Escolar Documentos
Profissional Documentos
Cultura Documentos
GE Digital Energy
NetPro
Uninterruptible Power Supply
2000 - 4000 VA
Manufactured by:
GE Digital Energy
General Electric Company
CH 6595 Riazzino (Locarno)
Switzerland
NetPro UPS
ver 4.0 - GB
GE Digital Energy
GB
USER MANUAL
NetPro
Uninterruptible Power Supply
2000 - 4000 VA
Please read these instructions carefully before installation and start-up of the NetPro UPS.
Keep this manual in a safe place for future reference.
CONTENTS
1
INTRODUCTION ............................................................................................................ 2
1.1 Introduction
1.2 Safety Rules
1.3 Transport / Storage
INSTALLATION .............................................................................................................. 2
2.1 Installation Rules
2.2 Installation Procedure
OPERATION................................................................................................................... 4
3.1 Description of Front Panel
3.2 Start-up
3.2.1 Start-up, mains available
3.2.2 Start-up, mains not available (battery start)
3.2.3 Start-up with programmed runtime (autonomy time)
COMMUNICATION ...................................................................................................... 16
4.1 RS232 Port
4.2 Relay Interface Card (option)
4.3 SNMP Interface Card (option)
MAINTENANCE............................................................................................................ 17
6.1 General
6.2 Batteries
TROUBLESHOOTING ................................................................................................. 18
SPECIFICATIONS........................................................................................................ 19
General Electric Digital Energy. All rights reserved; reproduction without permission prohibited. This manual may be subject to
change; no liability can be accepted for any error or omission.
OPM_NPE_XXX_2K0_4K0_1GB_V040
GE Digital Energy
1 - Introduction
1.1
Introduction
The GE (General Electric) Digital Energy NetPro UPS, a truly on-line uninterruptible power supply,
protects your equipment from all forms of power interference, including complete power failures.
1.2
Safety Rules
! CAUTION: RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The appliance
outlets may be electrically live, even when the UPS is disconnected from the mains.
! The UPS contains potentially hazardous voltages. Do not open the UPS, there are no user
serviceable parts inside.
! All maintenance and service work, including replacement of the batteries, should be
performed by qualified service personnel.
1.3
Transport / Storage
! No liability can be accepted for any transport damage when the equipment is shipped in nonoriginal packaging.
! Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature
must be within -20 +45 "C. If the unit is stored for a period exceeding 3 months, optimal battery
lifetime is obtained if the storage temperature does not exceed 25C.
! If the unit is stored for an extended period of time, the batteries must be recharged periodically.
Connect the unit to a wall outlet and recharge the batteries for 24 hours:
- if the storage temperature is within -20 and +30C: every 3 months,
- if the storage temperature is within -20 and +45C: every month.
2 - Installation
The shipping box contains a NetPro UPS, two IEC male-female power cords, a data cable, a CD ROM
and this manual. Inspect the UPS for damage after unpacking. If any damage is present please
immediately notify the carrier and place of purchase.
IMPORTANT:
Before making any connection and switching on the NetPro UPS, please check the following
conditions:
!
!
your mains supply is 220 - 240 Volts and 50 (if the mains frequency is 60Hz, the output frequency
of the UPS can be changed, see section 3.4), and
the total power demand of the connected equipment does not exceed the rated output power of
the NetPro UPS (indicated on the rating label) (6, fig. 1).
WARNING
Connecting the UPS output to neutral or ground will result in a malfunctioning UPS, unless your
unit is a "NetPro+", i.e. equipped with an isolation transformer.
2.1
Installation Rules
! The UPS is intended to be used in normal domestic and office situations.
! Protect the UPS, according to the wiring rules, with a 16A (NP 2000/3000VA) or 25A
(NP 4000VA) D-type fuse.
! The UPS must be powered from a single phase wall outlet equipped with protective earth. Do not
use extension cords.
! Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.
! The ambient temperature should not exceed 40"C. Optimal battery lifetime is obtained if the
ambient temperature does not exceed 30"C.
! It is important that ventilation air can move freely around and through the unit. Do not block the air
vents.
! Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.
! Be careful when connecting laser printers: be sure that the demanded power does not exceed the
capacity of the UPS.
! The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.
OPM_NPE_XXX_2K0_4K0_1GB_V040
g
2.2
GE Digital Energy
Installation Procedure
fig. 1
12
12
4a
8
6
1
10
OK
11
3000 VA
RESET
NetPro 2000VA
NetPro 3000/4000VA
fig. 2
fig. 3
7
9a
fig. 4
Make sure the on/off switch (12, fig. 1) at the rear of the UPS is off, i.e. in position 0, and connect
the mains cord of the UPS to a working, AC wall socket outlet equipped with a protective earth
connection. The fans start rotating: mains power is available and the batteries are charging.
For best results, allow the UPS to recharge the batteries during a period of approx. 12 hours. It is
acceptable to use the UPS without first charging the battery, but the runtime may be reduced.
For advanced communication possibilities, the RS232 interface port (3, fig. 1) can be connected
to a computer system and/or optional interface cards (5, fig. 1) can be added. See chapter 4.
OPM_NPE_XXX_2K0_4K0_1GB_V040
GE Digital Energy
3 - Operation
3.1
14
15
16
17
LCD screen
2x16 characters, shows UPS system data, status
messages, alarm messages, settings. The language
is selectable: English (default), German, French,
Italian, Spanish. Section 3.4.3 describes the
selection procedure.
15
13
14
16
17
19
18
20
18-20 Push-buttons
#' (18) and '$
$' (20) you can
With the button keypads '#
scroll through the several screens, with keypad 'OK'
(19) a selection is confirmed. Keypad activity is
accompanied by a beeping buzzer. If there is no
keypad activity during 20 seconds the LCD screen
will return to a default screen.
3.2
Start-up
3.2.1
1
2
3
3.2.2
1
!"##$%&'(#"%#')
*+''''''''''&$(
If the 'OK' key (19, fig. 5) is pressed within 5 seconds, the UPS will start. Pressing key $ (20,
fig. 5), or waiting 5 seconds, will abort the start-up attempt. The UPS operates on battery: it
discharges the batteries. The UPS will stop delivering output power at the end of the runtime
unless the mains input is available by that time
OPM_NPE_XXX_2K0_4K0_1GB_V040
g
3.2.3
GE Digital Energy
Start-up with programmed runtime (autonomy time)
If a start-up runtime has been programmed (see section 3.4.3 Setup menu) and the batteries do not
contain sufficient energy to provide this runtime at the moment of start-up, the following screen will
appear:
",#+*-'#++'.+/
'''''(#"%#')
If 'OK' (19, fig. 5) is pressed the message is ignored and the UPS will start up. If no key is pressed, the
UPS will wait until the batteries have been sufficiently charged to guarantee the programmed runtime, and
only then start up. Calculation of the runtime is based on the assumption that the UPS supplies a 100%
load.
This feature is not active during a 'battery start' (see above).
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
1
Switching off
Turn the 'on/off' switch (12, fig. 1) at the rear of the unit into position 0. If the UPS is switched off
the output will always be absent for a few seconds to ensure that the connected equipment is
able to reboot.
If electric isolation is required, unplug the power cord from the wall outlet.
The unit can be switched off in a programmed way: see section 3.6.2.
OPM_NPE_XXX_2K0_4K0_1GB_V040
g
3.4
GE Digital Energy
Use: Screen Menus
Operation of the NetPro UPS is done via the push-buttons and the LCD screen on the front panel. In
addition 4 LEDs inform the user about operating conditions.
Furthermore some functions of the UPS can be programmed via the RS232 communication port. For
more information see section 3.6 and chapter 4.
The messages displayed on the LCD screen can be divided into three menus:
Default menu
Status and alarm menu
Setup menu
If the UPS operates under normal conditions, the LCD shows the standard menu. The message shown
depends on the operating mode of the UPS. From any menu, the LCD screen will always return to the
standard menu after a push-button inactivity time-out of 20 seconds.
If the operating conditions change, e.g. by a mains failure or rise of temperature, a ! mark will appear in
the right lower corner of the display. With key # (18) you can enter the status and alarm screens.
The setup menu allows you to program the UPS. To enter the menu press # (18) until the menu is
reached. You can scroll through the individual setup screens with $ (20) and # (18).
3.4.1
Default menu
Under normal operating conditions (see 3.3.1), the LCD shows a default screen (the mentioned values
are examples):
0123''40'''01567
48023"''''''940/
230V
12
23min
=
=
=
1520VA =
912W
=
0123''40'''01567
48023"''''''940/
- - -V
12
23min
=
=
=
1520VA =
912W
=
!
=
0083''40''!&:"((
;
225V
Bypass
OPM_NPE_XXX_2K0_4K0_1GB_V040
=
=
g
3.4.2
GE Digital Energy
Status messages and alarm messages
The NetPro UPS alerts the user with a blinking ! signal on the LCD that the status has changed or that an
alarm situation occurs. The accompanying screen messages appear after the push-buttons $ or # have
been pressed. The blinking ! signal will disappear from the display (see also 3.4.1).
3 kinds of messages can be displayed on the LCD:
- status indications
(3.4.2.1)
indicate abnormal operating situations; the screen message is accompanied by a 1x per 8 secs. sounding buzzer. The buzzer is resettable with the
OK button (19), but only after the default screen is displayed again.
In case of 'weak mains' the yellow LED (16) on the front panel illuminates
and the buzzer remains silent.
Kind of message
Status indication
On line
On battery
On bypass
Error
High priority
alarm
Low priority
alarm
!
!
Battery low
Overload
Output error
High temperature
Temperature
Replace battery
Bypass error
Input error
Weak mains
OPM_NPE_XXX_2K0_4K0_1GB_V040
GE Digital Energy
+7<=67>
+7'?@AA>BC
During a power failure, i.e. whenever the mains input voltage is outside
the input voltage range, the UPS uses the energy stored in its internal
battery. The remaining runtime, displayed in the default screen, counts
down until either the mains returns or the batteries are empty. See also
3.5.
+7'?CD@EE
Bypass mode: the load is directly connected to the mains supply. See
also 3.3.4
$BBFB
$BBFB
GH@BI>B'>BBFB
$BBFB
#>5D>B@AJB>
$BBFB
%>D=@K>'?@AA>BC
Either the batteries are almost chemically worn out or the battery wiring,
including the battery fuse, is faulty. If the batteries are aged, they must
be replaced as soon as possible to ensure full protection for your
equipment (see section 6.2). Perhaps the 'replace battery' alarm occurs
after a manual test which you started immediately after installation or
after a power failure. In this case the alarm may be incorrect as the
batteries have been (partly) discharged during transport/storage or
during the power failure. Allow the UPS to recharge the batteries.
$BBFB
!CD@EE'>BBFB
$BBFB
:BFI-'FJADJA'FLL
$BBFB
M7DJA'>BBFB
$BBFB
/>@N'5@67E
The UPS is still on-line but the incoming mains voltage dropped
(instantaneously) below 187Vac. The alarm will only occur at loads less
than 100%, as at full load the UPS switches to battery operation if the
incoming mains voltage drops below 187Vac (see chapter 8 'input
specifications'). The alarm lasts at least 15 seconds, regardless the
duration of the alarm situation. This alarm is not supported by the
buzzer.
OPM_NPE_XXX_2K0_4K0_1GB_V040
GE Digital Energy
$BBFB
$BBFB
!@AA>BC'=FO
$BBFB
P@7'>BBFB
$BBFB
+Q>B=F@R
$BBFB
+JADJA'>BBFB
The output voltage drops below 207Vac. This situation can occur during
an overload, with either the bypass disabled or during battery operation.
$BBFB
S6IH'A>5D>B@AJB>
$BBFB
M7DJA'KF7Q>BA>B
OPM_NPE_XXX_2K0_4K0_1GB_V040
g
3.4.3
GE Digital Energy
Setup Menu
The 'setup screens' allow you to program the NetPro UPS, to read several operating parameters and to
test parts of the system. To enter the setup screens from a default screen, press the # key (18) until the
first of the setup screens appears (the mentioned values are examples):
*>A:BF'1222''32T
*:12"2UV9W08:24U
NetPro 3000
V06
second line
= UPS type,
= software version number
= serial number
!@AA>BC'K@D@K6AC
X2Y'''''''4U-0"H
80%
14.2Ah
Pressing # (18) displays the third setup screen. The upper line of the screen shows a programmable UPS
function; the lower line shows its actual setting.
Changing settings:
Using $ (20) and # (18) you can scroll through the several setup screens; OK (19) confirms a screen
choice. Subsequently '+' and '-' are displayed, and a proper setting for the function can be selected with $
(20) and # (18), and stored with OK (19). If a setting is stored, '+' and '-' will disappear.
One of the default screens will appear after 20 seconds of no key activity,
Blocking settings:
Pressing OK (19) and # (18) simultaneously in a default screen during at least 2 seconds blocks the
display of all setup screens described below. The display shows during 5 seconds:
($##M*Z(
.+G[$\
Pressing OK (19) and # (18) simultaneously in a default screen during 2 seconds again releases the
blocking of the setup screens. The display shows during 5 seconds:
($##M*Z(
,*.+G[$\
Table 2 gives an overview of all programmable functions, ranges and settings:
Screen text
Range
Default
NP 3000/4000 only:
Prog. outlet
If set 'AUTO': Off auton. time
ON/OFF/AUTO
ON
0 - 60 min.
Fr.tracking rate
2 Hz/sec or 10 Hz/sec
10 Hz/sec
0 - 60 min.
0 min.
Buzzer delay
0 - 60 sec.
8 sec.
Language
English
No-load shutdown
ON/OFF
OFF
Battery capacity*
(display shows no text, just a figure 4
- 250)
4 - 250 Ah
7Ah
Bypass enable
YES/NO
YES
Output voltage*
230V
Output frequency*
50 / 60 Hz
50 Hz
Restore defaults*
* Restore defaults: restores the default settings except the settings marked with *
OPM_NPE_XXX_2K0_4K0_1GB_V040
10
GE Digital Energy
:BFI-'FJA=>A
NetPro 3000/4000 only:
One of the applicance outlets (4a, fig. 1) is programmable. Three settings are possible:
! ON
! OFF
! AUTO
When the UPS is started the outlet is always switched ON, but it can be switched off either manually or
automatically.
With the default setting 'ON', the outlet functions similar to the other appliance outlets: it delivers output
power as long as the output converter does. When 'OFF' is selected, the outlet switches off. When the
option 'AUTO' is selected, the system asks for the 'Off autonomy time': the remaining runtime (in minutes)
at which, during a mains failure, the programmable output is automatically switched off until the mains
returns. This way less critical equipment (e.g. screens, printer) can be switched off automatically in order
to lengthen the remaining runtime.
Figure 6 shows an example. The total predicted runtime is 15 minutes, and the 'off autonomy time' has
been set on 5 minutes: the outlet switches off 5 minutes before the predicted end of autonomy.
As the load decreases when the outlet switches
off, the actual remaining autonomy at the 'outlet
off' moment (which was predicted at present
load) will be longer than the programmed 5minute period.
In configurations with small loads and large
battery capacities, i.e. very long runtimes, the
step size with which the runtime is counted
down can be longer than the programmed 'off
autonomy time' (see section 3.5). In this case
the programmable outlet will be switched off
when the remaining runtime is one step from
zero.
output
off
15
end of
autonomy
Example: suppose the runtime is counted down with 10 minute steps, and the 'off autonomy time' is set
as mentioned above. Despite of the 5-minute setting, the outlet will be switched off 10 minutes (= one
step) before end of autonomy.
If the step size does not exceed the 'off autonomy time', the programmable outlet will be switched off at
the programmed moment although the accuracies may not match. Example: 'off autonomy time' set at 14
minutes while the step size is 10 minutes, the outlet will indeed be switched off 14 minutes before the end
of the autonomy.
If the option 'AUTO' is selected the programmable outlet can still be switched off manually using the front
panel keys.
Each time the mains returns, the programmable outlet will always be switched on. Therefore do not use
this outlet to switch off equipment that should permanently remain off.
PB-AB@KN67I'B@A>
The frequency tracking rate is the maximum rate at which the UPS adjusts its output frequency to
fluctuations of the input frequency. If the UPS is not connected to a generator set the default setting may
be too high. Note that a change of the frequency tracking rate is coupled with a change of the tracking
range (see chapter 8, bypass).
(A@BA'@JAF7-A65>
The runtime, below which the UPS is inhibited to start up, can be set here. The UPS will first recharge its
batteries and start up as soon as the 'start up autonomy' is available. The setting can be bypassed (see
also 3.2.3). Calculation of the 'start up autonomy' is based on the assumption that the UPS supplies 100%
load.
OPM_NPE_XXX_2K0_4K0_1GB_V040
11
GE Digital Energy
!J]]>B'R>=@C
In case of low priority alarms (see 3.4.2.2) the buzzer will not immediately sound but only after a certain
delay in order to avoid frequent buzzer activity during momentary alarm situations (e.g. overload,
temperature, weak mains). The buzzer delay time does not affect buzzer operation during alarms with
high priority.
.@7IJ@I>
$7I=6EH
Changes the language of the screen messages: you can select English (default), German, French,
Spanish, Italian.
*F'=F@R'EHJARFO7
Setting ON means that the function is activated: the UPS will switch off during a mains failure when the
load is < 5% of the maximum load. Be careful with very small loads: e.g. a fax machine in stand-by mode
could be recognised by the UPS as a no-load situation.
!@AA>BC'K@D@K6AC
'''''''''''''W"H
In order to generate reliable runtime predictions the UPS needs to be informed about the total battery
capacity. The Ah value shown in the display is the programmed capacity and should indicate the capacity
of the standard internal battery plus the capacity of the battery extension pack(s).
!CD@EE'>7@?=>
'''''&$(
If the NetPro is supplied by a generator set, and the generator's frequency is often out of the UPS's input
tolerances, frequently occurring 'bypass error' alarms (see 3.4.2.2) will be the result. During these alarms
bypass operation is inhibited. To avoid this situation the bypass function can be disabled: the UPS
functions as a UPS without automatic bypass switch.
If NO is selected, i.e. if the bypass function is disabled, the default screen alternates every 10 seconds
with the following message, displayed during 2 seconds:
/"%*M*Z
!CD@EE'R6E@?=>R
+JADJA'QF=A@I>
'''''0123
The output voltage can be set to 220/230/240 Vac.
+JADJA'LB>^J>7KC
'''''82S]
The output frequency can be set to 50/60 Hz.
NOTE: The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the output
frequency is selectable 50/60Hz. If the unit is used as a frequency converter, the bypass function is no
longer available. As a result an audible alarm will be generated continuously (see 3.4.2.2 Bypass error).
To avoid this, we advise to disable the bypass (see above).
WARNING:
Changing of the output frequency can cause severe damage of equipment connected to
the appliance outlets of the UPS: Be sure that the new frequency is suitable for the
connected equipment!
OPM_NPE_XXX_2K0_4K0_1GB_V040
12
g
3.5
GE Digital Energy
Runtime: calculation and indication
The available runtime is displayed in the default screen, and is counted down during battery operation
until either the mains returns or the batteries are empty.
Normally, i.e. if the runtime is less than 100 minutes, the runtime is calculated in minutes, and the step
size of the changes is one minute. In case of small loads and/or battery extension packs the available
runtime can be substantially longer. The accuracy of the runtime calculations however is limited: approx
1% of the initial runtime.
For this reason the measuring unit and step size will change at longer runtimes: if for example the runtime
is between 200 and 500 minutes the step size is 5 minutes; if the runtime is > 5000 minutes the runtime is
calculated in hours and the step size is 2 hrs. The following table gives an overview:
Runtime Rt, in minutes
Unit
Step size
Rt < 100
minutes
1 minute
minutes
2 minutes
minutes
5 minutes
minutes
10 minutes
minutes
20 minutes
hours
1 hr
Rt 5000
hours
2 hrs
Please note that unit and step size do not change during countdown: the initial units and step sizes
remain unaltered, until eventually the batteries are empty.
If during battery operation the available runtime becomes less than the step size it will be shown as '< S',
where S is the step size. If for example the initial autonomy was 1200 minutes, i.e. between 1000 and
2000, the countdown occurs with steps of 20 minutes each, and during the last 20 minutes before the
batteries are empty the runtime will be displayed as '< 20 min'.
3.6
Other Features
3.6.1 Shutdown
Using communication capabilities, the computer can direct the UPS to turn itself off following controlled
shutdown of the system. Subsequently the UPS will remain off for at least 30 seconds. LED 'operation' will
go out. The unit will start up again as soon as the mains returns (and, if activated, the start-up runitme is
available).
3.6.2 Programmed shutdown
The UPS monitoring software allows you to program a 'sleep period' of the UPS by sending two
commands to the UPS:
- shut down after # minutes, and subsequently:
- shut down during # hours.
The first command indicates the period of time after which the UPS should 'fall asleep', the second
indicates the duration of the sleep period. After the first command LED 'prog shutdown' starts blinking and
the standard screen shows the time until sleep (see 3.4.1). In the 'sleep'-mode LED 'operation' is off, LED
'progr. shutdown' is on, and the LCD shows the remaining sleep time:
#65>'J7A6='O@N>_
SS_``_((
During the 'sleep period' the UPS is not completely switched off as it has to keep track of the remaining
sleep time. However, if a mains failure occurs during the sleep period and the battery capacity eventually
drops below 80% of the normal capacity, the UPS will automatically switch off in order to save battery
power. When the mains returns the UPS will start up automatically (as soon as the start-up runtime is
available, if this feature is activated). The programmed sleep time however is lost.
The programmed shutdown in progress can be cancelled: press the OK button during 10 seconds to
cancel shutdown and switch the UPS on.
OPM_NPE_XXX_2K0_4K0_1GB_V040
13
GE Digital Energy
PBF7AD@7>='A>EA
Key OK (19) confirms the selection. Subsequently all LEDs will blink, the buzzer will sound intermittently,
and all characters in the LCD will illuminate and gradually disappear: the upper row from the right, the
lower row from the left.
After succesful completion of the front panel test the LCD screen should display
PBF7AD@7>='A>EA
A>EA'+[
!@AA>BC'A>EA
(If no test has been performed since switch-on, the second line of this screen shows 'NO RESULT' until
push-button 'OK' is pressed).
Push-button OK (19) confirms the selection, and the screen shows:
!@AA>BC'A>EA
!JEC'A>EA67I
The test status (indicated by the second line) can be:
BUSY TESTING
V OUTPUT TOO LOW
BAD BATTERY
V BATT TOO LOW
TEST OK
=
=
=
=
=
testing
output voltage too low for succesful completion of the test
the batteries should be replaced
battery voltage too low to start the test
battery has been tested with positive result
OPM_NPE_XXX_2K0_4K0_1GB_V040
14
GE Digital Energy
G@=6?B@A>'?@AA
+[
The default setting of the capacity normally results in a reliable runtime prediction. Local circumstances
however (e.g. low ambient temperature) may cause the prediction to be unreliable. In this case you can
have the UPS to recalculate the battery capacity. The predicted runtime shown in the display is 10% lower
than calculated in order to balance out small changes in load, ambient temperature and battery condition.
In order to keep track of the capacity deterioration due to aging of the batteries, we advise to perform a
battery calibration test at least once per year.
During a battery calibration test the batteries will be discharged to 'battery low' alarm level (see section
3.4.2.3 'battery low'). The test will result in a new capacity indication in the second setup screen (see
3.4.3) and, after complete recharge, new runtime predictions. Please note that immediately after a battery
calibration test the expected runtime time is very short: allow the UPS to recharge its batteries.
3.6.6 Deep battery test
This test, initiated by UPS monitoring software, is identical to a 'battery calibration test' (see above).
Please refer to the manual of the appropriate monitoring software package for more information.
OPM_NPE_XXX_2K0_4K0_1GB_V040
15
GE Digital Energy
4 - Communication
4.1
The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication
between the UPS and the computer (UPS software required). The interface port is operative as soon as
the mains power cord is plugged into a live wall outlet, even if the UPS is switched off.
We strongly recommend to use only original GE Digital Energy software products in combination with
the interface port.
5 = COMMON
8 = UPS CONNECTED
Pin #
1
2
3
4
5
6
7
8
9
Function
RS232 input (UPS shutdown)
RS232 output
1)
General alarm
Plug and Play
Common
Bypass active
Battery low
UPS connected
Mains failure
fig. 7
MAINS FAILURE
5
PnP
DC
9
RS232
4
8
GENERAL ALARM
3
7
BATTERY LOW
2
6
1
BYPASS ACTIVE
DATA FROM
UPS
DATA TO UPS
DC
RS232
RS232
PORT
DC
RS232
REMOTE UPS
SHUT DOWN
MAX: +48V 100mA
1)
Active if the output voltage of the UPS is no longer guaranteed due to other circumstances than
already indicated by pin 6-7-9:
- Output converter overload
- Overtemperature (pre-)alarm
- Battery failure
- Fan failure
- High charger voltage
- Bypass out of limits
- Inverter shutdown (due to inverter failure or batt. failure)
4.2
The card is equipped with potential free change-over contacts for the following alarms:
mains failure
general alarm
battery low
bypass active
For more information please refer to the user manual that comes with the interface card.
4.3
This card allows the data interface to be connected directly to an Ethernet network.
For more information please refer to the user manual that comes with the interface card.
OPM_NPE_XXX_2K0_4K0_1GB_V040
16
GE Digital Energy
5 - Optional Features
Apart from the options described in 4.2 and 4.3 the following options are possible:
5.1
Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In this
case the UPS must be informed about the new total battery capacity to allow a reliable recalculation of the
available runtime (see section 3.4.3). Dependent of the charge condition of the new batteries the new
runtime calculations may temporarily be unreliable.
The additional batteries increase the runtime and recharging time for the unit, all other operational
information is the same as for standard models. It is not allowed to connect an external charger to the
UPS!
5.2
Units equipped with a temperature protected isolation transformer ("NetPro +") are housed in a larger
cabinet than the standard unit. The isolation transformer allows the output neutral to be connected to
- protective earth (default setting)
- the input neutral
or be isolated. Please contact your dealer.
5.3
If you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,
a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial in
and check the status of the UPS to perform remote diagnostics. This way service costs, specially in
remote areas, can be reduced considerably.
6 - Maintenance
6.1
General
The UPS is virtually maintenance free: take care of proper environmental conditions and keep air
inlets/outlets free of dust. Please read 2.1.
6.2
Batteries
The service life of the battery is from 3 to 6 years, depending on the operating temperature and on the
number of discharge cycles.
As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performed
regularly to ensure failsafe operation (see section 3.6.4). When the condition of the battery is critical, a
'replace battery' alarm will be activated (see 3.4.2.2). Have your dealer replace the batteries as soon as
possible.
NOTE: under certain circumstances a manual battery test can result in a false alarm: please see 3.6.4
'quick battery test'.
Regular deep battery tests are advised in order to re-calibrate the capacity of aging batteries. Sections
3.4.3 'battery capacity' and 3.6.5 give more information.
OPM_NPE_XXX_2K0_4K0_1GB_V040
17
GE Digital Energy
7 - Troubleshooting
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the thermal circuit breaker: it may be tripped. If so: reset it (see 1, fig.1) and be sure that the UPS is
not overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
www.gedigitalenergy.com.
PROBLEM
POSSIBLE CAUSE
SOLUTION
UPS overload
System failure
Overtemperature
See 3.4.2.3
Allow the UPS to cool down
Read 2.2
Connect line cord
UPS overtemperature
See 3.4.2.3
Allow UPS to cool down
See above
UPS overtemperature
See 3.4.2.3
Allow UPS to cool down
Programmed shutdown in
progress
See 3.6.2
See 3.6.1
OPM_NPE_XXX_2K0_4K0_1GB_V040
18
GE Digital Energy
8 - Specifications
NetPro model
2000
3000
4000
2000
3000
4000
1200
1800
2400
10
14
16
AC input voltage
AC input voltage range
:
:
:
:
:
:
:
:
220 - 240 V
100% load: 187 - 264 V
60% load: 160 - 264 V
30% load: 125 - 264 V
255 V (at any load)
187 V (at any load)
sinusoidal
1
50 or 60 Hz 10%
6.6
10.0
:
:
:
:
:
:
:
:
220/230/240 V (selectable)
1%
50 or 60 Hz 0.15% unless synchronized to the mains
sine wave
< 2% (typical 1.5%) with linear load
0.6
up to 6:1
max. 10 A per outlet
:
:
:
:
:
:
187 - 264 V
max. 2 or 10 Hz/sec.(selectable, factory setting 10Hz/sec)
2 Hz/sec
10 Hz/sec
nominal 2%
nominal 10%
< 7
< 10
< 1 msec.
:
:
:
:
:
:
:
:
:
:
:
:
:
72
108
120
6
9
10
sealed and maintenance free
3 - 6 years (depending on use)
1.5 A
2 - 6 hours for 80% capacity, std. battery
see 3.6.4
190
117
60
38
21
13
9
-
270
165
95
63
35
22
15
9
310
185
105
72
40
25
18
10
:
:
:
27
38
293x220x557
steel-plastic / IP20
42
Safety
Electromagnetic compatibility
Ambient temperature
Audible noise at 1 meter
:
:
:
:
Ratings
Voltage Amperes (VA)
with computer type load
Watts (W)
with resistive load
Input thermal circuit breaker (A)
Input converter
13.5
Output converter
AC output voltage
AC output voltage tolerance
Output frequency
Output waveform
Harmonic distortion
Power factor
Crest factor (peak to RMS current)
Capacity appliance outlets
Bypass
AC input voltage range
Frequency tracking rate
Frequency tracking rate
Frequency tracking range
Phase difference
Transfer time
Overload capability
The UPS is fully protected against overload
Overload behaviour:
on-line operation, bypass enabled
on-line operation, bypass disabled
battery operation, NP2000
battery operation, NP3000/4000
bypass operation
General
Weight (kg)
Dimensions (hxwxd, mm)
Enclosure / protection
Environment
OPM_NPE_XXX_2K0_4K0_1GB_V040
19