Você está na página 1de 4

PANWATER ENGINEERING SDN BHD (Company No.

173663-M)

Lot 2321, AL 49, Kampung Baru Sungai Buluh,


47000, Selangor Darul Ehsan, MALAYSIA.
Tel : 603-61579399 (Hunting Line) Fax: 603-61570399
E-mail:panwater@panwater.com
Website: www.panwater.com

Client: COOLING TOWER PROPOSAL


PT. Pasadena Engineering Indonesia Enquiry Ref: Email
Wisma Bumiputera 9th Floor Proposal No: PCT/11309/Q3
Jl. Jend. Sudirman Kav. 75, Proposal Date: 3-Jun-2015
Jakarta Selatan 12910 Telephone: 62 21 5701637 & 5701643
Indonesia Facsmile: 62 21 526 0675
For Attention Of: Mr. Rachmat Shiddekh Mobile: Email: pei@pasadenagroups.biz
Project Title : Cooling Tower Proposal For Biogas Plant
Item No. / Designation Cooling Tower
Cooling Tower Type FRP Cross Flow PP Tri Bars Splash Filled
Cooling Tower Application POME
Cooling Tower Model PET 355-FC1
Quantity Required 2 Sets
No. of cells per tower 1 Cells
Total Circulation Flow Rate 50 m/hour
Circulation Flow Rate Per Cell 50 m/hour
Inlet Temperature 80 C
Outlet Temperature 40 C
Wet Bulb Temperature 28 C
Fan Motor Power Per Tower 5.5 Kw
Total Heat Rejection Load 2,000,000 Kcal/hour
Price per set Ex-Panwater Factory USD 10,200
Total Price Ex-Panwater Factory USD 20,400
Inland hauliage to Port Klang USD 400
Port charges, forwarding & docs. fees USD 200
Ocean Freight charges to Jakarta USD 300
Total Price CIF Port USD 21,300
Remarks :
1. Price quoted exclude supervision of installation. Per diem rate for supervisory service is USD 100 per day.
2. Two way air tickets, local expenses such as transportation, hotel and food for the erection supervisor are to be provided by the customer.
3. All local manpower, tools and equipment for the complete installation of the cooling towers are to be provided by the customer.
4. Estimated total shipping volume for proposed cooling tower is by 1 unit containers.
5. Estimated duration for erection of cooling tower by others is 6 days.
WARRANTY:
Panwater guarantees its products for a period of one year from date of commissioning or 18 months from date of shipment against manufacturing defects in material or
workmanship. During this warranty period, Panwater will repair or replace, at its option, parts found to be defective under normal use when the equipment is installed and
operated in accordance with Panwater's instructions and good engineering practice. This warranty is void if the equipment is operating in environment or with fluids not
compatible with the materials supplied or at pressures and temperatures outside of the stated operating range.
Commercial Terms & Conditions
Delivery Period: The cooling towers shall be ready for delivery 10 weeks upon confirmation of order together with down payment..
Payment Terms: Down payment of 20% upon confirmation of order, balance by Irrevocabale Letter of Credit at sight within 30 days after order confirmation.
Validity Period: Price quoted shall be valid for 30 days from date of this offer and shall be fixed and firmed through the duration of delivery period.
Price Currency: Price quoted in US Dollars.

For & On Behalf Of


PANWATER ENGINEERING SDN BHD

H. C. Koh
Koh Hang Chuang
Mobile: +6012-215 3308
Email: hckoh@panwater.com
Client PT. Pasadena Engineering Indonesia COOLING TOWER SPECIFICATION
Project Biogas Plant Proposal Date: 31-May-2015
Location Indonesia Purchase Date:
Item No. Cooling Tower Delivery Date:
Reference No. 11309 Commissioning Date:
Tower Performance General Data
Tower Model PET 355-FC1 Tower Type Induced Draft Cross Flow
No. of Cells Per Tower 1 Cells Total Brake Horsepower 5 Kw
Deisgn Flow Rate 50 M/Hour Fill Packing Type PP Tri Bars
Inlet Temperature 80.0 C Drift Eliminator Type PD18 Cellular PVC
Outlet Temperature 40.0 C Water Distribution Type Gravity Target Nozzles
Wet Bulb Temperature 28.0 C Inlet Connections Per cells One Per Cell
Cooling Range 40.0 C Pump Head Required 7.9 M
Approach To Wet Bulb 12.0 C Inlet Connections Size 4" ANSI Flange
Total Heat Rejection 2,000,000 Kcal/Hour Access To Fan Deck HDG Steel Ladder
Total Cooling Capcity 2,326 Kw Estimated Shipping Volume 12 M
Evaporation Loss 6% Estimated Shipping Weight 3,600 Kgs
Drift Loss 0.02 % Operating Weight Exclude Basin 5,100 Kgs
Service Water Quality Process Water Country Of Origin Malaysia

Tower Dimensions Axial Flow Fan Specification


Overall Tower Length 2.60 M No. Per Cell One Per Cell
Overall Tower Width 5.47 M Manufacturer Panwater
Overall Tower Heigth 4.96 M Nominal Fan Diameter 1.53 M
Fan Stack Height 1.20 M No. Of Blades Per Fan 5 Blades
Basin Curb To Deck Height 2.56 M Operating Speed 722 RPM
Basin Curb To Inlet Height 2.78 M Total Air Delivery Per Fan 906 M/min
Internal Basin Length 2.69 M BHP At Duty Per Fan 4.7 Kw
Internal Basin Width 3.81 M Fan Blade Materials Aluminium Alloy
Internal Basin Height 1.2 M Fan Hub Mateials Aluminium Alloy
Water Basin Holding Volume 10.6 M Fan Assembly Hardwares SS 304 Stainless Steel

Materials Of Construction Electric Motor Specification


Tower Framework FRP Pultrusions No. Per Cell One Per Cell
Fan Deck Molded FRP Manufacturer Marathon
Perimeter Handrail FRP Pultrusions Type TEFC To IEC
Splash Bars Extruded Polypropyene Insulation Class F
Splash Bars Supporting Grids SS 304 Stainless Steel Enclosure IP 55
Drift Eliminators Extruded Polypropyene Rated Motor Power 5.5 Kw
Fan Stack FRP Full Load Speed 722 RPM
Hot Water Basin FRP Electrical Supply 380V/3 Phase/50 Hz
Hot Water Splash Box FRP
Target Nozzles Polypropylene Speed Reducer Specification
External Cladding FRP No. Per Cell Not Applicable
Air Inlet Louvers FRP Speed Reducer Manufacturer Not Applicable
Fan Machinery Supports SS 304 Stainless Steel Speed Reducer Type Not Applicable
Structural Fasteners SS 304 Stainless Steel Speed Reducer Model Not Applicable
Footing Brackets SS 304 Stainless Steel Speed Reduction Ratio Not Applicable
Anchor Bolts SS 304 Stainless Steel No. Of Reduction Not Applicable
Cold Water Basin & Foundation RC Concrete By Buyer

Specifications and dimensions contain herein subject to verification. Panwater reserves the right to alter the specifcations and dimensions in the interest of product improvement.