EE482: Power System Analysis (2) Quiz #1 Fault Calculation 2nd Semester 2014-2015 Time: 20 minutes

For the system shown in Fig. 1, consider a base MVA=1.25 MVA, then calculate:
a) The short-circuit MVA at the 11 kV bus, MVAsc.
b) The system short circuit impedance Xsc in Ohms and p.u.
c) Total system impedance in Ohms and p.u. from the source to the 1000 V bus, Xtot.
d) Three-phase fault current in Amperes at the 1000 V bus using Ohmic method, IF-1000V.
e) Verify the three-phase fault current calculation at the 1000 V bus using the p.u. method.

`
1000 V
11 kV

1.25 MVA
X=5.5%
Isc = 2.5 kA
Fig. 1

V ph 11 10 3 3 6351
X sc 2.54
I sc 2.5 10 3 2500
3 11 10 3 2.5 10 3 MVAsc 47.63
MVAsc 3VLL I sc 6
47.63 MVA, MVAsc pu 38.1 pu
10 MVAbase 1.25
1 1
X sc pu 0.0262 pu (2.62%)
MVAsc pu 38.1
OR
X sc 1 VLL2 112 2.54
X sc pu , X base 11k V 96.8 , X sc pu 0.0262 pu (2.62%)
X base 11kV 38.1 MVAbase 1.25 96.8
X TX % MVAnew 5.5 1.25
X TX pu 0.055 pu
100 MVAold 100 1.25
X tot pu X sc pu X TX pu 0.0262 0.055 0.0812 pu
VLL2 1.0 2
X base 1000V 0.8 ,
MVAbase 1.25
X tot 1000V X tot pu X base 1000V 0.0812 0.8 0.065
1000 3 V
I F 1000V 8887.8 A (8.888 kA)
0.065
1.0 pu MVAbase 1.25 MVA
I F pu 1000V 12.315 pu, I base kA 1000V 0.7217 kA (721.7 A),
0.0812 pu 3VLL kV 3 1.0 kV
I F kA 1000V I F pu 1000V I base kA 1000V 12.315 0.7217 8.888 kA

................................................................................................................................................................