ELECTROMAGNETIC
FLOWMETER

ELECTROMAGNETIC FLOWMETER 1
www.flotech.com.sg

EFS800 - CFT180/RFT200
ELECTROMAGNETIC FLOWMETER

Accurate, Reliable and Stable Flow


Measurement.

Measuring Principle
The measuring principle of the electromagnetic flowmeter (Magmeter) is based upon the Faradays Law of
electromagnetic induction; whereby a voltage is induced by an electrical conductor passing through a magnetic field.

The following equation is applicable to the induced voltage: U = kBVD where

U Induced voltage
k Instrument constant
B Magnetic field strength
V Velocity of the conductor
D Conductor width

In electromagnetic flowmeter, the medium acts as the


electrical conductor when flowing through the meter tube,
the induced voltage is proportional to the average flow
velocity (the faster the flow rate, the higher the voltage).
The induced voltage is picked up by a pair of electrodes
(mounted in the meter tube) and transmitted to a flow
transmitter to produce various standardized output
signals.

Using the pipe cross-sectional area, the flow volume is


calculated by the transmitter.

Applications
iSOLV electromagnetic flowmeter can be used for precise flow measurement of all electrically
conductive liquids - sludges, slurries, sewage, milk, water. The only pre-requisite being that the minimum
conductivity of the medium is greater than 5S/cm. Temperature, viscosity, density has no
influence on the measurement.

With isolated inert linings and electrodes, Flow measurement of very corrosive liquids (eg: acids,
accaustics and corrosive chemicals) is not an issue.

iSOLV electromagnetic flowmeter has many applications across many industries environment.

Chemical Water/wastewater
Pulp and paper
Pharmaceutical Building automation (HVAC)
Food and beverage

ELECTROMAGNETIC FLOWMETER 2
www.flotech.com.sg

Specification
EFS 800/CFT180 Integral Remote Flow Transmitter EFS800 Flowhead
Performance Flow Transmitter RFT200
Accuracy +/- 0.3% to 0.5%
Repeatability +/- 0.1%
Full Scale Range Setting 0.5 m/s to 10 m/s
Fluid Conductivity > 5S/cm
Power Consumption <20 VA
Fluid Temperature -25oC to 180oC (Depending On Liner Material & Coil Insulation Class)
Ambient Temperature -20oC to 60oC
Relative Humidity 0 - 97%
Calibration Certificate Wet Calibration 3 Points (Additional Test Points Upon Request)

Sensor
Model EFS 800

Process Connection
Size DN10-DN3800
Type Flange DIN 2501/ ANSI/JIS
Pressure Rating Refer To Page 5 & 6. Higher Pressure Rating Available On Request

Material
Tube SS304
Liner (Wetted Parts) Hard Rubber (Std) / PTFE/ Others On Request
Signal Electrode (Wetted Parts) SS316 (Std)/ Hastelloy C/ Tantalum/ Titanium
Process - Flange Carbon Steel (Std)/ SS304 (Optional With Price Adder)
Housing DN 10 to DN 300: Die-Cast Aluminium With Epoxy Paint
DN 350 to DN 3800: Steel With Epoxy Paint
Grounding Rings SS304 (Std) / SS316
Flow Direction Bi-directional (Forward / Reverse)
Field Coils E class = 130oC
H class = 180oC
Protection Class IP 67 / IP 68

Optional
Removable Electrode Construction Available (Upon Request)
3rd Electrode For None Full Bore Detection Available (Upon Request)

Transmitter
Housing Type Remote Integral
Model No RFT200 CFT180
Power Supply 8 5 253 VAC, 18 36 VDC
Display 2 x 16 Alpha Numeric Character LCD

Outputs
Current 4-20mA
Pulse <5kHz Frequency D. C.
Contact Relay 1 no for Alarm/ Empty Pipe
Communications Available On Request: HART/ Profibus DP/ Profibus PA/
Foundation Fieldbus/ RS485
Housing Material Aluminium Alloy
Protection Class IP65 IP67
Cable Length 10m (Std) Other Length NA
Available up to 50m
Cable Entry M20 X 1.5 (Std) / NPT / PF
ELECTROMAGNETIC FLOWMETER 3
www.flotech.com.sg

Flowmeter Sizing and Selection


Proper selection, sizing and installation of electromagnetic flowmeter will ensure trouble free operation and cost
saving. The following information will be required.

1) Type of liquid consider suitability of liner and electrodes


2) Conductivity = 5S/cm
3) Maximum / minimum temperature
4) Maximum / minimum pressure. Negative pressure?
5) Maximum / minimum flow rates
6) Solids content

Flow Table

Meter Size Qmin (m3/h) Qmax (m3/h)


10 0.14 2.83
15 0.32 6.36
20 0.57 11.31
25 0.88 17.67
32 1.45 28.95
40 2.26 45.24
50 3.53 70.69
65 5.97 119.46
80 9.05 180.96
100 14.14 282.74
125 22.09 441.79
150 31.81 636.17
200 56.55 1,130.97
250 88.36 1,767.15
300 127.23 2,544.69
350 173.18 3,463.61
400 226.19 4,523.89
450 286.28 5,725.55
500 353.43 7,068.58
600 508.94 10,178.76
700 692.72 13,854.42
800 904.78 18,095.57
900 1,145.11 22,902.21
1000 1,413.72 28,274.33
1200 2,035.75 40,715.04
1400 2,770.88 55,417.69
1600 3,619.11 72,382.29
1800 4,580.44 91,608.84
2000 5,654.87 113,097.34
2200 6,842.39 136,847.78
2400 8,143.01 162,860.16
2600 9,556.72 191,134.50
2800 11,083.54 221,670.78
3000 12,723.45 254,469.00

ELECTROMAGNETIC FLOWMETER 4
www.flotech.com.sg

Dimension
Dimensions for integral flow transmitter and flow sensor

Size *Pressure Rating **Dimensions (mm)


(mm) PN A D D0 n-x
10 40 200 90 60 4-14
15 40 200 95 65 4-14
20 40 200 105 75 4-14
25 40 200 115 85 4-14
32 40 200 140 100 4-18
40 40 200 150 110 4-18
50 40 200 165 125 4-18
65 40 200 185 145 8-18
80 40 200 200 160 8-18
100 16 250 220 180 8-18
125 16 250 250 210 8-18
150 16 300 285 240 8-22
200 10 350 340 295 8-22
250 10 450 395 350 12-22
300 10 500 445 400 12-22
350 10 500 505 460 16-22
400 10 600 565 515 16-26
450 10 600 615 565 20-26
500 10 600 670 620 20-26
600 10 600 780 725 20-30
700 10 700 895 840 24-30
800 10 800 1015 950 24-33
900 10 900 1115 1050 28-33
1000 10 1000 1230 1160 28-36

* Please request for drawing for dimension of other Pressure Rating.


** Dimensions are based on DIN2501 standards.

85 205

35

n-x
D0

EFS 800 / CFT180

ELECTROMAGNETIC FLOWMETER 5
www.flotech.com.sg

Dimensions for remote flow sensor

Size *Pressure Rating **Dimensions (mm)


(mm) PN A D D0 n-x
10 40 200 90 60 4-14
15 40 200 95 65 4-14
20 40 200 105 75 4-14
25 40 200 115 85 4-14
32 40 200 140 100 4-18
40 40 200 150 110 4-18
50 40 200 165 125 4-18
65 40 200 185 145 8-18
80 40 200 200 160 8-18
100 16 250 220 180 8-18
125 16 250 250 210 8-18
150 16 300 285 240 8-22
200 10 350 340 295 8-22
250 10 450 395 350 12-22
300 10 500 445 400 12-22
350 10 500 505 460 16-22
400 10 600 565 515 16-26
450 10 600 615 565 20-26
500 10 600 670 620 20-26
600 10 600 780 725 20-30
700 10 700 895 840 24-30
800 10 800 1015 950 24-33
900 10 900 1115 1050 28-33
1000 10 1000 1230 1160 28-36
1200 6 1200 1405 1340 32-33
1400 6 1400 1630 1560 36-36
1600 6 1600 1830 1760 40-36
1800 6 1800 2045 1970 44-39
2000 6 2000 2265 2180 48-42
2200 2.5 2200 2405 2340 52-33
2400 2.5 2400 2605 2540 56-33
2600 2.5 2600 2805 2740 60-33
2800 2.5 2800 3030 2960 64-36
3000 2.5 3000 3230 3160 68-36
>3200 2.5 Upon Request

* Please request for drawing for dimensions of Higher Pressure Rating.


** Dimensions are based on DIN2501standards.

n-x

D0

A
EFS 800 / RFT 200

ELECTROMAGNETIC FLOWMETER 6
www.flotech.com.sg

Primary flow sensor in metal pipe

1) Measuring ground
2) Grounding wire 10mm2Cu (AWG 7)

Primary flow sensor in plastic pipe or in metal pipe with insulating


coating / lining / painting

1) Measuring ground
2) Grounding wire 10mm2Cu (AWG 7)
3) Grounding rings

Primary flow sensor in pipe runs with cathodic protection


5
Primary flow sensor must be electrically isolated from the pipe. Protective
rings for good grounding are compulsory.
1) Measuring ground
2) Grounding wire 10mm2Cu (AWG 7)
3) Grounding rings
4) Screw bolts (insulated)
5) Connecting wire 10mm2Cu (AWG 7)

Installation
Location and position as required, but electrode axis ( x......x )
must be approximately horizontal.

Pipe must be completely filled at all times.


Flow direction - Avoid top / bottom
Ensure there is sufficient clearance for installation and
maintenance work.

Straight inlet run minimum of 5xDN and outlet 2xDN (DN=


meter size) measured from the electrode axis.

Support the pipeline on both sides of the flowmeter to minimise


vibrations.
Do not install flowmeter in vicinity of strong electromagnetic fields.
Example: High-tension electrical cables
Install protective rings for plastic pipes and internally coated metal
pipelines for proper grounding.

ELECTROMAGNETIC FLOWMETER 7
www.flotech.com.sg

Some Typical Installations

A & B - Preferred locations. (Pipe is fully filled!)


C - Highest point of pipe run (Air bubbles
accumulate in measuring tube causing incorrect
or unstable measurements)
D - Top/bottom flow direction to drain does not
create a fully filled pipe condition causing unstable
or inaccurate reading.

Install in slightly ascending pipe section. If not


possible, ensure adequate velocity to prevent air,
gas or vapour from concentrating in the flow
sensor.

Install flow sensor in lower section of pipe.

Install air valve downstream of flowmeter.


Negative pressure (Vacuum) may damage the
liner.

Always install control and shutoff valves


downstream of flowmeter to avoid flow profile
distortion or possible negative pressure (Vacuum)

Never install flow sensor on pump suction side


(Vacuum!). May cause damage to the liner.

Install flowmeter in bypass for heavily


contaminated fluids. 2
A) Flowmeter
B) Flushing and cleaning without interrupting
system operation

ELECTROMAGNETIC FLOWMETER 8
www.flotech.com.sg

Ordering Information

CFT18 - Compact Version RFT200 - Remote Version


(Example) EFS800 EFS800

R20 Version
C18 - Compact (CFT180) [DN10 - DN1000]
R20 - Remote (RFT 200) [DN10 - DN3800]

W Electronic Type
XM - XEM Version (Selection meter size btw DN1000 - DN3800)
[High Temp coil & refer to In/ Output options]
XE - XE Version (Selection meter size btw DN10 - DN1000)
[High Temp coil & refer to In/Output options]
W - WT4300 (Selection meter size btw DN10 - DN1000)
[In/Output options 0 and 03 only]

H Liner
H - Hard Rubber (std) [for Meter Size from DN25 to DN3800] (max temp < 90 C)
T - PTFE [for Meter Size from DN10- DN900] (max temp < 200 C)

15 Meter Size
10 - 3/8" (DN10 PN40) 7H - 28 (DN700 PN10)
15 - 1/2" (DN15 PN40) 8H - 32 (DN800 PN10)
20 - 3/4" (DN20 PN40) 9H - 36 (DN900 PN10)
25 - 1" (DN25 PN40) 1T - 40 (DN1000 PN10)
32 - 1 1/4" (DN32 PN40) 12 - 48 (DN1200 PN6)
40 - 1 1/2" (DN40 PN40) 14 - 56 (DN1400 PN6)
50 - 2" (DN50 PN40)
16 - 64 (DN1600 PN6)
65 - 2 1/2" (DN65 PN40)
18 - 72 (DN1800 PN6)
80 - 3" (DN80 PN40)
1H - 4" (DN100 PN16) 2T - 80 (DN2000 PN6)
1Q - 5" (DN125 PN16) 22 - 88 (DN2200 PN2.5)
1F - 6 (DN150 PN16) 24 - 96 (DN2400 PN2.5)
2H - 8 (DN200 PN10) 26 - 104 (DN2600 PN2.5)
2F - 10 (DN250 PN10) 28 - 112 (DN2800 PN2.5)
3H - 12 (DN300 PN10) 30 - 120 (DN3000 PN2.5)
3F - 14 (DN350 PN10) 3Q - 128 (DN3200 PN2.5)
4H - 16 (DN400 PN10) 34 - 136 (DN3400 PN2.5)
4F - 18 (DN450 PN10) 36 - 144 (DN3600 PN2.5)
5H - 20 (DN500 PN10) 38 - 152 (DN3800 PN2.5)
6H - 24 (DN600 PN10)

S Electrode
S - SS 316Ti/ 1.4571 (Std)
B - Hastelloy B-2
H - Hastelloy C-4
M - Titanium
T - Tantalum

G Pressure Rating
0 - DIN Standard
B - PN 10
C - PN 16
D - PN 25
E - PN 40
G - ANSI 150 Ibs
F - ANSI 300 lbs
I - ANSI 600 Ibs
A - JIS 10K

Continue to the next page

ELECTROMAGNETIC FLOWMETER 9
www.flotech.com.sg

Ordering Information

(Example) 0 Flange Material


0 - Carbon Steel (Std)
3 - SS 304

C Earthing Rings
0 - None
C - Ground Plate (SS 304) Type 1(Std)
X - Others

15 Earthing Rings Size (Selection based on Meter Size)


0 - None
10 - 3/8" (DN10)
15 - 1/2" (DN15)
20 - 3/4" (DN20)
25 - 1" (DN15)
32 - 1 1/4" (DN32)
40 - 1 1/2" (DN40)
50 - 2" (DN50)
65 - 2 1/2" (DN65)
80 - 3" (DN80)
1H - 4" (DN100)
1Q - 5" (DN125)
1F - 6 (DN150)
2H - 8 (DN200)
2F - 10 (DN250)
3H - 12 (DN300)
3F - 14 (DN350)
4H - 16 (DN400)
4F - 18 (DN450)
5H - 20 (DN500)
6H - 24 (DN600)
7H - 28 (DN700)
8H - 32 (DN800)
9H - 36 (DN900)
1T - 40 (DN1000)
12 - 48 (DN1200)
14 - 56 (DN1400)
16 - 64 (DN1600)
18 - 72 (DN1800)
2T - 80 (DN2000)

H Magnetic Coil Temperature Range


0 - Standard Temperature < 130 oC (Std)
H - High Temperature < or = 180 oC (For H coil option, meter size must come with
PTFE Liner)

0 Protection Class (Primary Sensor Head)


0 - IP 67
3 - IP 68

K Power Supply
0 - 85 - 253 VAC
K - 18 - 36 VDC

Continue to the next page

ELECTROMAGNETIC FLOWMETER 10
www.flotech.com.sg

Ordering Information

(Example) 06 In/ Output Options


0 - Current output + Pulse output active + Contact input + Contact output
(WT4300 only)
02 - Current output + Pulse output active + Contact input + Contact output + HART
protocol (XE / XEM only)
03 - Current output + Pulse output passive + Contact input + Contact output
(WT4300 only)
04 - Current output + Pulse output passive + Contact input + Contact output + HART
protocol (XE / XEM only)
05 - Current output + Pulse output passive + Contact output + RS485
06 - Pulse output passive + Contact output + Profibus DP XE / XEM
14 - Profibus PA 3.0 only
15 - Foundation Fieldbus

0 Cable Gland
0 - Converter housing with threads for cable connector M 20 x 1.5 (Std)
1 - Converter housing with threads for cable connector NPT 1/2"
2 - Converter housing with threads for cable connector PF 1/2"

L20 Cable
0 - None (Compact Transmitter)
C - Cable (Remote Transmitter) - 10m (Std)
LXX - Other length up to 50m (Specify)

Ordering Code: (Example)

EFS800 R20 W H 15 S G 0 C 15 H 0 K

0 0 L20

ELECTROMAGNETIC FLOWMETER 11
www.flotech.com.sg

SALES AND SERVICE


CENTRES

REGIONAL NETWORK

CHINA THAILAND
FLOTECH CONTROLS (SHANGHAI) CO., LTD THAIFLO CONTROLS CO., LTD
Room 316 Huacheng Plaza, No. 1471 Gumei 947 Thosapol Land 3 Building
Road, Minhang District Shanghai China 15th Floor , Moo 12 Bangna- Tr ad Road
(201102) ( KM.3) , Bangna, Bangna, Bangkok 10260
Tel: (86) 21 64593908 Thailand
Fax: (86) 21 64595018 Tel: ( 66) 2 7441 308 - 10
Email: info@flotechshanghai.com Fax: ( 66) 2 7441 311
Email: center @thaiflo.com

: 1471316 Br anch Office Rayong


: 201102 Tel: ( 66) 3 8607 073
: (86) 21 64593908 Fax: ( 66) 3 8608 493
: (86) 21 64595018
: info@flotechshanghai.com
VIETNAM
FLOTECH CONTROLS VIETNAM
INDONESIA REPRESENTATIVE OFFICE
PT F LO T EC H C O N T R O L S IN D O N E S IA Email: info@flotech.com.sg
Komplek Ruk an A rth a G a d in g N ia g a
Blo k F / 7, J ln. Bo u le va rd A rth a G a d in g
J ak art a 14240, In d o n e sia
SINGAPORE - HEAD OFFICE
FLOTECH CONTROLS PTE LTD
Tel: (62) 21 45 8 5 0 7 7 8
438 Tagore Industrial Avenue
Fa x : (62) 21 45 8 5 0 7 7 9
Singapore 787814
Email: s ales jk t@ flo te ch .co .id
Tel: (65) 6553 0366
Fax: (65) 6553 0828
Branc h O ff ic e Pe ka n b a ru
Email: info@flotech.com.sg
Tel : (62) 761 6 7 4 8 3 9
Website: www.flotech.com.sg
Fa x : (62) 761 6 7 8 2 9 5
www.isolv.biz

MALAYSIA
M - FLOTECH CONTROLS SDN BHD
No. 20, Jalan TP 7/6
Taman Perindustrian UEP Subang Jaya
40400 Shah Alam
Selangor Darul Ehsan
M alaysia
Tel: (60) 3 5192 5325/6
Fax: (60) 3 5192 5327
Email: sales@mflotech.com.my

20_1009 Reg. No. 198204457H


ELECTROMAGNETIC FLOWMETER 12

Você também pode gostar