Rough design

16. Lightning system

16.1. Vietnam standard

16.1.1. Requested building

Over 7m height building

Any explosion material store

16.1.2. Air terminal

Galvanized steel rod

> 100mm2 (D12) for section area

> 3000mm for height

16.1.3. Conductor

Steel rod (galvanized)

> 50mm2 (D12)

Connected by welding

Supporting clamp or saddle made by brass or copper tape

16.1.4. Down conductor

5m from GL covered by PVC pipe

Min. 2 down conductor

16.1.5. Electrode

L63x63x6tx2500 (galvanized) or copper plated D20 x 2500L

Connected by welding

Max 30ohm/1 point

16.1.6. Connection : full weld more than 50mm

16.1.7. Explosion / flammable material store

Lightning mast shall be used for oil, gasoline, gas tank including underground
tank.

Page 225
Rough design

16.2 KDVN standard

16.2.1 Design methods

Rolling sphere method

Fig.1

Table 1 Table 2

Page 226
Rough design

Mesh method

TCXDVN-46 20m x 10m

Table 3

Angle method

Fig. 2

Page 227
Rough design

Fig. 3

Fig. 4

Page 228
Table 4

51
Page 229
Rough design

16.2.2 Conductor & Down conductor

Distance between down conductors

TCXDVN-46 20m

Table 5

Table 6

Page 230
Rough design

Table 7

Page 231
Rough design

Fig. 5 Fig. 6

Fig. 7

Fig. 8 Fig.9

Page 232
Rough design

16.2.3 Earth electrode


Earth resisrance system < 10 ohm ( TCXDVN 46-2007).
Fig. 10 show specific earth resistance.

Fig. 10
Table 8 show formula for calculating earth resistance

Table 8

Page 233
Rough design

Table 9

Page 234
TCXDVN 46 : 2007

Khi la chn vt liu, cn xem xt nguy c b n mn bao gm n mn in ho. i vi vic bo v


dy dn, cn ch lp bo v chng li s n mn trong mi trng khc nghit, v d:
a) Ph dy dn bng ch dy t nht 2mm trn nh ng khi. Bc ch c hai u v ti cc im
ni
b) Nu c th th b phn thu st nn trn, nu khng c th dng lp PVC mng 1mm
bc trong trng hp cn chng g (c bit i vi nhm).
Cc mi ni trong c th c din tch mt ct bng khong mt na mi ni ngoi (xem 12.10.2). Cc
mi ni mm do c th c s dng nhng cn tun theo tiu chun TCXD 25:1991.
6.2 Kch thc
Kch thc ca cc b phn hp thnh trong mt h thng chng st cn m bo cc yu cu nu
trong Bng 1 v Bng 2. dy ca cc tm kim loi s dng trn mi nh v to thnh mt phn ca
h thng chng st cn m bo yu cu trong Bng 3.

Bng 1. Vt liu, cu to v din tch tit din ti thiu ca kim thu st, dy dn st, dy xung
v thanh chn di t
Din tch tit
Vt liu Cu to Ghi ch
din ti thiua
Dy dt c 50 mm chiu dy ti thiu 2 mm
ng Dy trn ce 50 mm ng knh 8 mm
Cp 50 mm ng knh ti thiu ca mi si 1,7 mm
f,g
Dy trn c 200 mm ng knh 16 mm
Dy dt c 50 mm chiu dy ti thiu 2 mm
ng ph thicb Dy trn ce 50 mm ng knh 8 mm
Cp 50 mm ng knh ti thiu ca mi si 1,7 mm
Dy trn cf,g 200 mm ng knh 16 mm
Dy dt c 70 mm chiu dy ti thiu 3 mm
Nhm
Dy trn c 50 mm ng knh 8 mm
Cp 50 mm ng knh ti thiu ca mi si 1,7 mm
Dy dt c 50 mm chiu dy ti thiu 2,5 mm
Dy trn c 50 mm ng knh 8 mm
Hp kim nhm
Cp 50 mm ng knh ti thiu ca mi si 1,7 mm
Dy trn cf 200 mm ng knh 16 mm
Dy dt c 50 mm chiu dy ti thiu 2,5 mm
Dy trn c 50 mm ng knh 8 mm
Thp m kmc
Cp 50 mm ng knh ti thiu ca mi si 1,7 mm
Dy trn cf,g 200 mm ng knh 16 mm
d h
Thp khng g Dy dt c 50 mm chiu dy ti thiu 2 mm

4
Page 235
TCXDVN 46 : 2007

Din tch tit


Vt liu Cu to Ghi ch
din ti thiua
Dy trn ch 50 mm ng knh 8 mm
Cp 70 mm ng knh ti thiu ca mi si 1,7 mm
Dy trn cf,g 200 mm ng knh 16 mm
a
Sai s cho php: - 3 %.
b
Nhng nng hoc ph in, chiu dy lp ph ti thiu l 1 micron.
c
Lp ph phi nhn, lin tc v khng c vt sn vi chiu dy danh nh l 50 microns.
d
Chromium 16 %; Nickel 8 %; Carbon 0,07 %.
e
50 mm (ng knh 8 mm) c th gim xung 28 mm (ng knh 6 mm) trong mt s trng hp khng
yu cu sc bn c hc cao. Trong trng hp cn lu gim khong cch gia cc im c nh.
f
Ch p dng cho kim thu st. Trng hp ng sut pht sinh do ti trng nh gi gy ra khng ln th c th
s dng kim thu st di ti a ti 1m ng knh 10mm
g
Ch p dng cho thanh cm xung t.
h
Nu phi quan tm c bit ti vn c v nhit th cc gi tr trn cn tng ln 78 mm (ng knh 10
mm) i vi dy trn c v 75 mm (dy ti thiu 3 mm) i vi thanh dt c.

Bng 2. Vt liu, cu to v kch thc ti thiu ca cc ni t


Kch thc ti thiua
Vt liu Cu to Ghi ch
Cc ni t Dy ni t Tm ni t
ng knh ti thiu ca
Cpb 50 mm2
mi si 1,7 mm
Dy trn cb 50 mm2 ng knh 8 mm
b 2
Dy dt c 50 mm chiu dy ti thiu 2 mm
ng knh
Dy trn c
15 mm
ng
ng knh chiu dy thnh ng ti
ng
20 mm thiu 2 mm
500 mm x 500
Tm c chiu dy ti thiu 2 mm
mm
600 mm x 600
Tm mt co tit din 25 mm x 2 mm
mm
Dy trn c ng knh ng knh
Thp
m kmc 16 mmd 10 mm
ng knh chiu dy thnh ng ti
ng m kmc
25 mmd thiu 2 mm
Dy dt c
90 mm2 chiu dy ti thiu 3 mm
m kmc
Tm c m 500 mm x 500
chiu dy ti thiu 3 mm
kmc mm
Tm mt co 600 mm x 600
tit din 30 mm x 3 mm
m kmc mm

5
Page 236
TCXDVN 46 : 2007

Kch thc ti thiua


Vt liu Cu to Ghi ch
Cc ni t Dy ni t Tm ni t
Dy trn c ng knh m ng 99,9 % ng, dy
m ngce 14 mm ti thiu 250 microns
Dy trn c ng knh
khng mf 10 mm
Dy dt c
trn hoc m 75 mm2 chiu dy ti thiu 3 mm
kmf,g
Cp m ng knh ti thiu ca
70 mm2
kmf,g mi si 1,7 mm
Thp ng m 50 mm x50
kmc mm x 3 mm
ng knh ng knh
Thp Dy trn c
16 mm 10 mm
khng g
Dy dt c 100 mm chiu dy ti thiu 2 mm
a
Sai s cho php: - 3 %.
b
C th ph bng thic.
c
Lp ph phi nhn, lin tc v khng c vt sn vi chiu dy danh nh l 50 microns i vi vt liu trn v
70 microns i vi vt liu dt.
d
Chn ng cn c tin trc khi m km.
e
ng cn c lin kt vi li thp.
f
Ch cho php khi hon ton chn trong b tng.
g
Ch cho php khi c lin kt tt ti cc im cch nhau khng qu 5m vi ct thp nhng b phn mng
c tip xc vi t

Bng 3. dy ti thiu ca tm kim loi s dng lp mi nh v to thnh mt phn ca h


thng chng st.
Vt liu dy ti thiu (mm)
Thp m 0,5
Thp khng g 0,4
ng 0,3
Nhm v Km 0,7
Ch 2,0
GHI CH: Cc s liu trong bng ny l hp l khi mi nh l mt phn ca h thng chng st. Tuy nhin vn
c nguy c tm kim loi b nh thng i vi cc c st nh thng.

6
Page 237
Rough design

16.2.2. For factory (Vietnamese method)

Note:
o Use for under 4000m2 factory
o All materials to be hot dip galvanized

20m

Page 238
Rough design

16.3. Early Streamer Emission Lightning protection system (ESET)

16.3.1. This system intercepts lightning discharge earlier than general system

16.3.2. System condition

16.3.2.1. ESET shall be installed on minimum 10m height from grounding level

16.3.2.2. ESET shall be minimum 3 meter higher from highest point of building or structure
including antenna, fence, equipment, tank and others

16.3.2.3. ESET shall be isolated from building, structure and connected to grounding directly.
Fiber glass pole
PVC sheathed copper wire

16.3.2.4. Grounding and conductor


1 or 2 set grounding for 1 set ESET
Grounding resistance < 4
Electrode: use minimum 5 electrode for 1 grounding point
Conductor: PVC sheathed copper wire 50mm2

16.3.3. Protection radius (reference)

16.3.3.1. Condition
R: protection radius (m) at highest point of building
h: ESET height (m) above highest point of building
H: Height of structure (m)

Page 239
Rough design

16.3.3.2. Early Streamer Emission Terminal Type (ESET) protection radius (m) table

System 3000 Interceptor EF carrier


Air Indelec system
Bld. Mast
height height Terminal S 4.50 S 3.40 TS 3.40 TS 2.25 > >
height S 6.60 10kA 6.5kA
m m Standard High Standard High Standard High Standard High Standard High Standard High
m level level level level level level 85% 93% 98% level level 93% 98%

10 5 15 70 60 50 50 35 68 60 43 63 48 43 33

15 5 20 74 64 54 54 39 78 66 43 70 56 - -

20 5 25 79 68 58 58 42 82 74 50 72 63 53 41

25 5 30 83 72 62 62 46 89 80 55 78 67 - -

30 5 35 86 76 65 65 49 96 86 59 83 70 63 48

40 5 45 94 83 72 72 55 105 90 67 83 70 70 53

50 5 55 100 89 78 78 60 112 100 75 83 70 75 54

60 5 65 107 95 84 84 65 118 110 80 83 70 77 55

100 5 105 129 116 103 103 81 112 100 75 - - 81 49

150 5 155 152 138 123 123 98 - - - - - 77 44

Page 240
Rough design

16.3.3.3. Protection level


High level protection should be selected for building containing vital communication,
computer or sensitive equipments and hospital, airport structure

16.3.4. Sample drawing for each Manufacture (Refer to 16.3.4.1, 2, 3, 4)

SYSTEM 3000 - TYPICAL INSTALLATION OF DYNASSPHERE AIR-TERMINATION

Page 241
Protection Performance
Rp3
The protection radius (Rp) of a Stormaster ESE terminal is h1 Rp2
calculated using the following formula as defined by the French Rp1
National Standard NF C 17-102 (July 1995). h2

Rp = h(2D-h) + T(2D + T) for 5m where: h3

The following key parameters determine the calculation of RP.


T as established during the test.
Stormaster-ESE-50 = T (s) 50
L Stormaster-ESE-60 = T (s) 60
h = actual height of Stormaster terminal above the area to be
protected (m).
D (in m) depends on the selected level of protection,
protection levels are specified in annex B of the standard
NF C 17-102.
D = 20m for protection level 1 (High Protection)
D = 45m for protection level 2 (Medium protection)
D = 60m for protection level 3 (Standard protection)

PROTECTION RADIUS (M) - (Rp)


h = height of Stormaster terminal 2 4 5 6 10 15 20 45 60
above area to be protected (m)
Protection Level 1 (High Protection)
Stormaster 50 28 55 68 69 69 70 70 - -
Stormaster 60 32 64 79 79 79 80 80 - -
Protection Level 2 (Medium Protection)
Stormaster 50 35 69 86 87 88 90 92 95 -
Stormaster 60 40 78 97 97 99 101 102 105
Protection Level 3 (Standard Protection)
Stormaster 50 38 76 95 96 98 100 102 110 110
Stormaster 60 44 87 107 107 109 111 113 120 120

Research and Development


The company has an ongoing commitment to Research and
Development.

LPI personnel and its associates have been involved in a number of field
trials throughout lightning prone regions of the world. This experience
has extended throughout such countries as Australia, Indonesia, Sri Lanka
the USA and South Korea.

Page 242