Escolar Documentos
Profissional Documentos
Cultura Documentos
GroundedWyeTransformersUsingSinglePhaseTestCurrents
Presentedat:MinnesotaPowerSystemsConference
St.Paul,MN,USA
November11,2015
TomErnst
GEDigitalEnergy
4523JeremiahRd.
Cookeville,TN38506
thomas.ernst@ge.com
CraigTalbot
MinnesotaPower
30WestSuperiorSt.
Duluth,MN55802
ctalbot@mnpower.com
Abstract
Thispaperprovidesanalternatemethodfortestingtransformerdifferentialrelaysappliedtodelta
groundedwyetransformersusingsinglephasetestcurrents.Thealternatemethodisbasedonthe
transformerthreelinediagramandtransformernameplate.Thisalternatemethodsimulatesactual
currentflowsinthetransformerduringsinglelinegroundfaultsonthewyesideandprovides
confirmationthattherelaysslopecharacteristicsandphaseshiftsettingsareoperatingcorrectly.The
alternatemethodisbasedonthetransformerthreelinediagramandprovidesverificationthatthe
relayssettingsarecorrectforthetransformerapplication.
Threephasetestingisnotpossiblewithsometestsetsdueinpartbythelimitednumberofcurrent
channelsavailableand,insomeapplications,testsetscanalsobelimitedbythehighcurrentvalues
requiredfordifferentialslope2regiontests.Traditionalmethodsofsinglephasetestingtypically
requiretheadditionof3multipliersandotheradjustmentstoaccountforzerosequencecurrent
removal,furtherincreasingthemagnitudeofthetestcurrents.Also,traditionaltests(both3phaseand
1phase)usecurrentsandphaseshiftsbasedontherelaysettings.Thealternatemethodimprovesboth
issuesasonly2channelsarerequiredofthetestsetand,sincethetestsimulatesrealworld,no
multipliersarerequired.Thealternatemethodusestwotestcurrentsthatarealways180degreesoutof
phaseofeachotherforthedifferentiallybalancedconditionregardlessofthetransformerphaseshift
leadorlag.Asaresult,thealternatemethodisespeciallyusefulforcommissiontestingasitprovesthe
transformerphaseshiftrelaysettingsarecorrectforthetransformerconnectionratherthantestingthe
relaysettings.
Introduction
Testingoftransformerdifferentialcharacteristicscanbechallenging.Threephasetesting,whilestraight
forwardfromamagnitudeandphaserelationshippointofview,requires6highamperagetestcurrents.
Fordeltagrdwyewindingtransformers,traditionalsinglephasetestingrequiresnonobvious
multipliersanddoesnotsimulaterealworldfaultconditions.Thispaperdiscussesanalternatemethod
ofsinglephasetestingthatsimulatesrealworldsinglephaseloadingconditionswithouttheneedfor
phaseshiftsorcurrentmultipliers.Thisalternatemethodverifiesthedifferentialrelaysettingsare
appropriatefortheinstalledtransformerbyusingtheinstallationdrawingsandtransformernameplate
diagramtodeterminethetestconnections.ApplicationexamplesofinstallationsatMinnesotaPower
substationsareusedtodemonstratethemethod.
Traditional3PhaseTesting
Differentialpickuptestscanbeperformedusing3phasetestcurrents.Themagnitudeofthecurrents
requiredforpickupistypicallylow(10%20%offullload)andonly3currentchannelsarerequired
fromthetestset.Formicroprocessorrelays,itisimportanttoconfirmthatallthreephasespickup
whenperforminga3phasetest.
Slopecharacteristictestsrequiresimultaneousinjectionoftestcurrentsintoaminimumof2relay
windings.Themagnituderelationshipofthecurrentsbetweenthewindingsisbasedonthetransformer
threephasevoltageratio.Thephaseshiftbetweenthetestcurrentsisafunctionofthetransformer
internalandexternalconnections.Determiningthecorrectanglerequiresanexaminationofthe
substation3lineinstallationdrawingandthetransformernameplatediagram.Athorough
understandingof3phasepowerisalsorequiredsincetheexternalconnectionscanreversetheleadlag
relationshipofthewindingsifphasesA,BandCarenotconnectedtobushings1,2and3.
Figure1showsaninstallationwithatypicaldeltagrdwyetransformerwithstandardIEEEphaseshift
(secondarylagsprimaryby30).Inthisinstallationtheinstalledphaserelationshipmatchesthe
transformernameplatephaserelationshipsincephaseAisonbushings1,Bisonbushings2andCison
bushings3.The3phasetestcurrenttosimulatefullloadforthisinstallationarealsoshowninfigure1.
Figure1:Typicaldeltagrdwyetransformerandassociated3phasetestcurrents
Figure2showsthesametransformerasfigure1buttheexternalconnectionsarerolledsuchthatphase
Aisonbushings3,Bisonbushings2andCisonbushings1.Theresultinginstalledphaseshifthasthe
lowvoltagesideleadingthehighvoltagesideby30eventhoughthetransformernameplatedrawing
showsalaggingsecondaryvoltage.Notethatthetestcurrentsreflectthisleadingphaseangleshift.
Figure2:Typicaldeltagrdwyetransformerwithrolledphasingandassociated3phasetestcurrents
Figure3showsthetestsetconnectionsfor3phasetestingofthetransformerinstallationshownin
Figure1.Threephasedifferentialslopetestingrequires6testcurrentseachhavingdifferentphase
angles.Sometestsetscannotperform3phasedifferentialslopetestsbecauseofthelimitednumberof
currentchannelsavailable.Additionally,sometestsetswith6currentchannelshavelimitedVA
capabilitywhenusingthe6channels;thisinturnlimitsthemagnitudeofthetestcurrents,especially
whentestingtheregion2slopecharacteristic.
DifferentialRelay
Figure3:3Phasetestingconnectionsforthefigure1transformer
Traditional1PhaseTesting
Traditionalsinglephasetestingoftransformerdifferentialrelays,asshowninfigure4,inherentlychecks
thefunctionalityofeachphaseandrequiresonly2injectedcurrents.Byonlyusing2injectedcurrents
mostrelaytestsetscanperformthistypeoftesting.However,injectingsinglephasecurrentsfor
differentialslopetestingoftenrequiresmultipliersandphaseshiftsthatarenotobviousfromthe
substationandtransformer3linediagrams,especiallyfordeltagrdwyewindingtransformers.
Figure4:Traditional1phasetestconnections
Alternate1PhaseMethod
Analternatemethodofusingsinglephasetestcurrentsisshowninfigures5and6.Thisconnectionis
relatedtothetransformerinternalandexternal3linediagramsandsimulatesrealworldloadandshort
circuitconditionswithouttheneedfornonobviousmultipliers.Differentiallybalancedsinglephase
throughcurrentforadeltagrdwyetransformerwith30degreelagsecondaryandtheassociatedtest
connectionsareshowninfigures5(a)and5(b)respectively.Thedifferentiallybalanced1phasethrough
currentandassociatedtestconnectionsforadeltagrdwyetransformerwith30degreeleadsecondary
areshowninfigures6(a)and6(b)respectively.
Figure5(a):Differentiallybalanced1phasethroughcurrentfora30degreelagtransformer
Figure5(b):Differentiallybalanced1phasetestconnectionsfora30degreelagtransformer
2.5@180
2.5@0
Installed
A(H3)
200/5A
C(H1)
A(X3)
X0
100@0
H3
H2
H1
B(H2)
B(X2)
C(X1)
Nameplate
H1
Test
Currents
toRelay
H3
115,000
13,800/7970GY N1/N2=115/8
20MVA
X3
X2
X3
H2
X1
X0
X2
X0
X1
2000/5A
3.61@180
1443@0
Figure6(a):Differentiallybalanced1phasethroughcurrentfora30degreeleadtransformer
DifferentialRelay
Figure6(b):Differentiallybalanced1phasetestconnectionsfora30degreeleadtransformer
Thetestcurrentmagnitudesandanglesshowninfigures5(b)and6(b)arecalculatedbasedonthe
differentiallybalancedthroughcurrentconditionsshowninfigures5(a)and6(a).Thecurrents
calculatedbyaproperlymodeledshortcircuitprogrammayalsobeappliedtosimulatetherelays
performanceduringrealworldexternalfaultconditions.Eventhoughdeltagrdwyetransformers
create3phaseangleshiftsof+/30degrees,thealternate1phasemethodtestcurrentsarealways180
degreesapartfordifferentiallybalancedthroughcurrentconditions.Thesuccessofthealternatesingle
phasetestclearlyindicatesifthetransformerphaseshiftsettingisenteredproperlyfortheinstallation.
Figure7showsthetransformerdifferentialrelaycalculatedquantitiesforthetestshowninfigure5(b)
wherethephaseshift(W2AngleWRT)settingisenteredcorrectly(30degrees).Notethatthe
differentialcurrentmagnitudeis0forallthreephasesandtherestraintcurrentmagnitudeis0.5per
unitinphasesAandC,correctlyindicatingadifferentiallybalancedthroughcurrentcondition.
20
115
DELTA
NO
0
200
5
100.4
2.510
Rotations
ABC
2
W2
20
13.8
WYE
YES
-30
2000
5
836.7
2.092
W3
W4
0
230
WYE
NO
0
2000
5
0.0
0.000
0
13.8
WYE
NO
0
8000
5
0.0
0.000
W5
Magnitude
Angle
W6
Magnitude
Angle
W6
0
0.48
WYE
YES
0
3000
5
0.0
0.000
TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5
IA
IB
IC
2.50
0.0
0.00
0.0
2.50
180.0
0
69
WYE
YES
0
1000
5
0.0
0.000
ACTUAL VALUES
I diff, pu
12
Operating Characteristic
11
10
9
3.61
180.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.00
0.00
0.0
0.0
0.0
DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.00
0.00
Angle
-180.0
-180.0
Icd
0.00
0.0
RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.50
0.00
Icr
0.50
8
7
6
0.00
0.0
5
4
3
2
1
DIFF. OPERATION
0
0
Slope characteristics
0.00
0.0
0.00
0.0
0.00
0.0
6
Iad
7
Ibd
9
Icd
10
11
12
I restr, pu
NO TRIP
Ia
No trip
Ib
No trip
Ic
No trip
Figure7:Differentiallybalancedthroughcurrentconditionwithcorrectphaseshiftsetting
Ifthephaseshiftsettingisenteredincorrectly(30degrees)andthetestcurrentsshowninfigure5(b)
areentered,thetransformerdifferentialrelaycalculatedquantitiesclearlyshowaproblem(figure8):
thedifferentialcurrentmagnitudesarenot0forphasesBandCandtherelaytrips.
Oncethedifferentiallybalancedthroughcurrentconditionisestablishedcorrectly,asinfigure7,the
angleofoneofthewindingcurrentscanberolleduntiltherelaytrips.Atthispoint,theslopecanbe
calculatedbydividingthedifferentialcurrentmagnitudebytherestraintcurrentmagnitude.Figure9
showstheresultsofthisslopetestshowingatripwithwinding2currentrolledfrom180to165.6
degreesandacalculatedslope(S1)of:S1=0.13/0.50=0.26or26%.Thiscorrelateswellwiththeslope1
settingof25%.Asimilartestcanberunwithlargertestcurrentstoverifytheslope2performance.
20
115
DELTA
NO
0
200
5
100.4
2.510
Rotations
ABC
2
W2
20
13.8
WYE
YES
30
2000
5
836.7
2.092
W3
W4
0
230
WYE
NO
0
2000
5
0.0
0.000
0
13.8
WYE
NO
0
8000
5
0.0
0.000
W5
Magnitude
Angle
W6
Magnitude
Angle
W6
0
0.48
WYE
YES
0
3000
5
0.0
0.000
TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5
IA
IB
IC
2.50
0.0
0.00
0.0
2.50
180.0
0
69
WYE
YES
0
1000
5
0.0
0.000
ACTUAL VALUES
I diff, pu
12
Operating Characteristic
11
10
9
3.61
180.0
0.00
0.0
7
6
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.00
0.00
0.0
0.0
0.0
DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.00
0.50
Angle
-180.0
0.0
Icd
0.50
-180.0
RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.50
0.50
Icr
0.50
0.00
0.0
0.00
0.0
5
4
3
2
1
DIFF. OPERATION
0
0
Slope characteristics
0.00
0.0
0.00
0.0
6
Iad
Ibd
10
Icd
11
12
I restr, pu
0.00
0.0
TRIP
Ia
No trip
Ib
Trip
Ic
Trip
Figure8:Differentiallybalancedthroughcurrentconditionwithincorrectphaseshiftsetting
20
115
DELTA
NO
0
200
5
100.4
2.510
Rotations
ABC
2
W2
20
13.8
WYE
YES
-30
2000
5
836.7
2.092
W3
W4
0
230
WYE
NO
0
2000
5
0.0
0.000
0
13.8
WYE
NO
0
8000
5
0.0
0.000
W5
Magnitude
Angle
W6
Magnitude
Angle
W6
0
0.48
WYE
YES
0
3000
5
0.0
0.000
TEST CURRENTS
W1
Magnitude
Angle
W2
Magnitude
Angle
W3
Magnitude
Angle
W4
Magnitude
Angle
W5
IA
IB
IC
2.50
0.0
0.00
0.0
2.50
180.0
0
69
WYE
YES
0
1000
5
0.0
0.000
ACTUAL VALUES
I diff, pu
12
Operating Characteristic
11
10
9
3.61
165.6
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.0
0.00
0.00
0.00
0.0
0.0
0.0
DIFFERENTIAL CURRENTS
Iad
Ibd
Magnitude 0.13
0.00
Angle
-277.1
-194.4
Icd
0.13
-97.1
RESTRAINT CURRENTS
Iar
Ibr
Magnitude 0.50
0.00
Icr
0.50
8
7
6
0.00
0.0
5
4
3
2
1
DIFF. OPERATION
0
0
Slope characteristics
0.00
0.0
0.00
0.0
0.00
0.0
6
Iad
7
Ibd
9
Icd
10
11
12
I restr, pu
TRIP
Ia
Trip
Ib
No trip
Figure9:Slopeverificationtestwithwinding2testcurrentanglerolledtopointoftrip
Ic
Trip
Sincethealternatemethodisasinglephasetest,itisnecessarytorepeatthetestforeachphasefora
totalof3connectionsforeachwindingpair.Tables1and2showtestconnectionsrequiredfora2
windingdeltagrdwyetransformerwith30degreelag(figures5(a)&(b))andlead(figures6(a)&(b))
connectionsrespectively.
Table1:Testconnectionsfora2winding30degreelagdeltawyeconnectiontransformer
TestID Winding1(delta)connections Winding2(wye)connections
A
InonA&outonC
A
B
InonB&outonA
B
C
InonC&outonB
C
Table2:Testconnectionsfora2winding30degreeleaddeltawyeconnectiontransformer
TestID Winding1(delta)connections Winding2(wye)connections
A
InonA&outonB
A
B
InonB&outonC
B
C
InonC&outonA
C
Thetraditionalsinglephasetestmethodrequiresinjectingtestcurrentswithmagnitudesandanglesnot
obviousfromthesubstationandtransformerdrawingswhilethealternatemethodcurrentmagnitudes
andanglesarevisuallyrelatedtotheinstalled3linediagramandtheinternalturnsratio(N1/N2)ofthe
transformer.However,acloseinspectionshowsthata3multiplierisimpliedduetotherelationship
betweenthetransformer3phasevoltageratioandtheinternalturnsratio.Asaresult,thetestcurrents
forthealternatemethodarestilllargerthanthoserequiredfor3phasetesting.Forthisreason,itmay
stillbedifficultforsometestsetstodeliverhightestcurrentstoverifytheregion2slope.
Itshouldbepossibletodevelopanautomatedtestplanforthealternatesinglephasemethodwhich
wouldselectthetestoutputsfromtable1ortable2dependingonthephaseshiftsetting.Assuch,the
methodcouldbeusedformaintenancetesting.However,themethodisuniquelysuitedforcommission
testingwherethecoreactivityofthemethodistodeterminethetestconnectionsbasedonan
examinationoftheinstallationdrawingswiththeultimategoalofverifyingthatthephaseshiftsettingis
correctfortheinstallation.
ApplicationExamples
TwoapplicationexamplesatMinnesotaPowersubstationsareincludedbelow.Thefirstexampleisa
distributionsubstationwherethedistributionvoltagelagsthetransmissionvoltage.Thesecond
exampleisanotherdistributionsubstationinadifferentdivisionwherethedistributionvoltageleadsthe
transmissionvoltage.Inbothcases,IEEEstandardphaseshifttransformerswereinstalled(Xsidelags
theHsideby30).
Ananalysisofatransformerdifferentialrelayoperationcausedbyanincorrectphaseshiftsettingisalso
includedintheApplicationExamplessection.
Laggingexample
Inthisexample,thedistributionvoltage(34.5kV)lagsthetransmissionvoltage(115kV)by30.Figure
10showsthetransformernameplatediagramandfigure11showsthesubstation3linediagramofthe
transformerinstallationwitharrowsshowingdifferentiallybalancedsinglephaseloading.SinceABC
phasesareconnectedtobushings123respectively,theinstallationphasordiagrammatchesthe
transformernameplatephasordiagram.
Figure10:Transformernameplateforexample1
MinnesotaPowerusesacalculationsheettodocumentthebasisoftheirrelaysettingsandtodefinethe
commissionteststobeperformed.Thecommissiontestingdefinitionsfortheexample1transformer
differentialslopecharacteristicareshowninfigure12.Youwillnotethatthetestconnectionsmatch
withthoseshowninfigure5(b)andTable1fora30laginstallation.
197A
1200/5MR
300/5Tap
3.28@0
N1/N2=115/19.9
A(H1)
C(H3)
C(X3)
1200/5MR
1200/5Tap
B(H2)
A(X1)
X0
B(X2)
4.73@180
1137A
Figure11:3lineinstallationdiagramforexample1withdifferentiallybalanced1phaseload
Test Values
A-phase
B-phase
C-phase
I mag.
3.28
4.73
0.00
I ang.
0
180
0
Connection:
In on A-Ph Wdg 1 (+) and out on C-Ph Wdg 1 (+) with A-Ph Wdg 1 (-) jumpered to C-Ph Wdg 1 (-)
A-Ph Wdg 2 (+), role angle until 87R asserts
no connection
Monitor 87R bits. Use MET DIF to view operate current (IOP) and Restraint currents (IRT). Initially IOP = 0 and IRT = 1.0.
Note point where 87R asserts. IOP/IRT should equal Slope at trip point.
Repeat for B-Phase:
Test Values
A-phase
B-phase
C-phase
I mag.
3.28
4.73
0.00
I ang.
0
180
0
Connection:
In on B-Ph Wdg 1 (+) and out on A-Ph Wdg 1 (+) with B-Ph Wdg 1 (-) jumpered to A-Ph Wdg 1 (-)
B-Ph Wdg 2 (+), role angle until 87R asserts
no connection
Monitor 87R bits. Use MET DIF to view operate current (IOP) and Restraint currents (IRT). Initially IOP = 0 and IRT = 1.0.
Note point where 87R asserts. IOP/IRT should equal Slope at trip point.
Repeat for C-Phase:
Test Values
A-phase
B-phase
C-phase
I mag.
3.28
4.73
0.00
I ang.
0
180
0
Connection:
In on C-Ph Wdg 1 (+) and out on B-Ph Wdg 1 (+) with C-Ph Wdg 1 (-) jumpered to B-Ph Wdg 1 (-)
C-Ph Wdg 2 (+), role angle until 87R asserts
no connection
Monitor 87R bits. Use MET DIF to view operate current (IOP) and Restraint currents (IRT). Initially IOP = 0 and IRT = 1.0.
Note point where 87R asserts. IOP/IRT should equal Slope at trip point.
Figure12:Testingdefinitionsforexample1transformerdifferentialslopecharacteristic
LeadingExample
Inthisexample,thedistributionvoltage(13.8kV)leadsthetransmissionvoltage(115kV)by30.Figure
13showsthetransformernameplatediagramandfigure14showsthesubstation3linediagramofthe
transformerinstallationwitharrowsshowingdifferentiallybalanced1phaseloading.SinceABCphases
areconnectedtobushings321respectively,theinstallationphasordiagramisshifted60fromthe
transformernameplatephasordiagramtoshowa30leadrelationship.
Figure13:Transformernameplateforexample2
Thecommissiontestingdefinitionsfortheexample2transformerdifferentialslopecharacteristicare
showninfigure15.Youwillnotethatthetestconnectionsmatchwiththoseshowninfigure6(b)and
Table2fora30leadinstallation.
A
B
C
160A
A(H3)
C(H1)
A(X3)
X0
C(X1)
B(H2)
600/5MR
400/5Tap
2.00@0
B(X2)
N1/N2=115/8.2
5.60@180
2000/5SR
2240A
Figure14:3lineinstallationdiagramforexample2withdifferentiallybalanced1phaseload
Test Values
I mag.
I ang. Connection:
A-phase
2.00
0
In on A-Ph Wdg 1 (+) and out on B-Ph Wdg 1 (+) with A-Ph Wdg 1 (-) jumpered to B-Ph Wdg 1 (-)
B-phase
5.60
180
A-Ph Wdg 2 (+), role angle until 87R asserts
C-phase
0.00
0
no connection
Monitor 87R bits and view the operate current (IOP) and restraint current (IRT).
Use Differential and Restraint in Actual Values to view Differential current and Restraint current for A phase and B phase. C phase differential
and restraint currents should be 0 if the winding compensation factor (Angle WRT) is correct.
Repeat for B-Phase:
Test Values
I mag.
I ang. Connection:
A-phase
2.00
0
In on B-Ph Wdg 1 (+) and out on C-Ph Wdg 1 (+) with B-Ph Wdg 1 (-) jumpered to C-Ph Wdg 1 (-)
B-phase
5.60
180
B-Ph Wdg 2 (+), role angle until 87R asserts
C-phase
0.00
0
no connection
Monitor 87R bits and view the operate current (IOP) and restraint current (IRT).
Use Differential and Restraint in Actual Values to view Differential current and Restraint current for B phase and C phase. A phase differential
and restraint currents should be 0 if the winding compensation factor (Angle WRT) is correct.
Repeat for C-Phase:
Test Values
I mag.
I ang. Connection:
A-phase
2.00
0
In on C-Ph Wdg 1 (+) and out on A-Ph Wdg 1 (+) with C-Ph Wdg 1 (-) jumpered to A-Ph Wdg 1 (-)
B-phase
5.60
180
C-Ph Wdg 2 (+), role angle until 87R asserts
C-phase
0.00
0
no connection
Monitor 87R bits and view the operate current (IOP) and restraint current (IRT).
Use Differential and Restraint in Actual Values to view Differential current and Restraint current for C phase and A phase. B phase differential
and restraint currents should be 0 if the winding compensation factor (Angle WRT) is correct.
Figure15:Testingdefinitionsforexample2transformerdifferentialslopecharacteristic
TransformerDifferentialRelayIncorrectOperationAnalysisExample
Figure16showsatransformerthroughfaulteventthattherelayincorrectlyinterruptedasaninzone
differentialfaultandissuedatrip.TRHA,TRHB,andTRHCarehighsidetransformercurrents.TRLA,
TRLB,andTRLCarelowsidetransformercurrentsand1TA,1TB,and1TCarelowsidemainbreaker
currents.Thisisa2windingdeltagrdwyetransformer.Thelowside(TRL_)currentsareusedforover
currentbackupandthedifferentialelementsusethehighside(TRH_)andlowsidemainbreaker(1T_)
currents.Duetoconstructionconstraints,thetransformerwasnotfullyloadedbeforetheBphaseto
groundfeederfaultoccurred.Theloadcurrentsonthetransformerwerebelowtheminimumpickupof
therelaydifferentialelements.Duringthetripinvestigationitwasdeterminedthattherelaysettingfor
phaseanglecompensationforthelowvoltagesideofthetransformerwascompensatedforalagging
relationship.Inthisinstallation,phasesABCareconnectedtobushing321resultinginthelowside
leadingthehighsideby30.Thistypeofconnectioncanbeseeninfigure4.
Thealternatemethodoftestingwasnotusedforcommissioningofthistransformerdifferentialrelay.
Forthisapplication,ifthetestconnectionsshowninfigures6(a)and6(b)andtable2wereused,the
phaseanglecompensationsettingserrormayhavebeenidentifiedandathroughfaulttripofthe
differentialrelaymayhavebeenavoided.
Figure16:Transformerthroughfaultwithincorrectphaseshiftrelaysettings
Conclusion
Threephasetestingoftransformerdifferentialrelaycharacteristicsrequiresathoroughunderstanding
of3phasepowertodeterminetheappropriatephaseshiftandatestsetwith6highamperagetest
currentoutputs.Traditionalsinglephasetestingrequiresnonobviousmultipliersfordeltagrdwye
windingtransformersanddoesnotsimulaterealworldfaultconditions.Thealternatemethodofsingle
phasetestingdiscussedinthispapersimulatesrealworlddifferentiallybalancedsinglephaseloading
conditionsthatreflecttheinstallation3lineandtransformernameplatediagrams.Whilethismethod
canbeusedformaintenancetesting,itismostideallysuitedforcommissiontestingwherethegoalisto
assurethesettingsarecorrectfortheinstallation.
Biographies
TomErnstisaP&CTechnicalApplicationEngineerfortheNorthAmericanCommercialteam.Hehas
beenwithGEsince2011supportingtheGridAutomationProtectionandControlPortfolio.Priorto
joiningGE,TomhasbeenwithMinnesotaPowerasaSupervisingEngineer,DeltaEngineering
InternationalasaManagerofElectricalEngineering,HDREngineeringasaManagerofElectrical
EngineeringandNorthernStatesPowerasaSupervisingEngineer.HereceivedhisBachelorofScience
inElectricalEngineeringfromtheUniversityofMinnesotain1978andhisMasterofScienceinPower
SystemsfromMichiganTechnologicalUniversityin2008.HeisaregisteredProfessionalEngineerinthe
StateofMinnesota.
CraigTalbotisaSupervisingEngineerfortheRelayandMaintenanceEngineeringDepartmentat
MinnesotaPower.HejoinedMinnesotaPowerin2011asaRelayandMaintenanceEngineer.Priorto
joiningMinnesotaPowerheworkedatL&SElectricInc.asaFieldEngineer.HereceivedhisBachelorof
ScienceinElectricalEngineeringfromMontanaStateUniversityin2002.Craigisaregistered
ProfessionalEngineerintheStateofMinnesota.