Você está na página 1de 1

PROJECT : PROPOSED GROUP HOUSING (AMBROSIA) FOR AJNARA AT SECTOR 118, NOIDA

WATER REQUIREMENT CALCULATION BASED ON 135 LPCD (Phase I) Date : 09 Apr, 2014
Design Assumption: 5 Pax for 2 & 3 BHK; Since Project has mix of 1765 Units of 2 & 3 BHK Type , we have concisdred Occupancy as 5 Pax for respective Unit. This may be reviewed for
acceptance.
OHT requirement 33% of
FLOW TO STP OHT IN CUM
TOTAL WATER the total volume
FLUSHING cold water domestic Hot water Domestic
No Of Total REQUIREMENT
S.NO. DESCRIPTION PAX/Unit DOMESTIC FLUSHING FLUSHING DOMESTIC
Units PAX TOTAL FLUSHING DOMESTIC FIRE
@85% @ 100% @33% @33%

LPCD LPD LPCD LPD LPCD LPD LPD LPD LPD LPD LPD LPD CUM CUM CUM

1 Tower AM-A 191 5 955 45 42975 70 66850 20 19100 128925 73058 42975 116033 14181.75 22060.5 15 23 25

2 Tower AM-B 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

3 Tower AM-C 191 5 955 45 42975 70 66850 20 19100 128925 73058 42975 116033 14181.75 22060.5 15 23 25

4 Tower AM-D 191 5 955 45 42975 70 66850 20 19100 128925 73058 42975 116033 14181.75 22060.5 15 23 25

5 Tower AM-E 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

6 Tower AM-F 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

7 Tower AM-G 191 5 955 45 42975 70 66850 20 19100 128925 73058 42975 116033 14181.75 22060.5 15 23 25

8 Tower AM-H 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

9 Tower AM-I 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

10 Tower AM-J 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

11 Tower AM-K 143 5 715 45 32175 70 50050 20 14300 96525 54698 32175 86873 10617.75 16516.5 11 17 25

12 Visitors @10% of Total PAX which is for 8825 Pax * - - 883 45 39735 70 61810 20 17660 119205 67550 39735 107285 13112.55 20397.3 This quantity is overall distributed in
13 Service Persons @1 for 10 flats * - - 177 15 2655 30 5310 7965 4514 2655 7169 876.15 1752.3 OH Diversity Capacity

Community Center/Convenient Shopping (presently


14 calculated on Flat Basis and to be checked on Area/ 0 0
Occupancy Basis later) *
a Floating Population - - 200 5 1000 10 2000 0 3000 1700 1000 2700 330 660
3 2 5
b Fixed Population (Operation & Maintenance Staff) - - 30 15 450 30 900 0 1350 765 450 1215 148.5 297

A Total 1765 10115 440965 687770 194160 1322895 749641 440965 1190606

15 General Filter Back Wash - 25000 25000 25000 25000

16 Swimming Pool Make-up & Filter Back Wash 0 10000 10000 7000 7000

17 Water Body Make-up - 5000 5000


Irrigation water requirement for landscape/green area x
18 200000 - 200000
6Litr/SQM
19 Makeup Water Requirement for DG Cooling Tower 50000 0 50000

B Total 690965 727770 194160 1612895 1222606

Grand Total in CU-M (A+B) 691 728 195 1613 1223


Flushing Fresh
Fresh Hot Gross Water Flow to
water Cold
Remarks From STP Water
Water Demand Demand 1625 STP 1250
200 KLD KLD KLD
700 KLD 750 KLD

Note:- * = To be reviewed by the Client