Introduction
TheIEC60364standarddefinesanumberofinstallationmethodswhichrepresentthevariousinstallation
conditions.Bythefollowingicons,theyaredividedintogroupsanddefinedbythelettersAtoGwhichdetermine
howtoreadthetableofthecurrentcarryingcapacitiesinconductors.

MethodA
A1Insulatedsinglecoreconductorsinconduitinathermallyinsulatedwall
A2Multicorecableinconduitinathermallyinsulatedwall
Thismethodalsoappliestosinglecoreormulticorecablesinstalleddirectlyina
thermallyinsulatedwall(usemethodsA1andA2respectively),conductorsinstalledin
mouldings,architravesandwindowframes.

MethodB
B1Insulatedsinglecoreconductorsinconduitonawall
B2Multicorecableinconduitonawall
Thismethodapplieswhenaconduitisinstalledinsideawall,againstawallorspaced
lessthan0.3xD(overalldiameterofthecable)fromthewall.MethodBalsoapplies
forcablesinstalledintrunking/cableductagainstawallorsuspendedfromawalland
cablesinstalledinbuildingcavities.

http://www.openelectrical.org/wiki/index.php?title=Cable_Reference_Installation_Methods

1/3

1/14/2017

CableReferenceInstallationMethodsOpenElectrical

MethodC
CSinglecoreormulticorecableonawoodenwall
Thismethodalsoappliestocablesfixeddirectlytowallsorceilings,suspendedfrom
ceilings,installedonunperforatedcabletrays(runhorizontallyorvertically)andinstalled
directlyinamasonrywall(withthermalresistivitylessthan2K.m/W).

MethodD
D1Multicoreorsinglecorecablesinstalledinconduitburiedintheground
D2Multicoreorsinglecorecablesburieddirectlyintheground

MethodE
EMulticorecableinfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleatsprovided
thatthecableisspacedmorethan0.3xD(overalldiameterofthecable)fromthewall.Note
thatcablesinstalledonunperforatedcabletraysareclassifiedunderMethodC.

MethodF
FSinglecorecablestouchinginfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleatsprovidedthatthecableis
spacedmorethan0.3xD(overalldiameterofthecable)fromthewall.Notethatcablesinstalledonunperforated
cabletraysareclassifiedunderMethodC.
http://www.openelectrical.org/wiki/index.php?title=Cable_Reference_Installation_Methods

2/3

1/14/2017

CableReferenceInstallationMethodsOpenElectrical

MethodG
GSinglecorecableslaidflatandspacedinfreeair
Thismethodappliestocablesinstalledoncableladder,perforatedcabletrayorcleats
providedthatthecableisspacedmorethan0.3xD(overalldiameterofthecable)from
thewallandwithatleast1xDspacingsbetweencables.Notethatcablesinstalledon
unperforatedcabletraysareclassifiedunderMethodC.Thismethodalsoappliesto
cablesinstalledinairsupportedbyinsulators.

Relatedtopics:
BacktoLowVoltageCableDataReference
Retrievedfrom"http://www.openelectrical.org/wiki/index.php?title=Cable_Reference_Installation_Methods"
Category:Cables
Thispagewaslastmodifiedon24April2013,at11:14.