Você está na página 1de 9

Medium Voltage Product

TPU 6x.xx
Indoor supporting current transformers
Technical parameters Value Rated secondary currents
5 A; 1 A, others on request (possibility to combine different
Highest voltage for equipment 24 up to 25 kV
values in one transformer)
Power frequency test voltage, 1 min. 50 up to 55 kV

Lighting impulse test voltage up to 125 kV Accuracy classes


0.2; 0.2S; 0.5; 0.5S; 1; 3; 5; 5P10; 5P15; 5P20; 10P10;
Rated primary current 10 - 3 200 A
10P15; 10P20; others on request.
Rated short-time thermal current 2 - 1001s kA

Burdens, classes 5-30/0.2-5/5P; 10P VA/cl


Rated frequency
(acc. to other param. - Ith)
50 Hz or 60 Hz, others on request

Reconnectable (primary till 400-800 A) primary or secondary


The transformers are designed and manufactured in confor-
mity with the following standards and recommendations: IEC,
VDE, ANSI, BS, GOST and CSN, others on request.
Description
The TPU 6x.xx transformers are cast in epoxy resin and Cantilever strength
designed for insulation voltages up to 25 kV. The 24 kV ver- 5 kN
sion has the same dimensions as the 25 kV. For certain types
of panels there is a need for extra long creepage distance
on the transformers. For this purpose you can order current Permissable torques for screw connections
transformers with ribs on the top. The transformers are
manufactured in conformity with dimensions stated hereunder. M5 max 3.5 Nm min 2.8 Nm

The TPU 6x.xx transformers are designed as single-turn or M8 max 20 Nm min 16 Nm


multi-turn versions, with one transformer ratio or with double
M12 max 70 Nm min 56 Nm
ratio having the possibility to be reconnectable on the primary
or on the secondary side. The number of secondary windings
(from 1 to 6 max. 12 secondary terminals - 2 rows), de-
pends on the combination of the technical parameters (such
as the accuracy class, burden, short-circuit current, overcur-
rent factor) and the transformer dimensions size.

When agreed between the manufacturer and the customer the


TPU transformers can be provided with the voltage indication
system. For this purpose, however, it is necessary to know
in what insulation level the transformers shall operate. The
secondary windings are used for measurement or protec-
tion purposes, or for special use (testing winding, X class
windings). One terminal of each secondary winding used and
one terminal of short-circuited and not used winding have to
be earthed during the transformer operation. The secondary
windings are lead out into a cast-type secondary terminal box
with plastic cover. The terminal cover is sealable. The termi-
nals are provided with M5 screws for the termination and with
throughgoing holes for direct earting (first row of secondary
terminals).

Technical data

The transformer can be mounted in any position. The trans-


former body is fixed by using four screws. Earth clamp M8 is
on the transformer base plate.

Rated primary voltages


24 kV; 25 kV

Rated primary currents


10; 15; 20; 25; 30; 40; 50; 60; 75; 100; 150; 200; 300; 400;
500; 600; 750; 1 000; 1 250; 1 500; 2 000; 2 500; 3 000 and
3200 A; primary reconnectable modification max till 400-800A.
Other primary currents can also be agreed upon with the
customer.

2 TPU 6x.xx | Indoor supporting current transformers


Code designation - TPU current transformers

TPU 4 x . x x

voltage current dimension primary terminals

6.up to 25 kV 0 to 600 A multiturn 1..short 178 mm, DIN 1..no pr.rec., no ribs /40x80mm, 80x80mm/
3to 1 250 A singleturn 2..long 178 mm, DIN 2..prim. rec., no ribs /40x80mm, 80x80mm/
4to 1 500 A singleturn 3..no pr.rec., with ribs /60x68mm, 80x80mm/
5to 2 000 A singleturn 4..prim. rec., with ribs /40x80mm, 80x80mm/
6to 2 500 A singleturn 5..no pr.rec., with ribs /40x80mm, 80x80mm/
7to 3 000 A singleturn
8to 3 200 A singleturn

Marking of current transformer outlets - example

a) b) c)

d) e) f)

a) Single-core design | b) Double-core design | c) Three-core design | d) Single-core design, reconnectable on the secondary side | e) Double-core design,
reconnectable on the secondary side | f) Double-core design, reconnectable on the primary side

Standartized insulation levels of TPU 6x.xx transformers

24/50/125 kV
25/50/125 kV
25/55/125 kV

Fig. 1. 1 Secondary terminal box Fig. 2. 2 Secondary terminal box


(3 secondaries and voltage indicator) (2 secondaries and grounding screw)

TPU 6x.xx | Indoor supporting current transformers 3


Standartized transformers

Type Ithn/dyn Ratio Burden Class FS/ALF Type Ithn/dyn Ratio Burden Class FS/ALF
[kA] [A] [VA] [kA] [A] [VA]
60.11 6.3/16 20//5 10 5P 15 60.11 50/125 300//5/5 15/15 0.5/5P FS5/15
60.11 6.3/16 20//5 20 5P 10 60.11 40/100 400//5 30 5P 15
60.11 6.3/16 20//5/5 15/15 0.5/5P FS5/10 60.11 40/100 400//5/5 15/15 0.5/5P FS5/15
60.11 12.5/31.5 20//5 10 5P 15 60.11 50/125 400//5 15 5P 15
60.21 12.5/31.5 20//5/5 15/15 0.5/5P FS5/5 60.11 50/125 400//5/5 15/15 0.5/5P FS5/15
60.21 16/40 20//5 15 5P 15 60.11 50/125 500//5 30 5P 10
60.21 16/40 20//5/5 10/10 0.5/10P FS5/10 60.11 50/125 500//5/5 15/15 0.5/5P FS5/15
60.11 6.3/16 30//5 15 5P 15 60.11 50/125 600//5 30 5P 10
60.11 6.3/16 30//5 20 5P 10 60.11 50/125 600//5/5 15/15 0.5/5P FS10/15
60.11 6.3/16 30//5/5 15/15 0.5/5P FS5/15 61.11 50/125 400//5 10 5P 15
60.11 12.5/31.5 30//5 10 5P 15 61.11 50/125 400//5/5 10/10 0.5/5P FS5/10
60.11 12.5/31.5 30//5 20 5P 10 62.11 50/125 600//5 15 5P 15
60.21 12.5/31.5 30//5/5 15/15 0.5/5P FS5/10 62.11 50/125 600//5 20 5P 10
60.21 25/63 30//5 10 5P 15 62.11 50/125 600//5/5 15/15 0.5/5P FS5/10
60.21 25/63 30//5 15 5P 10 63.11 50/125 750//5 15 5P 15
60.21 25/63 30//5/5 10/10 0.5/5P FS5/10 63.11 50/125 750//5 30 5P 10
60.11 6.3/16 50//5 15 5P 15 63.11 50/125 750//5/5 15/15 0.5/5P FS5/10
60.11 6.3/16 50//5 30 5P 10 63.11 63/160 1 000//5 10 5P 20
60.11 6.3/16 50//5/5 15/15 0.5/5P FS5/10 63.11 63/160 1 000//5 20 5P 15
60.11 16/40 50//5 10 5P 15 63.11 63/160 1 000//5 30 5P 10
60.11 16/40 50//5 30 5P 10 63.11 63/160 1 000//5/5 15/15 0.5/5P FS5/10
60.21 16/40 50//5/5 15/15 0.5/5P FS5/15 63.11 63/160 1 250//5 15 5P 15
60.11 31.5/80 50//5 10 5P 15 63.11 63/160 1 250//5 30 5P 10
60.21 31.5/80 50//5 30 5P 10 63.11 63/160 1 250//5/5 15/15 0.5/5P FS5/15
60.21 31.5/80 50//5/5 15/15 0.5/5P FS5/10 64.11 63/160 1 500//5 15 5P 15
60.11 16/40 100//5 15 5P 15 64.11 63/160 1 500//5 30 5P 10
60.11 16/40 100//5/5 15/15 0.5/5P FS5/15 64.11 63/160 1 500//5/5 15/15 0.5/5P FS5/15
60.11 31.5/80 100//5 15 5P 15 65.11 80/200 2 000//5 15 5P 20
60.11 31.5/80 100//5/5 15/15 0.5/5P FS5/10 65.11 80/200 2 000//5 30 5P 15
60.11 31.5/63 200//5 15 5P 15 65.11 80/200 2 000//5/5 15/15 0.5/5P FS5/15
60.11 31.5/63 200//5 30 5P 15 66.11 100/250 2 500//5 15 5P 20
60.11 31.5/63 200//5/5 15/15 0.5/5P FS5/15 66.11 100/250 2 500//5 30 5P 15
60.11 40/100 200//5 15 5P 15 66.11 100/250 2 500//5/5 30/30 0.5/5P FS5/15
60.11 40/100 200//5 30 5P 10 67.11 100/250 3 000//5 15 5P 15
60.11 40/100 200//5/5 15/15 0.5/5P FS5/10 67.11 100/250 3 000//5 30 5P 20
60.11 31.5/80 300//5 15 5P 15 67.11 100/250 3 000//5/5 30/30 0.5/5P FS5/15
60.11 31.5/80 300//5 30 5P 10 68.11 100/250 3 200//5 15 5P 15
60.11 31.5/80 300//5/5 15/15 0.5/5P FS5/15 68.11 100/250 3 200//5 30 5P 20
60.11 50/125 300//5 15 5P 15 68.11 100/250 3 200//5/5 30/30 0.5/5P FS5/15
60.11 50/125 300//5 30 5P 10

4 TPU 6x.xx | Indoor supporting current transformers


Dimensional Drawing

TPU 60.11 Weight: 31-35 kg TPU 60.12 Weight: 31-35 kg


TPUTPU 60.11
63.11 Creepage distance: 270
WEIGHT: mm
31-35kg
TPU 60.12 Creepage distance: 282 mm
TPU 63.11 CREEPAGE DISTANCE: 270mm WEIGHT: 31-35kg
CREEPAGE DISTANCE: 282mm

282
282

2
2

280
280
Pg16 14
Pg16 14
M8
M8

39
22

20
39
22

20

173 160

4
173 160
4

195
195
32 120 32
32 120 32
14

23 23 23

14
14
14
150

150
178
96

40

39,5
150

150
178
96

23
19
20 19

33,5 17

80 M12 80,5 M8 M12


10 275 20 10 275 20
355 355

Drawing n. Polarity Drawing n. Polarity


44615000 P1 to secondary terminal 44615020 P1 to secondary terminal
44615010 P2 to secondary terminal 44615030 P2 to secondary terminal

TPU 60.13 Weight: 31-35 kg TPU 60.14 Weight: 31-35 kg


TPUTPU 60.13
63.13 Creepage distance: 280
WEIGHT: mm
31-35kg TPU 60.14 Creepage distance: 282 mm
WEIGHT: 31-35kg
TPU 63.13 282
CREEPAGE DISTANCE: 280mm CREEPAGE DISTANCE: 282mm
282
264 264
2
2

340
340

280
280

Pg16 14 Pg16 14
M8
M8
39
39

22

20
22

20

173 160
4

173 160
4

195
195
32 120 32
32 120 32
14

23 23 23
14

14
14
150

150
178
96
86

60

39,5
150

150
178
96
86

23

19 19

18 33,5 17

68 M12 80,5 M8 M12


10 275 20 10 275 20
355 355

Drawing n. Polarity Drawing n. Polarity


44615040 P1 to secondary terminal 44615060 P1 to secondary terminal
44615050 P2 to secondary terminal 44615070 P2 to secondary terminal

TPU 6x.xx | Indoor supporting current transformers 5


TPU 60.15 Weight: 31-35 kg TPU 60.21 Weight: 43-49 kg
TPU 60.15 WEIGHT: 31-35kg
TPU 63.15 Creepage distance: 280 mm TPU 63.21
TPU 60.21 Creepage distance:
WEIGHT:270 mm
TPU 63.15 CREEPAGE DISTANCE: 280mm 43-49kg

282
TPU 63.21 CREEPAGE DISTANCE: 270mm

382

2
340
280

280
Pg16 14 Pg16 14
M8
M8
39
22

20

39
22

20
173
4

195 160 173 260

4
195
32 120 32 14
14

32 120 32

14
14
150

150
178
96
86

40

150

150
178
96

40
19
19
20
20

80 M12 80 M12
10 20
10 375 25
275
455
355

Drawing n. Polarity
Drawing n. Polarity
1VL4600577R0101 P1 to secondary terminal
44615080 P1 to secondary terminal
1VL4600577R0102 P2 to secondary terminal 44615090 P2 to secondary terminal

TPU 60.22 Weight: 43-49 kg TPU 60.23 Weight: 43-49 kg


Creepage distance: 282 mm TPUTPU
63.2360.23 Creepage distance: 280
WEIGHT: mm
43-49kg
TPU 60.22 WEIGHT: 43-49kg
TPU 63.23 CREEPAGE DISTANCE: 280mm
CREEPAGE DISTANCE: 282mm
382
264

382 132
2

340
280

280

Pg16 14 Pg16 14

M8
M8
39

39
22

20

22

20

173 260
4

173 260
4

195
195
32 120 32
32 120 32
14

23 23 23
14

14
14

39,5

150

150
178
150

150
178

96
86

60
96

23

19 19

33,5 17 18

80,5 M8 M12 68 M12


10 375 25 10 375 25
455 455

Drawing n. Polarity Drawing n. Polarity


44615100 P1 to secondary terminal 44615120 P1 to secondary terminal
44615110 P2 to secondary terminal 44615130 P2 to secondary terminal

6 TPU 6x.xx | Indoor supporting current transformers


TPU 60.24 Weight: 43-49 kg TPU 64.11 Weight: 36-41 kg
TPU 60.24 Creepage distance: 282 mm Creepage distance:
WEIGHT:270 mm
WEIGHT: 43-49kg
CREEPAGE DISTANCE: 282mm
TPU 65.11
TPU 64.11 36-41kg
382 TPU 65.11
TPU 66.11 CREEPAGE DISTANCE: 270mm

TPU 66.11
264
TPU 67.11
TPU 67.11
132

TPU 68.11
TPU 68.11 282

2
340
280

280
Pg16 14

Pg16 14
M8
M8
39
22

20

39
22

20
173 260
4

195 173 160

4
32 120 32 195
23 23 23
14

32 120 32 14
14

14
19
39,5
150

150
178
96
86

23

150

150
178
96

40
80
19

33,5 17
20
80,5 M8 M12 80 M12
10 375 25 10 275 20
455 355

Drawing n. Polarity Drawing n. Polarity


44615140 P1 to secondary terminal 44615160 P1 to secondary terminal
44615150 P2 to secondary terminal 44615170 P2 to secondary terminal

TPU 64.13 Weight: 36-41 kg TPU 64.21 Weight: 50-57 kg


TPUTPU 64.13
65.13 Creepage distance: 270
WEIGHT: mm
36-41kg TPUTPU
65.2164.21 Creepage distance: 272
WEIGHT: mm
50-57kg

TPUTPU 65.13 TPUTPU


66.2165.21
CREEPAGE DISTANCE: 270mm CREEPAGE DISTANCE: 272mm
66.13
TPU 66.13
TPU 67.2166.21
TPU
282

TPUTPU
67.13
67.13
225
TPU 67.21
TPUTPU 68.13
68.13 TPUTPU
68.2168.21
2

407
2
34
280

280

Pg16 14
254

Pg16 14
M8
39

4
22

20

39

173 160
4

173 260
22

195 195 M8

32 120 32 32 120 32
14
14

14

19
120

178
150

150
96

80
40
110
150

150
178
96

40
80

14

20 M12
20
80 235 25
80 M12 10 375
10 275 20 455
355 461

Drawing n. Polarity Drawing n. Polarity


44615180 P1 to secondary terminal 44615200 P1 to secondary terminal
44615190 P2 to secondary terminal 44615210 P2 to secondary terminal

TPU 6x.xx | Indoor supporting current transformers 7


TPU 64.23 Weight: 50-57 kg
TPU 64.23 WEIGHT: 50-57kg
TPU 65.23 Creepage distance: 272 mm
TPU 65.23 CREEPAGE DISTANCE: 272mm
TPUTPU 66.23
66.23
TPUTPU 67.23
67.23
TPUTPU 68.23
68.23 407
270

2
34

340
280
254

Pg16 14
4
39

173 260
22

195 M8

32 120 32
14

110
120
150

150
178
96

80
40
14

20 M12
80 235 25
10 375
455
461

Drawing n. Polarity
44615220 P1 to secondary terminal
44615230 P2 to secondary terminal

8 TPU 6x.xx | Indoor supporting current transformers


Contact us

ABB s.r.o.

1VLC000502 Rev.7, en. 2016.08.05


EPMV Brno

Videnska 117, 619 00 Brno,


Czech Republic
Tel.: +420 547 152 021
+420 547 152 614
Fax: +420 547 152626
E-mail: info.ejf@cz.abb.com

www.abb.com

The data and illustrations are not binding. We reserve the right to
make changes without notice in the course of technical develop-
ment of the product.

Copyright 2016 ABB.


All rights reserved.