The impedance of a transformer is marked on most nameplates - but what is it and what
does the Z% figure mean?
Definition
The percentage impedance of a transformer is the volt drop on full load due to the winding
resistance and leakage reactance expressed as a percentage of the rated voltage.
It is also the percentage of the normal terminal voltage required to circulate full-load
current under short circuit conditions
Measuring Impedance
The impedance is measured by means of a short circuit test. With one winding shorted,
a voltage at the rated frequency is applied to the other winding sufficient to circulate full
load current - see below:
It is easy to calculate the maximum current that a transformer can deliver under
symmetrical fault conditions. By way of example, consider a 2 MVA transformer with an
impedance of 5%. The maximum fault level available on the secondary side is:
and from this figure the equivalent primary and secondary fault currents can be
calculated.
A transformer with a lower impedance will lead to a higher fault level (and vice versa)
The figure calculated above is a maximum. In practice, the actual fault level will be
reduced by the source impedance, the impedance of cables and overhead lines between
the transformer and the fault, and the fault impedance itself.
determines the volt drop that occurs under load - known as 'regulation'
affects load sharing when two or more transformers operate in parallel
As with all passive plant, the positive and negative sequence impedances (Z1 and Z2) of
a transformer are identical.
However, the zero sequence impedance is dependent upon the path available for the flow
of zero sequence current and the balancing ampere turns available within the
transformer. Generally, zero sequence current requires a delta winding, or a star
connection with the star point earthed. Any impedance in the connection between the
star point and earth increases the overall zero sequence impedance. This has the effect
of reducing the zero sequence current and is a feature that is frequently put to practical
use in a distribution network to control the magnitude of current that will flow under earth
fault conditions.
Differential Protection
Differential protection is a unit scheme that compares the current on the primary side of a transformer with
that on the secondary side. Where a difference exists (other than that due to the voltage ratio) it is
assumed that the transformer has developed a fault and the plant is automatically disconnected by tripping
the relevant circuit breakers. The principle of operation is made possible by virtue of the fact that large
transformers are very efficient and hence under normal operation power-in equals power-out. Differential
protection detects faults on all of the plant and equipment within the protected zone, including inter-turn
short circuits.
Principle of Operation
The operating principle employed by transformer differential protection is the Merz-Price circulating current
system as shown below. Under normal conditions I1and I2 are equal and opposite such that the resultant
current through the relay is zero. An internal fault produces an unbalance or 'spill' current that is detected
by the relay, leading to operation.
Design Objectives
An ideal scheme is required to be:
Where CT secondaries are connected in star on one side of a transformer and delta on the other,
allowance must be made for the fact that the secondary currents outside the delta will only be 1/3 of the
star equivalent.
Other Issues
Biased Relays
The use of a bias feature within a differential relay permits low settings and fast operating times even when
a transformer is fitted with an on-load tapchanger (see above). The effect of the bias is to progressively
increase the amount of spill current required for operation as the magnitude of through current
increases. Biased relays are given a specific characteristic by the manufacturer.
Interposing CTs
The main function of an interposing CT is to balance the currents supplied to the relay where there would
otherwise be an imbalance due to the ratios of the main CTs. Interposing CTs are equipped with a wide
range of taps that can be selected by the user to achieve the balance required.
As the name suggests, an interposing CT is installed between the secondary winding of the main CT and
the relay. They can be used on the primary side or secondary side of the power transformer being
protected, or both. Interposing CTs also provide a convenient method of establishing a delta connection for
the elimination of zero sequence currents where this is necessary.
Modern Relays
It should be noted that some of the newer digital relays eliminate the need for interposing CTs by enabling
essentials such as phase shift, CT ratios and zero sequence current elimination to be programed directly
into the relay.
DGA is one of the most valuable diagnostic tools available. It is a procedure used to assess the condition
of an oil-filled transformer from an analysis of the gases dissolved in the cooling/insulating medium. It is a
well established technique that is cost effective, providing essential information from a relatively simple,
non-destructive test based upon oil sampling. Whilst the analysis is normally done in a laboratory, on-line
devices are also available. The results reveal much about the health of the plant including its present
condition, any changes that are taking place, the degradation effects of overload, ageing, the inception of
minor faults and the most likely cause of major failures.
Oil sampling from transformers is equivalent to blood sampling from humans.
It should be noted that a severe fault may also produce free gases that collect in the Buchholz relay. This
closely associated topic is dealt with in Tutorial T5
In the Laboratory
In the laboratory the mixture of gases must be extracted from the oil, for example by the application of a
vacuum. The mixture is then passed through a chromatograph where the individual components are
separated, identified and quantified. The results are normally presented in tabular form with each gas
listed together with the quantity found in parts per million (ppm) by volume.
Moisture
The life of a transformer is dependent upon three crucial parameters; temperature, oxygen and
moisture. This tutorial deals with moisture. Information about the detrimental effects of oxygen is given
elsewhere.
Most power transformers use paper and oil as the main form of insulation and during manufacture stringent
efforts are made to ensure that both are as dry as possible when new plant leaves the factory. Once in
service the moisture content begins to increase. Excessive moisture can put the life of a transformer at
risk. It is important to understand the source of this moisture, its effect and the preventive measures that
can be taken.
Source of Moisture
Once in service a transformer is subjected to the following sources of moisture:
External moisture is repeatedly drawn into a free-breathing transformer as the working temperature rises
and falls with load.
Internal moisture is generated as cellulose insulation ages. The process by which this occurs is extremely
complex but can be summarised as follows. Cellulose consists of long chains of hydro-carbons. When
these chains are broken the carbon and hydrogen combine with any oxygen present to form carbon
monoxide, carbon dioxide and water. The gases are dissolved in the oil - see Tutorial T3 DGA. The water
remains largely in the paper where its presence contributes to further ageing as a vicious cycle is
established.
Effect of Moisture
Moisture reduces the dielectric strength of paper and oil which in turn increases the risk of electrical
failure. It also reduces the mechanical strength of the paper.
Since hot oil is able to support more moisture than cold oil, percentage saturation is temperature
dependent. If hot oil is cooled the relative saturation will increase and an emulsion of water and oil may
form. Free water may also be produced which will have a serious effect on dielectric strength and can lead
to the formation of rust where it collects, typically in the bottom of main tanks and conservators.
Furthermore, when wet paper gets very hot, for example during a period of sustained over-loading, the
possibility of bubble formation arises. When this occurs moisture in the paper is boiled off as water vapour
introducing a risk of partial discharge and electrical breakdown.
Moisture Dynamics
Moisture in a transformer is very dynamic, moving with temperature between the paper and the oil. By far
the greatest quantity is contained in the paper which acts like a sponge. The ratio of water in paper to oil is
about 1000:1 (reducing to 500:1 if the oil is old). As the temperature rises moisture moves relatively rapidly
from the paper to the oil. As the temperature falls the moisture moves back into the paper, but more
slowly.
After a period of prolonged steady temperature, the water in the paper and oil reaches equilibrium. At that
point by measuring the moisture content of the oil it is possible to estimate the quantity of water in the
paper from standard look-up tables. In a large transformer we are talking about tonnes of paper,
thousands of litres of oil and hundreds of litres of water.
Asset Management
Dealing with the problem of moisture in a transformer is a very important part of effective asset
management. For example:
Always record the temperature when an oil sample is taken for moisture analysis.
Never change oil because it is wet. The new oil will very quickly degrade to the same condition as the old
as moisture leaves the paper to re-establish a condition of equilibrium.
Consider:
(a) Careful oil sampling and testing
(b) The use of on-line moisture sensors
(c) Silica gel breather design, application and maintenance
(d) On-line conditioning and monitoring systems
(e) Devices that continuously remove moisture from the air-space in the conservator
(f) Continuous on-line moisture removal systems connected into the oil system
(g) Specialist field drying services using heat and vacuum.
Buchholz Relays
A Buchholz relay is a gas and oil operated device installed in the pipework between the top of the
transformer main tank and the conservator. A second relay is sometimes used for the tapchanger selector
chamber. The function of the relay is to detect an abnormal condition within the tank and send an alarm or
trip signal. Under normal conditions the relay is completely full of oil. Operation occurs when floats are
displaced by an accumulation of gas, or a flap is moved by a surge of oil. Almost all large oil-filled
transformers are equipped with a Buchholz relay, first developed by Max Buchholz in 1921.
General Arrangement
B - Upper Float
A - Gas Collection Chamber C - Lower Float
D - Oil Surge Detector
Conditions Detected
A Buchholz relay will detect:
Fault conditions within a transformer produce gases such as carbon monoxide, hydrogen and a range of
hydrocarbons (Tutorial T3). A small fault produces a small volume of gas that is deliberately trapped in the
gas collection chamber (A) built into the relay. Typically, as the oil is displaced a float (B) falls and a switch
operates - normally to send an alarm. A large fault produces a large volume of gas which drives a surge of
oil towards the conservator. This surge moves a flap (D) in the relay to operate a switch and send a trip
signal. A severe reduction in the oil level will also result in a float falling. Where two floats are available
these are normally arranged in two stages, alarm (B) followed by trip (C).
Functional Tests - a test petcock enables dry air to be admitted into the relay to check correct operation. A
trickle of air is equivalent to a gradual accumulation of gas. A blast simulates an oil surge. These tests are
sometimes referred to as 'blowing the Buchholz'. On completion it is important that the relay is bled to
remove the air that has been introduced.
Draining - a valve in the bottom of the relay enables an oil sample to be taken or the relay to be
drained. As with gas sampling, this facility can be brought down to ground level for enhanced operator
safety and convenience.
Accessories
A range of accessories and services are available to assist with the safe and correct operation of Buchholz
relays including:
Transformer nameplates carry a vector group reference such at Yy0, Yd1, Dyn11 etc. This relatively
simple nomenclature provides important information about the way in which three phase windings are
connected and any phase displacement that occurs.
Winding Connections
HV windings are designated: Y, D or Z (upper case)
LV windings are designated: y, d or z (lower case)
Where:
Y or y indicates a star connection
D or d indicates a delta connection
Z or z indicates a zigzag connection
N or n indicates that the neutral point is brought out
Phase Displacement
The digits ( 0, 1, 11 etc) relate to the phase displacement between the HV and LV windings using a clock
face notation. The phasor representing the HV winding is taken as reference and set at 12 o'clock. It then
follows that:
All references are taken from phase-to-neutral and assume a counter-clockwise phase rotation. The
neutral point may be real (as in a star connection) or imaginary (as in a delta connection)
When transformers are operated in parallel it is important that any phase shift is the same through
each. Paralleling typically occurs when transformers are located at one site and connected to a common
busbar (banked) or located at different sites with the secondary terminals connected via distribution or
transmission circuits consisting of cables and overhead lines
Basic Theory
An ac voltage applied to a coil will induce a voltage in a second coil where the two are linked by a magnetic
path. The phase relationship of the two voltages depends upon which way round the coils are
connected. The voltages will either be in-phase or displaced by 180 deg as below:
When 3 coils are used in a 3 phase transformer winding a number of options exist. The coil voltages can
be in phase or displaced as above with the coils connected in star or delta and, in the case of a star
winding, have the star point (neutral) brought out to an external terminal or not.
Example - Dyn11
We now know that this transformer has a delta connected primary winding (D) a star connected secondary
(y) with the star point brought out (n) and a phase shift of 30 deg leading (11). Connections and vector
diagrams are as follows::
HV
LV
Other Configurations
By connecting the ends of the windings in other ways a wide range of options becomes available as set out
below.