Escolar Documentos
Profissional Documentos
Cultura Documentos
REF 543,
Buyers Guide
REF 545.
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Issued: June 1999
Status: Updated
Version: E/02.04.2004
Data subject to change without notice
Features Feeder terminal for protection, control, Time synchronization via binary input. Syn-
measurement and supervision of medium chronization pulse once per second or
voltage networks. once per minute.
New application areas for power quality Additional functions including synchro-
measurement, protection, capacitor bank check, frequency protection, capacitor
protection and control and motor protec- bank protection and control, measurement
tion. of current and voltage harmonics.
Voltage and current measurement via con- RTD/analogue module for temperature
ventional measuring transformers or cur- measurement, current/voltage measure-
rent sensors and voltage dividers. ment and mA-outputs.
Fixed human-machine interface including a Communication over three communication
large graphic display, or an external display interfaces: one for local communication
module for flexible switchgear installation. with a PC and two for remote communica-
tion with a substation communication sys-
Extended functionality including protec-
tem or with a substation monitoring system.
tion, control, measurement, communica-
tion, power quality and condition Part of the ABB Distribution Automation
monitoring. system.
Protection functions including e.g. non-
directional and directional overcurrent and
earth-fault protection, residual voltage,
overvoltage and undervoltage protection,
thermal overload protection, CBFP and
auto-reclosing.
Control functions including local and
remote control of switching objects with
synchro-check, status indication of the
switching objects and interlockings on bay
and station level
Measurement of phase currents, phase-to-
phase and phase-to-neutral voltages, neu-
tral current and residual voltage, frequency,
power factor, active and reactive power
and energy.
Condition monitoring including circuit-
breaker condition monitoring, trip circuit
supervision and internal self-supervision of
the feeder terminal.
Fig. 1 Setting group example window.
3
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Application The REF 541, REF 543 and REF 545 feeder protection, measurement, control, condition
terminals are designed to be used for protec- monitoring and general functions, the feeder
tion, control, measurement and supervision of terminals are provided with a large amount of
medium voltage networks. They can be used PLC functions allowing several automation
with different kinds of switchgear including and sequence logic functions needed for sub-
single busbar, double busbar and duplex sys- station automation to be integrated into one
tems. The protection functions also support unit. The data communication properties
different types of networks such as isolated include IEC 60870-5-103 communication,
neutral networks, resonant-earthed networks SPA bus communication, DNP 3.0 communi-
and partially earthed networks. Application cation, Modbus communication or LON bus
area also covers medium-sized three phase communication with higher-level equipment.
asynchronous motors as well as protection Further, the LON communication together
and control of shunt capacitor banks used for with the PLC functions minimizes the need
reactive power compensation. In addition to for hardwiring between the feeder terminals.
Design The feeder terminals REF 541, REF 543 and Measurement functions
REF 545 differ from each other regarding the The measurement functions include three-
number of digital inputs and outputs avail- phase currents, neutral current, three-phase
able. Please, refer to section Ordering for voltages, residual voltage, frequency, active
more details. and reactive power and power factor. In addi-
tion, other measurement functions are avail-
The REF 54_ feeder terminals incorporate a able.
wide range of feeder terminal functions:
As a standard feature the REF 54_ terminal
Protection functions includes pulse counter inputs. The number of
Measurement functions pulse inputs varies from 7 (REF 541) to 10
(REF 545) according to the REF variant.
Power quality functions
Control functions Disturbance recorder
Condition monitoring functions The transient disturbance recorder is able to
record 16 current or voltage waveforms and
General functions 16 logic digital signals. The sampling fre-
Communication functions quency of the analogue inputs is 2 kHz at the
rated frequency of 50 Hz and 2.4 kHz at the
Standard functions rated frequency of 60 Hz.
The function blocks are documented on the The user can set the length of a recording
CD-ROM Technical Descriptions of Func- within a range determined by the number of
tions (1MRS 750889-MCD). analogue inputs used. The number of record-
ings depends on the sampling frequency,
Protection functions length of recordings and number of analogue
Protection is one of the most important func- inputs.
tions of the REF 54_ feeder terminal. The
protection function blocks are independent of The recordings can be uploaded with a DR-
each other and have their own setting groups, Collector Tool which converts the data to a
data recording, etc. COMTRADE format. The DR-Collector Tool
is supported in CAP501 and CAP505 relay
Typical current-based protection functions tools.
(e.g. overcurrent) can use either Rogowski
coil or conventional current transformer mea- Power quality functions
surement. Correspondingly, voltage-based Power quality functions enable measurement
functions (e.g. overvoltage) use either voltage of total harmonic distortion (THD) of voltage
dividers or voltage transformers. and current, and total demand distortion
(TDD) of current. Individual harmonics are
For further information about functionality measured up to 13th.
levels and the protection functions included
in them, refer to the table Functionality lev-
els, protection functions in section
Ordering.
4
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
The power quality functions produce statisti- surement, power quality, control, condition
cal data about harmonic distortion for long monitoring and general functions. In addition,
term evaluation. Short time average and max- the digital inputs and outputs and LON inputs
imum values for THD and individual har- and outputs can be connected to standard
monics are also supported. functions by using the Relay Configuration
Tool.
LIB 510 supports graphical presentation of
harmonics in the PQ Monitoring Tool.
Other functions
Control functions Low auxiliary voltage indication
The control functions are used to indicate the The REF 54_ feeder terminal is provided
status of switching devices, i.e. circuit break- with a low auxiliary voltage indication fea-
ers and disconnectors, and to execute open ture. The power supply module issues an
and close commands for controllable switch- internal alarm signal when a drop in the
ing devices of the switchgear. Furthermore, power supply voltage is detected (ACFail,
control functions provide on/off switching active low). The alarm signal is activated if
objects for control logic purposes and miscel- the power supply voltage falls about 10%
laneous objects for data monitoring, etc. below the lowest rated DC input voltage of
the power supply module.
The control functions configured with the
Relay Configuration Tool must be linked to The indication of a low auxiliary voltage is
object status indicators included in the available in the feeder terminal configuration
MIMIC configuration picture displayed on and can be connected to any signal output of
the HMI. The object status indicators are used the REF 54_.
to indicate the status of switching devices via
the MIMIC picture and to control them Overtemperature indication
locally. The status of different objects, e.g. The REF 54_ feeder terminal includes an
open/close/undefined, displayed in the internal temperature supervision function.
MIMIC view can be freely designed. The power supply module issues an internal
alarm signal when overtemperature has been
detected inside the terminal enclosure. The
Condition monitoring functions alarm signal will be activated once the tem-
Condition monitoring function blocks such as perature inside the terminal enclosure
supervision of the energizing current and increases to +78C (+75...+83C). Over-
voltage input circuit, operation time counter, temperature indication is available in the
circuit breaker electric wear, scheduled main- feeder terminal configuration and can be con-
tenance, trip circuit supervision and breaker nected to any signal output of the REF 54_.
travel time are available for the REF 54_
feeder terminals. Analogue channels
The feeder terminal measures the analogue
General functions signals needed for protection, measuring, etc.
Additional functions are available for differ- via sensors or galvanically separated match-
ent general purposes to be used in logics such ing transformers.
as activation of HMI backlight, switchgroups,
and resetting of operation indications, latched Depending on whether sensors are included
output signals, registers and disturbance or not, REF 54_ feeder terminals have 9
recorder. (without sensors) or 10 (with sensors) ana-
logue channels. The number of channels used
depends on the feeder terminal configuration
Communication functions and the kind of matching transformers or sen-
The feeder terminal REF 54_ provides three sor inputs used. Furthermore, the feeder ter-
serial communication protocols: IEC_103, minal includes virtual analogue channels for
SPA and LON. calculating the phase-to-phase voltages, neu-
tral current and residual voltage from phase
Standard functions currents and voltages.
Standard functions are used for logics such as
In addition to 9 conventional matching trans-
interlocking, alarming and control sequenc-
formers, sensors developed by ABB can be
ing. The use of logic functions is not limited
used parallel in REF 54_ feeder terminals.
and the functions can be interconnected with
The feeder terminal has 9 sensor inputs. A
each other as well as with protection, mea-
5
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Analogue outputs can be utilized for transfer- eight freely programmable alarm LEDs
ring any measured or calculated information with different colours and modes accord-
to panel meters or e.g. PLCs. ing to the configuration
LED indicator for control interlocking
Alarm LED indicators three protection LED indicators
The feeder terminal offers eight alarm LED HMI push-button section with four arrow
indicators to be configured with the Relay buttons and buttons for clear and enter
Mimic Editor. The LED colours (green, yel-
optically isolated serial communication
low, red), their use, and the ON and OFF state port
texts can be freely defined. Three basic oper-
ation modes are supported: non-latched, backlight and contrast control
latched-steady and latched flashflashing. freely programmable button (F) which can
Alarms can be acknowledged remotely, be used in the configuration of the feeder
locally or by using logic of the feeder termi- terminal
nal. a button for remote/local control
HMI has two main levels, the user level and
The alarm channels include time tagging for the technical level. The user level is for
detected alarms. The time tagging principle everyday measurements and monitoring
used depends on the operation mode. whereas the technical level is intended for
advanced feeder terminal programming.
Interlocking LED indicator
The interlocking LED indicates that control
operation has been interlocked or that the Serial communication
interlocking is in bybass mode, e.g. when The feeder terminal has threeserial communi-
control is possible despite of interlocking. cation ports, one on the front panel and two
on the rear panel.
Trip Circuit Supervision
The purpose of this function is to supervise The standard optical ABB connector
the tripping circuitry of the circuit breaker. The standard optical ABB connector (RS-232
An alarm will be generated in case a faulty connection) on the front panel is intended for
tripping circuit, e.g. a circuit is not able to the connection of a PC for configuring the
perform a trip, is detected. feeder terminal with the CAP 50_ tools. The
front interface uses the SPA bus protocol.
The supervision is based on the constant-cur-
SPA/IEC_103/DNP 3.0/Modbus communi-
rent injection through the tripping circuitry.
cation on the rear connector X3.2
The 9-pin D-type subminiature male connec-
Display panel tor (RS-232 connection) on the rear panel
The feeder terminal is provided with either a connects the feeder terminal to the distribu-
fixed display or an external display module. tion automation system via the SPA bus,
The external display module requires a sepa- IEC_103, DNP 3.0 or Modbus. The fibre-
rate voltage supply from a common source optic interface module type RER 123 is used
with the main unit. The display consists of 19 to connect the feeder terminal to the fibre-
rows divided into two windows: a main win- optic communication bus for SPA and
dow (17 rows) and an assisting window IEC_103 protocols. RS-485 interface module
(2 rows). RER 133 is used to connect the feeder termi-
nal to the RS-485 communication bus for
The graphic display presents detailed infor- DNP 3.0 and Modbus.
mation on MIMIC, objects, events, measure-
ments, control alarms, and parameters. The LON/SPA bus communication on the rear
assisting window is used for terminal-depen- connector X3.3
dent indications/alarms and help messages. The 9-pin D-type subminiature female con-
nector (RS-485 connection) on the rear panel
Additionally, the panel includes the following connects the feeder terminal to the substation
HMI items: automation system via the SPA bus or the
LON bus. The fibre-optic interface module
three push-buttons for object control (I, O, type RER 103 is used to connect the feeder
object selection) terminal to the fibre-optic communication
bus. The RER 103 module supports both SPA
bus and LON bus communication.
7
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
8
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
9
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Connector description
+
L1 L3
Q1 A
0 -
+
Q0 N
n
*) X4.1
+ +
- I
1
Q9 a
da dn
PS1_4_ACFail Mains
2
-
PS1_4_TempAlarm
X1.1
27 100V Ch 10, VT4 X3.2
25 SERIAL BUS
L1 L3 24
P1 S1 100V Ch 9, VT3
X3.3
22 SERIAL BUS
21
100V Ch 8, VT2
S2 19 X4.1
3
P2 18
100V Ch 7, VT1
IRF 4
16
S1 15 0,2A
14 1A Ch 6, CT5 5
13
12 6
1A
S2 11 5A
Ch 5, CT4
10
9 7
1A
8 5A PS1_4_HSPO3 9
Ch 4, CT3 8
7
6 1A 10 + +
5 5A Ch 3, CT2
4 External
3 1A PS1_4_HSPO1 11 0 open
2 5A 13
Ch 2, CT1
1 PS1_4_TCS1 TCS1 12 **)
15 + +
X2.1 Ch 10, sensor
DIFF
External
X2.2
PS1_4_HSPO2 16 1 close
Ch 9, sensor 18
DIFF
PS1_4_TCS2 TCS2 17
X2.3 Ch 8, sensor
DIFF
X2.4 Ch 7, sensor
DIFF
X4.2
X2.5 Ch 5, sensor
DIFF
8
X2.6 Ch 4, sensor
Disconnector Q1
DIFF 9 Close
PS1_4_HSPO4 11
X2.7 Ch 3, sensor 10
DIFF
12
X2.8 DIFF
Ch 2, sensor Disconnector Q1
PS1_4_HSPO5
13 Open
X2.9 Ch 1, sensor 15
DIFF 14
16
17
X4.2
1 PS1_4_SO1 18
2 PS1_4_BI1
4 PS1_4_BI2
5
6 PS1_4_BI3
7
X5.2
3
X5.1
1
BIO1_5_BI1 BIO1_5_SO1 4
- 2
3 5
BIO1_5_BI2
4 6
BIO1_5_SO2
BIO1_5_BI3
- 5 7
6 9
BIO1_5_BI4
7 8
BIO1_5_SO3
BIO1_5_BI5
- 8 10
9 12
BIO1_5_BI6
11
- 10
BIO1_5_BI7
BIO1_5_SO4
11 13
15
12
BIO1_5_BI8
*) Power flow direction 14
13 BIO1_5_SO5
BIO1_5_BI9 16
14
**) Example connection 18
15
16 BIO1_5_BI10
17
17 BIO1_5_SO6
18 BIO1_5_BI11
X5.2
1
BIO1_5_BI12
2
REF 541
(1MRS 090115-AABA/BABA/CABA)
ef541ext_c
10
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
+
+ Q1 Q2
L1 L3
A
+ 0
Q0
N
+
Q3 n
X4.1
+
*) Mains 1 I
+ PS1_4_ACFail
Q9 a - 2
da dn
PS1_4_TempAlarm
X1.1
27 X3.2
100V Ch 10, VT4 SERIAL BUS
25
L1 L3 24
P1 S1 100V Ch 9, VT3
X3.3
22 SERIAL BUS
21
100V Ch 8, VT2
S2 19 X4.1
P2 18 IRF 3
100V Ch 7, VT1 4
16
S1 15 0,2A
14 1A Ch 6, CT5
5
13
12 1A 6
S2 + _
11 5A
Ch 5, CT4
10
9 1A 7
8 5A
Ch 4, CT3
PS1_4_HSPO3 9
0 External
8
7
_ open
6 1A 10
5 5A
Ch 3, CT2
4
3 1A PS1_4_HSPO1 11 **)
+ + _
2 5A Ch 2, CT1 13
1 PS1_4_TCS1 TCS1
12
_
X2.1 Ch 10, sensor
15
1 External
DIFF
close
X2.2 PS1_4_HSPO2 16
DIFF
Ch 9, sensor
PS1_4_TCS2 TCS2
18 +
17
X2.3
DIFF
Ch 8, sensor
X2.4
DIFF
Ch 7, sensor
X4.2
X2.5 Ch 5, sensor
DIFF 8
X2.6
Disconnector Q1
Ch 4, sensor Close
DIFF
9
PS1_4_HSPO4 11
X2.7 Ch 3, sensor 10
DIFF
12 Disconnector Q1
X2.8
DIFF
Ch 2, sensor Open
13
X2.9 Ch 1, sensor PS1_4_HSPO5 15
DIFF
14
16
17
X4.2
1 PS1_4_SO1 18
2 PS1_4_BI1
4 PS1_4_BI2
5
6 PS1_4_BI3
7
X5.2
3
X5.1
1
BIO1_5_BI1
- 2 BIO1_5_SO1 4
3 5
BIO1_5_BI2
4 6
BIO1_5_BI3 BIO1_5_SO2
- 5 7
6 9
BIO1_5_BI4
7 8
BIO1_5_SO3
- 8 BIO1_5_BI5
10
9 12
BIO1_5_BI6
11
10 BIO1_5_SO4
BIO1_5_BI7
- 11 13
15
12
BIO1_5_BI8
13 14
BIO1_5_SO5
BIO1_5_BI9 16
14 18
15
BIO1_5_BI10
16
17
17 BIO1_5_SO6
BIO1_5_BI11
18
X5.2 X7.1
1
BIO1_5_BI12
2
17
BIO2_7_PO1 18
X7.2
X7.1 1
BIO2_7_PO2 2
1
BIO2_7_BI1
- 2
3
3
BIO2_7_BI2 Disconnector Q2
4 BIO2_7_PO3 4 Close
BIO2_7_BI3 5
5 6
*) Power flow direction 6
BIO2_7_BI4 7
**) Example connection Disconnector Q2
7 Open
BIO2_7_BI5 BIO2_7_PO4 8
8 9
10
9
BIO2_7_BI6 11
10 Disconnector Q3
BIO2_7_BI7
11 BIO2_7_PO5 12 Close
13
12 14
BIO2_7_BI8
15
13 Disconnector Q3
BIO2_7_BI9
14
BIO2_7_PO6
16 Open
15 17
18
16 BIO2_7_BI10
REF 543
(1MRS 090127-AABA/BABA/CABA)
ef543ext_c
11
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
+
+ Q1 Q2
L1 L3
A
+ 0
Q0
N
+
Q3 n
X4.1
*) +
+
a PS2_4_ACFail 1 I
Q9 da dn PS2_4_TempAlarm
Mains
- 2
X1.1
27 X3.2
100V
Ch 10, VT4 SERIAL BUS
25
L1 L3 24
P1 S1 100V
Ch 9, VT3 X3.3
22 SERIAL BUS
21
100V
Ch 8, VT2
S2 19 X4.1
3
P2 18
100V IRF 4
Ch 7, VT1
16
S1 15 0,2A
14 1A
Ch 6, CT5 5
13 _
12 1A 6 +
S2 11 5A
Ch 5, CT4
10
7 External
9
8
1A
5A
Ch 4, CT3
PS2_4_HSPO3 9 0 open
7 8 _
6 1A 10
5
4
5A
Ch 3, CT2 **)
11
3 1A PS2_4_HSPO1
+ _
2
1
5A
Ch 2, CT1 PS2_4_TCS1 TCS1
13
12
+
15
_ External
X2.1
DIFF
Ch 10, sensor 1 close
X2.2 PS2_4_HSPO2 16
Ch 9, sensor
DIFF
PS2_4_TCS2 TCS2
18
17
+
X2.3 Ch 8, sensor
DIFF
X2.4 Ch 7, sensor
DIFF X4.2
1
X2.5 Ch 5, sensor
DIFF Disconnector Q1
X2.6 PS2_4_HSPO4 *)
2 Close
Ch 4, sensor 4
DIFF
3
X2.7 Ch 3, sensor 5
DIFF
Disconnector Q1
X2.8 Ch 2, sensor 6
DIFF
PS2_4_HSPO5 8 Open
7
X2.9 Ch 1, sensor
DIFF 9
Disconnector Q2
10 Close
X5.1 PS2_4_HSPO6 12
11
1
BIO1_5_BI1 13
- 2
3 Disconnector Q2
BIO1_5_BI2
PS2_4_HSPO7
14
16
Open
4 15
BIO1_5_BI3
- 5
6
BIO1_5_BI4 PS2_4_HSPO8 17
18
7
BIO1_5_BI5
- 8
9 X5.2
BIO1_5_BI6 3
10
BIO1_5_BI7 BIO1_5_SO1 4
- 11
5
12
BIO1_5_BI8
6
13 BIO1_5_SO2
BIO1_5_BI9 7
14
9
15
BIO1_5_BI10
16
8
17 BIO1_5_SO3
BIO1_5_BI11 10
18
12
X5.2
11
BIO1_5_SO4
1
BIO1_5_BI12 13
2 15
14
BIO1_5_SO5
16
X6.1 18
1
BIO1_6_BI1
- 2 17
3 BIO1_5_SO6
BIO1_6_BI2
X6.2
4 3
BIO1_6_BI3
5
6 4
BIO1_6_BI4 BIO1_6_SO1
5
*) Power flow direction 7
BIO1_6_BI5
8 6
9 BIO1_6_SO2
BIO1_6_BI6 7
9
10
BIO1_6_BI7
11 8
BIO1_6_SO3
12 10
BIO1_6_BI8
12
13
BIO1_6_BI9
14 11
BIO1_6_SO4
15 13
BIO1_6_BI10
16 15
17
BIO1_6_BI11 14
18
BIO1_6_SO5
16
18
X6.2
1 17
BIO1_6_BI12 BIO1_6_SO6
2
X7.1
X7.1
1 17
BIO2_7_BI1 BIO2_7_PO1 18
2
3 X7.2
BIO2_7_BI2
1
4 BIO2_7_PO2 2
BIO2_7_BI3
5
3
6
BIO2_7_BI4
Disconnector Q3
7 4 Close
BIO2_7_BI5 BIO2_7_PO3 5
8 6
9 7
BIO2_7_BI6
10
Disconnector Q3
11
BIO2_7_BI7
BIO2_7_PO4
8
9
Open
12 10
BIO2_7_BI8 11
13
14 BIO2_7_BI9 12
BIO2_7_PO5 13
15 14
16 BIO2_7_BI10 15
16
BIO2_7_PO6 17
REF 545 18
(1MRS 090133-AABA/BABA/CABA)
ef545ext_c
12
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
X6.1
SHUNT
1 X6.2
2 +
-
RTD1_6_AI1
3 + 11
DIFF
RTD1_6_AO1
4 mA- 12
5 -
+
RTD1_6_AI2
6 DIFF + 13
7
SHUNT
RTD1_6_AO2
SHUNT
mA- 14
8
9 +
RTD1_6_AI3 RTD1_6_AO3 + 15
10 - DIFF
mA- 16
11
12 -
RTD1_6_AI4 RTD1_6_AO4 + 17
13 +
mA- 18
SHUNT DIFF
14
SHUNT
15
16 +
RTD1_6_AI5
17 - DIFF
18
X6.2
1 -
2 +
RTD1_6_AI6
SHUNT DIFF
3
SHUNT
4
5 +
RTD1_6_AI7
6 - DIFF
7
8 -
9 +
RTD1_6_AI8
SHUNT DIFF
10
RTD1diag
13
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
14
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
15
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
16
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
The recording can be triggered by any (or several) of the alternatives listed below:
triggering on the rising or falling edge of any (or several) of the digital inputs
triggering on overcurrent, overvoltage or undervoltage
manual triggering via the menu or with the push-button F on the front panel (if configured)
triggering via serial communication
periodic triggering
The recording length depends on the number of recordings and inputs used. For example, the following
combination of recording length, number of recordings and number of inputs is available at 50 Hz:
# recordings \ # inputs 1 3 10
1 1163 cyc. 412 cyc. 126 cyc.
23.2 s 8.2 s 2.5 s
5 232 cyc. 82 cyc. 25 cyc.
4.6 s 1.6 s 0.5 s
10 115 cyc. 41 cyc. 12 cyc.
2.3 s 0.8 s 0.24 s
17
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
18
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
19
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
20
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Three-phase directional O/C function, high-set stage, DOC6High, I>>, and instantaneous stage,
DOC6Inst, I>>>
Operation mode Not in use
Definite time
Instantaneous
Start current 0.0540.00 x In
Operate time 0.05300.00 s
Basic angle b 090
Operation direction Forward
Reverse
Earth-fault protection Disabled
Enabled
Non-directional operation (when the direction Disabled
cannot be determined) Enabled
Measuring mode Phase-to-phase voltages, peak-to-peak measurement
Phase-to-phase voltages, fundamental freq. measurement
Phase-to-earth voltages, peak-to-peak measurement
Phase-to-earth voltages, fundamental freq. measurement
Drop-off time of the operate time counter 0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy 0.1...10 x In: 2.5% of set value or 0.01 x In
10...40 x In: 5.0% of set value
2.5% of measured voltage or 0.01 x Un
2
Start time Injected currents > 2.0 x start current:
internal time < 42 ms
total time < 50 ms
Reset time 40...1000 ms (depends on the minimum pulse width set for
the trip output)
Reset ratio, typically 0.95
Retardation time < 45 ms
Operate time accuracy at DT mode 2% of set value or 20 ms
21
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Non-directional earth-fault protection, high-set stage, NEF1High, Io>>, and instantaneous stage,
NEF1Inst, Io>>>
Start current 0.1012.00 x In
Operate time 0.05300.00 s
Operation mode Not in use
Definite time
Instantaneous
Measuring mode Peak-to-peak
Fundamental frequency
Drop-off time of the operate time counter 0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy 2.5% of set value or + 0.01 x In
Start time Injected currents > 2.0 x start current:
internal time < 32 ms
total time < 40 ms
Reset time 40...1000 ms (depends on the minimum pulse width set for
the trip output)
Reset ratio, typically 0.95
Retardation time < 45 ms
Operate time accuracy at DT mode 2% of set value or 20 ms
22
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
23
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Directional earth-fault protection, high-set stage, DEF2High, Io>>, and instantaneous stage,
DEF2Inst, Io>>>
Start current 1.0500.0% of In
Start voltage 2.0100.0% of Un
Operate time 0.1300.0 s
Operation mode Not in use
Definite time
Instantaneous
Operation criteria Basic angle & Uo
Basic angle
IoSin/Cos & Uo
IoSin/Cos
Non-directional Io
Non-directional Uo
Operation direction Forward
Reverse
Basic angle b -90... 0
Operation characteristic IoSin()
IoCos()
Intermittent E/F Not active
Active
Measuring mode Peak-to-peak
Fundamental frequency
Drop-off time of the operate time counter 0...1000 ms
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy 2.5% of set value + 0.0005 x In
2.5% of set value or + 0.01 x Un
Phase angle 2
Start time Injected neutral current > 2.0 x start current
and residual voltage > 2.0 x start voltage:
internal time < 72 ms
total time < 80 ms
Reset time 40...1000 ms (depends on the minimum pulse width set for
the trip output)
Reset ratio, typically 0.95
Retardation time < 50 ms
Operate time accuracy at DT mode 2% of set value or 20 ms
24
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Residual overvoltage protection, high-set stage, ROV1High, Uo>>, and instantaneous stage,
ROV1Inst, Uo>>>
Start voltage 2.0100.0% of Un
Operate time 0.05300.00 s
Operation mode Not in use
Definite time
Measuring mode Peak-to-peak
Fundamental frequency
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy 2.5% of set value or 0.01 x Un
Start time Injected voltages >2 x start voltage:
internal time < 32 ms
total time < 40 ms
Reset time 40...1000 ms (depends on the minimum pulse width set for
the trip output)
Reset ratio, typically 0.95
Retardation time Total time for blocking: < 25 ms
Total time when voltage drops below start value: < 50 ms
Operate time accuracy at DT mode 2% of set value or 20 ms
25
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Three-phase thermal overload protection for motors, generators and transformers, TOL3Dev, 3
BASIC SETTINGS
Starting current of the motor 0.10...10.00 x In
Max. starting time permitted for the motor 0.1...120.0 s
Number of starts allowed from cold state 1...3
Type of device to be protected Motor; through-ventilated, rated power < 1500 kW
Motor; through-ventilated, rated power > 1500 kW
Motor; surface cooling, rated power < 500 kW
Motor; surface cooling, rated power > 500 kW
Generator; hydro or small air-cooled turbine generators
Generator; large turbine generators
Transformer
Trip temperature 80.0120.0%
Prior alarm temperature 40.0100.0%
Restart inhibit (temperature limit for
successful restarting) 40.0100.0%
Ambient temperature -50.0100.0C
Cooling time-constant 1.0...10.0 x time constant
Heating time-constant for generator or
transformer 1...999 min
ADVANCED SETTINGS
Short time-constant for stator 0.0...999.0 min
Long time-constant for stator 0.0...999.0 min
Weighting factor of the short time-constant for
stator 0.00...1.00
Temperature rise of stator at rated current
Maximum temperature of stator 0.0...350.0 C
Short time-constant for rotor 0.0...350.0 C
Long time-constant for rotor 0.0...999.0 min
Weighting factor of the short time-constant for 0.0...999.0 min
rotor
Temperature rise of rotor at rated current 0.00...1.00
Maximum temperature of rotor
0.0...350.0 C
0.0...350.0 C
Operation mode (principle of ambient Not in use
temperature compensation) No sensors; the set ambient temperature
1 sensor used
2 sensors used
Waiting time for a successful restart (Read-
only parameter) 0...99999 s
Predicted time to the trip (Read-only
parameter) 0...99999 s
Note! The values below apply when f/fn = 0.95...1.05
Operation accuracy 1.0%, I = 0.1...10.0 x In
Reset ratio Trip: (Calculated temp. rise - 0.1) / Trip temperature
Start: (Calculated temp. rise - 0.1) / Prior alarm
temperature
Restart: (Calculated temp. rise - 0.1) / Restart inhibit
temperature limit
26
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
27
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
28
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
29
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Three-phase overload protection for shunt capacitor banks, OL3Cap, 3I>, 3I<
Operate times of the overload stage Ib>
I/Ib> t [s] Standard durations [s] Standard
1.15 1799 1800 IEC 60871-1
1.20 299 300 IEC 60871-1
1.30 58 60 ANSI/IEEE 37.99, IEC
60871-1
1.40 13.5 15 ANSI/IEEE 37.99
1.70 0.9 1 ANSI/IEEE 37.99
2.00 0.29 0.3 ANSI/IEEE 37.99
2.20 0.1 0.12 ANSI/IEEE 37.99
Note! The minimum operate time is 100 ms
Start current of trip stage 0.30...1.50 x In
Time multiplier k for trip stage 0.05...2.0
Start current of alarm stage 0.80...1.20 x Ib
Operate time of alarm stage 0.5...6000.0 s
Start current of undercurrent stage 0.10...0.70 x Ib
Operate time of undercurrent stage 0.1...120 s
Setting of reconnection inhibit time trec 0.5...6000 s
Operation accuracies Note! The values below apply when f/fn=0.95...1.05
2.5% of set value or 0.01 x In
Start time Injected currents = 2.0 x start current
internal time < 32 ms
total time < 40 ms
Reset time 40...1000 ms (depends on the minimum pulse width set
for the TRIP output)
Reset ratio Overload stages: Typ. 0.95
Undercurrent stage: Typ. 1.05
Retardation time Total retardation time when the current exceeds the
start value: < 50 ms
Operate time accuracy at definite time mode 2% of set value or 20 ms
(alarm stage Ia>, undercurrent stage I<)
Operate time accuracy at inverse time mode Depends on the frequency of the current measured:
(trip stage Ib>) 10% of theoretical value or 40 ms
30
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
31
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Three-phase current unbalance protection for H-bridge connected shunt capacitor banks,
CUB3Cap, 3I>
Operation mode Not in use; Definite time; Extremely inv.; Very inv.;
Normal inv.; Long-time inv.; RI-type inv.; RD-type inv.
Start current of the tripping stage 1.0...100.0% dIn
Operate time of the tripping stage in DT mode 1.0...300 s
Time multiplier k for the tripping stage in 0.05...2.0
IDMT mode
Start current of the alarm stage 1.0...100.0% dIn
Operate time of the alarm stage 1.0...300.0 s
Comp natural dI1 0.0...20.0% dIn
Comp natural dI2 0.0...20.0% dIn
Comp natural dI3 0.0...20.0% dIn
Rec natural dI Do not activate; Rec all phasors; Rec phasor dI1, Rec
phasor dI2, Rec phasor dL3
Note! The values below apply when f/fn=0.95...1.05
Operation accuracies 2.5% of set value + 0.0005 x dIn
Phase angle measurement: 2
Start time Injected currents = 2.0 x start current
internal time <32 ms
total time <40 ms
Reset time 40...1000 ms (depends on the minimum pulse width set for
the TRIP output)
Reset ratio, typically 0.95
Retardation time < 45 ms
Operate time accuracy at definite-time mode 2.5% of set value or 0.1% dIn
Operate time accuracy at inverse-time mode 2.5% of set value or 0.1% dIn
Synchro-check/voltage check function stage 1 and stage 2, SCVCSt1 and SCVCSt2, SYNC
Upper threshold voltage Umax 0.501.00 x Un
Lower threshold voltage Umin 0.100.80 x Un
Voltage difference U 0.020.60 x Un
Phase angle difference phase 590
Frequency difference f 0.025.00 Hz
Operation accuracy Note! The values below apply when f/fn = 0.95...1.05
2.5% of set value or 0.01 x Un
10 mHz
2
Reset time < 50 ms
Reset ratio 0.975 x Un
Operate time accuracy 2% of set value or 20 ms
32
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
33
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
34
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
35
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
36
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
37
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
38
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Ordering The following is to be specified when order- Each REF 54_ feeder terminal has a specific
ing REF 54_ terminals: order number, display order number that identifies the feeder termi-
language combination and quantity of feeder nal type as well as the hardware and the soft-
terminals. ware as described below. The order number is
39
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
REF54_HC127AAAA
A = fixed display, B = external display module
A = without sensor, B = with sensor
Reserved for future use
Auxiliary voltage range of a power supply module and
voltage range of digital inputs
A: power supply: PS1/240 V (Medium) or PS2/240 V
Ur = 110/120/220/240 V ac;
110/125/220 V dc
digital inputs: Ur = 110/125/220 V dc
threshold voltage: Ut = 80 V dc
B: power supply: PS1/240 V (High) or PS2/240 V
Ur = 110/120/220/240 V ac;
110/125/220 V dc
digital inputs: Ur = 220 V dc
threshold voltage: Ut = 155 V dc
C: power supply: PS1/48 V (Low) or PS2/48 V
Ur = 24/48/60 V dc
digital inputs: Ur = 24/48/60/110/125/220 V dc
Language combinations
Suffix Language combination
001 English-German
002 English-Swedish
003 English-Finnish
007 English-Portuguese
008 English-Polish
009 English-Russian
010 English-Spanish
Number of inputs/outputs
Number of inputs/outputs REF 541 REF 543 REF 545
Digital inputs 15 25 34
Trip circuit supervision inputs 2 2 2
Power outputs (NO single-pole) 0 2 3
Power outputs (NO double-pole) 5 9 11
Signal outputs (NO) 2 2 4
Signal outputs (NO/NC) 5 5 8
Self-supervision outputs 1 1 1
40
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
The functionality level determines the extent information on the separate function blocks
of the selection of function blocks available included in each selection, please consult
for the feeder terminal. For more detailed your relay supplier.
41
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
42
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
43
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Optional functionality
Function Code Ordering number
CAPACITOR BANK PROTECTION
Three-phase overload protection for shunt capacitor banks OL3Cap 1MRS100116
Current unbalance protection for shunt capacitor banks CUB1Cap 1MRS100117
Three-phase current unbalance protection for H-bridge CUB3Cap 1MRS100052
connected shunt capacitor banks
CAPACITOR BANK CONTROL
Power factor controller COPFC 1MRS100143
POWER QUALITY
Current waveform distortion measurement PQCU3H 1MRS100512
Voltage waveform distortion measurement PQVO3H 1MRS100513
44
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
REF541C_118CAAA
REF541C_118CABA
REF541E_115CAAA
REF541E_115CABA
REF541C_118AAAA
REF541C_118BAAA
REF541C_118AABA
REF541C_118BABA
REF541C_118AAAB
REF541C_118BAAB
REF541C_118AABB
REF541C_118BABB
REF541E_115AAAA
REF541E_115BAAA
REF541E_115AABA
REF541E_115BABA
REF541E_115AAAB
REF541E_115BAAB
REF541E_115AABB
REF541E_115BABB
Analogue interface
Sensor channels (current or voltage) 9 9 9 9 9 9 9 9 9 9
Current transformer 1/5 A 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Current transformer 0.2/1 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Voltage transformer 100 V 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Main processor boards
CPU module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Power supply boards
PS1: 80...265 Vdc/ac (High) 1 1 1 1 1 1 1 1
PS1: 80...265 Vdc/ac (Medium) 1 1 1 1 1 1 1 1
PS1: 18...80 Vdc/ac(Low) 1 1 1 1
PS2: 80...265 Vdc
PS2: 18...80 Vdc
Digital I/O boards
BIO1: threshold voltage 155 Vdc 1 1 1 1 1 1 1 1
BIO1: threshold voltage 80 Vdc 1 1 1 1 1 1 1 1
BIO1: threshold voltage 18 Vdc 1 1 1 1
BIO2: threshold voltage 155 Vdc
BIO2: threshold voltage 80 Vdc
BIO2: threshold voltage 18 Vdc
Analogue I/O board
RTD/analogue module 1 1 1 1 1 1 1 1 1 1
Display boards
Graphic HMIHMI display, fixed 1 1 1 1 1 1 1 1 1 1 1 1
Graphic HMI display, external 1 1 1 1 1 1 1 1
Mechanical design
1/2 enclosure 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Digital inputs 15 15
Power outputs, single-pole 0 0
Power outputs, double-pole 5 5
Signal outputs (NO) 2 2
Signal outputs (NO/NC) 5 5
Supervised trip circuits 2 2
IRF outputs 1 1
RTD/analogue inputs 0 8
Analogue outputs 0 4
45
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
REF543H_127CAAA
REF543H_127CABA
REF543C_129CAAA
REF543C_129CABA
REF543H_127AAAA
REF543H_127BAAA
REF543H_127AABA
REF543H_127BABA
REF543H_127AAAB
REF543H_127BAAB
REF543H_127AABB
REF543H_127BABB
REF543C_129AAAA
REF543C_129BAAA
REF543C_129AABA
REF543C_129BABA
REF543C_129AAAB
REF543C_129BAAB
REF543C_129AABB
REF543C_129BABB
Analogue interface
Sensor channels (current or voltage) 9 9 9 9 9 9 9 9 9 9
Current transformer 1/5 A 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Current transformer 0.2/1 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Voltage transformer 100 V 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
Main processor boards
CPU module 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Power supply boards
PS1: 80...246 Vdc/ac (High) 1 1 1 1 1 1 1 1
PS1: 80...265 Vdc/ac (Medium) 1 1 1 1 1 1 1 1
PS1: 18...80 Vdc/ac (Low) 1 1 1 1
PS2: 80...265 Vdc
PS2: 18...80 Vdc
Digital I/O boards
BIO1: threshold voltage 155 Vdc 1 1 1 1 1 1 1 1
BIO1: threshold voltage 80 Vdc 1 1 1 1 1 1 1 1
BIO1: threshold voltage 18 Vdc 1 1 1 1
BIO2: threshold voltage 155 Vdc 1 1 1 1 1 1 1 1
BIO2: threshold voltage 80 Vdc 1 1 1 1 1 1 1 1
BIO2: threshold voltage 18 Vdc 1 1 1 1
Analogue I/O board
RTD/analogue module 1 1 1 1 1 1 1 1 1 1
Display boards
Graphic HMI display, fixed 1 1 1 1 1 1 1 1 1 1 1
Graphic HMI display, external 1 1 1 1 1 1 1 1
Mechanical design
1/2 enclosure 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Digital inputs 25 25
Power outputs, single-pole 2 2
Power outputs, double-pole 9 9
Signal outputs (NO) 2 2
Signal outputs (NO/NC) 5 5
Supervised trip circuits 2 2
IRF outputs 1 1
RTD/analogue inputs 0 8
Analogue outputs 0 4
46
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
REF545E_133CAAA
REF545E_133CABA
REF545E_133AAAA
REF545E_133BAAA
REF545E_133AABA
REF545E_133BABA
REF545E_133AAAB
REF545E_133BAAB
REF545E_133AABB
REF545E_133BABB
Analogue interface
Sensor channels (current or voltage) 9 9 9 9 9
Current transformer 1/5 A 4 4 4 4 4 4 4 4 4 4
Current transformer 0.2/1 A 1 1 1 1 1 1 1 1 1 1
Voltage transformer 100 V 4 4 4 4 4 4 4 4 4 4
Main processor boards
CPU module 1 1 1 1 1 1 1 1 1 1
Power supply boards
PS1: 80...265 Vdc/ac (High)
PS1: 80...265 Vdc/ac (Medium)
PS1: 18...80 Vdc/ac (Low)
PS2: 80...265 Vdc 1 1 1 1 1 1 1 1
PS2: 18...80 Vdc 1 1
Digital I/O boards
BIO1: threshold voltage 155 Vdc 2 2 2 2
BIO1: threshold voltage 80 Vdc 2 2 2 2
BIO1: threshold voltage 18 Vdc 2 2
BIO2: threshold voltage 155 Vdc 1 1 1 1
BIO2: threshold voltage 80 Vdc 1 1 1 1
BIO2: threshold voltage 18 Vdc 1 1
Analogue I/O board
RTD/analogue module
Display boards
Graphic HMI display, fixed 1 1 1 1 1 1
Graphic HMI display, external 1 1 1 1
Mechanical design
1/2 enclosure 1 1 1 1 1 1 1 1 1 1
Digital inputs 34
Power outputs, single-pole 3
Power outputs, double-pole 11
Signal outputs (NO) 4
Signal outputs (NO/NC) 8
Supervised trip circuits 2
IRF outputs 1
RTD/analogue inputs 0
Analogue outputs 0
48
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Application
examples
000
3I > 50/51 MCS
R
REF 54_
U 90V
U
R 000
q SPAU 341
q p>
CBFP * /62
SPAD 346C
000
3I > 50/51 MCS 3I >
&
51B TCS
REA 101
3U > 59 CBCM 0 I
CBFP * /62
3I~harm R
3U~harm
P 3I
MF
Q 3U
E
REF 54_
M M
EXINFDR1
Fig. 6 Protection, control, measurement and supervision functions of a utility infeeder, implemented with
REF 54_ feeder terminals, an REA arc monitoring system and SPACOM differential relay and volt-
age regulator (main single-line diagram presentation). The neutral point of the MV network sup-
plied by the infeeder is isolated.
49
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000
3I > 50/51 MCS
R
REF 54_
U 90V
U
R 000
SPAU 341
SPAD 346C
000
3I > 50/51 MCS 3I >
&
51B TCS
3U > 59 R
CBFP * /62
P
3I~harm
3I
MF
Q
3U~harm
3U
U0
E
I0
M M
REF 54_
EXINFDR3
Fig. 7 Protection, control, measurement and supervision functions of a utility infeeder, implemented with
REF 54_ feeder terminals, an REA arc monitoring system and SPACOM differential relay and volt-
age regulator (main single-line diagram presentation). The neutral point of the MV network sup-
plied by the infeeder is earthed via the Petersen coil.
50
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
M M
000
3I > 50/51 MCS
MF
3I2f > 68
DI> 46 R
f< 81U
P 3I
0 I 79
I0 3U
CBFP * /62
E
REF 54_
EXFDR1
Fig. 8 An REF 54_ feeder terminal used for the protection, control, measurement and supervision func-
tions of a utility feeder (main single-line diagram presentation). The neutral point of the supplying
network is isolated. The scheme is also fully applicable in high-impedance earthed networks,
where the neutral point is earthed via a high resistance or a Petersen coil.
51
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000 000
3U > 59 MCS 3U > 59 MCS
U0 3U U0 3U
f f
REF 54_ REF 54_
EXMEAS1
Fig. 9 REF 54_ feeder terminals used for the protection, control, measurement and supervision functions
of a utility/industrial measurement cubicle (main single-line diagram presentation). The neutral
point of the supplying network is isolated. The scheme is also fully applicable in high-impedance
earthed networks, where the neutral point is earthed via a high resistance or a Petersen coil.
52
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000
3I > 50/51 MCS
CBFP * /62
R
REF 54_
U 90V
U
R 000
SPAU 341
SPAD 346C
000
3I > 50/51 MCS 3I >
&
51B TCS
I0> 50N/51N R
SYNC 25
3U > 59 P 3I
CBFP * /62
Q 3U
MF MF
3I~harm
3U~harm
I0 E
REF 54_
EXINFDR4
Fig. 10 Protection, control, measurement and supervision functions of a utility/industrial infeeder, imple-
mented with REF 54_ feeder terminals, an REA arc monitoring system and SPACOM differential
relay and voltage regulator (main single-line diagram presentation). The neutral point of the MV
network supplied by the infeeder is earthed via a high resistance.
53
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
MF
000
3I> 67 MCS
3 49F CBCM 0 I
SYNC 25
f< 81U R
3U > 59
P 3I
3U < 27
Q 3U
CBFP * /62
pf f
E
REF 54_
EXFDR3
3I >
&
REA 101
Fig. 11 An REF 54_ feeder terminal and an REA arc monitoring system (main single-line diagram presen-
tation) used for the protection, control, measurement and supervision functions of a utility/industrial
ring/meshed network cable feeder. The earthing of the supplying network can be of low or high
impedance type.
54
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000
3I > 50/51 MCS
MF
3I2f> 68 CBCM 0 I
DI> 46
CBFP * /62 R
P 3I
E 3U
REF 54_
EXFDR4
Fig. 12 An REF 54_ feeder terminal used for the protection, control, measurement and supervision func-
tions of a utility/light industrial cable feeder (main single line diagram presentation). The earthing of
the supplying network can be of low or high impedance type.
55
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000
3I > 50/51 MCS
MF
I0> 50N/51N TCS
I02f> 68 CBCM 0 I
CBFP * /62
R
REF 54_
U 90V
U
q R 000
SPAU 341
q p>
DI0> 87N
DI0> 87N
CBFP * /62
SPAD 346C
000
3I> 67 MCS 3I >
&
I0> 50N/51N TCS
REA 101
SEF 51N CBCM 0 I
3U > 59
3U < 27 R
f< 81U
P 3I
MF
CBFP * /62
pf 3U
3I~harm
3U~harm f E
REF 54_
EXINFDR2
Fig. 13 Protection, control, measurement and supervision functions of a utility infeeder, implemented with
REF 54_ feeder terminals, an REA arc monitoring system and SPACOM differential relay and volt-
age regulator (main single-line diagram presentation). The neutral point of the MV network sup-
plied by the infeeder is earthed via a low resistance. The scheme is also fully applicable to other
types of low-impedance earthed networks, where the neutral point is earthed effectively or via a
low reactance.
56
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
000
3I > 50/51 MCS
MF
3I2f> 68
DI> 46 R
f< 81U
P 3I
0 I 79
E 3U
CBFP * /62
REF 54_
EXFDR2
Fig. 14 An REF 54_ feeder terminal used for the protection, control, measurement and supervision func-
tions of a utility feeder (main single-line diagram presentation). The neutral point of the supplying
network is earthed via a low resistance. The scheme is also fully applicable to other types of low-
impedance earthed networks, where the neutral point is earthed effectively or via a low reactance.
57
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
3U> 59 MCS
3U< 27 TCS
U0 3U
f
REF 54_
DI> 51NC
CBFP 62BF
DI 3I
I0
asynmot1REFa
REF 54_
Fig. 15 REF 54_ used for the protection of a double Y connected capacitor bank
58
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
3U> 59 MCS
3U< 27 TCS
U1< 27
U2 > 47
U1> 59
U0 3U
f
REF 54_
DI > 46 CBCM
3 49
CBFP 62BF
P 3I
M Q U
pf f
asynmot1REFb
E
REF 54_
Fig. 16 REF 54_ used for the protection of a motor with direct-on-line starting
59
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
3I > 50/51 = multiple-stage three-phase overcurrent protection, low-set, high-set and instantaneous
stage available
I0> 67N = multiple-stage directional earth-fault protection, low-set, high-set and instantaneous
stage available
I0-0> 51N = instantaneous stage for earth-fault protection, to operate in the event of a double earth
fault in isolated or impedance earthed networks
I0> 50N/51N = multiple-stage earth-fault protection, low-set, high-set and instantaneous stage
available
SEF 51N = low-set stage for sensitive earth-fault protection, to operate in the event of a high
resistive earth fault in effectively or low-impedance earthed networks
3I > 50/51 = multiple-stage three-phase overcurrent protection, one stage dedicated for blockable
busbar overcurrent protection
51B
U0> 59N = multiple-stage residual overvoltage protection, low-set, high-set and instantaneous
stage available
3I2f > 68 = inrush detection based on the 2nd harmonic content of phase currents, applied for
preventing possible unnecessary operation of overcurrent or earth-fault protection
during transformer switching-in or to start cold load pick-up logic
DI> 46 = phase discontinuity protection
0 I 79 = multiple-shot auto-recloser
I02f> 68 = inrush detection based on the 2nd harmonic content of neutral current, applied to
prevent possible unnecessary operation of the earth-fault protection during transformer
switching-in
CBFP * /62 = circuit-breaker failure protection
SYMNOT1
60
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
U ,<U ,>U > 27, 47, 59 = phase-sequence voltage protection, stages 1 and 2 available
1 2 1
51C,37C,
3I>, 3I< 68C = three-phase overload protection for shunt capacitor banks
U 90V
= automatic voltage regulation
3I
= 3-phase current measurement, indication and supervision
61
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
= disturbance recorder
SYMNOT3
62
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
Application selection tables for REF 541, REF 543 and REF 545
functions
63
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
64
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
65
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
66
ProtectIT Feeder Terminal REF 541, REF 543, REF 545.
1MRS750443-MBG
67
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation