Você está na página 1de 8

Accurate fault location technique for power

transmission lines

Prof. A.T. Johns, DSc, PhD, C.Eng, FlEE


S. Jamali, BSc, MSc

Indexing terms: Fault location, Transmission lines

posec in Reference 4 can be applied to untransposed lines


Abstract: The paper describes a very accurate if the impedance for each phase can be set. However, it
fault location technique which uses post-fault has been reported that when using the latter technique
voltage and current derived at both line ends. for untransposed lines represented by symmetrical
Fault location is independent of fault resistance parameters, a substantial error occurs [SI.
and the method does not require any knowledge (b)Shunt capacitance
of source impedance. It maintains high accuracy Capacitance current for long lines, particularly under
for untransposed lines and no fault type identifica- high resistance fault conditions, can be comparable with
tion is required. The paper presents the theory of the current in the fault path. Most algorithms do not
the technique and the results of simulation studies consider shunt capacitance, and the vast majority of
to determine its performance. those that do, use a lumped model for shunt capacitance
[7, 81. This in turn is not an exact representation of the
line and does not permit very high accuracy in fault loca-
L i s t of symbols tion.
(c) Fault resistance
V, , V, , V, = voltages at fault, sending and receiving ends Unknown fault resistance, and the phase difference
I,, I , = currents at sending and receiving ends between the fault current contribution from the local and
Y = line propagation constant remote source ends, introduce error.
20 = line characteristic impedance ( d ) Remote source impedance setting
X = distance to fault from sending end S Some previous fault location algorithms require a setting
L = line length for the remote source impedance. In modern transmis-
a, b, c = phases a, b, and c of line sion networks, normally several lines and generators are
A , B,C = phases A , B, C of second circuit of double connected to the line terminals. Switching operations
circuit line often change the source operating configuration from
n = modal component value (n = 1 to 6 ) those assumed in setting the fault location equipment,
[Q], [SI = voltage and current eigenvector matrices which in turn can lead to a large error in fault location.
(e) Capacitance voltage transformer
1 Introduction Difficulties are often encountered in the use of capacitor
voltage transformers, which are generally incapable of
The need for very high accuracy in fault location is gener- passing higher frequency phenomena. Thus, where an
ally becoming more important because, in ehv systems, algorithm utilises high frequency components, difficulties
there is often little visual evidence of a fault, and post- can arise. Tapping the capacitor divider of CVTs can
fault clearance tests performed at reduced system voltage lead to problems with relaxation transients caused by
can be inconclusive. The degree of accuracy required is other tuning circuits, and additional (separate) capacitor
therefore increasing and is much higher than can be divider provision is likely to be prohibitively expensive in
obtained using simple conventional impedance to fault most applications.
measuring techniques. Even a small measurement error A fault location technique which takes account of the
may require detailed local examination over several kilo- foregoing limitations is considered in this paper. In doing
metres of a typical line. so, many of the fundamental limitations on the accuracy
For a verv accurate fault location the following achievable are reduced. The results of simulation studies
sources of error should be considered : to determine the basic accuracy of the methods are given,
( a )Line assymmetry and it will be shown that the technique also has the merit
The self and mutual impedances and admittances of each of not requiring determination of the phase(s) involved in
phase of transmission lines are determined by line a particular fault. Previous techniques use different algo-
geometry and they are not identical for all phases. Most rithmic routines for different types of fault, thus seriously
previous fault location techniques use symmetrical com- impairing accuracy if incorrect fault identification occurs
ponents that are only applicable to transposed lines under contingency or difficult fault situations.
[ l , 2, 3, 6, 7, 81, though the fault location technique pro- The principles of the method were briefly summarised
in Reference 9. This more rigorous and comprehensive
Paper 7529C (PS, P l l ) , first received 14th November 1989 and in
revised form 5th April 1990
paper extends the theory and results to the important
The authors are with the Power and Energy Systems Research Centre,
case of double-circuit transmission lines, and also con-
The City University, Northampton Square, London E C l V OHB, United siders the effect of setting and hardware errors on the
Kingdom accuracy likely to be attainable in practice.
I E E PROCEEDINGS, Vol. 137, P t . C, N o . 6 , N O V E M B E R 1990 395
2 Principles components are used. Furthermore, the fault location
algorithm relates to a distributed line, and inherently
The voltages and currents measured at each end of a includes for the effect of shunt capacitance.
transmission line are filtered to produce a measure of
the steady-state power frequency voltage and current 2.2 Extension to single -circuit lines
phasors. The latter are obtained as data described by The method described above cannot be applied directly
means of postfault processing applied to data captured to a multiphase power line since a number of phases are
during the fault clearance process. A hardware descrip- involved. Consider a single-circuit 3-phase transmission
tion is given in Reference 9. line in which the phases are identified by a, b, c as indi-
cated in the single line equivalent of Fig. 2. In this case,
2.1 Simple single-phase line
Consider the relationship applicable to an assumed ISa,b.c (.A,B,C) IRa.b,c(.A,B.C)
single-phase line application. With reference to Fig. 1 , the
-H j
source
. IS 4
line
~ f o u
line
l t ~
I k
source h
twoport twoport - - - - -.

network section sect ion network

I I
Fig. 2 Single-line diagram offaulted line described by 2-port matrices
abc = phases of one circuit
Fig. 1 Single-phasefaulted linelsource network ABC = phsaes of second circuit in case of double-circuit line

the vector of the various voltages and currents ([V,,, b , < ] ,


postfault steady-state voltage V, across the fault at a dis- [ I S o , b , c ] , etc.) are related using the two port matrices
tance x from end S is readily expressed in terms of the [A,], [BSI, [ A R ] , [ B R ] which in turn are 3 x 3 matrices
voltages and currents measured at the line ends defined using the line series impedance matrix [ Z ] and
V, = cosh (yx)V, - Z , sinh (yx)Z, (1) the line shunt admittance matrix [U. With reference to
Fig. 2, the multiconductor equivalent of eqns. 1 and 2 is
V, = cosh (y(L - x))V, - Z , sinh (y(L - x))IR (2) (4)
['Fa, b, c l = [ASl[VSa, b, c l - [BSl[zSa, b, c 1
The surge (or characteristic) impedance Z , and line pro-
pagation constant y are given by Z , = ( Z / Y ) ' / * and ['Fa. b. c 1 [ARIIVR,, b, c 1 - [ B R I [ r R , , b, c 1 (5)
y = ( Z Y ) ' l 2 ,respectively, where Z is the line series imped-
where b , , I , CV,. b , J , [I,,, b , J , etc. are vectors defin-
ance and Y is the line shunt admittance per unit length. ing voltages and currents for each phase e.g. [VR/Ro,b,c] =
Eqns. 1 and 2 are equated to eliminate any necessity for [V,, , V R b , I / R c I T , [ I T denoting a matrix transpose.
defining the fault point network, thereby eliminating any It is important to note that the two port matrices
uncertainties in the precise value of the fault path imped- [A,], [BSI etc. can, if necessary, be formed to include any
ance. Rearrangement of the eqns. 1 and 2 provides an discrete line transposition, which in turn is conducive to
exact evaluation of the distance to the fault x as given in maintaining very high levels of measurement accuracy in
eqn. 3 long line applications. In most cases, however, it is suffi-
x = [tanh-'( - B/A)]/y (3) cient to treat each line section as homogeneous.
The basic fault location algorithm can be extended to
where multi-phase transmission lines by decoupling eqns. 4 and
A =Z, cosh (yL)I, - sinh (yL)VR Z , I, + 5 into uncoupled or independent single-phase networks
of the type shown in Fig. 1 . This is done using the theory
B = cosh (yL)VR- Z , sinh (yL)Z, - V, of natural modes and matrix function theory [ I l l as
If all relevant line parameters could be specified without commonly used in the digital simulation of faulted EHV
error, eqn. 3 would lead to an exact evaluation of the transmission systems [ 1 2 ] . The theory of such techniques
distance to fault x. In such a hypothetical case, x would is well documented and the reader is therefore referred to
be calculated as a real value. However, in practice the the latter references for further details. It is important to
calculated value of x has a very small imaginary part note that the theory of natural modes (which leads to the
which is ignored; the real part is thus taken to represent modal transformation) is general and does not presup-
the fault distance. Eqn. 3 requires only known line data pose that the line is either balanced or properly trans-
( Z and Y ) and known phasor values derived from meas- posed.. As indicated later, some simplification can,
urands at the line ends. Therefore, any fault location esti- however, be achieved by assuming that a particular line is
mate thereby derived is independent of both the fault ideally transposed. Briefly, the method involves finding
impedance and the source impedance. The method can of the matrix of Eigenvectors of the [ Z ] [ Y ] product ( [ Q ]
course use superimposed measurands of the type used in say) and the [ Y ] [ Z ] product ([SI say). The voltages and
high speed directional comparison protection equipment currents are thereby derived from each phase a, b, c and
[ l o ] , and in this case the voltages and currents used are are transformed to corresponding [ Q ] and [SI eigen-
taken as the difference between prefault steady-state and vector matrices [12]
postfault values. In this respect, it has been found that,
generally, the accuracy of fault location is marginally CV,J = CV,i vS2 & 3 I T = CQI - ' [ G o ~ S GL c l T
better for most line configurations when superimposed ['.%I = [IS1 I S 2 IS31 = [IS, ISb zScl (6)
396 I E E P R O C E E D I N G S , Vol. 137, P t . C , N o . 6 , N O V E M B E R 1990
ADDlication of the transformation to modal auantities 3 Practical considerations
resilts in a multiconductor line being decomposkd into a
number of single-phase uncoupled models of the type 3.1 Use of transposed line parameters for
shown in Fig. 1. For each modal component, there is an untransposed lines
equation pair of the form of eqns. 1 and 2. Thus for a The modal surge impedances and propagation constants
single-circuit line, there are three pairs of such equations are precomputed, as indicated in Section 2.1, from the
corresponding to the modes 1, 2, 3 so that for mode 2 for line impedance and shunt admittance matrices [ Z ] , [Y ] .
example, the equation pair used would take the form of The latter are in turn computed from a knowledge of the
eqns. 7 and 8. line conductor geometry, the earth plane resistivity and
the conductor parameters. They represent basic param-
VF2 =As2 vs2 -4 2 Is2 (7) eters set into the algorithm according to the line applica-
tion involved. However, it has been found that for the
'FZ = 'R2 - B R 2 ' R 2 (8) vast majority of applications, the algorithm is so accurate
Any one or more mode pair equations can be used to that, even if perfect line transposition is assumed, the
determine the fault location. For example, a mode 2 error in typically less than 1%, which is acceptable in
based evaluation given by eqn. 9 yields most practical applications. If perfect line transposition is
assumed, the calculation of the modal surge impedances
x = [tanh-'( - B 2 / A 2 ) ] / y 2 (9) and propagation constants is simplified. For example, the
where mode-2 surge impedance for a single-circuit line can be
expressed directly in terms of the positive phase sequence
A , = Z o 2 cosh (72 L ) ~ R-Zsinh (y2 +
L ) V R ~ 2021.92 line impedance (2,)and shunt admittance (Yl) per unit
and length of line as Z,, = ( Z l / Y l ) ' / 2 . Similarly y , =
( Z l / Y l ) 1 / 2 . The assumption of perfect transposition leads
B 2 = cosh (72 J!A)VR~
- 2 0 2 sinh (72 L)1R2 - vs2 to Eigenvector matrices that are equal [SI = [ Q ] and
Eqn. 9, and any companion equations formed using that are independent of the line geometry. In this case, it
the other modes, is the exact equivalent of eqn. 3. The is unnecessary to calculate the voltage and current eigen-
appropriate modal surge impedances required are vector matrices as it can be shown that, for a single-
readily determined from the matrix product [ Z , , = circuit line, they take the special form given in eqn. 13

=[I -:-!I
[ y l P 1 [ Q ] - ' [ Z ] [ S ] in which [ y ] is a diagonal matrix of c111.

so-called modal propagation constants comprising the 1


square root of the Eigenvalues of the matrix product
[ Z ] [ Y ] , [ l l , 121. Matrix [Z,,] thus takes the diagonal [SI =CQI (1 3)
form of [Z,, Z,, Z , , ] for a 3-phase line, the individual
values being the modal surge impedances.
Perfect transposition can also be assumed for most
2.3 Extension to double-circuit lines double-circuit lines without incurring a serious loss of
The fault location technique can be extended to double- accuracy. For a double-circuit transposed line, the eigen-
circuit applications by using the phasor values from the vector matrices of voltage and current have the following
second circuit e.g., V F a , b , E , A , and Isa, b, E , A , c (see Fig. form :
3a). In this case, the 2-port matrices [ A s ] , [BSI, [ A R ] and
[ B R ] are 6 x 6 matrices. Eqns. 4 and 5 can then be gener-
alised for a double-circuit line, i.e.
IQ1
CQDI= [SDI = CQI [ -CQl
- (14)

,aF'[ b,c. A . B . C I = [ASl[vSa, b.c. A , B . C l where [ Q ] is given in equation 13.


- [BSl[lSa. b. c, A , E . C l (10) Evidently, in the double-circuit line case, there are six
modes of propagation, each having an associated modal
[bo,b , r , A , E . C 1 = [VRl[vRo, b. E, A , E, C l surge impedance. Consequently, there are six possible
basic fault locating algorithms of the form of eqn. 9. It is
- C B R l ['Ro, b, E , A , E , C l (1 1) important to note that it is unnecessary to use all signal
Consequently the modal form of eqn. 6 consists of six pairs, and some computational economy can thereby be

Cb.1 = ["'I
modes of current and voltage in a double-circuit line

vS6
=

=
Cvsl b2ys3 ... vS6y

CQDI - '[bov s b vsc ' ' ' Vscl


gained. For double-circuit line applications, some further
simplification has been found to be possible by using
measurands based upon the aerial-mode components for
an assumed ideally transposed single-circuit line. These
are obtained via the assumed transposed single-circuit
Eigenvector matrices of eqn. 13, i.e. the presence of the

[lsnl =

I:[ 1 = CIs11s2 I s 3 ' . '

= [ S D I '[IS. l S b I S c ' . ' ' S C I T


where [ Q D ] and [S,] are double-circuit eigenvector
ISJT

(12)
second circuit is ignored and each circuit is treated as if it
were a single-circuit line. The fault location algorithm of
eqn. 9 then uses only modes 2 and 3, voltages and cur-
rents in combination given in Eqn. 15, where %: means
Vs or V R. This in turn covers all faults on the circuit abc
(see Fig. 3a).
matrices.
The decoupled form of eqn. 12 results in six pairs of S
', R2 = &,R o - h,Rc
equations, all of the basic form of eqns. 7 and 8. The rest ' S . R2 = ' S . Ra - ' S . Rc
of the fault locating routine for double-circuit lines is as
previously described. In this form, intercircuit faults can 'S, R 3 = 'S, Ra - 2%, R b + &,Rc
also be located. IS, R 3 = l S , R a - 21S, Rb -b IS. Rc (15)
IEE PROCEEDINGS, Vol. 137, P t . C , N o . 6 , N O V E M B E R 1990 397
Faults on the second circuit, can also be covered by 3.3 Synchronisation of sending and receiving end
means of aerial-mode signals derived from the voltages data
and currents for that circuit (denoted A , B, C in Fig. 3a) It will be evident from eqn. 9 that the basic fault location
given in eqn. 16 algorithm involves entering data derived from both ends
of the line, and this in turn requires that the relevant
phasor quantities are related to a common phasor refer-
ence. Time synchronisation of the measurands at both
ends could be achieved by means of a continuous data
channel linking each end, but this approach is unwieldy.

EW EW
The above approach to fault location in double-circuit 7"' 1

applications has the obvious advantage that 'stand-alone'


locator equipment, which requires only voltages and cur-
rents from each circuit, can be used. Thus, the fault
locator applied to circuit abc uses only currents and volt-
ages from that circuit, likewise the second circuit uses
only voltages and currents associated with phases A, B
and C. This is possible on account of the fact that, in
practice, only predominantly common-mode (zero
sequence) coupling exists between each circuit. It is thus
evident from eqns. 15 and 16 that any common-mode
components induced in each circuit are cancelled and do
not appear within the measurands for each circuit.
It is important to note that the simplified form of the
algorithm for double-circuit lines, as described above,
results in some degradation in performance under inter-
circuit fault conditions e.g. conductor clashing between
circuits. This limitation is one that utilities generally EW1*.8.10rn
...-. .
8.10m EW2
accept on account of the relatively low incidence of such
faults, and it is undoubtedly for this reason that previous
work on fault location does not take account of such
faults. However, if in the future inter-circuit faults assume I
I
greater importance, the full algorithm involving deriving I

the measurands from the voltages and currents of both I


j 21.00m
I
circuits i.e. via the inverse of Eqn. 14, can be used. In the I
I
latter form, the new fault locator thus overcomes the lim- I
I
itations which previously existed in the ability of present I 1
..............................
generation equipments to deal with contingency faults on
double-circuit lines. b
Fig. 3 Line conjgurotion
U Vertical single-circuit and double-circuit lines
6 Horizontal single-circuit line
3.2 Mode selection
All types of fault will excite at least one aerial-mode com-
ponent i.e. modes 2 and/or 3 are always excited. In practice, prefault voltage and current data at one end
Although the earth-mode (mode 1) can also be used, it is can be used to provide a common phasor reference to
unnecessary to do so, except in the case of single-circuit relate such data to that measured at the receiving end.
vertical conductor constructed line configurations typi- For example, the prefault mode-2 voltage at the sending
cally of the type shown in Fig. 3a. The relatively high end can be calculated in the equipment at the receiving
degree of asymmetry in such configurations has been end from the two port network equations for an
found to result in a greater degree of accuracy being unfaulted line given in eqn. 17. This approach obviates
attained by using earth-mode signals to locate faults the need for data synchronisation via a communication
involving earth. In such applications, the basic fault link.
locating algorithm is, therefore, applied to all three
modes. The presence of a significant level of residual
current is used to identify the presence of a fault involv-
ing earth, and this in turn is used to display the fault Evaluation of eqn. 17 gives the phase angle between the
location as determined by a mode 1 based evaluation of sending and receiving end voltages, and thereby provides
the basic fault locating algorithm of eqn. 9. Where a fault the time between the prefault zero-crossing of the meas-
does not involve earth, the fault location, as determined urands at each end. The latter time, in turn, is used to
by either the mode 2 or mode 3 based evaluation of the provide a common phasor reference, which in turn relates
basic fault locating algorithm, is used; the particular the sampled voltage data derived at each end. A similar
mode selected is that associated with the largest modal process is applied in respect of sampled current data,
component. It is important to note that the greater where the relevant two port relationship, used to derive a
degree of symmetry associated with double-circuit lines common current phasor reference, is as given in Eqn. 18.
(see Fig. 3a) eliminates any necessity for mode selection,
and aerial-mode based signals suffice. IS2 = sinh ( 7 2 L)vR2/202 - cosh ( 7 2 L)1R2 (18)
398 I E E PROCEEDINGS, V o l . 137, P t . C , N o . 6 , N O V E M B E R 195'0
4 Performance evaluation small improvement in accuracy in long line applications
as, the ration BIA, which in turn is used in the determi-
The accuracy of the fault location technique has been nation of fault location estimates (see Equation 3), is
determined by using a steady-state line simulation pro- better numerically conditioned in the long line case. For
gramme. This method of performance evaluation reveals short lines, the measurands B and A tend to a relatively
the inaccuracies in the algorithm itself, and does not small number, and the associated errors due to the use of
include any errors introduced by the hardware and/or
transducers i.e. it reveals the best can be expected by way
of fault location accuracy. The programme uses distrib-
uted line parameters in deriving phase variable relation-
ships, and thereby gives a detailed and realistic line
representation under operating and fault conditions. The
values of voltage and current at the terminating busbars
are produced for any fault type and source condition.
The results presented in this paper relate to single and
double-circuit 400 kV vertical constructed lines of the
type commonly used on the UK supergrid system, and to
a typical single-circuit 500 kV horizontally constructed
line as commonly used in longer distance transmission
applications in the USA. Details of the line configuration
involved are given in Figs. 3a and 3b. A wide range of -O
-0.8 I
line lengths and source conditions have been considered,
and the results presented give an indication of the accur-
acy typically obtained under earth fault conditions. The
accuracy for pure phase faults clear of ground has been
found to be better than that for earth faults, and for
reasons of brevity, only results for earth faults are given
1.0 b
here. Relevant parameters used are
(a) phase conductors are 4 x 541710.33 cm SCA with o.i3[
0.305 m bundle spacing 0.6
(b)earthwire is 54/1/0.33 cm SCA
(c)earth resistivity (assumed homogeneous) = 100 Rm
( d ) source short circuit levels = 5 GVA and X I R
ratio = 40 at both ends
(e)fault path resistance is 100 R
(f)line lengths = 100 and 250 km
(9) prefault line loading is zero.
The lines considered are deliberately untransposed to
adequately reveal the effect on the accuracy of assuming
perfect transposition when setting the parameters into the -0 8
I
locator. -1.01 ' ' ' ' ' ' ' ' '
0 1 2 3 4 5 6 7 8 9 1 0
If the locator is set using the exact parameters derived actual fault position (XIO')
from the actual eigenvector/eigenvalues for an untrans- ( % from end 5 on Fig.2)
posed line, the only errors that occur are those due to
hardware i.e. the algorithm error is zero. The results pre-
C
sented are for a locator having approximate settings
derived on the assumption of ideal line transposition in 0.8-
accordance with the details given in Section 3.1. Fig. 4
0-6-
shows the percentage of error in fault location that
occurs for phase-a-to-earth faults on different line con- 5 04-
figurations. It should be noted that, in the double-circuit
line case, the fault is on circuit abc in Fig. 3a and is
located without any data from the other circuit i.e., it
uses only voltages and currents associated with circuit
abc as explained in Section 3.1. The error is expressed as
a percentage of the total line length, i.e.

% error =
[(estimated location)
- (actual location)] x 100
-o.61
-0.8
-1.01 ' I ' I ' ' ' a ' 1
total line length 0 1 2 3 4 5 6 7 8 9 IO
actual fault position (XIOI)
It can be seen from the various results of Fig. 4 that the ( % from end 5 on Fig.2)
locator gives an inherently accurate evaluation of fault Fig. 4 Measuring accuracy for a-earth fault on different line con-
position that is largely independent of the actual fault figurations
point. In particular, it can be seen that the accuracy is (i) for 100 km line application
not unduly affected by the line length; this is a conse- (ii) for 250 km line application
a Single-circuit horizontal line (see Fig. 3b)
quence of the fact that the algorithm takes fully into h Single-circuit vertical line (see Fig. 30)
account the presence of shunt capacitance. There is some c Double-circuit line (see Fig. 3a)

IEE PROCEEDINGS, Vol. 137, Pt. C, No. 6, NOVEMBER 1990 399


a finite word length are consequently larger. The consis- when the locator was set, assuming perfect line transposi-
tency of the new algorithm and its relative independence tion.
of line configuration is also apparent, the magnitude of
error always being less than 0.6% for all situations. It is
interesting to note from a comparison of Figs. 4a and 4b 5 Effect of setting and hardware inaccuracies
that the accuracy attained for single-phase-to-earth faults In the simulated performance tests carried out in the pre-
is better for horizontally constructed lines than for verti- vious section, it was assumed that perfect setting data
cal lines. Furthermore, a comparison of Fig. 4c with 44 and perfect input data are available to the algorithm. In
and 4b shows that accuracy for the double-circuit line is practice this will not be the case, and a number of simula-
better than for the single-circuit cases. tion tests have therefore been run to determine whether
Fig. 5 shows typical responses for double-phase-to- the algorithm is particularly sensitive to any of these
earth (a-6-e) faults involving a 100R fault resistance to factors. In the following simulation tests, assumed ideally
earth in each faulted phase. The response for the horizon- transposed line parameters are again used when setting
tal line subjected to an a-b-e fault is very similar to that the locator, though the actual lines studied are untrans-
for an a-earth fault shown in Fig. 4a. A comparison of posed.
Figs. 4b with 5b shows that, for single-circuit vertical
lines, the error for multiphase earth faults is greater than
for corresponding single-phase-to-earth faults. For 5. I Remote source impedance setting
double-circuit lines, the error is comparable with single- The algorithm does not require any source impedance
phase-to-earth faults and multiphase-to-earth faults setting and is independent of source configurations. In
(compare Fig. 4c with Fig. 5b). The largest error is always practice, source impedance variations could be a major
less than approximately 1.1% for all fault positions, and source of error since they change, as different com-
occurs on single-circuit vertical lines. binations of plant are connected or disconnected with
As mentioned previously, the results presented above changing load situations; the source independence of this
are typical of those obtained. In all cases studied, the method of location is therefore a useful factor.
error was found to be less than approximately 1.5%
5.2 Input parameter errors
a In the performance evaluation, all input parameters have
been derived from line geometry and electrical param-
eters, which in turn are converted into [ Z ] and [ Y ]
matrices. A good illustration of the effect of setting incor-
rect values for the various parameters into the basic fault
locating algorithm (eqn. 9) can be obtained by varying
the line impedance matrix [ Z ] about the true value for
the actual line. This in turn affects both the modal surge
impedance and propagation values as used in finally
locating the fault. Variations in the mean conductor
height and earth resistivity along the line length have a
much more pronounced effect on the magnitude of the
[ Z ] matrix than on the [ Y ] matrix which is practically
unaffected by the earth and conductor losses. Maximum
-121 ' ' ' ' ' ' ' ' '
errors in the magnitude of the [ Z ] matrix are difficult to
J

0 1 2 3 L 5 6 7 8 9 1 0
actual fault position (XIO') quantify exactly, particularly if very unusual situations,
('L from end 5 on Fig.2) such as variations in conductor sag corresponding to
heavy loading on warm days as against light loading on
b cold days together with extreme variations in earth resis-
tivity along the line length, are postulated. However, a

0'41
O
maximum assumed error corresponding to & 10% in the

:"'1
0.3 magnitude of [ Z ] generally gives a fair indication of
worst-case performance under conditions corresponding
to most practical situations. The [ Z ] matrix has therefore
g 0.1 been subjected to a maximum f 10% error, which in turn
has been reflected in setting the parameters into the algo-
rithm. The results of such tests are thus indicative of the
likely error caused by setting incorrect line parameters
into the locator. The results for these tests are shown in
Fig. 6 for an a-phase-to-earth fault on the single-circuit
-0.31
250 km horizontal line configuration. The algorithm per-
-0.41 forms very well, a + 5 % error in the magnitude of [ Z ]
-0.5' I ' ' " " " ' matrix elements resulting in only an additional 0.7% of
0 1 2 3 L 5 6 7 8 9 10 error (in comparison to 0% curve) in distance to fault
(XI01)
actual f a u l t position evaluation; a f 10% error results in a maximum 1.3%
( % from end S on Fig.2)
additional error.
Fig. 5 Measuring accuracy for a-b-earth fault on different line con-
figurations 5.3 Line length setting error
(i) 100 km line application A further source of setting error relates to the line length.
(ii) 250 km line application
a Single-circuit vertical line (see Fig. 3a)
It can be seen from Fig. 7 that if there is a -5% error in
b Double-circuit line (see Fig. 3 4 line length keyed into the algorithm, an error of up to
400 I E E PROCEEDINGS, Vol. 137, P t . C , N o . 6 , N O V E M B E R 1990
approximately -4.3% will be introduced in the fault Table 1 : Different cases of magnitude error in voltage and
location estimate for an a-earth fault on the 250 km hori- current phasors entered into the locator algorithm
zontal line. In general, it has been found that the
maximum error obtained is less than the setting error. 1 +2% +2% -2% -2%
Similar results are obtained for vertical line construc- 2 -2% -2% +2% +2%
tions. 3 +2% -2% +2% -2%
25 4 -2% +2% -2% +2%

2oi
15 '...+loo/.
'. .. 1.5 -

1.0.'-
__---
_.--
case 2
----------- --__ -_ -.
....
. 0.5- \
1 q . e L *.
-.
----_-
L.

e \
z c
_ / - - -

O--_
---_-_-- -
Y a s Z
U
al \
.. L
-0.5-
ca5e :-----
1
t
3
0 - - _ _ _ _ _ Y-
__-- K
E -1.0-

- 2 50 1 2 23 4 5 6 . 7 8 9 0IO ~

actual fault position


(Yo from end S on F1g.2)
(x101) -1.5
-201
t ' 1 " 1 ' " "
0 1 2 3 4 5 6 7 8 9 1 0
(XI01)
Fig. 6 Effect of line series impedance error on the accuracy of mea- actual fault position
surement for 250 km horizontal (single-circuit) line configuration subjected (7. from end 5 on F19.2)
to a-earthfault Fig. 8 Examples of measurement error introduced by error in voltage
Percentage error in magnitude of line series impedance matrix [ Z ] when setting and current magnitudes for a locator applied to 250 km horizontal line
the locator subjected to a-earth fault

be seen that the maximum error occurs for Case 2, and is


approximately 1.5%. Not surprisingly, errors have been
found to be least when all voltage and current phasors
are simultaneously subjected to the same error (not
shown).
Table 2 shows some corresponding cases involving
+ l o " error in the argument of the 3-phase voltage and
current entered into the locator. Fig. 9 shows the mea-
sured error for these cases. Again, it can be seen that the
maximum error is approximately 1.5%

Table 2: Different cases of argument error in voltage and


current phasors entered into the locator algorithm
0 1 2 3 L 5 6 7 8 9 IO
(x101)
actual fault position 1 +IO" +lo" -10" -10"
('/a from end S on Fig 2 ) 2 -10" -10" +lo" +lo"
Fig. 7 Effect of error in line length keyed into the locator for 250 km 3 +IO" -10" +lo" -10"
horizontal line subjected to a-earth fault 4 -10" +lo" -10" +IO"
Percentage error in assumed line length keyed into the locator (5% and -5%)

5.4 Simulated hardware error


Such errors arise due to the combined effect of transducer
errors, locator hardware errors and the calculation
(including filtering) of the voltage and current phasors
which are used in the basic fault locator algorithm. A
.
L

good indication of the likely effect of hardware errors on e


the accuracy of fault location can be obtained by intro- U
al

ducing various combinations of errors in the magnitude 2 I case 1


and phase angle of the voltage and current phasors
entered into the fault location algorithm. With modern -_____-----
F
E -1 0 \
digital processing equipment, it is generally possible to case 2 \
limit overall amplitude and phase errors (including trans-
* -1.5 \

ducer errors) to typically 2% and f loyo,respectively.


Table 1 shows four cases involving a k 2% error in the -201 " " " " "
0 1 2 3 4 5 6 7 8 9 IO
magnitude of the 3-phase voltage and current of the actual f a u l t position
(x101)
sending end S and receiving end R in an a-phase-to-earth ( % from end S on Fig 2 )
fault study on the 250 km horizontal line. Fig. 8 shows Fig. 9 Examples of measurement error introduced by error in voltage
the corresponding variation in measured error with fault and current arguments for a locator applied for 250 km horizontal line
position for each of the four cases given in Table 1. It can subjected to an a-earthfault

IEE PROCEEDINGS, Vol. 137, Pt. C , No. 6 , NOVEMBER 1990 401


6 Conclusions 8 References

The basis of a very accurate method of fault location for 1 ERIKSON, L., SAHA, M.M., and ROCKEFELLER, G.D.: An
accurate fault locator with compensation for apparent reactance in
transmission lines has been presented. The method the fault resistance resulting from remote end infeed, IEEE Trans.,
involves measurement at both ends but does not require PAS-104, 1985, pp. 424435
the use of a continuous data channel. It has been shown 2 SCHEWEITZER, E.O., 111, Evaluation and development of trans-
that, in spite of simplifying the algorithm by using trans- mission line fault locating techniques which use sinusoidal steady-
posed line parameters, a very high degree of accuracy in state information, Computers & Elec. Engng U S A , 1983, IO, (4), pp.
269-218
locating faults is possible for practical untransposed lines. 3 COOK, V.: Fundamental aspects of fault location algorithms used
There is some variation in accuracy according to the line in distance protection, I E E Proc. C , 1986, 133, (6),pp. 359-368
configuration, length and fault type, but under all condi- 4 TAKAGI, T., YAMAKOSHI, Y., YAMAURA, M., KONDOW, R.,
tions a high degree of accuracy is nevertheless possible. and MATSUSHIMA, T.: Development of a new type fault locator
Moreover, the accuracy is not significantly affected by using the one-terminal voltage and current data, IEEE Trans..
1982, PAS-101, pp. 2892-2898
fault resistance and source impedance. 5 KONDOW, R., SUGIYAMA, Y., and YAMADA, M.:
The likely effect of hardware and setting errors has Microprocessor-based fault locator. IEE Conf. Publ. 249, 1985, pp.
been investigated and it has been found that the resulting 188-192
percentage error in fault location is generally less than 6 JEYASURYA, B., and RAHMAN, M.A.: Accurate fault location of
transmission line using microprocessors. IEE Conf. Publ. 302, 1989,
the magnitude of the percentage error involved. In the pp. 13-17
case of an error in the argument of the phasors entered 7 SACHDEV, M.S., and AGARWAL, R.: A technique for estimating
into the algorithm, the percentage error has been found transmission line fault location from digital relay measurements,
to be less than a maximum of approximately 1.5% for a IEEE Trans., 1988, PWRD-3, (I), pp. 121-129
8 LAWRENCE, D.J., and WASER, D.L.: Transmission line fault
10 data error. location using digital fault recorder, IEEE Trans., 1988, PWRD-3,
(2). pp. 496-502
9 JOHNS, A.T., JAMALI, S., and HADEN, S.M.: New accurate
transmission line fault location equipment. IEE Conf. Publ. 302,
1989, pp. 1-5
7 Acknowledgments 10 JOHNS, A.T., and WALKER, E.P.: Co-operative research into the
engmeering and design of a new digital directional comparison
The authors are grateful for the use of facilities provided scheme, IEE Proc. C , 1988, 135, (4). pp. 334-368
by the UK Science and Engineering Research Council 11 WEDEPOHL, L.M.: Application of matrix methods to the solution
and GEC Measurements Limited. The use of facilities at of travelling-wave phenomena in poly-phase systems, Proc. I E E ,
1963, 110, (12), pp. 22W2212
the City University, London, UK and at GEC Measure- 12 JOHNS, A.T., and AGGARWAL, R.K.: Digital simulation of
ments Laboratories, Stafford, UK are also gratefully faulted ehv transmission lines with particular reference to very-high-
acknowledged, speed protection, Proc. IEE, 1976, 123, (4), pp. 353-359

402 IEE P R O C E E D I N G S , Vol. 137, P t . C , N o . 6, N O V E M B E R I990

Você também pode gostar