EtherNet/IP
Technical Manual
Type: SI-EN3D
To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
Table of Contents
1
2
3
4
5
6
7
8
9
10
11
12
13
14
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
u Applicable Documentation
The following manuals are available for the SI-EN3D option:
Yaskawa AC Drive 1000-Series Option SI-EN3D Dual-Port EtherNet/IP Installation Manual (TOEPYAICOM16)
The Installation Manual contains information required to install the option and set up related drive parameters.
Yaskawa AC Drive 1000-Series Option SI-EN3D Dual-Port EtherNet/IP Technical Manual (SIEPYAICOM16)
The Technical Manual contains detailed information about the option. In the U.S., access http://www.yaskawa.com
to obtain the Technical Manual. Customers in other areas should contact a Yaskawa representative.
1000-Series AC Drive Safety Precautions
Read this manual first. This manual contains essential safety information and simplified information for the drive.
This document also provides basic instructions on mechanical installation, a connection diagram, main circuit and
control circuit connections, switch and jumper configuration, basic troubleshooting, standards compliance and
fusing, drive specifications, and an abbreviated parameter list.
1000-Series AC Drive Quick Start Guide
This guide contains basic information required to install and wire the drive. It also gives an overview of fault
diagnostics, maintenance, and parameter settings. The purpose of this guide is to prepare the drive for a trial run
with an application and for basic operation. This manual is available for download on our documentation website,
www.yaskawa.com.
1000-Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/Modbus
specifications. Use this manual to expand drive functionality and to take advantage of higher performance features.
This manual is available for download on our documentation website, www.yaskawa.com.
u Terms
Note: Indicates supplemental information that is not related to safety messages.
Drive: Yaskawa 1000-Series AC Drive
Option: Yaskawa AC Drive 1000-Series SI-EN3D Dual-Port EtherNet/IP Option
u Registered Trademarks
EtherNet/IP is a trademark of the ODVA.
All trademarks are the property of their respective owners.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
4
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
n General Safety
General Precautions
The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before
operating the drive and run the drive according to the instructions described in this manual.
Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to
which this manual is applicable.
The products and specifications described in this manual or the content and presentation of the manual may be changed without notice
to improve the product and/or the manual.
When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales
office and provide the manual number shown on the front cover.
If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
NOTICE
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
2 Product Overview
Product Overview
u Applicable Models
The option can be used with the drive models in Table 1.
Table 1 Applicable Models
Drive Series
A1000
CIMR-Ao4A0002o to 4A0675o
CIMR-Ao4A0930 and 4A1200
CIMR-Ao5Aoooo
<1> See PRG on the drive nameplate for the software version number.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
3 Receiving
Receiving
Option
Ground Wire
Screws (M3)
LED Label
NS
Quantity
MS
Installation Manual
MANUAL
Tools required to prepare the option cables for wiring are not listed in this manual.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
4 Option Components
Option Components
K
L
B
A
Underside
123
456
78
Latch release
Pin
Description
1 (Pair 2)
2 (Pair 2)
3 (Pair 3)
4 (Pair 1)
5 (Pair 1)
6 (Pair 3)
7 (Pair 4)
8 (Pair 4)
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
4 Option Components
Name
Color
MS
NS
10/100 <1>
LINK/ACT <1>
Operating Status
Status
Remarks
OFF
Green
ON
Normal operation
Green
Flashing
Standby/Initializing
Red
Flashing
Red
Green/Red
ON
Flashing
OFF
Green
ON
Green
Red
Red
Green/Red
Green
Green
Green
Green
Flashing
Flashing
ON
Flashing
OFF
ON
OFF
ON
Green
Flashing
<1> Remove the cover to check the status of the LED. Be careful not to touch the main circuit terminals or the control board in the drive.
n Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After the
LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume operational
conditions as shown in Table 3.
Table 4 Power-Up Diagnostic LED Sequence
10
Sequence
1
Time (ms)
250
Red
OFF
250
3
4
5
6
Green
Green
Green
Green
OFF
Green
Red
OFF
250
250
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
5 Installation Procedure
Installation Procedure
u Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label. After
all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The
internal capacitor remains charged after the power supply is turned off.
WARNING
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety shields to show details. Be sure to
reinstall covers or shields before operating any devices. The option should be used according to the instructions described
in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation,
adjustment, and maintenance of this product.
Do not touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Do not use damaged wires, place excessive stress on wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never shut the power off while the drive is outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
11
5 Installation Procedure
NOTICE
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option and connecting any other devices.
Failure to comply could result in damage to the option.
L
B
NS
G
MS
E
D
12
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
5 Installation Procedure
1.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the digital operator
(B) and front covers (A, D). Front cover removal varies by model.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
2.
With the front covers and digital operator removed, apply the LED label (C) in the appropriate position on the drive
top front cover (A).
NS
MS
3.
Make sure the screws on the left and right sides of the option terminal block (J) are tightened with a tightening torque
of 0.5 to 0.6 Nm (4.4 to 5.3 in lbs), then insert the option (B) into the CN5-A connector (L) located on the drive and
fasten it using one of the included screws (H).
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
13
5 Installation Procedure
F
NS
TX
MS
RX
4.
Connect the ground wire (I) to the ground terminal (K) using one of the remaining provided screws (H). Connect the
other end of the ground wire (I) to the remaining ground terminal and installation hole on the option (B) using the last
remaining provided screw (H) and tighten both screws to 0.5 to 0.6 Nm (4.4 to 5.3 in lbs).
H
NS
TX
MS
RX
5.
There are two screw holes on the drive for use as ground terminals. When connecting three options, two ground wires will need
to share the same drive ground terminal.
Note:
14
Separate communication cables from main circuit wiring and other electrical lines.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
5 Installation Procedure
6.
Connect the Ethernet communication cable to the option modular connector (CN1) port 1.
To connect the option to a network, firmly connect RJ45 8-pin shielded twisted pair Cat5e cable(s) into the modular
connector ports (see Figure 7).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only
receive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP). Using a cable not specifically
recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on
network cabling (http://www.odva.org).
The dual RJ45 network ports on the option board act as a switch to allow for flexibility in cabling topology. For example,
a traditional star network topology may be employed by using a single port on the option board. Alternatively, a daisychained approach may be employed by using both RJ45 ports. The daisy-chained approach reduces the requirements
of central switch ports. A ring topology is also possible.
Star Topology
Yaskawa
Drive
Yaskawa
Drive
Daisy-Chained Topology
Yaskawa
Drive
Yaskawa
Drive
Yaskawa
Drive
Yaskawa
Drive
Ring Topology
Yaskawa
Drive
Yaskawa
Drive
Yaskawa
Drive
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
15
5 Installation Procedure
R/L1
S/L2
T/L3
Power
U/T1
V/T2
W/T3
M Motor
Drive
<1>
SI-EN3D
EtherNet/IP
Option
FE
EtherNet/IP Cable
EtherNet/IP Cable
7.
8.
Use the second communication cable port to daisy chain a series of drives where applicable.
Replace and secure the front covers of the drive (A, D) and replace the digital operator (B).
NS
TX
MS
RX
9.
Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables
are pinched between the front covers and the drive when replacing the covers.
u EDS Files
For easy network implementation of drives equipped with the option, an EDS file can be obtained from:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: Contact a Yaskawa representative.
Note:
16
Download the option EDS file. The option will not function as a slave in the network without the appropriate EDS file.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be found
in the drive manual.
Confirm proper setting of the parameters in Table 5 before starting network communications. After changing parameter
settings, cycle power to the drive for the new settings to take effect.
Table 5 Related Parameters
No.
(Addr.
Hex)
b1-01
(0180)
<1>
b1-02
(0181)
<1>
Name
Description
0: Digital operator
Analog input terminals
Frequency Reference Selection 1:
2: MEMOBUS/Modbus communications
1
3: Option PCB
4: Pulse input (terminal RP)
0: Digital operator
Run Command
1: Digital input terminals
Selection 1
2: MEMOBUS/Modbus communications
3: Option PCB
Values
Default: 1
Range: 0 to 4
Default: 1
Range: 0 to 3
F6-01
(03A2)
Communications Error
Operation Selection
Default: 1
Range: 0 to 3
F6-02
(03A3)
Default: 0
Range: 0, 1
F6-03
(03A4)
Default: 1
Range: 0 to 3
F6-06
(03A7)
Torque Reference/Torque
Limit Selection from Comm.
Option
Default: 0
Range: 0, 1
F6-07
(03A8)
Default: 0
Range: 0, 1
<3>
F6-14
(03BB)
F7-01
(03E5)
IP Address 1
Default: 192
Range: 0 to 255
F7-02
(03E6)
IP Address 2
Default: 168
Range: 0 to 255
F7-03
(03E7)
IP Address 3
Default: 1
Range: 0 to 255
F7-04
(03E8)
IP Address 4
Default: 20
Range: 0 to 255
Subnet Mask 1
Subnet Mask 2
Sets the second most significant octet of network static Subnet Mask.
Subnet Mask 3
Sets the third most significant octet of network static Subnet Mask.
Subnet Mask 4
Sets the fourth most significant octet of network static Subnet Mask.
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 255
Range: 0 to 255
Default: 0
Range: 0 to 255
F6-08
(036A)
<5>
<6>
<6>
<6>
<6>
F7-05
(03E9)
F7-06
(03EA)
F7-07
(03EB)
F7-08
(03EC)
Reset Communication
Parameters
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
17
Name
Description
Gateway Address 1
Gateway Address 2
Gateway Address 3
Gateway Address 4
F7-16
(03F4)
F7-17
(03F5)
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
F7-18
(03F6)
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID
2AH Object.
F7-19
(03F7)
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
F7-20
(03F8)
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
F7-21
(03F9)
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH
Object.
F7-22
(03FA)
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
F7-14
(03F2)
F7-15
(03F3)
F7-23 to
F7-32
(03FB to
0374)
F7-33 to
F7-42
(0375 to
037E)
Values
Default: 192
Range: 0 to 255
Default: 168
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 1
Range: 0 to 255
Default: 2
Range: 0 to 2
Default: 1
Range: 0 to 8 <9>
Default: 10
Range: 10; 100 to 102 <10>
Default: 0.0
Min.: 0.0
Max.: 30.0
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set the Net Control bit in the
assemblies or Control Supervisor Object. To control the drive frequency reference of the drive via the master device, set b1-01 to 3 or set the Net
Reference bit in the assemblies or AC/DC Object.
<2> When set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop switch.
18
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Description
Value Range
0 to 255
0 to 255
0 to 255
U6-92
Online Speed
Link Speed
10: 10 Mbps
100: 100 Mbps
U6-93
U6-94
Online Duplex
Port 2 Duplex
Duplex Setting
Port 2 Duplex Setting
U6-95
Port 2 Speed
0: Half, 1: Full
0: Half, 1: Full
10: 10 Mbps
100: 100 Mbps
U6-98
U6-99
First Fault
Current Fault
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
19
7 Configuring Messaging
Configuring Messaging
This section provides information on methods used to control the drive with the option installed.
20
Description
Type
Bytes
Page
Output
Output
Output
Output
Input
Input
Input
Input
4
4
6
6
4
4
6
6
21
21
22
22
29
29
30
30
Output
23
Output
23
Output
40
25
Output
44
26
Input
31
Input
32
Input
40
33
Input
44
36
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
The convention in this manual is from the PLC perspective. As such, an assembly is called an Output Assembly when outputted from the
PLC and received by this node. This section details Output Assemblies that are Consumed by this drive.
Word
0
20
1
Byte
0
1
2
3
Bit 7
Bit 6
Bit 5
Fault Reset
Speed Reference
Bit 3
Bit 2
Fault Reset
Bit 1
Bit 0
Run Fwd
Bit 1
Run Rev
Bit 0
Run Fwd
Name
Run Fwd
Bit 4
Description
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex or 10.24 Hz
Unit depends on o1-03.
Word
0
21
1
Byte
0
1
2
3
Bit 7
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
Speed Reference
Bit 6
NetRef
Bit 5
NetCtrl
Bit 4
Bit 3
Bit 2
Fault Reset
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
21
Word
0
22
1
2
Name
Run Fwd
Fault Reset
Speed Reference
Byte
0
1
2
3
4
5
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Fault Reset
Bit 1
Bit 0
Run Fwd
Bit 1
Run Rev
Bit 0
Run Fwd
Description
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex
Unit depends on o1-03.
Word
0
23
1
2
Name
Run Fwd
Run Rev
Fault Reset
NetCtrl
NetRef
Speed Reference
22
Byte
0
1
2
3
4
5
Bit 7
Bit 6
NetRef
Bit 5
NetCtrl
Bit 4
Bit 3
Bit 2
Fault Reset
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Description
Torque Reference/Torque Limit
the Torque Reference/Torque Limit in units of 0.1%.
Torque Reference/Torque Sets
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Limit
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
u MEMOBUS/Modbus Message Output (Vendor Specific Yaskawa Electric (YE) Assy) 100 (0x64)
Output Instance
Word
0
100
1
2
Note:
Byte
0
1
2
3
4
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Function Code
Register Number (High Byte)
Register Number (Low Byte)
Register Data (High Byte)
Register Data (Low Byte)
Bit 1
Bit 0
Name
Function Code
Register Number
Register Data
Description
MEMOBUS/Modbus Function Code
MEMOBUS/Modbus Register Number
MEMOBUS/Modbus Register Data
Table 8 Function Code Decode Table
Function Code
0x00
0x03
0x10
Note:
MEMOBUS/Modbus Function
No Operation
Read Register
Write Register
Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor
data using the MEMOBUS/Modbus message area.
u Speed/Torque Control Output (Vendor Specific Yaskawa Electric (YE) Assy) - 101 (0x65)
Output Instance
Word
Byte
0
0
1
101
1
2
3
Bit 7
MultiFunction
Input 8
Bit 6
MultiFunction
Input 7
Bit 5
MultiFunction
Input 6
Bit 4
MultiFunction
Input 5
Bit 3
MultiFunction
Input 4
Bit 2
MultiFunction
Input 3
MultiFunction
Photocoupler 2
MultiFunction
Photocoupler 1
MultiFunction
Digital
Output
2
3
4
5
6
7
Name
Run Fwd
Run Rev
Multi-Function Input 3
Bit 1
Bit 0
Run Rev
Run Fwd
Fault Reset
External
Fault
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
23
Description
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
0: No Fault Reset
1: Fault Reset
Multi-Function Digital
Output
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Multi-Function
Photocoupler 1
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Multi-Function
Photocoupler 2
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Reference
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
24
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
u Extended Speed/Torque Control Output (Vendor Specific Yaskawa Electric (YE) Assy)
- 115 (0x73)
Output Instance
Word
Byte
0
0
1
1
2
115
3
4/5
6
7
8
9-20
Bit 7
MultiFunction
Input 8
MultiFunction
Photocoupler 2
Bit 6
MultiFunction
Input 7
MultiFunction
Photocoupler 1
Bit 5
MultiFunction
Input 6
MultiFunction
Digital
Output
Multi-Function Input 8
External Fault
Fault Reset
Multi-Function Digital
Output
Bit 1
Bit 0
Run Rev
Run Fwd
Fault Reset
External
Fault
Description
Multi-Function Input 7
Reserved
Analog Output 1 (Low Byte)
Analog Output 1 (High Byte)
Analog Output 2 (Low Byte)
Analog Output 2 (High Byte)
Digital Outputs (Low Byte)
Digital Outputs (High Byte)
Reserved
Run Rev
Multi-Function Input 6
8-11
12
13
14
15
16
17
18-39
Run Fwd
Multi-Function Input 5
Bit 2
MultiFunction
Input 3
Multi-Function Input 4
Bit 3
MultiFunction
Input 4
2
3
4
5
6
7
Name
Multi-Function Input 3
Bit 4
MultiFunction
Input 5
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
25
Description
Terminal P1
Multi-Function
0: P1 OFF
Photocoupler 1
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
Multi-Function
0: P2 OFF
Photocoupler 2
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Command
Sets drive speed reference.
Speed Reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Reference/Torque Limit
the Torque Reference/Torque Limit in units of 0.1%.
Torque Reference/Torque Sets
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Limit
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Torque Compensation
Sets the amount of Torque Compensation Sets in units of 0.1%.
Analog Output 1
Analog Output 2
Digital Outputs
MEMOBUS/Modbus (0x0007)
MEMOBUS/Modbus (0x0008)
MEMOBUS/Modbus (0x0009)
u High Speed/Torque Control Output (Vendor Specific Yaskawa Electric (YE) Assy) - 116
(0x74)
This assembly is dynamic and can be configured as to what parameters are used. The first 20 Bytes (0-19) are fixed and the
next 20 Bytes can be configured using parameters F7-23 to F7-32. If an error occurs while trying to write to the dynamic
parameters, the appropriate error bit in Assembly 166 will be set. If more information is needed as to the nature of the error,
the extended error status can be read explicitly through Class 4, Instance 0xA6, Attribute 0x64. This will return 20 Bytes with
each dynamic parameter in Assembly 116 having a Byte dedicated to its extended error status. Refer to Input Assemblies
(Drive Produces) on page 29 for more information.
Output Instance
Word
Byte
0
0
1
1
2
116
3
5
6
26
Bit 7
MultiFunction
Input 8
Bit 6
MultiFunction
Input 7
Bit 5
MultiFunction
Input 6
Bit 4
MultiFunction
Input 5
Bit 3
MultiFunction
Input 4
Bit 2
MultiFunction
Input 3
MultiFunction
Photocoupler 2
MultiFunction
Photocoupler 1
MultiFunction
Digital
Output
2
3
4
5
6
7
8
9
10
11
12
13
Function
Function
Input 12
Input 11
Bit 1
Bit 0
Run Rev
Run Fwd
Fault Reset
External
Fault
MultiFunction
Input 10
NetCtrl
MultiFunction
Input 9
NetRef
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Word
7
8
9
116
Byte
14
15
16
17
18
19
Bit 7
Bit 6
Run Rev
Multi-Function Input 3
Multi-Function Input 4
Multi-Function Input 5
Multi-Function Input 6
Multi-Function Input 7
Multi-Function Input 8
Bit 4
Bit 3
Bit 2
Analog Output 2 (Low Byte)
Analog Output 2 (High Byte)
Digital Outputs (Low Byte)
Digital Outputs (High Byte)
Reserved
Reserved
Programmable Bytes
Defined by F7-23
Default: Not Used
Programmable Bytes
Defined by F7-24
Default: Not Used
Programmable Bytes
Defined by F7-25
Default: Not Used
Programmable Bytes
Defined by F7-26
Default: Not Used
10
20-21
11
22-23
12
24-25
13
26-27
14
28-29
Programmable Bytes
Defined by F7-27
Default: Not Used
15
30-31
Programmable Bytes
Defined by F7-28
Default: Not Used
16
32-33
Programmable Bytes
Defined by F7-29
Default: Not Used
17
34-35
Programmable Bytes
Defined by F7-30
Default: Not Used
18
36-37
Programmable Bytes
Defined by F7-31
Default: Not Used
19
38-39
Programmable Bytes
Defined by F7-32
Default: Not Used
Name
Run Fwd
Bit 5
Bit 1
Bit 0
Description
Forward Run Command
0: Stop
1: Forward Run
Reverse Run Command
0: Stop
1: Reverse Run
Terminal S3 Function Input
0: Terminal S3 Function (H1-03) OFF
1: Terminal S3 Function (H1-03) ON
Terminal S4 Function Input
0: Terminal S4 Function (H1-04) OFF
1: Terminal S4 Function (H1-04) ON
Terminal S5 Function Input
0: Terminal S5 Function (H1-05) OFF
1: Terminal S5 Function (H1-05) ON
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
27
Speed Reference
Description
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
0: No Fault Reset
1: Fault Reset
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
28
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
The convention in this manual is from the PLC perspective. An Input Assembly is outputted from this node and read by the PLC. This
section details Input Assemblies that are Produced by this drive.
Word
0
70
1
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
1
2
3
Bit 2
Running 1
(FWD)
Bit 1
Bit 0
Faulted
Bit 3
Bit 2
Running
2
Running
1
Ready
(REV)
(FWD)
Drive State
Speed Actual (Low Byte)
Speed Actual (High Byte)
Bit 1
Bit 0
Warning
Faulted
Name
Description
Faulted
0: No Faults Occurred
1: Fault Occurred
Faulted
Forward Running
0: Stop or Reverse Running
1: Forward Running
Running 1 (FWD)
Speed Actual
Word
0
71
1
Byte
Bit 7
At Speed
Bit 6
Ref from
Net
1
2
3
Name
Faulted
Warning
Running 1 (FWD)
Running 2 (REV)
Ready
Ctrl from Net
Ref from Net
At Speed
Bit 5
Ctrl from
Net
Bit 4
Description
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
0: No Warning Occurred
1: Warning Occurred
Forward Running
0: Stop or Reverse Running
1: Forward Running
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Drive Ready
0: Not Ready
1: Ready
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
29
Speed Actual
Description
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Word
0
72
1
2
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Running 1 (FWD)
Bit 1
Bit 0
Faulted
Bit 3
Bit 2
Running 2 Running 1
Ready
(REV)
(FWD)
Drive State
Speed Actual (Low Byte)
Speed Actual (High Byte)
Torque Actual (Low Byte)
Torque Actual (High Byte)
Bit 1
Bit 0
Warning
Faulted
1
2
3
4
5
Name
Faulted
Bit 2
Running 1
(FWD)
Description
Faulted
0: No Faults Occurred
1: Fault Occurred
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Torque Actual
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
Word
0
73
1
2
Byte
Bit 7
At Speed
1
2
3
4
5
Name
Faulted
Warning
Running 1 (FWD)
30
Bit 6
Ref from
Net
Bit 5
Ctrl from
Net
Bit 4
Description
Faulted
0: No Faults Occurred
1: Fault Occurred
Warning
0: No Warning Occurred
1: Warning Occurred
Forward Running
0: Stop or Reverse Running
1: Forward Running
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Speed Actual
Description
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Drive Ready
0: Not Ready
1: Ready
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
Torque Actual
u MEMOBUS/Modbus Message Input (Vendor Specific Yaskawa Electric (YE) Assy) - 150
(0x96)
Input Instance
Word
0
150
1
2
Note:
Byte
0
1
2
3
4
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Function Code
Register Number (High Byte)
Register Number (Low Byte)
Register Data (High Byte)
Register Data (Low Byte)
Bit 1
Bit 0
Byte
Write Success
Read Success
Write Failure
Read Failure
0x10
0x03
0x90
0x83
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(Low Byte)
Read Data
(High Byte)
Read Data (Low Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(Low Byte)
Output Assembly
Register Number
(High Byte)
Output Assembly
Register Number
(Low Byte)
Error Code
Error Code
1
2
3
0
0
Description
Invalid Function Code
Invalid Register Number
Upper/Lower Limit Error
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
31
Description
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done.
Writing Enter when drive is running.
Attempt to write data that is read only.
Attempt to write a parameter when drive is running.
During a CPF03 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.
Attempting to write during a drive undervoltage (Uv) event.
Attempting to write while the drive is storing data.
Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor
data using the MEMOBUS/Modbus message area.
u Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 151 (0x97)
Input Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Faulted
Alarm
Ready
MultiFunction
Photocoupler 2
0
1
151
1
2
3
ZSV
2
3
4
5
6
7
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
Speed Agree
Ready
Alarm
Faulted
OPE
UV
LOCAL/REMOTE
32
Reset
MultiFunction
Digital
Output
Bit 2
REV
Running
Bit 1
Bit 0
ZSP
Running
LOCAL/
REMOTE
Uv
oPE
Description
Running
Reset
Bit 3
Name
REV Running
Bit 4
Speed
Agree
MultiFunction
Photocoupler 1
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
0: No Reset
1: Reset
Speed Agree
0: No Speed Agree
1: Speed Actual at speed reference
Drive Ready
0: Not Ready
1: Ready
Drive Alarm
0: No Drive Alarm
1: Alarm
Drive Fault
0: No Drive Fault
1: Fault
OPE Fault
0: No oPE Fault
1: oPE
Undervoltage
0: No Undervoltage
1: Undervoltage
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Output Frequency
Torque Actual
Current Actual
Description
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
Zero Servo Completed
0:
1: Completed
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
Actual Output Current
Monitors drive output current.
Unit is 0.01 A.
Unit is not affected by Current Scale CS.
u Extended Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) 155 (0x9B)
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Faulted
Alarm
ZSV
1
2
3
155
4
5
6
2
3
4
5
6
7
8
9
10
11
12
13
14
7
15
8
9
16
17
18
19
Ready
Bit 4
Speed
Agree
Bit 3
Fault Reset
MultiFunction
Photocoupler 2
MultiFunction
Photocoupler 1
MultiFunction
Digital
Output
Bit 2
REV
Running
Bit 1
Bit 0
ZSP
Running
LOCAL/
REMOTE
Uv
oPE
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
33
Word
Byte
Bit 7
Bit 6
20 <1>
10
21 <1>
22 <1>
11
23 <1>
24 <1>
12
25 <1>
155
26 <1>
13
27 <1>
14
Bit 4
Bit 3
Bit 2
Parameter F7-33
Default: Alarm Code (Low Byte)
Parameter F7-33
Default: Alarm Code (High Byte)
Parameter F7-34
Default: Output Power (Low Byte)
Parameter F7-34
Default: Output Power (High Byte)
Parameter F7-37
Default: Terminal A3 Input (Low Byte)
Parameter F7-37
Default: Terminal A3 Input (High Byte)
Parameter F7-36
Default: Terminal S1 to S8 Input (Low Byte)
Parameter F7-36
Default: Terminal S1 to S8 Input (High Byte)
28 <1>
29 <1>
30 <1>
Parameter F7-38
Default: PG Counter (Ch2) (Low Byte)
31 <1>
Parameter F7-38
Default: PG Counter (Ch2) (High Byte)
32-39
Reserved
15
16-19
Bit 5
Bit 1
Bit 0
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Fault Reset
Speed Agree
Ready
Alarm
Faulted
oPE
Uv
LOCAL/REMOTE
34
Description
Running
0: Stop
1: Forward or Reverse Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network
Speed Agree
0: No Speed Agree
1: Speed Actual at speed reference
Drive Ready
0: Not Ready
1: Ready
Drive Alarm
0: No Drive Alarm
1: Alarm
Drive Fault
0: No Drive Fault
1: Fault
oPE Fault
0: No oPE Fault
1: oPE
Undervoltage
0: No Undervoltage
1: Undervoltage
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Output Current
Description
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
Zero Servo Completed
0:
1: Completed
Monitor parameter U1-05
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
Contained MEMOBUS/Modbus Address
Monitor parameter U1-01
Actual Drive Speed
Monitors drive output frequency.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Actual Output Current
Monitors drive output current.
Unit is 0.01 A
Unit is not affected by Current Scale CS.
(0x46)
Drive Terminal A1 Input MEMOBUS/Modbus
Monitor parameter U1-13
Main DC Voltage
Error Code
F7-33 Alarm Code
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
35
u High Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166
(0xA6)
If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set. If
more information about the nature of the error is needed, the extended error status can be read explicitly through Class 4,
Instance 0xA6, Attribute 0x64. This will return 20 Bytes with each dynamic parameter in Assembly 166 having a Byte
dedicated to its extended error status.
Output Instance
Word
Byte
Bit 7
Bit 6
Bit 5
Faulted
Alarm
Ready
ZSV
MultiFunction
Photocoupler 2
1
2
3
4
166
5
6
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Parameter F7-35
Default: Terminal A2 Input (High Byte)
16
17
18
19
20 <1>
21 <1>
Parameter F7-33
Default: Alarm Code (High Byte)
8
9
10
36
Bit 4
Bit 3
Bit 2
Speed
REV
Fault Reset Running
Agree
MultiMultiFunction
Function
LOCAL/
PhotoDigital
REMOTE
coupler 1
Output
Motor Speed (Low Byte)
Motor Speed (High Byte)
Torque Actual (Low Byte)
Bit 1
Bit 0
ZSP
Running
Uv
oPE
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Word
Byte
Bit 7
Bit 6
30 <1>
Bit 4
Bit 3
Bit 2
Parameter F7-34
Default: Output Power (Low Byte)
Parameter F7-34
Default: Output Power (High Byte)
Parameter F7-35
Default: Terminal A2 Input (Low Byte)
Parameter F7-35
Default: Terminal A2 Input (High Byte)
Parameter F7-36
Default: Terminal S1 to S8 Input (Low Byte)
Parameter F7-36
Default: Terminal S1 to S8 Input (High Byte)
Parameter F7-37
Default: Terminal A3 Input (Low Byte)
Parameter F7-37
Default: Terminal A3 Input (High Byte)
Parameter F7-38
Default: PG Counter (Ch2) (Low Byte)
31 <1>
Parameter F7-38
Default: PG Counter (Ch2) (High Byte)
32 <1>
Parameter F7-39
Default: NetRef and NetCtrl (Low Byte)
22 <1>
11
23 <1>
24 <1>
12
25 <1>
26 <1>
13
27 <1>
28 <1>
14
29 <1>
15
16
166
Bit 5
33 <1>
Parameter F7-39
Default: NetRef and NetCtrl
34 <1>
Parameter F7-40
Default: Drive Software Version (Low Byte)
35 <1>
Parameter F7-40
Default: Drive Software Version (High Byte)
36 <1>
Parameter F7-41
Default: Not Used
37 <1>
Parameter F7-33
Default: Not Used
38 <1>
Parameter F7-33
Default: Not Used
39 <1>
Parameter F7-42
Default: Not Used
17
18
19
40
41
Assy. 116
F7-30
Error
Assy. 116
F7-29
Error
Assy. 116
F7-28
Error
Assy. 116
F7-27
Error
Assy. 116
F7-26
Error
Assy. 116
F7-25
Error
42
43
Assy. 166
F7-40
Error
Assy. 166
F7-39
Error
Assy. 166
F7-38
Error
Assy. 166
F7-37
Error
Assy. 166
F7-36
Error
Assy. 166
F7-35
Error
20
21
Bit 1
Bit 0
NetCtrl
NetRef
Assy. 116
F7-32
Error
Assy. 116
F7-24
Error
Assy. 166
F7-42
Error
Assy. 166
F7-34
Error
Assy. 116
F7-31
Error
Assy. 116
F7-23
Error
Assy. 166
F7-41
Error
Assy. 166
F7-33
Error
Description
Running
0: Stop
1: Forward or Reverse Running
Zero Speed
0: Running
1: Stop or DC Injection Braking
Reverse Running
0: Not Reverse Running
1: Reverse Running
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
37
Description
Fault Reset command from Network
0: Fault Reset command is not from network
1: Fault Reset command is from network
Speed Agree
0: No Speed Agree
1: Speed Actual at speed reference
Drive Ready
0: Not Ready
1: Ready
Drive Alarm
0: No Drive Alarm
1: Alarm
Drive Fault
0: No Drive Fault
1: Fault
oPE Fault
0: No oPE Fault
1: oPE
Undervoltage
0: No Undervoltage
1: Undervoltage
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Multi-Function
Photocoupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON
Multi-Function
Photocoupler 2
Terminal P2
0: Terminal P2 OFF
1: Terminal P2 ON
ZSV
Motor Speed
Torque Actual
PG Count Value
Frequency Command
38
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Description
Programmable: MEMOBUS/Modbus (0xF1)
Serial interface Control Response
Status of reference command from Network
0: Reference command is not from network
1: Reference command is from network
Programmable: MEMOBUS/Modbus (0x4D)
Monitor parameter U1-25
Possible extended error codes are listed in Table 11 and Table 12. If an error occurs, extended error code 0x02 (Register
number failure) is usually set.
Table 11 Extended Error Codes for Assembly 116/166
Error Code
0x00
0x01
0x02
0x21
0x22
0x23
0x24
Description
No error
Sub function code failure
Register number failure
Limit check error failure
Write failure
Write failure at Uv
Write failure at busy
Table 12 Extended Error Codes in Class 0x04 Instance 0xA6 Attribute 0x64
Dynamic Parameter
F7-23
F7-24
F7-25
F7-26
F7-27
F7-28
F7-29
F7-30
F7-31
F7-32
F7-33
F7-34
F7-35
F7-36
F7-37
F7-38
F7-39
F7-40
F7-41
F7-42
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
39
10
Service Name
Get Attribute All
Reset
Get Attribute Single
n Attributes Supported
Instance
ID
Attribute
Vendor ID
Name
Description
Get
Set
Size
Range
Default
Word
Manufacturer code.
44 (2C H): Yaskawa Electric
Word
44 (Yaskawa)
Device Type
Device profile.
The profile for this product is an AC
drive.
2: AC drive
Word
2 (AC drives)
Product Code
Word
<1>
Revision
Word
Depends on software
Status
Word
Long
String
(14 Bytes)
Byte
3
State of the drive
State
<1> Product code is 2 Bytes. The first Byte is the drive type and the second Byte is the model number of the drive.
Service Name
Get Attribute Single
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
20
21
22
40
Name
Description
Get
Set
Size
Range
Default
Word
Array 4 Bytes
00 00 00 00
Array 4 Bytes
00 00 00 00
Array 6 Bytes
00 00 00 00 00 00
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
Name
23
Data
70
Data
71
Data
72
Data
73
Data
100
Data
101
Data
115
Data
Description
Same function as the Extended Speed
and Torque Control
(Output Assembly)
Same function as the Basic Speed
Control
(Input Assembly)
Same function as the Extended Speed
Control
(Input Assembly)
Same function as the Extended Speed
and Torque Control
(Input Assembly)
Same function as the Speed Control
(Input Assembly)
Same function as the MEMOBUS/
Modbus Message Command (Output
Assembly)
Same function as the Standard Control
(Output Assembly)
Same function as the Extended Speed/
Torque Control (Output Assembly)
Get
Set
Size
Range
Array 6 Bytes
00 00 00 00 00 00
Array 4 Bytes
00 00 00 00
Array 4 Bytes
00 00 00 00
Array 6 Bytes
00 00 00 00 00 00
Array 6 Bytes
00 00 00 00 00 00
Array 5 Bytes
00 00 00 00 00
Array 8 Bytes
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
Array 40
Bytes
Default
116
Data
Array 44
Bytes
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00
150
Data
Array 5 Bytes
00 00 00 00 00
151
Data
Array 8 Bytes
00 00 00 00 00 00 00 00
Data
Array 40
Bytes
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00 00 00 00 00
00 00 00 00
155
166
Data
Array 44
Bytes
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Service Name
Get Attribute Single
Set Attribute Single
41
n Attributes Supported
Instance
ID
Attribute
Name
Description
Get
Set
Size
Range
Default
Word
Byte
.
Depends on A1-02,
Control Method
Selection
Byte
Depends on capacity
Byte
Depends on capacity
Service Name
Get Attribute Single
Set Attribute Single
Reset
n Attributes Supported
Instance
ID
Attribute
42
Name
Description
Get
Set
Size
Range
Default
Word
Running
Run 1 (Forward Forward
Stop
Run Command) 0:
1: Forward Running
Byte
0, 1
Running
Run 2 (Reverse Reverse
Stop
Run Command) 0:
1: Reverse Running
Byte
0, 1
NetCtrl
(Command)
Byte
0, 1
State
Byte
Running 1
(FWD)
Byte
Running 1
(REV)
Byte
Ready
Byte
10
Faulted
Byte
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
11
12
13
15
16
17
18
Name
Description
Warning
0: No Warning
1: Warning
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
Current Fault
Refer
to Option Fault Code
Fault Code
Conversion Table on page 43 for
details.
Run Command from the option
The Run command is not from the
Control from 0:
Net (Status) option
1: Enables the Run command from
option
NetFaultMode Normal 2 (Vendor Specific)
External Fault
0: No External Fault
Force Fault
1: External Fault (EF0)
Triggered by the rising edge of the
signal.
Warning
Force Status
Get
Set
Size
Range
Default
Byte
Byte
0, 1
Word
0000
Byte
Byte
Byte
0, 1
Byte
Description
0
3220
5110
3222
2120
2300
3210
4200
4210
2220
2200
2221
2222
7110
7112
9000
9000
9000
9000
9000
9000
7310
7310
7301
3130
3130
None
DC Bus Undervolt (Uv1)
CTL PS Undervolt (Uv2)
MC Answerback (Uv3)
Ground Fault (GF)
Over Current (oC)
DC Bus Overvolt (ov)
Heatsink Overtemp (oH)
Heatsink Max Temp (oH1)
Motor Overload (oL1)
Drive Overload (oL2)
Overtorque Det 1 (oL3)
Overtorque Det 2 (oL4)
DynBrk Transistor (rr)
DynBrk Resistor (rH)
External Fault 3 (EF3)
External Fault 4 (EF4)
External Fault 5 (EF5)
External Fault 6 (EF6)
External Fault 7 (EF7)
External Fault 8 (EF8)
Overspeed Det (oS)
Speed Deviation (dEv)
PG Open (PGo)
Input Phase Loss (PF)
Output Phase Loss (LF)
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
43
Description
5210
5300
6320
3210
7500
7500
8321
9000
8000
8000
8000
8000
8000
51
52
53
54
55
56
59
65
66
67
38
39
70
73
77
78
79
8000
8000
8000
8000
8000
7000
1000
8000
9000
9000
8000
8000
5000
8000
5000
7000
7000
1000
Service Name
Get Attribute Single
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
44
Name
Description
Get
Set
Size
Range
Default
Word
Byte
Byte
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
11
Name
Description
Get
Set
Size
Range
Default
Byte
0 to 3
Word
Word
Word
Word
Word
12
Torque
Reference/
Torque Limit
15
Power Actual
(W)
Word
16
Input Voltage
(V)
Word
Dep. on capacity
17
Word
18
Word
2710H
19
Word
2710H
20
Word
0 to 1100
21
Word
0 to 1100
3E8H
22
Byte
-15 to 15
23
Byte
-15 to 15
24
Byte
-15 to 15
26
Byte
-15 to 15
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
45
Attribute
Name
27
28
Voltage Scale
(-15 to 15)
Time Scale
(-15 to 15)
29
Description
Get
Set
Size
Range
Default
Byte
-15 to 15
Byte
-15 to 15
Byte
n Services Supported
Service Code No. (Hex)
01
10
Service Name
Get Attribute All
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
46
Name
Description
Get
Set
Size
Range
Default
Word
Byte
0, 1
Byte
0 to 4
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
10
12
Note:
Name
Description
Struct of:
Supervisor IP Address = Long
Supervisor MAC Address = Array of
bytes
Capability Flags Describes DLR capabilities
Active
Supervisor
Address
Get
Set
Size
Range
Default
Struct
Long
0x00000002
Service Name
Get Attribute Single
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
DCSP Urgent
Name
Description
Get
Set
Size
Range
Default
Word
Byte
0 to 63
55
DSCP
Scheduled
Byte
0 to 63
47
DSCP High
Byte
0 to 63
43
DSCP Low
Byte
0 to 63
31
Byte
0 to 63
27
Service Name
Get Attribute All
Get Attribute Single
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
Name
Description
Get
Set
Size
Range
Default
Word
DWord
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
47
Attribute
Name
Configuration
Capability
Configuration
Control
Physical Link
Interface
Configuration
Host Name
10
Select ACD
Note:
11
Last Conflict
Detected
Description
Bit 0 = BOOTP Client
Bit 1 = DNS Client
Bit 2 = DHCP Client
Bit 3 = DHCP-DNS Update
Bit 4 = Configuration Settable
Bits 5-31 = Reserved
Bits 0-3 = Startup Configuration
0: NVRAM
1: BOOTP
2: DHCP
3: Reserved
Bit 4 =DNS Enabled (not supported)
Bits 5-31 = Reserved
Struct of:
Path Size: 0
Path: 0
Struct of:
IP Address = Long
Subnet Mask = Long
Gateway Address = Long
Name Server1 = Long
Name Server2 = Long
Domain Name = STRING
Host Name
Activates use of ACD
0: Disable ACD
1: Enable ACD
Structure containing information
related to the last conflict detected.
Struct of:
Bit 0: ACD Activity
Bits 1-7: Remote MAC
Bits 8-36: ARP PDU
Get
Set
Size
Range
Default
DWord
DWord
Struct
Struct
STRING
64 char
Null
BOOL
0, 1
Struct
Service Name
Get Attribute All
Get Attribute Single
Set Attribute Single
n Attributes Supported
Instance
ID
Attribute
48
Name
Description
Number of
Instances
Interface Speed Interface speed currently in use
Get
Set
Size
Range
Default
Word
UINT
UINT
UDINT
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
1
2
10
1
Name
Interface
Control
10
Interface Label
Note:
Description
Struct of:
Control Bits: Word
Bit 0 = Auto-negotiate
Bit 1 = Forced Duplex Mode
Bits 2-15 = Reserved
Forced Int Speed: Word
Get
Set
Size
Range
Default
DWord
Array of 6
Bytes
Struct
O
O
Short String
UDINT
Port 1
DWord
Struct
Short String
Port 2
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
49
11
Service Name
Get Attribute Single
Set Attribute Single
This is a dynamic explicit Class Object. With this Class object any drive parameter with a MEMOBUS/Modbus address greater
than 0x00FF can be accessed. The mapping of Class Object instance/attribute to MEMOBUS/Modbus address is as follows.
Given a typical MEMOBUS/Modbus Address of 0xXXYY
The EtherNet/IP Instance value is equal to XX
The EtherNet/IP Attribute value is equal to YY
As an example, to access parameter b5-12 (MEMOBUS/Modbus Address =0x01B0)
Class Object is 100 (0x64) (Always for this Class Object)
Instance = 0x01
Attribute = 0xB0
Parameter H5-11 is used to decide whether a RAM-ENTER will be done on the writes to registers in the drive. If H5-11 = 1
(default), the option will issue the RAM-ENTER with the parameter writes. If H5-11 = 0, no RAM-ENTER is issued and an
ENTER command must be explicitly sent by the user for the parameter to be activated after a write.
Explicit writes to RAM-ENTER (0x910) and ROM-ENTER (0x900) are handled as special cases. If a user writes a 0 to RAMENTER or ROM-ENTER, the command will be executed in the drive. If a user writes a 1 to those registers, the command will
not be executed but returns a success to the explicit write on the network. Writing a value other than 0 or 1 will result in an
error response of Invalid Attribute Value on the network.
Note:
Performing the RAM-ENTER increases the processing time of the writes and increases the response time to explicit writes.
n Attributes Supported
Instance
ID
Attribute
Name
00
01
YY
YY
Object Software
Revision
MEMOBUS/
Modbus
Register
0x0100
MEMOBUS/
Modbus
Register
0x0101
MEMOBUS/
Modbus
Registers
0x0100 to
0x01FF
MEMOBUS/
Modbus
Registers
0x0200 to
0x02FF
50
Description
Get
Set
Size
Range
Default
Word
Language selection
Word
0 to 2
Word
0 to 2
MEMOBUS/Modbus Registers
0x0100 to 0x01FF
Word
MEMOBUS/Modbus Registers
0x0200 to 0x02FF
Word
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
Attribute
Name
Description
Get
Set
Size
Range
Default
...
...
...
Word
255
YY
...
MEMOBUS/
Modbus
Registers
0xFF00 to
0xFFFF
Word
Note:
MEMOBUS/Modbus Registers
0xFF00 to 0xFFFF
1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of
monitor data using the MEMOBUS/Modbus message area.
Service Name
Get Attribute Single
Set Attribute Single
This is a dynamic explicit Class Object. With this Class object any parameter with a MEMOBUS/Modbus address less than
0x0100 can be accessed. This class is similar to the Drive Parameters Object Class 100, Object Class 100 differs slightly from
Object Class 125. In Object Class 125 the most significant byte of MEMOBUS/Modbus address is always zero and the Instance
ID remains at 1.
Given a typical MEMOBUS/Modbus Address 0f 0x00YY
The EtherNet/IP Instance value is equal to 0x01
The EtherNet/IP Attribute value is equal to YY
As an example, to access Drive Status (MEMOBUS/Modbus Address = 0x002C)
Class Object is 125 (0x7D) (Always for this Class Object)
Instance = 0x01
Attribute = 0x2C
n Attributes Supported
Instance
ID
Attribute
0
1
1
..
1
1
1
2
..
255
Note:
MEMOBUS/
Modbus
Address
0x0001
0x0002
..
0x00FF
Description
Object Software Revision
Drive Command Bits
Frequency Instruction
..
Unused
Get
Set
Size
Range
Default
O
O
O
O
O
O
O
O
O
Word
Word
Word
Word
Word
1
0
4
1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of
monitor data using the MEMOBUS/Modbus message area.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
51
12 Web Interface
12
Web Interface
The option contains a series of web pages that allow for viewing of status and diagnostic information through a standard web
browser.
The web page is accessed through a self-contained web server at port 80. Access the home page by typing the IP address of
the option in a web browser. Example: "http://192.168.1.20"
The IP address of the option can be read using monitors U6-80 to U6-83 on the digital operator if it is unknown. Refer to
Option Monitors on page 19 for details.
The home page is an HTML-based page providing basic drive and option data and a link to an enhanced web page requiring
a Java enabled web browser.
Enhanced Web Page Notes:
The Enhanced Web Pages use a series of Java applets.
PCs must have Java SE 6 Update 14 or later installed to view the enhanced web pages.
The Java applets require an internet connection to check the revocation status.
When no internet connection is available, disable the revocation check by changing a Java setting in the PC: All Programs /
Java / Configure Java / Advanced Tab. Set "Perform certificate checks on" to "Do not check".
Enhanced Web Page Tab
Main Tab
Drive Status Tab
Network Tab
Email Alerts Tab
Parameter Access Tab <1>
Configuration
Custom Tab
Tab <1>
Page
53
54
54
55
56
57
58
52
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
12 Web Interface
VST800340
CIMR-AU2A0004
u Main Tab
The Main tab shows basic option information such as IP address, MAC address, and firmware version.
VST800340
CIMR-AU2A0004
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
53
12 Web Interface
u Network Tab
The Network tab shows the status of the option network traffic and the status of open I/O connections.
54
Explanation
Cumulative number of messages transmitted successfully from the option.
Cumulative number of messages received successfully to the option.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
12 Web Interface
Network Monitor
Current Connections
Control Connection Delta
Time
Msg Tx Dropped
Msg Rx Dropped
Collisions
Msg Tx Errors
Msg Rx Errors
Tx Retry
Explanation
Current number of open connections.
The time between the last two writes to the Control register, MEMOBUS/Modbus address 0001H.
Cumulative number of messages dropped due to output network buffer being full and unable to hold the new message.
Cumulative number of messages dropped due to input network buffer being full and unable to hold the new message.
Cumulative number of collisions (half duplex only) reported by the MAC/PHY (Media Access Control/Physical
Connection).
Cumulative number of transmit underruns and transmit stops reported by the MAC/PHY.
Cumulative number of receive overruns, receive stops, and receive error frames reported by the MAC/PHY.
Cumulative number of transmits in which the 1st attempt was delayed due to busy medium reported by the MAC/PHY.
Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value. Set up
comparator values for the range of values to check in the chosen condition. If choosing only one condition and no OR
or AND are needed, set the OR/AND drop-down selection to NotUsed.
Enter the email address where the alert will be sent.
Enter the message that will appear in the email contents.
Enter the email subject.
Click the Email Active check box to enable the alert.
Clicking Save to device will save the entered information into the option memory.
Clicking Cancel and reload will cancel any pending edits and display the most recently saved settings from the option board.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
55
12 Web Interface
The MEMOBUS/Modbus address for the drive parameter being accessed must be entered in hexadecimal. The number must
begin with 0x to signify hexadecimal. Clicking Read will load and display the current value of the given MEMOBUS/
Modbus Address.
Clicking Set will save the given value to the given MEMOBUS/Modbus address.
After a Read or Set command is given, Status will display Waiting while the action is being carried out, then Complete
is displayed when finished.
56
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
12 Web Interface
u Configuration Tab
The Configuration tab sets web page behavior parameters. Access is restricted unless a valid password is entered.
n Security Login
Enter a valid password and click Log in. The button text will change to Log out and the status will change to Logged
in.
Note:
This password can be changed in the Change Password section of the tab. Entering a valid password allows access to the
settings in the Configuration tab, Email Alerts tab, and the Parameter Access tab.
n Change Password
To change the password, enter the new password in the New Password: and Confirm Password: text boxes then click
Change password. The Status display will change to Idle then Changing Password then Password Changed. If the
passwords in the two text boxes do not match, the Status will display Passwords dont match.
n Option Card
The values displayed in the various tabs are refreshed at the rate defined in the Applet Refresh Rate (ms) text box. Enter
values in the range of 1000 ms to 65.535 seconds.
Parameter Security can be enabled or disabled by clicking one of the radio buttons. When Disabled is selected, no password
is necessary and all functions in the web pages will be available. When Enabled is selected, a valid password must be entered
to edit email settings and to write parameters.
n Email Settings
The Email Server IP text box must contain the IP address of the email server. The subnet address is configured in drive
parameters F7-05 through F7-08. The configured email alerts will use the server at this address when sending emails.
Enter the email server port in the Email Port text box.
The value in the From Email Address text box identifies the origin of the email alerts to the recipient.
Click Submit Email Parameters to save the email settings to the option.
Click Save Configuration Parameters to Flash to save the entered values from this tab into non-volatile memory. These
values will then be remembered after cycling power.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
57
12 Web Interface
n General Settings
Click Save Options Card Parameters to save the Applet Refresh Rate and the Parameter Security settings to the option.
u Custom Tab
The Custom tab displays a selection of quick setting parameters.
58
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
13 Troubleshooting
13
Troubleshooting
n Faults
Both bUS (Option Communication Error) and EF0 (Option Card External Fault) can appear as an alarm or as a fault. When a
fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
Is the option properly installed?
Are the communication lines properly connected to the option? Are the wires loose?
Is the controller program working? Has the controller/PLC CPU stopped?
Did a momentary power loss interrupt communications?
Digital Operator Display
bUS
Cause
Fault Name
Option Communication Error
The connection was lost after establishing initial communication.
Only detected when the Run command or frequency reference is assigned to the option (b1-01 = 3 or
b1-02 = 3).
Possible Solution
Check that power is supplied to the PLC
Check that PLC is not in program mode
Option is damaged
If there are no problems with the wiring and the error continues to occur, replace the option.
Fault Name
Fault Name
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Possible Solution
Fault Name
Option Card Fault at Option Port CN5-A
Option not properly connected
Cause
Possible Solution
Turn off the power and reconnect the option card.
The option card connection to port CN5-A is Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
If the option is not a communication option card, try to use the card in a different option port. If the
faulty
option card works properly in a different option port, CN5-A is damaged, and the drive requires
replacement. If the error persists (oFb01 or oFC01 occur), replace the option card.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
59
13 Troubleshooting
Digital Operator Display
Fault Name
to
oFA03 to oFA06
oFA10, oFA11
to
oFA12 to oFA17
to
oFA30 to oFA43
Cause
Option card or hardware is damaged
Possible Solution
Cycle power to the drive.
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Fault Name
Option Card Fault at Option Port CN5-B
Option compatibility error
Cause
The option card installed into port CN5-B is
incompatible with the drive
Possible Solution
Confirm that the drive supports the option card to be installed.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
Fault Name
Option Card Fault at Option Port CN5-B
Same type of option card is currently connected
Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
Cause
The option card installed into port CN5-C is
incompatible with the drive
Fault Name
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Possible Solution
Confirm that the drive supports the option card to be installed.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
oFC00
60
Fault Name
Option Card Fault at Option Port CN5-C
Same type of option card is currently connected
Possible Solution
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
13 Troubleshooting
Cause
Minor Fault
(H2-oo = 10)
Possible Solutions
YES
Install a termination resistor at both ends of a communication line. Set the internal
termination resistor switch correctly on slave drives. Place DIP switch S1 to the
ON position.
Parameter F6-14, bUS Fault Auto Reset Select, will appear when the option is installed.
Setting F6-14 = 0 (Disabled) or F6-01 = 3 or greater (Alarm only) will not affect standard default drive behavior.
Setting F6-14 = 1 (Enabled) AND F6-01 3 (Fault) will cause the following operation: The bUS fault occurs after the F7-16
delay and the Run command is removed from the drive. Then the option throws a bUS fault to the drive. When the condition
is removed, the option commands a fault reset and returns control of the drive to the EtherNet/IP network.
Note:
The option will only read parameter F6-01 and F6-14 from the drive during power-up.
Parameter F7-16, Communications Loss Detection Time Delay, will appear when the option is installed.
The setting value of F7-16 is the length of time that the option will delay sending the bUS fault to the drive.
The status LEDs on the option are not affected by the delay time set in F7-16; the LEDs will indicate the bUS condition
immediately.
Note:
The option will only read parameter F7-16 from the drive during power-up.
Description
Cause
Possible Solution
08
09
0C
0E
13
14
15
16
Vendor-specific error
1F
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
61
13 Troubleshooting
Error
Code
(Hex)
20
Description
Cause
Attempted to change to a data value outside the setting Specify a data value within the setting range.
range.
Invalid parameter
Note:
Possible Solution
Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor
data using the MEMOBUS/Modbus message area.
Fault Declared
No Fault
n/a
Status Value
(U6-98/U6-99)
0
Force Fault
EF0
BUS ERROR
BUS ERROR
1100
1101
Duplicate IP Address
BUS ERROR
1102
None
1103
Description
No faults
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores
the new fault status value.
u Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of option.
Table 16 below lists the number of options that can be connected to the drive and the drive ports for connecting those options.
Table 16 Option Installation
Option
PG-B3, PG-X3
PG-F3 <2> <3> , PG-RT3 <2>
AO-A3, DO-A3
<3>
SI-B3 <3> , SI-C3, SI-EN3 <3> , SI-EN3D, SI-EM3 <3> , SI-EP3 <3> , SIES3 <3> , SI-ET3 <3> , SI-N3, SI-P3, SI-S3, SI-T3, SI-W3 <3> , AI-A3 <4> ,
DI-A3 <4>
<1>
<2>
<3>
<4>
62
Port/Connector
CN5-C
2 <1>
CN5-C
CN5-A, B, C
CN5-A
When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-C connector.
Not available for the application with Motor 2 Selection.
Not available with models 4A0930 and 4A1200.
When using AI-A3 and DI-A3 as monitors, the card can be connected to any of CN5-A, CN5-B or CN5-C. The input status of AI-A3 can then be
viewed using U1-21, U1-22, and U1-23, and the input status of DI-A3 can then be viewed using U1-17.
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
14 Specifications
14
Specifications
Table 17 Option Specifications
Item
Specification
Model
SI-EN3D
Supported Messages
IP Address Setting
Communication Speed
Number of Connections
I/O: 2
Explicit: 6
Duplex Mode
Address Startup Mode
Ambient Temperature
Humidity
Storage Temperature
Area of Use
Altitude
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
63
14 Specifications
64
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
65
Revision History
The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
Example:
MANUAL NO. SIEP YAICOM 16
Published in U.S.A.
May 2014
14-5
Date of
publication
66
Date of Publication
Revision
Number
Section
May 2014
1
Revision number
Date of
original publication
Revised Content
First Edition
YASKAWA SIEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Technical Manual
EtherNet/IP
Technical Manual
YASKAWA AMERICA, INC.
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan
Phone: 81-3-5402-4502 Fax: 81-3-5402-4580
http://www.yaskawa.co.jp
9F, Kyobo Securities Bldg., 26-4, Yeouido-dong, Yeongdeungpo-gu, Seoul, 150-737, Korea
Phone: 82-2-784-7844 Fax: 82-2-784-8495
http://www.yaskawa.co.kr
12F, Carlton Bld., No.21 HuangHe Road, HuangPu District, Shanghai 200003, China
Phone: 86-21-5385-2200 Fax: 86-21-5385-3299
http://www.yaskawa.com.cn
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India
Phone: 91-80-4244-1900 Fax: 91-80-4244-1901
http://www.yaskawaindia.in
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may ap ply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
2014 YASKAWA AMERICA, INC. All rights reserved.