Lw0.06;250Hz = 26 dB a.s.o.
Correction: A = 0.03 = 0.5 LwA = - 3 dB
Ao 0.06
LwA0.03 = 21 - 3 = 18 dB(A)

Lw2 [dB]

26

Exhaust air
DG8, 600 x 100 mm
Ao = 0.06 m

pt

A)
B(

20

+9
+6
+3
0
-3
-6
-9

40

Damper 100% open

[Pa]

> dgl 12

20

Hz

20

15

10

30

40

30

00

20

10

30

ps (-)

Sound power level Lw [dB]

20

Technical Data

0.25

0.5

f1 = A
Ao

Lw0.03;125Hz = 23 dB; Lw0.03;250Hz = 23 dB a.s.o.


LwNC0.03 = 18 - 4 = 14
LwNR0.03 = 18 - 2 = 16

Technical Data
Sound power level DG8 exhaust air - damper 50% open
1. Sound power level LwA and pressure drop pt; ps, DG8, B H = 600 100 mm
nom. surface of reference Ao = 0.06 m, sound power level of reference Wo = 10-12 W
Tolerances: total level 2 dB, octave level 4 dB
ps (-)

[Pa]
Sound power level LwA [dB(A)]

60
50
40
30
> dgl 12

pt
ps

Extraction
DG8, 600 x 100 mm
Ao = 0.06 m

20

40
30

26

35

44 53

50 60

[Pa]

50

50

40

40
30
> dgl 12

pt
ps

20

Exhaust air
DG8, 600 x 100 mm
Ao = 0.06 m

20

50

50

40

40
z
0H
z
5H
12
z
0H
50

30

30

25

20

pt (-)

09

0H

0
10

20

13

18

26

35

44 53

[Pa]

2
40

50 60

60

dB

[Pa]

[Pa]

Damper 50% open

ps (-)

10

15

20

30

40

50 60

[Pa]

Pressure drop ps [Pa]

2. Correction dimension of grille


it is: LwA = LwA + Lw2 [dB]

3. LwNC - u. LwNR - value


LwNC = LwA - 4
LwNR = LwA - 2

given: Lw2 = 10 log ( A ) = 10 log ( A )


Ao
0.06
+9
+6
+3
0
-3
-6
-9

Example: DG8, B H = 300 100 mm; veff = 3 m/s


Diagram LwA0.06 = 35 dB(A)
Lw0.06;125Hz = 39 dB; Lw0.06;250Hz = 39 dB a.s.o.
Correction: A = 0.03 = 0.5 LwA = - 3 dB
Ao 0.06
LwA0.03 = 35 - 3 = 32 dB(A)

Lw2 [dB]

30

40

Damper 50% open

(A)

Outlet velocity veff [m/s]

Hz

20

30

30

Sound power level Lw [dB]

50

60

20

10

Hz

50 60

00

40

20

30

0.25

0.5

f1 = A
Ao

Lw0.03;125Hz = 36 dB; Lw0.03;250Hz = 36 dB a.s.o.


LwNC0.03 = 32 - 4 = 28
LwNR0.03 = 32 - 2 = 30

27

Technical Data
Determination of volume air flow rate at TROX HESCO diffusion grilles
Supply air
Tests have shown that the most reliable measurements are obtained using a rotating vane anemometer. Care should be taken
that the anemometer head lies on the grille blades. The figure shows the exact position of the head containing the vanes:
* B/2; but between two blades !

rotating vane placed direct on the blades !

*B/2

1
Einstellung der
vorderen Lamellen

Korrekturfaktor f2 bei Einstellungswinkel


der hinteren Lamellen
1 = 0
1.13

1 = 22
1.07

1 = 42
0.98

1 = 55
0.80

44

1.03

0.93

0.88

0.80

84

0.89

0.88

0.84

0.73

110

0.74

0.77

0.76

0.70

140

0.56

0.62

0.59

0.60

gegeneinander

0.57

0.55

0.54

0.50

0 gerade

Observe the following


- With the blades set in the straight (neutral) position, make several measurements over the nominal width B of the grille
and then take the average of these readings.
- For a divergent setting of the front blades,
it is de
also
an advantage
toun
make
several measurements.
This is absolutely ne-
positionnement
dangle
Facteur
correction
f2 pour
de type.
cessary Positionnement
with the DG5 grille
des lamelles postrieures
lamelles frontales
1made
= 0 in the central
1 = 22
1 =the
42blades still have
1 = 55
The measurements must, however, only be
area, i.e. where
a straight setting.
effective discharge
velocity veff and0.98
the discharge velocity,
The measured
value vgem lies between the1.13
1.07
0.80 referred to the grille
0 gerade
nominal area.
1.03
0.93
0.88
0.80
44
To get the effective discharge velocity veff, the measured value vgem has to be multiplied by a correction factor f2.
0.89
0.88
0.84
0.73
84
110
140
oppos

0.74

0.77

veff0.56= vgem f0.62


2
0.57

[m/s]

0.55

0.76

0.70

0.59

0.60

0.54

0.50

The size of the correction factor f2 is dependent on the setting of the air control blades.
This applies to all DG types (DG1, DG3, DG5, DG6, DG7, DG8, DG17, DGL, DGX and DGR).
Setting of the
blades in front

Correction factor f2 for setting angle of the blades behind


1 = 0
1.13

1 = 22
1.07

1 = 42
0.98

1 = 55
0.80

44

1.03

0.93

0.88

0.80

84

0.89

0.88

0.84

0.73

110

0.74

0.77

0.76

0.70

140

0.56

0.62

0.59

0.60

opposed

0.57

0.55

0.54

0.50

0 straight

The supply air volume flow ZL of an air diffuser is calculated according to the formula below.
ZL = veff A 3600 r
= vgem f2 A 3600 r
= vgem f2 A 2'700
28

[m/h]

r = Area ratio A net = 0.77


= Contraction coefficient A nom= 0.974

Technical Data
Example
Given
DG1, 600 100 mm, Blades in straight position.
vgem (taken of measuring) = 2.8 m/s
Wanted

a) Outlet velocity veff


b) Air flow rate ZL of the diffuser

Solution a) Outlet velocity veff


veff = vgem f2 = 2.8 1.13 = 3.164 m/s
Luftvolumenstrom
Luftgeschwindigkeit vk2
b) Air flow
rate ZL of the diffuser
[m/h]
max. [m/s]

Luftvolumenstrom
[m/h]

Luftgeschwindigkeit vk2
max. [m/s]

Calculated
bis 1000 ZL = veff A 3600
3 r
bis 4000
= vgem f2 A 3600 r
= 2.8 1.13 0.6 0.1 3600 0.77 0.974
bis 1500
bis 5500
= 515 m/h, 3.5
diffuser
bis 2000

bis 7000

5
5.2
5.5

Exhaust air
Tests have shown
the most reliable measurements
are obtained using
rotating vane anemometer. Care
bisthat
2500
4.2
bis a10000
6 should be taken
that the anemometer head lies on the grille blades (as shown in the figure).
3000 air velocity v, the measured
4.5
10000 by a correction factor
7 f .
be multiplied
To calculate thebis
exhaust
value vgem has to ber
3
The correction factor f3 is 1.053. This is valid for all DG types (DG... and DGR...1 to 8, DG17, DGL..., and DGX...) with straight
blade positions.
The exhaust air volume flow AL of an air diffuser is calculated according to the formula below.
Dbit d'air
Dbit d'air
Vitesse d'air vk2
[m/h]
[m/h]
max. [m/s]
1000

3
AL = veff A 3600 r
= vgem f3 A 3600 r
A 2'700
= vgem 1.053
3.5
1500
2000

4000

Vitesse d'air vk2


max. [m/s]
5

[m/h]
5500

5.2

7000

5.5

4.2
2500
10000systems (pipes and ducts)
6
Maximum air
velocity in ventilation
and air conditioning
3000
plus 10000 services
Explanatory note:
Recommendations from4.5
diverse energy-saving consultancy

Air flow rate


[m/h]

Air velocity vk2


max. [m/s]

Air flow rate


[m/h]

Air velocity vk2


max. [m/s]

until 1000

until 4000

until 1500

3.5

until 5500

5.2

until 2000

until 7000

5.5

until 2500

4.2

until 10000

until 3000

4.5

more than10000

29

Technical Data
Definitions
Throw L0.5 [m]
The throw is the horizontal or vertical axial distance vL0.5 that an air stream travels from the air outlet before the maximum
stream velocity is reduced to 0.5 m/s. The average stream velocity at this point is approx. ~ 0.3 m/s. The throw varies depending on the grille size, grille configuration, outlet velocity, blades position as well as the outlet arrangement within the room.
Room depth RT [m] = L0.35
To prevent draughts, the air velocity at the opposite wall should not exceed 0.35 m/s on the axis of the air stream. In the diagrams 1, 2, 3 and 4 for the dimensioning of the grille, the room depths are determined for an air throw of L0.35. The mean air
velocity at this point is 0.15...0.2 m/s.
Outlet velocity veff [m/s]
Our diagrams are based on the effective air velocity at the free area of the air outlet with blades in straight position. Refer also
pages 28 + 29: Determination of volume flow rate at TROX HESCO diffusion grilles.
v" = /(A r 3600) [m/s]. Whereas: = air flow rate [m/h], A = nominal area [m], = contraction factor = 0.974,
r = free area/nominal area = 0.77.
Standard single grilles
Standard single grilles are those outlets which we keep on stock and include grilles whose aspect ratio (grille length/height ) or
B/H is less than 16. Calculation according to diagram 1, pages 3, 4, 5 and diagram 2, pages 7, 8 and 9.
Continuous grilles
These are single grilles which are joint together to form continuous grille. Calculation according to diagram 3 and 4, pages 10
and 11, provided that the aspect ration B/H is greater than 16. For supply air grilles we recommend setting up alternating active and passive zones, e.g. 1 m active, 1 m passive, 1 m active and so on.
Positioning of the grilles
The supply air grilles must be positioned as to avoid that the primary air stream reaches the occupied zone and that light fittings, beams, columns, etc. obstruct or deflect the air stream.
Distance D [m]
In the calculation examples above, the minimum distances D necessary between grille and side wall and between grille and
ceiling are given.

Note
Due to design changes the aerodynamic data and noise information may be subject to change.

30

Technical Data
Legend
Symbol

Unit

Designation

Nominal surface (nominal cross-section of a grille)

Ao

Nominal surface of reference in the acoustics = 0.06 m (DG... 600 x 100 mm)

< - Grad

Air stream divergence angle (with reference to H)

mm, m

Nominal width of grille

< - Grad

Air stream divergence angle (with reference to B)

dgl

div.

same diameter value = 2 B H


(B + H)
Divergent blade position of the front, vertical blades

Dh

mm, m

Distance of horizontal discharge between the DGs and distance between grille and
side wall

Dv

mm, m

Distance of vertical discharge between the DGs and distance from the side wall

DG

Diffusion grilles, type of grille

EH

Min. installation height (fitting height)


OK FB...UK DG = top edge of the floor to bottom edge of the diffusion grille

Conversion factor for vk1 of veff

f1

Correction factor for other grille dimensions

f2

Correction factor supply air

f3

Correction factor exhaust air

mm, m

Nominal height of grille

LwA

dB(A)

Sound power level, according to filter "A"

LwNC

Maintained noise rating curve of the sound power level spectrum, LwNC = LwA-4 dB

LwNR

Maintained noise rating curve of the sound power level spectrum, LwNR = LwA-2 dB

Lw2

dB

Acoustic power level difference referred to other grille sizes

L0.5

Air throw for a final velocity of 0.5 m/s on the air stream axis

L0.35

Air throw for a final velocity of 0.35 m/s on the air stream axis (^=room depth RT)

OK FB

Top edge of the floor

UK DG

Bottom edge of the diffusion grille

ps

Pa

Pressure drop

pt

Pa

Total pressure drop

RH

Room height according to the plan of the building

RT

Room depth (by free stream or Coanda effect) = L0.35

RT44...140

Room depth , diverging positions of blades 44, 84, 110 u. 140

RTg

Room depth, opposed position of blades

RB

Room width according to the plan of the building

Surface proportion (free surface/nominal surface = 0.77)

RL

Room length according to the plan of the building

A
)
( AA ) = ( 0.06
o

31

Technical Data

Symbol

Unit

Designation

Contraction number = 0.974

K, Kelvin

Temperature difference Theta (room temperature - supply air temperature)

QL0.5

K, Kelvin

Temperature difference Theta at the end of the air stream (on the stream axis) for
L0.5

QS

C, Celsius

Air stream temperature Theta in the grille (supply air temperature)

QR

C, Celsius

Room air temperature Theta

mm

Depth of mounting for DGR5, DGR7 and DGR17

veff

m/s

Air velocity at the DG, referred to the net cross-section area when the blades are in
the straight position.

veff 44...140

m/s

Air velocity, diverging positions of blades 44, 84, 110 u. 140

veff geg

m/s

Air velocity by opposed position of blades

vL

m/s

Air velocity on the stream axis

L0.5

m/h

Air volume rate at the air throw distance L0.5

m/h

Air volume rate

ABL

m/h

Air volume rate exhaust air

ZUL

m/h

Air volume rate supply air

vgem

m/s

Measured air velocity at DG

vk

m/s

Velocity in the stream core

vk1

m/s

Incident air stream velocity in the supply air duct (pressure duct)

vk2

m/s

Transfer air stream velocity in the supply air duct (flow duct)

vk3

m/s

Air velocity in the exhaust air duct

vk4

m/s

Transfer air velocity in the exhaust air duct

Number of diffusion grilles

y, y'

Air stream drop in the cooling case or air stream rise in the heating case

y20

Air stream drop at a room temperature of 20 C

32

We reserve the right to make design and shade of colour changes (05/2015)