HV/LV distribution transformers

TRIHAL cast resin dry type transformers 160 to 2500 kVA


insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m

standards
In accordance with standards :
IEC 60076-1 to 60076-5;
s
sse
IEC 60076-11 (2004);

d l o CENELEC (European Committee for Electrotechnical

uce
standardization) harmonization documents HD 538-1 S1:

red 1992 and EN 60726: 2003 / A2: 1991 / A3: 1992


concerning dry type transformers.
IEC 60905
DIN 42523 R.

common electrical characteristics

electrical characteristics for insulation 7,2 and 12 kV

electrical characteristics for insulation 17,5 and 24 kV

(*) the rated power is defined by natural air cooling (AN). (3) reminder of insulation levels :
Should there be particular constraints, it may be increased rated insulation
by 40 % by forced cooling addition (AF). Please consult us.
(1) other possibilities upon request, consult us.
level (kV) 7,2 12 18 24
(2) non standard ratings available on request. kV r.m.s. 50Hz - 1mn 20 28 38 50
kV B.I.L. 1,2/50 s 60 75 95 125
France Transfo
(4) according to CEI 551.
is becoming (5) according to CEI 270.
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m

dimensions and weights


without enclosure housing (IP00)

Dimensions and weights indicated in the table


below are provided as an example for single
voltage transformers with insulation level 12kV
(1st table) and 24 kV (2nd table), according to
electrical characteristics shown page 1.
Consequently, these tables give you
approximate dimensions and weights for
insulation level from 7.2 to 12kV (1st table) and
from 17.5 to 24kV (2nd table).
Only the definitive drawings following from the
order will commit us contractually.
For other voltages, impedance voltages and
dual-voltages, weights and dimensions are
different (consult us).
.

insulation level 7,2 and 12kV - low voltage 400 to 433V

insulation level 17,5 and 24kV - low voltage 400 to 433V

2 france transfo
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m

dimensions and weights


with IP31 metal enclosure

Dimensions and weights indicated in the table


below are provided as an example for single
voltage transformers with insulation level 12kV
(1st table) and 24 kV (2nd table), according to
electrical characteristics shown page 1.
Consequently, these tables give you
approximate dimensions and weights for
insulation level from 7.2 to 12kV (1st table) and
from 17.5 to 24kV (2nd table).
Only the definitive drawings following from the
order will commit us contractually.
For other voltages, impedance voltages and
dual-voltages, weights and dimensions are
different (consult us).
.

insulation level 7,2 and 12kV - low voltage 400 to 433V

insulation level 17 and 24kV - low voltage 400 to 433V

france transfo 3
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m
minimum clearances required HV and LV standard connection connections

Trihal transformers
without enclosure housing
(IP 00)
The winding resin coating and the plug-in
connectors dont ensure any protection
against touch when the transformer is
energized.

The contrator must ensure that cables and busbars are


adequately supported to prevent mechanical stresses
from being imposed on the transformer terminals,
busbars or bushings.

minimum clearances required HV and LV standard connection

Trihal transformers
with IP 31 metal enclosure

*500 mm. for an access to tapping on the HV side,


but 200 mm. minimum.

LV terminations

HV terminations

160 400 kVA* 500 800 kVA* 1000 1250 kVA*


thickness 5 thickness 5 thickness 10

The contrator must ensure that cables and busbars are


adequately supported to prevent mechanical stresses
from being imposed on the transformer terminals,
busbars or bushings.
1600 kVA* 2000 kVA* thickness 10
thickness 12 2500 kVA* thickness 2 X 10
* valid for aluminium terminations

Schneider Electric Industries SAS


Adresse postale : Due to the evolution of standards and materials, the
france transfo present document will bind us only after confirmation
BP 10140 from technical department.
F-57281
Maizires-ls-Metz cedex
France
tl : 33 (0)3 87 70 57 57
fax: 33 (0)3 87 51 10 16
http://www.schneider-electric.com GEa 126 b 04/2005