LIGHTNING ARRESTERS

Sl.
Description LIGHTNING ARRESTERS
No.
01 Makers Name and place M/s Oblum Electrical Industries
of manufacture Pvt Ltd., Hyderabad
02 a)Type of Construction Gapless type
b)Type of Mounting Pedestal
c)Model ZAQ
03 a)Rated Voltage KV (rms) 216kV
b)Reference voltage KV (rms) Greater than the rated voltage
of arrester
04 Maximum continuous Operating 168kV (rms)
Voltage KV (rms)
05 Nominal Discharge Current 10kA
(8/20 microsecond wave)
06 KA
Min. Discharge capability 8 kJ/kV (OD 2 shots)
07 Rated Frequency 50Hz
08 a) IR at MCOV Less than 400A
b) IC at MCOV About 1400A
09 a) Reference current, mA 3mA
b) Reference volt at Greater than the rated voltage
reference current of arrester
10 Max. residual voltage in KV
(Peak) 8/20 microsecond wave
at 5000 amps. 550kVPeak
b) at 10000 amps. 600kVPeak
c) at 20000 amps. 668kVPeak
d) Max. partial Less than 10pC
discharge (Pico
11 Max. coulombs)
Switching Impulse Residual 496kVPeak
Voltage (KVp)
12 Max. Steep Current Impulse RDV 668kVPeak
(KVp)
13 Impulse High Current short
duration discharge Amps. (4/10 100kA
microsecond wave) KA
14
T.O.V. (KVP)
a) 0.1 second 382kVPeak
b) 1.0 second 366kVPeak
351kVPeak
c) 10.0 second
1
Sl.
Description LIGHTNING ARRESTERS
No.
d) 100.0 second 336kVPeak

15 Insulation
withstand 1050kVPeak
a) Lightning IMP (Dry) (KVp)
460kV (rms)
b) Power frequency with stand
Voltage KV (rms)
Dry/Wet 700kVPeak
c) Switching Impulse Wet (KVp)
16 Pressure Relief Class Class - A
17 PR Relief Class KA (RMS) 40kA
18 Long Duration Current Impulse
Test 600A
a) Current Peak Amps. 2400 sec

19 b)
a) Virtual
Leakage Duration
current Micro
at Sec. Will be supplied later
normal voltage
b) Leakage current at Will be supplied later
max. operating
20 voltage.
Arrester percentage rating
21 Dimensions of the
arresters Please refer Drawing
a) Max. Dia of Porcelain Please refer Drawing

22 b)
a) Max. Height
Material of Porcelain
of valve Will be supplied later
b) Details of sealing Will be supplied later
c) Description of Pressure Will be supplied later
Relief system
3 units of 72.5kV each
d) No. of units per arrester
23 Creepage distance 6125mm
24 Minimum clearancemm
a) Between phases mm 3600mm
b) Between phase to earth 3000mm

25 Size of grounding terminal Please refer Drawing


26 Size of the line terminal Please refer Drawing
27 Diameter of the grading Please refer Drawing
28 ring
Min. space required for 3 phase Please refer Drawing
installation
Sl.
Description LIGHTNING ARRESTERS
No.
29 Max. Cantilever Strength of the 1000kGM
arrester KGM.
30 Overall weight of one single Will be supplied later
phase stack (Approx.) Kgs.
31 Weight of complete 250Kgs 10%
arrester (Approx.) Kgs.
32 Net weight of each Will be supplied later
arrester (Approx.) Kgs.