Você está na página 1de 3

3877-3

MECHANICAL & ELECTRICAL SERVICES


1
_______________________________________________________________________
_
Services
1.

Description

Size (mm) (Minimum)

TNB Room
Consumer HT Room
Transformer Room

6000 (W) x 5000 (D) x 4000 (H)


6000 (W) x 5000 (D) x 4000 (H)
10000 (W) x 4500 (D) x 4000
(H)
8500 (W) x 9000 (D) x 4000 (H)

LV Switch Room
2.

Generator Set
Room

4.

Security
System

Electrical Riser

2500 (W) x 1000 (D)

MDF Room
Telephone Riser

6000 (W) x 8500 (D) x 3000 (H)


1000 (W) x 750 (D)

Located at Basement Car Park


Located at every floor

1500 kVA

6500 (W) x 9000 (D) x 5000 (H)

Located beside TNB room

ELV Riser

800 (W) x 750 (D)

Data Riser

1000 (W) x 750 (D)

For CCTV, SMATV, PA & Card


Access System
For structure cabling system

Fire Protection
Fire Pump Room (for
sprinkler & hose reel
pumps)
Fire Control Room

Hose
Tank

Reel/Wet

15000 (W) x 10000 (D)


3500 (W) x 3500 (D)
RC Tank 1: 55m2 x 3500 (H)
RC Tank 2: 47m2 X 3500 (H)

Sprinkler Tank

Riser

Fire Riser
6.

Located beside TNB Room


Located adjacent to Genset
Room
Located adjacent to TNB Sub
Station
Located at every floor

Telephone

3.

5.

Remarks

Electrical

RC Tank: 31m2 X 3500 (H)

1300 (W) x 650 (D)

To be located at Carpark Level 1


between Sprinkler Tank and
Hose/Wet Riser Tank
To be located near entry to
building at Ground Floor. Can be
combined with Security Room
To be located flush with Fire
Pump Room at Carpark Level 1.
Tank to be compartmented inot 2
half
To be located flush with Fire
Pump Roomks at Carpark Level
1
Within
every
staircase/fire lobby

escape

Domestic Cold
& Hot Water
DCW Suction Tank

RC Tank : 167m2 X 3500 (H)

DCW Transfer Pump


Room
DCW Roof Storage Tank
Podium West Block

4000 x 4000 x 3500(H)

DCW Roof Storage Tank


Podium Centre Block

8000 x 6000 x 2500(H)

DCW Roof Storage Tank


Podium East Block

7000 x 6000 x 2500(H)

7000 x 6000 x 2500(H)

Rc tank located Carpark Level 1


Tank to be compartmented into 2
half.
Attached to rc suction tank
between the tank compartment
FRP Sectional Tank located on
RC Flat Roof c/w 600 high rc
plinth
FRP Sectional Tank located on
RC Flat Roof c/w 600 high rc
plinth
FRP Sectional Tank located on
RC Flat Roof c/w 600 high rc
plinth

3877-3
MECHANICAL & ELECTRICAL SERVICES
2
_______________________________________________________________________
_
Services
Description
Size (mm) (Minimum)
Remarks

7.

DCW Roof Storage Tank


- Tower

14000 x 6000 x 2500(H)

Cold Water Riser (All


Podium Block & Tower)

600 (W) x 600 (D)

DCW Hydro Pneumatic


Pump Room (All block
and Tower)

2500 x 2500 x 3000(H)

Located at roof level near to


DCW Tank All Blocks &
Tower

Sanitary
Plumbing
Last manhole

8.

FRP Sectional Tank located on


RC Flat Roof c/w 600 high rc
plinth
Located within the public toilets

Sanitary Plumbing Riser


(All Podium Block &
Tower)

600 (W) x 600 (D)

Toilet Exhaust Fan Room

2500 x 2500 x 3000 (H)

Located at building perimeter,


actual location to be determine
Located within the public toilets

Air
Conditioning

AHU Room (Tower)

5000 x 6500

AHU
Room
Podium Block)

5000 x 6500

(Each

Hex & Chilled Water


Pump Room
Toilet Exhaust Shaft
(AllPodium Block)
Toilet Exhaust Shaft
(Tower)
Smoke Spill Make Up
shaft (All Podium Block
& Tower)
Smoke Spill Shaft (All
Podium Bloc & Tower)
Carpark Fresh Air Shaft

16000 x 13000 x 4000 (H)

Located on RC Flat Roof above


toilet (if enclosure is require,
otherwise fan is exposed)
2 nos. per floor for on floor units
around Lift core Area. Size
include
Fresh
air
Duct
within(OR 2 nos.. 25m x 25m
central AHU Room on Roof )
2 nos. per floor for on floor units
around Lift Core Area. Size
include Fresh air Duct within
(OR 2 nos. 20m x 15m central
AHU Room on Roof)
Located at Capark Level 2

600 (W) x 900 (D)

Located within or next to toilet

1200 (W) x 900 (D)

Located within or next to toilet

1500 (W) x 1500 (D)

Around Lift Core area

1500 (W) x 1500 (D)

Around Lift Core area

3 nos. 4000 (W) x 3000 (D)

Carpark
Shaft

Exhaust

Air

3 nos. 4000 (W) x 3000 (D)

Carpark

Exhaust

Fan

4500 (W) x 4500 (D) x 3000 (H)

Carpark Levels. Locate so that


the shaft discharge to Ground
floor open area and opposite side
of Fresh Air Shaft for cross
ventilation
Carpark Levels. Locate so that
the shaft discharge to Ground
floor open area and opposite side
of Fresh Air Shaft for cross
ventilation
Locate next to Exhaust Air Shaft

3877-3
MECHANICAL & ELECTRICAL SERVICES
3
_______________________________________________________________________
_
Services
Description
Size (mm) (Minimum)
Remarks
Room
Carpark Supply Air Fan
Room
Pressurization Shaft (All
Podium Block & Tower)

9.

4500 (W) x 4500 (D) x 3000 (H)

Locate next to Exhaust Air Shaft

600 (W ) x 1500 (H)

Attached to All internal Escape


Staircases, perimeter Staircase
without window and Bomba Lift
Lobby
Locate at RC Flat Room

Pressurization Fan Room


(All Podium Block &
Tower)

3500 (W) x 300 (D) x 3000 (H)

BAS Riser (All Podium


Block & Tower)

600 (W) x 600 (D)

BAS
Around Lift Core area

10. LPG
LPG Farm
LPG Riser

7500 (W) x 1000 (D) x 3000 (H)


600 (W) x 600 (D)

Note: All dimensions are shown for room clearance only.

Outside Building Perimeter


Well Ventilated