Escolar Documentos
Profissional Documentos
Cultura Documentos
Service Manual
Model 6000 Series Chiller
Information is reserved for trained, qualified technical personnel. It includes schematics & wiring diagrams.
Any repair or service to a unit is to be performed by a certified technician ONLY.
Attempting repairs outlined in this guide may result in voiding your warranty
Table of Contents
SECTION 1.
SECTION 2.
SECTION 3.
SECTION 4.
SECTION 5.
SECTION 6.
SECTION 7.
SECTION 8.
SECTION 9.
TROUBLESHOOTING GUIDE
REPLACING MAIN CONTROL BOARD
CALIBRATION
TESTING REFRIGERATION IN 6X05
QUICK VALVE SEAT CHECK
MAIN BOARD CONTINUITY CHART
SPARE PARTS LIST
SCHEMATICS
WIRING DIAGRAMS
Press and release the power ON button, then switch the circuit breaker off.
Press and hold the Set/Menu button while switching the circuit breaker on.
The controller will display "DEF" and go to the standby mode.
Your set temperature and other settings will have to be reset.
Problem
#1
Display does not light up
Corrective Action
1) Check that breaker CB1 is on. Check for proper line voltage.
2) Using schematic on page 8, check main board +5V at voltage regulator RG1.
a)
b)
c)
If no voltage, verify that the AC input voltage is present at SP9 and SP12.
If the AC voltage is normal, check the fuses and transformer for continuity. Repair
any open circuit.
If there is no AC voltage present at SP9 and SP12, trace the wires back to the
circuit breaker and check for continuity. Replace or repair the wire that is open.
3) Check main board copper traces for open circuits, use the Main Board CONTINUITY
CHART on pg. 6.
4) If problem still exists, replace the main board, then replace display board.
5) If the centigrade light is on, remove the wire from CN4 on the main circuit board, the
display should light up. Removed wires should be replaced or repaired.
#2
Flashes HI-L high limit
#3
Reads E-5F sensor failure
1) Using schematic on page 8, examine the 4 wires from the temperature probe at their
solder terminals on the main circuit board. The 2 red and 2 black wires should be
securely soldered. Solder any loose or torn wires.
2) Check sensor voltages and resistances shown on schematic.
3) Check main board, -5V at voltage regulator RG2.
4) If voltages and resistances are OK, replace main circuit board.
#4
Continuously pumps
#5
Compressor continuously
runs
#6
Readout not within
0.5C
#7
Unit is not pumping
1) Using schematic on page 9, unsolder R10. If unit still pumps, ALT2 is shorted.
2) If pins 4 and 6 on U8 is less than 50K ohms, U8 is shorted.
1) Using schematic on page 9, unsolder R14. If compressor and fan still run, ALT3 is
shorted.
2) If pins 4 and 6 on U10 is less than 40 K ohms, U10 is shorted.
1) Using schematic on page 8, check that RTD probe is within 0.19 ohms. (Subtract
resistance of probe wires and your test leads from reading.)
2) Using schematic on page 8, check R5. It should be between 199.8 and 200.2 ohms, if
not, then there is no field calibration. Replace main board.
1) The fluid in the evaporator may be frozen. The evaporator is considerably colder than
the fluid temperature. For temperatures below 15C, use a fluid mixture with a suitable
temperature range for the set point desired. Refer to the Operators Manual, section 2.2
for recommended fluid mixtures.
2) Using schematic on page 8, Check voltage across SP5 and SP6 on main board. If no
line voltage measured, replace main board.
3) Using schematic on page 8, Check voltage across SP5 and SP6 on main board. If line
voltage is measured low, verify pump motor is running. Check fluid level in entire
system to be sure the pump is receiving fluid. Check for blockage within the circulating
system.
4) The coupling key between the motor shaft and pump head is a sacrificial type designed
to prevent damage if the fluid freezes. If the coupling key is worn, replace it.
#8
Unit will not turn on/off
#9
Set temperature cant be
changed
#10
The circuit breaker trips
b) If the on/off switch does not works, the display is defective and needs to be replaced.
1) Perform a default as described in section 3.7 in the operators manual to reset the
microprocessor.
2) The rotary encoder on the display is defective. Replace the display board.
1) Using a clamp ammeter, monitor the AC current into the circuit breaker.
a)
b)
If the current is less than the amount printed on the serial tag, replace the
defective circuit breaker.
If the current is greater than the specified amperage, determine the source of the
extra current draw.
#12
Unit does not cool at all.
1) Check that compressor & compressor fan are running. While the unit is set for cooling,
check voltage across connector CONN14 on modulating board If the voltage is not
~28Vdc, replace the modulating board.
2) If the compressor & compressor fan are not running, check the circuit breaker, power to
the compressor (line voltage), compressor overload, compressor relay, and compressor
start & run capacitors.
3) Listen for the modulating valve to "click" (open and close).
a)
b)
SECTION 3. CALIBRATION
These units are rated to be within 0.5C of actual temperature over the entire temperature range.
There is no calibration procedure. To check calibration you need to have a traceable thermometer
of known accuracy of 0.05C accuracy or better. Check at a least two points, one cold and one
hot. If the user temperature extremes are known, check at or near these points. The readout must
be within 0.5C over this range to pass
temperature control and to conserve energy. Refrigeration pressures and temperatures will change
considerably with use.
To observe the HEAD (HEAd) and SUCTION (SUCt) temperatures:
1)
2)
3)
4)
5)
Press and HOLD the SET/ENTER button until the display reads Unit.
Then release and press and HOLD SET/ENTER button once again until the display reads
EPC.
Then turn the set knob clockwise until it reads HEAd or SUCt.
Then press the SET/ENTER button to read the temperature.
Use the following REFRIGERATION SERVICING section for example of head and suction
temps, and pressures.
Refrigeration Parameters
Model
suction temp
head temp
suction pressure
head pressure
6205
14C - 19C
67C - 75C
40 - 55 (psi)
6305
10C - 15C
65C - 85C
40 - 50 (psi)
6505
10C - 15C
65C - 75C
40 - 45 (psi)
6705
10C - 16C
65C - 80C
40 - 50 (psi)
6105
8C - 15C
64C - 81C
31 - 45 (psi)
To properly test your unit, testing conditions for 6000 series at 20C:
1)
2)
3)
The two black wires to the modulating valve go to CONN14. Remove this connector from the
modulating PC board.
2)
Run the refrigeration for about 30 seconds. The suction should drop below -20 psi
3) Shut off the unit. The pressure should not change for at least a minute.
If steps 2 or 3 do not correct the problem, then the compressor valves and/or modulating valve are
defective. Reconnect CONN14 when finished.
FROM
TO
FROM
TO
FROM
TO
FROM
TO
U7,1
TP4
U7,17
U5,11
U6,9
U3,26
U7,50
U12,10
U7,1
U12,1
U7,18
U6,16
U6,11
U12,2
U7,51
U12,19
U7,2
C5,
U7,19
RN,4
U7,38
U12,23
U7,52
U12,18
U7,3
C6,
U7,19
U6,5
U7,39
U12,21
U7,53
U12,17
U7,4
U7,7
U7,20
U6,4
U7,40
U12,24
U7,54
U12,16
U7,4
U7,8
U7,21
U5,3
U7,41
U12,25
U7,55
U12,15
U7,6
U11,7
U7,22
U6,3
U7,43
U12,3
U7,56
U12,13
U7,8
RN1,1
U7,23
RN1,8
U7,44
U12,4
U7,57
U12,12
U7,9
RN1,9
U7,25
CN9,4
U7,45
U12,5
U7,58
U12,11
U7,9
U6,17
U7,26
CN9,3
U7,46
U12,6
U7,62
U12,27
U7,11
U5,1
U6,6
U7,31
U7,47
U12,7
U7,63
U12,22
U7,14
U5,4
U6,7
U3,1
U7,48
U12,8
U7,16
U5,2
U6,8
U3,27
U7,49
U12,9
Model 6205(P)
Model 6305(P)
Model 6505(P)
Model 6705(P)
Model 6105(P)
Display PCB
500-109
500-109
500-109
500-109
500-109
Modulating PCB,
120V
240V
500-101
500-102
500-101
500-102
500-101
500-102
500-101
500-102
500-101
500-102
Main PCB
120V/60Hz
240V/50Hz
500-144
500-145
500-144
500-145
500-144
500-145
500-144
500-145
500-144
500-145
Turbine Pump
6205T 215-308
6505T 215-308
6705T 215-305
6105T 215-305
PD Pump Head,
1 gpm
4 gpm
215-105
-----
215-105
-----
215-105
-----
----215-106
----215-106
PD Pump Motor,
120V/60Hz
240V/50Hz
215-102
215-103
215-102
215-103
215-102
215-103
215-102
215-103
215-102
215-103
Filter Assembly
300-098
300-098
300-098
300-098
300-098
Refrigeration
Head/Suction
Sensor Assembly
525-329
525-329
525-329
525-329
525-329
Pressure Regulator
750-032
750-032
750-032
750-032
750-032
Circuit Breaker
215-157
215-157
215-270
215-157
215-157
Refrigeration (drop-in),
120V/60Hz
240V/50Hz
750-157
750-158
750-153
750-154
750-155
750-156
---------
---------
6305T 215-308
Compressor,
208-230V/ 60Hz, 134a
240V/ 50Hz, 134a
---------
---------
---------
750-126
750-127
750-128
750-129
Condenser Coil
-----
-----
-----
750-160
750-160
---------
---------
---------
215-188
215-188
215-188
215-188
Condenser
Fan Motor Blade
-----
-----
-----
215-076
215-076
750-075
750-075
750-075
750-075
750-075
Modulating Valve
750-093
750-093
750-093
750-133
750-133
590-106
590-106
590-106
590-108
590-108
Air Filter
400-388
400-388
400-388
400-388
400-388
775-088
775-088
775-088
775-088
775-088
215-181
215-182
215-181
215-182
215-181
215-182
215-181
215-182
SECTION 8. SCHEMATICS
10
Wiring Diagram, 6205, 6205P, 6305, 6305P, 6505, 6505P - 120V, 60Hz
11
Wiring Diagram, 6205, 6205P, 6305, 6305p, 6505, 6505p, 240V, 50Hz
12
13