Liebert PDX and Liebert PCW Thermal Management Systems

System Design Manual17-29kW, 5-8 Tons, Upflow and Downflow, 60Hz


TABLE OF CONTENTS
LIEBERT PDX AND LIEBERT PCW NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0 LIEBERT PDX AND LIEBERT PCW CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1 Cooling configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Blower configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 LIEBERT PDX/PCW CAPACITY DATA60HZ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3.0 DIMENSIONAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.1 Floor Stand Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.2 Plenum Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.0 HEAT REJECTIONLIEBERT MC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.0 HEAT REJECTIONDRYCOOLERS AND PUMPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
5.1 Pump Packages and Expansion Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.0 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.1 Electrical Field ConnectionsLiebert MC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.2 Standard Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.3 Electrical DataLiebert MC Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
6.3.1 Wye- vs. Delta-Connected Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4 Standard Electrical Connections, Liebert MC, Premium Efficiency Control . . . . . . . . . . . . 41
6.5 Electrical DataDrycoolers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.0 PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
8.0 GUIDE SPECIFICATIONSNOMINAL 17, 18, 23 OR 29KW THERMAL MANAGEMENT
SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
1.0 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
2.0 PRODUCT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
3.0 EXECUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

i
ii
Liebert PDX and Liebert PCW Nomenclature

LIEBERT PDX AND LIEBERT PCW NOMENCLATURE


Model Number Part 1/2 Model Details Part 2/2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
P X 0 2 9 U A 1 A D H E 2 8 0 1 P L 5 F P A 1 2 3
Digit 1, 2 = Product Family Digit 14 = Air filter
PX = Liebert PDX (DX) 8 = MERV 8, 2" (with Clogged Filter Sensor)
PW = Liebert PCW (CW) 9 = MERV 11, 2" (with Clogged Filter Sensor)
Digit 3, 4, 5 = Cooling Capacity, kW Digit 15 Coil, Valve & Pressure Options
Nominal Sensible Capacity, kW 0 = Air-Cooled, no valve
Digit 6 = Air Discharge 1 = Standard Pressure, 2 Way MBV (condenser valve)
U = Upflow with front air return 2 = High Pressure, 2 Way MBV (condenser valve) 1
C = Upflow with bottom air return 7 = Standard Pressure, 3 Way MBV (condenser valve)
D = Downflow - discharge into raised floor 8 = High Pressure, 3 Way MBV (condenser valve) 1
H = Downflow with front air discharge B = Standard Pressure, Dual Cool (Air-cooled)
1 = Downflow with front and right side discharge E = High Pressure, Dual Cool (Air-Cooled)
2 = Downflow with front and right and left side discharge Digit 16 = Enclosure options
3 = Downflow with front and left side discharge 1 = No options
Digit 7 = System Type C = Double-skin panels
A = Air-Cooled 3 = IBC/OSHPD bracing 2
W = Water/Glycol-Cooled 8 = Double skin panels and IBC/OSHPD 2
G = GLYCOOL Digit 17 = High-Voltage Options
C = Chilled Water M = Locking Disconnect (65kA) No condensate pump
D = Dual Cool (Air-Cooled + FC Coil - 3-Way FC Valve) P = Locking Disconnect (65kA) with condensate pump
H = Dual Cool (Water/Glycol-Cooled + FC Coil - 3-Way FC Valve) Digit 18 = Low-Voltage Option Packages
2 = Dual Cool (Air-Cooled + FC Coil - 2Way FC Valve) 0 = None
3 = Dual Cool (Water/Glycol-Cooled + FC Coil - 2-Way FC Valve) L = Terminal Package
Digit 8 = Airflow (fan type) H = Reheat & Humidifier Lockout
1 = EC plug fans R = Remote Humidity Contact
Digit 9 = Power Supply C = Term. Pkg. and R/H lockout
A = 460V / 3ph / 60Hz D = Term. Pkg. and remote humidifier contact
B = 575V / 3ph / 60Hz E = Term. Pkg. and R/H lockout and remote humidifier contact
C = 208V / 3ph / 60Hz F = Remote humidifier contact plus R/H lockout
D = 230V / 3ph / 60Hz Digit 19 = Monitoring Cards
2 = 380 / 3ph / 60Hz 0 = No Cards
Digit 10 = Cooling System U = One Liebert IntelliSlot IS-UNITY-DP Card
S = Standard Scroll w/TXV (no sound jacket) C = One Liebert IntelliSlot IS-485EXI
D = Digital Scroll w/TXV (no sound jacket) 6 = One IS-Unity-DP and IS-485EXI
P = Digital Scroll w/EEV (no sound jacket) 3 7 = Two Liebert IntelliSlot IS-UNITY-DP Cards
8 - Digital Scroll with TXV & Sound Jacket Digit 20 = Sensors
9 - Digital Scroll with EEV & Sound Jacket 3 0 = None
2 = Chilled Water - 2-Way Standard Pressure S = Smoke Sensor
3 = Chilled Water - 3-Way Standard Pressure H = High-Temperature Sensor
1 = Chilled Water - 2-Way High Pressure F = Smoke and High-Temperature Sensors
T = Chilled Water - 3-Way High Pressure C = Compressor Overload Sensor
Digit 11 = Humidification A = Smoke and Compressor Overload Sensors
0 = No humidifier D = High-Temperature Compressor Overload Sensors
H = Infrared Humidifier K = Smoke, High-Temperature Compressor Sensors
S = Steam Gen Canister Humidifier Digit 21 = Packaging
Digit 12 = Display P = Domestic
E = Large Display w/ Supply Air Sensor C = Wood Crate Export
Digit 13 = Reheat Digit 22 = Configuration code
0 = No reheat A = No SFAs (An Alpha except S)
2 = Electric reheat (Two-Stage) S = SFA
4 = Hot Water Reheat (CW only) Digit 23-25 = Factory Configuration Number
Note: The 14-digit model number consists of the first 10 digits and last 1. High-pressure MBV also results in high pressure FC valve.
four digits of the configuration number. 2. Consult Factory for IBC/OSPHD option availability.
3. Consult Factory for EEV option availability

1 Liebert PDX and Liebert PCW


Liebert PDX and Liebert PCW Configurations

1.0 LIEBERT PDX AND LIEBERT PCW CONFIGURATIONS

1.1 COOLING CONFIGURATIONS

AIR-COOLED
Air-cooled unit piping is
spun closed from the factory
and contains a nitrogen
holding charge. Each
installation requires field-
supplied refrigerant and
piping to a condenser.

GLYCOL-COOLED
Glycol-cooled units are factory-charged and tested.
Field-supplied and field-installed piping is required
from the unit to the drycooler and pump package.

GLYCOOL-INTEGRATED FLUID ECONOMIZER


GLYCOOL units are factory-charged and tested. Field-supplied
and field-installed piping is required from the unit to the
drycooler and pump package. An additional Liebert Economizer
coil is included for use when fluid temperatures are sufficiently
low (below room temperature). Economizer cooling is provided
by circulating cold glycol through this second coil, reducing or
WATER-COOLED
eliminating compressor operation.
Water-cooled units are factory-charged and
tested. Field-supplied and field-installed
water piping is required from the unit to the
cooling tower.

DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.

Liebert PDX and Liebert PCW 2


Liebert PDX and Liebert PCW Configurations

1.2 Blower configurations


Figure 1 Downflow, discharge into raised floor

Return Air
Filter

Front

Coil

Raised Blower
Floor

Floor
Stand
Supply (optional)
Air

Bottom Supply

3 Liebert PDX and Liebert PCW


Liebert PDX and Liebert PCW Configurations

Figure 2 Downflow, front air discharge models

Return Air
Filter

Front

Coil

Supply
Air
Blower

Floor

Front Supply
Applicable to Installations
Without Raised Floors

Figure 3 Upflow, front return models

Supply Air
Top Supply

Blower
Front

Coil

Filter

Return
Air

Liebert PDX and Liebert PCW 4


Liebert PDX and Liebert PCW Configurations

Figure 4 Upflow, bottom rear return, with rear return floor stand
Supply Air

Top Supply

Blower

Front

Coil

Filter Return
Air

5 Liebert PDX and Liebert PCW


Liebert PDX/PCW Capacity Data60Hz

2.0 LIEBERT PDX/PCW CAPACITY DATA60HZ


Table 1 Liebert PDX air-cooled capacity data
Model Size PX018 PX023 PX029
Net Capacity, kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Standard and Digital Compressors
85 F DB, 65 F WB (33% RH), 120F SCT
Total, kW (kBTUH) 20.5 (69.9) 26.2 (89.4) 33.0 (112.6)
Sensible, kW (kBTUH) 20.5 (69.9) 26.2 (89.4) 32.9 (112.3)
75 F DB, 61 F WB (45% RH), 120F SCT
Total, kW (kBTUH) 17.7 (60.4) 22.9 (78.1) 28.9 (98.7)
Sensible, kW (kBTUH) 17.7 (60.4) 22.5 (76.8) 28.6 (97.6)
Fan Data
Standard Airflow, CFM (m3h) 1 2800 (4760) 3500 (5950) 4300 (7310)
Standard Fan Motor, kW (hp) 3.1 (4.2)
Standard Fan Motor with Dual Cool, kW (hp) 3.1 (4.2) 3.6 (4.8)
External Static Pressure, in. WG (Pa) 0.2 (50)
Evaporator Coil
Face Area, ft2 (m2), Without GLYCOOL or Dual Cool 9.9 (0.92)
DX Coil Rows 3 4
Face Velocity Without Econ-O-Coil, FPM (m/s) 283 (1.4) 354 (1.8) 434 (2.2)
Face Area, ft2 (m2), With GLYCOOL or Dual Cool 9.4 (0.87)
GLYCOOL or Dual Cool Rows 4
Face Velocity With Econ-O-Coil, FPM (m/s) 298 (1.5) 372 (1.9) 457 (2.3)
Electric Reheat (Two-Stage)
Capacity, kW (BTUH), Including Motor Heat 13.6 (46.4) 13.9 (47.5) 15.1 (51.6)
Infrared Humidifier
Capacity, lb/hr (kg/hr) 7.7 (3.5)
Steam Generating Humidifier
Capacity, lb/hr (kg/hr) 10.8 (4.9)
Condensate Pump - Dual Float Type
Capacity, ft WG @ 5gpm (18.9 l/m) 45@208V, 48@230V, 40@460V
Filter Section - MERV rating per ASHRAE 52.2 - 2007 - Deep Pleated Disposable Type
Standard 2" (51mm) Filter Rating MERV 8 Pleated Filter
Optional 2" (51mm) Filter Rating MERV11 Pleated Filter
Quantity 1 1 1
Nominal Size, in. (mm) 29.5 x 28.5 (749 x 724)
Effective Surface Area, ft2 (m2) 5.8 (0.54)
Piping Connection Sizes
Hot Gas Line, in. 5/8 7/8
Liquid Line, in. 5/8
Humidifier Supply Line, in. 1/4
Condensate Drain Line, in. 3/4

Liebert PDX and Liebert PCW 6


Liebert PDX/PCW Capacity Data60Hz

Table 1 Liebert PDX air-cooled capacity data (continued)


Model Size PX018 PX023 PX029
Outdoor Air-Cooled Condenser, Standard 95F (35F) Ambient Selection
Condenser Match-Up, Air-Cooled 95F (35C) Ambient and 85F Return Air
Model (R-410A) Refrigerant MCS028 MCM040 MCL055
Number of Fans 1 1 1
Hot Gas Line, in. 7/8 1-1/8
Liquid Line, in. 5/8 7/8
Dual-Cool Unit Capacity Using Econ-O-Coil, (Four-Pipe System) with Water in Econ-O-Coil Circuit)
85F DB, 65F WB (33% RH), 45F EWT, 55 F LWT
Total, kW (kBTUH) 28.9 (98.7) 32.3 (110.3) 37.0 (126.4)
Sensible, kW (kBTUH) 27.5 (93.9) 30.6 (104.8) 35.2 (120.2)
Flow Rate, GPM (l/m) 21.6 (81.6) 21.6 (81.6) 28.7 (108.6)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
75F DB, 61F WB (45% RH), 45F EWT, 55F LWT
Total, kW (kBTUH) 17.7 (60.4) 22.1 (75.5) 24.8 (84.7)
Sensible, kW (kBTUH) 16.8 (57.4) 21.0 (71.7) 23.6 (80.6)
Flow Rate, GPM (l/m) 19.7 (74.4) 19.5 (73.8) 22.0 (83.4)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
Fluid Volumes and Piping Connection Sizes
Econ-O-Coil, gal (L) 2.3 (8.6) 2.7 (10.1)
Econ-O-Coil Water Supply and Return, in. OD Copper 1-1/8
Unit Weights
Air-Cooled, Dry Weight, lb (kg) 670 (304) 700 (317)
Air Cooled with Dual Cool, Dry Weight, lb (kg) 750 (340) 790 (358)
1. Airflow data rated with 2" MERV 8 filter, rated per ASHRAE 52.2-2007.
2. The net capacity data has fan motor heat factored in for all ratings.
3. Capacity data is factory-certified to be within 5% tolerance.

7 Liebert PDX and Liebert PCW


Liebert PDX/PCW Capacity Data60Hz

Table 2 Liebert PDX water-cooled data


Model Size PX018 PX023 PX029
Net Capacity, kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Standard and Digital Compressors
85 F DB, 65 F WB (33% RH), 105F SCT
Total kW (kBTUH) 21.8 (74.4) 27.7 (94.5) 35 (119.5)
Sensible kW (kBTUH) 21.8 (74.4) 27.7 (94.5) 35 (119.5)
75 F DB, 61 F WB (45% RH), 105F SCT
Total, kW (kBTUH) 19.3 (65.9) 25.1 (85.6) 31.3 (106.9)
Sensible kW (kBTUH) 18.0 (61.4) 23.4 (79.8) 29.9 (102.0)
Fan Data
Standard Airflow, CFM (m3h) 1 2800 (4760) 3500 (5950) 4300 (7310)
Standard Fan Motor, kW (hp) 3.1 (4.2)
Standard Fan Motor with Dual Cool, kW (hp) 3.1 (4.2) 3.6 (4.8)
External Static Pressure, in. WG (Pa) 0.2 (50)
Evaporator Coil
Face Area, ft2 (m2), Without GLYCOOL or Dual Cool 9.9 (0.92)
DX Coil Rows 3 4
Face Velocity Without Econ-O-Coil, FPM (m/s) 283 (1.4) 354 (1.8) 434 (2.2)
Face Area, ft2 (m2), With GLYCOOL or Dual Cool 9.4 (0.87)
GLYCOOL or Dual Cool Rows 4
Face Velocity With Econ-O-Coil, FPM (m/s) 298 (1.5) 372 (1.9) 457 (2.3)
Electric Reheat (Two-Stage)
Capacity, kW (BTUH) Including Motor Heat 14.4 (49.2) 14.9 (50.9) 15.1 (51.6)
Infrared Humidifier
Capacity, lb/hr (kg/hr) 7.7 (3.5)
Steam Generating Humidifier
Capacity, lb/hr (kg/hr) 10.8 (4.9)
Condensate Pump - Dual Float Type
Capacity - ft WG @ 5gpm (18.9 L/m) 45 @ 208V, 48 @ 230V, 40 @ 460V
Filter Section - MERV Rating per ASHRAE 52.2 - 2007 - Deep Pleated Disposable Type
Standard 2" (51mm) Filter Rating MERV 8 Pleated Filter
Optional 2" (51mm) Filter Rating MERV11 Pleated Filter
Quantity 1 1 1
Nominal Size, in. (mm) 29.5 x 28.5 (749 x 724)
Effective Surface Area, ft (m )
2 2
5.8 (0.54)
Water Valve
Water Valve Type MBV
Water Valve Nominal Size, in. 1 1 1
Water Requirements, Brazed Plate Condenser
THR, kW (BTUH) @ 85F(29C), 33%RH 103.6 (30.3) 109.4 (32.0) 147.9 (43.3)
104F (29.4C) EWT - 130F (43.3C) Condensing Temperature
Flow Rate, GPM (L/m) 18.4 (69.7) 20.6 (78.0) 29.2 (110.5)
Unit Pressure Drop, ft. of water (kPa) 3.1 3.9 14.6
Piping Connection Sizes
Condenser Water Supply and Return, in. OD Copper 1-1/8
Humidifier Supply Line, in. 1/4
Condensate Drain Line, in. 3/4

Liebert PDX and Liebert PCW 8


Liebert PDX/PCW Capacity Data60Hz

Table 2 Liebert PDX water-cooled data (continued)


Model Size PX018 PX023 PX029
Unit Fluid Volumes
Water-Cooled Unit, gal (L) 1.7 (6.4) 1.9 (7.0)
Dual-Cool Unit Capacity Using Econ-O-Coil, (Four-Pipe System) with Water in Econ-O-Coil Circuit)
85F DB, 65F WB (33% RH), 45F EWT, 55F LWT
Total kW (kBTUH) 28.9 (98.7) 32.3 (110.3) 37.0 (126.4)
Sensible kW (kBTUH) 27.5 (93.9) 30.6 (104.8) 35.2 (120.2)
Flow Rate, GPM (L/m) 21.6 (81.6) 28.7 (108.6)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
75F DB, 61F WB (45% RH), 45 F EWT, 55F LWT
Total kW (kBTUH) 17.7 (60.4) 22.1 (75.5) 24.8 (84.7)
Sensible kW (kBTUH) 16.8 (57.4) 21.0 (71.7) 23.6 (80.6)
Flow Rate, GPM (l/m) 19.7 (74.4) 19.5 (73.8) 22.0 (83.4)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
Fluid Volumes & Piping Connection Sizes
Econ-O-Coil, gal (L) 2.3 (8.6) 2.7 (10.1)
Econ-O-Coil Water Supply and Return, in. OD Copper 1-1/8
Unit Weights
Water Cooled, Dry Weight, lb (kg) 690 (313) 720 (327)
Water Cooled with Dual Cool, Dry Weight, lb (kg) 770 (349) 810 (367)
1. Airflow data rated with 2" MERV 8 filter, rated per ASHRAE 52.2-2007.
2. The net capacity data has fan motor heat factored in for all ratings.
3. Capacity data is factory-certified to be within 5% tolerance.

9 Liebert PDX and Liebert PCW


Liebert PDX/PCW Capacity Data60Hz

Table 3 Liebert PDX glycol-cooled data


Model Size PX018 PX023 PX029
Net Capacity, kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Standard and Digital Compressors
85F DB, 65F WB (33% RH), 130F SCT
Total kW (kBTUH) 19.4 (66.2) 23.5 (80.2) 31.4 (107.2)
Sensible kW (kBTUH) 19.4 (66.2) 23.5 (80.2) 31.4 (107.2)
75 F DB, 61 F WB (45% RH), 130F SCT
Total kW (kBTUH) 16.7 (57.0) 20.3 (69.3) 27.2 (92.9)
Sensible kW (kBTUH) 16.7 (57.0) 20.3 (69.3) 27.2 (92.9)
Fan Data
Standard Airflow, CFM (m3h) 1 2800 (4760) 3500 (5950) 4300 (7310)
Standard Fan Motor, kW (hp) 3.1 (4.2)
Standard Fan Motor with Dual Cool, kW (hp) 3.1 (4.2) 3.6 (4.8)
External Static Pressure, in. WG (Pa) 0.2 (50)
Evaporator Coil
Face Area, ft2 (m2), Without GLYCOOL or Dual Cool 9.9 (0.92)
DX Coil Rows 3 4
Face Velocity Without Econ-O-Coil, FPM (m/s) 283 (1.4) 354 (1.8) 434 (2.2)
Face Area, ft2 (m2), With GLYCOOL or Dual Cool 9.4 (0.87)
GLYCOOL or Dual Cool Rows 4
Face Velocity With Econ-O-Coil, FPM (m/s) 298 (1.5) 372 (1.9) 457 (2.3)
Electric Reheat (Two-Stage)
Capacity, kW (BTUH) Including Motor Heat 14.4 (49.2) 14.9 (50.9) 15.1 (51.6)
Infrared Humidifier
Capacity, lb/hr (kg/hr) 7.7 (3.5)
Steam Generating Humidifier
Capacity, lb/hr (kg/hr) 10.8 (4.9)
Condensate Pump - Dual Float Type
Capacity, ft WG @ 5gpm (18.9 l/m) 45@208V, 48@230V, 40@460V
Filter Section - MERV rating per ASHRAE 52.2 - 2007 - Deep Pleated Disposable Type
Standard 2" (51mm) Filter Rating MERV 8 Pleated Filter
Optional 2" (51mm) Filter Rating MERV11 Pleated Filter
Quantity 1 1 1
Nominal Size, in. (mm) 29.5 x 28.5 (749 x 724)
Effective Surface Area, ft2 (m2) 5.8 (0.54)
Water Valve
Water Valve Type MBV
Water Valve Nominal Size, in. 1 1 1
40% PG Fluid Requirements, Brazed Plate Condenser
THR, kBTUH (kW)@ 85F(29C), 33% RH 103.6 (30.3) 109.4 (32.0) 147.9 (43.3)
104F (29.4C)EWT - 130F (43.3C)Condensing Temperature
Flow Rate, GPM (L/m) 18.4 (69.7) 20.6 (78.0) 29.2 (110.5)
Unit Pressure Drop, ft. of water (kPa) 3.1 (9.3) 3.9 (11.7) 14.6 (43.6)
Piping Connection Sizes
Condenser Glycol Supply and Return, in. OD Copper 1-1/8
Humidifier Supply Line, in. 1/4
Condensate Drain Line, in. 3/4

Liebert PDX and Liebert PCW 10


Liebert PDX/PCW Capacity Data60Hz

Table 3 Liebert PDX glycol-cooled data (continued)


Model Size PX018 PX023 PX029
Unit Fluid Volumes
Glycol-Cooled Unit, gal (L) 1.7 (6.4) 1.9 (7.0)
Drycooler Match-Up 95F (35C) Ambient 40% EG
Base Model Size-Circuits 174-16 225-26
Drycooler Connections, in. OD Cu 2-1/8
Volume, gal (L) 6.9 (26.2) 6.9 (26.2) 11.1 (42.1)
Fan, hp (kW) 2x 3/4 (0.5) 2x 3/4 (0.5) 2x 3/4 (0.5)
Pressure Drop, ft. water (kPa) 4.3 (12.85) 5.3 (15.84) 4.3 (12.85)
Glycol Pump, hp (kW) for 40 ft. of Piping Water Head 3/4 (0.5) 1-phase 3/4 (0.5) 3-phase
Expansion Tank Capacity, gal (L) 8.8 (33.1)
Dual-Cool Unit Capacity Using Econ-O-Coil, (Four-Pipe System) with Water in Econ-O-Coil Circuit
85 F DB, 65 F WB (33% RH), 45 F EWT
Total kW (kBTUH) 28.9 (98.7) 32.3 (110.3) 37.0 (126.4)
Sensible kW (kBTUH) 27.5 (93.9) 30.6 (104.8) 35.2 (120.2)
Flow Rate, GPM (l/m) 21.6 (81.6) 28.7 (108.6)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
75 F DB, 61 F WB (45% RH), 45 F EWT
Total kW (kBTUH) 17.7 (60.4) 22.1 (75.5) 24.8 (84.7)
Sensible kW (kBTUH) 16.8 (57.4) 21.0 (71.7) 23.6 (80.6)
Flow Rate, GPM (l/m) 19.7 (74.4) 19.5 (73.8) 22.0 (83.4)
Unit Pressure Drop, ft. of water (kPa) 16.1 (48.1) 23.8 (70.9) 32.3 (96.5)
Fluid Volumes & Piping Connection Sizes
Econ-O-Coil, gal (L) 2.3 (8.6) 2.7 (10.1)
Econ-O-Coil Water Supply and Return, OD Copper, in. 1-1/8
Unit Weights
Glycol-Cooled, Dry weight, lb (kg) 690 (313) 720 (327)
Glycol-Cooled with Dual Cool, Dry Weight, lb (kg) 770 (349) 810 (367)
1. Airflow data rated with 2" MERV 8 filter, rated per ASHRAE 52.2-2007.
2. The net capacity data has fan motor heat factored in for all ratings.
3. Capacity data is factory-certified to be within 5% tolerance.

11 Liebert PDX and Liebert PCW


Liebert PDX/PCW Capacity Data60Hz

Table 4 Liebert PDX GLYCOOL data


Model Size PX018 PX023 PX029
Net Capacity, kW (BTUH), Standard Air Volume and Evaporator Fan Motor, Standard and Digital Compressors
85 F DB, 65 F WB (33% RH), 130F SCT
Total kW (kBTUH) 19.4 (66.2) 23.5 (80.2) 31.4 (107.2)
Sensible kW (kBTUH) 19.4 (66.2) 23.5 (80.2) 31.4 (107.2)
75 F DB, 61 F WB (45% RH), 130F SCT
Total kW (kBTUH) 16.7 (57.0) 20.3 (69.3) 27.2 (92.9)
Sensible kW (kBTUH) 16.7 (57.0) 20.3 (69.3) 27.2 (92.9)
Fan Data
Standard Airflow, CFM (m3h) 1 2800 (4760) 3500 (5950) 4300 (7310)
Standard Fan Motor, kW (hp) 3.1 (4.2) 3.6 (4.8)
External Static Pressure, in. WG (Pa) 0.2 (50)
Evaporator Coil
Face Area, ft2 (m2), Without GLYCOOL or Dual cool 9.9 (0.92)
DX Coil Rows 3 4
Face Velocity Without Econ-O-Coil, FPM (m/s) 283 (1.4) 354 (1.8) 434 (2.2)
Face Area, ft2 (m2), With GLYCOOL or Dual cool 9.4 (0.87)
GLYCOOL or Dual Cool Rows 4
Face Velocity With Econ-O-Coil, FPM (m/s) 298 (1.5) 372 (1.9) 457 (2.3)
Electric Reheat (Two-Stage)
Capacity, kW (BTUH) Including Motor Heat 14.4 (49.2) 14.9 (50.9) 15.1 (51.6)
Infrared Humidifier
Capacity, lb/hr (kg/hr) 7.7 (3.5)
Steam Generating Humidifier
Capacity, lb/hr (kg/hr) 10.8 (4.9)
Condensate Pump - Dual Float Type
Capacity, ft WG @ 5gpm (18.9 l/m) 45 @ 208V, 48 @ 230V, 40 @ 460V
Filter Section - MERV Rating per ASHRAE 52.2 - 2007 - Deep Pleated Disposable Type
Standard 2" (51mm) Filter Rating MERV 8 Pleated Filter
Optional 2" (51mm) Filter Rating MERV11 Pleated Filter
Quantity 1 1 1
Nominal Size, in. (mm) 29.5 x 28.5 (749 x 724)
Effective Surface Area, ft2 (m2) 5.8 (0.54)
Water Valve
Water Valve Type MBV
Water Valve Nominal Size, in. 1 1 1
40% PG Fluid Requirements, Brazed Plate Condenser
THR, kBTUH (kW) @ 85F (29C), 33% RH 103.6 (30.3) 109.4 (32.0) 147.9 (43.3)
104F (29.4C)EWT - 130F (43.3C) Condensing Temperature
Flow Rate, GPM (l/m) 18.4 (69.7) 20.6 (78.0) 29.2 (110.5)
Unit Pressure Drop, ft. of water (kPa) 3.1 (9.3) 3.9 (11.7) 14.6 (43.6)
Piping Connection Sizes
Unit Glycol Supply and Return, in. OD Copper 1-1/8
Humidifier Supply Line, in. 1/4
Condensate Drain Line, in. 3/4

Liebert PDX and Liebert PCW 12


Liebert PDX/PCW Capacity Data60Hz

Table 4 Liebert PDX GLYCOOL data (continued)


Model Size PX018 PX023 PX029
Fluid Volumes
GLYCOOL Unit, gal (L) 4.0 (15.0) 4.5 (17.1)
Drycooler Match-Up 95F (35C)Ambient 40% EG
Base Model Size-Circuits 174-16 225-26
Drycooler Connections, in. OD Cu 2-1/8
Volume, gal (L) 6.9 (26.2) 11.1 (42.1)
Fan, hp (kW) 2x 3/4 (0.5)
Pressure Drop, ft. water (kPa) 4.3 (12.85) 5.3 (15.84) 4.3 (12.85)
Glycol Pump hp (kW) for 40 ft. of Piping Water Head 3/4 (0.5) 1-phase 1.5 (1.1) 3-phase 3 (2.2) 3-phase
Expansion Tank Capacity, gal (L) 8.8 (33.1)
GLYCOOL Coil Net Capacity Using 40% EG (Two-Pipe System)
85F DB, 65F WB (33% RH), 35F EWT, 45F LWT
Total kW (kBTUH) 22.3 (76.2) 32.6 (111.3) 36 (122.9)
Sensible kW (kBTUH) 22.3 (76.2) 30.2 (103.1) 34.6 (118.2)
Flow Rate, GPM (L/m) 18.4 (69.7) 20.6 (78.0) 29.2 (110.5)
Unit Pressure Drop, ft. of water (kPa) 15.5 (46.3) 28.8 (86.1) 44.3 (132.4)
75F DB, 61F WB (45% RH), 35F EWT, 45F LWT
Total kW (kBTUH) 18.0 (61.5) 26.2 (89.5) 29.0 (99.0)
Sensible kW (kBTUH) 16.8 (57.4) 23.0 (78.5) 26.1 (89.1)
Flow Rate, GPM (l/m) 18.4 (69.7) 20.6 (78.0) 29.2 (110.5)
Unit Pressure Drop, ft. of water (kPa) 17.8 (53.2) 33.8 (101.0) 46.8 (139.9)
Unit Weights
GLYCOOL Dry Weight, lb (kg) 770 (349) 810 (367)
1. Airflow data rated with 2" MERV 8 filter, rated per ASHRAE 52.2-2007.
2. The net capacity data has fan motor heat factored in for all ratings.
3. Capacity data is factory-certified to be within 5% tolerance.

13 Liebert PDX and Liebert PCW


Liebert PDX/PCW Capacity Data60Hz

Table 5 Liebert PCW chilled water data


Model Size PW017 PW029
Net Capacity Data kW (BTUH), Standard Air Volume and Evaporator Fan Motor
85F DB, 65F WB (33% RH), 45F EWT, 55F (LWT)
Total kW (kBTUH) 20.7 (70.7) 36.7 (125.3)
Sensible kW (kBTUH) 19.7 (67.3) 34.9 (119.2)
Flow Rate, GPM (l/m) 17.9 (67.8) 32.1 (121.2)
Unit Pressure Drop, ft. of water (kPa) 12.9 (38.6) 39.3 (117.4)
75F DB, 61F WB (45% RH), 45F EWT, 55F (LWT)
Total kW (kBTUH) 14.2 (48.5) 25.6 (87.4)
Sensible kW (kBTUH) 13.5 (46.1) 24.32 (83.0)
Flow Rate, GPM (l/m) 12.7 (48) 22.7 (86.4)
Unit Pressure Drop, ft. of water (kPa) 10 (30) 25.2 (75)
Fan Data
Standard Airflow, CFM (m3h) 1 3500 (5947) 4800 (8155)
Standard Fan Motor, kW (hp) 3.1 (4.2)
External Static Pressure, in. WG (Pa) 0.2 (50)
Chilled Water Coil
Face Area, ft2 (m2) 9.7 (0.90)
Rows 2 4
Face Velocity, FPM (m/s) 360 (1.8) 495 (2.5)
Electric Reheat (Two-Stage)
Capacity, kW (BTUH) Including Motor Heat 13.2 (45.1) 14.9 (50.9)
Hot Water Reheat 180F (82.2C) E.W.T., 75F (23.9C) E.A.T
Capacity, kW (kBTUH) Including Motor Heat 12.1 (41.3) 41.3 (12.1)
Pressure Drop, Ft. of Water (kPa) 12.8 (38.3)
Maximum Face Area, ft2 (m2) 3.78 (0.351)
Coil Rows 1 1
Infrared Humidifier
Capacity, lb/hr (kg/hr) 7.7 (3.5)
Steam Generating Humidifier
Capacity, lb/hr (kg/hr) 10.8 (4.9)
Condensate Pump - Dual Float Type
Capacity, ft WG @ 5gpm (18.9 l/m) 45@208V, 48@230V, 40@460V
Filter Section - Std. 2" (51mm)MERV rating per ASHRAE 52.2 - 2007 - Deep Pleated Disposable Type
Standard 2" (51mm) Filter Rating MERV 8 Pleated Filter
Optional 2" (51mm) Filter Rating MERV11 Pleated Filter
Quantity 1 1
Nominal Size, in. (mm) 29.5 x 28.5 (749 x 724)
Effective Surface Area, ft2 (m2) 5.8 (0.54)
Piping Connection Sizes
Chilled Water Supply and Return Connections, OD Cu 1-1/8
Humidifier Supply Line, in. 1/4
Condensate Drain Line, in. 3/4
Optional HWRH Supply and Return Connections, in. OD Cu 5/8

Liebert PDX and Liebert PCW 14


Liebert PDX/PCW Capacity Data60Hz

Table 5 Liebert PCW chilled water data (continued)


Model Size PW017 PW029
Fluid Volumes
Chilled Water Unit, gal (L) 2.3 (8.6) 2.7 (10.1)
Optional Hot Water Reheat, gal (L) 0.05 (0.189)
Water Control Valve
Water Valve Type MBV
Water Valve Nominal Size, in. 1 1
Water Valve Body 2-Way or 3-Way
Cv 30/9
Valve Close-Off Pressure, PSI (kPa) 200 (1379)
Unit Weights
Chilled Water, Dry Weight, lb (kg) 600 (272)
1. Airflow data rated with 2" MERV 8 filter, rated per ASHRAE 52.2-2007.
2. The net capacity data has fan motor heat factored in for all ratings.
3. Capacity data is factory-certified to be within 5% tolerance.

15 Liebert PDX and Liebert PCW


Dimensional Data

3.0 DIMENSIONAL DATA

Figure 5 Cabinet and floor planning dimensionsDownflow

33-1/8"
(842mm)
34-5/8"
(879mm)

1-1/2" TOP
(38mm)

77-9/16" 34"
(1970mm) (864mm)

34"
(864mm)

Shaded areas indicate


the recommended minimum
34-1/2" clearance for component access. DPN002936
(876mm) Rev. 2
FRONT
Table 6 Weights for downflow, Liebert PDX and Liebert PCW, lb. (kg)
Liebert PDX Model No. PX018-023 PX029
Air Cooled 670 (304) 700 (317)
Air Cooled w/Dual Cool 750 (340) 790 (358)
Water/Glycol 690 (313) 720 (327)
GLYCOOL or Water/Glycol w/Dual Cool 770 (349) 810 (367)
Liebert PCW Model No. PW017-029
Chilled Water 600 (272)
Source: DPN002936, Rev. 2

Liebert PDX and Liebert PCW 16


Dimensional Data

Figure 6 Cabinet and floor planning dimensionsFront discharge, downflow

33-1/8"
(842mm)
34-5/8"
(879mm)
2

26-1/8" 5-1/2"
(663mm) (139mm)
TOP
1-1/2" 34" 34"
(38mm) (864mm) (864mm)

RIGHT ISO VIEW


1

77-9/16"
(1970mm)

9"
(226mm)
26-1/8"
(663mm)
10 3/4" (273mm)

34" 34"
26-9/16" (864mm) (864mm)
(674mm)
34-1/2"
(876mm)
3
FRONT 1
LEFT ISO VIEW
1 Shaded area indicates the recommended minimum clearance for component access.

2 Optional opening for units with right side discharge or right and left side discharge.
DPN002944
3 Optional opening for units with left side discharge or right and left side discharge Rev. 0
Table 7 Weights for downflow, Liebert PDX and Liebert PCW, lb. (kg)
Liebert PDX Model No. PX018-023 PX029
Air-Cooled 670 (304) 700 (317)
Air-Cooled w/Dual Cool 750 (340) 790 (358)
Water/Glycol 690 (313) 720 (327)
GLYCOOL or Water/Glycol w/Dual Cool 770 (349) 810 (367)
Liebert PCW Model No. PW017-029
Chilled Water 600 (272)
Source: DPN002944, Rev. 0

17 Liebert PDX and Liebert PCW


Dimensional Data

Figure 7 Cabinet and floor planning dimensionsUpflow

34-11/16"
(881mm)
32-15/16"
(836mm)

1-3/4" Top View


(45mm)

34"
(864mm)
OFF

77-5/8"
(1971mm) 34"
(864mm)
Shaded area indicates a
recommended minimum
clearance for component NOTE: Unit with front return
access. shown. Bottom return with
rear return floor stand also
available.
34-1/2" DPN002937
(876mm) Rev. 0
Front View
Table 8 Approximate weights, upflow models, lb. (kg)
Liebert PDX Model No. PX018-023 PX029
Air-Cooled 670 (304) 700 (317)
Air-Cooled w/Dual Cool 750 (340) 790 (358)
Water/Glycol 690 (313) 720 (327)
GLYCOOL or Water/Glycol w/Dual Cool 770 (349) 810 (367)
Liebert PCW Model No. PW017-029
Chilled Water 600 (272)
Source: DPN002937, Rev. 0

Liebert PDX and Liebert PCW 18


Dimensional Data

3.1 Floor Stand Dimensions


Figure 8 Floor stand dimensionsDownflow and upflow floor stands

32-5/8"
(829mm)

30-11/16"
(779mm)

1"
typ
(25mm)

7/8"
(23mm) 3"
(76mm)
A*

DPN002970
Rev. 0
Table 9 Floor stand heightDownflow
A
Height, in. (mm)
6 (152)
9 (229)
12 (305)
15 (381)
18 (457)
21 (533)
24 (610)
* Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height A.
Source: DPN002970, Rev. 0

19 Liebert PDX and Liebert PCW


Dimensional Data

Figure 9 Floor stand dimensionsUpflow, rear return and upflow floor stands

1" (25mm)
Ductwork
Flange

31-5/8"
(804mm)

32-5/8" (829mm)

Removable
Panel for Filter
Access Filter

24-1/8"
(613mm)

28-7/8" (734mm)
Duct Flange Opening
FRONT

3" 7/8"
(76mm) (23mm) 12-1/2"
(318mm)
Leveling feet are provided with 1-1/2" (38mm) Duct Flange
adjustment from nominal height. Opening

DPN002971
REAR
Rev. 1

Liebert PDX and Liebert PCW 20


Dimensional Data

3.2 Plenum Dimensions


Figure 10 Plenum dimensionsUpflow and downflow

Front Views - Check One Rear Views - Check One


34-1/2"
31-3/4"
(876mm)
(807mm)

With Grille H With Grille


1-7/16"
(37mm)

Without Grille Without Grille

Left Side Views - 77-5/8"


Right Side Views -
Check One 1971mm)
Check One

With Grille With Grille

Side View Front View


Unit With Plenum Unit With Plenum

Without Grille Without Grille

Notes
1. Typical unit orientation shown with grille plenum. Plenum with grille
is available only for 18" height plenum. Nominal grille size is
24" x 14" (609mm x 355mm).
2. All plenums are shipped flat and must be field-assembled. DPN002981
3. Unit with front return shown. Bottom return with rear return Rev. 1
floor stand also available.
Table 10 Upflow unit plenum dimensions
H
Height, in. (mm)
18" (457)
24" (609)
30" (762)
36" (914)
42" (1066)
48" (1219)

21 Liebert PDX and Liebert PCW


Heat RejectionLiebert MC

4.0 HEAT REJECTIONLIEBERT MC


Table 11 Liebert MC Selection for Liebert PDX units
Outdoor Design Ambient Temperature, F (C)
Model # 95 (35) 100 (38) 105 (41) 110 (43) 115 (46) 120 (49)
Traditional Open Room (75F/45RH Return Air Conditions)
PX018 MCS028 MCM040 MCM040 MCM040 MCL055 MCM080
PX023 MCM040 MCM040 MCM055 MCL055 MCM080 MCL110
PX029 MCL055 MCL055 MCL055 MCL055 MCM080 MCL165
High-Temperature Return (85F/33RH Return Air Conditions)
PX018 MCS028 MCM040 MCM040 MCM040 MCL055 MCM080
PX023 MCM040 MCL040 MCL055 MCL055 MCM080 MCL110
PX029 MCL055 MCL055 MCL055 MCM055 MCM080 MCL165

Table 12 Condenser shipping weights, dimensions and volume, approximate


Domestic Packaging Export Packaging
Packaged Dimensions Packaged Dimensions
# of Weight (LxWxH) Volume Weight (LxWxH) Volume
Model # Fans lb (kg) in. (cm) ft3 (m3) lb (kg) in. (cm) ft3 (m3)
76x36x63 77x37x64
MCS028 1 335 (152) 100 (2.8) 455 (206) 106 (3.0)
(193x91x160) (196x94x163)
76x36x63 77x37x64
MCM040 1 410 (186) 100 (2.8) 535 (243) 106 (3.0)
(193x91x160) (196x94x163)
76x36x63 77x37x64
MCL055 1 525 (238) 100 (2.8) 645 (293) 106 (3.0)
(193x91x160) (196x94x163)
136x36x63 137x37x64
MCM080 2 750 (340) 179 (5.0) 945 (429) 188 (5.3)
(345x91x160) (348x94x163)
136x36x63 137x37x64
MCL110 2 910 (413) 179 (5.0) 1110 (503) 188 (5.3)
(345x91x160) (348x94x163)
196x36x63 197x37x64
MCL165 3 1330 (603) 257 (7.3) 1600 (726) 270 (7.7)
(498x91x160) (413x66x142)
Weights are based on units with EC fans, units with AC fans may be slightly less.
Net and packaged weights will increase with factory options: legs taller than 18", coated coils and seismic options. Field-installed
receivers also add to net weights. Consult factory for additional information. See Table 13 for weight added by longer legs.

Table 13 Condenser net weight


Additional Weight by Condenser Model, lb. (kg)
MCS028 MCM040 MCM080 MCL055 MCL110 MCL165
Leg Height 1 1 1 2 1 1 2 1
In. (mm) Circuit Circuit Circuit Circuits Circuit Circuit Circuits Circuit
18 (457) 154 (70) 231 (105) 441 (200) 441 (200) 344 (156) 602 (273) 602 (273) 891 (404)
36 (914) 286 (130) 363 (165) 590 (268) 590 (268) 486 (220) 766 (347) 766 (347) 1136 (515)
48 (1219) 318 (144) 395 (179) 622 (282) 622 (282) 518 (235) 798 (362) 798 (362) 1184 (537)
60 (1524) 349 (158) 426 (193) 653 (296) 653 (296) 549 (249) 829 (376) 829 (376) 1230 (558)
Liebert Lee-Temp
55 (25) 55 (25) 100 (45) 110 (50) 60 (27) 115 (52) 120 (54) 175 (79)
Receiver
Coated Coil 4 (2) 5 (2) 10 (5) 10 (5) 8 (4) 16 (7) 16 (7) 24 (11)
Condenser + Liebert Lee-Temp + Coated Coil = Total Weight
Source: DPN003034, Rev. 0

Liebert PDX and Liebert PCW 22


Heat RejectionLiebert MC

Figure 11 Condenser planning dimensionsMCS028

58-7/8" (1495mm) See table below for


42-3/4" dimensions A, B and C
50-5/8" (1085mm) 58-7/8"
(1287mm) (1495mm)
42-3/4"
Height to Top (1085mm) 5
(12 0-5/
87 8"
of Fan Guard mm
Height to Top )
B C
of Fan Guard
C
B
A A

42-1/2" 44-1/8"
(1079mm) (1121mm)
44-1/8"
(1121mm) 42-1/2"
ANCHOR PLAN Emerson recommends a (1079mm)
F clearance of 36" (915mm)
on each side for proper 15-1/4"
operation and component (387mm)
Electric Box End

access.
See Figure 15
for typical 40-7/8" *Cross-bracing required for legs longer than 18".
footprint (1038mm) Quantity varies depending on model and options.
35-7/8"
dimensions.
(910mm)

DPN002372 DPN002373
Rev. 4 Rev. 5

Leg Height B C
A *, In. (mm) In. (mm) In. (mm)
18 (457) 31-5/8 (803) 39-5/8 (1006
36 (914) 49-5/8 (1260) 57-5/8 (1464)
48 (1219) 61-5/8 (1565) 69-5/8 (1768)
60 (1524) 73-5/8 (1870) 81-5/8 (2073)
* 18" legs standard for all models. Cross-bracing is required for legs longer than 18" (457mm).
Number varies according to model and options.
See Tables 12 and 13 for weights, including added weight for legs of various lengths.
Source: DPN002372, Rev. 2; DPN002373, Rev. 3

23 Liebert PDX and Liebert PCW


Heat RejectionLiebert MC

Figure 12 Condenser planning dimensionsMCM040 and MCM080 with/without Liebert Lee-Temp


Height to Top
of Fan Guard

Emerson recommends a clearance of


H 36" (915mm) on each side for proper
operation and component access.
G A*
A
See table below for B
dimensions A, B, C,
D, E, F, G and H F

575V Transformer
Enclosure Option
Eyebolts for lifting
condenser provided
on four-fan models
C
Height to Top 15-1/4"
of Fan Guard 387mm

46" For dual


(1168mm) circuit only
H
G A* 15-1/4"
A 387mm
B

See Figure 15 for typical


footprint dimensions. 46"
(1168mm)
ANCHOR PLAN
E D
Electric Box End

Leg supplied for


Provided On 39-5/16"
each Liebert
Four-Fan Models Lee-Temp kit on (999mm)
2- & 4-fan models 44-3/8"
(1127mm)

46-5/16" DPN002172, Rev. 5


(1177mm) DPN002189, Rev. 6

Liebert No. A A* (575V) B C D E Leg Height G H


Model # Fans In. (mm) In. (mm) In. (mm) In. (mm) In. (mm) In. (mm) F * In (mm) In. (mm) In. (mm)
57-3/16 65-3/8 46-5/16 31-5/8 39-5/8
MCM040 1 48 (1219) 18 (457)
(1453) (1661) (1177) (803) (1006
MCM080 2 105-1/4 113-7/16 96-1/16 94-7/16 36 (914) 49-5/8 57-5/8
(2674) (2882) (2440) (2398) (1260) (1464)
Source: DPN002172, Rev. 3; and DPN002189, Rev. 4. 61-5/8 69-5/8
48 (1219) (1565) (1768)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18". Number
varies according to model and options. 73-5/8 81-5/8
60 (1524)
See Tables 12 and 13 for weights, including added weight for legs of various lengths. (1870) (2073)

Liebert PDX and Liebert PCW 24


Heat RejectionLiebert MC

Figure 13 Condenser planning dimensionsMCL055, MCL110 and MCL165

See table below for


Height to Top dimensions A, B, C, D, E, F,
of Fan Guard G and H

Eyebolts for lifting condenser


H provided on 3- and 4-fan models

G A*
A See Figure 15 for typical
B footprint dimensions.

Emerson recommends a clearance of


36" (915mm) on each side for proper
C
operation and component access.

*Cross bracing required for legs longer than 18" (457mm).


Number varies per model and options selected.
55-1/2"
ANCHOR PLAN (1409mm)
E D

Provided on 53-7/8"
3- and 4-Fan Models (1368mm)
48-3/4"
(1239mm) DPN002416
Rev. 4

A
# of in. B C D E Leg Height G H
Model # Fans (mm) in. (mm) in. (mm) in. (mm) in. (mm) F * In. (mm) In. (mm) In. (mm)
68 56 54-3/8 35-7/8 43-5/8
MCL055 1 18 (457)
(1727) (1423) (1381) (911) (1108)
124-1/8 112-1/8 110-1/2 53-7/8 61-5/8
MCL110 2 36 (914)
(3152) (2848) (2806) (1368) (1565)
180-1/4 73-7/16 168-1/4 110-1/2 56-1/8 65-7/8 73-5/8
MCL165 3 48 (1219)
(4578) (1866) (4274) (2806) (1425) (1673) (1870)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18"
(457mm). Number varies according to model and options. 77-7/8 85-5/8
60 (1524)
See Tables 12 and 13 for weights, including added weight for legs of various lengths. (1978) (2175)
Source: DPN002416, Rev. 4

25 Liebert PDX and Liebert PCW


Heat RejectionLiebert MC

Figure 14 Cabinet and anchor dimensionsMCL055, MCL110 and MCL165 with Liebert Lee-Temp
receiver

Emerson recommends a clearance of


Height to Top 36" (915mm) on each side for proper
of Fan Guard operation and component access.

Eyebolts for lifting condenser


H provided on three- and four-fan models

G A*
B A

See table below for


dimensions A,A*, B,
C, D, E, F, G and H.

See Figure 15 for typical


footprint dimensions. C

15-1/4"
(387mm)

55-1/2" For
(1410mm) Dual-Circuit
Only
15-1/4"
ANCHOR PLAN (387mm)
E D
Electric Box End

Provided on One leg supplied


3- & 4- Fan for each Liebert 48-3/4"
Lee-Temp kit (1239mm)
Models
on 2, 3 and 4 53-7/8"
fan models (1368mm)

DPN002415
54-3/8" Rev. 5
(1381mm)

Leg Height
# of A B C D E F* G H
Model # Fans in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) In. (mm) In. (mm) In. (mm)
68 56 54-3/8 35-7/8 43-5/8
MCL055 1 18 (457)
(1727) (1423) (1381) (911) (1108
124-1/8 112-1/8 110 1/ 53-7/8 61-5/8
MCL110 2 36 (914)
(3152) (2848) (2806) (1368) (1565)
180-1/4 73-7/16 168-1/4 11-1/2 56 1/8 65-7/8 73-5/8
MCL165 3 48 (1219)
(4578) (1866) (4274) (2806) (1425 (1673) (1870)
* 18" legs standard for all models. Cross-bracing required for legs longer than 18" (457mm). 77-7/8 85-5/8
Number varies according to model and options. 60 (1524)
(1978) (2175)
See Tables 12 and 13 for weights, including added weight for legs of various lengths.
Source: DPN002415, Rev. 3

Liebert PDX and Liebert PCW 26


Heat RejectionLiebert MC

Figure 15 Typical condenser footprint dimensions, all units

13/16" (21mm)
2-1/2" 3-5/8"
(64mm) (93mm)
1-7/8" (48mm)
2-1/2" (64mm)

1/2"x1"
3-5/8"
(12.7mm x 25.4mm)
(93mm)
Obround
1-7/8" (48mm)

27 Liebert PDX and Liebert PCW


Heat RejectionDrycoolers and Pumps

5.0 HEAT REJECTIONDRYCOOLERS AND PUMPS


Table 14 Drycooler weights and dimensions
Domestic Packaging Export Packaging
Net Packaged Dimensions Packaged Dimensions
No. of Weight Weight LxWxH Volume Weight LxWxH Volume
Model # Fans lb. (kg) lb (kg) in. (cm) ft3 (m3) lb (kg) in. (cm) ft3 (m3)
*D**174 2 540 (245) 605 (275) 805 (365)
97 x 30 x 55 98 x 31 x 56
*D**197 2 580 (263) 645 (293) 93 (2.6) 845 (384) 98 (2.8)
(246 x 76 x 140) (249 x 79 x 142)
*D**225 2 620 (281) 685 (311) 885 (402)

Table 15 Glycol-cooled drycooler match-ups

Outdoor Temperature Suggested


PDX Model F (C) # Fans Models 2 Pump hp 3
PX018 100 (38) 2 DSO174*8 1.5
PX023 105 (41) 2 DSO225*16 2
PX029 95 (35) 2 DSO197*16 2
1. * = A (460V / 3ph / 60Hz) or Y (208/230V / 3ph / 60Hz) or B (575V / 3ph / 60Hz)
2. Match-ups sized for 40% propylene glycol.
3. Suggested pump selections provide at least 30 ft. H2O head pressure for piping losses.

Figure 16 Drycooler planning dimensional dataTwo-fan units

43-9/16"
(1106mm)
91-1/2"
(2324mm)

37-7/8"
(962mm)

18"
(457mm)

84"
(2134mm) 82"
43-3/16" (2083 mm)
(1097mm)

Emerson recommends a clearance of


36" (915mm) on each side for proper
operation and component access. Two-Fan 41-3/16"
Drycooler (1046mm)
See Figure 17 for typical
drycooler footprint dimensions.

Liebert PDX and Liebert PCW 28


Heat RejectionDrycoolers and Pumps

Figure 17 Typical drycooler footprintDimensions


1
(25.4mm)
1-3/4 4-1/4
(44.5mm) (108mm)

2
(50.8mm)
1-3/4
(44.5mm)
9/16" (14mm)
Typical Diameter

4-1/4
(108mm)

2
(50.8mm)

29 Liebert PDX and Liebert PCW


Heat RejectionDrycoolers and Pumps

5.1 Pump Packages and Expansion Tank


Figure 18 Single-pump package and mounting

17-1/4"
SINGLE PACKAGE 0.75 - 7.5 HP (438.2mm)

1
3
19"
(482.6mm)

2-7/8"
15-7/8" (72.9mm)
(403.2mm)

1-3/4"
6-3/8"
(44.4mm)
(161.9mm)

8-3/4"
(222.3mm)

12-1/4"
(311.1mm) 30"
(762mm)
17"
(431.8mm)
PUMP PACKAGE MOUNTING ANGLES
(Angles are inside, bottom
of pump package. View used for
1 3" (76.2mm) diameter pump suction mounting reference.)
connection knockouts 4

2 3" (76.2mm) diameter pump discharge


connection knockouts
3 7/8" (22.2mm) diameter electrical knockouts
4
4 1/2" (12.7mm) diameter holes for mounting

3/4"
(19mm)

C
A DPN000278
Rev. 0
B

Liebert PDX and Liebert PCW 30


Heat RejectionDrycoolers and Pumps

Figure 19 Dual-pump package and mounting

DUAL PACKAGE 0.75 - 5 HP

2
1 32-1/4"
(819.2mm)
2
3
1

3
4-1/8"
6-3/8" (104.8mm)
15-7/8" (161.9mm) "
2-7/8" 19"
(403.2mm) (482.6mm)
(73mm)

8-3/4" (222.2mm) 1-3/4"


(44.4mm)
12-1/4"
(311.1mm)

23-3/4" 30"
(603.2mm) (762mm)
27-1/4" 1 3" (76.2mm) diameter pump suction
(692.1mm) connection knockouts
32" 2 3" (76.2mm) diameter pump discharge
(812.8mm) connection knockouts
3 7/8" (22.2mm) diameter electrical knockouts
5 5" (127mm) diameter pump discharge
DPN000328 connection hole
Rev. 0 6 5" (127mm) diameter pump suction
connection hole

31 Liebert PDX and Liebert PCW


Heat RejectionDrycoolers and Pumps

Figure 20 Expansion tank


30-1/2" (774.7mm)
1/2" F.P.T. 6-13/16" 17-1/4"
9" 1/2" F.P.T.
Fitting (173mm) (438.2mm)
(228.6mm) Fitting

2-3/4"
(69.9mm) 2-1/2"
(63.5mm) 7"
(177.8mm)

4" 1/2" (12.7mm)


1"
1" (101.6mm) 8 Holes
(25.4mm)
(25.4mm) 1-1/2" (38.1mm)
1-1/2" 8.8 gal. (33.3 L)
(38.1mm) 6-1/8" 3" (76.2mm) Expansion Tank DPN000329
(155.6mm) Rev. 0
Expansion Tank- (P/N 1C16717P1)
This tank, included in a standard pump package, has an internal volume of 8.8 gal. (33 l) and a
maximum pressure of 100 psi (690 kPa).
This tank is sized for a typical open system with a fluid volume of less than 75 gal. (280l). When
used in a closed system, volumes of up to 140 gal. (530 l) can be accommodated. The use of a safety
relief valve, field supplied, is recommended for systems closed to atmospheric venting. Other piping
accessories for filling, venting, or adjusting the fluid in the system, are recommended, but not
included.
Figure 21 Pump curve, 60 Hz
180
Curve HP
A 3/4 (1-ph)
160 B 3/4 (3-ph)
C 1.5
Total Head, Feet/Water

140 D 2
F E 3
F 5
120 E
G 7.5
D
100 G
C

80 B

A
60

40

20
0 10 20 30 40 50 60 70 80 120 160 200 250 300 400
Flow Rate, GPM

Liebert PDX and Liebert PCW 32


Electrical Data

6.0 ELECTRICAL DATA


Table 16 Electrical data for Liebert PDX and PCW - 60Hz units
With Electric Reheat With Electric With Standard No Reheat
and Humidifier Humidifier Reheat No Humidifier
Model Voltage FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208 65.2 79.2 90 45.2 50.9 70 65.2 79.2 90 31.9 37.6 60
230 60.8 73.7 80 43.0 48.7 70 60.8 73.7 80 31.9 37.6 60
PX018 380 32.2 39.0 45 23.1 26.1 35 32.2 39.0 45 17.0 20.0 30
460 29.3 35.6 40 20.7 23.4 30 29.3 35.6 40 14.9 17.6 25
575 24.1 29.3 30 18.9 21.0 25 24.1 29.3 30 11.5 13.6 20
208 70.4 85.7 100 50.4 57.4 80 70.4 85.7 100 37.1 44.1 70
230 66.0 80.2 100 48.2 55.2 80 66.0 80.2 100 37.1 44.1 70
PX023 380 36.0 43.8 50 26.9 30.9 45 36.0 43.8 50 20.8 24.8 40
460 32.5 39.6 50 23.9 27.4 40 32.5 39.6 50 18.1 21.6 35
575 26.8 32.7 40 21.6 24.4 35 26.8 32.7 40 14.2 17.0 25
208 73.9 90.1 100 53.9 61.8 90 73.9 90.1 100 40.6 48.5 70
230 69.5 84.6 100 51.7 59.6 90 69.5 84.6 100 40.6 48.5 70
PX029 380 38.9 47.2 60 29.8 34.3 50 38.9 47.2 60 23.7 28.2 45
460 35.6 43.3 50 27.0 31.1 45 35.6 43.3 50 21.2 25.3 40
575 28.9 35.2 40 23.7 26.9 35 28.9 35.2 40 16.3 19.5 30
208 55.8 69.8 70 22.5 28.1 30 42.5 53.1 50 9.2 11.5 20
230 49.2 61.5 70 20.3 25.4 30 38.1 47.6 45 9.2 11.5 20
PW017 380 26.2 32.8 35 11.0 13.8 15 20.1 25.1 25 4.9 6.1 15
460 24.2 30.3 35 9.8 12.3 15 18.4 23.0 20 4.0 5.0 15
575 23.2 29.0 30 10.6 13.3 15 15.8 19.8 20 3.2 4.0 15
208 55.8 69.8 70 22.5 28.1 30 42.5 53.1 50 9.2 11.5 20
230 49.2 61.5 70 20.3 25.4 30 38.1 47.6 45 9.2 11.5 20
PW029 380 27.1 33.9 35 11.9 14.9 15 21.0 26.3 25 5.8 7.3 15
460 25.0 31.3 35 10.6 13.3 15 19.2 24.0 25 4.8 6.0 15
575 23.7 29.6 30 11.1 13.9 15 16.3 20.4 20 3.7 4.6 15

33 Liebert PDX and Liebert PCW


Electrical Data

6.1 Electrical Field ConnectionsLiebert MC


Figure 22 Electrical field connectionsUpflow and downflow models

41 42 43 44 58 59 82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 72 73

41 42 43 44 58 59 82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 72 73
17
1
16

49-1 49-3

49-1 49-3
18
4 13

SH

SH
37C 38C 37B 38B

37C 38C 37B 38B


15
19
11

37 38 24 50 51 55 56 70 71 84 85

37 38 24 50 51 55 56
3
11 8

10
2
10 9

71 84 85
4
12 12
1 Terminal Block
5 6 7
for Customer 14
Refer to specification sheet for total Connection
unit full load amps, wire size amps DPN002933
and max overcurrent protective device size. Rev. 0

6.2 Standard Electrical Connections


Source: DPN002933, Rev. 0
1. Electric conduit knockouts on top and bottom of electric box; knockout size, 1.75in (44.5mm).
2. Three-phase connectionElectric service connection terminals.
3. Factory-installed disconnect switchFused disconnect switch provided on units.
4. Three-phase electric service field-supplied.
5. Earth ground connectionConnection terminal for field-supplied earth grounding wire.
6. Earth ground bar (optional)Connection terminals with factory ground from each
high-voltage component for field-supplied earth grounding wire.
7. Control and monitoring section of electric box.
8. Remote unit shutdownReplace existing jumper between Terminals 37 + 38 with normally
closed switch having a minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring. Two
additional contact pairs available as an option (labeled as 37B & 38B, 37C & 38C). Replace
existing jumper for appropriate pair as done for Terminals 37 & 38.
9. Remote Alarm Device (RAD) ConnectionsField-supplied 24V Class 1 wiring for special
alarm. Connection made by adding normally open contacts. Special alarm connections may be
factory wired or field wired. See schematic, RADS1-4, for factory-wired special alarms. For
field-wired special alarms, use 24V Class 1 wiring to connect normally open contacts between
Terminals 24 & 50, 24 & 51, 24 & 55, or 24 & 56.
10. Smoke detector alarm connectionsField-supplied 24V Class 1 wiring to remote alarm
circuits. Factory-wired contacts from optional smoke detector are #91-Common, #92-NO, and
#93-NC. Optional smoke detector trouble connections #80 & # 81.
11. Common alarm connectionField-supplied 24V Class 1 wiring to common alarm terminals 75
+ 76 (and optional 94 + 95, and 96 + 97), which are factory-connected to common alarm relay (R3).

Liebert PDX and Liebert PCW 34


Electrical Data

12. Heat rejection connectionField-supplied 24V Class 1 wiring to interlock heat rejection from
pigtails 70 + 71 which are factory-connected to compressor side switch (self-contained units only)
or to GLYCOOL relay (K11, GLYCOOL units only).
On Dual Cool units only, pigtails 72 + 73 connect auxiliary cooling source to GLYCOOL relay K11.
See indoor and outdoor electric schematic for more information.
13. Reheat and Humidifier LockoutOptional emergency power lockout of reheat and/or
humidifier: Connections provided for remote 24VAC source. Class 1 wiring to connections #82 &
#83.
14. Main Fan Auxiliary SwitchOptional main fan auxiliary side switch. Terminals located in
field wiring compartment for remote indication that the evaporator fan motor/unit is on. Field to
connect 24V maximum, Class 1 wiring to connections #84 & #85.
15. Optional Condensate Alarm (Dual Float Condensate Pump only)Relay terminals located in
field wiring compartment for remote indication. Class 1 wiring to connections #88 & #89.
16. Optional Remote Liebert Liqui-tect IndicatorOptional remote Liebert Liqui-tect
indicator for unit shutdown. Terminals located in field wiring compartment. Field to connect 24V
maximum, Class 1 wiring to connections #58 & #59.
17. Optional Analog Inputs #3 & #4Customer connection to Terminals 41, 42, 43, 44 for analog
inputs.
18. Spare Terminals for Optional DevicesCustomer connection when optional device is
supplied. See unit schematic.
19. Heat Rejection CANBUS Connection (AIR Units only)Customer connection to terminals
49-1, 49-3 and SH.

35 Liebert PDX and Liebert PCW


Electrical Data

Figure 23 Electrical field connections for Liebert iCOMDownflow models

21

20

22
24 25

23

21
20 DPN002934
Rev. 0

20) Opening for field wiring; suggested entry point for high-voltage field wiring to unit.
21) Opening for field wiring; suggested entry point for low-voltage field wiring to unit.
22) Vacant Liebert IntelliSlot; may contain optional Liebert IntelliSlot cards.
23) Populated Liebert IntelliSlot; optional Liebert IntelliSlot cards may be placed in either of two supplied Liebert
IntelliSlot locations.
24) Wire tie anchors; use to secure field-supplied network cables to Liebert IntelliSlot.
25) Wire tie anchors; use to secure customer Ethernet wiring to control board and display.

Liebert PDX and Liebert PCW 36


Electrical Data

Figure 24 Electrical field connections for Liebert iCOMUpflow models

21

24 25

22

23
20

20

DPN002935
Rev. 0
20) Opening for field wiring; suggested entry point for high-voltage field wiring to unit.
21) Opening for field wiring; suggested entry point for low-voltage field wiring to unit.
22) Vacant Liebert IntelliSlot; may contain optional Liebert IntelliSlot cards.
23) Populated Liebert IntelliSlot; optional Liebert IntelliSlot cards may be placed in either of two supplied Liebert
IntelliSlot locations.
24) Wire tie anchors. Use to secure field-supplied network cables to Liebert IntelliSlot.
25) Wire tie anchors. Use to secure customer Ethernet wiring to control board and display.

37 Liebert PDX and Liebert PCW


Electrical Data

6.3 Electrical DataLiebert MC Condensers


Table 17 Electrical data, three-phase, 60Hz condenser, Premium Version (EC control)
Model Voltage FLA WSA OPD
Small Platform
208/230V 3.0 3.8 15
MCS028 460V 1.4 1.8 15
575V 1.2 1.5 15
Medium Platform
208/230V 2.3 3.2 15
MCM040 460V 1.4 1.9 15
575V 1.2 1.6 15
208/230V 4.6 5.5 15
MCM080 460V 2.8 3.3 15
575V 2.3 2.8 15
Large Platform
208/230V 5.7 7.1 15
MCL055 460V 2.8 3.5 15
575V 2.3 2.9 15
208/230V 11.4 12.8 15
MCL110 460V 5.6 6.3 15
575V 4.7 5.3 15
208/230V 17.1 18.5 20
MCL165 460V 8.4 9.1 15
575V 7.0 7.6 15
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
2. 208V575V premium models must be connected to wye three-phase systems.

Table 18 Electrical data, Liebert Lee-Temp receiver, 60Hz


Rated Voltage - Single-Phase 120 208/230
Watts/Receiver 150 300 150 300
Amps 1.4 2.8 0.7 1.4
Wire Size Amps 1.8 3.5 0.9 1.8
Maximum Overcurrent
Protection Device, Amps 15 15 15 15
The Liebert Lee-Temp receiver requires a separate power feed for heaters.
The condenser is not designed to supply power to the receiver heater pads.

Liebert PDX and Liebert PCW 38


Electrical Data

6.3.1 Wye- vs. Delta-Connected Power Supply


Figure 25 Wye- vs. delta-connected power supply connection diagram
Wye-Connected Power Diagram Delta-Connected Power Diagram

Phase A Phase A

Winding Winding
B Phase B Winding A-B
C-A
Winding
A
Phase B
Neutral
Winding B-C
Winding
C Phase C Phase C

NOTE
The Liebert MC Condenser is designed to operate with wye-connected power with a solidly
grounded neutral. Condenser power connections are provided for three-phase wire and earth
ground.
The Liebert MC condenser Premium EC fan models will not operate properly with
delta-connected power. A field-supplied isolation transformer or other power solutions will be
needed for proper condenser function.

Acceptable Power Supplies208V to 480V Nominal Units


208V wye with solidly grounded neutral and 120V line-to-ground
380V wye with solidly grounded neutral and 220V line-to-ground
480V wye with solidly grounded neutral and 277V line-to-ground

Acceptable Power Supplies575V Nominal Units


575V wye with solidly grounded neutral and 332V line to ground
(A step down transformer is provided in the Liebert unit to convert 575V input to 480V output to
operate the 480V EC motors)
Unacceptable Power Supplies208V to 480V or 575V Nominal Units
Wye with high-resistance (or impedance) ground
Delta without ground or with floating ground
Delta with corner ground
Delta with grounded center tap

39 Liebert PDX and Liebert PCW


Electrical Data

Figure 26 CANbus connections between Liebert PDX and Liebert MC condenser (premium

P80 B A P15

TB50 J6 Termination Jumper


H

1
CAN H
TB50
1
OUTPUT 2
3 CANL L
D58
J6 must be set to Pins 1 and 2.

3
H

J4
TB49
3
TB49

1
INPUT 2 CANbus Addressing Switch
L

3
1

ON
J6
3

CAN SW6

BOOTPSWD SYS APP


CONDENSER
ON

CAN SW6

1
1
2
3

1
2
3

DETAIL1
CAN Cable Connection (A) Shield Connection

A SH
Factory Wiring Between B
70 Liebert MC Control Board Heat Rejection Interlock Wire
71
Low voltage field entrance and Terminal Strip
located on bottom left of B 230
A
Canbus Cable Connection
condenser enclosure
Heat Rejection Interlock (B)

INDOOR UNIT
58

58
49-1
49-1
59

59
49-3
49-3
82

82
SH

SH
83

83
37-C

37-C
88

88
38-C 87-B

38-C 87-B
89

89
75

COMPONENT NOTES 75
1. Component appearance, orientation and positioning
88-B

88-B
76

76

may vary. Terminal names and callouts remain constant.


2. All circuits to these connection points are Class 2.
94

94

CABLE NOTES (A):


1. Field-supplied cable.
95

38

38

95

shielded
22-18AWG stranded tinned copper
96

24

24

96

twisted pair (minimum 4 twists per foot)


low capacitance (15pf/ft or less)
97

50

50

97

must be rated to meet local codes and conditions.


examples Belden 89207 (plenum rated), or Alpha Wire 6454
91

51

51

91

Category 5, 5e, or higher.


2. Do not run in same conduit, raceway, or chase as high
92

55

55

92

voltage wiring.
93

56

56

93

3. Contact factory for CANbus network lengths greater than


350ft. (107m)
80

70

70

80

WIRE NOTES (B):


1. Field-supplied wire
81

71

71

81

18AWG or greater
rated 600V
2. Run two wires from indoor unit to condenser. Partial View

DPN003266
Rev. 0

Liebert PDX and Liebert PCW 40


Electrical Data

6.4 Standard Electrical Connections, Liebert MC, Premium Efficiency Control


Figure 27 Standard connections, Premium Efficiency Control

Liebert Lee-Temp receiver tank 1 per circuit).


Fan 2
NOTE: Heater pad voltage available Fan 2
for 120V/1 phase/60 Hz or 230V/1 phase/60Hz
150 or 300 Watt, varies by condenser Fan 1

Electrical connection
Fan 1
box with cover;
Without Liebert cover removed
Lee-Temp Electrical service connection.
With Liebert
Pigtails in electric handy box
are factory-wired to Liebert Lee-Temp Lee-Temp
heater pads for field-connection
of separate continuous electric
source; wire not by Emerson.

5A

5B

6
4
2
7 5C

11 3
Left Right Two
8 Knockouts
10 Knockout
9 12
13
70
71
230
DPN002169 DPN002374
Pg. 1, Rev. 3 Pg. 1, Rev. 2

41 Liebert PDX and Liebert PCW


Electrical Data

Source: DPN002169, Rev. 3


1. Three-phase electrical serviceTerminals are on top of disconnect switch for one-fan and
two-fan units. Terminals are on bottom of disconnect switch for three-fan and four-fan units.
Three-phase service not by Emerson. See Note 5.
2. Earth groundField lug terminal for earth ground connection. Ground terminal strip for fan
motor ground connection.
3. Primary high voltage entranceTwo knockouts 7/8" (22.2mm) diameter at the bottom of the
enclosure.
4. SPD field connection terminalsHigh-voltage surge protective device (SPD) terminals. SPD
is an optional device.
5. CANbus terminal connectionsField terminals for CANbus cable connection.
5A is the CANbus connectors.
TB49-1 is the input terminal for CANbus high.
TB49-3 is the input terminal for CANbus low.
TB50-1 is output terminal for CANbus high.
TB50-3 is the output terminal for CANbus low.
Each CANbus cable shield is connected to terminal SH, Item 9.
5B is the END OF LINE jumper.
5C is the CANbus DEVICE ADDRESS DIP SWITCH. CANbus cable not by Emerson. See
Note 2.
6. Remote unit shutdownReplace existing jumper between terminals TB38-1 and TB38-2 with
field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied
Class 1 wiring (optional feature; may be user specified).
7. Alarm terminal connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is
normally open and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use
field-supplied Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has
occurred that shuts down the condenser unit. TB74-4 is common; TB74-5 is normally open;
and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load. Use field-supplied
Class 1 wiring.
8. Indoor unit interlock and SPD alarm terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 and
71 for Circuit 1, and normally open contact is closed across Terminals 70 and 230 for Circuit 2
from indoor room unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 and 13. SPD is an
optional device.
9. CANbus shield terminalTerminal for field connection of the CANbus field-supplied cables.
The shield of CANbus field-supplied cables must not be connected to ground.
10. Primary low voltage entranceOne knockout, 7/8" (22.2mm) diameter, that is free for
customer low-voltage wiring.
11. SPD entrance One knockout, 7/8" (22.2mm) diameter, at the bottom of the enclosure. High
voltage surge protective device (SPD) is optional

Liebert PDX and Liebert PCW 42


Electrical Data

NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
Conductors 22-18AWG stranded tinned copper
Twisted pair (minimum 8 twists per foot)
Braided shield or foil shield with drain wire
Shield must be wired to ground at indoor unit
Low Capacitance (15pF/FT or less)
UL approved temperature rated to 75C
UL approved voltage rated to 300V
UV-resistant and moisture-resistant if not run in conduit
Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV
resistant outdoor rated) category 5, 5e or higher.

6.5 Electrical DataDrycoolers


Table 19 60Hz electrical valuesDrycoolers without pump controls
# of Fans Drycooler Model # Voltage Phase FLA WSA OPD
Standard Models
208/230 3 7.0 7.9 15
2 174, 225 460 3 3.4 3.8 15
575 3 2.8 3.2 15
Values are calculated per UL 1995. OPD values may be adjusted higher than calculations to compensate for maximum
anticipated application temperatures.

Table 20 60Hz electrical valuesDrycoolers with pump controls, 3/4 hp pump, standard models
# of Fans Drycooler Model # Voltage Phase FLA WSA OPD
208/230 3 10.5 11.4 15
2 174, 225 460 3 5 5.4 15
575 3 4.1 4.5 15

Table 21 60Hz pump FLA values


Input Power, Volts
Pump hp 208/230 460 575
3/4 3.5 1.6 1.3
Values based on NEC handbook values for 3-phase motors.

43 Liebert PDX and Liebert PCW


Electrical Data

Figure 28 Fan speed control direct drive drycoolers

Factory-wired to 24V
Class 2 control circuit. Factory-wired to components Electric service connection Electric service
on electric panel. to fuse block (factory-wired). connection terminals
for field wiring.

Factory-installed
disconnect switch.

Control Interlock
Class 2 wiring to
interlock drycooler 24V
controls to Liebert
room unit. 7/8 in.
(22.2mm) diameter hole
provided in bottom of
electric box. Pump fuses & overload
heaters (shipped with
Electric service connection standard pump packages)
terminals for power supply to are to be field-installed
pumps when pump controls in pump fuse block(s)
are factory-supplied. 7/8 in. and starter(s).
(22.2mm) diameter knockouts
provided in bottom of
electric box. Three
terminals for three-phase Electric service entrance.
Earth ground connection (60Hz). Electric service.
pump option only. A 7/8 in (22.2mm) diameter hole
Connection terminal for field- Single-phase, not by Emerson.
in a 1-1/8 in (28.6mm) knockout
supplied earth grounding wire. Three-phase, not by Emerson (for
provided in bottom of electric
Earth ground bar (50Hz). three-phase pump option only).
box.
Connection terminals with factory
ground from each high voltage
component for field-supplied Refer to specification sheet for full load amp DPN000277
earth grounding wire. and wire size amp ratings.
Rev. 1

Liebert PDX and Liebert PCW 44


Electrical Data

Figure 29 Fluid temperature control direct drive drycoolers

Electrical service connection


Factory-wired to 24V terminals when factory
Class 2 control circuit disconnect is not supplied.
Factory-wired to components Electric service connection
Fuse block supplied on terminals when factory
on electric panel
DNT drycoolers. disconnect is supplied.

Factory-installed
Unit Alarm Connection disconnect switch
Field-supplied 24V. (optional).
Class 2 wiring to
Terminals "24 & 50"
to indicate "Standby Glycol
Pump On". (Supplied
with dual pump controls
only.)

Control interlock
Field-supplied
Class 2 wiring to
interlock drycooler
24V controls to
Liebert room unit
(Not required on
CSU 3000). 7/8" Pump fuses & overload
(22.2mm) diameter heaters (shipped with
hole provided in standard pump packages)
bottom of electric box. are to be field-installed in
pump fuse block(s) and
Flow switch connection starter(s).
(Dual pump controls only)
Earth ground bar (50Hz).
Field-supplied 24V Class 2
Connection terminals with factory
wiring from terminals 74 +
ground from each high voltage
77 to field mounted flow
component for field-supplied
switch.
earth grounding wire. Electric service entrance. Electric service.
Electric service connection A 7/8" (22.2mm) diameter hole not by Emerson.
terminals for power supply to in a 1-1/8" (28.6mm) knockout (Field-wired to Liebert
pumps when pump controls Earth ground connection (60 HZ). provided in bottom of electric CSU 3000.
are factory-supplied. Dual Connection terminal for field- box. Interconnecting wiring
pump connection shown. 7/8" supplied earth grounding wire. not by Emerson).
(22.2mm) diameter knockouts
provided in bottom DPN000276
of electric box. Refer to specification sheet for full load amp and wire size amp ratings.
Rev. 1

45 Liebert PDX and Liebert PCW


Piping

7.0 PIPING
Table 22 Recommended refrigerant line sizes - OD copper (inches)*
Standard Scroll and Digital Scroll Models
Model PX018 PX023 PX029
Equivalent Hot Gas Liquid Hot Gas Liquid Hot Gas Liquid
Length Line Line Line Line Line Line
50 ft. (15m) 5/8 1/2 3/4 5/8 7/8 5/8
100 ft. (30m) 5/8 1/2 3/4 5/8 7/8 5/8
150 ft. (45m) 5/8 1/2 3/4 5/8 7/8 5/8
300 ft. (91m) 7/8 5/8 7/8 5/8 1-1/8 3/4
Source: DPN000788, Rev. 0

Table 23 Indoor unit approximate refrigerant charge for R-410A


R-410A Charge
System Type Model lb (kg)
PX018 5.0 (2.3)
Air-Cooled PX023 5.3 (2.4)
PX029 5.8 (2.6)

Table 24 Interconnecting piping refrigerant charge


R-410A, lb/100 ft. (kg/30m)
Line Size,
O.D., in. Liquid Line Hot Gas Line
3/8 3.2 (1.4)
1/2 5.9 (2.7) 0.7 (0.3)
5/8 9.6 (4.3) 1.1 (0.5)
3/4 14.3 (6.4) 1.6 (0.7)
7/8 19.8 (8.8) 2.3 (1.0)
1-1/8 33.8 (15.1) 3.9 (1.7)
1-3/8 51.5 (23.0) 5.9 (2.6)
Source: DPN003099, Rev. 0

Table 25 Condenser refrigerant charge


Standard Approximate R-410A Refrigerant Needed
Condenser Condensers Condensers
Models Without Liebert Lee-Temp With Liebert Lee-Temp
MCS028 2.5 (1.2) 18.3 (8.4)
MCM040 3.5 (1.6) 19.3 (8.8)
MCL055 5.0 (2.3) 24.2 (11.0)
MCM080 8.5 (3.8) 39.6 (18.1)
MCL110 10.7 (4.9) 49.0 (22.2)
MCL165 18.4 (8.4) 79.9 (36.2)
Source: DPN002411, Rev. 6

Liebert PDX and Liebert PCW 46


Piping

Figure 30 Piping schematicAir-cooled models


LIEBERT MC CONDENSER
LIEBERT MC CONDENSER
Check
WITH LIEBERT LEE-TEMP RECEIVER
Valve Relief Valve Service
Valve Liquid Return
Optional Field
Installed
Fusible Plug Head Pressure
LIEBERT LEE-TEMP RECEIVER Control Valve

CONDENSER Liquid
COIL Liquid
CONDENSER
COIL
Hot Gas
Discharge Hot Gas Discharge

LIEBERT PDX AND ASSOCIATED PIPING

Liquid

EVAPORATOR
Digital Solenoid Valve Sensing
COIL
Bulb
Suction
For rises over 25ft. (7.6m),
Service trap every 20ft. (6m) or
Valve evenly divided*

Check External
Valve Compressor Service Equalizer Trap at base of risers
Valve over 5ft. (1.5m)*

*Isolation
Valve

Hot Gas Discharge

Expansion Solenoid Sight Filter Drier Liquid Return


*Isolation
Valve Valve Glass Valve

* Components are not supplied by


Refrigerant Piping Emerson but are required for
Field Piping proper circuit operation and
maintenance
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core DPN002929
Schematic representation shown. Do not use for specific connection locations. Rev. 2

47 Liebert PDX and Liebert PCW


Piping

Figure 31 Piping schematicWater/glycol models


For systems with drycoolers,
refer to 5.0 - Heat RejectionDrycoolers and Pumps.

Expansion Optional Dual Pump System Shown


LIEBERT
Tank**
CUSTOMER HEAT REJECTION Glycol
HEAT REJECTION Pumps Check
Valves*
(on Dual Pump
Drycooler Systems only)
(Glycol) Pressure
Cooling Tower Gate Valves*
Aquastat Port*
and Pump
Sensing
System
by Others Bulbs
Hose Air Vents
Bib* Shutoff Valve* Pressure Port*
(typical)***
Flow Switch
Supplied with Dual
Pump Systems

Shutoff Valve* Flow-regulating


Return Supply Valve*

Return Supply

LIEBERT PDX UNIT


Return Supply
(and associated piping)
Optional 3-Way
Liquid Motorized Ball Shutoff Valve* Shutoff Valve*
Digital Solenoid Valve Sensing Bulb Evaporator Valve
Hose Hose
Coil Bib* Bib*
Suction

Service
Valve 2-Way
Service Motorized
Check Valve External From
Ball Valve
Valve Compressor Equalizer Liebert
Discharge iCOM
Control
Heat
Exchanger
To
Liebert
Expansion Sight Filter Drier
iCOM
Valve Glass
Pressure Control
Transducer

Factory Piping * Components are not supplied by DPN002931


Field Piping Emerson but are requird for proper Rev. 1
Optional Factory Piping circuit operation and maintenance
** Field installed at highest point in
Service / Schrader (Access) Connection No Valve Core system on return line to pumps
Service / Schrader (Access) Connection with Valve Core *** Locate at tops of all risers and
any intermediate system high points
NOTE: Schematic representation shown.This schematic does not imply or define elevations and component location, unless
specifically noted.

Liebert PDX and Liebert PCW 48


Piping

Figure 32 Piping schematicGLYCOOL models


For systems with drycoolers, refer Expansion Optional Dual Pump System shown
to 5.0 - Heat RejectionDrycoolers LIEBERT
Tank**
and Pumps. HEAT REJECTION Glycol
Pumps
Check Valves*
Drycooler (on Dual Pump
(Glycol) Pressure Port* Systems only)
Aquastat Gate Valves*
Sensing
Bulbs
Hose Air Vents Pressure Port*
Bib* Shut-Off Valve* (typical)***
Flow Switch
Supplied with Dual
Pump Systems

Flow-Regulating
Shutoff Valve*
Valve*

Return Supply

LIEBERT PDX UNIT Econ-O-Coil Return Supply


(and associated piping) Shutoff Valve* Shutoff Valve*
Liquid 3-way
Digital Solenoid Valve Chilled Hose Hose
Sensing Bulb Evaporator Glycol Thermistor Bib* Bib*
Coil Valve
Suction

Service
Valve Service 3-Way
Valve External Motorized From
Check Compressor
Valve Equalizer Ball Valve Liebert
Discharge iCOM
Control
Heat
Exchanger
To Liebert
Expansion Sight Filter Drier iCOM
Valve Glass Pressure Control
Transducer

Factory Piping * Components are not supplied by DPN002932


Emerson but are required for
Rev. 1
Field Piping
proper circuit operation and
Service / Schrader (access) connection no valve core
maintenance
Service / Schrader (access) connection with valve core ** Field-installed at highest point in
NOTE: Schematic representation shown. This schematic system on return line to pumps
does not imply or define elevations and component location, *** Locate at tops of all risers and
unless specifically noted. any intermediate system high points

49 Liebert PDX and Liebert PCW


Piping

Figure 33 Piping schematic, chilled water units

CUSTOMER
HEAT REJECTION

CHILLED
WATER
SUPPLY

RETURN SUPPLY

LIEBERT PCW
(And Associated Piping) RETURN SUPPLY

Bleed Valve Optional 3-way Shutoff Valve* Shutoff Valve*


Chilled Water
Valve Hose
CHILLED Hose Bib*
WATER Bib*
COIL

2-way
Chilled Water
Valve From
Liebert
iCOM

Factory Piping
* Components are not supplied by
Field Piping
Emerson but are required for
Optional Factory Piping
proper circuit operation and
Schematic representation shown. This schematic does maintenance
not imply or define elevations and component location
unless specifically noted.
DPN002930
Rev. 2

Liebert PDX and Liebert PCW 50


Piping

Figure 34 Optional piping schematic for Econ-O-Coil

Return Supply Return Supply

Thermistor* Thermistor* Actuator


Actuator

Return Return

Supply Supply
Liebert Econ-O-Coil Liebert Econ-O-Coil

Optional Liebert Econ-O-Coil (2-way valve) Optional Liebert Econ-O-Coil (3-way valve)
Factory Piping
* Supplied with 10 ft. (3m) extra thermistor wire for installation on field supply line.
Field Piping
1) Place thermistor in location where flow is always present.
DPN002972
2) Thermistor must be located out of the supply air stream.
Rev. 0

51 Liebert PDX and Liebert PCW


Piping

Figure 35 Primary connection locationsLiebert PDX downflow, air-cooled models


All dimensions from
NOTE: Drawing not to scale. rear corner of unit
Tolerance on all piping dimensions including panels
All dimensions from X
O
is 1/2" (13mm).
rear corner of unit
X including panels Y
O ECS
Y
CD
33"
Electrical Top (837mm)
ECR
Connections
L1
CE
LV3 E2
E3 E1 LV2 G1
E4 HUM

TOP VIEW Front of Unit Front of Unit LV1


34-1/2"
(876mm)
Section A-A

Supply Air
28-1/2"
Discharge
(725mm) Opening
A A 30-1/2"
(775mm)
B B
FRONT VIEW Section B-B Front
of Unit
* Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain
a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water.
Select appropriate drain system materials. The drain line must comply with all local codes.
DPN002938
** Supplied on Dual Cooling Systems only (4 pipe system) Rev. 2

Connection Size/Opening, in.


Point Description X, in. (mm) Y, in. (mm) PX018, PX023 PX029
L1 Liquid Line System 1 2-7/8 (73) 24-3/4 (630) 1/2" 5/8"
G1 Hot Gas Discharge 1 2-7/8 (73) 27-3/8 (694) 5/8" 7/8"
CD Condensate Drain* 32 (811) 12-1/8 (309) 3/4
CE Condensate Electrical 31-1/4 (796) 23-3/4 (606) 1-1/2
HUM Humidifier Supply Line 32 (815) 30-1/8 (766) 1/4
ECS Econ-O-Coil Supply ** 2-7/8 (73) 7-5/8 (195) 1-1/8
ECR Econ-O-Coil Return ** 2-7/8 (73) 11-3/4 (298) 1-1/8
E1 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 28-3/8 (722) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 26-1/8 (665) 7/8, 1-3/8, 1-3/4
E3 Electrical Connection (High-Voltage) Top 31 (788) 27-3/4 (704) 7/8, 1-3/8, 1-3/4
E4 Electrical Connection (High-Voltage) Top 31 (788) 30 (760) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) Bottom 2-3/4 (70) 30-1/4 (768) 1-1/8
LV2 Electrical Connection (Low-Voltage) Bottom 3-7/8 (98) 29-1/8 (740) 1-1/2
LV3 Electrical Connection (Low-Voltage) Top 31-5/8 (802) 24-7/8 (631) 1
Source: DPN002938, Rev. 2

Liebert PDX and Liebert PCW 52


Piping

Figure 36 Primary connectionsLiebert PDX downflow, air cooled, front discharge models
All dimensions from All dimensions from
rear corner of unit rear corner of unit
X including panels including panels
O X O

Note: Drawing not to scale. Y


Y ECS
Tolerance on
all piping dimensions
is 1/2" (13mm). Electrical Top
33"
Connections (837mm)
ECR
L1
LV1
E1
E2 G1

Front of Unit Front of Unit


TOP VIEW
34-1/2" (876mm)

SECTION C-C
HUM ECR
ECS
L1

G1 Z
CE CD Y
Without Left Side Discharge Without Right Side Discharge

HUM ECR
C C ECS
L1

G1
FRONT VIEW Z
CE CD Y
With Left Side Discharge With Right Side Discharge

1. Pipes at various heights to allow using tube cutter. These locations


will require stub tubes and elbows for connection.
2. Humidifier will need to be routed through this opening to the
connection at the left hand side of the unit.
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling DPN002945
water. Select appropriate drain system materials. The drain line must comply with all local codes. Rev. 0
** Supplied on dual cooling systems only (four-pipe system)

Connection Size/Opening, in.


Point Description X, in. (mm) Y, in. (mm) Z, in. (mm) PX018, PX023 PX029
L1 Liquid Line System 2-7/8 (73) 24-3/4 (630mm) 3 (76) 1/2 5/8
G1 Hot Gas Discharge 2-7/8 (73) 27-3/8 (694) 3 (76) 5/8 7/8
CD Condensate Drain* 12-1/8 (309) 3 (76) 3/4 FPT
CE Condensate Electrical 23-3/4 (606) 2-3/4 (70) 1-3/8
HUM Humidifier Supply Line 30-1/8 (766) 2-1/2 (64) 1/4
ECS Econ-O-Coil Supply ** 2-7/8 (73) 7-5/8 (195) 3 (76) 1-1/8
ECR Econ-O-Coil Return ** 2-7/8 (73) 11-3/4 (298) 3 (76) 1-1/8
E1 Electrical Connection (High-Voltage) 31 (788) 27-3/4 (704) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) 31 (788) 30 (761) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) 31-5/8 (802) 27-7/8 (631) 1
Source: DPN002945, Rev. 0

53 Liebert PDX and Liebert PCW


Piping

Figure 37 Primary connection locationsLiebert PDX downflow, water/glycol/GLYCOOL-cooled models


All dimensions from
Note: Drawing not to scale. All dimensions from rear corner of unit
Tolerance on rear corner of unit including panels
all piping dimensions including panels X
O
is 1/2" (13mm).
X Y
O WSG
ECS
Y CD ECR

Electrical Top 33"


WS
Connections (837mm)

LV3 CE
E3 E2
E1 LV2 WR
E4 HUM

Front of Unit Front of Unit LV1


TOP VIEW
34-1/2" (876mm)

SECTION A-A

28-1/2" Supply Air


(725mm) Discharge Opening

A A 30-1/2"
(775mm)

B FRONT VIEW B
SECTION B-B
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling DPN002942
water. Select appropriate drain system materials. The drain line must comply with all local codes. Rev. 1
** Supplied on dual cooling systems only (four-pipe system)

Point Description X in. (mm) Y in. (mm) Connection Size / Opening, in.
WS Water/Glycol Supply 2-7/8 (74) 11-3/4 (297) 1-1/8
WR Water/Glycol/GLYCOOL Return 2-7/8 (73) 27-3/8 (694) 1-1/8
WSG GLYCOOL Supply 2-7/8 (73) 7-5/8 (195) 1-1/8
CD Condensate Drain* 32 (811) 12-1/8 (309) 3/4
CE Condensate Electrical 31-1/4 (796) 23-3/4 (606) 1-1/2
HUM Humidifier Supply Line 32 (815) 30-1/8 (766) 1/4
ECS Econ-O-Coil Supply ** 2-7/8 (73) 7-5/8 (195) 1-1/8
ECR Econ-O-Coil Return ** 2-7/8 (73) 11-3/4 (298) 1-1/8
E1 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 28-3/8 (722) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 26-1/8 (665) 7/8, 1-3/8, 1-3/4
E3 Electrical Connection (High-Voltage) Top 31 (788) 27-3/4 (704) 7/8, 1-3/8, 1-3/4
E4 Electrical Connection (High-Voltage) Top 31 (788) 30 (760) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) Bottom 2-3/4 (70) 30-1/4 (768) 1-1/8
LV2 Electrical Connection (Low-Voltage) Bottom 3-7/8 (98) 29-1/8 (740) 1-1/2
LV3 Electrical Connection (Low-Voltage) Top 31-5/8 (802) 24-7/8 (631) 1
Source: DPN002942, Rev. 1

Liebert PDX and Liebert PCW 54


Piping

Figure 38 Primary connection locationsLiebert PDX downflow, water/glycol/GLYCOOL-cooled, front


discharge models
All dimensions from
NOTE: Drawing not to scale.
rear corner of unit All dimensions from
Tolerance on
including panels rear corner of unit
all piping dimensions
is 1/2" (13mm). X including panels X
O O
Y
WSG
Y ECS
ECR
Electrical Top
Connections
33" WS
(837mm)
LV1
E1
E2 WR

Front of Unit Front of Unit


TOP VIEW 34-1/2" (875.9mm)

SECTION C-C
HUM WS ECR

Without Left Side Discharge WR Z


CE CD Y

C C Without Right Side Discharge


HUM WS ECR
ECS
FRONT VIEW
WR
With Left Side Discharge
Z
Notes CE CD
1. Pipes at various heights to allow tube cutter to be used. Will
require stub tubes and elbows for connection at these locations.
With Right Side Discharge
2. Humidifier must be routed through this opening to the
connection at the left hand side of the unit.
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling
water. Select appropriate drain system materials.The drain line must comply with all local codes. DPN002947
** Supplied on dual cooling systems only (four-pipe system)
Rev. 0

Point Description X, in. (mm) Y, in. (mm) Z, in. (mm) Connection Size / Opening, in.
WS Water/Glycol Supply 2-7/8 (74) 16-1/4 (413) 3 (76) 1-1/8
WR Water/Glycol/GLYCOOL Return 2-7/8 (73) 27-3/8 (694) 3 (76) 1-1/8
WSG Glycool Supply 2-7/8 (73) 7-5/8 (195) 3 (76) 1-1/8
CD Condensate Drain* 21-1/8 (537) 3 (76) 3/4
CE Condensate Electrical 22-3/4 (578) 2-3/4 (70) 1-3/8
HUM Humidifier Supply Line 20 (508) 2-1/2 (64) 1/4
ECS Econ-O-Coil Supply ** 2-7/8 (73) 7-5/8 (195) 3 (76) 1-1/8
ECR Econ-O-Coil Return ** 2-7/8 (73) 11-3/4 (298) 3 (76) 1-1/8
E1 Electrical Conn. (High-Voltage) Bottom 31 (787) 27-3/4 (705) 7/8, 1-3/8, 1-3/4
E2 Electrical Conn. (High-Voltage) Bottom 31 (787) 30 (762) 7/8, 1-3/8, 1-3/4
LV1 Electrical Conn. (Low-Voltage) Bottom 31-5/8 (805) 24-7/8 (632) 1-1/8
Source: DPN002947, Rev. 0

55 Liebert PDX and Liebert PCW


Piping

Figure 39 Primary connection locations, Liebert PCW chilled water downflow models
NOTE: Drawing not to scale.
Tolerance on All dimensions from
all piping dimensions rear corner of unit
is 1/2" (13mm). All dimensions from including panels
X rear corner of unit X
O
O including panels
Y
HWR
Y

CD
Electrical Top
33"
Connections (836.5mm) HWS
WS
CE
LV3 E2 WR

E3 E1 LV2
HUM
E4
Front of Unit LV1
TOP VIEW Front of Unit
34-1/2" (875.9mm)

SECTION A-A

28-1/2" Supply Air


(725mm)
Discharge Opening
A A
30-1/2" (775.1mm)

FRONT VIEW
B B SECTION B-B
* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain DPN002940
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling
Rev. 1
water. Select appropriate drain system materials. The drain line must comply with all local codes.

Point Description X Y Connection Size / Opening


HWR Hot Water Reheat Return (Optional) 2-7/8 (73) 7-5/8 (195) 5/8
HWS Hot Water Reheat Supply (Optional) 2-7/8 (73) 11-3/4 (298) 5/8
WS Water Supply 2-7/8 (73) 7-5/8 (195) 1-1/8
WR Water Return 2-7/8 (73) 11-3/4 (298) 1-1/8
CD Condensate Drain* 32 (811) 12-1/8 (309) 3/4
CE Condensate Electrical 31-1/4 (796) 23-3/4 (606) 1-1/2
HUM Humidifier Supply Line 32 (815) 30-1/8 (766) 1/4
E1 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 28-3/8 (722) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) Bottom 31-1/2 (801) 26-1/8 (665) 7/8, 1-3/8, 1-3/4
E3 Electrical Connection (High-Voltage) Top 31 (788) 27-3/4 (704) 7/8, 1-3/8, 1-3/4
E4 Electrical Connection (High-Voltage) Top 31 (788) 30 (760) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) Bottom 2-3/4 (70) 30-1/4 (768) 1-1/8
LV2 Electrical Connection (Low-Voltage) Bottom 3-7/8 (98) 29-1/8 (740) 1-1/2
LV3 Electrical Connection (Low-Voltage) Top 31-5/8 (802) 24-7/8 (631) 1
Source: DPN002940, Rev. 1

Liebert PDX and Liebert PCW 56


Piping

Figure 40 Primary connection locations, Liebert PCW chilled water downflow models, front discharge
All dimensions from
All dimensions from rear corner of unit
rear corner of unit including panels
X including panels X
O O
NOTE: Drawing not to scale.
Tolerance on Y
Y HWR
all piping dimensions
is 1/2" (13mm).
Electrical Top
33"
Connections (836.5mm) HWS
WS
LV1
WR
E1
E2

Front of Unit Front of Unit


TOP VIEW
34-1/2" (875.9mm)

SECTION C-C
HUM HWS
HWR
WS

Without Left Side Discharge WR Z


CE CD Y
C C Without Right Side Discharge

HUM HWS
HWR
FRONT VIEW WS
With Left Side Discharge WR
Z
Notes CE CD Y
1. Pipes at various heights to allow tube cutter to be used. With Right Side Discharge
Stub tubes and elbows required for connection at these locations.
2. Humidifier must be routed through this opening to the
connection at the left hand side of the unit

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling DPN002946
water. Select appropriate drain system materials.The drain line must comply with all local codes. Rev. 0

Point Description X, in. (mm) Y, in. (mm) Z, in. (mm) Connection Size / Opening, in.
HWR Hot Water Reheat Return (Optional) 2-7/8 (73) 7-5/8 (195) 3 (76) 5/8
HWS Hot Water Reheat Supply (Optional) 2-7/8 (73) 11-3/4 (298) 3 (76) 5/8
WS Water Supply 2-7/8 (73) 24-3/4 (629) 3 (76) 1-1/8
WR Water Return 2-7/8 (73) 27-3/8 (695) 3 (76) 1-1/8
CD Condensate Drain* 21-1/8 (537) 3 (76) 3/4
CE Condensate Electrical 22-3/4 (606) 2-3/4 (70) 1-1/2
HUM Humidifier Supply Line 20 (508) 2-1/2 (64) 1/4
E1 Electrical Conn. (High-Voltage) Top 31 (788) 27-3/4 (704) 7/8, 1-3/8, 1-3/4
E2 Electrical Conn. (High-Voltage) Top 31 (788) 30 (760) 7/8, 1-3/8, 1-3/4
LV1 Electrical Conn. (Low-Voltage) Top 31-5/8 (802) 24-7/8 (631) 1
Source: DPN002946, Rev. 0

57 Liebert PDX and Liebert PCW


Piping

Figure 41 Primary connection locations, Liebert PCW air-cooled upflow models


NOTE: Drawing not to scale.
Tolerance on all piping
dimensions is 1/2" (13mm).
34-1/2" All dimensions from
(876mm) rear corner of unit
X
O including panels

ECS
CDP

ECR
32-1/2"
(828mm)
L1
G1
HUM
E2 LV2
E1
LV1

TOP VIEW Front of Unit

30-1/2"
(775mm)
FRONT VIEW
28-1/2"
(725mm)
Dimensions from Supply Air
rear bottom corner of Discharge Opening
unit including panels
CD
Y

O
X
TOP VIEW Front of Unit
RIGHT SIDE VIEW
* Field pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units
contain a factory installed condensate trap. Do not trap external to the unit. Drain line
may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
** Supplied on dual-cooling systems only. DPN002939
*** Unit with front return shown. Bottom return with rear return floor stand also available. Rev. 1

Connection Size/Opening, in.


Point Description X, in. (mm) Y, in. (mm) PX018, PX023 PX029
L1 Liquid Line System 1 5-1/8 (131) 25-5/8 (652) 1/2" 5/8"
G1 Hot Gas Discharge 1 2-7/8 (73) 25-5/8 (652) 5/8" 7/8"
CD Condensate Drain* 16-5/8 (422) 3-1/4 (80) 3/4 FPT
CDP Condensate Drain with Pump 3-1/4 (83) 5-7/8 (149) 1/2"
HUM Humidifier Supply Line 29-1/2 (750) 26 (663) 1/4
ECS Econ-O-Coil Supply ** 4-1/4 (111) 3-1/4 (81) 1-1/8
ECR Econ-O-Coil Return ** 2-5/8 (67) 10 (256) 1-1/8
E1 Electrical Connection (High-Voltage) 31-1/4 (794) 30 (761) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) 31-1/4 (794) 27-3/4 (702) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) 1-1/2 (38) 27-1/2 (699) 1
LV2 Electrical Connection (Low-Voltage) 1-1/2(38) 26-1/2 (673) 1
Source: DPN002939, Rev. 1

Liebert PDX and Liebert PCW 58


Piping

Figure 42 Primary connection locationsLiebert PDX upflow, water/glycol/GLYCOOL models


NOTE: Drawing not to scale.
Tolerance on all
piping dimensions All dimensions from
is 1/2" (13mm). 34-1/2" rear corner of unit
(876mm) X including panels
O

Y
ECS
CDP

ECR
32-1/2"
(828mm)

WS WR
HUM
E2 LV2
E1 LV1

TOP VIEW Front of Unit

FRONT VIEW
30-1/2"
Dimensions from (775mm)
rear bottom corner of 28-1/2"
unit including panels (725mm)
Supply Air
CD Discharge Opening

Y
X O

RIGHT SIDE VIEW


TOP VIEW Front of Unit

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units
contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials.The drain line must comply
with all local codes.
** Supplied on dual cooling systems only (4 pipe system) DPN002943
*** Unit with front return shown. Bottom return with rear return floor stand also available. Rev 0
Point Description X in. (mm) Y in. (mm) Connection Size / Opening, in.
WS Water/Glycol/GLYCOOL 5-1/8 (74) 25-5/8 (297) 1-1/8
WR Water/Glycol/GLYCOOL Return 2-7/8 (73) 25-5/8 (652) 1-1/8
CD Condensate Drain* 16-5/8 (422) 3-1/4 (80) 3/4 FPT
CDP Condensate Drain With Pump 3-1/4 (83) 5-7/8 (149) 1/2
HUM Humidifier Supply Line 29-1/2 (750) 26 (663) 1/4
ECS Econ-O-Coil Supply ** 4-1/4' (111) 3-1/4 (81) 1-1/8
ECR Econ-O-Coil Return ** 2-5/8 (67) 10 (256) 1-1/8
E1 Electrical Connection (High-Voltage) 31-1/4 (794) 30 (761) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) 31-1/4 (794) 27-3/4 (702) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) 1-1/2 (38) 27-1/2 (699) 1
LV2 Electrical Connection (Low-Voltage) 1-1/2 (38) 26-1/2 (673) 1
Source: DPN002943, Rev. 0

59 Liebert PDX and Liebert PCW


Piping

Figure 43 Primary connection locations, Liebert PCW chilled water upflow models

NOTE: Drawing not to scale. All dimensions from


Tolerance on all piping rear corner of unit
dimensions is 1/2" (13mm). 34-1/2" including panels
(875.8mm) X
O

CDP

32-1/2"
(828.0mm)

WS WR
HUM
E2 LV2
E1 LV1

TOP VIEW Front of Unit

30-1/2"
FRONT VIEW (775.0mm)

Dimensions from 28-1/2" Supply Air


rear bottom corner of (725.0mm)
Discharge Opening
unit including panels
CD
Y

O
X
RIGHT SIDE VIEW TOP VIEW Front of Unit

* Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain
a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water.
Select appropriate drain system materials. The drain line must comply with all local codes.
** Unit with front return shown. Bottom return with rear return floor stand also available. DPN002941
Rev. 0
X Y
Point Description in. (mm) in. (mm) Connection Size / Opening, in.
WS Water Supply 5-1/8 (131) 25-5/8 (652) 1-1/8
WR Water Return 2-7/8 (73) 25-5/8 (652) 1-1/8
CD Condensate Drain* 16-5/8 (422) 3-1/4 (80) 3/4 FPT
CDP Condensate Drain With Pump 3-1/4 (83) 5-7/8 (149) 1/2
HUM Humidifier Supply Line 29-1/2 (750) 26 (663) 1/4
E1 Electrical Connection (High-Voltage) 31-1/4 (794) 30 (761) 7/8, 1-3/8, 1-3/4
E2 Electrical Connection (High-Voltage) 31-1/4 (794) 27-3/4 (702) 7/8, 1-3/8, 1-3/4
LV1 Electrical Connection (Low-Voltage) 1-1/2 (38) 27-1/2 (699) 1
LV2 Electrical Connection (Low-Voltage) 1-1/2 (38) 26-1/2 (673) 1
Source: DPN002941, Rev. 0

Liebert PDX and Liebert PCW 60


Piping

Figure 44 Liebert MC Condenser pipingSingle-circuit units

* Cover
Note: The Liebert
MCs refrigerant lines
have traps inside the
unit; external traps
are not needed.

Leaving Fan 2
Liquid
Line
Fan 1

Entering
Field Piping
Hot Gas
Vertical Line
Optional fusible plug service kit to be brazed into the liquid line(s)
in either the vertical or horizontal position (where required).
Horizontal Vertical position is recommended; horizontal position is optional.

Horizontal
Vertical

Leaving
Liquid
Line DPN002166
MCS028 ONLY
Rev. 2

Table 26 Liebert MC Condenser piping sizes, single-circuit units


Connection Sizes, OD, in (mm)
Number
Model No. of Fans Hot Gas Line Liquid Line
MCS028 1 7/8 5/8
MCM040 1 7/8 5/8
MCL055 1 1-1/8 7/8
MCM080 2 1-1/8 7/8
MCL110 2 1-3/8 1-1/8
MCL165 3 1-3/8 1-1/8
Source: DPN002166, Rev. 2

61 Liebert PDX and Liebert PCW


Piping

Figure 45 Condenser piping for single-circuit condensers (with Liebert Lee-Temp)

Entering Hot Hot Gas Line


Gas Line To Condenser

Metal Clamp

Isolator
Detail A-A
Position Elbow to
Direct Relief Valve Fasten hot gas line to cabinet
Downward B VIEW using flat surface clamps with
isolators (field-supplied)
Leaving
Liquid Line See Detail A-A
Liquid Line
From Condenser
Field Piping
GENERAL ARRANGEMENT

Emerson-supplied piping assembly


will include one to three valves and check
valves depending on condenser capacity
and refrigerant
NOTE:
1.The following materials are supplied by liebert for each circuit (shipped loose with condenser) for field
installation: insulated Liebert Lee-Temp receiver with electric heater pads, sight glasses, head pressure
control valve, check valve, rotalock valve and pressure relief valve. All other piping to be supplied
and installed by others.
DPN002167
2. Consult factory for proper line sizing for runs longer than 150ft.(45.7m) equivalent length. Rev. 5

Table 27 Condenser piping connection sizessingle-circuit condensers with Liebert Lee-Temp


Condenser
Connections, OD.In Liebert Lee-Temp Connections
Liquid Line
to Liebert
Hot Gas Tee Lee-Temp Valve Receiver Out
Model # Hot Gas Liquid IDS, In. ODS, In. IDS, In.
MCS028 7/8 5/8 7/8 5/8 5/8
MCM040 7/8 5/8 7/8 5/8 5/8
MCL055 1-1/8 7/8 1-1/8 7/8 7/8
MCM080 1-1/8 7/8 1-1/8 7/8 1-1/8
MCL110 1-3/8 1-1/8 1-3/8 1-1/8 1-1/8
MCL165 1-3/8 1-1/8 1-3/8 1-1/8 1-1/8
Source: DPN002167, Rev. 5

Liebert PDX and Liebert PCW 62


Piping

Figure 46 Piping connection locations for 1-, 2-, 3- and 4-fan drycoolers

Inlet Connection
(Upper Header)
Outlet Connection
(Lower Header)

DPN000275
1/2" FPT Connections Rev. 3
EXPANSION TANK
(GLYCOOL CSU 3000
Units Supplied with
Compression Tank)
Table 28 Standard drycooler piping connection sizes and internal volume
Internal
No. of Internal No. of Dry Weight Volume, No. of Inlet and Outlet Connection
Model # Coil Circuits Fans lb. (kg) gal. (L) Inlets/Outlets Size, OD Copper, in.
174 8 2 540 (245) 6.9 (26.2) 1/1 2-1/8
197 16 2 580 (263) 9 (34) 1/1 2-1/8
225 26 2 620 (281) 11.1 (42.1) 1/1 2-1/8
260 16 3 735 (333) 10.0 (37.8) 1/1 2-1/8
350 16 3 795 (361) 13.1 (50.0) 1/1 2-1/8

63 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

8.0 GUIDE SPECIFICATIONSNOMINAL 17, 18, 23 OR 29KW THERMAL


MANAGEMENT SYSTEM

1.0 GENERAL
1.1 SUMMARY
These specifications describe requirements for a mission critical environmental control system. The
system shall be designed to control temperature and humidity conditions in rooms containing
electronic equipment, with good insulation and vapor barrier. The manufacturer shall design and
furnish all equipment to be fully compatible with the heat dissipation requirements of the room.

1.2 DESIGN REQUIREMENTS


The precision environmental control system shall be a Liebert PDX or Liebert PCW factory-
assembled unit. Standard 60Hz units shall be CSA-certified to the harmonized U.S. and Canadian
product safety standard, CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and are
marked with the CSA c-us logo. It shall be specifically designed for service from the front and right
side of the unit. The system shall be designed for draw-through air arrangement to insure even air
distribution to the entire face area of the coil.

1.3 SUBMITTALS
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams;
Dimensional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.

1.4 SERVICEABILITY/ ACCESS


The cabinet shall be designed so all components are easily accessible for service and maintenance
through the front and right sides of the unit.

2.0 PRODUCT
2.1 COOLING SYSTEM
2.1.1 Air-Cooled Refrigeration SystemModel 018, 023, and 029
2.1.1.1 System Description
Single refrigeration circuit shall include a liquid line filter drier, a refrigerant sight glass with
moisture indicator, an expansion valve, pressure safety switches and a liquid line solenoid valve. The
indoor evaporator refrigerant piping shall be filled with a nitrogen holding charge and spun shut.
Field relief of the Schrader valve shall indicate a leak-free system.
2.1.1.2 Hydrophilic-Coated Evaporator Coil
Liebert PDX
Model 018
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92 m2) face area, three rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 283 FPM (1.4 m/s) at 2800 CFM (4757 CMH).
Model 023
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92 m2) face area, three rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 354 FPM (1.8 m/s) at 3500 CFM (5947 CMH).

Liebert PDX and Liebert PCW 64


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Model 029
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92 m2) face area, four rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 434 FPM (2.2 m/s) at 4300 CFM (7306 CMH).
2.1.1.3 R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for
phaseout of HCFC refrigerants.
2.1.1.4 Compressor
Digital Scroll Compressor
The compressor shall be an R-410A scroll-type with variable capacity operation from 20-100%,
commonly known as a Digital Scroll. The compressor solenoid valve shall unload the compressor to
provide variable capacity operation. The compressor shall have a suction gas cooled motor, EPDM
Rubber vibration isolators, internal thermal overloads, automatic reset high pressure switch with
lockout after three failure occurrences, rotalock service valves, low pressure transducer, and
crankcase heater. The compressor shall be removable and serviceable from the front of the unit. The
crankcase heater and a discharge check valve shall be provided for additional system protection from
refrigerant migration during Off cycles.
Compressor Sound Jacket (Optional)
The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall
consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
Standard Scroll Compressor
The compressor shall be an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration
isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three
failures, rotalock service valves, pump down and low pressure transducer. The crankcase heater and
a discharge check valve shall be provided for additional system protection from refrigerant migration
during Off cycles.
2.1.1.5 Expansion Valve
Thermostatic Expansion Valve (TXV)
A manual adjustable externally equalized expansion valve thermostatic expansion valve (TXV) shall
control the flow of liquid refrigerant entering the direct expansion coil. The TXV shall maintain
consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the unit's
operating range. The TXV shall prevent liquid refrigerant from returning to the compressor.
Precision Controlled Electronic Expansion Valve (Optional for Digital Scroll
Compressors)
A precision controlled electronic expansion valve expansion valve (EEV) shall be provided. The EEV
shall be of stepper-motor type. The EEV shall maintain consistent superheat of the refrigerant vapor
at the outlet of the evaporator coil over the unit's operating range. The valve shall be controlled by a
separate electronic controller. Superheat shall be determined through the suction pressure-
temperature method
2.1.2 Dual Cool: Chilled Water + Air-Cooled Refrigeration (Model 018, 023, and 029)
2.1.2.1 System Description
Two independent circuits shall be included. The dual-cooling source system shall consist of an air-
cooled system with the addition of a free-cooling chilled water coil or free-coiling chilled glycol coil
(Econ-O-Coil), a modulating control valve and a comparative temperature sensor. The system shall be
able to function either as a modulating chilled water system or as a compressorized system, or a
combination of both. The primary cooling mode shall be chilled water. The secondary refrigeration
circuit shall include a liquid line filter drier, a refrigerant sight glass with moisture indicator, an
expansion valve, pressure safety switch, and a liquid line solenoid valve. The indoor evaporator
refrigerant piping shall be filled with a nitrogen holding charge and spun shut. Field relief of the
Schrader valve shall indicate a leak-free system. Switchover between the two cooling modes shall be
performed automatically by the microprocessor control.

65 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.2.2 Hydrophilic-Coated Evaporator Coil


Liebert PDX (Model 018, 023, and 029)
Model 018
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be three rows deep. The free-cooling chilled water coil shall have 9.4 ft2 (0.87 m2) face area.
The free-cooling chilled water coil shall be four rows deep. It shall be constructed of copper tubes and
hydrophilic coated aluminum fins. The hydrophilic coating shall significantly improve the speed of
condensate drainage from the fins and shall provide superior water carryover resistance. One
stainless steel condensate drain pan shall be provided. It shall have a face velocity of 298 FPM (1.5
m/s) at 2800 CFM (4757 CMH).
Model 023
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be three rows deep. The free-cooling chilled water coil shall have 9.4 ft2 (0.87 m2) face area.
The free-cooling chilled water coil shall be four rows deep. It shall be constructed of copper tubes and
hydrophilic coated aluminum fins. The hydrophilic coating shall significantly improve the speed of
condensate drainage from the fins and shall provide superior water carryover resistance. One
stainless steel condensate drain pan shall be provided. It shall have a face velocity of 372 FPM
(1.9 m/s) at 3500CFM (5947CMH).
Model 029
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be four rows deep. The free-cooling chilled water coil shall have 9.4 ft2 (0.87 m2) face area.
The free-cooling chilled water coil shall be four rows deep. It shall be constructed of copper tubes and
hydrophilic coated aluminum fins. The hydrophilic coating shall significantly improve the speed of
condensate drainage from the fins and shall provide superior water carryover resistance. One
stainless steel condensate drain pan shall be provided. It shall have a face velocity of 457 FPM
(2.3 m/s) at 4300 CFM (7306 CMH).
2.1.2.3 R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for
phaseout of HCFC refrigerants.
2.1.2.4 Compressor
Digital Scroll Compressor
The compressor shall be an R-410A scroll-type with variable capacity operation from 20-100%,
commonly known as a Digital Scroll. The compressor solenoid valve shall unload the compressor to
provide variable capacity operation. The compressor shall have a suction gas cooled motor, EPDM
Rubber vibration isolators, internal thermal overloads, automatic reset high pressure switch with
lockout after three failure occurrences, rotalock service valves, low pressure transducer, and
crankcase heater. The compressor shall be removable and serviceable from the front of the unit. The
crankcase heater and a discharge check valve shall be provided for additional system protection from
refrigerant migration during Off cycles.
Compressor Sound Jacket (Optional)
The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall
consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
Standard Scroll Compressor
The compressor shall be an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration
isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three
failures, rotalock service valves, pump down and low pressure transducer. The crankcase heater and
a discharge check valve shall be provided for additional system protection from refrigerant migration
during Off cycles.

Liebert PDX and Liebert PCW 66


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.2.5 Expansion Valve


Thermostatic Expansion Valve (TXV)
A manual adjustable externally equalized expansion valve thermostatic expansion valve (TXV) shall
control the flow of liquid refrigerant entering the direct expansion coil. The TXV shall maintain
consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the unit's
operating range. The TXV shall prevent liquid refrigerant from returning to the compressor.
Precision Controlled Electronic Expansion ValveOptional for Digital Scroll
Compressors
A precision controlled electronic expansion valve expansion valve (EEV) shall be provided. The EEV
shall be of stepper-motor type. The EEV shall maintain consistent superheat of the refrigerant vapor
at the outlet of the evaporator coil over the unit's operating range. The valve shall be controlled by a
separate electronic controller. Superheat shall be determined through the suction pressure-
temperature method
2.1.2.6 Dual-Cool: Free-Cooling Control Valve
Three-Way Motorized Ball Valve
The water circuit shall include a pre-piped 3-way motorized ball valve. The Liebert iCOM control
shall manage the valve actuator movement to maintain the desired room conditions for various
entering water temperatures. Cooling capacity will be controlled by bypassing chilled water around
the coil.
Two-Way Motorized Ball ValveOptional
The water circuit shall include a pre-piped 2-way motorized ball valve. The Liebert iCOM shall
manage the valve actuator movement to maintain the desired room conditions for various entering
water temperatures. The motorized ball valve travel for dehumidification shall be proportional.
2.1.2.7 Comparator Sensor
The system shall be equipped with a Liebert iCOM microprocessor-controlled comparator sensor that
permits free-cooling operation whenever entering chilled water temperature is below return-air
temperature. The comparator sensor shall be factory-installed on a free-cooling 3-way valve and field-
installed on a free-cooling 2-way valve.
2.1.2.8 System Design Pressure
Standard Pressure
The water circuit shall be designed for a pressure of 150PSI (1034kPa)
High Pressure (OPTIONAL)
The water circuit shall be designed for a pressure of 400PSI (2758kPa).
2.1.3 Water / Glycol Cooled Refrigeration System (Model 018, 023, and 029)
2.1.3.1 System Description
Single refrigeration circuit shall include a liquid line filter drier, an expansion valve. The water
piping shall be filled with a nitrogen holding charge and spun shut. Field relief of the Schrader valve
shall indicate a leak-free system

67 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.3.2 Hydrophilic-Coated Evaporator Coil


Liebert PDX (Model 018, 023, and 029)
Model 018
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92m2) face area, three rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 283 FPM (1.4 m/s) at 2800 CFM (4757 CMH).
Model 023
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92m2)) face area, three rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 354 FPM (1.8 m/s) at 3500 CFM (5947 CMH).
Model 029
The direct-expansion, tilted-slab cooling coil shall have 9.9 ft2 (0.92m2) face area, four rows deep. It
shall be constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating
shall significantly improve the speed of condensate drainage from the fins and shall provide superior
water carryover resistance. One stainless steel condensate drain pan shall be provided. It shall have a
face velocity of 434 FPM (2.2 m/s) at 4300 CFM (7306 CMH).
2.1.3.3 R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for
phaseout of HCFC refrigerants.
2.1.3.4 Compressor
Digital Scroll Compressor
The compressor shall be an R-410A scroll-type with variable capacity operation from 20-100%,
commonly known as a Digital Scroll. The compressor solenoid valve shall unload the compressor to
provide variable capacity operation. The compressor shall have a suction gas cooled motor, EPDM
Rubber vibration isolators, internal thermal overloads, automatic reset high pressure switch with
lockout after three failure occurrences, rotalock service valves, low pressure transducer, and
crankcase heater. The compressor shall be removable and serviceable from the front of the unit. The
crankcase heater shall be provided for additional system protection from refrigerant migration during
Off cycles.
Compressor Sound Jacket (Optional)
The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall
consist of a 3/8 inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
Standard Scroll Compressor
The compressor shall be an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration
isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three
failures, rotalock service valves, pump down and low pressure transducer. The crankcase heater shall
be provided for additional system protection from refrigerant migration during Off cycles.

Liebert PDX and Liebert PCW 68


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.3.5 Expansion Valve


Thermostatic Expansion Valve (TXV)
A manual adjustable externally equalized expansion valve thermostatic expansion valve (TXV) shall
control the flow of liquid refrigerant entering the direct expansion coil. The TXV shall maintain
consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the unit's
operating range. The TXV shall prevent liquid refrigerant from returning to the compressor.
Electronic Expansion Valve (Optional for Digital Scroll Compressors)
An electronically controlled expansion valve (EEV) shall be provided.The EEV shall be of stepper-
motor type. The EEV shall maintain consistent superheat of the refrigerant vapor at the outlet of the
evaporator coil over the unit's operating range. The valve shall be controlled by a separate electronic
controller. Superheat shall be determined through the suction pressure-temperature method.
2.1.3.6 Brazed-Plate Condenser
The condenser shall be an insulated, brazed-plate type. The plates are to be stainless steel material.
The primary side shall be piped to a condenser water source, and the secondary side shall be
connected to the refrigeration system. A field-supplied strainer is to be field-installed upstream of the
Liebert PDX, on the condenser water supply line. Water pressure rating of the condenser shall be
600psig DWP.
2.1.3.7 Condenser Motorized Ball Valve
Three-Way Valve
A pre-piped 3-way motorized ball valve shall control the water/glycol flow passing through the
insulated, brazed-plate condenser. The Liebert iCOM control shall manage the valve actuator
movement to maintain the desired condensing temperature for various entering water temperatures.
Two-Way Valve (Optional)
A pre-piped 2-way motorized ball valve shall control the water/glycol flow passing through the
insulated, brazed-plate condenser. The Liebert iCOM control shall manage the valve actuator
movement to maintain the desired condensing temperature for various entering water temperatures.
The maximum differential pressure across the closed valve shall be 200 PSI (1379kPa).
2.1.3.8 System Design Pressure
Standard Pressure
The water/glycol circuit shall be designed for a pressure of 150PSI (1034kPa).
High Pressure (Optional)
The water/glycol circuit shall be designed for a pressure of 400PSI (2758kPa).
2.1.4 Dual Cooling Source System: Chilled Water + Water/ Glycol Cooled Refrigeration
(Models 018, 023, and 029)
2.1.4.1 System Description
Two independent circuits shall be included. The dual-cooling source system shall consist of a
water-cooled system with the addition of a free-cooling chilled water coil or free-cooling chilled glycol
coil (Econ-O-Coil), a modulating control valve and a comparative temperature sensor. The system
shall be able to function either as a modulating chilled water system or as a compressorized system,
or as a combination of the two. The primary cooling mode shall be chilled water. The secondary
refrigeration circuit shall include a liquid line filter drier and an expansion valve.
The water piping shall be filled with a nitrogen holding charge and spun shut. Field relief of the
Schrader valve shall indicate a leak-free system. Switchover between the two cooling modes shall be
performed automatically by the microprocessor control. Four (4) pipe connections shall be included on
water/glycol systems: Econ-O-Coil supply, Econ-O-Coil return, condenser supply and condenser
return.

69 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.4.2 Hydrophilic-Coated Evaporator Coil


Model 018
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be three rows deep. The Econ-O-Coil coil shall have 9.4 ft2 (0.87 m2) face area. The Econ-O-
Coil shall be four rows deep. It shall be constructed of copper tubes and hydrophilic coated aluminum
fins. The hydrophilic coating shall significantly improve the speed of condensate drainage from the
fins and shall provide superior water carryover resistance. One stainless steel condensate drain pan
shall be provided. It shall have a face velocity of 298 FPM (1.5 m/s) at 2800 ft3/m (4757 m3hr).
Model 023
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be three rows deep. The free-cooling cooling coil shall have 9.4 ft2 (0.87 m2) face area. The
free-cooling chilled water coil shall be four rows deep. It shall be constructed of copper tubes and
hydrophilic coated aluminum fins. The hydrophilic coating shall significantly improve the speed of
condensate drainage from the fins and shall provide superior water carryover resistance. One
stainless steel condensate drain pan shall be provided. It shall have a face velocity of 372 FPM
(1.9m/s) at 3500 ft3/m (5947 m3h).
Model 029
The direct-expansion, tilted-slab cooling coil shall have 9.4 ft2 (0.87 m2) face area. The refrigeration
coil shall be four rows deep. The free-cooling cooling coil shall have 9.4 ft2 (0.87 m2) face area. The free-
cooling chilled water coil shall be four rows deep. It shall be constructed of copper tubes and
hydrophilic coated aluminum fins. The hydrophilic coating shall significantly improve the speed of
condensate drainage from the fins and shall provide superior water carryover resistance. One
stainless steel condensate drain pan shall be provided. It shall have a face velocity of 457 FPM
(2.3m/s) at 4300 ft2/m (7306 m3hr).
2.1.4.3 R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for
phaseout of HCFC refrigerants.
2.1.4.4 Compressor
Digital Scroll Compressor
The compressor shall be an R-410A scroll-type with variable capacity operation from 20-100%,
commonly known as a Digital Scroll. The compressor solenoid valve shall unload the compressor to
provide variable capacity operation. The compressor shall have a suction gas cooled motor, EPDM
Rubber vibration isolators, internal thermal overloads, automatic reset high pressure switch with
lockout after three failure occurrences, rotalock service valves, low pressure transducer, and
crankcase heater. The compressor shall be removable and serviceable from the front of the unit. The
crankcase heater shall be provided for additional system protection from refrigerant migration during
Off cycles.
Compressor Sound Jacket (Optional)
The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall
consist of a 3/8-inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
Standard Scroll Compressor
The compressor shall be an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration
isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three
failures, rotalock service valves, pump down and low pressure transducer. The crankcase heater shall
be provided for additional system protection from refrigerant migration during Off cycles.

Liebert PDX and Liebert PCW 70


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.4.5 Expansion Valve


Thermostatic Expansion Valve
A manual adjustable externally equalized expansion valve thermostatic expansion valve (TXV) shall
control the flow of liquid refrigerant entering the direct expansion coil. The TXV shall maintain
consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the unit's
operating range. The TXV shall prevent liquid refrigerant from returning to the compressor.
Electronic Expansion ValveOptional for Digital Scroll Compressors
An electronically controlled expansion valve (EEV) shall be provided.The EEV shall be of stepper-
motor type. The EEV shall maintain consistent superheat of the refrigerant vapor at the outlet of the
evaporator coil over the unit's operating range. The valve shall be controlled by a separate electronic
controller. Superheat shall be determined through the suction pressure-temperature method.
2.1.4.6 Brazed-Plate Condenser
The condenser shall be an insulated, brazed-plate type. The plates are to be stainless steel material.
The primary side shall be piped to a condenser water source, and the secondary side shall be
connected to the refrigeration system. A field-supplied strainer is to be field-installed upstream of the
Liebert PDX, on the condenser water supply line. Water pressure rating of the condenser shall be
600 psig DWP.
2.1.4.7 Condenser Motorized Ball Valve
Three-Way Valve
A pre-piped three-way motorized ball valve shall control the water/glycol flow passing through the
insulated, brazed-plate condenser. The Liebert iCOM shall manage the valve actuator movement to
maintain the desired condensing temperature for various entering water temperatures.
Two-Way Valve (Optional)
A pre-piped 2-way motorized ball valve shall control the water/glycol flow passing through the
insulated, brazed-plate condenser. The Liebert iCOM control shall manage the valve actuator
movement to maintain the desired condensing temperatures for various entering water temperatures.
The maximum differential pressure across the closed valve shall be 200 PSI (1379kPa).
2.1.4.8 Dual-Cool: Free-Cooling Control Valve
Three-Way Motorized Ball Valve
The water circuit shall include a pre-piped three-way motorized ball valve. The Liebert iCOM shall
manage the valve actuator movement to maintain the desired room conditions for various entering
water temperatures. Cooling capacity shall be controlled by bypassing chilled water around the coil.
Two-Way Motorized Ball Valve (OPTIONAL)
The water circuit shall include a pre-piped two-way motorized ball valve. The Liebert iCOM shall
manage the valve actuator movement to maintain the desired room conditions for various entering
water temperatures. The motorized ball valve travel for dehumidification shall be proportional.
2.1.4.9 2.1.4.9Comparator Sensor
The system shall be equipped with a Liebert iCOM microprocessor-controlled comparator sensor that
permits free-cooling operation whenever entering chilled water/glycol temperature is below return-air
temperature. The comparator sensor shall be factory-installed on a free-cooling three-way valve and
field-installed on a free-cooling two-way valve.
2.1.4.10 Design Pressure
Standard Pressure
The water circuit shall be designed for a pressure of 150PSI (1034kPa)
High PressureOptional
The water circuit shall be designed for a pressure of 400PSI (2758kPa).

71 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.5 Glycool: Glycol Economizer + Glycol Refrigeration System (Model 018, 023, and 029)
2.1.5.1 System Description
The refrigeration circuit shall be included, constructed of copper tubes and sharing common
hydrophilic-coated aluminum fins. The refrigeration circuit shall include a liquid line filter drier and
an expansion valve. The water piping shall be threaded closed with a nitrogen holding charge.
Field-relief of the Schrader valve shall indicate a leak-free system.
2.1.5.2 Hydrophilic-Coated Evaporator Coil
Liebert PDX (Models 018, 023, and 029)
Model 018
The GLYCOOL unit shall have two independent cooling circuits, constructed of copper tubes with
hydrophilic-coated aluminum fins. The first cooling circuit shall be a chilled glycol circuit and
designed for closed-loop applications using properly treated glycol solutions. The second cooling
circuit shall be a direct expansion refrigeration circuit. The coil shall be constructed into the
tilted-slab. Each coil shall have 9.4 ft2 (0.87m2) face area. The chilled glycol circuit coil shall be four
rows deep. The direct expansion circuit coil shall be three rows deep. The hydrophilic coating shall
significantly improve the speed of condensate drainage from the fins and shall provide superior water
carryover resistance. The coil shall be provided with a stainless steel drain pan. It shall have a face
velocity of 298 FPM (1.5 m/s) at 2800 CFM (4757 CMH).
Model 023
The GLYCOOL unit shall have two independent cooling circuits, constructed of copper tubes with
hydrophilic-coated aluminum fins. The first cooling circuit shall be a chilled glycol circuit and
designed for closed-loop applications using properly treated glycol solutions. The second cooling
circuit shall be a direct expansion refrigeration circuit. The coil shall be constructed into the
tilted-slab. Each coil shall have 9.4 ft2 (0.87 m2) face area. The chilled glycol circuit coil shall be four
rows deep. The direct expansion circuit coil shall be three rows deep. The hydrophilic coating shall
significantly improve the speed of condensate drainage from the fins and shall provide superior water
carryover resistance. The coil shall be provided with a stainless steel drain pan. It shall have a face
velocity of 372 FPM (1.9 m/s) at 3500 CFM (5947 CMH).
Model 029
The GLYCOOL unit shall have two independent cooling circuits, constructed of copper tubes with
hydrophilic coated aluminum fins. The first cooling circuit shall be a chilled glycol circuit and
designed for closed-loop applications using properly treated glycol solutions. The second cooling
circuit shall be a direct expansion refrigeration circuit. The coil shall be constructed into the tilted-
slab. Each coil shall have 9.4 ft2 (0.87m2) face area. The chilled glycol circuit coil shall be four rows
deep. The direct expansion circuit coil shall be four rows deep. The hydrophilic coating shall
significantly improve the speed of condensate drainage from the fins and shall provide superior water
carryover resistance. The coil shall be provided with a stainless steel drain pan. It shall have a face
velocity of 457 FPM (2.3 m/s) at 4300 CFM (7306 CMH).
2.1.5.3 R-410A Refrigerant
The system shall be designed for use with R-410A refrigerant, which meets the U.S. Clean Air Act for
phaseout of HCFC refrigerants.
2.1.5.4 Compressor
2.1.5.4.1 Digital Scroll Compressor
The compressor shall be an R-410A scroll-type with variable capacity operation from 20-100%,
commonly known as a digital scroll. The compressor solenoid valve shall unload the compressor to
provide variable capacity operation. The compressor shall have a suction gas-cooled motor, EPDM
rubber vibration isolators, internal thermal overloads, automatic reset high pressure switch with
lockout after three failures, rotalock service valves, low pressure transducer and crankcase heater.
The compressor shall be removable and serviceable from the front of the unit. The crankcase heater
shall be provided for additional system protection from refrigerant migration during Off cycles.

Liebert PDX and Liebert PCW 72


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Compressor Sound Jacket (Optional)


The compressor sound jacket shall reduce the level of sound emitted from the compressor. It shall
consist of a 3/8-inch closed cell polymeric 4.5 - 8.5 lb/ft3 density jacket that encloses the compressor.
Standard Scroll Compressor
The compressor shall be an R-410A scroll-type with a suction gas-cooled motor, EPDM vibration
isolators, internal thermal overloads, automatic reset high pressure switch with lockout after three
failures, rotalock service valves, pump down and low pressure transducer. The crankcase heater shall
be provided for additional system protection from refrigerant migration during Off cycles.
2.1.5.5 Expansion Valve
Thermostatic Expansion Valve
A manual adjustable externally equalized expansion valve thermostatic expansion valve (TXV) shall
control the flow of liquid refrigerant entering the direct expansion coil. The TXV shall maintain
consistent superheat of the refrigerant vapor at the outlet of the evaporator coil over the units
operating range. The TXV shall prevent liquid refrigerant from returning to the compressor.
Electronic Expansion Valve (Optional for Digital Scroll Compressors)
An electronically controlled expansion valve (EEV) shall be provided.The EEV shall be of stepper
motor. The EEV shall maintain consistent superheat of the refrigerant vapor at the outlet of the
evaporator coil over the units operating range. The valve shall be controlled by a separate electronic
controller. Superheat shall be determined through the suction pressure-temperature method.
2.1.5.6 Brazed-Plate Heat Condensers
The condenser shall be an insulated, brazed-plate type. The plates are to be stainless steel material.
The primary side shall be piped to a condenser water source, and the secondary side shall be
connected to the refrigeration system. A field-supplied strainer shall be field-installed upstream of
the Liebert PDX, on the water/glycol supply line. Water pressure rating of the condenser shall be
600psig DWP.
2.1.5.7 Three-Way GLYCOOL Valve
The GLYCOOL coil shall include a pre-piped, three-way motorized ball valve. The Liebert iCOM
shall manage the valve actuator movement to maintain the desired room conditions for various
entering water temperatures.
2.1.5.8 Condenser Motorized Ball Valve
Three-Way Valve
A pre-piped three-way motorized ball valve shall control the water/glycol flow passing through the
insulated, brazed-plate condenser. The Liebert iCOM shall manage the valve actuator movement to
maintain the desired condensing temperature for various entering water temperatures.
2.1.5.9 Comparator Sensor
The system shall be equipped with a factory-installed Liebert iCOM microprocessor-controlled
comparator sensor that permits free-cooling operation whenever entering chilled glycol temperature
is below return air temperature.
2.1.5.10 System Design Pressure
Standard Pressure
The GLYCOOL circuit shall be designed for a pressure of 150PSI (1034kPa).
High PressureOptional
The GLYCOOL circuit shall be designed for a pressure of 400PSI (2758kPa).
2.1.6 Chilled Water System (Model 017 and 029)
2.1.6.1 System Description
The water circuit shall be designed to distribute water into the entire coil face area.

73 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.1.6.2 Hydrophilic-Coated Evaporator Coil


Model 017
The chilled-water tilted-slab cooling coil shall be 9.7ft2 (0.90m2) face area, 2 rows deep. It shall be
constructed of copper tubes and hydrophilic coated aluminum fins. The hydrophilic coating shall
significantly improve the speed of condensate drainage from the fins and shall provide superior water
carryover resistance. The coil shall have a face velocity of 361 FPM (1.8m/s) at 3500 CFM (5947m3/h).
One stainless steel condensate drain pan shall be provided. The water circuit shall be filled with a
nitrogen holding charge and spun shut. Field relief of the Schrader valve shall indicate a leak-free
system.
Model 029
The chilled-water, tilted-slab cooling coil shall be 9.7 ft2 (0.9m2) face area, 4 rows deep. It shall be
constructed of copper tubes and hydrophilic-coated aluminum fins. The hydrophilic coating shall
significantly improve the speed of condensate drainage from the fins and shall provide superior water
carryover resistance. The coil shall have a face velocity of 495 FPM (2.5 m/s) at 4800 CFM (8155m3/h).
One stainless steel condensate drain pan shall be provided. The water circuit shall be filled with a
nitrogen holding charge and spun shut. Field relief of the Schrader valve shall indicate a leak-free
system.
2.1.6.3 Control Valve
Three-Way Motorized Ball Valve
A pre-piped three-way motorized ball valve controls the chilled water flow passing through the cooling
coil. The Liebert iCOM control shall manage the valve actuator movement to maintain the desired
room conditions for various entering water temperatures. Cooling capacity shall be regulated by
varying the chilled water flow.
Two-Way Motorized Ball ValveOptional
A two-way pre-piped way motorized ball valve shall control the chilled water flow through the cooling
coil. The Liebert iCOM control shall manage the valve actuator movement to maintain the desired
room conditions for various entering water temperatures. Cooling capacity shall be regulated by
varying the chilled water flow. The maximum differential pressure across the closed valve shall be
200 PSI (1379kPa).
2.1.6.4 System Design Pressure
Standard Pressure
The chilled water circuit shall be designed for a maximum system pressure of 150PSI (1034kPa).
High PressureOptional
The chilled water circuit shall be designed for a maximum system pressure of 400PSI (2758kPa).

2.2 FAN SECTION


2.2.1 Fan and Motor
The unit shall be equipped with one plug fan: integral direct driven fan with backward-curved blades
and electronically commutated DC motors; commonly referred to as EC fan. The fan speed shall be
variable and automatically regulated by the Liebert iCOM through all modes of operation. The fan
shall have a dedicated motor, fault monitoring circuitry and speed controller, which shall provide a
level of redundancy. The impeller shall be made of aluminum and dynamically balanced. The EC fan
shall be located within the unit. The EC fan shall also provide greater energy savings than
forward-curved centrifugal fan and variable speed drives.

Liebert PDX and Liebert PCW 74


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.2.2 Air Flow Configuration


2.2.2.1 Upflow Supply
Upflow Supply with Front Air Return
The supply air shall exit from the top of the cabinet. The return air shall be through the front
factory-installed grilles. The EC fan shall be mounted on the top of the unit. The fan shall be located
to pull air through the filters and cooling coil to ensure even air distribution and maximum coil
performance.
Upflow Supply with Rear Air Return
The supply air shall exit from the top of the cabinet. The return air shall be through the rear of the
factory-supplied, 24" rear return, skirted floor stand assembly with air filters. The EC fan shall be
mounted on the top of the unit. The fan shall be located to pull air through the filters and cooling coil
to ensure even air distribution and maximum coil performance.
2.2.2.2 Downflow Configurations
Downflow Supply with Front Air Discharge
The supply air shall exit from the front of the cabinet opening. The EC fan shall be mounted on the
bottom of the unit. The fan shall be located to draw air through the filters and cooling coil to ensure
even air distribution and maximum coil performance.
Downflow Supply with Front and Right Side Air Discharge
The supply air shall exit from the front and right side cabinet openings. The EC fan shall be mounted
on the bottom of the unit. The fan shall be located to draw air through the filters and cooling coil to
ensure even air distribution and maximum coil performance.
Downflow Supply with Front Air and Left Side Air Discharge
The supply air shall exit from the front and left side cabinet openings. The EC fan shall be mounted
on the bottom of the unit. The fan shall be located to draw air through the filters and cooling coil to
ensure even air distribution and maximum coil performance.
Downflow Supply with Front, Right and Left Side Air Discharge
The supply air shall exit from the front, right and left side cabinet openings. The EC fan shall be
mounted on the bottom of the unit. The fan shall be located to draw air through the filters and cooling
coil to ensure even air distribution and maximum coil performance.
Downflow Supply with Discharge into Raised Floor
The supply air shall exit from the bottom of the unit directly into the raised floor. The EC fan shall be
mounted on the bottom of the unit. The fan shall be located to draw air through the filters and cooling
coil to ensure even air distribution and maximum coil performance.

2.3 CABINET CONSTRUCTION AND ACCESSIBILITY


2.3.1 Cabinet Construction
The exterior panels shall be 20 gauge steel and powder-coated with black color paint to protect
against corrosion. The exterior panels shall be insulated with 1/2" to 1" (12.7 to 25.4mm), 1-1/2 lb.
(0.68 kg) insulation. Front and side panels shall have captive, quarter-turn fasteners. The cabinet
shall be designed so that all components are serviceable and removable using the front and right sides
of the unit.
2.3.2 Double-Skin Panels (Optional)
The exterior panels shall be internally lined with 20 gauge galvanized steel, sandwiching the
insulation between the panels for easy cleaning.

75 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.4 LOCKING DISCONNECT SWITCH


A locking-type fused disconnect switch shall be mounted in the electrical panel and shall be capable of
disrupting the flow of power to the unit. The locking type shall consist of a main unit switch
operational from outside the unit. The electric panel compartment shall be accessible only with the
switch in the Off position. The locking disconnect shall be lockable in support of lockout/tagout safety
programs.

2.5 SHORT-CIRCUIT CURRENT RATING (SCCR)


The electrical panel shall provide at least 65,000A SCCR.

2.6 FILTRATION
2.6.1 MERV 8 Filters
The filter shall be an integral part of the system and located within the cabinet. The filter shall be
deep-pleated, 2 in. (51mm) thick with a MERV 8 rating efficiency based on ASHRAE 52.2-2007. A
filter clog switch shall be included. Mesh type, cleanable filters shall be unacceptable.
2.6.2 MERV 11 Filters
The filter shall be an integral part of the system, located within the cabinet. The filter shall be deep-
pleated, 2 in (51mm) thick with a MERV 11 rating efficiency based on ASHRAE 52.2-2007. A filter
clog switch shall be included. Mesh type, cleanable filters shall be unacceptable.
2.6.3 Extra Filter SetOptional
_______ extra set(s) of filters shall be provided per system.

2.7 ELECTRIC REHEAT (OPTIONAL)


Model 017 - Chilled Water
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 45.1 kBTUH (13.2 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 018 - Air-Cooled or Water/Glycol-Cooled
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 46.4 kBTUH (13.6 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 023 - Air-Cooled or Water/Glycol-Cooled
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 47.5 kBTUH (13.9 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 029 - Air-Cooled or Water/Glycol-Cooled
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat coils shall be 51.6 kBTUH (15.1 kW) including motor heat. The electric reheat
shall be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 018 -Glycool, Dual-Cool Air-Cooled, Dual-Cool Water/Glycol
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 49.2 kBTUH (14.4 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.

Liebert PDX and Liebert PCW 76


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Model 023 -Glycool, Dual-Cool Air-Cooled, Dual-Cool Water/Glycol


The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 50.9 kBTUH (14.9 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 029 -Glycool, Dual-Cool Air-Cooled, Dual-Cool Water/Glycol
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 51.6 kBTUH (15.1 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.
Model 029 - Chilled Water
The reheat is a low-watt density 304/304 stainless steel finned-tubular electric reheat. The reheat
section shall include UL/CSA recognized safety switches to protect the system from overheating. The
capacity of the reheat shall be 50.9 kBTUH (14.9 kW) including motor heat. The electric reheat shall
be controlled in two stages. The reheat elements shall be accessible from the right of the cabinet.

2.8 HOT WATER REHEATOPTIONAL ON CHILLED WATER UNITS ONLY


The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of 41.3 kBTUH
(12.1 kW) including motor heat when supplied with 180F (82.2C) entering water temperature at
4 GPM (0.25 l/s) flow rate with a pressure drop of 12.8 PSI (38.3 kPa). The control system shall be
factory pre-piped with a two-way motorized control valve. A cleanable Y-strainer should be
field-supplied and installed on the hot water supply line.

2.9 INFRARED HUMIDIFIER


The humidifier shall be of the infrared type, consisting of high intensity quartz lamps mounted above
and out of the water supply. The evaporator pan shall be stainless steel and arranged to be
serviceable without disconnecting water supply lines, drain lines or electrical connections. The
complete humidifier section shall be pre-piped ready for final connection. The infrared humidification
system shall use bypass air to prevent overhumidification of the controlled space. The auto-flush
system shall automatically flush deposits from the humidifier pan. The system shall be field
adjustable to change the cycle time to suit local water conditions. The humidifier shall have a capacity
of 7.7 lb/h (3.5 kg/h).

2.10 STEAM GENERATING CANISTER HUMIDIFIEROPTIONAL


A canister-type steam generating humidifier shall be factory-installed in the cooling unit and
operated by the Liebert iCOM. It shall be complete with disposable cylinder, all supply and drain
valves, steam distributor and electronic controls. The need to change the canister shall be indicated
on the Liebert iCOM display. The humidifier is designed to operate with water conductivity from
330-670 (60Hz) microS/cm. System shall automatically fill and drain as well as maintain the required
water level based on conductivity. An air-gap within the humidifier assembly shall prevent back flow
of the humidifier supply water. The humidifier shall have a capacity of 10.8 lb/h (4.9 kg/h).

2.11 CONDENSATE PUMP


The dual-float condensate pump shall have a minimum capacity of 5 GPM (18.9 l/min) at 40 ft.
(12.2m) head. Pump shall be complete with integral primary and secondary float switches, pump,
motor assembly and reservoir. The secondary float shall send a signal to the local alarm and shut
down the unit upon high water condition. The condensate pump shall be factory-installed on upflow
units and field-installed on downflow units.

77 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.12 LIEBERT ICOM MICROPROCESSOR CONTROL WITH LARGE GRAPHIC DISPLAY


The Liebert iCOM shall be factory-set to allow precise monitoring and control of the IT equipment it
is placed near. This control shall include predictive methods to control air flow and cooling capacity
based on supply and remote sensors. Proportional and Tunable PID shall also be user-selectable
options. Internal unit component control shall include the following:
Compressor Short Cycle ControlShall prevent compressor short-cycling and needless
compressor wear.
System Auto RestartThe auto restart feature shall automatically restart the system after a
power failure. Time delay shall be programmable.
Sequential Load ActivationOn initial startup or restart after power failure, each operational
load shall be sequenced with a minimum of one second delay to minimize total inrush current.
Predictive Humidity ControlShall calculate the moisture content in the room and prevent
unnecessary humidification and dehumidification cycles by responding to changes in dew point
temperature.
The Liebert iCOM shall be compatible with all Liebert remote monitoring and control devices.
Options shall be available for BMS interface via Modbus, HTTP, BACnet and SNMP.
The Liebert iCOM shall be microprocessor-based with a 320x240 dot matrix graphic front monitor
display and control keys for user inputs mounted in an ergonomic, aesthetic housing. The display and
housing shall be viewable while the front panel is open or closed. The controls shall be menu driven.
The display shall be organized into three main sections: User Menus, Service Menus and Advanced
Menus with a secure login for each section. The system shall display user menus for active alarms,
event log, graphic data, unit view/status overview (including the monitoring of room conditions,
operational status in percentage of each function, date and time), total run hours, various sensors,
display setup and service contacts. A password shall be required to make system changes within the
service menus. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep mode,
alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network setup,
auxiliary boards and diagnostics/service mode. A password shall be required to access the advanced
menus, which include the factory settings and password menus.
The User Menus Shall Be
Active Alarms: Unit memory shall hold the 200 most recent alarms with time and date stamp
for each alarm.
Event Log: Unit memory shall hold the 400 most recent events with ID number, time and date
stamp for each event.
Graphic Data View: Two selectable graphic records shall be available from the following: return
air temperature, return air humidity, dew point, supply air temperature.
Unit View - Status Overview: Simple or Graphical Unit View summary displays shall include
temperature and humidity values, active functions (and percent of operation) and any alarms of
the host unit.
Total Run Hours: Menu shall display accumulative component operating hours for major
components including compressors, Econ-O-Coil (FC), fan motor, humidifier and reheat.
Various Sensors: Menu shall allow setup and display of optional custom sensors.
Display Language: Customer shall be able to select the desired language at the time of the
order from the following choices: English, French, Italian and Spanish.
Service Contacts: Menu shall allow display of local service contact name and phone number.
System View - Status Overview: System view shall display a summary of operation for the
total number of operating units within a Unit-to-Unit (U2U) configuration.
Spare Parts List: Menu shall include a list of critical spare parts, their quantity and part
numbers.
Unit Diary: Menu shall include a free field area within the unit memory where unit history may
be stored for reference.

Liebert PDX and Liebert PCW 78


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

The Service Menus Shall Be


Setpoints: Menu shall allow setpoints within the following ranges:
Temperature Setpoint: 41-104F (5-40C)*
Temperature Proportional Band: +1-50F (-17 to 10C)
Fan Temperature Setpoint: 41-104F (5-40C)*
Humidity Setpoint: 20-80% RH*
Humidity Sensitivity: 1-30% RH
High Temperature Alarm: 35-90F (2-32C)
Low Temperature Alarm: 35-90F (2-32C)
High Humidity Alarm: 15-85% RH
Low Humidity Alarm: 15-85% RH
* The microprocessor may be set within these ranges; however, the unit may not be able to
control to extreme combinations of temperature and humidity.
Standby Settings/Lead-Lag: Menu shall allow planned rotation or emergency rotation of
operating and standby units.
Alarm Setup: Menu shall allow customer settings for alarm notification (audible/local/remote).
The following alarms shall be available:
High Temperature
Low Temperature
High Humidity
Low Humidity
Compressor OverloadOptional
Main Fan OverloadOptional
Humidifier Problem
High Head Pressure
Change Filter
Fan Failure
Low Suction Pressure
Unit Off
Audible Alarm: The audible alarm shall annunciate any alarm that is enabled by the operator.
Common Alarm: A programmable common alarm shall be provided to interface user-selected
alarms with a remote alarm device.
Remote Monitoring: All alarms shall be communicated to the Liebert monitoring system with
the following information: date and time of occurrence, unit number and present temperature and
humidity.
Sensor Calibration: Menu shall allow unit sensors to be calibrated with external sensors.
Maintenance/Wellness Settings: Menu shall allow reporting of potential component problems
before they occur.
Options Setup: Menu shall provide operation settings for the installed components.
System/Network Setup: Menu shall allow Unit-to-Unit (U2U) communication and setup for
Teamwork modes of operation (up to 32 units).
Teamwork Modes of Operation: Saves energy by preventing operation of units in opposite
modes multiple units.
Diagnostics/Service Mode: The Liebert iCOM shall be provided with self-diagnostics to aid in
troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass.
Control inputs shall be indicated as On or Off at the front display. Control outputs shall be able to
be turned On or Off from the front display without using jumpers or a service terminal. An LED
on a circuit board will indicate each control output.
The Advanced Menus Shall Be
Factory Settings: Configuration settings shall be factory-set based on the pre-defined
component operation.
Change Passwords: Menu shall allow new passwords to be set or changed.

79 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.13 LIEBERT ICOM CONTROL METHODS AND OPTIONS


Controlling Sensor Options: Liebert iCOM shall be flexible in the sense that it allows for
controlling the capacity and fan from multiple different sensor selections. The sensor selections shall
be:
Cooling Capacity:
Supply
Remote
Return
Fan Speed:
Supply
Remote
Return
Manual (for diagnostic or to receive a signal from the BMS through the IS-UNITY-DP card)
Teamwork Modes of Operation: Liebert iCOM teamwork shall save energy by preventing
operation of multiple units in opposing modes. The thee modes of teamwork operation are:
Teamwork Mode 1: This mode allows the control to optimize a group of cooling units equipped
with Liebert iCOMs using the U2U. The capacity and fan operations is coupled together in this
mode.
Teamwork Mode 2: This mode allows the control to optimize a group of cooling units equipped
with Liebert iCOMs using the U2U. The capacity and fan operations is decoupled in this mode,
meaning the fan and cooling ramp and respond to the thermal load based on its controlling
sensors.
Optimized Aisle - Teamwork Mode 3: This mode allows the control to optimize a group of
connected cooling units equipped with Liebert iCOMs using the U2U. The capacity and fan
operations is decoupled in this mode, meaning the fan and cooling ramp and respond to the
thermal load based on its controlling sensors. When using Optimized Aisle, the fans can be
controlled by using static pressure (DP or static) with a secondary remote temperature sensor as
an override to ensure the inlet rack temperature is being met.
Temperature Compensation: Liebert iCOM allows the ability to compensate the supply and return
set points to maintain cooling OR return temperatures to meet cooling needs or Service Level
Agreement (SLA) guidelines.
Dew Point Control: Liebert iCOM shall be able to control the humidity based on dew point to
ensure accurate humidity control. This method will eliminate the need to dehumidify or humidify
based on the air temperature when looking at moisture content.
Virtual Back-Draft Damper: Liebert iCOM allows for the use of a virtual back-draft damper -
eliminating the need for a mechanical damper. This allows the EC fan to spin at a low speed (15%) to
act as a damper.
Cascade: Liebert iCOM cascade option shall allow the units to turn On and Off based on heat load
when in Teamwork Mode 1. When utilizing Optimized Aisle, Teamwork Mode 3, the cascading shall
become more dynamic as the units coordinate the fan speed to save energy and to meet the cooling
demands. For instance, with a group of six cooling units equipped with Liebert iCOMs and only 50%
of the heat load, the Liebert iCOM shall operate only four units at 80% fan speed and leave the other
two units in standby/cascade. As the heat load increases, the Liebert iCOM shall automatically
respond to the new load and bring on the fifth unit. As the heat load shifts up or down, the control
shall meet the needs by cascading units On or putting them into standby.
Virtual Master: The Liebert iCOM control shall allow for a virtual master that coordinates
operation. If for any reason the virtual master becomes disconnected, the control shall shift
responsibility to the next unit in the group.
Remote 2T Sensor Sharing: Each Liebert PDX/PCW unit can connect up to ten 2T sensors. The
2T sensors can be used as a controlling sensor or reference sensor. As part of the U2U network and
teamwork, those sensors can be shared and used to control the units and provide greater flexibility,
visibility and control using that to respond to changes in the data center. The 2T sensors can be set to
a minimum or maximum or average temperature control.

Liebert PDX and Liebert PCW 80


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Quick Start: Each Liebert PDX/PCW unit shall be equipped with a quick-start feature that allows
the unit to quickly recover from a loss of power.
Liebert MC Condenser: Liebert PDX (air-cooled) can be matched to a premium Liebert MC
condenser to provide an intelligent communication link. This shall enable enhanced monitoring and
alarming, diagnostics, low-noise mode and fan reversal for cleaning mode.

2.14 SUPPLY AIR SENSOR


2.14.1 DownflowRaised Floor
The supply air temperature sensor shall provide real-time, direct feedback to the cooling unit to
provide a consistent supply air temperature by adjusting the compressor capacity or the chilled water
valve accordingly to maintain its setpoints.
2.14.2 DownflowFront Discharge
The supply air temperature sensor shall provide real-time monitoring of the supply air temperature.
2.14.3 Upflow
The supply air temperature sensor shall provide real-time monitoring of the supply air temperature.

2.15 REMOTE TEMPERATURE AND HUMIDITY SENSORSOPTIONAL


The unit shall be supplied with remote temperature and humidity sensors. The sensors shall be
connected to the unit by a (30 ft. [9m]), (60 ft. [18m]), (90 ft. [27m]), (120 ft. [36m]), (150 ft. [45m])
shielded cable.

2.16 RACK TEMPERATURE SENSORSOPTIONAL


The Liebert PDX/PCW shall be provided with ____ 2T rack temperature sensors, which consist of a
vented case with two temperature probes. The sensors shall provide real-time, direct feedback to the
cooling unit to optimize the amount of cooling and airflow provided. The sensor data shall be available
to remote BMS and monitoring systems. The sensor network shall consists of one CAN wire leaving
the cooling unit and connecting to a 2T sensor. Each remaining 2T sensor is connected to the previous
sensor.
2.16.1 Additional CAN Cables for Rack SensorsOptional
________ additional _______ feet (m) long CAN cables shall be provided.

2.17 HIGH TEMPERATURE SENSOROPTIONAL


The high temperature sensor shall immediately shut down the system when high temperatures are
detected. The high temperature stat shall be mounted in the electrical panel with the sensing element
in the return air.

2.18 SMOKE SENSOROPTIONAL


The smoke sensor shall sample the return air, shut down the unit upon activation and send visual
and audible alarms. Dry contacts shall be available for a remote customer alarm. This smoke sensor
is not intended to function as or replace any room smoke detection system that may be required by
local or national codes.

2.19 REMOTE SHUTDOWN TERMINAL


The remote shutdown terminal shall provide the customer with a location to remotely shut down the
unit, complying with the National Fire Code.

2.20 COMMON ALARM CONTACT


The common alarm contacts shall provide the customer with a set of normally open contacts for
remote indication of unit alarms. Four alarm contacts shall be provided for units without a
condensate pump. Three alarm contacts shall be provided for units with a condensate pump.

81 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.21 LOW-VOLTAGE TERMINAL PACKAGEOPTIONAL


One extra N/O common alarm contacts shall be provided. Two extra remote shutdown terminals shall
be provided. One pair of N/O contacts shall be factory-installed and wired to indicate Main Fan
Overload. One pair of N/O contacts shall be provided for Liebert Liqui-tect signal shut down. (Liebert
Liqui-tect not included.)

2.22 REHEAT / HUMIDIFIER LOCKOUTOPTIONAL


The reheat and humidifier lockout shall include the necessary relays to disable the reheat and
humidifier from an external 24V signal while on emergency power.

2.23 REMOTE HUMIDIFIER CONTACTOPTIONAL


A pair of N/O contacts shall be factory-installed and wired to indicate Main Fan Overload.

2.24 COMPRESSOR OVERLOADOPTIONAL


A pair of N/O contacts shall be factory-installed and wired to each compressor to indicate Compressor
Overload

2.25 LIEBERT INTELLISLOT UNITY-DP CARDOPTIONAL


The Liebert IntelliSlot Unity Card (IS-UNITY-DP) shall provide ground fault isolated RS-485
Modbus, BACnet IP and Modbus IP network connectivity to Building Management Systems for unit
monitoring and management. Also, it shall provide ground fault isolated 10/100 baseT Ethernet
connectivity for unit monitoring and management. The supported management interfaces include:
SNMP for Network Management Systems, HTTP for Web page viewing, SMTP for e-mail and SMS
for mobile messaging. The card shall support IP and 485 protocols simultaneous.

2.26 LIEBERT INTELLISLOT SITELINK-E CARDOPTIONAL


The Liebert IntelliSlot SiteLink-E Card shall provide ground fault isolated connection to a Liebert
SiteLink-E for monitoring and management. Liebert SiteLink-E supports Emerson interfaces as a
BACnet router that provides the communications link between Liebert units and other protocols and
modules. The Liebert SiteLink-E is designed to communicate with Liebert cooling units, UPSs and
power distribution units and route the information over a BACnet, Modbus or LONWorks network
to a Building Automation System (BAS) workstation. Required for communication with Liebert
SiteScan Web 4.0 or newer.

2.27 LIEBERT NFORMOPTIONAL ADVANCED MONITORING


The critical infrastructure management software shall centrally monitor and manage distributed
equipment using the customers existing network infrastructure. The system shall provide the critical
infrastructure management and monitoring for air conditioning systems, uninterruptible power
supply systems, power distributions units, static transfer switches, direct current power systems,
Alber battery monitoring, rack enclosure monitoring, leak detection systems and other critical
infrastructure systems as specified. The system shall have an architecture that allows up to 10,000
managed devices, including Liebert and third-party devices, in a single-server installation.

Liebert PDX and Liebert PCW 82


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.27.1 System Requirements


All material and equipment used shall be standard components, regularly manufactured and
available and not custom-designed especially for this project. All systems and components shall have
previously been thoroughly tested and proven in actual use prior to installation on this project.
The manufacturer shall furnish or supply a site-specific critical infrastructure management software
system based on customer requirements. The system must be a software-only solution; no
substitutions shall be accepted.
The system architecture shall consist of network interface cards that will be installed in all critical
infrastructures that, at a minimum, support HTTP and SNMP simultaneously.
The system shall receive SNMP traps from managed equipment and display the alarm notification in
a graphical user interface.
The system shall be based on SNMP open protocols and integrate seamlessly with Emerson Network
Power, Aperture software suite and Network Management Systems.
Open protocol support shall include:
HTTP(s)
TCP/IP/v4, TCP/IP/v6
SNMP v.1, SNMP v.2
The system shall have the capability of being remotely monitored and managed 24 hours a day, 7
days a week by the manufacturer.
The system shall have the ability to be deployed worldwide.
The system shall operate as a client-to-server application.
The Web interface of each managed device shall integrate directly into the system.
The system shall support Enterprise level databases including Microsoft SQL.
The system shall support exporting of all recorded parametric trend data.
The system shall operate on a server defined by the customer. Specific server brand or function is not
permissible.
The system shall support virtual server environments by default.
The system shall include one year of Software Assurance at no additional cost.
2.27.2 Approved Products
The critical infrastructure monitoring system shall be Liebert Nform as manufactured by Emerson
Network Power, Liebert Corporation. No substitutions shall be accepted.
2.27.3 Scope Of Work
2.27.3.1 Owner-Supplied Items
The critical infrastructure monitoring system shall be Liebert Nform as manufactured by Emerson
Network Power, Liebert Corporation. No substitutions shall be accepted.

83 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.27.3.2 Scope of Work


Owner-Supplied Items
The owner shall furnish the following system components:
Network (LAN) hardware and software required to provide an Ethernet backbone for transport of
IP data packets from network interface cards installed in all equipment to the critical
infrastructure server and to the Liebert Nform workstations. These components may include
hubs, routers, cabling, network operating systems, firewalls, IP addresses, Virtual Private
Network (VPN) and other components as required. The owner shall supply network drops for the
critical infrastructure server, workstation clients and all network-interfaced equipment.
Dedicated critical infrastructure server meeting the following minimum requirements:
Microsoft Windows 7, XP, 2003, Windows Vista or Windows Server 2008 operating system
Pentium 3.0GHz single processor or better (1.8GHz dual processor or better recommended)
4 GB of RAM or more
40 GB hard drive (SCSI recommended)
10/100 BaseT network port or better
Monitor / keyboard and mouse port as required for setup
Standard USB ports
CD or DVD-ROM drive for software installation (CD/DVD-RW suggested for installation and
backup)
Critical infrastructure server may be virtual environment compatible
Critical Infrastructure Workstation PCs meeting the following minimum requirements:
System should meet the minimum requirements for Microsoft Windows 7, XP, 2003, Windows
Vista or Windows Server 2008 operating systems.
Microsoft Internet Explorer v6.0 or better
1 GB RAM
10 GB hard disk
The owner shall supply the following information to facilitate system implementation:
IP addresses and subnet masks and other information as required to configure network devices
Provide a person as the nominated system owner for administrator purposes
Secure location for hardware and server
Critical Infrastructure System Vendor Responsibilities
The vendor shall provide hardware and software as listed.
Critical infrastructure software and licenses for server and workstation installations.
Provide Liebert Nform Software Assurance for the first year at no additional cost.
Provide 7 x 24 system application and service support through a toll-free telephone number.
Provide warranty (parts and labor) per the manufacturer's warranty statement.
Vendor shall be ISO 9001 listed for design and manufacture of environmental control systems for
critical monitoring and control applications.

Liebert PDX and Liebert PCW 84


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.28 LIEBERT vNSAOPTIONAL


The Liebert vNSA network switch is designed for connecting multiple Ethernet-ready devices. The
unit shall have one or two 8-port switches, providing a total of eight or 16 Ethernet ports. The Liebert
vNSA shall have 100-240VAC single phase for proper operation. A universal power supply (12V, 1.5A)
shall be installed inside a steel enclosure secured with a key lock, with a hard-wired connection for
120V or 230V operation. A Liebert iCOM display shall be mounted on the front. Liebert iCOM shall
permit interconnecting Liebert PDX/PCW units to communicate through the use two CAT5 or better
network patch cables with RJ-45 connectors to connect devices to available ports.
The number of ports available for Ethernet-ready devices varies by the number of 8-port switches
included. The Liebert iCOM display use one port for connection to the Liebert iCOM display. The
16-port model shall use two ports to interconnect the switches.
# of Ports Needed to Connect
Total To Liebert Upper and # Ports Maximum # Liebert PDX/PCW
Model # Ports iCOM Display Lower Switches Available that may be connected
vNSA8-iCOM 8 1 N/A 7 3
vNSA16-iCOM 16 1 2 13 6

2.29 LIEBERT LIQUI-TECT 410 POINT LEAK DETECTION SENSOR FOR REMOTE
MOUNTINGOPTIONAL
A total of ________ (quantity) solid-state water sensor(s) with no moving parts and hermetically
sealed to keep out dust and dirt shall be provided. The Liebert Liqui-tect 410 (LT410) shall provide a
single-point detection of leaks. The point detection sensor shall have two gold-plated sensing probes to
prevent corrosion resistance and to provide accurate readings. The LT410 shall constantly monitor
points for leaks, internal faults and power failures and warn of any abnormal conditions. Mounting
brackets shall allow for sensor height adjustment and leveling. The LT410 shall provide two
independent outputs to signal both a local alarm panel and a remote building management system or
external equipment. The LT410 shall be rated for 24VAC, 50/60Hz and 0.10 amp.

2.30 LIEBERT LIQUI-TECT 460 ZONE LEAK DETECTION MODULE WITH CABLE KIT
FOR REMOTE MOUNTINGOPTIONAL
A total of ________ (quantity) zone water sensor cables with no moving parts and hermetically sealed
to keep out dust and dirt shall be provided. The Liebert Liqui-tect 460 (LT460) shall provide a zone
detection of leaks. The LT460 shall constantly monitor points for leaks, internal faults and power
failures and warn of any abnormal conditions. LEDs shall provide status indication and also ensure
the cable is properly installed and operational under raised floors. The LT460 shall provide two
independent outputs provide a signal to a local alarm panel, Liebert environmental unit, remote
building management system or external equipment.
Liebert Liqui-tect 460 Module
The LT460 shall consist of a metal enclosure with a hinged top door providing access to the internal
circuit board for wiring termination and configuration of DIP switches. The LT460 shall monitor up to
100 feet of connected LT500Y leak detection cable.
LT500Y Leak Detection Cable
The cable material and construction shall allow the cable to lie flat when used with hold-down clips.
The LT500Y shall be plenum-rated and UL-listed for safe operation. Cables shall be available in
lengths of 20, 25, 30, 35 and 45 feet.
The LT460 shall be rated for 24VAC, 50/60Hz and 0.12A.

85 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.31 FLOOR STANDOPTIONAL


2.31.1 Supply Air Floor StandOptional
Downflow Raised Floor (Upflow Not Rear Return)
The floor stand shall be constructed of galvanized steel. The floor stand shall have adjustable legs
with vibration isolation pads. The floor stand shall be: (6in. [15cm]). (9 in. [23cm]), (12 in. [30cm]), (15
in. [38cm]), (18 in. [46cm]), (21 in. [53cm]), (24 in. [61cm]) high.
2.31.2 RETURN AIR FLOOR STAND AssemblyOptional
The upflow unit with rear return air configuration shall be supplied with a skirted-floor stand
assembly. The floor stand assembly shall be constructed of galvanized steel with powder-coated
panels and supplied with air filter. The floor stand assembly shall be 24-1/8 in. (613mm) high and
have adjustable legs with vibration isolation pads. It shall provide a rear return duct flange and
removable panel for filter access.

2.32 PLENUMOPTIONAL
2.32.1 Plenum Construction
The exterior panels shall be 20 gauge steel and powder-coated with black color paint to protect
against corrosion. The exterior panels are insulated with 1/2" to 1" (25.4mm), 1-1/2 lb. (0.68 kg)
insulation. Front and side panels shall have captive, quarter-turn fasteners.
2.32.1.1 Double-Skin Panels (Optional)
The exterior panels shall be internally lined with 20 gauge galvanized steel, sandwiching the
insulation between the panels for easy cleaning.
2.32.2 Air Flow Configuration
2.32.2.1 Ducted
The unit shall be supplied with a ducted air discharge plenum. The plenum shall be 18 in. (457mm),
24 in. (609mm), 30 in. (762mm), 36 in. (914mm), 42 in. (1066mm) or 48 in. (1219) with top duct
connection.
2.32.2.2 Two-Way Grille
The unit shall be supplied with a two-way air discharge plenum. The plenum shall be 18 in. (457mm)
high.
2.32.2.3 Three-Way Grille
The unit shall be supplied with a three-way air discharge plenum. The plenum shall be 18 in.
(457mm) high.
2.32.2.4 Four-Way Grille
The unit shall be supplied with a four-way air discharge plenum. The plenum shall be 18 in. (457mm)
high.

2.33 HEAT REJECTION


2.33.1 Liebert MC Condenser Summary
These specifications describe requirements for a Liebert air-cooled condenser for a Liebert Thermal
Management system. The condenser shall be designed to reject waste heat to outdoor air and to
control refrigerant head pressure as indoor equipment loading and outdoor ambient conditions
change.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60Hz units shall be CSA-certified to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and shall be marked with
the CSA c-us logo.

Liebert PDX and Liebert PCW 86


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.33.1.1 Liebert MC Design Requirements


The air-cooled condenser shall be a factory-assembled unit, complete with integral electrical panel,
designed for outdoor installation. The condenser shall be a draw-through design.
2.33.1.2 Liebert MC Standard Features
Condenser shall consist of microchannel condenser coil(s), propeller fan(s) direct-driven by individual
fan motor(s), electrical controls, housing and mounting legs. The Liebert air-cooled condenser shall
provide positive refrigerant head pressure control to the indoor cooling unit by adjusting heat
rejection capacity. Microchannel coils shall provide superior heat transfer, reduce air-side pressure
drop, increase energy efficiency and significantly reduce the system refrigerant volume required. EC
fans and fan operating techniques shall reduced sound levels. Various methods shall be available to
match indoor unit type, maximum outdoor design ambient and maximum sound requirements.
2.33.1.3 Liebert MC Condenser Coil
Liebert microchannel coils shall be constructed of aluminum microchannel tubes, fins and manifolds.
Tubes shall be flat and contain multiple, parallel flow microchannels and span between aluminum
headers. Full-depth louvered aluminum fins shall fill spaces between the tubes. Tubes, fins and
aluminum headers shall be oven-brazed to form a complete refrigerant-to-air heat exchanger coil.
Copper stub pipes shall be electric resistance-welded to aluminum coils and joints protected with
polyolefin to seal joints from corrosive environmental elements. Coil assemblies shall be factory
leak-tested at a minimum of 300 psig (2068kPag). Hot gas and liquid lines shall be copper and shall
be brazed using nitrogen gas flow to the stub pipes with spun-closed ends for customer piping
connections. Complete coil/piping assembly shall be then filled and sealed with an inert gas holding
charge for shipment.
Aluminum Microchannel Coil with E-CoatOptional
Aluminum microchannel coil with E-coat shall provide a flexible epoxy coating to all coil surface areas
without material bridging between fins. E-coat shall increase coil corrosion protection and shall
reduce heat rejection capacity degradation to less than 10% after a severe 2000 hour 5% neutral salt
spray test (ref. ASTM B117). The coating process shall ensure complete coil encapsulation, and the
color shall be black.
2.33.1.4 Liebert MC Fan Motor/Blade Assembly
The fan motor/blade assembly shall have an external rotor motor, fan blades and fan/finger guard.
Fan blades shall be constructed of cast aluminum or glass-reinforced polymeric material. Fan guards
shall be heavy gauge, close-meshed steel wire, coated with a black corrosion resistant finish. Fan
terminal blocks shall be in an IP54 enclosure on the top of the fan motor. Fan assemblies shall be
factory-balanced, tested before shipment and mounted securely to the condenser structure.
Liebert MC Condenser EC Fan Motor
The EC fan motors shall be electronically commutated for variable speed operation and shall have
ball bearings. The EC fans shall provide internal overload protection through built-in electronics.
Each EC fan motor shall have a built-in controller and communication module, linked via RS485
communication wire to each fan and the Premium Control Board, allowing each fan to receive and
respond to precise fan speed inputs from the Premium Control Board.
Liebert MC Condenser AC Fan MotorOptional
The AC fan/motor assembly shall be an integral assembly of a three-phase motor, quiet fan blade
assembly and finger/hail guard. Fan blades shall be constructed of stamped aluminum or steel
extrusion coated with polypropylene plastic. Fan guards shall be heavy gauge, close-meshed, steel
wire, coated with a black corrosion resistant finish. Fan terminal blocks shall be on the top of the fan
guard with IP54 protection class. Fans shall be factory-balanced and -tested before shipment.
The AC fan motors shall be for variable speed operation and shall have ball bearings. The AC fans
shall provide internal overload protection through a built-in thermal switch. The AC fan control board
shall provide electronic voltage regulation to the AC fans.

87 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.33.1.5 Electrical Controls


Electrical controls and service connection terminals shall be provided and factory-wired inside the
attached control panel section. Only high-voltage supply wiring and low voltage indoor unit
communication/interlock wiring are required at condenser installation.
EC Fan Speed and Premium Control
The EC fan/Premium Control System shall include an electronic control board, EC fan motor(s) with
internal overload protection, refrigerant and ambient temperature thermistors and refrigerant
pressure transducers. The Premium Control Board shall communicate directly with the indoor units
Liebert iCOM control via field-supplied CANbus communication wires and via field-supplied
low-voltage interlock wires. The control board shall use sensor and communication inputs to maintain
refrigerant pressure by controlling each EC fan on the same refrigerant circuit to the same speed. The
Premium control board shall be rated to a temperature of -30F to 125F. The premium control shall
be factory set for (fan speed) (fan speed with Liebert Lee-Temp) control.
AC Fan Speed and Basic ControlOptional
The AC fan/Basic Control system shall include an electronic control board, AC fan motor(s) with
internal overload protection, refrigerant and ambient temperature thermistors and refrigerant
pressure transducers. The control board shall receive an indoor unit run signal via field-supplied
low-voltage interlock wires to the compressor side switch, field-supplied low-voltage interlock wires.
The control board shall use sensor and communication inputs to maintain refrigerant pressure by
controlling each AC fan on the same refrigerant circuit to the same speed. The Basic Control board
shall be rated to a temperature of -30F to 125F. The basic control shall be factory set for (fan speed)
(fan speed with Liebert Lee-Temp) control.
Locking Disconnect Switch
A Locking-Type disconnect switch shall be factory-mounted and wired to the electrical panel and be
capable of disrupting the flow of power to the unit and controlled via an externally mounted locking
and lockable door handle. The locking disconnect shall be lockable in support of lockout/tagout safety
programs.
Short Circuit Current Rating
The electrical panel shall provide at least 65,000A SCCR.
Cabinet
The condenser cabinet shall be constructed of bright aluminum sheet and divided into individual fan
sections by full width baffles. Internal structural support members, including coil support frame,
shall be galvanized steel for strength and corrosion resistance. Panel doors shall be provided on two
sides of each coil/fan section to permit coil cleaning. An electrical panel shall be contained inside a
factory-mounted NEMA 3R weatherproof electrical enclosure.
2.33.1.6 Mounting Legs Standard Aluminum Legs
Aluminum legs shall be provided to mount unit for vertical air discharge with rigging holes for
hoisting the unit into position. Standard height is 18 in. (457mm).
Optional Galvanized Steel Legs with Bracing
Condensers shall be shipped with (36in. [914mm]) (48in. [1219mm]) (60in. [1524mm]) mounting legs
with stabilization bracing. Legs, bracing and hardware shall be galvanized steel.

Liebert PDX and Liebert PCW 88


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.33.1.7 Liebert MC Condenser Accessories


Liebert Lee-Temp SystemOptional
Liebert Lee-Temp Receiver Kit shall contain an insulated, heated receiver tank with sight glasses,
mounting plate, mounting hardware, pressure relief valve, rotalock valve for refrigerant charge
isolation and piping assembly with head pressure operated three-way valve and check valve.
Components shall be field-assembled to the condenser. The three-way valve shall sense refrigerant
head pressure and adjust the flooding charge in the condenser coil to adjust the condenser heat
rejection capacity. The Liebert Lee-Temp heater shall be 150W, shall include an integral thermostat
to maintain refrigerant temperature at a minimum of 85F (29C) and shall require a separate power
supply of (208/230-1-60) (120-1-60V).
The Liebert Lee-Temp Kit shall function with Liebert MC variable speed fan motors and electronic
controls that lower fan speed in lower outdoor ambient temperatures for maximum energy efficiency.
This system shall allow system startup and positive head pressure control with ambient
temperatures as low as -30F (-34.4C).
2.33.1.8 Fusible Plug KitOptional
A fusible plug kit shall be field-installed on the liquid line for compliance with building codes
requiring refrigerant relief during high temperature and building fire conditions.
2.33.1.9 IBC/OSHPD Seismic Certification and IBC Wind/Snow Load ComplaintOptional
IBC/OSHPD Seismic Certification and IBC Wind/Snow Load Compliant condensers shall be provided
with any applicable bracing and field-installation instructions. Condensers shall bear a label
certifying compliance with IBC/OSHPD requirements.

2.34 LIEBERT DRYCOOLER


2.34.1 Liebert Drycooler Summary
These specifications describe requirements for a Liebert air-cooled drycooler for a Liebert Thermal
Management system. The drycooler shall be designed to reject waste heat to outdoor air and to control
glycol temperature as pumped glycol rates and outdoor ambient conditions change.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60Hz units shall be CSA-certified to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and shall be marked with
the CSA c-us logo.
2.34.2 Liebert Design Requirements
The drycooler shall be a factory-assembled unit, complete with integral electrical panel, designed for
outdoor installation and vertical airflow only. The drycooler shall be a draw-through design.
2.34.3 Liebert Drycooler Standard Features-All Drycoolers
The drycooler shall consist of drycooler coil(s), housing, propeller fan(s) direct-driven by individual fan
motor(s), electrical controls and mounting legs. The Liebert air-cooled drycooler shall provide glycol
temperature control to the indoor cooling unit by adjusting heat rejection capacity. Various methods
shall be available to match indoor unit type, minimum outdoor design ambient and maximum sound
requirements
2.34.3.1 Liebert Drycooler Coil
The Liebert-manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes
shall be expanded into continuous, corrugated aluminum fins. The fins shall have full-depth fin
collars completely covering the copper tubes, which shall connected to heavy wall Type L headers.
Inlet coil connector tubes shall pass through relieved holes in the tube sheet for maximum resistance
to piping strain and vibration. Coil shall be split flow into multiple coil circuits, combined to yield a
drycooler with ______ internal circuits. The supply and return lines shall be (spun shut [1-4 fan
models]), (brazed with a cap [6 or 8-fan models]) and shall include a factory-installed Schrader valve.
Coils shall be factory leak-tested at a minimum of 300 psig (2068kPag), dehydrated, then filled and
sealed with an inert gas holding charge for shipment. Field relief of the Schrader valve shall indicate
a leak-free coil.

89 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.34.3.2 Housing
The drycooler housing shall be constructed of bright aluminum sheet and divided into individual fan
sections by full-width baffles. Structural support members, including coil support frame, motor and
drive support, shall be galvanized steel for strength and corrosion resistance. Aluminum legs shall be
provided to mount unit for vertical air discharge and shall have rigging holes for hoisting the unit into
position. An electrical panel shall be inside an integral NEMA 3R weatherproof section of the
housing.
2.34.3.3 Propeller Fan
The propeller fan shall have aluminum blades secured to a corrosion protected steel hub. Fans shall
be secured to the fan motor shaft by means of a keyed hub and dual setscrews. Fan diameter shall be
26" (660mm) or less. Fans shall be factory-balanced and run before shipment. Fan guards shall be
heavy gauge, close-mesh steel wire with corrosion resistant PVC finish that shall be rated to pass a
675-hour salt spray test.
2.34.3.4 Fan Motor
The fan motor shall be continuous air-over design and shall be equipped with a rain shield and
permanently sealed bearing. Motors shall be rigidly mounted on die-formed galvanized steel supports.
2.34.3.5 Electrical Controls
Electrical controls, overload protection devices and service connection terminals shall be provided and
factory-wired inside the integral electrical panel section of the housing. A locking disconnect switch
shall be factory-mounted and wired to the electrical panel and controlled via an externally mounted
locking door handle. An indoor unit interlock circuit shall enable drycooler operation whenever indoor
unit compressors are active. Only supply wiring, indoor unit interlock wiring and high voltage wiring
to pumps when controlled by the drycooler shall be required at drycooler installation.
2.34.4 Specific Features by Drycooler Type
2.34.4.1 Fan Speed Control (DSF/DDF) Drycooler (1 Fan) with Integral Pump Control
The DSF/DDF drycooler shall have a fan speed controller that senses the leaving glycol temperature
and varying the speed of a FSC duty motor in direct proportion to the heat rejection needs of the
system. Fan speed controller shall be factory set to range of 70 to 100F (21 to 38C) for glycol-cooled
applications. The fan speed control shall be field adjustable to a range of 30 to 60F (2 to 7C) for free-
cooling applications. The motor shall be single-phase and include built-in overload protection. The
motor shall have an ODP enclosure. The DSF/DDF drycooler shall control operation of glycol pumps
powered from the electrical panel. The air-cooled drycooler shall have a ____ volt, 1 ph, ____ Hz power
supply.
2.34.4.2 Fan Cycling Control (DSO, DDO) Drycooler (All Fan Quantities) with Integral Pump
Control
The DSO/DDO/(D)DNT drycooler shall sense the leaving glycol temperature and cycle fixed speed
fans to maintain glycol temperatures. Aquastats shall have field-adjustable set-points. The fixed
speed motors shall be three-phase and have individual internal overload protection. Fixed speed
motors shall have a TEAO enclosure. The DSO/DDO drycooler shall control operation of glycol pumps
powered from the electrical panel. The air-cooled drycooler shall have a ____ volt, 3 ph, ____ Hz power
supply.
2.34.4.3 Fan Cycling Control (DDNT/DNT) Drycooler (All Fan Quantities)
The DDNT/DNT drycooler shall sense the leaving glycol temperature and cycle fixed-speed fans to
maintain glycol temperatures. Aquastats shall have field-adjustable setpoints. The fixed-speed
motors shall be three-phase and have individual internal overload protection. Fixed-speed motors
shall have a TEAO enclosure. The air-cooled drycooler shall have a ____ volt, 3 ph, ____ Hz power
supply.

Liebert PDX and Liebert PCW 90


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

2.34.4.4 Main Fan Control ((D)DNL) Drycoolers (All Fan Quantities)


The DDNL/DNL drycooler shall control fixed-speed fans when an external contact closure completes
the internal 24VAC circuit. The fixed-speed motors shall be three-phase and have individual internal
overload protection. Fixed-speed motors shall have a TEAO enclosure. The air-cooled drycooler shall
have a ____ volt, 3 ph, ____ Hz power supply.
2.34.4.5 No Fan Control ((D)DNC) Drycoolers (All Fan Quantities)
The DDNC/DNC drycooler shall activate all fixed-speed fans when supply power is applied to the
drycooler. The fixed-speed motors shall be three-phase and have individual internal overload
protection. Fixed-speed motors shall have a TEAO enclosure. The air-cooled drycooler shall have a
____ volt, 3 ph, ____ Hz power supply.
2.34.4.6 Liebert Quiet-Line Drycoolers (All Fan Quantities)
Liebert Quiet-Line drycoolers shall be available for DSO, DDO, (D)DNT, (D)DNL and (D)DNC control
types. The fan motor(s) shall have a TEAO enclosure and provide individual overload protection for
quiet operation.
2.34.5 Pump Controls
2.34.5.1 Single Pump Option
Pump controls for a single glycol pump up to 7.5 hp shall be incorporated into the same integral
electrical panel as the drycooler fan controls and may include fuses or circuit breakers as required for
the pump motor. Pump voltage, phase and frequency shall be same as drycooler voltage, phase and
frequency.
2.34.5.2 Dual Pump Option
Pump controls for a dual glycol pump system shall operate one pump as primary and the second
pump shall operate as a standby pump. Pump controls shall be incorporated into the same integral
electrical panel controlling drycooler fans. A field-supplied flow switch shall sense loss of flow and
switch to the standby pump for continuous system operation. An internal switch shall allow manual
selection of the primary (lead) pump.
2.34.5.3 Pump Package
Single Pump Package
This system shall be provided with a centrifugal pump mounted in a weatherproof and vented
enclosure. The pump shall be rated for ___ GPM (___ l/m) at ___ ft. (___ kPa) of head and operate on
___ volt, 3-phase, ___ Hz.
Dual Pump Package
The dual pump package shall include pumps, enclosure, and field-mounted flow switch. The standby
pump shall automatically start up on failure of the lead pump by drycooler pump controls or by a
separate factory-wired control box and shall include a lead/ lag switch for the pumps. Each pump
shall be rated for _______ GPM (___ l/s) at ___ ft. (___ kPa) of head.
2.34.5.4 Ancillary Items
Expansion Tanks, Fluid Relief Valves, Air Management and Other Devices
An expansion tank shall be provided for expansion and contraction of the glycol fluid due to
temperature change in the closed system. The tank and air vents shall be field-installed at the
system's highest elevation to allow venting of trapped air. A fluid pressure relief valve shall be
provided for system safety. The system shall include (tank-steel [expansion, compression, diaphragm,
bladder], air separator, air vent, fluid pressure relief valve, pressure gauges, flow switches, tempering
valves, [primary, primary and standby] pumps, supply and return piping).

91 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

3.0 EXECUTION
3.1 INSTALLATION OF PRECISION COOLING UNITS
3.1.1 General
Install precision cooling units in accordance with manufacturer's installation instructions. Install
units plumb and level, firmly anchored in locations indicated, and maintain manufacturer's
recommended clearances.
3.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory
mounted. Furnish copy of manufacturer's electrical connection diagram submittal to electrical
contractor.
3.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer's piping connection diagram submittal to piping contractor.

3.2 FIELD QUALITY CONTROL


Start up the system in accordance with manufacturer's startup instructions. Test controls and
demonstrate compliance with requirements. These specifications describe requirements for a
computer room environmental control system. The system shall be designed to maintain temperature
and humidity conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation
requirements.
3.2.1 Supply and Drain Water Piping
Connect water supply and drains to air conditioning unit. Provide pitch and trap as manufacturer's
instructions and local codes require.

3.3 SEISMIC IBC/OSHPD (OPTIONAL)


Install the condenser in accordance with manufacturer's installation instructions provided with
seismic option. Firmly anchor maintaining manufacturer's recommended clearances. Mounting
requirement details such as anchor brand, type, embedment depth, edge spacing, anchor-to-anchor
spacing, concrete strength, special inspection and attachment to non-building structures must be
outlined and approved by the Engineer of Record for the projection or building. Electrical, pipe, and
duct connections must permit movement in three dimensions and isolate the unit from field
connections. Electrical conduit shall be flexible having at least one bend between the rigid connection
at the unit cabinet and the connection to rigid conduit or foundation. The piping flexible connection or
loop must be suitable for the operation pressure and temperature of the system. Furnish copy of
manufacturer's piping connection diagram submittal to piping contractor.

Liebert PDX and Liebert PCW 92


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Notes

93 Liebert PDX and Liebert PCW


Guide SpecificationsNominal 17, 18, 23 or 29kW Thermal Management System

Liebert PDX and Liebert PCW 94


Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
2014 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-19810_REV0_04-15

Emerson Network Power


Liebert
www.emerson.com

Você também pode gostar