DoestheSMCFlexaffectpowerfactor?
Answer
ThealgorithmsintheSMCproductsshouldnotaffectthepowerfactorwhenrunningthemotoratfullspeed.
TheSMC3andSMCFlexareinbypassatfullspeed.Thepowerfactoratthispointshouldbethesameas
themotorpowerfactor.TheSMC50shouldberunningatfullvoltageSCRconductionatfullspeed,
thereforethepowerfactorshouldbethatofthemotorpowerfactor.Theloadofthemotorwhilerunningat
speedcanadjustthepowerfactorbutthatchangeisafunctionofthemotorload.
MonitoringthepowerfactorandtheusersettingsishowtheSMC50senseswhentogointoenergysaver
mode.
Duringcommonstarts(softstart,currentlimit,linearacceleration)thepowerfactorshouldtrackthepower
factoroftheacceleratingmotor.
Thepumpcontrolalgorithm(pumpstartandpumpstop)canshiftthepowerfactoraspartofthecontrol
algorithm.
Highlightingtheenergysavermodepreviously,whilerunninginthismode,thepowerfactorcanalsochange.
DISCLAIMER
Thisknowledgebasewebsiteisintendedtoprovidegeneraltechnicalinformationonaparticularsubjector
subjectsandisnotanexhaustivetreatmentofsuchsubjects.Accordingly,theinformationinthiswebsiteis
notintendedtoconstituteapplication,design,softwareorotherprofessionalengineeringadviceorservices.
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/769204/page/1 1/3
30/08/2016 769204IspowerfactoraffectedbytheSMCFlex?
Beforemakinganydecisionortakinganyaction,whichmightaffectyourequipment,youshouldconsulta
qualifiedprofessionaladvisor.
ROCKWELLAUTOMATIONDOESNOTWARRANTTHECOMPLETENESS,TIMELINESSORACCURACY
OFANYOFTHEDATACONTAINEDINTHISWEBSITEANDMAYMAKECHANGESTHERETOATANY
TIMEINITSSOLEDISCRETIONWITHOUTNOTICE.FURTHER,ALLINFORMATIONCONVEYEDHEREBY
ISPROVIDEDTOUSERS"ASIS."INNOEVENTSHALLROCKWELLBELIABLEFORANYDAMAGESOF
ANYKINDINCLUDINGDIRECT,INDIRECT,INCIDENTAL,CONSEQUENTIAL,LOSSPROFITORDAMAGE,
EVENIFROCKWELLAUTOMATIONHAVEBEENADVISEDONTHEPOSSIBILITYOFSUCHDAMAGES.
ROCKWELLAUTOMATIONDISCLAIMSALLWARRANTIESWHETHEREXPRESSEDORIMPLIEDIN
RESPECTOFTHEINFORMATION(INCLUDINGSOFTWARE)PROVIDEDHEREBY,INCLUDINGTHE
IMPLIEDWARRANTIESOFFITNESSFORAPARTICULARPURPOSE,MERCHANTABILITY,ANDNON
INFRINGEMENT.Notethatcertainjurisdictionsdonotcountenancetheexclusionofimpliedwarrantiesthus,
thisdisclaimermaynotapplytoyou.
ThispageisbestviewedinInternetExplorer10,Firefox31,Chrome37,Safari6ornewer.
Top (/app/answers/detail/a_id/769204/page/1#top)
(http://www.rockwellautomation.com/global/blog/overview.page)
(https://www.facebook.com/ROKAutomation)
(https://plus.google.com/+RockwellautomationInc)
(https://www.linkedin.com/company/rockwell
(http://www.slideshare.net/RockwellAutomation)
(http://twitter.com/ROKAutomation)
(http://www.youtube.com/rokautomation)
automation)
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/769204/page/1 2/3
30/08/2016 769204IspowerfactoraffectedbytheSMCFlex?
Top (/app/answers/detail/a_id/769204/page/1#top)
https://rockwellautomation.custhelp.com/app/answers/detail/a_id/769204/page/1 3/3