MS-9200UD
F1reL1Te" ALarms lntelligent Addressable FACP
with Built-ln 14.4K Baud Modem
www.firelite.com Section: Addressable


GENERAL
The FireLite MS-9200UD is a compact, cost-effective, intelli
gent addressable fire alarm control panel with a capacity of
198 addressable FireLite devices on one Signaling Line Cir
cuit (SLC) and a built-in 14.4K Baud modem for remote site
upload/download or remete monitoring. USTED
S624
The Signaling Line Circuit (SLC) loop supports up to 99
addressable detectors including photoelectric, photoelectric
with heat, ionization, photoelectric duct, fixed heat, fixed heat
with rate-of-rise, and fixed high-heat detectors. lt also sup
ports up to 99 addressable modules including monitor (two
wire detector, normally open devices), dual-monitor func
tions (two monitor circuits from one module,. two addresses
used), control (for Notification Appliance Circuits), and relay
(two Form-C) modules. The panel uses surface-mount tech
nology and is designed for ease of installation, programming,
and maintenance. lt features the latest in advanced fire pro
tection technology, including maintenance alert and auto
matic detector test functions.
SPECIAL FEA TURES:
Built-in 14.4K Baud modem.
Selectable strobe synchronization per NAC.
Remate site up/oad/download.
Four C/ass B or two Class A NAC circuits.

FEATURES
SLC Loop:
SLC can be configured for NFPA Style 4, 6, or 7 opera
tion.
SLC supports up to 198 addressable devices (99 detec Remete site upload/download capability.
tors and 99 monitor, control, or relay modules), including Two-level user-programmable passwords.
the new addressable dual-monitor module, heat dtec Custom English labels (per point) may be manually en
tors, and duct detector. tered or selected from an interna! library file.
SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG Two programmable Form-C relay outputs.
(3.25 mm2). Requires twisted, shielded wire (3,000 ft./914.4 99 software zones.
m untwisted, unshielded wire). User Interface:
Notification Appliance Circuits (NACs): Built-in 14.4K Baud modem (DACT).
Four onboard NACs with additional NAC capability using ,- Remete Acknowledge, Silence, Reset and Drill via addres
output control modules (CMF-300 or CMF-300-6). sable monitor modules, ACS Series annunciators or LCD-
Silence lnhibit and Auto Silence timer options. 80F remete annunciator.
Continuous, March Time, Temporal or California code for EIA-232 printer/PC interface (variable baud rate) on main
main circuit board NACs with two-stage capability. circuit board.
Selectable strobe synchronization per NAC. Integral 80-character LCD display witl;l backlighting.
6.0 amps total NAC power with XRM-24. Real-time clock/calendar with automatic daylight savings
Advanced Fire Technology: adjustments.
Sensitivity testing with printable results, onsite or offsite. History file with 1,000-event capacity.
Automatic drift compensation. EIA-485 supporting up to 32 ACS Series annunciators.
Programming and Software: EIA-485 supporting up to 32 LCD-80F annunciators.
Autoprogram (learn mode) reduces installation time. Maintenance alert warns when smoke detector dust ac
Fully programmable from local keypad, local PS-2 key cumulation is excessive.
board or PC via PK-Plus Windows utility. Automatic device type-code verification. cont'd pg. 3

ISO 9001
This document is not intended to be used for instaliation purposes. We try to
keep our product information up-to-date and accurate. We cannot cover ali
specific applications or anticpate all requirements. Ali specifications are sub
ject to change without notice. For more information, contact FireLite Alarms,. CERTIFIED
One Fire-Lite Place, Northford, Connecticut 06472. Phone: (800) 627-3473, ENGINIEIING I MANUFACllllM: Made in the U.S.A.
Toli-Free FAX: (877) 699-4105.
DF-52293 03/10/03 - Page 1 of 4
EIA-485
INTERFACE
(DIM-485) built into

-------
! ----J
24 VDC
the motherboard
MAI.-.. --
(four wires)


"(

i._nn.,,
SMOKE
DETECTORS
LCD-SOF S0350, S0350T, CP350,
Up to 6,000 ft. (1825.8 m) S0355, S0355T, CP355
between each LC0-80F
in the EIA-485 loop, and
Optional
REVERSE 1
between each LC0-80F POLARITY/
:;)
and the FACP .....
CITY BOX

!!l!!l!l
HEAT
OUTPUT DETECTOR$
(4XTMF) H350, H350R,
H355, H355R
24 VDC

11
1 !!' .1 1 EIA-485 8 FORM-C, 5-AMP RELAYS
in ACS mode (optional, order ACM-8RF)
(two wires)
DUCT DETECTOR$
0350P, 0350RP
NACs (Notificatlon
Appliance Circuits)
ANNUNCIATORS BELLS, SIGNALS, STROBES
AFM-LEO, LOM,
ACS/ACM EIA-232
INTERFACE
(PIM-24) built into
the motherboard MONITOR
MMF-300, MOF-300,
MMF-302, CMF-300,
CRF-300, 1300

PRINTER
NOTE: System can use either
the prinler OR the LCD-BOF. MINI MONITOR
They cannot be used simu/laneously. MMF-301

ADDRESSABLE
MULTI-MODULES
MMF-300-10,
MMF-302-6
CMF-300-6,'
CRF-300-6

1
WIRING REQUIREMENTS
The SLC requires use of a specific wire type to ensure proper circuit
operation. lt is recommended that all SLC wiring be twisted-pair shielded
to minimize the effects of electrical interference. Wire size should be
no smaller than 18 AWG (0.75 mm 2 ) and no larger than 12 AWG (3.25
mm 2 ). The wire size depends on the length of the SLC circuit. Use the
table below to determine the specific wiring requirements for the SLC.
PULL STATION
BG-12LX
Wire Distance Typical Wire Size 52293d1.wm
Requirements in Feet (m)
10,000 feet 12 AWG (3.25 mm'): Belden 9583, Genesis 4410,
Twisted-pair, shielded
(3,048 m) Signal 98230, WPW 0999.
8,000 feet 14 AWG (2.00 mm'): Belden 9581, Genesis 4408,
Twisted-pair, shielded
(2,438 m) Signal 98430, WPW 0995.
4,875 feet 16 AWG (1.30 mm 2): Belden 9575, Genesis 4406
Twisted-pair, shielded
(1,486 m) and 4606, Signal 98630, WPW 0991.
3,225 feet 18 AWG (0.75 mm2): Belden 9574, Genesis 4402
Twisted-pair, shielded
(983 m) and 4602, Signal 98300, WPW 0975.
3,000 feet
Unwisted, unshielded 12 - 18 AWG (3.25 - 0.75 mm').
(915 m)
5229311 .tbl

Page 2 of 4 - DF-52293 03/10/03


One person audible or silent walk test with walk-test log AUTO TEST FAIL trouble type. System Reset clears this
and printout. trouble.
Point trouble identification.
Local piezo sounder.
NFPA STANDARDS
The MS-9200UD complies with !he following NFPA 72 Fire
Waterflow (nonsilenceable) selection per monitor point.
Alarm Systems requirements:
System alarm verification selection per detector point.
LOCAL (Automatic, Manual, Waterflow and Sprinkler Su
PAS (Positive Alarm Sequence) and presignal delay per
pervisory).
point (NFPA 72 compliant).
AUXILIARY (Automatic, Manual and Waterflow) (requires
Optional 4XTMF module (conventional reverse polarity/
4XTMF).
city box transmitter).
REMOTE STATION (Automatic, Manual and Waterflow)
CONTROLS AND INDICATORS (requires 4XTMF ).
LED INDICATORS PROPRIETARY (Automatic, Manual and Waterflow).
1. AC POWER (green) CENTRAL STATION (Automatic, Manual and Waterflow,
2. FIRE ALARM (red) and Sprinkler Supervised).
3. SUPERVISORY (yellow)
4. ALARM SILENCED (yellow)
SPECIFICATIONS
5. SYSTEM TROUBLE (yellow) AC Power - TB1: 120 VAC, 60 Hz, 3.0 amps. Wire size:
6. MAINTENANCE/PRESIGNAL (yellow) mnimum 14 AWG (2.00 mm2) with 600 V insulation.
7. DISABLED (yellow) Battery (lead acid only) - TB2: Maximum charging circuit:
8. BATIERY FAULT (yellow) Normal flat charge 27.6 VDC@ .80 amp. Maximum battery
9. GROUND FAUL T (yellow) charger capacity: 18 AH. MS-9200UD cabinet holds maxi
MEMBRANE SWITCH CONTROLS mum of two 18 AH batteries. For 25- 120 AH batteries, use
1. ACKNOWLEDGE/STEP the CHG-120F or CHG-75 Battery Charger and BB-55F
2. ALARM SILENCE Battery Box.
3. DRILL NOTE: Jumper JP3, on the FACP main circuit board, must
4. SYSTEM RESET (lamp test) be cut to disable the FACP battery charger when using the
5 - 16. 12-key pad with full alphabet CHG-120F.
17 - 20. 4 cursor keys Remote Synchronization Output - TB2: A 24 VDC, 40
21. ENTER mA signal that mimics !he sync signal of NAC 1 and can be
utilized by remole power supplies such as the FCPS-24FS6/
FIELD -PROGRAMMING FEATURES 8. This allows NAC devices attached to the power supply to
OFFLINE PROGRAMMING: Create the entire program in synchronize with the devices connected to NAC 1 of !he
your office using a Windows-based software package (or FACP.
der programming kit PK-Plus separately). Upload/download
Communication Loop - (standard) TBS: 24 VDC nomi
system programming locally to the MS-9200UD in less !han
nal, 27.6 VDC maximum. Maximum length: 10,000 ft. (3048
one minute.
m) total twisted, shielded pair length. Maximum loop cur
AUTOPROGRAMMING: Command the MS-9200UD to pro ren/: 400 mA (short circuit) or 100 mA (normal). Maximum
gram itself (takes less than 30 seconds). In the Auto-Pro loop resistance: 40 ohms. Supervised and power-limited.
gram mode, the MS-9200UD scans for all possible devices Notification Appliance Circuits - TB4: Power-limited cir
at all addresses, stores the device types, and addresses cuitry. Maximum voltage drop in wiring: 2.0 VDC. Nominal
found, and then loads default values for all options (General operating voltage: 24 VDC. Curren/ limit: fuseless, electronic,
Alarm). lt also checks for two or more devices set to the power-limited circuitry. Maximum signaling curren/ per cir
same address. cuit: 2.50 amps. End-of-Line Resistor: 4.7K ohm, 1/2 watt
ONLINE EDIT: While still providing fire protection, the MS- (P/N 71252 UL listed) for NACs. Refer to FireLite Device
9200UD may be programmed from the front panel. Simple Compatibility Document for listed compatible devices.
menu trees displayed on the LCD allow the trained user to Programmable and Trouble Output Relays - TB5, TB6,
perform all functions without referring back to the program TB7: Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5
ming manual. amps@ 30 VAC (resistive). Form-C relays.
ENGLISH LABEL LIBRARY: Quickly select labels from a Four-Wire Resettable Smoke Detector Power (24 VDC
standard library of more !han 50 adjectives/nouns, such as nominal) - TB1, Terminals 3 (+) & 4 (-): Maximum ripple
"FLR 3 HALLWAY," or enter custom labels letter-by-letter. voltage: 1 O mVRMS. Up to 0.5 amps for powering four-wire
Use recall function to repeat previously used label. smoke detectors. Power-limited circuit. Refer to FireLite
PROGRAM CHECK: Automatically catch common errors, Device Compatibility Document for listed compatible devices.
such as control modules not linked to any zone or input point. Nonresettable Power #1 (24 VDC Nominal) -TB1, Termi
nals 3 (+) & 4 (-): Maximum ripple voltage: 1O mVRMS. Up to
MAINTENANCE ALERT 0.5 amps total DC curren! available from each output. Power
The MS-9200UD continuously monitors each smoke detec limited circuit. TB1, Terminals 1 (+) & 2 (-) can be config
tor and is capable of reporting maintenance conditions. This ured as resettable 24 V or non-resettable via JP4.
reduces the risk of false alarms due to dust accumulation. NOTE: lf using optional XRM-24, total NAC and auxiliary cur
Refer to the control panel installation manual for more infor ren/ draw cannot exceed 6 amps.
mation. EIA-485 (ACS) - TB6: ACS annunciator connector, Termi
nal 1 (+) and Terminal 2 (-).
AUTOMATIC TEST OPERATION EIA-485 (TERM) - TB7: Terminal mode annunciator con
The MS-9200UD performs an automatic test of each detec nector, Terminal 1 (Out+), 2 (In+), 3 (Out-), 4 (In-).
tor every two hours. Failure to mee! the test limits causes an EIA-232 - TBS: PC/printer connector, Terminal 1 (Trans
mit), 2 (Receive), 3 (DTR), 4 (Ground).

DF-52293 03/10/03 - Page 3 of 4


CABINET SPECIFICATIONS Circuit option requires externa! 24 VDC to power notification
Door: 18.67" (47.43 cm) high x 15.78" (40.08 cm) wide x appliances.
1.08" (2.74 cm) deep. Backbox: 18.50" (47.0 cm) high x CRF-300: Addressable relay module containing two isolated
15.50" (39.37 cm) wide x 4.37" (11.1 cm) deep. Trim Ring sets of Form-C contacts, which operate as a DPDT switch.
(FC-TR): 21.62" (54.92 cm) high x 18.62" (47.3 cm) wide. Mounts directly to a 4.0" (10.16 cm) box, surface mount using
the SMB500.
PRODUCT LINE INFORMATION
BG-12LX: Addressable manual pull station with interface
MS-9200UD: 198-point addressable Fire Alarm Control Panel.
module mounted inside.
lncludes 80-character LCD display, single printed circuit board,
cabinet and dress panel. 1300: This module isolates the SLC loop from short circuit
ACM-BRF: Optional plug-in relay module provides 8 Form-C conditions (required for Style 7 operation).
5.0 amp relays. SMB500: Used to mount ali modules except the MMF-301
PK-PLUS: Programming software far Windows-based PC and M301.
computer (cable not included). MMF-300-1O: Ten-input monitor module. Mount one or two
FC-TR: Trim Ring far semi-flush mounting. modules in a BB-2Fcabinet (optional). Mount up to six modules
BB-55F: Battery box, required to house two PS-12250 on a CHS-6 chassis in a BB-6F.
batteries and one CHG-120F battery charger. For batteries MMF-302-6: Six-zone interface module. Mount one or two
greater than 25 AH, consult factory for housing/mounting modules in a BB-2F cabinet (optional). Mount up to six modules
arrangements. on a CHS-6 chassis in a BB-6F.
BB-26: Battery backbox, holds up to two PS-12250 batteries. CMF-300-6: Six-circuitsupervised control module. Mount one
CHG-120F: Remole battery charging system far lead-acid or two modules in a BB-2F cabinet (optional). Mount up to six
batteries with a rating of 25 to 120 AH. CHG-120F or CHG- modules on a CHS-6 chassis in a BB-6F.
75 required for charging greater /han 25 AH batteries. CRF-300-6: Six Form-C relay control module. Mount one or
CHG-75: Battery charger far lead-acid batteries with a rating two modules in a BB-2F cabinet (optional). Mount up to six
of 25 to 75 AH. CHG-120F ar CHG-75 required for charging modules on a CHS-6 chassis in a BB-6F.
greater /han 25 AH batteries. NOTES: 1) Compatible with legacy FireLite 300 Series de
PS-12180: Battery, 12 volt, 18.0 AH, (two required). vices. Please consult factory for further informa/ion on ali the
PS-12250: Battery, 12 volt, 25 AH, (two required; requires 300 series devices: CP300, S0300, S0300T, M300, M301,
CHG-75). M302, C304, and BG-10LX. 2) "A" suffix should be included
only when ordering ULC listed units (e.g., S0350A, MMF-300A).
PS-12550: Battery, 12 volt, 55 AH, (two required; requires
3) Far more informa/ion on Compatible Addressable Devices
CHG-75). far use with the MS-9200UD, see /he following data sheets
PRTIPK-CABLE: Cable printer/personal computer interface (document numbers): SD350ISD350T (DF-52149), CP350
cable. (DF-52158), MMF-300 SerieslMDF-300 (DF-52121), BG-12LX
Windows is a registered trademark of Microsoft Corporation. (DF-52013), MMF-300-10 (DF-52347), MMF-302-6 (DF-
52356), CMF-300-6 (DF-52365), and CRF-300-6 (DF-52374).
COMPATIBLE ADDRESSABLE DEVICES
Ali feature a polling LEO and rotary switches for addressing. COMPATIBLE ANNUNCIATORS
CP350/CP355: Addressable low-profile ionization smoke EIA-485 interface: Built into the motherboard.
detector. AFM-LED Zone Series: LED-type fire annunciators capable
SD350ISD355: Addressable low-profile photoelectric smoke of providing up to 99 software zones of annunciation. Avail
able in increments of 16 or 32 with expandable (AFM-X Se
detector.
ries) and non-expandable (AFM Series) configurations to
SD350T/SD355T: Addressable low-profile photoelectric mee! a variety of applications.
smoke detector with thermal sensor.
ACSIACM Annunciator Series: Allows annunciation of loop
H350IH355: Fast-response, low-profile heat detector. modules and detectors.
H350RIH355R: F ast-response, low-profile heat detector with LDM Graphic Series: Lamp Driver Module series for use
rate-of-rise option. with custom graphic annunciators.
D350P: Photoelectric duct smoke detector. LCD-BOF (Liquid Crystal Display) point annunciator: 80-
D350RP: Photoelectric duct smoke detector with relayoption. character, backlit LCD-type fire annunciators capable of dis
MMF-300: Addressable Monitor Module farone zoneof normally playing English-language text. Up to 32 LCD-80F annuncia
open dry-contact initiating devices. Mounts in standard 4.0" (10.16 tors may be connected to the EIA-485 terminal mode serial
cm) box. lncludes plastic cover plate and end-of-line resistor. interface on the MS-9200UD motherboard.
Module may be configured for either a Style B (Class B) or Style NOTE: For more informa/ion on Compatible Annunciators
D (Class A) IDC. far use with the MS-9200UD, see the following data sheets
(document numbers) AFMIAFM-X Series (DF-51465), ACM
MDF-300: Dual Monitor Module. Same as MMF-300 except
BRF (DF-51555), ACSIACM Series (DF-52378), LDM Series
it provides two Style B (Class B) only IDCs. (DF-51384), LCD-BOF (DF-52185).
MMF-301: Miniature version of MMF-300. Excludes LEO and
Style D option. Connects with wire pigtails. May mount in AGENCY LISTINGS AND APPROVALS
device backbox. See the first page of this data sheet far listing agencies and
MMF-302: Similar to MMF-300, but may monitor up to 20 file numbers. These listings and approvals apply to the ba
conventional two-wire detectors. Requires resellable 24 VDC sic MS9200UD control panel. In sorne cases, certain mod
power. Consult factory far compatible smoke detectors. ules may not be listed by certain approval agencies, or list
CMF-300: Addressable Control Module farone Style Y/Z (Class ing may be in process. Consult factory far lates! listing sta
B/A) zone of supervisedpolarized Notification Appliances. Mounts tus.
directlyto a 4.0" (10.16 cm) electrical box. Notification Appliance
Page 4 of 4 - DF-52293 03/10/03
September 29, 1999 D-500

(2) F1re-ure ALarms PS Series Batteries


Section: Power Supplies/Accessories

GENERAL
Power-Sonic PS Series batteries provide secondary power for the
whole series of FireLite tire alarm control panels.

FEATURES MH14328 (S)


Provide secondary power for control panels.
Gelled electrolyte.
Sealed and maintenance-free.
Overcharge protected.
Extended shelf lite.
Easy handling with leakproof construction.
Ruggedly constructed, high-impact ABS plastic case.
Long service lite.
Compact design.

CAPACITY
Battery capacity, expressed in ampere-hours (AH), is the product of
a discharge curren! and the length of time that the curren! is dis
charged. Batteries are rated according to their performance during
20 hours of discharge at a constan! curren!.
The rated capacity of a battery is determined by subjecting it to a
constan! discharge curren! for 20 hours at 68 F (20 C). Alter 20
hours the voltage across the terminals is measured. The discharge
curren! which causes a reading of 1.72 volts per cell (5.16 V on a 6

4
V battery and 10.32 V on a 12 V battery) is called the rated curren!. SEALED RECHARGEABLE
This curren! multiplied by 20 is the rated capacity of the battery. BATTERY
HHI/H
lf!.!i"i"llfl1t1Nlltlll/l
APPLICATIONS POll/"Ell
,......, SDNlr
Use the PS Series batteries to provide backup power for control Model PS-695 6 Volt 9. 5 AH
panels. Select batteries based on curren! requirements for your Power-Sonic Corporation
system and the capacity of its charger. These batteries can be
used over a temperature range of -76 F to+140 F (-60 C to +60 C).

CONSTRUCTION
The sealed construction of the Power-Sonic battery allows trouble
free, sale operation in any position. There is no need to add elec
trolyte, as gases generated during overcharge are recombined in a
unique "Oxygen Cycle." The battery is sealed, leakproof, and main
tenance-free. The case is made of ABS, a high-impact plastic resin
(acrylonitrile butadiene styrene copolymer) with high resistance to
chemicals and flammability. The PS-695 Battery

INSTALLATION
AII panels have space reserved for batteries. See the appropriate
panel installation manual for battery size restrictions. Typical inter
connection diagrams are shown in the literature accompanying each
control panel.

This document is not intended to be used far installation purposes. We try to keep our prod
uct information up-to-date and accurate. We cannot cover all specific applications or antici IS0-9001
pa te all requirements. AII specifications are subject to change without notice. Far more Engineering and Manufacturing

(2) FlreUTe ALarms


information, contact Firelite. Phone: (203) 484 7161 FAX: (203) 484-7118 Quality System Certified to
lnternational Standard IS0-9001
One Fire-Lite Place, Northford, Connecticut 06472
.

DF-50970 - Page 1 of 3
HEIGHT 1 BELOW
3.70 0.08 inches
TOP VIEW (94 2 mm)

HEIGHT 2 BELOW
3.86 0.08 inches
(96 2 mm)

,.., ,.., ooooonooooooooooooooooao oooooaoooooool'.J


000000000000 0000 000000 00 0000,oooooooo o L_ 1

T1
::::::::::::::::::::::::::::;::::::::: __J

SEALED RECHARGEABLE BATTERY


BB-17F: Optional Battery Backbox A
14-1/2" W X 8-1/4" H X 4-3/4" 0
SIDE 2 (mm: 368.3 W x 209.55 H x 120.65 O)
For remole mounting of two 12-volt
MODEL PS-1270 VIEW PS-12180 batteries.

12 VOLT 7.0 AMP HOUR

5.94 0.04 inches


(151 1 mm) 2.56 0.04 inches 1
(65 1 mm)
1109dim1.tif
BB-55F: Optional Battery Backbox
See CHG-120F catalog sheet for details.

ENGINEERING SPECIFICATIONS 6040bb55.wml

The tire control panel shall be equipped with secondary power provided by gelled-electrolyte batteries. The batteries
shall be maintenance-free and shall be capable of powering the system in a manner and for a length of time determined
by the governing regulations and the authority having jurisdiction.
DIMENSIONS
Nominal Discharge
Capacity Current Height over
Nominal @ @ Width Depth Height terminal Weight
Voltage 20 hr. rate 20 hr. rate
MODEL V A.H. mA in. mm. in. mm. in. mm. in. mm. lbs. kg.

PS-695 6 9.5 475 4.26 108 2.75 70 5.54 141 5.54 141 4.9 2.2

PS-1250 12 5.0 250 3.54 90 2.76 70 4.02 102 4.21 107 4.1 1.9
PS-1270 12 7.0 325 5.94 151 2.56 65 3.70 94 3.86 98 5.7 2.6
PS-12120 12 12 600 5.94 151 3.86 98 3.70 94 3.86 98 8.8 4.0

PS-12180 12 18 875 7.13 181 2.99 76 6.57 167 6.57 167 12.8 5.8
PS-12250 12 25 1300 6.89 175 6.54 166 4.92 125 4.92 125 18.7 8.5
PS-12600 12 60 3000 10.25 260 6.60 168 8.20 208 9.45 240 39.7 18.0
PS-121000 12 100 5000 12.00 305 6.60 168 8.20 208 9.45 240 65.7 29.8
5097011.tbl

Effect of Temperature on Capacity


Characteristic Discharge Curves 120% ,--,-----,,-----,--,--, -,
- -,--
-

--r--
- --.....-i\
6.5 13

i 6.0 12 r-:::::::--.... r-.


'\ 1\ \ \ \ ,g 80% 1-....,,c---+ ----+---:::--!'="""1'--,.,, .,,,--=,j- - 0.2s e
-...
t----r--
5.5 11
1.DC
----- - o.se
--- (J_ ----- - 1 e
' 0.175C o.se 1::- 60%
5.0 10
0.25C : ----- - 2 e
, ctl
4.5 9
\ 0.6C
c..
40% f---,,""71,c......,...=--+--+----l-----l---l

4.0 8 L -- 1C
: 3C .....2c-
o ,'
2 3 5 10 2030 60 2 3 5 10 20 30 0% -----'----'-----'---'-- -'--___J
1109grf1.tif --- minutes- -
/- hours ----j -20' -1 O' O' 1 O' 20 30' 40' 50' 60'
Discharge Time @ 20 C (68'F)
Temperature (Oegrees C.)
Page 2 of 3 - DF-50970
1109grl2.wmf
-- PS-121000 RECHARGEABLE BAffERY:
APPLICATIONS AND CHARGING
CYCLE APPLICATIONS: Limit initial current to 20A. Charge until battery voltage (under charge) reaches 14.40 to 14.70
volts at 68 F (20 C). Hold at 14.40 to 14.70 volts until current drops to approximately 1000 mA. Battery is fully charged
under these conditions, and charger should either be disconnected or switched to "float" voltage.
"FLOAT" OR "STAND-BY" SERVICE: Hold battery across constan! voltage source or 13.50 to 13.80 volts continu
ously. When held at this voltage, the battery will seek its own curren! level and maintain itself in a fully charged position.
NOTE: Due to the self-discharge characteristics of this type of battery, it is imperativa that the battery be charged after
six to nine months of storage, otherwise permanent loss of capacity might result from sulfation.

100%


90%

o:: 80%
Charging before
use is necessary
70% to help recovar
full capacity.

-----+-----+------+------+-------------------J
o:: 60%
:;
\
1
Charge may
g_ 50% 1
O C fail to restore
40 C 30 C full capacity.
(104 F) (86 F) (68 F) DO NOT
40%
------
_L let batteries
reach this state.
1

1
1
1

0% \,

o
1

o 2 4 6 8 10 12 14 16 18 20
Standing Period (Months)
PS-121000
14.0 V Shelf-Life
and Storage
13.0V

O) 12.0 V

g 11.0 V

.E

9.0V PS-121000
Discharge
B.O V
Characteristics
1

200A
1
'

6 12 24 36 48 1 2 4 6 8 10 20 40
MINUTES X---- HOURS
Discharge Time

DF-50970 - Page 3 of 3
May 3, 2001 OF-52149 E-150

(2) Ftre-ure ALarms SD350(A)/SD350T(A)


Addressable Photoelectric Detectors
www.firelite.com Section: Addressable Devices

GENERAL
The S0350 and S0350T Addressable, low-profile plug-in
Photoelectric Oetectors use a state-of-the-art photoelectric
sensing chamber with communications to provide open area
protection and are used exclusively with Fire-Lite's MS-9200
and MS-9600 Addressable Fire Alarm Control Panels. The
S0350T adds thermal sensors that will alarm at a fixed tem
perature of 135 F. Since this detector is addressable, it will
help emergency personnel quickly locate a fire during its early
stages, potentially saving precious rescue time while also 7272-0075:194
reducing property damage. Two LEOs on each sensor light
to provide a local, visible sensor indication. Remole LEO
annunciator capability is available as an optional accessory
(Part No. RA400Z).

FEATURES
SLC Loop
2-wire loop connection.
Unit uses base for wiring.
Addressing
Addressable by device.
Oirect Oecade 01-99 (MS-9200) and 01-159 (MS-9600)
.
entry of address "'
(')
Architecture o
C/)

Unique single source, dual chamber design to respond


quickly and dependably to a broad range of tires. SD350
Sleek, low-profile design.
Other System Features
Integral communications and built-in type identification. Fully coated circuit boards and superior RF/transient pro-
Built-in tamper-resistant feature. tection.

Removable cover and insect-resistant screen for simple 94-VO plastic flammability rating.
field cleaning. Low standby curren!.
Operation Options
Withstands air velocities up to 1,500 feet-per-minute with Remote LEO output connection (Part No. RA400Z).
out triggering a false alarm.
Factory preset at 1.5% nominal sensitivity for panel alarm APPLICATIONS
threshhold leve!. Use photoelectric detectors in life-safety applications to pro
vide a broad range of fire-sensing capability, especially where
Visible LEO "blinks" when the unit is addressed (communi-
smoldering fires are anticipated. lonization detectors are of
cating with the fire panel) and latches on in alarm.
ten better than photoelectric detectors at sensing fast, flam
Mechanicals ing fires.
Sealed against back pressure.
CONSTRUCTION
Oirect surface mounting or electrical box mounting.
These detectors are constructed of LEXAN in an off-white


Mounts to: single-gang box, 3.5" or 4" octagonal box, or color. The S0350(T) plug-in low-profile smoke detectors are
4" square electrical box (using a plaster ring - included). designed to commercial standards and offer an attractive ap
pearance.

ISO 9001
This document is not intended to be used for instaliation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover all specific applica-
tions or anticpate ali requirements. Ali specifications are subject to change without
notice. For more information, contact FireLite Alarms, One Fire-Lite Place, Northford,
Connecticut 06472. Phone: (800) 627-3473, Toll Free FAX: (877) 699-4105, FAX ENGINEEBINC&MANUFACTUBING
Back: 888 388-3299. Made in the U.S.A.
DF-52149 - Page 1 of 2
- INSTALLATION
The SD350(T) Plug-ln Detectors use a detatchable mount
ing base to simplify installation, service and maintenance.
PRODUCT LINE INFORMATION
SD350(A) Addressable Photoelectric Detector (B350LP
base included). (A) model has ULC listing.
Mount base on box which is at leas! 1.5 inches (3.81 cm) SD350T(A) Same as above with thermal element
deep. Suitable boxes include: (B350LP base included). (A) model has ULC
listing.
4" (10.16 cm) square box with plaster ring.
RA400Z Remole LEO. Mounts to a single-gang box.
4" (10.16 cm) octagonal box. B350LP Plug-in detector base (included). Diameter:
6.1" (155 mm). Mounting: 4" (102 mm) square
3.5" (8.89 cm) octagonal box.
box with or without plastic ring, 4" octagon
Single-gang box. box, 3 1/2" octagon box or single gang box.
AII mounting boxes have a mnimum depth of
NOTE: Because of the inherent supervision provided by the
1.5" (38 mm).
SLC loop, end-of-line resistors are not required. Wiring "T
taps" or branches are permitted for Style 4 (Class B) wiring. B224RB Plug-in System Sensor relay detector base.
Diameter: 6.2" (157 mm). Mounting: 4" (102
OPERATION mm) square box with or without plastic ring,
4" octagon box, 3 1/2" octagon box. AII
Each SD350(T) uses one of 99 possible addresses on the
mounting boxes have a mnimum depth of
MS-9200 Signaling Line Circuit (SLC) or up to 318 (159 on
each loop) on the MS-9600 SLC. lt responds to regular polis 1.5" (38 mm).
from the system and reports its type and status. 85018H Plug-in System Sensor sounder detector
base. Diameter: 6.0" (153 mm). Mounting: 4"
The SD350(T) Addressable Photoelectric Sensor unique
(102 mm) square box with or without plastic
unipolar chamber responds quickly and uniformly to a broad
ring. Mounting box has a mnimum depth of
range of smoke conditions and can withstand wind gusts up
1.5" (38 mm).
to 1,500 feet-per-minute without sending an alarm leve! sig
nal. Because of the unipolar chamber, the SD350(T) is ap
proximately two times more responsive than most photoelec
tric sensors. This makes it a more stable detector.

DETECTOR SENSITIVITY TEST


Each detector can have their sensitivity tested (required per
NFPA 72, Chapter 7 on lnspection, Testing and Mainte
nance) when installed/connected to an MS-9200 or MS-
9600 addressable tire alarm control panel. The results of
the sensitivity test can be printed off the MS-9200 and MS-
9600 for record keeping.

SPECIFICATIONS
Voltage range: 15 - 32 VDC (peak).
Standby curren!: 300 A @ 24 VDC.
LEO curren!: 6.5 mA @ 24 VDC (latched "ON").
Air velocity: 1,500 ft./min. (7.6 m/sec.) maximum.
Diameter: 5.0 inches (12.7 cm), 6.2 inches (155 mm) installed
1n B350LP Base.
Height: 1. 7 inches (43 mm) installed in B350LP Base.
Weight: 3.6 oz. (102 g).
Operating Temperature Range: O to 49 C (32 to 120F)
SD350.
Operating Temperature Range: O to 38 e (32 to 1 OO F)
SD350T.
Temperature: O - 49 C (32 - 120 F).
Relative humidity: 10% - 93%, non-condensing.

Page 2 of 2 - OF-52149
May 3, 2001 DF-52158 E-250
CP350
(2) Fl9LIT9" ALarms lntelligent Addressable
loni:zation Detector
www.firelite.com Section: Addressable Devices

GENERAL
The CP350 Addressable, low-profile (Height: 1.7 inches) plug
in lonization Detector uses a state-of-the-art ionization sens
ing chamber to provide open area protection and is used
exclusively with Fire-Lite's MS-9200 and MS-9600 Address
able Fire Alarm Control Panels. The ionization detector is
used to sense products-of-combustion and report the mea
sured level of such products to the tire alarm control panel.
Since this detector is addressable, it will help emergency
personnel quickly locate a tire during its early stages, poten 7271-0075: 193
tially saving precious rescue time while also reducing prop
erty damage. Two LEDs on each sensor light to provide a
local, visible sensor indication. Remole LEO annunciator
capability is available as an optional accessory (Part No.
RA400Z).

FEATURES
SLC Loop
2-wire loop connection.
Unit uses base for wiring.
Addressing
Addressable by device.
Oirect Decade 01-99 (MS-9200) and 01-159 (MS-9600)
:Jf...
_ .._...
... .....
. .
. ..

entry of address.
Architecture CP350
Unique single source, dual chamber design to respond
quickly and dependably to a broad range of tires.
Other System Features
Sleek, low-profile design.
Fully coated circuit boards and superior RF/transient
Integral communications and built-in type identification. protection.
Built-in tamper-resistant feature. 94-VO plastic flammability rating.
Removable cover and insect-resistant screen for simple Low standby curren!.
field cleaning. Options
Operation Remate LEO output connection (Part No. RA400Z).
Withstands air velocities up to 1,500 feet-per-minute
without triggering a false alarm. APPLICATIONS
Factory preset at 1.5% nominal sensitivity for panel alarm Use ionization detectors in life-safety applications to provide
threshold level. a broad range of fire-sensing capability, especially fast, flam
ing tires. Where smoldering tires are anticipated, a photo
Visible LEO "blinks" when the unit is addressed (commu- electric sensor may provide !aster response.
nicating with the tire panel) and latches on in alarm.
Mechanicals CONSTRUCTION
Sealed against back pressure. These detectors are constructed of LEXAN in an off-white
color. The CP350 plug-in low-profile smoke detectors are
Direct surface mounting or electrical box mounting. designed to commercial standards and offer an attractive ap
Mounts to: single-gang box, 3.5" or 4" octagonal box, or pearance.
4" square electrical box (using a plaster ring) .

1 SO gOO 1
This document is not intended to be used for installation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover ali specific applica-
tions or anticpate ali requirements. Ali specifications are subject to change without
notice. For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, CERTIFIED
Connecticut 06472. Phone: (800) 627-3473, Toll Free FAX: (877) 699-4105, FAX ENGINEERINC & MANUFACTURING
Back: 888 388-3299. Made in the U.S.A.
DF-52158 - Page 1 of 2
--. INSTALLATION
The CP350 Plug-ln Detectors use a detatchable mounting
bracket to simplify installation, service and maintenance.
PRODUCT LINE INFORMATION
CP350 Addressable lonization Detector (B350LP
base included).
Mount base on box which is at least 1.5 inches (3.81 cm) CP350A Same as above with ULC listing (B350LP
deep. Suitable boxes include: base included).
4" (1 O.16 cm) square box with plaster ring. RA400Z Remole LEO. Mounts to a single-gang box.
4" (10.16 cm) octagonal box. 8350LP Plug-in Detector base (included). Dimensions:
6.1" (155 mm . Mounting: 4" (102 mm) square
3.5" (8.89 cm) octagonal box.
box with or without plastic ring, 4" octagon box,
Single-gang box. 3 1/2" octagon box or single gang box. AII
NOTE: Because of the inherent supervision provided by the
mounting boxes have a minimum depth of 1.5"
SLC loop, end-of-line resistors are not required. Wiring "T (38 mm).
taps" or branches are permitted for Style 4 (Class B) wiring. B224RB Plug-in System Sensor relay detector
base. Diameter: 6.2" (157 mm). Mounting:
OPERATION 4" (102 mm) square box with or without
Each CP350 uses one of 99 possible addresses on the MS- plastic ring, 4" octagon box, 3 1/2" octagon
9200 Signaling Line Circuit (SLC) or up to 318 (159 on each box. AII mounting boxes have a mnimum
loop) on the MS-9600 SLC. lt responds to regular polis from depth of 1.5" (38 mm).
the system and reports its type and status. 8501 BH Plug-in System Sensor sounder detector
The CP350 Addressable lonization Sensor unique unipo- base. Diameter: 6.0" (153 mm). Mounting:
lar chamber responds quickly and uniformly to a broad range 4" (102 mm) square box with or without
of smoke conditions and can withstand wind gusts up to 1,500 plastic ring. Mounting box has a minimum
feet-per-minute without sending an alarm level signal. Be- depth of 1.5" (38 mm).
cause of the unipolar chamber, the CP350 is approximately
two times more responsive than most ionization sensors. This
makes it a more stable detector.

SPECIFICATIONS
Voltage range: 15 32 VDC (peak).
LEXAN is a registered trademark of GE Plastics, a subsidiary of General
Standby current: 300 A @ 24 VDC. Electric Company.
LED current: 6.5 mA @ 24 VDC (latched "ON").
Air velocity: 1,500 ft./min. (7.6 m/sec.) maximum.
Diameter: 5.0 inches (12.7 cm), 6.1 inches (155 mm) installed
in B350LP base.
Height: 1. 7 inches (43 mm) installed in B350LP base
Weight: 3.6 oz. (102 g).
Temperature: O - 49C (32 - 120 F).
Relative humidity: 10% - 93%, non-condensing.

Page 2 of 2 - DF-52158
.
June 25, 2001 DF-52167 E-700

H350/H350R
(2) Flr9LIT9 ALarms lntelligent Addressable Thermal (Heat)
Detectors for use with MS-9600

e
www.fire/ite.com Section: Addressable Devices

GENERAL
The H350 and H350R model thermal detectors are address 7270-0075: 195
able sensors that use a state-of-the-art thermistor sensing
circuit for fast response. These sensors are designed to pro

<8>
vide open area protection and are intended for use with the
MS-9600 tire alarm control panel.
Both the H350 and H350R sensors provide fixed tempera
ture alarm detection at 135F. The H350R sensor responds
to rate-of-rise conditions of greater than 15 F/minute.
Two LED's on each sensor light to provide a local, visible

... .........____...,i: ..
sensor indication. Remate LEO annunciator capability is avail
. .
... . !.
able as an optional accessory (Part No. RA400Z). ..

FEATURES ,. "'. ...


'

.
.... . ,,,,,,,,.,.
SLC Loop
Two-wire SLC loop connection.
Addressing
Addressable by device.
Oirect Oecade 01-159 (MS-9600) entry of address. -..""'....:......___.-/"
Architecture H350
Sleek, low-profile, stylish design.
State-of-the-art thermistor technology for fast repsonse.
Integral communications and built-in device-type identifica-
tion. APPLICATIONS

----
Built-in tamper resistan! feature. Use thermal detectors far protection of property.
Built-in functional test switch activated by externa! magnet.
Operation CONSTRUCTION
Factory preset at 135 F (58C). These detectors are constructed of Bayblend in an off-white
Rate-of-Rise model (H350R), 15F (8.3C) per minute. color.
360-field viewing angle of the visual alarm indicators (two The H350 and H350R plug-in intelligent thermal detectors
bicolor LEOs). LEDs blink green in Normal condition and are designed to commercial standards and offer an attrac
turn on steady red in Alarm. tive appearance.
Visible LEOs "blink" every time the unit is addressed.
Mechanicals INSTALLATION
Sealed against back pressure. The H350 and H350R plug-in intelligent thermal detectors
SEMS screws for wiring of the separate base. use a detachable base to simplify installation, service and
Oesigned for direct-surface or electrical-box mounting. maintenance. lnstallation instructions are shipped with each
Plugs into separate base for ease of installation and main detector.
tenance. Mount base (all base types) on box that is at least 1.5" (38.1
Separate base allows interchange of photoelectric, ioniza- mm) deep. Suitable boxes include:
tion and thermal sensors.
4" (101.6 mm) square box.
Other System Features
Remole test feature from the panel. 3 1/2" (88.9 mm) or 4" (101.6 mm) octagonal box.
Walk test with address display. Single-gang box (except relay or isolator base).
Low standby curren!.
94-SV plastic flammability rating. NOTE: Because of the inherent supervision provided by the
Options SLC loop, end-of-line resistors are not required. Wiring "T
Remate LEO output connection to optional RA400Z remate taps" or branches are permitted for Style 4 (Class "B") wiring
LEO annunciator. only.


Recessed (RMK400) or surface (SMK400) base mounting
kits.
Bayblend is a registered trademark of Bayer Corporation.

1 ISO 9001
This document is not intended to be used for instaliation purposes. We try to keep our
product information up-to-date and accurate. We cannot cover ali specific applica-
tions or anticpate ali requirements. Ali specifications are subject to change without
notice. Far more information, contact FireLite Alarms, One Fire-Lite Place, Northford, CERTIFIED
'-.__/
I
Connecticut 06472. Phone: (800) 627-3473, Tell Free FAX: (877) 699-4105, FAX ENGINEERINC& MANUFAClURING
Back:(888) 388-3299. Made in the U.S.A.
DF-52167 - Page 1 of 2
OPERATION
Each H350 or H350R uses one of 159 possible addresses
(MS-9600) on a control panel SLC loop. lt responds to regu
-..___./
lar polis from !he control panel and reports its type and !he
status. 11 it receives a test command from the panel (or a
local magnet test), it stimulates its electronics and reports an
alarm. 11 blinks its LEDs when polled and turns the LEDs on
when commanded by the panel . The H350 and H350R offer
features and performance that represen! the lates! in ther
mal detector technology.

SPECIFICATIONS
Diameter: 6.1" (155 mm) installed in B350LP.
Height: 2.0" (51 mm).
Weight: 5 oz. (150 gm).
lnstallation temperature: -4 to 100 F (-20 to 38 C).
Humidity range: 10% to 93% relative humidity (non-condens
ing).
Voltage range: 15 to 32 VDC peak.
Standby current: 300 A @ 24 VDC (one communication
every 5 seconds with LEO blink enabled).
LED current: 6.5 mA @ 24 VDC.
Mounting: B350LP flanged base.
Fixed Temperature setpoint: 135 F (57 C).
Rate of Rise detection: Responds to greater than 15 F/min.

PRODUCT LINE INFORMATION


H350 lntelligent thermal sensor (B350LP base in
cluded).
H350R Same as above with Rate-of- Rise feature.
RA400Z Remole LEO. Mounts to a single-gang box.
B350LP Plug-in detector base (included). Dimensions:
____,, 6.1" (155 mm. Mounting: 4" (102 mm) square
boxwith orwithout plastic ring, 4" octagon box,
3 1/2" octagon box or single gang box. Ali
mounting boxes have a mnimum depth of 1.5"
(38mm).
M02-04-00 Test magnet.
B224RB Plug-in System Sensor relay detector
base. Diameter: 6.2" (157 mm). Mounting:
4" (102 mm) square box with or without
plastic ring, 4" octagon box, 3 1/2" octagon
box. AII mounting boxes have a mnimum
depth of 1.5" (38 mm).
85018H Plug-in System Sensor sounder detector
base. Diameter: 6.0" (153 mm). Mounting:
4" (102 mm) square box with or without
plastic ring. Mounting box has a mnimum
depth of 1.5" (38 mm).

Page 2 of 2 - DF-52167
'-._./
e FlreUTe' ALarms
www.firelite.com
J uly 14, 2004

MMF-300(A) Series/MDF-300
Addressable Monitor Modules
Section: Addressable Devices
DF-52121 E-325

GENERAL California

<>
Four different monitor modules are available for FireLite
State Fire
Alarm's MS-9200, MS-9200UO and MS-9600 intelligent tire h

@
alarm control panels to suit a variety of applications. Moni ;; ;,s 185
tor modules are used to supervise a circuit of dry-contact
input devices, such as conventional heat detectors and pul!
stations, or monitor and power a circuit of two-wire smoke
detectors (MMF-302). APPROVED
MMF-300 (Replaces MJOO) - The MMF-300 Moni USTED
tor Module is a standard-sized module (typically mounts to a
4" (101.6 mm] square box) that supervises either a Class A
csxxxx
(Style O) or Class B (Style B) circuit of dry-contact input de
vices.
MMF-301 (Replaces M301)-The MMF-301 is a Min
iature Monitor Module (a mere 1.3" (33.02 mm) H x 2.75"
(69.85 mm) W x 0.5'' (12.70 mm) O) used to supervise a
Class B (Style B) circuit. lts compact design allows the
MMF-301 to be mounted in a single-gang box behind the
device it is monitoring.
MMF-302 (Replaces M302) - The MMF-302 lnter
f-ace Module is a standard-sized module used to monitor and
supervise compatible two-wire, 24 volt, smoke detectors on
a Class A (Style O) or Class B (Style B) circuit.
MDF-300 (New) - The MOF-300 Dual Monitor Module
is a standard-sized module (typically mounts to a 4" [101.6
mm] square box) that supervises two Class B (Style B) cir
'-.._./ cuits of dry-contact input devices.
MMF-300 MONITOR MODULE
MDF-300
Built-in type identification automatically identifies this de
vice as a monitor module to the control panel.
Oevice Circuit. A 47K ohm End-of-Line Resistor (provided)
Powered directly by two-wire SLC loop. No additional terminates the Style B circuit. No resistor is required for
power required. supervision of the Style O circuit. Maximum IOC resistance
High noise (EMF/RFI) immunity. is 1,500 ohms.
SEMS screws with clamping plates for ease of wiring. MMF-300 Operation - Each MMF-300 uses one of
Oirect Oecade 01 - 99 (MS-9200 and MS-9200UO) and 99 (MS-9200 and MS-9200UO) or 159 (MS-9600) avail
01-159 (MS-9600) entry of address. able module addresses on an SLC loop. lt responds to
LEO flashes red during normal operation and latches regular polis from the control panel and reports its type
on steady to indicate alarm. and the status (open/normal/short) of its lnitiating Oevice
The MMF-300 Monitor Module is intended for use in intel Circuit (IOC). A flashing LEO indicates that the module is
ligent, two-wire systems, where the individual address of in communication with the control panel. The LEO latches
each module is selected using the built-in rotary switches. steady on alarm (subject to current limitations on the loop).
lt provides either a two-wire or four-wire Class A or Class MMF-300 Specifications
B fault-tolerant lnitiating Oevice Circuit (IOC) for normally
Nominal operating voltage: 15 to 32 VOC.
open-contact fire alarm and supervisory devices. The MMF-
300 can be used to replace M300 modules in existing sys Maximum current draw: 5.1 mA (LEO on).
tems. Average operating current: 400 A (LEO flashing).
MMF-300 Applications - Use to monitor a zone of EOL resistance: 47K ohms.
four-wire smoke detectors, manual fire alarm pull stations,
Temperature range: 32 F to 120 F (O C to 49 C)
waterflow devices, or other normally-open dry-contact alarm
activation devices. May also be used to monitor normally Humidity range: 10% to 93% noncondensing.
open supervisory devices with special supervisory indica Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
tion at the control panel. Monitored circuit may be wired as 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
an NFPA Style B (Class B) or Style O (Class D) lnitiating x 2.125" (53.975 mm) deep box.

ISO 9001
FireLite Alarms is a Honeywell company.
T his document is not intended to be used fer installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticpate all
requirements. AII specifications are subject to change without notice. CERTIFIED
'-..-/
Fer more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. ENGINIEBING I MANUFACTUBING
Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. QUALITY SYSTEMS
DF-52121 07/14/04 - Page 1 of 3
MMF-301 MINI MONITOR MODULE MMF-302 INTERFACE MODULE
Built-in type identification automatically identifies this Supports compatible two-wire smoke detectors.
'-..-/
device as a monitor module to the MS-9200, MS- Supervises IOC wiring and connection of externa! power
9200UO or MS-9600. source (resettable).
Powered directly by two-wire SLC Loop. No additional High noise (EMF/RFI) immunity.
power required. SEMS screws with clamping plates far ease of wiring.
High noise (EMF/RFI) immunity Oirect-dial entry of address (01-99 far MS-9200/MS-
Tinned, stripped leads far ease of wiring. 9200UO, 01-159 far MS-9600).
Oirect-dial entry of address (01-99 far MS-9200/MS- LEO flashes during normal operation.
9200UO, 01-159 far MS-9600) LEO latches steady to indicate alarm on command from
The MMF-301 Mini Monitor Module can be installed in a control panel.
single-gang junction directly behind the monitored unit. lts The MMF-302 Interface Module is intended far use in intel
small size and light weight allow it to be installed without ligent, addressable systems, where the individual address
rigid mounting. The MMF-301 is intended far use in intelli of each module is selected using built-in rotary switches.
gent, two-wire systems where the individual address of This module allows intelligent panels to interface and moni
each module is selected using rotary switches. lt provides tor two-wire conventional smoke detectors. lt transmits the
a two-wire initiating device circuit far normally-open-con status (normal, open, or alarm) of one full zone of conven
tact tire alarm and security devices. The MMF-301 can be tional detectors back to the control panel. AII two-wire de
used to replace M301 module in existing systems. tectors being monitored must be UL compatible with the
module.

1 MMF-302 Applications - Use the MMF-302 to moni

1:
2
tor a zone of two-wire smoke detectors. The monitored cir

;D cuit may be wired as an NFPA Style B (Class B) or Style O

_lfl
10 s i s (Class A) lnitiating Oevice Circuit. A 3.9 K ohm End-of-Line
98 76 98 76
Resistor (provided) terminates the end of the Style B or O
TENS ONES (class B or A) circuit (maximum IOC loop resistance is 25

rLII ohms). lnstall ELR across terminals 8 and 9 far Style O


application.
MMF-302 Operation - Each MMF-302 uses one of
1 159 available module addresses on a MS-9600 SLC loop.
lt uses one of 99 on a MS-9200 or MS-9200UO. lt responds
to regular polis from the control panel and reports its type

u
11 . and the status (open/normal/short) of its lnitiating Oevice
'--._/
Circuit ( IOC). A flashing LEO indicates that the module is
in communication with the control panel. The LEO latches

o steady on alarm (subject to current limitations on the loop).


MMF-302 Specifications
Nominal operating voltage: 15 to 32 VOC.
MMF-301 Applications - Use to monitor a single Maximum current draw: 5.1 mA (LEO on).
device or a zone of faur-wire smoke detectors, manual fire
Average operating current: 270 A (LEO flashing).
alarm pull stations, waterflow devices, or other normally-open
dry-contact devices. May also be used to monitor normally EOL resistance: 3.9K ohms.
open supervisory devices with special supervisory indica Externa! supply voltage (between Terminals T3 and T4):
tion at the control panel. Monitored circuit/device is wired DC voltage: 18 to 28 volts power limited. Ripple voltage:
as an NFPA Style B (Class B) lnitiating Oevice Circuit. A 47K 0.1 VRMS maximum. Current: 90 mA per module maximum.
ohm End-of-Line Resistor (provided) terminales the circuit. Requires regulated, resettable 24 VOC power.
MMF-301 Operation - Each MMF-301 uses one of Temperature range: 32 F to 120 F (O C to 49 C)
159 available module addresses on an SLC loop MS- Humidity range: 10% to 93% noncondensing.
9600. lt uses one of 99 on a MS-9200 or MS-9200UO. lt
responds to regular polis from the control panel and re Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
ports its type and the status (open/normal/short) of its lni 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
tiating Oevice Circuit (IOC) x 2.125" (53.975 mm) deep box.
MMF-301 Specifications MDF-300 DUAL MONITOR MODULE
Nominal operating voltage: 15 to 32 VOC. Built-in type identification automatically identifies this de
Average operating current: 375 A maximum. vice as two monitor modules to the control panel.
EOL resistance: 47K ohms. Powered directly by the two-wire SLC loop. No addi
tional power required.
Temperature range: 32 F to 120 F (O C to 49 C)
High noise (EMF/RFI) immunity.
Humidity range: 10% to 93% noncondensing.
SEMS screws with clamping plates far ease of wiring.
Dimensions: 1.3" (33.02 mm) high x 2.75" (69 85 mm) wide Oirect-dial entry of address (01 - 159 on the MS-9600,
x 0.5" (12.70 mm) deep 01-99 for MS-9200/MS-9200UO)
Wire length: 6" (152.4 mm) mnimum. LEO flashes red during normal operation and latches
on steady red to indicate alarm.
'-..-/

Page 2 of 3 - DF-52121 07/14/04


--- -------- --

The MDF-300 Dual Monitor Module is intended for use in I ordinances and regulations.
inteliigent, two-wire systems, where the individual address
of each module is selected using the built-in rotary ARCHITECTS'/ENGINEERS'
-...___., switches. lt provides two independant two-wire fault-toler SPECIFICATIONS
ant lnitiating Device Circuits (IDCs) at two separate, con
secutive addresses. lt is capable of monitoring normally Specifications of these and ali F ireLite Alarms products
open-contact fire alarm and supervisory devices, or either are available from FireLite Alarms.
normally open or normaliy closed devices fer non-fire ap
plications.
PRODUCT LINE INFORMATION
MMF-300 Monitor Module.
MDF-300 Applications - Use to monitor a zone of
four-wire smoke detectors, manual fire alarm pull sta MMF-300(A) Monitor Module (Canada)
tions, waterflow devices, or other normally-open dry-con MMF-301 Mini Monitor Module.
tact alarm activation devices. May also be used to monitor MMF-301 (A) Mini Monitor Module (Canada).
normally-open supervisory devices with special supervi
MMF-302 Two-Wire Detector Monitor Module.
sory indication at the control panel. Monitored circuit may
be wired as an NFPA Style B (Class B) lnitiating Device MMF-302(A) Two-Wire Detector Monitor Module (Canada).
Circuit. The 47K ohm End-of-Line Resistors (provided) MDF-300 Dual Monitor Module.
termnate the Style B circuit. Maximum IDC resistance is SMB500 Optional Surface-Mount Backbox.
1,500 ohms.
MDF-300 Operation - Each MDF-300 uses two of 99
(MS-9200 or MS-92DOUD) or 159 (MS-9600) available MOUNTING DIAGRAM
module addresses on an SLC loop. lt responds to regular for standard-sized modules
polis from the control panel and reports its type and the
status (open/normal/short) of its lnitiating Device Circuit

1
(IDC). A flashing LEO indicates that the module is in com
munication with the control panel. The LEO latches steady
on alarm (subject to current limitations on the loop).
MDF-300 Specifications
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LEO on).
Average operating current: 750 A (LEO flashing)
EOL resistance: 47K ohms.
Maximum IDC wire resistance: 1,500 Ohms.
'---'
Temperature range: 32 F to 12D F (O C to 49 C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.
Accessories: SMB500 electrical box.

INSTALLATION
MMF-300, MMF-302 and MDF-300 modules mount di
rectly to a standard 4" (101.6 mm) square, 2.125" (53.975
mm) deep, electrical box. They may also be mounted to
the SMB500 surface-mount box. Mounting hardware and
installation instructions are provided with each module.
Ali wiring must conform to applicable local cedes, ordi
nances, and regulations. These modules are intended far
power-limited wiring only.
The MMF-301 module is intended to be wired and
mounted withot rigid connections inside a standard elec
trical box. Ali wiring must conform to applicable local cedes,

'- '

DF-52121 07/14/04 - Page 3 of 3


September 28, 2001 OF-52130 E-350

'---'.
(2) FlreUTe ALarms CMF and CRF Series
Addressable
Control and Relay Modules
www.firelite.com Section: Addressable Devices

<8>
GENERAL
CMF-300 Control Module (Replaces C304)
The CMF-300 Addressable Control Module provides
FireLite Alarm's MS-9200 and MS-9600 intelligent control Approved
panels a supervised Class B (Style Y) or Class A (Style Z)
circuit for Notification Appliances (horns, strobes, etc.).
Addressability aliows the CMF to be activated, either manu 730()-(XJ75:185

ally or through panel programming, on a select (zone or


area of coverage) basis.
CRF-300 Relay Module (Replaces C304
configured as a relay)
The CRF-300 Addressable Relay Module provides the
MS-9200 and MS-9600 systems with two isolated sets of
Form-C dry-contact outputs for activating a variety of auxil
iary devices, such as fans, dampers, door holders, con
trol equipment, etc. Addressability allows the dry contact
to be activated, either manually or through panel program
ming, on a select basis.

FEATURES
Built-in type identification automatically identifies these
devices to the control panel.
Interna! circuitry and relay powered directly by two-wire
SLC loop. The CMF module requires power (for horns,
strobes, etc.).
'---'' Integral LEO "blinks" green each time a communication
is received from the control panel and turns on in steady
red when activated. CMF-300 and CRF-300 Module
High noise immunity (EMF/RFI).
The CMF may be used to switch 24-volt NAC power.
OPERATION
Wide viewing angle ot LEO.
Each CMF or CRF uses one of 99 (MS-9200) or 159 (MS-
SEMS screws with clamping plates for wiring ease. 9600) possible module addresses on a SLC loop. lt re
Direct Decade 01-99 (MS-9200) and 01-159 (MS-9600) sponds to regular polis from the control panel and reports
entry of address. its type and status, including the open/normal/short sta
tus of its Notification Appliance Circuit (NAC). The LEO
APPLICATIONS blinks with each poli received. On command, it activates
The CMF is used to switch 24 VDC audible/visual power. its interna! relay. The CMF supervises Class B (Style Y) or
Tl1e CRF may be programmed to operate dry contacts for Class A (Style Z) notification or control circuits.
door holders, Air Handling Unit shutdown, etc.
Upon code command from the panel, the CMF wili discon
CONSTRUCTION nect the supervision and connect the externa! power sup
ply in the proper polarity across the load device. The dis
The tace plate is made of off-white Noryl.
connection of the supervision provides a positive indica
Controls include two rotary switches for direct-dial entry
tion to the panel that the control relay actually turned ON.
of address (01-99 on the MS-9200 and 01-159 on .the
The externa! power supply is always relay isolated from
MS-9600).
the communication loop so that a trouble condition on the
The CMF is configured for a single Class B (Style Y) or externa! power supply will never interfere with the res! of
Class A (Style Z) Notification Appliance Circuit. the system.
The CRF provides two Form-C dry contacts that switch
Rotary switches set a unique address for each module.
together.
The address may be set befare or alter mounting. The
built-in TYPE CODE (not settable) will identify the module
Noryl is a registered trademark of GE Plastics, a subsidiary of to the control panel, so as to differentiate between a mod
General Electric Company. ule and a sensor address.

ISO 900
This document is not intended to be used for installation purposes. We try to keep
our product information up-to-date and accurate. We cannot cover all specificl
applications or anticpate ali requirements. AII specifications are subject to change
without notice. For more information, contact FireLite Alarms, One Fire-Lite Place, CERTIFIE

-.._/
Northford, Connecticut 06472. Phone: (800) 627-3473, Toll Free FAX: (877) 699-I fNGINEERINli & MANUFACTURINGI
4105, FAX Back:(888) 388-3299. Made in the U.S.A.
DF-52130 - Page 1 ol 2
SPECIFICATIONS FOR CMF RELAY CONTACT RATINGS
Normal operating voltage: 15 to 32 VOC. for both CMF and CRF models
'-_/ Maximum current draw: 5.1 mA (LEO on). Load Description Application Maximum Current
Average operating current: 390 A (LEO flashing). Voltage Rating
Externa! supply voltage (between Terminals T3 and T4): Resistive Non-Coded 30VOC 3.0 A
maximum 80 volts (RMS or OC). Resistive Coded 30VOC 2.0 A
Drain on externa! supply: 2 mA maximum (using interna! Resistive Non-Coded 110VOC 0.9 A
EOL relay).
Resistive Non-Coded 125VAC 0.9 A
EOL resistance: 47K ohms.
lnductive (UR = 5 ms) Coded 30VOC 0.5 A
Temperature range: 32 F to 120 F (O C to 49 C).
lrductive (UR = 2 ms) Coded 30VOC 1.0 A
Humidity range: 10% to 93% non-condensing.
lrductive (PF = 0.35) Non-Coded 125VAC 0.5 A
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square G724rate.tbl

x 2.125" (53.975 mm) deep box.

SPECIFICATIONS FOR CRF


Normal operating voltage: 15 to 32 VOC.
Maximum current draw: 5.1 mA (LEO on).
Average operating current: 270 A (LEO flashing).
EOL resistance: not used.
Temperature range: 32 F to 120 F (O C to 49 C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide
x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square
x 2.125" (53.975 mm) deep box.

PRODUCT LINE INFORMATION


i
CMF-300 lntelligent Addressable Control Module.
CRF-300 lntelligent Addressable R elay Module.
SMBSOO Optional Surface-Mount Backbox.
..._____.
CBSOO Control Module Barrier - required by UL for
separating power-limited and non-power lim
i ted wiring in the s ame junct i on box as
CMF-300.

MOUNTING
DIAGRAMS
Note CB500 Module Barrier,
which creates isolated quadrant.

ISOLATEO
QUADRANT

4" (101.6 mm) square x 2.125" (53.975 mm) deep box


'-./

Page 2 of 2 - DF-52130
July 14, 2004 DF-52013 E-500

''-.....-'
@) Flr9LIT9" ALarms BG-12LX
Addressable Manual Pull Station
www.firelite.com Section: Addressable Devices

Patented, U.S. Patent No. D428,351; 61380,846


GENERAL U.S. Patent Pending: 09/686,286
The FireLite Alarms BG-12LX is a state-of-the-art, dual
action (i.e., requires two motions to actvate the station)
California
pull station that includes an addressable interface State Fire

c@us
(mounted inside) for FireLite's addressable MS-9200, MS- Marshal
9200UD, and MS-9600 fire alarm control panels. Because 7150-0075:184
the BG-12LX is addressable, the control panel can dis
play the exact location of the activated manual pull station.
USTED
<8> MEA
This leads tire service personnel quickly to the location of
the alarm.
67-02-E
FEATURES APPROVED
Aesthetically pleasing, highly visible, dual-action design.
Meets ADA 5 lb. maximum pull force.
Easily operated (dual-action).
Attractive shape and textured finish.
Mounts, semi-flush, to a standard single-gang (2.125"
[5.3975 cm] mnimum depth), double-gang, or 4" (10.16
cm) square electrical box.
When the handle latches in down position, the word "AC
TIVATED" appears at the top of the handle in bright yel
low to clearly indicate the station has been operated.
Key/lock reset; needs only a 1/4-turn to lock/unlock.
lncludes Braille text on station handle.
'---"' Captive screw terminals wire-ready for easy connection
to SLC loop (accepts up to 12 AWG/3.25 mm2 wire).
Optional trim ring (BG-TR).
Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
Maintenance personnel can open station (for inspection
and testing) without causing an alarm condition.
Built-in bicolor LEO, which is visible through the handle
of the station, flashes red in normal operation and latches
on steady red when in alarm.
BG-12LX
CONSTRUCTION
Shell, door, and handle are molded of durable LEXAN
(or polycarbonate equivalen!) with a textured finish. Manual stations connect with two wires to one of the con
trol panel SLC loops. Each manual station, on command
OPERATION from the control panel, sends data to the panel represent
Pushing in, then pulling down on the handle causes it to ing the state of the pull station switch. Two rotary decimal
latch in the down/activated position. Once latched, the word switches allow address settings (01-99).
"ACTIVATED" (in bright yellow) appears at the top of the
handle, while a portian of the handle protrudes from !he
PRODUCT LINE INFORMATION
bottom of the station. To reset the station, simply unlock BG-12LX Dual-action addressable pull station.
the station with the key and pull the door open. This action lncludes key lock/reset feature.
resets the handle; closing the door automatically resets SB-1/0 Surface backbox, indoor/outdoor.
the switch. SB-10 Surface backbox.
LEXAN is a registered trademark of GE Plastics,
a subsidiary of General Electric Company. BG-TR Optional trim ring.

ISO 9001
FireLite Alarms is a Honeyweli company.
This document is not intended to be used far instaliation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover ali specific applications or anticpate ali
requirements. Ali specifications are subject to change without notice. CEATIFIED
___,
Far more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. ENGINIERING & MANUFACTURING
Phone: (800) 627-3473, Toli-Free FAX: (877) 699-4105. QUAllTY SYSTEMS
DF-52013 07/14/04 - Page 1 of 2
INSTALLATION ARCHITECTURAL/
The BG-12LX can be semi-flush mounted into a single ENGINEERING SPECIFICATIONS
'-..._...,
gang, double-gang, or standard 4" (10.16 cm) square elec Manual Fire Alarm Statons shall be non-code, with a key
trical outlet box, or surface mounted to the Model SB-1/0 or operated reset lock in arder that they may be tested, and
SB-1 O surface backbox. lf the BG-12LX is semi-flush so designed that after actual Emergency Operation, they
mounted, then the optional trim ring (BG-TR) may be used. cannot be restored to normal except by use of a key. An
The BG-TR is usually needed for semi-flush mounting with operated station shall automatically condition itself so as
4" (10.16 cm) or double-gang boxes (not with single-gang to be visually detected as activated. Manual stations shall
boxes). be constructed of red-colored LEXAN (or polycarbonate
ELECTRICAL SPECIFICATIONS equivalen!} with clearly visible operating instructions pro
vided on the cover. The word FIRE shall appear on the
Normal operating voltage: 24 VDC. front of the stations in white letters, 1.00 inches (2.54 cm)
Maximum SLC loop voltage: 28.0 VDC. or larger. Stations shall be suitable for surface mounting
Maximum SLC loop current: 230 A. on matching backbox SB-1/0 or SB-1O; or semi-flush mount
ing on a standard single-gang, double-gang, or 4" (10.16
cm) square electrical box, and shall be installed within the
limits defined by the Americans with Disabilities Act (ADA)
or per national/local requirements. Manual Stations shall
be Underwriters Laboratories listed.
o = = = Manual stations shall connect with two wires to one of the
control panel SLC loops. The manual station shall, on com
mand from the control panel, send data to the panel re.pre
senting the state of the manual switch. Manual stations shall
provide address setting by use of rotary decimal switches.

ll TERMINAL
CONNECTIONS
1 SLC (-)
2 SLC (+)

'-.-/
o

fh). 1\
Back of station without door.
1
O A!Y)Rr:'.SS O
<_'.
1 1

.....,i 2 .

fD),
--....................
!j
!
. ,
1 !.
3 ::,..... ...........:, 3 /.,
4 . 1 4 t
, LOOP .
5 i . 5 f
9'a1 !L(}- 1 9s 1 f

evsev
..
6 s

= _ __)

1 ' ,_

m
1 r,,;;o s::i0,:1
[Wi'(Q)i:JJ jj]U)i]
----- ,------ ROTARYDECIMAL SWITCHES
... -- -
tz: of't.
'
<>

;-,
!;T l o .
.

:ro==-
1 ; . 4iCv'1i [,1
:;_ ,,,.,,.1 . ;
!- 1 1
j

(
1
----
--e,u1 1
\__ _::.:.::. :::== O-- l

Cover open to show easy access to the


..__,,, addressable interface module, rotary switch,
and UL /abe/.
Page 2 of 2 - DF-52013 07/14/04
July 14, 2004 DF-52389 E-940

'---''
(2) FlSUTe" ALarms 1300(A)
Fault lsolator Module
www.firelite.com Section: Addressable Devices

<
GENERAL California
State Fire
The FireLite Alarms 1300(A) Fault lsolator Module is Marshal
used with the MS-9200, MS-9200UD, and MS-9600 to pro 7300-0075 159
tect the system against wire-to-wire short circuits on the
SLC loop. The 1300(A) should be placed between each USTED CS68

<>
device on the SLC loop, to isolate a short-circuit problem S2424 ("A" suffix only)
between the modules. lt is required for true Style 7 opera (non "A" suffix)
tion so that other devices can continue to operate normally MEA
in the event of a short-circuit on the SLC. 3-94-E APPROVED
FEATU RES
Powered by SLC loop directly, no externa! power required.
Mounts in standard 4" (10.16 cm) square, 2.125" (5.3975
cm) deep junction boxes.
Integral LEO blinks to indicate normal condition. lllumi
nates steady when short circuit condition is detected.
High noise (EMF/RFI) immunity (:)

APPLICATIONS
The Fault lsolator Modules should be spaced between o
groups of sensors in a loop to protect the rest of the loop. CAUTlON; DE-NERGll.E
UNrT PRIOR TO SEIMCING
Use to isolate short circuit problems within a section of a
loop so that other sections can continue to operate nor
mally. The 1300(A) supports a maximum of 25 devices in
l

'-._../
between isolators, except when using relay bases.
NOTE ON LOADS PER RELA Y BASE
ANO /SOLATORSIJSOLA TOR BASES:
/300(A) I 0

__;---- 25 DEVICES-----4,______
_
1300(A) 1300(A)
or ISO or ISO
Base Base
detector module
The maximum number of addressable devices between isolators
(or 822481 isolator bases) is 25 devices.

8224 relay bases draw more curren! than other intelligent devices.
When ca/cu/ating the 25-device maximum, B224RB represents
2.5 DEVICES. See example on page 2.
NOTE ON MAXIMUM NUMBER OF SLC DEVICES: Each isola
tor module reduces the capacity of an SLC by two address posi
tions. Requirements differ as applied to relay bases (see note

Face plate for IJOO(A)

ISO 9001
FireLite Alarms is a Honeywell company.
This document is not intended to be used fer installation purposes. We try to keep our product informa
tion up-to-date and accurate. We cannot cover ali specific applications or anticpate ali requirements.
Ali specifications are subject to change without notice. CEATIFIED
'-../ For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. Phone: ENGINEEBINli I MANUFACTUBING
(800) 627-3473, Tell-Free FAX: (877) 699-4105. QUAllTY SYSTEMS
DF-52389 07/14/04 - Page 1 of 2
abo ve). condition when the short circuit condition is removed.

SPECIFICATIONS INSTALLATION
'---' Operating voltage: 15 - 28 VDC (peak) Mount on a standard 4" (10.16 cm) mounting junction
Maximum current upon activation due to short cir box which is at least 2.125" (5.398 cm) deep
cuit: refer to the manual for /he main FACP. Terminal screws are provided for "in and out" wiring.
Stand by current: 450 A maximum; 1300(A) is not iso lnstallation instructions are provided with each module.
lating - relay closed. Surface-mount box is available as an option.
Temperature range: 32 F to 120 F (O C to 49 C).
Relative humidity: 10% to 93%. ARCHITECTURAL/
Weight: 150 grams (5 oz.) ENGINEERING SPECIFICATIONS
Fault lsolator Modules shall be provided to automatically
CONSTRUCTION isolate wire-to-wire short circuits on an SLC loop. The Fault
The face plate is made of off-white plastic. lncludes yellow lsolator Module shall limit the number of modules or detec
LED indicator that pulses when normal and illuminates tors that may be rendered inoperative by a short circuit
steady when a short is detected. fault on the SLC Loop. lf a wire-to-wire short occurs, the
Fault lsolator Module shall automatically open-circuit (dis
OPERATION connect) the SLC loop. When the short circuit condition is
Automatically opens circuit when the line voltage drops be corrected, the Fault lsolator Module shall automatically re
low four volts. Fault lsolator Modules should be spaced be connect the isolated section of the SLC loop. The Fault
tween groups of addressable devices (maximum 25, see lsolator Module shall not require any address-setting, and
notes on page 1) in a loop to protect the res! of the loop. lf its operations shall be totally automatic. lt shall not be nec
a short occurs between any two isolators, then both isola essary to replace or reset an Fault lsolator Module after its
tors immediately switch to an open circuit state and isolate normal operation. The Fault lsolator Module shall mount in
the groups of sensors between them. The remaining units a standard 4" ( 10.16 cm) deep electrical box, in a surface
on the loop continue to fully operate. mounted backbox, or in the Fire Alarm Control Panel. lt
shall provide a single LED which shall flash to indicate that
In Style 4 loops, the 1300(A) is generally used at each T
the lsolator is operational and shall illuminate steadily to
tap branch, to limit the effect of short circuits on a branch
indicate that a short circuit condition has been detected
to the devices on that branch. The LED indicator is on con
and isolated.
tinuously during a short circuit condition.
The 1300(A) Fault lsolator Module automatically restares PRODUCT LINE INFORMATION
'---'
the shorted portian of the communications loop to normal 1300 lsolator module.
1300A lsolator module, ULC-Listed.
SMBSOO Optional surface-mount backbox.

EXAMPLE OF DEVICE COUNT


(see notes under Applications on page 1)

p l 1
STARTS
NEXTCOUNT
1300(A) ) 1, ) w 1300(A)
Module Module
detector with detector with module
standard base relay base

COUNTS AS ... 1 + 3.5


(2.5 + 1)
+ 1 5.5 @
(less than 25 total)

52389d2.wmf

Page 2 of 2 - DF-52389 07/14/04


July 15, 2004 DF-50961 F-951

....___,.
(2) F1re-ure ALarms PIBV2 and OSY2
Supervisory Switches

@
www.firelite.com Section: Conventional lnitiating Devices

California
GENERAL State Fire
The System Sensor PIBV2 and OSY2 are designed for Marshal
supervising abnormal conditions of water valves. Model 7770-1209:149
PIBV2 is a Post lndicator/Butterfly Valve Supervisory Switch.
Model OSY2 is an Outside Screw-and-Yoke Supervisory USTED CS169
Switch. S739
BSA MEA
<>
750-76-SA 427-91-E
FEATURES
Durable metal enclosure.
APPROVED
Weather resistance.
Easy installation.
OSY2 suitable for 1" through 12" valves.
The OSY2
PIBV2 for use on butterfly, post-indicator, and recessed
wall-post valves.
Switches locked in synchronized position.
Rugged terminal block accommodates up to 12 AWG
(3.25 mm2)
Two SPDT switches.
Single side conduit entry, easier to install.
sary plugs! Less expensive fittingsl

"'--"
Adjustable actuator(OSY2).
Security screws.
Tamper indicator option and key removal tools. 1:
\,
1/2" NPT adjustable nipple (PIBV2).

OPERATION
Both models will give a TAMPER INDICATION if removed TheP/BV2
from their mountings, or if the covers are removed (order
544-7000 Switch Kit).
Model PIBV2 mounted on a valve with the actuator arm
normally resting against the movable target indicator as
sembly. lf the normal position of the valve is altered, the CONSTRUCTION
valve stem moves, forcing the actuator arm to operate the Housing is die-cast metal, with a 1.5"(3.81 cm) tapped
switch. The switch will operate between the first and sec conduit entrance. Model OSY2 includes a mounting
ond revolution of the valve control wheel, when properly bracket.
installed.
Overall dimensions: 8.75"(20.955 cm) high x 3.5" (8 890
Model OSY2 mounts on an outside screw-and-yoke-type cm) wide x 3.75" (8.255 cm) deep
gate valve. The actuator normally rests in a recess drilled
Contact ratings: 10 A@ 125/250 VAC; 2.5 A@ 24 VDC
in the valve stem. lf the normal position of the valve is
(TBD).
altered, the valve stem moves forcing the actuator arm out
of the recess, and causing the switch to operate. The switch Operating temperature ranges: Ambient Air: 32 F to
will operate between the first and second revolution of the 120 F(O C to 49 C).
valve control wheel, when properly installed. Shipping weight: PIBV2: 2 lbs. (0.907 kg) OSY2 2.8 lbs.
(1 270 kg).

ISO 9001
This document is not intended to be used for installation purposes. We lry to keep our product
information up-to-date and accurate. We cannot cover ali specific applications ar anticpate ali

'--"
requirements. Ali specifications are subject to change without notice. Far more informalion,
contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticul 06472. Phone: (800) 627-
CERTIFIED
3473. Toll Free FAX: (877) 699-4105. FAX Back:(888) 388-3299
WEB: ww,.v.firelit8.com ENGINIEBll'f. & MANUFACTUING

DF-50961 07115104 - Page 1 of 2


_..--;r
Tampe r-Resistant
PIBV2 SCREWS

/
WRENCHfor
"..__/ TAMEP R SCREWS Tamper-Resistant
Screws (p/nWFDW)
4.25'
(88.90 mm) OSY2
Tamper-por of
WRENCH ASSEMBLED
(pinWFDW) r
SPRING
TERMINAL BLOCK
Actuating SEAL
ACTUATING CAM Lever
SETSCREW -BASE HOUSING
Actuating Lever
/ MOUNTING
7 <3-1/4" BRACKET
(82.55 mm)
......
,5-3/4"
'-../'
(146.05 mm) ,
ASSEM LED -RETA INING
CARRIAGE / WASHER
-RETAINING NUT
BOLT
...,/' Actuating Lever
HEX WRENCH - ROLLER
(pin HEXW)
/... (2' thru 12' only)
WIRING DIAGRAMS CLAMPING BAR
/
(slide bar to remove or install)

i-
To Power Source
Compatible Typical Local Bel/ Connection
WithBell

.....
Typica/ FACP Connection
TypicalLocal Bell Conneclion

'---------+-'-- l 1 J
Supervisory Switch Supervisory Switch
'----"
BREAK WIRE as shown for
End-01-Line supervision of connection.
Resistor DO NOT allow slrippe d
wire leads t o extend
beyond switch houslng.
Typical FACP Connection DO NOT loop wires.
APPLICATIONS
System Sensor Sprinkler Products are specifically de (1.905 cm) tapped conduit entrance and incorporate the
signed to meet the stringent performance requirements necessary facilities for attachment to the valve. A ground
of sprinkler and fire detection/alarm systems. ing provision is provided. The switch assembly shall in
elude two switches, each with a rated capacity of 1 O Amp
INSTALLATION @ 125/250 VAC and 2.5 Amp@ 24 VDC. The entire in
Both models are designed for ease of installation and stalled assembly shall be tamper-resistant. PIBV2 or
field maintenance. lnstallation instructions are packaged OSY2 shall be Underwriters' Laboratories lnc. listed for
with each switch. PIBV2(A) and OSY2(A) may be mounted indoor and outdoor use, and Factory Mutual approved.
with the actuator pointing DOWN or HORIZONTAL -
mounting the switch with the actuator pointing UP is PRODUCT LINE INFORMATION
NOT ACCEPTABLE. Mode/ Description
PIBV2 Post lndicator/Butterfly Valve supervisory switch
ARCHITECTURAL/ENGINEERING with two SPDT switches.
SPECIFICATIONS PIBV2A Post lndicator/Butterfly Valve supervisory switch
Post lndicator/Butterfly Valve Supervisory Switch (PIBV2) with two SPDT switches (avai/ab/e on/y in
or Outside ScrewAnd-Yoke Supervisory Switch (OSY2) Ganada).
shall be installed on each valve as designated on the draw OSY2 Outside Screw-And-Yoke supervisory switch
ings and/or as specified herein. Switches shall be mounted with a mounting bracket and two SPDT switches.
so as not to interfere with the normal valve operation and
shall be adjusted to operate within two revolutions of the OSY2A Outside Screw-And-Yoke supervisory switch
valve control or when the stem/valve flag has moved no with a mounting bracket and two SPDT switches
more than one-fifth of the distance from its normal posi (available on/y in Ganada).
_ ___., tion. The mechanism shall be contained in a weather 544-7000 Tamper kit for OSY2 or PIBV2.
proof die-casi metal housing, which shall provide a 3/4"
Page 2 of 2 - DF-50961 07/15/04
July 15, 2004 DF-50943 F-950

'--" (2) Fl9LIT9" ALarms WFD Series, Schedule 10/40


Waterflow Detectors, 1.0"-8.0 "

@@ '
www.firelite.com Section: Conventional lnitiating Devices
GENERAL
System Sensor WFD vane-type Waterflow Detectors de California

U LC /
tect the flow of water in wet pipe sprinkler pipes. The ,<_'. State Fire
Marshal
detectors provide a signal which can be used by fire
detection systems, fire control systems, and auxiliary lE:'J
f' 7770-1209:140
indicators when waterflow occurs. WFD Series detectors
are used for wetpipe sprinkler systems that use ferrous USTED CS16
(steel or black iron) piping, 1.0" (2 54 cm) lines and larger.
Models are available to fit both Schedule 1O and Schedule
S739
MEA
APPROVED
40 pipe, and for 1.0"(2.54 cm) and 1 5"(3 81 cm) copper
427-91-E
pipe systems. WFD sprinkler equipment products are
specifically designed to meet the stringent performance
requirements of sprinkler and fire detection/alarm sys
tems. The design of these devices emphasizes ease of
installation and field maintenance.

FEATURES
Sealed retard.
Visual switch activation.
Rugged switch assembly.
Heavy-duty aluminum pipe saddles.
Durable metal enclosure.
Rugged terminal block accommodates wires up to 12
AWG (3 25 mm2)
Three-year limited warranty.
Two SPDT synchronized switches.
Tamper-resistant assembly.
"-./ Optional tamper indicator.
Steel U-bolts provide secure mounting.
lmpact-resistant cover protects mechanism. When water stops flowing, the vane is no longer deflected
1.0" (2.54 cm) through 8 O" (20.32 cm) models available. and a spring draws the actuator arm of the linkage back
Schedule 10/40 pipe. against the stops on the pneumatic delay shaft, closing
Adjustable delay (O to 70 seconds). the switch levers and returning the device to its normal
condition. Observe switch activation with cover open.
SEMS clamping plate.
Water resistant. The pneumatic delay mechanism is adjustable within a
range of O to 70 seconds. lt incorporates an automatic,
Vertical or horizontal mounting. noncumulative reset to accommodate a sequence of surges
Adjustable pneumatic delay prevents false alarms due without acquiring an accumulated delay greater or less
to water surges. than the preset value. As shipped, the adjustment dial is
Serviceable without draining pipe. set for a delay of 20-30 seconds: but any value within the
Requires no power to operate sensing mechanism. O- to 70-second range can be selected in the field.
lmproved self-guiding security screws and removal tool. APPLICATIONS
Useful for watertlow rates up to 15 feet per second (4.57
WFDs are used in wetpipe sprinkler systems to signal
meters per second).
waterflow of 4 to 1 O GPM. The flow could be due to the
OPERATION opening of one or more sprinkler heads or test valves, or it
could be due to leakage or rupture of the piping
Water flowing in the pipe deflects the WFD's vane, which
operates a linkage to release the pneumatic delay shaft. By the appropriate choice of installation siles, the WFDs
The stop on the shaft then releases the switch levers at a can be used to signal general flow (installed in mains) or
rate determined by the presetting of the pneumatic delay flow by zones (installed in branch lines). Either horizontal
mechanism. When the shaft and its stops have pulled far or vertical pipes can be utilized.
enough away, the spring operated switch levers actuate Common usages of WFDs include operating a bell or
both SPDT switches, which each have NO and NC termi horn at the riser and signaling a control panel or master
nals that can be used to initiate an alarm or auxiliary box.
indication.

ISO 9001
FireLite Alarms is a Honeywell company.
This document is no! intended to be used for installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specific applications or anticpate all
requirements. AII specifications are subject to change without notice. CEATIFIED
.'-.../
For more information, contact FireLite Alarms, One Fire-Lite Place, Northford, Connecticut 06472. ENGINEEIING I MANUFAClURING
Phone: (800) 627-3473, Toll-Free FAX: (877) 699-4105. QUAllTY SYSTEMS
lf the WFDs are used at the upper limits of their tempera
ture ranges, especially at a 100% duty cycle, their working
Construction & Operation
life may be significantly shortened. ELECTRICAL:
"---.-/
CAUTION: The vane and linkage of the WFD can be Contact Ratings: 10 A@125 VAC, 2.5 A@24 VDC.
damaged by the sudden rush of water when /he control MECHAN/CAL:
va/ve opens. DO NO T use vane-type waterflow detectors Triggering Threshold Bandwidth (Flow Rate): 4 - 1 O
in drypipe sprink/er systems, deluge systems, or pre-ac GPM, mnimum.
lion systems. Use a pressure actuated detector on such
systems instead. Mechanical Delay Adiustment:
Dial Setting O 1 2 3 4 5
INSTALLATION Seconds (50%) O 15 30 45 55 70
The details of proper location and the method of installing Operating Temperature Ranges:
the detector on the pipe are contained in the installation
sheet packed with each detector. Briefly, a properly cen Ambient Air: 32 F to 120 F (O C to 49 C).
tered hole is made in the drained pipe. The edges of the System Water: 32 F to 1 OO F (O C to 43 C).
vane are squeezed together sufficiently to allow it to be Major Component Materials: aluminum saddle, steel u
inserted through the hole as the detector is set in place on bolt, cast aluminum mounting plate, epoxy painted
the pipe A U-bol! clamps the saddle of the detector metal cover, polyethylene vane.
against the pipe, sealing the 0-ring around the hole to
preven! leakage and securing the detector in place. Loop Overall Dimensions, lnstalled (HWD):
wiring is connected to the switches as appropriate. (P.D. +3.5" H) x (P.D. +3.0" W) x (6.7" D).
Tamper-resistant screws hold the cover in place over the Ambient Air Compatible Pipe: Steel water pipe, Sched
mechanism to protect the device. ule 10/40 (copper models available).
Static Pressure Rating: 250 PSI maximum (2.0" - B.O").
Shipping Weight: Vares from 4 lbs. to 7 lbs. ( 1. 81 to 3.17

l
kg.) according to size.
Tamper-proofwrench Cover
(PIN WFDW) ENGINEERING SPECIFICATIONS
Vane-Type Waterflow Detectors shall be installed on sys
tem piping as designated on the drawings and/or as
specified herein. Detectors shall mount on any clear pipe
L_ span of the appropriate nominal size, either a vertical or
4-_ l. horizontal run, at least 6.0" (15.24 cm) from any fittings or
valves which may change water direction, flow rate, or
Switch enclosure pipe diameter, or no closer than 24" (60.96 cm) to a valve
(Replacement or drain. The detector shall respond to waterflow in the
--..._/
P/N A77-01-02)
specified direction after a preset time delay which is field
Delay mechanism
(Replacement
adjustable. The actuation mechanism shall include a
PIN A3008-00) polyethylene vane inserted through a hale in the pipe and
connected by a mechanical linkage to the delay mecha
entrence nism. Outputs shall consist of 1 O A (Dual SPDT Switches/
Form-C Contacts). A conduit entrance for standard fit
tings of commonly used electrical conduit shall be pro
U-boll nut vided on the detectors. Ali detectors shall be listed by

WDF Size Hole Size


2 to 3-1/2 1-1/4 in.
U-bolt
4 to 8 2 in.

'-...../

WFD2"8"
Page 2 of 2 - DF-50943 07/15/04
PRODUCT LINE INFORMATION
MODEL DESCR/PTION
'----" WFD20 WFD Waterflow Detector, Schedule 10/40 2 O" (5.08 cm).
WFD20A Same as above (Ganada).
WFD25 WFD Waterflow Detector, Schedule 10/40, 2.5" (13.97cm).
WFD25A Same as above (Ganada).
WFD30 WFD Waterflow Detector, Schedule 10/40, 3 O" (7.6 cm).
WFD30A Same as above (Ganada).
WFD30-2A Samw as WFD30 (Ganada).
WFD35 WFD Waterflow Detector, Schedule 10/40, 3.5" (8.89cm)
WFD40 WFD Waterflow Detector, Schedule 10/40, 4 O" (10.16cm).
WFD40A Same as above (Ganada).
WFD50 WFD Waterflow Detector, Schedule 10/40, 5 O" (1270cm)
WFDSOA Same as above (Ganada).
WFD60 WFD Waterflow Detector, Schedule 10/40, 6.0" (15.24cm)
WFD60A Same as above (Ganada).
WFD80 WFD Waterflow Detector, Schedule 10/40, 8 O'' (20.32cm).
WFD80A Same as above (Ganada).
WFDT WFD Waterflow Detector, FITS: 1" (2 54 cm), 1.75" (445 cm), 1.50" (3.18 cm) ferrous and brass lhreaded lees;
10"(2.54 cm), 1.75" (4.45 cm), 150"( 3.18 cm), 2.0"(5.08 cm) copper sweal lees; 10"(2 54 cm) GPVG lees; and
1 50"(3 18 cm) poly-butylene lees.
546-7000 Tamper Switch Kit for WFD Detectors.
A3008-00 Timer Assembly for Waterflow Detectors, 2 0"(5.08 cm) to 8 0"(20.32 cm) sizes. Black.
A77-01-02 Terminal block.
WFDW Tamper-Proof Wrench for metal cover (WFD Detectors and WFDT).
WFDN4 NEMA-4 gasket kit for WFD Series.

'--..../

'--"

DF-50943 07/15/04 - Page 3 of 3


March 30,2000 G-250

"---"'' @) F1reuTe ALarms SpectrAlert TM Series


Horns, Strobes, and Horn/Strobes

@
Section: Audio/Visual Devices

GENERAL
System Sensor SpectrAlert Series strobes,horns, and combina S4011 & S5512 (P1215, P121575, P2415,
tion horn/strobes are UL listed for primary signaling in lile safety P241575, P2475, P24110). S5512 (S1215,

@
systems and meet ADA public mode visible signaling requirements. S121575,S2415,S241575,S2475, S24110).
SpectrAlert products can be connected to the alarm indicating cir USTED S4011 (HC12/24).
cuit of a tire alarm control panel and are compatible with DC line
supervision. The SpectrAlert product line mounts to standard CS549 (P2415A,P241575A,P2475A,P24110A,
backboxes using a universal mounting plate included with each unit. S2415A,S241575A, S2475A,S2411DA).
An optional small footprint mounting plate fits to a single-gang box. CS548 (H12/24A,HC12/24A).
An accessory backbox skirt gives a cosmetic finish to a 4" x 4" x

1-1/2" or a 2" x 4" x 1-7/8" surface-mounted backbox. Ali strobe OB8A4.AY (P1215,P121575, .,..
and horn/strobe mounting options require only one screw attach P2415,P241575,P2475,P24110,
ment of product to plate. S1215,S121575,S2415,S241575,
These products are designed for 12 and 24 VDC and full-wave rec S2475,S24110, H12/24). OD4A7.AY (HC12/24).
tified unfiltered power. Full-wave rectified operation requires more
curren! than DC operation. For detailed curren! draw information, 7135-1209:173 (P1215,P121575,P2415,
consult the Curren! Draw Tables (page 2). The horn/strobe com P241575,P2475,P24110).
bination products are factory-assembled with jumper wires for in 7125-1209:174 (S1215,S121575,
tandem operation. For independent wiring o! horn and strobe, re S2415,S241575,S2475,S24110).
move jumper wires. When wired for independent operation, the California 7135-1209:143 (H12/24,HC12/24).
State Fire

MEA
strobe will continue to run while the horn can be silenced. How Marshal
ever, the strobe must be running for horn to operate. 319-96-E (P1215,P121575,
P2415,P241575,P2475,
Horns - The SpectrAlert Series horns and horn/strobes pro
P24110,S1215,S121575,
vide two difieren! field-selectable/reversible tones,a high-low field
S2415,S241575,S2475,
selectable/reversible sound output setting (low setting on 24-volt
S24110,H12/24,HC12/24).
models only) and a field-selectable/reversible temp 3 pattern or
'--" non-temporal continuous pattern. These field-selectable features
are accomplished using pins and jumpers located on the back of
each SpectrAlert horn and horn/strobe. An accessory module is
not needed to make these field selections. The horn on horn/strobe
models will operate on a coded power supply. Those horn-only
models with "HC" in their part numbers wi/1 a/so operate on a
coded power supply. The horn and horn/strobe series includes
weatherproof models.
Strobes - The ADA-compliant SpectrAlert strobes are elec
tronic visible warning signals that flash at 1 Hz over their operating
voltage range. These products are available in 24-volt models at
15, 15/75, 75 and 1 1 O candela intensities and in 12-volt models at
15 and 15n5 candela intensities. The strobe series includes weath
erproof models. SpectrAlert products feature dramatic reductions
in curren! requirements.
SyncCircuit Module (MDL) - The SyncCircuit Mod
ule is available for synchronization of strobes and horns and can .!;

synchronize two Style Y (class B) circuits or one Style Z (class A) o,


o
circuit. The module can also generate a synchronized temp 3 tone ;;;
for System Sensor's Multi-Alert and PA400 horn products.* The
synchronization module allows the SpectrAlert horns on combina
tion horn/strobes to be silenced on two-wire systems. SpectrAlert's
SyncCircuit Module can be daisy-chained for multiple zone syn
chronization. The module does not operate on a coded power sup
ply.
'For Multi-A/ert and PA400: Strobes must be wired to a continuous SpectrAlert , SyncCircuit , and Multi-Alert are trade
source of power (non-coded power supply). marks o! System Sensor, a division o! Pittway Corporation.

ISO 9001
This document is not intended to be used far installation purposes. We try to keep our product
information up-to-date and accurate. We cannot cover all specillc applications or anticipate all
requirements. Ali specificalions are subject to change without notice. Far more information,
contact FireLite Alarms, One Fire-Ute Place, Northford, Connecticut 06472. Phone: (800) 627-
'---"' CERTIFIED
3473, Toll Free FAX: (877) 699-4105, FAX Back:(888) 388-3299
WEB: www.firelite.com ENGINEERINC & MANUFACTURING

DF-51609 - Page 1 of 6
FEATURES Single-gang mounting without the use of a mounting plate
(horn model only).
24-volt sirobe models: 15, 15/75, 75 and 11O candela.
Self-contained screw covers.
12-volt strobe models: 15 and 15/75 candela.
'-..._.,,,' Aesthetically pleasing design.
Horn models operate on 12 and 24 volts.
Synchronize horn and strobe with SyncCircuit module
Low curren! draw: reductions as high as 45%. (MDL).
Two field-selectable/reversible horn tones:
Silence horn on horn/strobe over a single pair of wires using
- 3000 Hz interrupted - electromechanical a SyncCircuit module (MDL).
Field-selectable/reversible high-low dBA output on horn 'Sound output vares with tone and output options setected; sound
(low output on 24-volt models only): /evels based upan anechoic room measurements.
- 101 peak dBA@ 10 ft. high output.*
- 96 peak dBA @ 1 O ft. low output: SPECIFICATIONS
Field-selectable/reversible temp 3 pattern or non-temp 3 con- Input terminals: 12 to 18 AWG (3.25 mm2 to 0.51 mm2).
tinuous pattern on horn.
Dimensions: see diagrams page 3.
Horn/strobe can be wired either in tandem or independently.
Weight, horn only: 7.2 oz. (204 g).
Weatherproof strobes, horns, and horn/strobes available.
Horns for use with coded power supply available. Weight, strobe and hornlstrobe: 8.8 oz. (250 g).
Universal mounting plate included with each unit. Mounting: see diagrams page 4.
One-screw mounting of strobe and horn/strobe to mounting Operating temperature: 32 F to 120 F (O C to 49 C).
plate. Operating voltage range:** 12 V: 10.5 - 17 V. 24 V: 20 - 30
SpectrAlert strobe and horn/strobe take up no room in !he v.
backbox. *' These products shou/d be operated within their rated voltage
range. UL does, however, test functional integrity to -20% and
+ 10% of manufacturer's stated ranges.

CURRENT DRAW TABLES


Strobe Only
AVERAGE CURRENT (mA) PEAK CURRENT (mA) IN RUSH CURRENT (mA)
I.t 2.fiM.- 12VModela 24YModell 12VMI 24V Modela
10.5V 12V 17V 20V 24V 30V 10.SV 12V 17V 20V 24V 30V 10.sv 12V 17V 20V 24V 30V
Candela OC FNR oc FWR OC FWR OC FWR OC FWR OC FWR DC FWR DC FWR DC FWR DC fWR DC FWR OC FWR DC FWR DC FWR OC FWR oc FWR DC FWR oc fWR
15 133 159 114 157 81 128 59 120 53 80 46 79 460 '60 450 '60 420 480 150 270 150 270 140 250 80 108 92 124 140 190 170 230 220 280 270 370
15175 168 162 142 171 99 150 76 92 66 93 56 132 490 520 490 520 '60 460 170 270 170 270 160 270 76 104 68 126 160 185 170 230 210 270 270 360
75 NA NA NA NA NA NA 145 170 123 159 102 141 NA NA NA NA NA NA 350 440 340 4(1() 330 480 NA NA NA NA NA NA 190 240 230 280 290 380

110 NA NA NA NA NA NA 169 220 140 191 115 174 NA NA NA NA NA NA 460 560 450 570 420 620 NA NA NA NA NA NA 190 230 220 290 290 370

Horn Only
AVERAGE CURRENT (mA)
J2VModela 24VModal
High/Low Temp 10.SV 12V 17V 20V 24V 30V
Tone Volume /Non OC FWR DC fWR OC FWR DC fWR OC FWR DC FWR
Electro- High Temo 10 11 10 10 14 14 19 21 25 16 29 2
meeh. Non 10 16 10 19 14 25 17 29 23 34 30 4
low Tomo NA NA NA NA NA NA 11 12 13 13 17 1!
Non NA NA NA NA NA NA 12 16 14 19 17 2
3000 Hz High Tomo 11 13 11 11 16 16 24 26 26 23 37 S!
lnterrupt. Non 11 17 11 21 14 28 19 34 27 39 35 4!
low Temo NA NA NA NA NA NA 14 14 17 15 21 1
Non NA NA NA NA NA NA 13 16 16 21 22 2

Horn/Strobe - 15 cd Horn/Strobe - 75 cd
AVERAGE CURRENT (mA) AVERAGE CURRENT (mA)
12VModell I 1ZV Model.l i
Hlgh/Low Temp 10.SV 12V 17V 20V 24V 30V High/Low Temp 10.SV 12V 17V 20V 24V 30V
Tone Volume /Non DC FWR OC FWR OC FWR OC FWR DC FWR OC FWR Tone Volume /Non OC FWR DC FWR OC FWR OC FWR DC FWR OC FWR
Electro- High Temo 143 170 124 167 95 142 76 101 76 96 75 141 Electro- High Temo NA NA NA NA NA NA 164 191 148 167 131 167
mech. Non 143 170 124 167 95 1-42 69 98 76 100 76 138 meeh. Non NA NA NA NA NA NA 163 1fl8 1-46 169 132 169
Low Temo NA NA NA NA NA NA 70 92 66 93 63 132 Low Teme NA NA NA NA NA NA 156 162 136 162 119 156
Non NA NA NA NA NA NA 71 92 67 93 63 132 Non NA NA NA NA NA NA 157 182 137 162 119 157
3000 Hz High Temn 144 172 125 166 97 1-44 63 106 81 103 63 148 3000Hz High Temo NA NA NA NA NA NA 169 196 151 172 139 174
lnterrupt. Non 144 173 125 168 95 146 78 102 80 100 81 142 lnlerrupt. Non NA NA NA NA NA NA 164 192 150 175 137 1n
Low Temo NA NA NA NA NA NA 73 94 70 95 67 "" Low Temn NA NA NA NA NA NA 159 164 140 164 123 180
Non NA NA NA NA NA NA 72 92 69 94 68 132 Non NA NA NA NA NA NA 158 188 139 163 124 162

Horn/Strobe - 15/75 cd Horn/Strobe - 11 O cd

Tone
Hlgh/Low
Volume
Tomp
/Non
10.SV
12VModA
12V
AVERAGE CURRENT (mA)

17V 20V
24V Modela
24V
OC FWR OC FWR OC FWR OC FWR oc IFWR DC FWR
30V
Tone
High/Low
Volume
Temp
/Non
10.SV 12V
AVERAGE CURRENT (mA)
12VModal!
17V
DC FWR DC FWR oc fWR
20V
DC FWR
24V
OC FWR
30V
DC FWR
Electro- High Temo 176 193 152 181 113 164 95 113 91 l 111 87 153 Eleciro- Hlgh Temo NA NA NA NA NA NA 168 241 165 209 144 200
mech. Non. 176 193 152 181 113 164 93 110 891113 68 150 mech. Non NA NA NA NA NA NA 166 236 163 211 145 202
Low Tema NA NA NA NA NA NA 87 104 791 106 75 14,4 Low Temo NA NA NA NA NA NA 180 232 153 204 189
132
Non NA NA NA NA NA NA 68 104 801106 75 144 Non NA NA NA NA NA NA 181 232 154 204 132
190

....._, 3000 Hz
lnterrupt.
Hlgh

Low
Temn
Non
Temo
179 195 152 183 115 166 100 118 94 l 116 95 158
179 196 152 183 113 168 95 11'4 93 l 119 93 154
NA NA NA NA NA NA 90 106 631108 79 ,
3000 Hz
lnterrupt.
High

Low
Temn
Non
Temn
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
193 246 166 214
188 2-42 167 217
163 234 157 206
207
152
150
210
136 193
Non NA NA NA NA NA NA 89 104 621107 60 144 Non NA NA NA NA NA NA 182 232 156 205 137 195

Page 2 of 6 - DF-51609
ENGINEERING SPECIFICATIONS Horn/Strobe Combination - Horn/strobe shall be a
System Sensor SpectrAlert model listed to UL 1971
General - SpectrAlert horns, strobes and horn/strobes
and UL 464 and shall be approved for tire protective service.
1 shall be capable of mounting to a standard 4" x 4" x 1-1 /2" Horn/strobe shall be wired as a primary signaling notification
(10.16 x 10.16 x 3.81 cm) backbox or a single-gang 2" x 4" x appliance and comply with the Americans with Disabilities Act
1-1/2" (5.08 x 10.16 x 3.81 cm) backbox using the universal
requirements for visible signaling appliances, flashing at 1 Hz
mounting plate included with each SpectrAlert product. Also, over its entire operating voltage range. The strobe light shall
SpectrAlert products, when used in conjunction with the ac consist of a xenon flash tube and associated lens/reflector
cessory SyncCircuit Module, shall be powered from a non system. The horn shall have two tone options, two audibility
coded power supply and shall operate on 12 or 24 volts. 12-
options (at 24 volts) and the option to switch between a tem
volt rated devices shall have an operating voltage range of poral 3 pattern and a non-temporal continuous pattern. Strobes
10.5 - 17 volts. 24-volt rated devices shall have an operating shall be powered independently of the sounder with the re
voltage range of 20 - 30 volts. SpectrAlert products shall have moval of factory-installed jumper wires. The horn on horn/
an operating temperature of 32 F to 120 F (O C to 49C) and strobe models shall operate on a coded or non-coded power
operate from a regulated DC or full-wave rectified, unfiltered
supply.
power supply.
Module - Module shall be a System Sensor SyncCircuit
Horn - Horn shall be a System Sensor SpectrAlert model model listed to UL 464 and shall be approved for
____ capable of operating at 12 and 24 volts. Horn shall tire protective service. The module shall synchronize
be listed to UL 464 for tire protective signaling systems. The SpectrAlert strobes at 1 Hz and horns at temporal 3. Also, the
horn shall have two tone options, two audibility options (at 24 module shall silence the horns on horn/strobe models, while
volts) and the option to switch between a temporal 3 pattern operating the strobes, over a single pair of wires. The module
and a non-temporal continuous pattern. The horn-only model shall be capable of mounting to a 4-11/16" (119.0625 mm)
shall NOT operate on a coded power supply except those square x 2-1/8" (53.975 mm) deep backbox and shall control
models (model numbers contain "HC") designed to do so. two Style Y (class B) or one Style Z (class A) circuit. Module
Strobe - Strobe shall be a System Sensor SpectrAlert shall be capable of multiple zone synchronization by daisy
model listed to UL 1971 and be approved for fire chaining multiple modules together and resynchronizing each
protective service. The strobe shall be wired as a primary other along the chain. The Module shall NOT operate on a
signaling notification appliance and comply with the Americans coded power supply.
with Disabilities Act requirements for visible signaling appli
ances, flashing at 1 Hz over the strobe's entire operating volt
age range. The strobe light shall consist of a xenon flash tube
r- 2-15/16" -ll>I
( 74.6125 mm) '
-.
15/16"
3.8125 m;;,r-
t
and associated lens/reflector system.

+-=l I JtJ
1
'-...../ DIMENSIONS
5-5/16" ,

1----1-'-,,-,
, 3-3/8" (134.9375 mm)
'-(85.725 mm)-1

l-ifF' ]i
1

1 - --
!_ :
T .j
1 111
@
-"'-+-
l
-"'-
1

1
',c . . . 1
Wi

1 I=--=-ii- , = 5-518"
1-5/16" ,./"'i

":!:.I ?)
1

(33.3375 mm)
1

1 ,-=-
11 (142.875 mm)
1
1

J1
lf J 1_!_ 1
1
UPPER LEFT: Horn/Strobe with Small Footprint Mounting
Plate (same dimensions for strobe only).
LOWER LEFT: Horn/Strobe with Universal Mounting Plate
(same dimensions far strobe only).

-1 UPPER RIGHT: Horn only (may be mounted with either

r( r_i
(58.7375 mm)

=r1--1 r
Sma/1 Footprint or Universal Mounting Plate).
2-15/16"-- ' LOWER RIGHT: SyncCircuit Module (MDL).
r (74.6125 mm)
(
1
-

lI
1
-f=-=----Zi:
Q_--
z ..
1_=
:..e=
1

OUTER: 5-5/8"
--.- -
-

Ir;==
5-1/4" (133.35 mm)--

====Jr==-=i11

1P

1
)

J
o:

t=T"' ;;E;:;{1" 5-1/4" -1 1


rL. lluf 11 L
(133.35 mm)
1
1 ! 1 i
c 1
1

I
1 1

1 ]
1

I
_,,==--.:_- .--=t= - J'C2J
-
- 2-5116" ' o
0
...___.,
(127 mm) (58.7375 mm)
0,-
1

-- 5" -- 1
__T.
__
1
1

DF-51609 - Page 3 of 6
4" x 4" x 1-1/2" backbox Horn Surface Mount

()O OJ ---
MOUNTING DIAGRAMS
2" x 4" x 1-7/8" backbox ;'! : ;j:.?
Horn k

\]t3l 91--

e ]1 t--j - ------ - t-1?\


-:--BBS e

\....J

f{1--- nJ- ;;:::


'.
.}. 110'1 1,_-. ....:
1 -. 11 "l:C.
Q-J./:---
e
. }
= "::.;? ------ --
- w --- ----- -
Q,
T


,r.,.., --
.
-o-
V - -a,,:.,
,_.,__;; ""-.o
-

. =q.SJ ,.:,KG- --=-- --<---


-1,
-- -

'_-,;_.l.-- --- .

- - t
==2 , ""-J.-:.

D-MP-- Horn with Universal Mountin: Plate


. ,,
"' (included with each product)
l. l
i \"' (1
Gj ,;<:
:ij11

"'- r?-co;_ 1, ..
(
- --- . --:: ;J"\
T 2" x 4" x 1-7/8" backbox
y 0:
11

- ._J' _
11 _,,.__----_ " - --
--
4" X 4" X 1-1/2"
backbox ;(.,_{l- id
L---
-- - - .
'""'.$ 111 .L
4 x 4" 1-1/2" backbox '--------:J

l-1! -.---

1
'r
1\)1
rCT1 ---- ---
1 l ,
_,JI
Oj
t
" ....\ ._.j
?-y ''''";..,
ei, fl.---<!,
Stro e or Horn/Strob e with
Universal Mounting Plate
(included with each product)
T
..
Strob e or Horn/Strob e
with accessory
l\'I !
\);
.

].
i

,Wi,:-,'=)> -. :-. --=.. .


I[ t;,:ce:-
Small Footprint
Mounting Plate
-- - - _.. Jt) JJ
. . -.,h
. --
11
-----

e1 <1, .. ,i
'-;?!

. L"-j
'---
4" x 4" x 1-1/2' backbox

srol -o' rD- -(---:1 ... _ _


4-11/16" X 4-11/16" X 2-1/8" (
...

,(
backbox
,--<--... _

p l
(119.0625 x 119.0625 x 53.975 mm) -:::::-- e>-
-- '<

tl,l1(1 . : -
/ -----=-'-

e
----: - - .,:---
- -'-
--i
F-1:
J __ - O:}
..
0 r--===--- - ---
.. --=- b 11.;J
..:.-- """':', .---'t'-. r. ,;.,)
-:,
11, ,; [ I '-- ___- _ Q------ ,

),?'
'.. --
-
Strob e or Horn/Strob e Surface Mount
[!
'

SyncCircuit Modul e Direct Mount


with acce ssory Backbox Skirt
.

SOUND OUTPUT GUIDE (dBA)


UL Reverberant Room dBA@ Volts DC Anechoic Room Peak dBA@ 10 ft./VDC
10.5 12 17 20 24 30 10.5 12 17 20 24 30
LOW Electromechanical NA NA NA 75 75 79 NA NA NA 94 96 98
TONE 3000 Hz lnterrupted NA NA NA 75 79 79 NA NA NA 94 96 98
Electromechanical
Temporal
75 75 79 82 82 82 94 95 98 100 101 102
TONE 3000 Hz lnterrupted
HIGH
75 75 79 82 85 85 94 95 98 100 101 102
LOW Electromechanical NA NA NA 79 82 85 NA NA NA 94 96 98
TONE 3000 Hz lnterrupted NA NA NA 82 82 85 NA NA NA 94 96 98
Electrome chanical
Non-
Temporal 79 79 85 85 88 88 94 95 98 100 101 102
TONE 3000 Hz lnterrupted
\"--'"' HIGH
79 82 85 88 88 90 93 95 98 100 101 102
Page 4 of 6 - DF-51609
WIRING DIAGRAMS
NOTE: Do NOT loop wires under terminal screws. lndependent Operation
'-.J
Tandem Operation FACTORY
HORN AND STROBE

INSTALLED HORNS
JUMPER WIRES
HO N/STROBE BO "'(-)
REMOVED

IQNEXT {<(-)
(+)

HORN
IQ NEXT
<-J.
OR EOL NOTE: Slrobes must be

DEVICE {( +
< + --1-----,

./
( ) powered for hom operat/on.

OR EOL IQNEXT
@2:J

, .I . ..- A 1 - -- EBQM FACP,


. 1 (-) FROM FACP,
.)<
(-
STROBES
@ STROBE {
. MODULE OR <----- M ODULE OR
. J . } PREV/OUS OR EOL
EJ

( ) PREVIOUS
----e-:::

___ , l '. DEVICE


FACTORY +

DEVICE
/NSTALLED (+) -:::
JUMPERS - ()
(-) NOTE: Break wire as shown
<-- for supervision of connection.
DO NOTallow slripped wire
leads to extend beyond switch
-------i HORN HORNISTROBE STROBE ONLY housing. DO NOT loop wires.

00
+
( _)_
( +

LA
')
[]'
(+
1
1
LJ
J L H H
(-) 1-)
)
(-) (-) )
__J ..
1,, -
Two-wire system, any mix of models,

jg
wired for TANDEM OPERATION. (+ -Q+
[]
(-) 1 (- )
T Horns silenced over two-wire circuit. M

-,_, 1
i RJ
L_J .
Any mix of horn/strobes or strobe-only devices is

L_, .
acceptable.
I s s
Horn control connects to interruptible power
source.
l lc- .
w} {c1:.I
MO D ULE1
FACP;;
...___/ l HORN ZONE1
o -, Four-wire system, combo models,
CONTROL OUT -1

i+
TONEXT
1 1
1 SpectrAlert
wired for INDEPENDENT OPERATION.
{l1.f
DEVICE
( ) 11} ZONE 1 DREDL (Horn can be tumed off at the panel

3
+ ZONE2
;
NAC - 1-1 IN OOT
(j > while strobes continua to opera/e.)
{?i

( )
r=
+
( ) -- \ ZONE 2
} TROUIIL.E
. ' lj IN (j

1- . ' ; ?,} SI.AVE


IN
SLAVE
OUT
{:; T Temp 3 coding of Multi-Alert
and PA400 sounders .
1,
..

r:-::mJ
TEMP JUMPR OFF
NOTE: Strobes must be powered from non-coded
1

1.if1J {-)} 2., {f.:t=Jr>


supply.
1

FACP ,2
ODUL

1 ?, HO.: :
1-
MO D ULE 1

{fi
1 CONTROL OUT
TONEXT

}
+U+ Spec:trAlert

ttl} -- i
1 -{)
HOAN
1 I
1
1 1 v
O CONTROL z

2
) 1 g g 1


FACP
:;
ZONE 1 ZONE2
NAC (; I I
- ,:T -u II
1:1 IN OUT {H

1
( )-+-' 1

M l
ONE1 ZON

8
NAC1 1 }
: 01:
1
{ffi
o-
O 1
2}z
oNE2

l
l 1

l
IN n,ouB LE{t"J

{
TONEXT .
?, I' l SpeclrAlert

{
,- HORN ONLY NA } il,"""' TAOU8LE M

} .
> DEVICE
i'l SLAVE SLAVE g--r_.-, I OREOL

[!] {
IN OUT H
::___J
->

"' }
o - 1
{) SU.VE SI.AVE (l
T<MP JUMPER Ali SpectrA/ert lN OUTtJ

'-----
homs, homlstrobes,
and strobes wllf __J 1
1 1 1 Homs willbe
1 TEMP. JUMPER O N temporaf-coded
opera/e in sync.
and in sync.

DIAGRAM NOTES:
1) Any mix o! SpectrAlert horn/strobe, strobe-only, or horn
only devices is allowable for Zone 1.
2) No devices or horn-only are allowed on Zone 2. 11 no de
...___/ vices are installed on Zone 2, termnate EOL resistor al
horn control terminal.
DF-51609 - Page 5 ol 6
o-
.........
F avg. mA*@ avg. mA*@
.. .
.\ RED WHITE volta ge candela
nom. VDC nom. FVvR
P1215 P1215W 12 15 124 167
'-.__,/ P121575W 12 15/75 152 181
Horn/Strobes P121575
P2415 P2415W 24 15 78 98
P241575 P241575W 24 15/75 91 111
P2475 P2475W 24 75 148 167

o P24110
P241575K (weatherprooQ
P24110W
-
24
24
110
15/75
165
91
209
111

z P2475K (weatherprooD
P24110K (weatherprooD
-
-
24
24
75
110
148
165
167
209

z-
P2415A P2415WA 24 15 78 98
P241575A P241575WA 24 15/75 91 111
P2475A P2475WA 24 75 148 167
Canadian Models, P24110A P24110WA 24 110 165 207
H orn/Strobes
P241575KA (weatherprooD - 24 15/75 91 111
P2475KA (weatherprooD - 24 75 148 167
P24110KA (weatherprooD - 24 110 165 209
Spanish Labeling, H/S P241575F (FUEGO) 24 15/75 91 111

o Strobes
S1215
S121575
S2415
S1215W
S121575W
S2415W
12
12
24
15
15/75
15
114
142
53
157
171
80
S241575 S241575W 24 15/75 66 93
S2475 S2475W 24 75 123 149
S24110 S24110W 24 110 140 191
S241575K (weatherprooQ - 24 15/75 66 93
S2475K (weatherprooD - 24 75 123 159
S2411OK (wealherprooD - 24 110 140 191
S2415A S2415WA 24 15 53 80
'-._/ S241575A S241575WA 24 15175 66 93
S2475A S2475WA 24 75 123 149
Canadian Models, S24110A S24110WA 24 110 140 191
Strobes
S241575KA (weatherprooQ - 24 15/75 66 93
S2475KA (weatherprooD - 24 75 123 149
S24110KA (weatherprooD - 24 110 140 191
Spanish Labeling, Strobes S241575F (FUEGO) 24 15/75 66 93
H12/24 H12/24W 12/24 NA 12 / 23 12 / 21
H12/24K (weatherprooD - 12/24 NA 12 / 23 12 / 21
Horns
HC12/24 (coded power) HC12/24W (coded power) 12/24 NA 12 / 23 12 / 21
HC12124K (weatherproof, - 12/24 NA 12 1 23 12 / 21
for code d power)
H12/24A H12124WA 12/24 NA 12 / 23 12 / 21
-
Accessories ..... H12/24KA (wealherprooD
HC12/24A (coded p ower) HC12/24WA (coded power)
12/24
12/24
NA
NA
12 / 23
12 / 23
12 / 21
12 / 21
MOL MOLW 12/24 NA 16 24
SyncCircuit Module
MOLA MOLWA 12/24 NA 16 24
Small Footpnt Mounting S-MP S-MPW NA NA NA NA
Plate for Single-Gang ONLY

Surface-Mount Backbox Skirt BBS BBSW NA NA NA NA


Universal Mounting Plate
0-MP 0-MPW NA NA NA NA
(replacement)

Weatherproof Backbox WBB - NA NA NA NA


NOTES: 1) Canadian model numbers end in "A". 2) Latin American model numbers end in "F". 3) AII weatherproof models must
use weatherproof backbox model WBB. 4) AII SpectrAlert products are designed for wall-mount only. 5) lnstallation of less than 75
candela strobes may be permissible under the equivalent facilitation clause of the ADAAG (Sec. 2.2). However, it is the responsibility
of the person or entity designing the fire alarm system to determine the acceptability of less than 75 candela strobes. 6) AII 15/75
'-.__,/
candela strobes or horn/strobes are recommended far 20' x.20' rooms or less. 'For a complete listing of SpectrAlert curren/ require
ments, please refer to the Curren/ Oraw tables on page 2 of this document, or the lnstruction Manual. Horn and hornlstrobe curren/
draws assume the horn is set at Temp 3, electromechanical tone, and high audibility.
Page 6 of 6 - DF-51609