CUMULATIVE VOLTAGE DROP FOR SDB-P1

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P1

4C 150+1C 70

70

223.52

358.47

0.299

3.751

3.751

0.938

TCL
(kW)

OUTGOING FROM SDP-P1


1.1

SDB-P1 TO ATS-P1

4C 95+1C 50

10

83.43

133.80

0.423

0.566

4.317

1.079

1.2

SDB-P1 TO LPP-B6

4C 16+1C 16

24

19.88

31.88

2.120

1.622

5.374

1.343

1.3

SDB-P1 TO LPP-SRB

4C 16+1C 16

48

10.90

17.48

2.120

1.779

5.530

1.383

1.4

SDB-P1 TO LPP-A06-OD

4C 10+1C 10

30

3.05

4.89

3.330

0.489

4.240

1.060

1.5

SDB-P1 TO LPP-B8

4C 25+1C 16

107

20.90

33.52

1.370

4.913

8.665

2.166

1.6

SDB-P1 TO LPP-A08-OD

4C 10+1C 10

130

2.70

4.33

3.330

1.875

5.626

1.406

1.7

SDB-P1 TO LPP-B9

4C 16+1C 16

135

21.16

33.94

2.120

9.712

13.464

3.366

1.8

SDB-P1 TO WORKSHOP

4C 16+1C 16

105

10.00

16.04

2.120

3.570

7.321

1.830

1.9

SDB-P1 TO PLANT ROOM

4C 16+1C 16

130

20.00

32.08

2.120

8.840

12.591

3.148

1.10

SDB-P1 TO WATER FEATURE-7&18

4C 35+1C 16

50

31.50

50.52

1.011

2.554

6.31

1.576

OUTGOING FROM ESDB-P1


1.1.1

ESDB-P1 TO ELPP-B6

4C 16+1C 16

20

10.40

16.68

2.120

0.707

5.025

1.256

1.1.2

ESDB-P1 TO ELPP-SRB

4C 16+1C 16

47

11.60

18.60

2.120

1.854

6.171

1.543

1.1.3

ESDB-P1 TO ELPP-S-8A

4C 10+1C 10

10

4.97

7.97

3.330

0.265

4.583

1.146

1.1.4

ESDB-P1 TO ELPP-B8

4C 10+1C 10

110

3.80

6.09

3.330

2.232

6.550

1.637

1.1.5

ESDB-P1 TO ELPP-B9

4C 16+1C 16

130

9.16

14.69

2.120

4.049

8.366

2.092

1.1.6

ESDB-P1 TO FAN-B-4

4C 35+1C 16

60

30.00

48.11

1.011

2.919

7.236

1.809

1.1.7

ESDB-P1 TO PUMP-B-A6

4C 4+1C 4

120

2.00

3.21

8.260

3.179

7.497

1.874

1.1.8

ESDB-P1 TO PUMP-B-A7

4C 4+1C 4

108

2.00

3.21

8.260

2.861

7.179

1.795

1.1.9

ESDB-P1 TO PUMP-B-A8

4C 4+1C 4

120

1.50

2.41

8.260

2.384

6.702

1.675

1.1.10

ESDB-P1 TO PUMP-B-S1

4C 10+1C 10

80

8.00

12.83

3.330

3.418

7.735

1.934

CUMULATIVE VOLTAGE DROP FOR SDB-P1

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P1

4C 150+1C 70

70

239.22

383.65

0.299

4.015

4.015

1.004

TCL
(kW)

OUTGOING FROM SDP-P1


1.1

SDB-P1 TO ATS-P1

4C 95+1C 50

10

97.73

156.73

0.423

0.663

4.678

1.169

1.2

SDB-P1 TO LPP-B6

4C 16+1C 16

24

19.88

31.88

2.120

1.622

5.637

1.409

1.3

SDB-P1 TO LPP-SRB

4C 16+1C 16

48

10.90

17.48

2.120

1.779

5.794

1.448

1.4

SDB-P1 TO LPP-A06-OD

4C 10+1C 10

30

3.05

4.89

3.330

0.489

4.504

1.126

1.5

SDB-P1 TO LPP-B8

4C 25+1C 16

107

20.90

33.52

1.370

4.913

8.928

2.232

1.6

SDB-P1 TO LPP-A08-OD

4C 10+1C 10

130

2.70

4.33

3.330

1.875

5.889

1.472

1.7

SDB-P1 TO LPP-B9

4C 16+1C 16

135

22.56

36.18

2.120

10.355

14.370

3.592

1.8

SDB-P1 TO WORKSHOP

4C 16+1C 16

105

10.00

16.04

2.120

3.570

7.585

1.896

1.9

SDB-P1 TO PLANT ROOM

4C 16+1C 16

130

20.00

32.08

2.120

8.840

12.855

3.214

1.10

SDB-P1 TO WATER FEATURE-7&18

4C 35+1C 16

155

31.50

50.52

1.011

7.916

11.93

2.983

OUTGOING FROM ESDB-P1


1.1.1

ESDB-P1 TO ELPP-B6

4C 16+1C 16

20

10.40

16.68

2.120

0.707

5.385

1.346

1.1.2

ESDB-P1 TO ELPP-SRB

4C 16+1C 16

47

11.60

18.60

2.120

1.854

6.532

1.633

1.1.3

ESDB-P1 TO ELPP-S-8A

4C 10+1C 10

10

4.97

7.97

3.330

0.265

4.943

1.236

1.1.4

ESDB-P1 TO ELPP-B8

4C 10+1C 10

110

3.80

6.09

3.330

2.232

6.910

1.728

1.1.5

ESDB-P1 TO ELPP-B9

4C 16+1C 16

130

9.16

14.69

2.120

4.049

8.727

2.182

1.1.6

ESDB-P1 TO FAN-B-4

4C 35+1C 16

60

30.00

48.11

1.011

2.919

7.596

1.899

1.1.7

ESDB-P1 TO PUMP-B-A6

4C 10+1C 10

120

6.60

10.58

3.330

4.230

8.908

2.227

1.1.8

ESDB-P1 TO PUMP-B-A7

4C 10+1C 10

108

6.60

10.58

3.330

3.807

8.485

2.121

1.1.9

ESDB-P1 TO PUMP-B-A8

4C 10+1C 10

120

6.60

10.58

3.330

4.230

8.908

2.227

1.1.10

ESDB-P1 TO PUMP-B-S1

4C 10+1C 10

80

8.00

12.83

3.330

3.418

8.096

2.024

SHEET 5 OF 12

CUMULATIVE VOLTAGE DROP FOR SDB-P1

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P1

4C 150+1C 70

70

239.22

383.65

0.299

4.015

4.015

1.004

SDB-P1 TO ATS-P1

4C 95+1C 50

10

97.73

156.73

0.423

0.663

4.678

1.169

1.2

SDB-P1 TO LPP-B6

4C 16+1C 16

24

19.88

31.88

2.120

1.622

5.637

1.409

1.3

SDB-P1 TO LPP-SRB

4C 16+1C 16

48

10.90

17.48

2.120

1.779

5.794

1.448

1.4

SDB-P1 TO LPP-A06-OD

4C 10+1C 10

30

3.05

4.89

3.330

0.489

4.504

1.126

1.5

SDB-P1 TO LPP-B8

4C 25+1C 16

107

20.90

33.52

1.370

4.913

8.928

2.232

1.6

SDB-P1 TO LPP-A08-OD

4C 10+1C 10

130

2.70

4.33

3.330

1.875

5.889

1.472

1.7

SDB-P1 TO LPP-B9

4C 16+1C 16

135

22.56

36.18

2.120

10.355

14.370

3.592

1.8

SDB-P1 TO WORKSHOP

4C 16+1C 16

105

10.00

16.04

2.120

3.570

7.585

1.896

1.9

SDB-P1 TO PLANT ROOM

4C 16+1C 16

130

20.00

32.08

2.120

8.840

12.855

3.214

1.10

SDB-P1 TO WATER FEATURE-7&18

4C 35+1C 16

155

31.50

50.52

1.011

7.916

11.93

2.983

TCL
(kW)

OUTGOING FROM SDP-P1


1.1

OUTGOING FROM ESDB-P1


1.1.1

ESDB-P1 TO ELPP-B6

4C 16+1C 16

20

10.40

16.68

2.120

0.707

5.385

1.346

1.1.2

ESDB-P1 TO ELPP-SRB

4C 16+1C 16

47

11.60

18.60

2.120

1.854

6.532

1.633

1.1.3

ESDB-P1 TO ELPP-S-8A

4C 10+1C 10

10

4.97

7.97

3.330

0.265

4.943

1.236

1.1.4

ESDB-P1 TO ELPP-B8

4C 10+1C 10

110

3.80

6.09

3.330

2.232

6.910

1.728

1.1.5

ESDB-P1 TO ELPP-B9

4C 16+1C 16

130

9.16

14.69

2.120

4.049

8.727

2.182

1.1.6

ESDB-P1 TO FAN-B-4

4C 35+1C 16

60

30.00

48.11

1.011

2.919

7.596

1.899

1.1.7

ESDB-P1 TO PUMP-B-A6

4C 10+1C 10

120

6.60

10.58

3.330

4.230

8.908

2.227

1.1.8

ESDB-P1 TO PUMP-B-A7

4C 10+1C 10

108

6.60

10.58

3.330

3.807

8.485

2.121

1.1.9

ESDB-P1 TO PUMP-B-A8

4C 10+1C 10

120

6.60

10.58

3.330

4.230

8.908

2.227

1.1.10

ESDB-P1 TO PUMP-B-S1

4C 10+1C 10

80

8.00

12.83

3.330

3.418

8.096

2.024

SHEET 6 OF 12

CUMULATIVE VOLTAGE DROP FOR SDB-P2

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(A)
mV/A/m)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P2

4C 70+1C 35

130

62.07

99.54

0.556

7.195

7.195

1.799

10

25.52

40.93

1.370

0.561

7.756

1.939

TCL
(kW)

OUTGOING FROM SDP-P2


2.1

SDB-P2 TO ATS-P2

4C 25+1C 16

2.2

SDB-P2 TO LPP-B5

4C 16+1C 16

58

15.64

25.08

2.120

3.084

10.279

2.570

2.3

SDB-P2 TO LPP-B7

4C 16+1C 16

120

12.56

20.14

2.120

5.124

12.320

3.080

2.4

SDB-P2 TO LPP-A07-OD

4C 10+1C 10

110

6.20

9.94

3.330

3.642

10.837

2.709

2.5

SDB-P2 TO LPP-A05-OD

4C 10+1C 10

52

2.15

3.45

3.330

0.597

7.792

1.948

CUMULATIVE VOLTAGE DROP FOR ESDB-P2


1.2.1

ESDB-P2 TO ELPP-B5

4C 10+1C 10

58

2.60

4.17

3.330

0.805

8.561

2.140

1.3.1

ESDB-P2 TO ELPP-S-10A

4C 10+1C 10

12

5.62

9.01

3.330

0.360

8.116

2.029

1.3.2

ESDB-P2 TO ELPP-B7

4C 10+1C 10

126

2.92

4.68

3.330

1.965

9.721

2.430

1.3.3

ESDB-P2 TO PUMP-B-A5

4C 10+1C 10

54

9.00

14.43

3.330

2.595

10.351

2.588

1.3.4

ESDB-P2 TO ELPP-S-5A

4C 10+1C 10

12

5.38

8.63

3.330

0.345

8.101

2.025

SHEET 7 OF 12

CUMULATIVE VOLTAGE DROP FOR SDB-P3

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(A)
mV/A/m)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P3

4C 150+1C 70

153

123.69

198.37

0.299

9.075

9.075

2.269

SDB-P3 TO ATS-P3

4C 70+1C 35

10

64.98

104.21

0.556

0.579

9.654

2.414

3.2

SDB-P3 TO LPP-B3

4C 25+1C 16

139

16.88

27.07

1.370

5.155

14.230

3.557

3.3

SDB-P3 TO LP-A03-OD

4C 16+1C 16

84

23.13

37.09

2.120

6.606

15.681

3.920

3.4

SDB-P3 TO LPP-B4

4C 16+1C 16

30

13.20

21.17

2.120

1.346

10.421

2.605

3.5

SDB-P3 TO LPP-A04-OD

4C 10+1C 10

64

5.50

8.82

3.330

1.880

10.955

2.739

TCL
(kW)

OUTGOING FROM SDP-P3


3.1

CUMULATIVE VOLTAGE DROP FOR ESDB-P3


3.1.1

ESDB-P3 TO ELPP-B3

4C 10+1C 10

110

5.36

8.60

3.330

3.149

12.803

3.201

3.1.2

ESDB-P3 TO FAN-B-1

4C 35+1C 16

45

35.00

56.13

1.011

2.554

12.208

3.052

3.1.3

ESDB-P3 TO ELPP-S-6A

4C 10+1C 10

12

5.82

9.33

3.330

0.373

10.027

2.507

3.1.4

ESDB-P3 TO ELPP-B4

4C 10+1C 10

32

5.60

8.98

3.330

0.957

10.611

2.653

3.1.5

ESDB-P3 TO PUMP-B-A3

4C 10+1C 10

90

6.60

10.58

3.330

3.172

12.826

3.207

3.1.6

ESDB-P3 TO PUMP-B-A4

4C 10+1C 10

82

6.60

10.58

3.330

2.890

12.544

3.136

SHEET 8 OF 12

CUMULATIVE VOLTAGE DROP FOR SDB-P4

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P4

4C 95+1C 50

173

64.59

103.59

0.423

7.580

7.580

1.895

SDB-P4 TO ATS-P4

4C 50+1C 25

10

43.76

70.18

0.768

0.539

8.119

2.030

4.2

SDB-P4 TO LPP-B2

4C 16+1C 16

46

10.58

16.97

2.120

1.655

9.235

2.309

4.3

SDB-P4 TO LP-A02-OD

4C 16+1C 16

35

10.25

16.44

2.120

1.220

8.800

2.200

TCL
(kW)

OUTGOING FROM SDP-P4


4.1

CUMULATIVE VOLTAGE DROP FOR ESDB-P4


4.1.1

ESDB-P4 TO ELPP-B2

4C 16+1C 16

47

8.76

14.05

2.120

1.400

9.519

2.380

4.1.2

ESDB-P4 TO FAN-B-2

4C 35+1C 16

10

35.00

56.13

1.011

0.567

8.687

2.172

CUMULATIVE VOLTAGE DROP FOR SDB-P6

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P6

4C 300+1C 150

165

193.24

309.91

0.186

9.511

9.511

2.378

TCL
(kW)

OUTGOING FROM SDP-P6


5.1

SDB-P6 TO ATS-P6

4C 16+1C 16

10

17.74

28.45

2.120

0.603

10.114

2.529

5.2

SDB-P6 TO LPP-B23

4C 16+1C 16

54

13.00

20.85

2.120

2.387

11.898

2.974

5.3

SDB-P6 TO LP-A023-OD

4C 10+1C 10

65

5.00

8.02

3.330

1.736

11.247

2.812

5.4

SDB-P6 TO MCC-PUMP-BA1-C

4C 240+1C 120

80

157.50

252.59

0.213

4.304

13.815

3.454

SHEET 9 OF 12

CUMULATIVE VOLTAGE DROP FOR ESDB-P6


5.1.1

ESDB-P6 TO ELPP-B23

4C 10+1C 10

80

4.08

6.54

3.330

1.743

11.857

2.964

5.1.2

ESDB-P6 TO ELPP-A-9A

4C 10+1C 10

12

5.1.3

ESDB-P6 TO ELPP-HEX-BA1-A

4C 10+1C 10

25

5.82

9.33

3.330

0.373

10.487

2.622

7.84

12.57

3.330

1.047

11.161

2.790

CUMULATIVE VOLTAGE DROP FOR SDB-P5

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-05 TO SDB-P5

4C 185+1C 95

65

260.62

417.97

0.256

3.478

3.478

0.869

TCL
(kW)

OUTGOING FROM SDP-P5


2.1

SDB-P5 TO ATS-P5

4C 70+1C 35

10

74.26

119.09

0.556

0.662

4.140

1.035

2.2

SDB-P5 TO LPP-B1

4C 16+1C 16

12

18.56

29.77

2.120

0.757

4.235

1.059

2.3

SDB-P5 TO LP-A01-OD

4C 10+1C 10

65

6.55

10.50

3.330

2.274

5.751

1.438

2.4

SDB-P5 TO MCC-PUMP-BA1-A

4C 150+1C 70

97

146.25

234.55

0.299

6.803

10.280

2.570

2.5

SDB-P5 TO MCC-SW1

4C 16+1C 16

61

15.00

24.06

2.120

3.111

6.588

1.647

CUMULATIVE VOLTAGE DROP FOR ESDB-P5


2.1.1

ESDB-P5 TO ELPP-B1

4C 10+1C 10

10

4.92

7.89

3.330

0.263

4.402

1.101

2.1.2

ESDB-P5 TO FAN-B-3

4C 35+1C 16

45

35.00

56.13

1.011

2.554

6.693

1.673

2.1.3

ESDB-P5 TO ELPP-S-7A

4C 10+1C 10

10

5.62

9.01

3.330

0.300

4.440

1.110

2.1.4

ESDB-P5 TO ELPP-HEX-BA1-B

4C 10+1C 10

50

7.84

12.57

3.330

2.093

6.233

1.558

2.1.5

ESDB-P5 TO ELPP-HEX-BA1-A

4C 10+1C 10

75

7.68

12.32

3.330

3.076

7.216

1.804

2.1.6

ESDB-P5 TO PUMP-B-A1

4C 10+1C 10

30

6.60

10.58

3.330

1.057

5.197

1.299

2.1.7

ESDB-P5 TO PUMP-B-A2

4C 10+1C 10

15

6.60

10.58

3.330

0.529

4.668

1.167

SHEET 10 OF 12

CUMULATIVE VOLTAGE DROP FOR MCC-PUMP-BA1-A

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-05 TO SDB-P5

4C 185+1C 95

65

260.62

417.97

0.256

3.478

3.478

0.869

2.4

SDB-P5 TO MCC-PUMP-BA1-A

4C 150+1C 70

97

146.25

234.55

0.299

6.803

10.280

2.570

TCL
(kW)

OUTGOING FROM MCC-PUMP-BA1-A


2.4.1

MCC-PUMP-BA1-A TO PUMP-BAI-A1-1

2(3C 50)+2(1C 25)

20

30.00

48.11

0.768

0.739

11.019

2.755

2.4.2

MCC-PUMP-BA1-A TO PUMP-BAI-A1-2

2(3C 50)+2(1C 25)

15

30.00

48.11

0.768

0.554

10.834

2.709

2.4.3

MCC-PUMP-BA1-A TO PUMP-BAI-A1-3

2(3C 50)+2(1C 25)

10

30.00

48.11

0.768

0.370

10.650

2.662

2.4.4

MCC-PUMP-BA1-A TO PUMP-BAI-A2-1

2(3C 16)+2(1C 16)

20

18.75

30.07

2.120

1.275

11.555

2.889

2.4.5

MCC-PUMP-BA1-A TO PUMP-BAI-A2-2

2(3C 16)+2(1C 16)

15

18.75

30.07

2.120

0.956

11.236

2.809

2.4.6

MCC-PUMP-BA1-A TO PUMP-BAI-A2-3

2(3C 16)+2(1C 16)

10

18.75

30.07

2.120

0.637

10.918

2.729

SHEET 11 OF 12

CUMULATIVE VOLTAGE DROP FOR MCC-PUMP-BA1-B

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-05 TO MCC-PUMP-BA1-B

4C 300+1C 150

33

281.25

451.05

0.186

2.769

2.769

0.692

TCL
(kW)

OUTGOING FROM MCC-PUMP-BA1-B


2.4.1

MCC-PUMP-BA1-B TO PUMP-BAI-B1-1

2(3C 70)+2(1C 35)

20

56.25

90.21

0.556

1.003

3.772

0.943

2.4.2

MCC-PUMP-BA1-B TO PUMP-BAI-B1-2

2(3C 70)+2(1C 35)

15

56.25

90.21

0.556

0.752

3.521

0.880

2.4.3

MCC-PUMP-BA1-B TO PUMP-BAI-B1-3

2(3C 70)+2(1C 35)

10

56.25

90.21

0.556

0.502

3.270

0.818

2.4.4

MCC-PUMP-BA1-B TO PUMP-BAI-B2-1

2(3C 50)+2(1C 25)

20

37.50

60.14

0.768

0.924

3.692

0.923

2.4.5

MCC-PUMP-BA1-B TO PUMP-BAI-B2-2

2(3C 50)+2(1C 25)

15

37.50

60.14

0.768

0.693

3.461

0.865

2.4.6

MCC-PUMP-BA1-B TO PUMP-BAI-B2-3

2(3C 50)+2(1C 25)

10

37.50

60.14

0.768

0.462

3.230

0.808

CUMULATIVE VOLTAGE DROP FOR MCC-PUMP-BA1-C

No.
LENGTH
OF
(M)
RUNS

LOAD
APPROPRIATE
CUMULATIVE CUMULATIVE
CURRENT
VOLTAGE
VOLTAGE
VOLTAGE
% VOLTAGE
IN AMPS
DROP ( IN
DROP (V)
DROP
DROP
(I)
mV/A/M)

SL.
No.

CABLES BETWEEN

PROPOSED
CABLE SIZE IN
(mm2)

MDB-11 TO SDB-P6

4C 300+1C 150

165

193.24

309.91

0.186

9.511

9.511

2.378

5.4

SDB-P6 TO MCC-PUMP-BA1-C

4C 240+1C 120

80

157.50

252.59

0.213

4.304

13.815

3.454

TCL
(kW)

OUTGOING FROM MCC-PUMP-BA1-C


5.4.1

MCC-PUMP-BA1-C TO PUMP-BAI-C1-1

2(3C 70)+2(1C 35)

20

30.00

48.11

0.556

0.535

14.350

3.588

5.4.2

MCC-PUMP-BA1-C TO PUMP-BAI-C1-2

2(3C 70)+2(1C 35)

15

30.00

48.11

0.556

0.401

14.216

3.554

5.4.3

MCC-PUMP-BA1-C TO PUMP-BAI-C1-3

2(3C 70)+2(1C 35)

10

30.00

48.11

0.556

0.268

14.083

3.521

5.4.4

MCC-PUMP-BA1-C TO PUMP-BAI-C2-1

2(3C 16)+2(1C 16)

20

22.50

36.08

2.120

1.530

15.345

3.836

5.4.5

MCC-PUMP-BA1-C TO PUMP-BAI-C2-2

2(3C 16)+2(1C 16)

15

22.50

36.08

2.120

1.147

14.963

3.741

SHEET 12 OF 12