MEZZANINE

(EXISTING)
2 ACU LP6
2 ACU OUTLET

6TH FLOOR

A - 507 (EXISTING)
2 ACU PP5 - B

2 ACU OUTLET

5TH FLOOR

A - 419 PP4B
DP4
A - 418 MAIN: 200AT/225AF , 3P 35KAIC
BRANCHES:
MAIN: 350AT/400AF , 3P 50KAIC
A - 417 20 - 30AT , 2P Bolt-on
BRANCHES:
1 - 150A , MCCB
In Nema-1 Encl. w/ Ground terminals
A - 415 1 - 200A , 3P LUGS ONLY
In Nema-1 Encl. w/ Ground Terminals
A - 413
3 - 80mm
10 ACU PP4A 1 - 14mm GW
MAIN: 150AT/225AF , 3P 35KAIC
10 ACU OUTLET BRANCHES:
IN 50mm PVC PIPE

4 - 40AT , 2P Bolt-on 3 - 80mm


8 - 30AT , 2P Bolt-on 1 - 14mm GW
In Nema-1 Encl. w/ Ground terminals IN 50mm PVC PIPE
4TH FLOOR via 100 X 100mm CT

A - 311 A - 316 PP3


MAIN: 200AT/225AF , 3P 35KAIC
A - 313 A- 322 BRANCHES:
A - 318 A - 324 20 - 30AT , 2P Bolt-on
In Nema-1 Encl. w/ Ground terminals
A - 319 A - 326
A - 320 A - 314

20 ACU 3 - 80mm
3 - 60mm
1 - 14mm GW
20 ACU OUTLET IN 50mm PVC PIPE 1 - 8.0mm GW
IN 50mm PVC PIPE

3RD FLOOR

A - 211
A - 213 100 AT , 3P
PP2
A - 215 DP2/3
MAIN: 250AT/300AF , 3P 50KAIC
BRANCHES:
6 ACU 1 - 100A , 3P LUGS ONLY
1 - 200A , 3P LUGS ONLY
6 ACU OUTLET In Nema-1 Encl. w/ Ground terminals
3 - 30mm
1 - 14mm GW
IN 65mm PVC PIPE

2ND FLOOR

3 - 125mm
1 - 14mm GW
NOTE: IN 65mm PVC PIPE
TO BE SUPPLY & INSTALL
BY ELECT'L CONTRACTOR

1200AT, 3P
LVSG
GROUND FLOOR (EXISTING)

ARLEGUI AIRCON RISER DIAGRAM


SCALE NTS

Designed by: ECC Engineer: Project Title: Sheet Content: Project Owner: Sheet Content:
Edgardo C. Chua
Registered Electrical Engineer
TECHNOLOGICAL INSTITUTE
ARLEGUI AIRCON
Checked by: ECC Reg. No. TIN No.
ARLEGUI AIRCON RISER DIAGRAM OF THE EE-101
0002084 165-077-849
PHILIPPINES
Date: Date Issued: