Escolar Documentos
Profissional Documentos
Cultura Documentos
Electrical data
IPN Primary nominal rms current 25 A
Features
IPM Primary current, measuring range 0 .. 55 A
R M Measuring resistance TA = 70 C TA = 85 C Closed loop (compensated)
RM min RM max RM min RM max current transducer using the Hall
with 12 V @ 25 A max 10 280 60 275 effect
@ 55 A max 10 80 60 75 Insulating plastic case recognized
with 15 V @ 25 A max 50 400 135 395 according to UL 94-V0.
@ 55 A max 50 140 135 135
ISN Secondary nominal rms current 25 mA Advantages
K N Conversion ratio 1 : 1000
Excellent accuracy
U C Supply voltage ( 5 %) 12 .. 15 V
Very good linearity
IC Current consumption 10 (@ 15 V) + IS mA
Low temperature drift
Accuracy - Dynamic performance data Optimized response time
Wide frequency bandwidth
X Accuracy @ IPN, TA = 25 C @ 15 V ( 5 %) 0.95 % No insertion losses
@ 12 .. 15 V ( 5 %) 1.25 % High immunity to external
L Linearity error < 0.15 % interference
Typ Max Current overload capability.
IO Offset current @ IP = 0, TA = 25 C 0.2 mA
Applications
IOM Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 IPN 0.3 mA AC variable speed drives and
IOT Temperature variation of IO 0 C .. + 70 C 0.1 0.5 mA servo motor drives
- 25 C .. + 85 C 0.1 0.6 mA Static converters for DC motor
tra Reaction time < 500 ns drives
tr Step response time to 90 % of IPN < 1 s Battery supplied applications
di/dt di/dt accurately followed > 200 A/s Uninterruptible Power Supplies
BW Frequency bandwidth (- 1 dB) DC .. 200 kHz (UPS)
Switched Mode Power Supplies
General data (SMPS)
TA Ambient operating temperature - 25 .. + 85 C Power supplies for welding
TS Ambient storage temperature - 40 .. + 90 C applications.
RS Resistance of secondary winding @ TA = 70 C 80 Application domain
@ TA = 85 C 85
m Mass 24 g Industrial.
Standard EN 50178: 1997
13November2014/version 3 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LA 25-P
Insulation coordination
U d Rms voltage for AC insulation test, 50 Hz, 1 min 3 kV
W Impulse withstand voltage 1.2/50 s 5.7 kV
Min
dCp Creepage distance 5 mm
dCI Clearance 5 mm
CTI Comparative tracking index (group I) 600
Applications examples
Safety
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
13November2014/version 3 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions LA 25-P (in mm)
dCl dCp
Connection
IP
IS RM
UC
UC
dCl
IP
dCl dCp
IP
Mechanical characteristics Remarks IS RM
General tolerance 0.2 mm IS is positive when IP flows in the direction of the arrow.
Primary through-hole 12.7 7 mm Temperature of the primary conductor should not exceed UC
Fastening & connection of secondary 3 pins 90 C. U C
0.6 0.7 mm Installation of the transducer must be done unless
Recommended PCB hole 1.2 mm otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document NANE120504 available on our Web site:
Products/Product Documentation.
Dynamic performances (di/dt and response time) are best
with a single bar completely filling the primary hole.
In order to achieve the best magnetic coupling, the
primary windings have to be wound over the top edge of
the device.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Page 3/3
13November2014/version 3 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com