Você está na página 1de 29

PJSB. FPS.SPS.

2016
COMMISSIONING OF SMOKE PURGING SYSTEM

Rev.

Rev. Date
Page.

Feb-16
1/2

Project :

Block / Location /Smoke Purging Fan Romm No.:


Inspection / Test Result
Item

Description

Yes

GENERAL VISUAL INSPECTION

Smoke Purging Room in good condition /


Room is Airtight ?

Smoke Purging Fan Control Panel in good condition?

Motorised Damper in good condition

SMOKE PURGING FAN No. .. / .


Brand :
Model :
Kw rating (Low /high speed)
Speed rpm (Low /high speed) :
Class :
Starting Amp (Low / High Speed)

SMOKE PURGING FAN SIMULATION TEST (normal mode)

Basement is designated with two compartment. Each


compartment has two nos fan room and each fan room has
two nos smoke purging system.
Total Smoke Purging Fan: 4 nos fan per compartment
During Normal Ventilation : max 4 nos fan per compartment
or 8 nos fan operate in low speed.
Fan Room No. :
Fan #1 : Timer operation setting :
Fan #2 : Timer operation setting :

Manual local start/stop operation at Control Panel ?

N/A

No

Remarks

PJSB. FPS.SPS. 2016


Rev.
0
Rev. Date
Feb-16
Page.
2/2

COMMISSIONING OF SMOKE PURGING SYSTEM

Item
C

Description

Yes

Inspection / Test Result


N/A
No
Remarks

SMOKE PURGING FAN SIMULATION TEST (normal mode)

Automatic operation by timer switches ?

Interlock position close/open of motorised damper


as per smoke purging fan operation?
Low / High Speed

Fan Rating Capacity ( cfm/fan) : ../ ..


Measured fan capacity (cfm/fan) : /

SMOKE PURGING FAN SIMULATION TEST (Fire mode)


Only either one of the two basement compartment will be
on fired. Maximum 4 nos smoke purging fan should run in
high speed.

Manual local start/stop operation at Control Panel ?

Remote Start/Stop Operation at Control Room ?

Automatic smoke purging fan operation by detectors/fire


alarm system at correct zone compartment ?

Remote Start/Stop Control Panel in Control Room


is functional and in good working order ?

Remark :

Tested by :
Fire Contractor

Verified by :
M&E Consultant

Signature :_____________________ Signature :_________________________

Witnessed by :
Main Contractor

Signature :_____________________

Name

:______________________Name

:_________________________

Name

:_____________________

Date

:_____________________ Date

:_________________________

Date

:_____________________

PJSB. FPS. SP. 2015


COMMISSIONING OF SPRINKLER SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/2

Project :

Block / Location :

Inspection/Test Result
Item

Description

Yes

Pump Room (Visual inspection)

Protection of rotating parts of pumps provided ?

Room clean from debris /dust ?

Sprinkler water tank full of water ?

Any sign of water leakage?

Sprinkler Pumpset

Jockey Pump
Brand :
Model :
Kw:

Starting Amp /

Prime Pump
Brand :
Model :
Kw:

Starting Amp /

Secondary Pump
Brand :
Model :
Kw:

Pump label provided?

Starting Amp/

N/A

No

Remarks

PJSB. FPS. SP. 2015


Rev.
0
Rev. Date
Nov-15
Page.
2/2

COMMISSIONING OF SPRINKLER SYSTEM

Item
B
1

Inspection/Test Result
Yes
N/A
No
Remarks

Description
Sprinkler Pump (Operational Test)
Pressure Gauge Reading :

Bar / Psi
Cut In

Cut Out

Jockey Pump

Prime Pump

Secondary Pump

Jockey pump stop when prime/secondary pump ?

Secondry pump cut in if prime pump fail ?

Sprinkler Control Panel in good condition?

C
1

Others
Check that all isolation valves in open position ?

Flow switch and alarm signal test satisfactory ?

Alarm valve and gong test satisfactory ?

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :______________________ Signature :_________________________

Signature :_____________________

Name

:______________________ Name

:_________________________

Name

:_____________________

Date

:______________________ Date

:_________________________

Date

:_____________________

Signature :_____________________

Name

:_____________________

Date

:_____________________

PJSB. FPS. WR. 2015


COMMISSIONING OF WET RISER SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/2

Project :

Block / Location :

Inspection / Test Result


Item

Description

Yes

Pump Room (Visual inspection)

Protection of rotating parts of pumps provided ?

Room clean from debris /dust ?

Wet Riser Water Tank full of water ?

Any sign of water leakage?

Wet Riser Pumpset

Jockey Pump
Brand :
Model :
Kw:

Starting Amp /

Duty Pump
Brand :
Model :
Kw:

Starting Amp /

Standby Pump
Brand :
Model :
Kw:

Pump label provided ?

Starting Amp/

N/A

No

Remarks

PJSB. FPS. WR. 2015


Rev.
0
Rev. Date
Nov-15
Page.
2/2

COMMISSIONING OF WET RISER SYSTEM

Item
B
1

Description

Yes

Wet Riser Pump (Operational Test)


Pressure Gauge Reading :
Cut In
Jockey Pump

Duty Pump

Standby Pump

Jockey pump stop when duty/standby pump run ?

Standby pump cut in if duty pump fail ?

Wet Riser Control Panel in good condition?

C
1

Others
All isolation valve in open position ?

Landing Valves & Rubber Hose/Cradle in good


condition?

Total Number of landing Valves: Nos

Inspection / Test Result


N/A
No
Remarks

Bar / Psi
Cut Out

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :______________________Signature :_________________________

Signature :_____________________

Name

:______________________ Name

:_________________________

Name

:_____________________

Date

:______________________ Date

:_________________________

Date

:_____________________

PJSB. FPS. HR. 2015


COMMISSIONING OF HOSE REEL SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/2

Project :

Block / Location :

Inspection / Test Result


Item

Description

Yes

Pump Room (Visual inspection)

Protection of rotating parts of pumps provided ?

Room clean from debris /dust ?

Hose reel water tank full of water ?

Any sign of water leakage?

HR Control Panel in good condition?

Hosereel Pumpset

Duty Pump
Brand :
Model :
Kw:

Amp/

Standby Pump
Brand :
Model :
Kw:

Amp /

Check HR pump label is provided?

Record HR Automatic Pressure Switch Setting

Pressure Gauge Reading


HR Pumpset
Duty Pump
Standby Pump

Bar / Psi
Cut In (psi)

Cut Out (psi)

N/A

No

Remarks

PJSB.FPS.HR.2015
Rev.
0
Rev. Date
Nov-15
Page.
2/2

COMMISSIONING OF HOSREEL SYSTEM

Item
C
1

Description
Water throw test
Operate three nos HR assembly at same time
and observed water throw at least 6m to 10m
away ?

D
1

Others
Hose Reel Drum Assembly in good condition ?

Total nos of HR Drum Assebly : ..Nos

Yes

Inspection Result
N/A
No
Remarks

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :____________________ Signature :_________________________

Signature :_____________________

Name

:____________________ Name

:_________________________

Name

:_____________________

Date

:____________________ Date

:_________________________

Date

:_____________________

PJSB. FPS. DR. 2015


COMMISSIONING OF DRY RISER SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/1

Project :

Block / Location :
Inspection / Test Result
Item

Description

Yes

Breeching Inlet

Free from damage ?

Dry Riser Pipe

Hydrostatic pressure test carried out?

Landing Valves & Rubber Hose/Cradle in good

N/A

No

Remarks

condition?
3

Total Number of landing Valves: Nos

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :______________________ Signature :_________________________

Signature :_____________________

Name

Name

:______________________ Name

:_________________________

:_____________________

Date

:______________________ Date

:_________________________

Date

:_____________________

PJSB. FPS. C02. 2015


Rev.
0
Rev. Date
Nov-15
Page.
1/1

COMMISSIONING OF FIXED CO2 SYSTEM

Project :

Block / Location :

Item

Description

Yes

A
1

GENERAL CODITIONS
Co2 Cylinder, CO2 Control Panel, Flashing lights, Alarm Bell
Fire Curtain, Nozzle & Pipeworks in good condition?

CO2 CONTROL PANEL


Brand :

BACKUP BATTERY
Brand :
Capacity :

AH /

Inspection / Test Result


N/A
No
Remarks

Volts

45kg CO2 CYLINDER


Brand:
Quanity :

E
1

SIMULATION TEST
General operation of CO2 panel in working order?

LED and Fault Test function?

Zone 1 alarm test ( smoke detector) function ?

Zone 2 alarm test (heat detector) function?

Is simulated discharge test working (Automatic and Manul Mode) ?


a) Fire curtain drop ?
b) Signal alarm to trigger actuator valve in ..second ?
c) Flashing light working ?

Alarm signal link to Fire Alarm Panel ?

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :_______________ Signature :_________________________

Signature :_____________________

Name

Name

:_______________ Name

:_________________________
CO2 COMM 18/29

:_____________________

Date

:_______________ Date

:_________________________

CO2 COMM 19/29

Date

:_____________________

PJSB. FPS. FA. 2015


Rev.
0
Rev. Date
Nov-15
Page.
1/1

COMMISSIONING OF FIRE ALARM SYSTEM

Project :

Block / Location :

Item

Description

Yes /Ok

FIRE ALARM PANEL


Brand :
No. Zones :
No. Alarm Bell :
No. of break glass
No. of smoke detector:
No. of heat detecor :

BACKUP BATTERY
Brand :
Capacity :

AH /

Inspection / Test Result


N/A
No/Fail
Remarks

Volts

SIMULATION TEST
a) LED and Fault Test ?
b) Main supply fail ?
c) Activation of any smoke detector ?
d) Simulation of any breakglass ?
e) Simulation of any sprinkler flow switch ?
f) Lift homing ?
g) Others ?

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :_______________ Signature :_________________________

Signature :_____________________

Name

Name

:_______________ Name

:_________________________
FA COMM 20/29

:_____________________

Date

:_______________ Date

:_________________________

FA COMM 21/29

Date

:_____________________

PJSB. FPS. FI. 2015


Rev.
0
Rev. Date
Nov-15
Page.
1/1

COMMISSIONING OF FIREMEN INTERCOM SYSTEM

Project :

Block / Location :

Item

Description

Yes /Ok

FIREMEN INTERCOM PANEL


Brand :
No. Zones :
No. of remote handset.

BACKUP BATTERY
Brand :
Capacity :

AH /

Inspection / Test Result


N/A
No/Fail
Remarks

Volts

SIMULATION TEST
a) LED and Fault Test ?
b) Main supply fail ?
c) Activation of any remote handset ?
d) Two /three way communication ?

Remark :

Tested by :

Verified by :

Witnessed by :

Fire Contractor

M&E Consultant

Main Contractor

Signature :_______________ Signature :_________________________

Signature :_____________________

Name

:_______________ Name

:_________________________

Name

:_____________________

Date

:_______________ Date

:_________________________

Date

:_____________________

FA COMM 22/29

PJSB. PS.CWS. 2015


COMMISSIONING OF INTERNAL COLD WATER SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/2

Project :

Block / Location :
Inspection / Test Result
Item

Description

Yes

Transfer Pump Room (Visual inspection)

Protection of rotating parts of pumps provided ?

Room clean from debris /dust ?

Suction Cold Water Tank full of water ?

Any sign of water leakage?

Cold Water Transfer Pumpset

Pressure Gauge Reading :

Duty Pump

Bar / Psi

Brand :
Model :
Kw:
3

Starting Amp /

Standby Pump
Brand :
Model :
Kw:

Starting Amp /

Pump label provided?

Auomatic simulation test functioning


a) Duty pump shall cut in when low water level in
roof tank reach pre-determined low level?
b) Duty pump shall cut off when water level in
roof tank reach top water pre-determined top level ?
c) Duty pump shall not run if water level in suction
is low?

N/A

No

Remarks

PJSB.PS.CWS.2015
Rev.
0
Rev. Date
Nov-15
Page.
2/2

COMMISSIONING OF INTERNAL COLD WATER SYSTEM

Item

Description

Yes

C
1

VFD Booster Pumpset


Duty Pump
Brand :
Model :
Kw:
Starting Amp /

Standby Pump
Brand :
Model :
Kw:

Inspection / Test Result


N/A
No
Remarks

Starting Amp /

Pressure Switch Setting & Operation


Cut In
Duty Pump

Standby Pump

D
1

Others
Roof Tanks in good condition / Water leakage?

Distribution/Riser/Dropper Cold Water Pipe: any


sign of leakage

Cut Out

Remark :

Tested by :

Verified by :

Witnessed by :

Plumber Contractor

M&E Consultant

Main Contractor

Signature :_____________________ Signature :_________________________

Signature :_____________________

Name

:______________________Name

:_________________________

Name

:_____________________

Date

:_____________________ Date

:_________________________

Date

:_____________________

PJSB. PS.SA. 2015


COMMISSIONING OF INTERNAL SANITARY SYSTEM

Rev.

Rev. Date
Page.

Nov-15
1/1

Project :

Block / Location :
Inspection / Test Result
Item

Description

Yes

Connection to Fixture (Visual inspection)

Full Water flushing and check any sign of

N/A

No

Remarks

water leakage?
2

Water flow test and no blockage?

Floor trap, bottle trap & gully trap condition in


good condition ?

Intermediate Inspection chamber condition?

Remark :

Tested by :

Verified by :

Witnessed by :

Plumber Contractor

M&E Consultant

Main Contractor

Signature :_____________________ Signature :_________________________

Signature :_____________________

Name

Name

:______________________Name

:_________________________

:_____________________

Date

:_____________________ Date

:_________________________

Date

:_____________________

PJSB. HVAC.ASU. 2015


COMMISSIONING OF AIRCOND SPLIT UNIT SYSTEM

Rev.

Rev. Date

Nov-15

Page.

1/1

Project :

Block / Location /Room :


Inspection / Test Result
Item

Description

Yes

INDOOR UNIT

Indooor Unit in good condition ?

Room thermostat is working?

Room temprature: Deg C.

Condenstate drain pipe no blocakge?

OUDOOR UNITS

In good condition and well ventilated?

A/C refrigerant pipe well insulated ?

N/A

No

Remarks

Remark :

Tested by :
Aircond Contractor

Verified by :
M&E Consultant

Witnessed by :
Main Contractor / Client

Signature :_____________________ Signature :_________________________

Signature :_____________________

Name

Name

:______________________Name

:_________________________

:_____________________

Date

:_____________________ Date

:_________________________

Date

:_____________________

Você também pode gostar