AHU DETAILS REQUIRED FROM SHIMIZU TO VENDOR

Flow rate in Line size Pipe size Coil Pipe


SL No. AHU No. Area
cmh calculated selected dia in mm

`1 AHU/151/004 11.73 40.7 50 VTS


`2 AHU/151/003 11.73 40.7 50 VTS
`3 MAU/158/001 24.63 59.0 65 VTS
`4 AHU/167/001 2.21 17.7 20 VTS
`5 AHU/162/001 2.24 17.8 20 VTS
`6 AHU/166/001 0.61 9.3 20 VTS
`7 AHU/161/001 10.37 38.3 40 VTS
`8 AHU/167/002 35.70 71.1 80 VTS
`9 Downflow booth 2 2.57 19.1 25 Details for PIBCV to be checked wit
`10 Downflow booth 1 2.57 19.1 25 Details for PIBCV to be checked wit
`11 AHU/163/001 12.58 42.2 50 VTS
`12 AHU/161/002 9.01 35.7 40 VTS
`13 AHU/169/001 26.69 61.5 65 VTS
`14 AHU/135/001 2.04 17.0 20 VTS
`15 Downflow booth 1-capsule 5 26.4 32 Details for PIBCV to be checked wit
`16 Isolator 0.1 3.5 20 Details for PIBCV to be checked wit
`17 AHU/116/001 0.53 8.6 20 VTS
`18 AHU/115/001 1.26 13.3 20 VTS
`19 AHU/114/001 3.74 23.0 25 VTS
`20 AHU/113/001 4.93 26.4 32 VTS
`21 AHU/112/001 3.23 21.4 25 VTS
`22 AHU/125/001 2.72 19.6 25 VTS
`23 AHU/111/001 2.72 19.6 25 VTS
`24 MAU/155/001 9.06 35.8 40 VTS
`25 MAU/153/001 29.70 64.8 80 VTS
`26 AHU/149/001 28.73 63.8 80 VTS
`27 AHU/148/001 68.17 98.2 100 VTS
`28 Point of Consumption 1.65 15.3 20 Details for PIBCV to be checked wit
`29 AHU/148/002 3.57 22.5 32 VTS
`30 AHU/148/003 2.21 17.7 25 VTS
`31 MAU/157/001 5.22 27.2 32 VTS
`32 AHU/147/001 2.04 17.0 20 VTS
`33 MAU/156/001 32.76 68.1 80 VTS
`34 AHU/145/002 9.01 35.7 40 VTS
`35 AHU/136/001 1.70 15.5 20 VTS
`36 AHU/145/001 0.70 9.9 20 VTS
`37 AHU/133/002 4.93 26.4 32 VTS
`38 AHU/133/001 2.55 19.0 20 VTS
`39 AHU/131/001 2.55 19.0 20 VTS
`40 AHU/139/001 2.38 18.4 20 VTS
`41 AHU/132/001 0.85 11.0 20 VTS
`42 AHU/146/001 0.51 8.5 20 VTS
`43 AHU/144/001 2.48 18.7 20 VTS
`44 AHU/143/001 2.48 18.7 20 VTS
`45 AHU/142/001 2.48 18.7 20 VTS
`46 AHU/141/001 2.48 18.7 20 VTS
`47 AHU/140/001 2.40 18.4 20 VTS
`48 AHU/138/001 2.52 18.9 20 VTS
`49 AHU/137/001 2.23 17.8 20 VTS
`50 Thermo/Cold Former-01 6.0 29.0 32 Details for PIBCV to be checked wit
`51 Thermo/Cold Former-02 6.0 29.0 32 Details for PIBCV to be checked wit
`52 Thermo/Cold Former-03 6.0 29.0 32 Details for PIBCV to be checked wit
`53 Thermo/Cold Former-04 6.0 29.0 32 Details for PIBCV to be checked wit
`54 Thermo/Cold Former-05 6.0 29.0 32 Details for PIBCV to be checked wit
`55 Thermo/Cold Former-06 6.0 29.0 32 Details for PIBCV to be checked wit
`56 Thermo/Cold Former-07 6.0 29.0 32 Details for PIBCV to be checked wit
`57 Downflow booth- Betnesol 5.0 26.6 32 Details for PIBCV to be checked wit
`58 AHU/151/001 11.73 40.7 50 VTS
`59 AHU/151/002 11.73 40.7 50 VTS
`60 AHU/134/001 2.04 17.0 20 VTS
`61 AHU/118/001 3.23 21.4 25 VTS
`62 AHU/119/001 1.19 13.0 25 VTS
`63 IBC Wash Room 20.00 53.2 65 Details for PIBCV to be checked wit
`64 AHU/128/001 2.55 19.0 20
`65 Granulation Suite (FBD AHU) 18.00 50.5 65 Details for PIBCV to be checked wit
`66 Granulation Suite (Vessel) 7.00 31.5 50 Details for PIBCV to be checked wit
`67 AHU/126/002 0.43 7.8 20 VTS
`68 AHU/122/001 2.72 19.6 20 VTS
`69 AHU/117/001 2.89 20.2 25 VTS
`70 AHU/123/001 2.72 19.6 20 VTS
`71 AHU/124/001 2.72 19.6 20 VTS
`72 MAU/154/001 15.25 46.5 50 VTS
`73 AHU/109/001 0.85 11.0 20 VTS
`74 AHU/130/001 0.68 9.8 20 VTS
`75 AHU/129/001 28.22 63.2 65 VTS
`76 AHU/105/001 25.84 60.5 65 VTS
`77 AHU/110/001 2.21 17.7 20 VTS
`78 AHU/107/001 6.29 29.8 32 VTS
`79 AHU/103/001 1.53 14.7 20 VTS
`80 AHU/104/001 0.68 9.8 20 VTS
`81 AHU/104/002 2.55 19.0 20 VTS
`82 AHU/104/003 2.21 17.7 20 VTS
`83 AHU/104/004 2.55 19.0 20 VTS
`84 AHU/104/005 2.38 18.4 20 VTS
`85 AHU/104/006 1.87 16.3 20 VTS
`86 Compressor Dryer 15.13 46.3 65 Details for PIBCV to be checked wit
`87 Coater AHU-01 49.0 83.2 100 Details for PIBCV to be checked wit
`88 Coater AHU-02 49.0 83.2 100 Details for PIBCV to be checked wit
`89 FBD-HDG 300 18 50.3 60 Details for PIBCV to be checked wit
`90 AHU/126/001 0.85 11.0 20 VTS
`91 AHU/108/001 1.53 14.7 20 VTS
`92 AHU/102/004 0.90 11.3 20 VTS
`93 AHU/102/003 7.89 33.4 40 VTS
`94 MAU/152/001 8.86 35.4 40 VTS
`95 AHU/102/005 2.47 18.7 20 VTS
`96 AHU/102/002 5.10 26.9 32 VTS
`97 AHU/102/001 1.70 15.5 20 VTS
`98 purified Water Genration 7.14 31.8 32 Details for PIBCV to be checked wit

Purified water storage and


`99 10.20 38.0 40 Details for PIBCV to be checked wit
distribution-production PHE

VENDOR REQUIRED
Approved Makes Belimo, Seimens

VTS- Vendor to Specify


Vendor to give the details

Flowrate Valve Size Valve


Remarks
from Vendor in mm Authority

ils for PIBCV to be checked with Equuipment Vendor


ils for PIBCV to be checked with Equuipment Vendor

ils for PIBCV to be checked with Equuipment Vendor


ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor

ils for PIBCV to be checked with Equuipment Vendor


ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor

ils for PIBCV to be checked with Equuipment Vendor


ils for PIBCV to be checked with Equuipment Vendor

ils for PIBCV to be checked with Equuipment Vendor


ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor
ils for PIBCV to be checked with Equuipment Vendor

ils for PIBCV to be checked with Equuipment Vendor

GSK REQUIRED FOR APPROVAL