3/2 Directional control valves


Actuation: electromagnetic
Directly controlled poppet valves
Port size: G 1/4, 1/4 NPT or
Connection hole pattern NAMUR
Solenoid: Category II2GD, Type of Protection EEx a IIC
T5/T6, IP66, T95C, Suitable for zones 1, 2 (gases) and
21, 22 (dusts)

Working from 0 bar up

High operational reliability even after long periods of


inoperation

Suitable for control and instrument-quality air

Also suitable for open-air installation with appropriate


solenoid variant

NAMUR FLANGE:
With integrated exhaust air recirculation
Add-on manual override
Wide range of mounting options

Solenoid valve also suitable for low power consumption


in non hazardous areas without barrier

TV-approval based on IEC 61 508, DIN V 19


251Approvals: DIN EN 161/3394 DVGW, group Rm and
EN 13611 Valves for safety systems to SIL 4 or AK 7 Ordering information
3/2 directional control valve, connection G 1/4,
housing brass, with protection class
EEx ia IIC T6
Type: 2401088.2003
Technical data
Medium:
For neutral gaseous and liquid fluids*
*With contaminated fluids, upstream installation of a dirt trap is recommended.
Operation:
Electromagnetic, directly-controlled 2
Flow direction: a a b b
Optional
Mounting position: 1 3
Any, but preferably with solenoid vertical
3 2 NAMUR flange
Connection:
G 1/4, 1/4 NPT
12
Operating pressure:
0 to 10 bar
Temperature: 3 1 2
-25* to +60C
*Please consult our technical service for use below +2C. If installed in the open
protect all connections against the penetration of moisture!
Materials:
Housing: Brass, hard-anodised aluminium
Seals: NBR (Perbunan)
Internal parts: Stainless steel, brass
Solenoid housing: Aluminium, anodized

Our policy is one of continued research and development. We therefore reserve the right
5/04 to amend, without notice, the specifications given in this document. N/UK 5.4.309.01
24010

General information
Switching function: Pressure connection 1, 2 or 3
Symbol Type Port size Operating *1) kv-value Material Dimensional Weight without Special features
pressure (bar) (Cv(US) kv x 1,2) Housing Seal drawing solenoid (kg)
2401088.2003 G 1/4 0 to 10 0.340 Brass NBR M01 0.65
2
a a 2b b 2401087.2003 1/4 NPT 0 to 10 0.340 Brass NBR M01 0.65
a a b 2401086.2003 G 1/4 0 to 10 0.340 St. st. NBR M01 0.65
1 b
3
1 3 2401012.2003 1/4 NPT 0 to 10 0.340 St. st. NBR M01 0.65
3 2
3 2 2401091.2003 G 1/4 NAMUR 0 to 10 0.340 Aluminium *2) NBR M02 0.55
12 2401090.2003 1/4 NPT NAMUR 0 to 10 0.340 Aluminium *2) NBR M02 0.55
12
2401009.2003 G 1/4 NAMUR 0 to 10 0.340 Aluminium *2) NBR M03 0.55 P port in flange
3 1 2
interface
3 1 2

*1) With gaseous and liquid fluids up to 40 mm2/s


*2) Hard-anodised
Note: At an ambient temperature of -20C, higher leakage values may be experienced for short periods.

Solenoid parameters for use in intrinsically safe circuits


Switch-on max. allowed Holding Holding Pick-up delay typical Categorie, Temperature Type
voltage (V) current Ii current voltage (s) type of protection Ambient/Fluid C
22...28 V 110 mA min 40 mA 5V 0,3 - 5 II2G EEx ia IIC T6 -40...+55 2003
II2G EEx ia IIC T5 -40...+70
II2D IP66 T95C -40...+70

Solenoid parameters for use in non harardous locations


Switch-on max. current Holding Power Pick-up delay typical IP Code Temperature Type
voltage (V) (limited) current consumption (s) Ambient/Fluid C
(switching
and holding)
22...26,4 V 75 mA min 40 mA 1,8 W at 24V 0,3 - 2 s IP 66 -40...+80 2003

Accessories
Flange plate Yoke

0612790 (NAMUR sigle connection plate) 0540593


0612791 NAMUR-rip use in combination with 0612790 (Alu)

Warning
These products are intended for use in industrial compressed air The system designer is warned to consider the failure modes of all
systems only. Do not use these products where pressures and component parts used in fluid power systems and to provide adequate
temperatures can exceed those listed under Technical Data. safeguards to prevent personal injury or damage to equipment in the
event of such failure.
Before using these products with fluids other than those specified, for
non-industrial applications, life-support systems, or other applications System designers must provide a warning to end users in the
not within published specifications, consult NORGREN. system instructional manual if protection against a failure mode
Through misuse, age, or malfunction, components used in fluid cannot be adequately provided
power systems can fail in various modes. System designers and end users are cautioned to review specific
warnings found in instruction sheets packed and shipped with these
products.

Our policy is one of continued research and development. We therefore reserve the right
N/UK 5.4.309.02 to amend, without notice, the specifications given in this document. 5/04
24010

Operating sequence

28 V V mA

25 120
22 V
Supply

20 100

15 75 80
60
10
40
5 20
Off 0 V 0
Time 0

V mA

25 120
20 100
Voltage curve

15 75 80
60
10
40
5 20
0 0
Time

mA

120
Current curve

100
75 80
60
40
20
0
On Time
Valve

Off Time

Current supply units (exerpt from list) Function of solenoid drive


Intrinsically safe power supply units can To switch the direct operated valve, a certain energy
be choosen in a list of compatibility in is required. This energy is stored in a condenser.
www.norgren.com
The charging voltage is 22 V. The higher the supply
voltage, the shorter the charging time. As soon as the
When selecting an intrinsically safe power supply, it is charging voltage has been reached, the valve switches.
important to observe the maximum permissible values acc. The small current now flowing through the coil is
to the EC-Type-Examination Certificate PTB 04 sufficient to hold the valve in the open position.
ATEX 2010 At least 40 mA are required for this.
Ui 28 V, Li 110 mA, Pi 1,5 W
The effective internal capacities Ci; and inductivities Li
of the solenoid are negligibly low.

Our policy is one of continued research and development. We therefore reserve the right
5/04 to amend, without notice, the specifications given in this document. N/UK 5.4.309.03
24010

Dimensional drawings
M01
70,5
?
98

1
51

2
35.7

12
3 1 Pg 11
12.2

12
2 For port size see
general information
5.5 30 3 3 deep
27 1 2
4 Add-on manual override
55

M02 122 70,5

29 50
?

7,5
?

3
M5

13,5
5,5

3
15

G 1/4
37,5
12

1
24

52

19,5
15,5
G 1/4
26,5

19

2
1 2
13
4,5

G 1/4 22,5 6,5 16


19 4 6,5 32 17
4 50
22

M03 122 70,5

29 50
?

7,5
?

3
M5

13,5
5,5

3
15

G 1/4
37,5
12

1
24

52

19,5
15,5
10
M6
26,5

2
1,5 1 2
13
4,5

G 1/4 22,5 6,5 16


19 6,5 32 17
4 50
22

Our policy is one of continued research and development. We therefore reserve the right
N/UK 5.4.309.04 to amend, without notice, the specifications given in this document. 5/04
24010

Add-on manual override Screw plug


Without detent With detent
Type: 0600205 Type: 0601765 Type: 0602764

Filter cartridge (for threads G 1/4 and 1/4 NPT) Circuit diagram
Type: 0681173

4
3
1,5

10,5

13
8,5

60

5
60
Thread pitch diameter
max. 11,85 mm

NAMUR hole pattern


32
M5 4 1 Pilot air, only in valves with
Remark p port in flange interface
2
1 2 Port 2 (A)

3 Coding stud threaded


2

1 4
4
24

M5 (10 deep)
2 3 5 Port 3 (R)

3 6 External air supply, only in valves with


Remark p port in flange interface

5 6

Our policy is one of continued research and development. We therefore reserve the right
5/04 to amend, without notice, the specifications given in this document. N/UK 5.4.309.05