standards
In accordance with standards :
IEC 60076-1 to 60076-5;
s
sse
IEC 60076-11 (2004);
uce
standardization) harmonization documents HD 538-1 S1:
(*) the rated power is defined by natural air cooling (AN). (3) reminder of insulation levels :
Should there be particular constraints, it may be increased rated insulation
by 40 % by forced cooling addition (AF). Please consult us.
(1) other possibilities upon request, consult us.
level (kV) 7,2 12 18 24
(2) non standard ratings available on request. kV r.m.s. 50Hz - 1mn 20 28 38 50
kV B.I.L. 1,2/50 s 60 75 95 125
France Transfo
(4) according to CEI 551.
is becoming (5) according to CEI 270.
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m
2 france transfo
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m
france transfo 3
HV/LV distribution transformers
TRIHAL cast resin dry type transformers 160 to 2500 kVA
insulation level 24 kV - low voltage 400 to 433 V - 50 Hz
thermal class F - ambient 40C, altitude 1000 m
minimum clearances required HV and LV standard connection connections
Trihal transformers
without enclosure housing
(IP 00)
The winding resin coating and the plug-in
connectors dont ensure any protection
against touch when the transformer is
energized.
Trihal transformers
with IP 31 metal enclosure
LV terminations
HV terminations