Cooling Systems
2 Rittal LCP
Rittal The System.
The whole is more than the sum of its parts.
The same is true of Rittal The System. With this in mind, we have bundled
our innovative enclosure, power distribution, climate control and IT infrastructure
products together into a single system platform. Complemented by our extensive
range of software tools and global service, we create unique added value for all
industrial applications: Production plant, test equipment, facility management and
data centres. Following our simple principle, faster better worldwide, we
combine innovative products with efficient service for optimum results.
Faster with our Rittal The System. range of modular solutions, which
guarantees fast planning, assembly, conversion and commissioning thanks to system
compatibility.
Better by being quick to translate market trends into products. In this way,
our innovative strength helps you to secure competitive advantages.
Worldwide thanks to global networking across 150 locations. Rittal has over
60 subsidiaries, more than 250 service partners and over 1,000 service engineers
worldwide. For more than 50 years, we have been on hand to offer advice, assis-
tance and product solutions.
Rittal LCP 3
1
5
3
7
2
4 Rittal LCP
IT cooling.
System layout
1 Air-cooled condenser
2 IT chiller
3 IT chiller for redundant application
4 LCP Rack CW
5 LCP T3+
6 LCP Passive
9
7 LCP Inline CW, set forward
8 LCP Inline flush CW, flush
9 LCP Rack DX
10 LCP Inline DX
10
10
Rittal LCP 5
3 fans
4 fans
5 fans
6 fans
6 Rittal LCP
Better.
Easily achieve 50% energy savings! Identical volumetric flow with 3 6 fans
Thanks to intelligent control and flexible configura- Reduced noise levels with lower speeds
tion with additional fans, energy savings of up to Short amortisation period
50% are easily achieved with the new LCP gener-
ation, at the same volumetric flow and constant
cooling output.
Rittal LCP 7
Water-based cooling solution
Rack cooling
Data centres support corporate processes at ever-higher outputs.
Power supply LCP CW generation The packing density in computer systems is increasing, and processor
capacity is growing. This leads to a continuous rise in heat develop-
ment.
A Keep temperatures at a constant level with the highly efficient Rittal
Liquid Cooling Packages (LCP). With optimised operating costs, our
A LCPs precisely and effortlessly dissipate heat losses of up to 24 kW
per enclosure.
B B
LCP Rack T3+, CW
Rack T3+ Redundant heat exchanger unit with two active water circuits
Redundant
(A/B medium supply)
Redundant coolant supply Redundant power infeed (A/B power supply) with automatic
power supply
changeover in case of an emergency
Fully redundant cooling output of 24 kW
Redundant fan design
Integrated controller with its own web server for network and
BMS interfaces
Auto-load balancing function
Auto-recovery function
Energy saving with high water inlet temperatures (more free cooling)
Rack CW Minimised operating costs with efficient EC fan technology
Integration into RiZone (data centre management software)
Inline CW
8 Rittal LCP
Water-based cooling solution
Rittal LCP 9
Coolant-based cooling solution
Rack cooling
10 Rittal LCP
Coolant-based cooling solution
Suite cooling
Rittal LCP 11
Water-based fanless cooling solution
Rack cooling
The fans in the IT equipment independently guide the warm air over
the high-capacity heat exchanger. The entire data centre functions
as a cold aisle, and there is homogeneous temperature distribution.
The LCP Passive creates a very large, effective heat exchanger
surface area in the data centre which facilitates high water inlet tem-
peratures and a high proportion of free cooling.
12 Rittal LCP
LCP Liquid Cooling Package CW
Benefits: Box-type plug-in fan units con- Monitoring: Application and mode
Maximum energy efficiency figurable as n+1 redundancy Monitoring of all system-relevant of operation:
thanks to EC fan technology Standard 3-phase connection parameters such as: The LCP draws in the air at the
and IT-based control for electrical redundancy Server air intake temperature sides at the rear of the server
Minimal pressure loss at the air With redundant temperature Server waste air temperature enclosures, cools it using high-
end, which in turn minimises sensor integrated at the air end Water inlet/return temperature performance compact impellers,
the power consumption of the as standard Water flow and blows the cooled air back
fans The separation of cooling and Cooling output into the front part of the server
Optimum adaptability thanks to rack prevents the ingress of Fan speed enclosure at the sides.
dynamic, continuous control of water into the server enclosure Leakage
Colour:
the cold water volume flow Up to 55 kW cooling output on Optional sensors
RAL 7035
Using high water inlet tempera- a footprint of just 0.36 m Direct connection of the unit
Special colours available
tures increases the proportion Minimal area load thanks to via SNMP over Ethernet
on request
of indirect free cooling, which low weight Integration into RiZone (data
in turn reduces operating costs Touchscreen display may be centre management software) Protection category:
Targeted cooling output thanks retrofitted IP 40 to IEC 60 529
to modular box-type plug-in
Technical information:
fan units
Available on the Internet.
Photo shows a configuration
example with equipment not
included in the scope of supply.
Benefits: Box-type plug-in fan units con- Monitoring: Application and mode
Maximum energy efficiency figurable as n+1 redundancy Monitoring of all system-relevant of operation:
thanks to EC fan technology Standard 3-phase connection parameters such as: The LCP is designed for siting
and IT-based control for electrical redundancy Server air intake temperature within a bayed enclosure suite.
Minimal pressure loss at the air With redundant temperature Server waste air temperature The hot air is drawn in from the
end, which in turn minimises sensor integrated at the air end Water inlet/return temperature room or hot aisle at the rear of the
the power consumption of the as standard Water flow device and expelled at the front
fans The separation of cooling and Cooling output into the cold aisle after cooling.
Optimum adaptability thanks to rack prevents the ingress of Fan speed The LCP achieves maximum per-
dynamic, continuous control of water into the server enclosure Leakage formance and efficiency in con-
the cold water volume flow Up to 55 kW cooling output on Optional sensors junction with aisle containment.
Using high water inlet tempera- a footprint of just 0.36 m Direct connection of the unit via A raised floor is not required.
tures increases the proportion Minimal area load thanks to SNMP over Ethernet
Colour:
of indirect free cooling, which low weight Integration into RiZone (data
RAL 7035
in turn reduces operating costs Touchscreen display may be centre management software)
Special colours available
Targeted cooling output thanks retrofitted
Note: on request
to modular box-type plug-in
Height 2200 mm available on
fan units Protection category:
request.
IP 40 to IEC 60 529
Photo shows a configuration
Technical information:
example with equipment not
Available on the Internet.
included in the scope of supply.
Rittal LCP 15
LCP Liquid Cooling Package CW
Benefits: The LCP does not have its own Application and mode Colour:
High cooling output of 20 kW fan of operation: RAL 7035
in a minimal space Maximum energy efficiency, Air/water heat exchanger
Approvals:
Easily exchanged for the as there is no electrical power mechanically integrated into a rear
Available on the Internet.
standard rear door of the consumption whatsoever door for server enclosures. The
server enclosure 482.6 mm (19) equipment built
Retrofitting is not a problem into the server enclosure must
A door opening angle of 120 have suitable airflow capabilities in
allows rear access to the order to route the heated waste
server enclosure and makes air through the heat exchanger
assembly and configuration rear door. The waste air is cooled
inside the enclosure easier down to room temperature. The
heat energy absorbed by the
water is transported to the exter-
nal cold water supply, where it is
cooled back down to the required
inlet temperature.
16 Rittal LCP
LCP Liquid Cooling Package DX
LCP Rack/Inline DX
Installation in bayed enclosure suite Flush/Rack DX Flush/Inline DX
Cooling medium R410a R410a R410a R410a
Model No. 3311.410 3311.420 3311.430 3311.440
380 V AC, 3~, 50 380 V AC, 3~, 50 380 V AC, 3~, 50 380 V AC, 3~, 50
Rated operating voltage V, Hz
480 V AC, 3~, 60 480 V AC, 3~, 60 480 V AC, 3~, 60 480 V AC, 3~, 60
Dimensions mm W x H x D 300 x 2000 x 1000 300 x 2000 x 1200 300 x 2000 x 1000 300 x 2000 x 1200
Number of fans 4 4 4 4
Air throughput of fans 4800 m3/h 4800 m3/h 4800 m3/h 4800 m3/h
Cooling output 12 kW 12 kW 12 kW 12 kW
Duty cycle % 100 100 100 100
Type of connection (electrical) Connection clamp Connection clamp Connection clamp Connection clamp
Fans may be exchanged with the system operational
EC fan
RAL 7035 RAL 7035
Colour
Special colours available on request Special colours available on request
Linear fan control Linear fan control
Temperature control
Inverter-regulated compressor Inverter-regulated compressor
Condenser unit 3311.360 3311.360
SNMP card 3311.320 3311.320
Included with the supply
Rittal LCP 17
Accessories for LCP CW/DX
18 Rittal LCP
Accessories for LCP CW/DX
The LCP 3311.130/ To achieve the max. The LCP 3311.260/.560 To achieve the max.
.230/.530 (max. 30 kW) cooling output of 30 kW, (max. 55 kW) is sup- cooling output of 55 kW,
is supplied with one fan the customer/service plied with four fan mod- the customer/service
module as standard. needs to install two ules as standard. needs to install two
additional fan modules. additional fan modules.