Introduction
Contents
Introduction .........................................2
Legend................................................2
Nomenclature .....................................2
General Features................................3
Component Features ..........................3
Options ...............................................4
Application Flexibility ..........................5
Physical & Electrical Data...................6
Nominal Capacity Ratings .................6
Air Flow Correction Factor ..................7
Legend
The following legends are used throughout
this manual:
AFR ...... Air Flow Rate
BEP ...... Baked Enamel Paint
cfm ....... Cubic feet per minute
dB ........ Decibels
EADB .... Entering Air Dry Bulb
EAWB .... Entering Air Wet Bulb
ET ......... Evaporating Temperature
EWT ...... Entering Water Temperature
ESP ...... External Static Pressure
Ft .......... Total Capacity Factor
ftwg ...... Feet fo Water Gauge
Fs ........ Sensible Capacity Factor
GPM .... Gallons per minute
Hz ........ Hertz
inwg ...... Inch of Water Gauge
kW ........ Kilowatts
kg ......... Kilograms
kPa ...... Kilo Pascals
LADB .... Leaving Air Dry Bulb
LAWB ... Leaving Air Wet Bulb
lbs .........
l/s ..........
MBh ......
NC ........
OD ........
Ph .........
Pa .........
SC ........
SCCF ....
SPL .......
TC .........
TCCF ....
TR ........
USgpm ..
V ...........
WFR .....
WTR .....
WPD .....
Nomenclature
F C U - DCD x - 1 2 / 40 / W G
Fan Coil Unit
G=Galvanised Finish
F=Painted FInish
District Cooling
Direct Drive
C:
P:
E:
F:
Fan / Motor
Fan Coil Unit for District Cooling use centrifugal double inlet
double width low noise fans direct driven by single phase,
3-speed permanent split capacitor motor. These motors have
integral thermal protection, low temperature rise, are highly
efficient, have high power factor and operate almost noiselessly
with permanent lubricated sleeve bearings.
Airports
Hi-rise Buildings
All motors used in Fan Coil Units for District Cooling are
inherently protected by means of thermal cut-out embedded
in the winding. This thermal cut-out is calibrated to trip out
when the winding reaches a pre determined temperature.
The thermal cut out will automatically reset when the
temperature returns to a safe limit.
Features:
High efficiency coil with high efficiency wavy corrugated fins.
Casing
Component Features
Coils
Drain Pan
The standard options available for Fan Coil Units for District
Cooling includes :
Electric Heaters
(specify option FEH)
Controls
Application
Options available :
1. Auxiliary drip lip supplied loose to be fitted on the edge of the
drain pan under the valves. Specify option ADP.
Capacity
Maximum capacity of the electric heater is determined by
the air capacity of the particular model. Table 1 shows the
2 variations available for each model in the Hi - Static fan
coil units.
Contactors and Controls
Contactors are not included as standard and must be
field supplied and installed.
Figure 1
Heater Elements
U shape finned tubular heating element constructed
from high quality 80/20 nickel chrome resistance wire
connected to terminal pins and centered in a metal tube
with galvanized steel fin.
The elements are isolated from the casing. Separate
power source is required for the heaters.
8QLW6L]H
1XPEHURI+HDWHU(OHPHQWV
9DULDQW
9DULDQW
[
[
[
[
[
[[
[
[
[
[
[
[
[
[
[
[
Table 1
Figure 2
3. Stainless steel drain pan insulated from outside with 4mm thick
polyethylene foam insulation. Specify option SDP.
4. Double skin drain pan with stainless steel internal skin and
heavy gauge galvanized steel outer skin sandwiched between
a fibre glass insulation. Specify option PSID.
1. DCDC
Discharge Plenum
(Specify option GDP)
A discharge plenum for free standing DCDF models only is
available. Option BEP must be ordered with this option. Option
GDP includes, in addition, a double deflection supply grille and
a single deflection return air grille, powder coated in matching
color. Colors available ivory white (RAL 7032) or light grey
(RAL 8019). Specify with option code.
Application Flexibility
2. DCDP
Ceiling suspended for concealed applications, includes a
factory installed plenum. The plenum is lined with 1/2 glass
fibre insulation. Units are supplied with 1 cleanable filter as
standard.
3. DCDE
Ceiling suspended, exposed type includes basic DCDC, plus a
cabinet with removable access panels lined with 1/2 fibre glass
insulation. Units are supplied with 1 cleanable filter. Units are
with electrostatically applied polyster powder coat and can be
supplied with supply and return air grilles on request.
4. DCDF
Floor mounted, vertical supply with 1 cleanable filter. Units
can be supplied with supply and return grill on request with
electrostatic polyster powder coat, oven-baked. Units have
a removable access panel to provide complete access to coil
and motor blower section. All units can be supplied for either
free or ducted air delivery.
SUPPLY AIR
SUPPLY
GRILL
DCDC
SUPPLY
GRILL
DCDE
RETURN AIR
FREE SUPPLY
FREE RETURN
(GRILLS OPTIONAL)
FREE
RETURN
DCDP
SUPPLY
GRILL
FREE
RETURN
DUCTED
SUPPLY
GRILL
SUPPLY
GRILL
RETURN AIR
FREE
RETURN
RETURN AIR
DCDE
RETURN AIR
Figure 3
DCDF
)LQ/HQJWK
)DFH$UHD
6SHHG
+] +]
0D[LPXP$PSV
0RWRU
7\SH
&RGH
4XDQWLW\
7\SH
6L]H
4XDQWLW\
7RWDO3RZHU,QSXW
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
6SHHG
)DQ
FIP
OV
LQFK
PP
LQFK
PP
IW
P
:DWWV
:DWWV
&RSSHUWXEHVPHFKDQLFDOO\ERQGHGWR+L(IILFLHQF\ZDY\FRUUXJDWHG$OXPLQLXP)LQV
'RXEOH,QOHW'RXEOH:LGWK&HQWULIXJDO)RUZDUG&XUYH'LUHFW'ULYH
93K+]6SHHG(OHFWULF0RWRUZLWK3HUPDQHQW6SOLW&DSDFLWRU
Table 2
6L]H
5RZV
5RZV
5RZV
1RPLQDO
:DWHU
:DWHU
:DWHU
:DWHU
:DWHU
:DWHU
$LUIORZ
7RWDO 6HQVLEOH
7RWDO 6HQVLEOH
7RWDO 6HQVLEOH
)ORZ 3UHVVXUH
)ORZ 3UHVVXUH
)ORZ
3UHVVXUH
5DWH &DSDFLW\ &DSDFLW\
&DSDFLW\ &DSDFLW\
&DSDFLW\ &DSDFLW\
5DWH
'URS
5DWH
'URS
5DWH
'URS
FIP
OV
0%K
N:
0%K
N:
JSP
OV
IWZJ
N3D
0%K
N:
0%K
N:
JSP
OV
IWZJ
N3D
0%K
N:
0%K
N:
JSP
OV
IWZJ
N3D
Table 3
Notes:
Chilled water capacity ratings are based on nominal air flow rate; air entering temperature DB/WB 78/65oF (25.6/18.3oC), 42oF
(5.5oC) entering chilled water temperature and 16oF (8.9oC) water temperature rise.
For conditions other than rated, use SKM FCU Computer Selection Software.
$FWXDO$LU
)ORZ1RP
$LU)ORZ
7RWDO&RROLQJ
&DSDFLW\
)W
6HQVLEOH
&DSDFLW\
&RROLQJRU
+HDWLQJ)V
1.1
1.0
TOTAL CAPACITY
0.9
0.8
0.7
SENSIBLE CAPACITY
0.6
0.5
0.4
0.3
30
40
50
60
70
80
90
110
100
120
130
140
150
Table 4
Figure 4
(OHYDWLRQ
0.96
SENSIBLE CAPACITY
IW
TOTAL CAPACITY
0.92
0.88
P
7RWDO
&DSDFLW\
6HQVLEOH
&DSDFLW\
Table 5
0.84
0.80
0
1000
2000
3000
4000
5000
6000 Ft.
305
610
915
1219
1525
1829 Mtr.
ELEVATION
Figure 5
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
5RZV
5RZV
.
.
.
.
$
.
.
5RZV
.
.
$
.
.
.
.
$
Table 6
Casing Attenuation
'&'3'&'('&')
'&'&
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
5RZV
.
.
5RZV
.
.
$
.
.
5RZV
.
.
$
.
.
.
.
$
Table 7
Casing Attenuation
'&'3'&'('&')
'&'&
1RP
$)5
5RZV
6SHHG
'&'&
+LJK
0HGLXP
/RZ
5RZV
([WHUQDO6WDWLF3UHVVXUH
5RZV
LQZJ
3D
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
Table 8
10
1RP
$)5
6SHHG
'&'3
'&'(
'&')
+LJK
0HGLXP
/RZ
5RZV
5RZV
([WHUQDO6WDWLF3UHVVXUH
5RZV
LQZJ
3D
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
Table 9
11
6L]H
FIP
OV
5RZV
6SHHG
'&'&
+LJK
0HGLXP
/RZ
LQZJ
3D
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
5RZV
([WHUQDO6WDWLF3UHVVXUH
5RZV
Table 10
12
'&'3
'&'(
'&')
+LJK
0HGLXP
/RZ
6L]H
FIP
OV
5RZV
LQZJ
3D
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
FIP
OV
5RZV
5RZV
([WHUQDO6WDWLF3UHVVXUH
Table 11
13
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
$LU)ORZ
:DWHU)ORZ
:DWHU
5DWH
5DWH
3UHVVXUH'URS
JSP
OV
IWZJ
N3D
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
5DWH
3UHVVXUH'URS
JSP
OV
Note :
Table 12 data is based on 78/65oF (25.6/18.3oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
14
IWZJ
N3D
Table 12
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
$LU)ORZ
5DWH
3UHVVXUH'URS
5DWH
JSP
OV
IWZJ
N3D
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
3UHVVXUH'URS
5DWH
JSP
OV
Note :
Table 13 data is based on 76/63oF (24.4/17.2oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
IWZJ
N3D
Table 13
15
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
$LU)ORZ
:DWHU)ORZ
:DWHU
5DWH
5DWH
3UHVVXUH'URS
JSP
OV
IWZJ
N3D
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU
:DWHU)ORZ
3UHVVXUH'URS
5DWH
JSP
OV
Note :
Table 14 data is based on 78/65oF (25.6/18.3oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
16
IWZJ
N3D
Table 14
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
$LU)ORZ
5DWH
3UHVVXUH'URS
5DWH
JSP
OV
IWZJ
N3D
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
3UHVVXUH'URS
5DWH
JSP
OV
Note :
Table 15 data is based on 76/63oF (24.4/17.2oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
IWZJ
N3D
Table 15
17
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
$LU)ORZ
5DWH
3UHVVXUH'URS
5DWH
JSP
OV
IWZJ
N3D
FIP
7RWDO&DSDFLW\
OV
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
5DWH
3UHVVXUH'URS
JSP
OV
Note :
Table 16 data is based on 78/65oF (25.6/18.3oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
18
IWZJ
N3D
Table 16
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
+LJK
0HGLXP
/RZ
(63
LQZJ
3D
$LU)ORZ
5DWH
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
+]
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
$LU)ORZ
5DWH
3UHVVXUH'URS
5DWH
JSP
OV
IWZJ
N3D
FIP
OV
7RWDO&DSDFLW\
%WXK
N:
6HQVLEOH
&DSDFLW\
%WXK
N:
:DWHU)ORZ
:DWHU
3UHVVXUH'URS
5DWH
JSP
OV
Note :
Table 17 data is based on 76/63oF (24.4/17.2oC) air on-coil DBT/WBT and 42/58oF (5.5/14.4oC) entering/leaving water temperature.
IWZJ
N3D
Table 17
19
**
Figure 6
**
Figure 7
Notes :
1. The max amps as tabulated (refer page 6, table 2) are max. total amps per unit at worst condition.
2. Full load inductive current (amps.) rating of 3-speed switch must be greater than the maximum amps.
3. Maximum allowable fuse rating for any unit size must not exceed 15 amps/250 volts AC.
4. A separate power feeder is required for units supplied with optional factory installed electric heaters.
5. The units are suitable for electrical system where voltage supplied to the terminals is not below or above
10% of the listed voltage.
20
The correct unit with correct coil size is obtained only when
required cfm at defined speed; i.e. High, Medium or Low to
meet sensible load of the space is matched to the correct coil
providing the required total and sensible cooling or outlet
temperatures at given flow rate and design temperature
rise with the unit operating at functional sound levels.To
achieve this the engineer or designer must not only check
aesthetic needs but also space limitations, psychrometric
feasibility, circulation and ventilation, room acoustical effect,
control system, piping accesses including overall chilled
water circuits and effect of diversity on same.
Selection Procedure
Machine Weight
0RGHO
1XPEHU
RI5RZV
5
'&'&
5
5
5
'&'3
5
5
5
'&')
5
5
5
'&'(
5
5
0DFKLQH
:HLJKW
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
OEV
NJ
8QLW6L]H
Table 18
21
UNIT SIZE 12 - 24
T ERM IN AL
C ONN EC TIO N
TER MIN AL
C ON N EC TIO N
4x5/8 [ 16 ]
MT G. H OL ES
W IT H R U BBE R
GR O MMET S
2
[51]
2
[5 1]
*[2299 ]
D RAI N
3/4
4
1
3
A
10
[76]
[25]
[25]
*[2299 ]
D R AIN
3/4
10
[76]
[254]
[254 ]
B
L
*11.2 5
1.5 4
[39 ]
0.75
0.75
[19]
[19]
AIR VENT
[25]
[19]
0.75
[286 ]
R IG H T H AND U N IT O PP OSITE
LEG END
1
SU PPLY FA N
FAN MO TOR
C OOLI N G C OI L
D R AIN PA N
E = 1.50 [38] FO R 3 R
2.24 " [57] FO R 4 R
3.74 " [95] FO R 6 R
INCH
MM
INCH
MM
INCH
MM
INCH
MM
INCH
MM
INCH
MM
INCH
MM
INCH
MM
06
20
508
33
838
21.5
546
12
305
15
381
26.7 5
6 79
12
305
9.6
2 44
08
24
610
37
940
25.5
648
12
305
15
381
26.7 5
6 79
12
305
9.6
2 44
10
24
610
37
940
25.5
648
15
381
17.2 5
438
29
7 37
13 .5
343
1 1.25
2 86
12
36
914
49
1245
37.5
952
12
305
15
381
26.7 5
6 79
12
305
9.6
2 44
15
42
1067
55
1397
43.5
1105
12
305
15
381
26.7 5
6 79
12
305
9.6
2 44
18
42
1067
55
1397
43.5
1105
15
381
17.2 5
438
29
7 37
13 .5
343
1 1.25
2 86
21
48
1219
61
1549
49.5
1257
15
381
17.2 5
438
29
7 37
13 .5
343
1 1.25
2 86
24
54
1372
67
1702
55.5
1410
15
381
17.2 5
438
29
7 37
13 .5
343
1 1.25
2 86
Table 19
22
UNIT SIZE 12 - 24
4-5/8 [ 16 ]
M TG.HOLES
W IT H RU BBER
TERMINA L
CONNEC TION
GROMM ETS
TERMINAL
CONNEC TION
2
[ 51 ]
DRAIN
[51 ]
DRAIN
3/ 4 [ 19 ]
3/4 [19 ]
1.5
8.5
1.5
[216 ]
[ 38 ]
[38 ]
8.5
[ 216]
B
*11.2 5
[ 286]
N
E
[ 19 ]
[ 19 ]
A IR VENT
[25 ]
0. 75
0. 75
[25 ]
D1
FILTER
REMOVAL
CO I L I N /OUT
0.5 9 [19 ] F O R SI ZES 06- 10
0.8 7 [22 ] F O R SI ZES 12- 24
1.5
1
LEGE N D
[ 25 ]
INSULATED R. A. PLENU M
SUPPLY FAN
FAN MOTOR
FIL TE R
D xA
COOLING COIL
ACCESS PANEL
6
5
4
5
[38 ]
FILTER
REMOVAL
2.5
E = 1.50 [ 38 ] FOR 3R
2.24 [ 57 ] FO R 4R
3.74 [ 95 ] FOR 6R
D xA
5
FILTER
REMOVAL
[63 ]
NO T E:
BOTTOM RETURN-OPTIONAL
* AD D 1.7 5 [44 ] F O R 6 R OW
(DUCTED )
(DUC TED )
23
584
33
838
D1
21.5
16.42 417
546
12
305 12.48
317
15
381
15
381
16.42 417
12
305
440
18.67 474
13.5
343
12
305
9.6
DC DP
K
UN IT
DIMEN SIONS FOR
INC H MM
MODEL
3R / 4R
244
244
06
08
11.25 286
12
15
L
INC H MM
INC H MM INC H MM
67
1.54
39
4.61 117
3.50
89
6R
2.64
67
1.54
39
3R / 4R + HEATER
22
2.64
08
27
686
37
940
25.5
648
12
305 12.48
317
10
27
686
37
940
25.5
648
14.5
368 14.84
377 17.32
12
39
991
49
1245
37.5
952
12
305 12.48
317
15
381
16.42 417
12
305
9.6
244
6R + H EATER
4.61 117
3.50
89
15
45
1143
55
1397
43.5 1105
12
305 12.48
317
15
381
16.42 417
12
305
9.6
244
3R / 4R
0.79
20
1.54
39
18
45
1143
55
1397
43.5 1105
14.5
368 14.84
377 17.32
440
18.67 474
13.5
343
11.25 286
3R / 4R + HEATER
1.82
46
2.56
65
21
51
1295
61
1549
49.5 1257
14.5
368 14.84
377 17.32
440
18.67 474
13.5
343
11.25 286
6R
0.79
20
1.54
39
6R + H EATER
2.88
73
3.63
92
9.6
10
18
21
24
24
57
1448
67
1702
55.5 1410
14.5
368 14.84
377 17.32
440
18.67 474
13.5
343
11.25 286
Table 20
23
3
[76]
8
[203]
5.75
[146]
LEGEND
1
SUPPLY FAN
FAN MOTOR
COOLING COIL
ACCESS PANEL
FILTER
8
[203]
JxG
FILTER
REMOVAL
4x5/8 [16]
MTG.HOLES
WITH RUBBER
GROMMETS
*L
*K
1
[25]
REAR RETURN-OPTIONAL
(DUCTED)
0.75
[19]
3
[76]
AIR VENT
1
[25]
E
3
[76]
CABLE
ENTRY
COIL IN/OUT
0.59 [15] FOR SIZES06-10
0.87 [22] FOR SIZES12-24
3
[76]
FREE RETURN-STANDARD
2.5
[64]
DRAIN
3/4 [32]
1
[25]
FILTER
REMOVAL
1.5
[38]
1
[25]
1.75
[44]
DCDE
E
A
B
C
D
F
UNIT
SIZE INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM
*K
*L
06
20
508
36
914 24.5
622
12
305
7.5
190
15
381
21
533
12
12
305
9.6
244
08
24
610
40
1016 28.5
724
12
305
7.5
190
15
381
25
635
12
12
305
9.6
244
10
24
610
40
1016 28.5
724
15
381
7.5
190
18.5
470
25
635
16
406
34
864
31
787
13.5
12
36
914
52
12
305
7.5
190
15
381
37
940
12
12
305
9.6
244
15
42
1067
58
12
305
7.5
190
15
381
43
1092
12
12
305
9.6
244
18
42
1067
58
15
381
7.5
190
18.5
470
43
1092
16
406
34
864
31
787
13.5
21
48
1219
64
15
381
7.5
190
18.5
470
49
1245
16
406
34
864
31
787
13.5
24
54
1372
70
15
381
7.5
190
18.5
470
55
1397
16
406
34
864
31
787
13.5
Table 21
24
HO L ES F OR
PIPES
3
[76]
[76]
L EG EN D
COOLING COI L
A CC ESS PANEL
F ILTER
K
[1
]
52
8
[51]
COIL IN/OU T
D
[203]
S U PPLY F AN
FAN MOTOR
O PTION PL ENU M
WI TH SUPPLY GR I LL
8
[203]
K
1
2
0 .59 [15] FO R SI Z ES 06 - 10
0 .87 [22] FO R SI Z ES 12 - 24
[102 ]
[171]
6.75
A IR VEN T
HOLES
1 1/4 [32 ]
H
FOR COIL
IN & O U T
T ERMI N AL
BOX
[76]
3
1
[25]
FIL T ER
RE M O VAL
2
[51]
10
[254]
DR AIN
3 /4 [19 ]
CABLE ENTR Y
O PTION
FL AN GE
LE FT H AND U N IT SH OW N
E = 5 [127] FO R 3R
4.5 [114] F O R 4R
3.5 [89] FOR 6R
N OT E
FO R BU ILT - IN PACKAGED VA L VES ADD 4 [102 ] IN
DIMENSIONS 'B ', 'C ' & 2 [51] IN D IM EN SIO N 'K'.
DCDF
A
UNIT
SIZE INCH MM
INCH
MM
INCH
MM
INCH MM
INCH
MM
INCH
MM
INCH
MM
INCH
MM
INCH MM
06
26
660
30
762
23.5
597
152
18
457
26
660
30
762
16
406
51
08
30
762
34
864
27.5
698
152
18
457
30
762
30
762
16
406
51
10
30
762
34
864
27.5
698
152
21
533
30
762
38.5
978
19.5
495
51
12
42
1067
46
1168
39.5 1003
152
18
457
42
1067
30
762
16
406
51
15
48
1219
52
1321
45.5 1156
152
18
457
48
1219
30
762
16
406
51
18
48
1219
52
1321
45.5 1156
152
21
533
48
1219
38.5
978
19.5
495
51
21
54
1372
58
1473
51.5 1308
152
21
533
54
1372
38.5
978
19.5
495
51
24
60
1524
64
1626
57.5 1460
152
21
533
60
1524
38.5
978
19.5
495
51
Table 22
25
Fan
Fan shall be double inlet, double width, direct driven with
centrifugal type wheel. Fan wheel shall be with multi forward
curved blades. Fan shall be applicable for operation up to
0.4 W.G. external static pressure. Fan shall be statically &
dynamically balanced. Fan housing and wheel shall be made of
galvanized steel sheet.
Motor
Motor shall be single phase, 3-speed permanent split capacitor
type, 220-240V/1 Ph/50/60Hz, highly efficient with integral
thermal protection (thermal cut-out embedded in the winding).
Motor shall have high power factor. Motor shall be with permanent
lubricated sleeve bearings.
Coil
Coil shall be constructed of 5/16 O.D. seamless copper tubes
arranged in a staggered form mechanically bonded to high
efficiency wavy corrugated aluminum fins. Copper fins or PreCoated Aluminum fins shall be provided if so specified.
Fins spacing shall be 12 fpi. For chilled water, shall be provided
as indicated on the equipment schedule. All coils shall be
provided with manual air vent, automatic air vent shall be
provided if so specified. Coil circuiting shall be counter flow.
(Direction of coil water flow shall be counter to direction of unit
26
Drain Pan
Drain pan shall be constructed from 1 mm thick zinc coated steel
sheets, shall be painted, irrespective of the type of finish for unit
casing, and insulated from outside with 4 mm thick polyethylene
foam insulation. Drain pan shall be constructed from Stainless
steel if so specified. Drain pan shall be extended to include
coil, headers and U - bends. The bottom of drain pan shall be
plane and drain connection shall be O.D. sweat copper pipe.
Auxiliary drip lip shall be supplied loose for field installation if so
specified.
Filter
Air filter shall be 1 thick washable aluminum media with Average
dust arrestance 54 % based on ASHRAE test # 52/76. 1 thick
washable or disposable synthetic media shall be provided if so
specified. Air filter is standard for all SKM Fan Coil Units for
District Cooling with exception of the DCDC units. Filter removal
shall be as shown on attached drawings.
Options
Following shall be provided if so specified :
Single deflection return air grill and double deflection supply
air grill for exposed units.
Discharge plenum for free standing units (Floor mounted
units).
Double skin drain pan.
Double skin casing for locations having a high temperature
difference between supply air temperature and surrounding
environment of the unit.
Valve Packages
Valve Packages shall be factory installed or field installed by
customer if so specified. As indicated on the equipment schedule,
Valve Packages shall consist of various combinations of gate or
stop valves, double regulating valves, 2-way motorized valves
and 3-way motorized valves.
Thermostat
Thermostat shall be field installed by customer, wall mounted
and decorative type. Cooling and / or heating thermostat with
3-speed switch, with H/C change over shall be provided as
indicated on the equipment schedule.
27